Heatcraft H-IM-RACC Installation Manual

Installation and Operations
Manual
Bulletin H-IM-RACC August 2007 Part Number 2500018
Replaces H-IM-73A and H-IM-43B
Remote Air-Cooled Condenser
Table of Contents
Inspection ������������������������������������������������������������������������������ 2
Rigging and Moving Units Installation Requirements Unit Location
Space and Location Requirements ��������������������������������������� 3
Walls or Obstructions Units in Pits Multiple Units Decorative Fences Sound Vibration
Vertical and Horizontal Condenser Assembly ��������������������� 4 Typical Piping Arrangements ����������������������������������������������� 5
Installation, Refrigerant Piping
Electrical Wiring ��������������������������������������������������������������������� 6
Start Up ���������������������������������������������������������������������������������� 8
Operation Winter Operation Head Pressure Control Fan Cycling Method Fan Cycling Operation and Installation Variable Speed
Flooded Head Pressure Control Valve ���������������������������������� 9
Operation Piping Maintenance Cleaning Instructions System Warranty ������������������������������������������������������������������ 11 In-Warranty Return Materials Procedure
Condenser Specications�����������������������������������������������12-13 General Fan Layout
Dimensions
Replacement Parts by InterLink™ ��������������������������������������� 14
Installation and Operations Manual
Inspection
Shipment should be checked against the bill of lading to verify that all items listed have been received. All parts should be carefully inspected to determine if any damage was incurred in shipment.
Any shortage and/or claims for damage should be immediately reported to the delivering carrier, followed by ling a claim for shortages and/or damages.
When uncrating, care should be taken to prevent damage. Heavy equipment should be left on its shipping base until it has been moved to the nal location.
Rigging and Moving Units
The exact method of handling and setting the unit depends on available equipment, size of unit, nal location and other variables. It is the judgement of the riggers and movers to determine the specic method of handling each unit.
All units are shipped on heavy skids and enclosed in open crating. Generally, it is advisable to bring the unit as close to its final location as possible before removing crating.
Units are provided with lifting ears near the four corners. Under no circumstances should the coil headers or return bends be used for moving these units.
NOTE FOR ALL MODELS: Spreader bars must be used (contractor-supplied)� Safety slings should be used when making lift�
Figure 1: Suggested Rigging
Figure 2: Leg Mounting
Installation Requirements
NOTE: Installation and maintenance to be performed only by qualied personnel who are familiar with local codes and regulations and are experienced with this type of equipment�
CAUTION: Sharp edges and coil surfaces are a potential injury hazard� Avoid contact with them�
WARNING: This equipment may contain a substance that harms public health and the environment by destroying ozone in the upper atmosphere� Venting of cer tain refrigerants to the atmosphere may be illegal in your location� Refrigerant recovery devices should be used when installing or servicing this product� Consult your local codes for requirements in your location�
WARNING: Refrigerant can be harmful if it is inhaled� Refrigerant must be used and recovered responsibly� Failure to follow this warning may result in personal injury or death�
Unit Location
Units are designed for outdoor application and may be mounted on a roof or concrete slab (ground-level installation). Concrete slabs used for unit mounting should be installed level and be properly supported to prevent settling. A one-piece concrete slab with footings extending below the frost line is recommended.
Roof-mounted units should be installed level on steel channels or an I-beam frame to support the unit above the roof. Use of vibration pads or isolators is recommended. The roof must be strong enough to support the weight of the unit.
2 Part # 2500018
© 2007 Heatcraft Refrigeration Products LLC
Remote Air-Cooled Condenser
The condenser should be located no closer than four feet from any wall or other obstruction to provide sucient clearance for air entrance. Do not attach ductwork to the coil inlet or fan outlet. Care should be taken to avoid air recirculation conditions that can be caused by sight screening, walls, etc. Keep unit fan discharge away from any building air intakes.
Space and Location Requirements
The most important aspect in selecting a location for air-cooled equipment is a supply of ambient air to the condenser and the adequate removal of heated air from the condenser area. If the requirement for adequate air circulation is not adhered to, higher head pressures will result, creating poor operation and possible failure of equipment. Units must not be located in the vicinity of steam, hot air or fume exhausts.
Walls or Obstructions
Multiple Units
For units placed side by side, the minimum distance between units is the width of the largest unit. If units are placed end to end, the minimum distance between units is four feet.
Decorative Fences
Fences must have 50 percent free area, with a one-foot undercut, a minimum clearance equal to the width of the unit and must not exceed the height of the unit. If these requirements are not met, unit must be installed as indicated for units in pits.
The unit should be located so that air may circulate freely and not be recirculated. For proper air ow and access, all sides of the unit should be a minimum of the width of the unit away from any wall or obstruction. It is preferable for this distance be increased whenever possible.
Care should be taken to see that ample room is left for maintenance through access doors and panels. Overhead obstructions are not permitted. When the unit is in an area where it is enclosed by three walls the unit must be installed as indicated for units in a pit.
Units In Pits
The top of the unit should be level with the top of the pit and side distance increased to two times the width of the unit.
Sound and Vibration
Units should be installed away from occupied spaces to redu ce the trans miss ion of soun d and vibratio n to o ccupied spaces. U nits shou ld be mounted o ver corridors, utility areas, rest rooms and other auxiliary areas where high levels of sound are not an important factor. So und and struc tural consultants should be retained for recommendations.
Th e refr igerant piping should be flexible enou gh to prevent the transmission of noise and vibration from the unit into the building. If the refrigerant lines are to be suspended from the structure of the building, isolation hangers should be used to prevent the transmission of vibration.
Where piping passes through a wall, it is advisable to pack berglass and sealing compound around the lines to minimize vibration and retain exibility in the lines. The unit needs to be secured in its nal location. Holes are provided in the base runner for this purpose.
If the top of the unit is not level with the top of pit, discharge cones or stacks must be used to raise discharge air to the top of the pit. This is a minimum requirement.
*W = Total width of the condenser.
Remote Air-Cooled Condenser Installation and Operations Manual, August 2007 3
Vertical Condenser
Vertical airow units should be located no closer than the width of the unit from a wall or other obstruction. If two or more units are to be positioned in the same area, a similar distance should be maintained between adjacent units. Sufficient free area should be left around and below unit to avoid air restriction to coil.
Leg Assembly for Vertical Airow Installation (Models 008-016; 1-3)
Figure 3. Leg assembly (vertical airow, models 008-016; 1-3)
Installation and Operations Manual
Remove fasteners securing condenser to skid.
1.
Remove leg extensions (Figure 4, item 1) by removing four
2. 5/16” x 3-1/2” bolts.
Install as shown in dotted lines with same four bolts.
3.
Install mounting angle (item 2) as shown (dotted lines) with
4. four 1/4 - 20 x 3/4” bolts provided.
Condenser can be hoisted by attaching hooks into 1-1/2”
5. holes in leg assemblies.
Horizontal Condenser
Horizontal airow units should be installed with the coil (inlet air side) facing the prevailing winds. Where strong winds are common, it is recommended that a wind deflector (not supplied) be used to discharge the air vertically from the unit, to prevent capacity loss during varying wind conditions. The wind deector should be installed on the fan side of the unit.
If horizontal airow units are installed with the air inlet facing a wall, a distance of at least 48 inches should be maintained between unit and wall. If it is necessary to have the unit positioned so the air discharge is toward a wall, it should be spaced at a distance no less than three times the coil face height from the wall.
Assemble the unit’s two legs (Figure 3, item 2) using three
1. 1/4 - 20 x 3/4” long bolts per leg. Captive nuts are provided on unit for this assembly.
Fo ur gus sets (Fi gure 3 , item 3) are p rovided for
2. leg support.
Assemble the gusset in each corner with 1/4 - 20 x 3/4” long
3. bolts and 1/4” nuts.
Discard the four mounting angles (Figure 5, item 1).
4.
Leg Assembly for Vertical Airow Installation (Models 024-133; 5-26)
Figure 4. Leg assembly (vertical airow, models 024-133; 5-26)
Leg Assembly for Horizontal Airow Installation (Models 008-016; 1-3)
Figure 5. Leg assembly (horizontal airow, models 008-016 ; 1-3)
Attach four mounting angles (Figure 5, item 1) to the
1. unit, using two 1/4 - 20 x 3/4” long bolts and 1/4” nuts per mounting angle.
Discard the two legs, (Figure 3, item 2) and four gussets
2. (Figure 3, item 3).
4 Part # 2500018
Remote Air-Cooled Condenser
Leg Assembly for Horizontal Airow Installation (Models 024-133; 5-26)
Figure 6. Leg assembly (horizontal airow, models 024-133; 5-26)
Remove bolts securing condenser to skid.
1.
Remove item 1 and attach to rear of bottom leg (item A)
2. to complete mounting base. Item 2 is not required in the horizontal discharge application and may be discarded.
Co ndenser can be hoisted by the 1- 1/2” holes in
3. leg assemblies.
This condition can be overcome in one of two following ways:
The discharge line may be properly sized for the desired
1. pressure drop at full load conditions and an oil separator installed at the bottom of the trap in the discharge line from the compressor.
A double riser discharge line may be used as shown
2. in Figure 8. Line A should be sized to carry the oil at mini mum load con dition s a nd L ine B s hould be sized so that at full load conditions, both lines would have sucient ow velocity to carry the oil to the condenser.
Figure 8
Typical Piping Arrangements
Figure 7 illustrates a typical piping arrangement with a remote condenser located at a higher elevation, common when the condenser is on a roof and the compressor and receiver are on grade level or in a basement equipment room.
Figure 7
In this case, the design of the discharge line is very critical. If properly sized for full load conditions, the gas velocity might be too low at reduced loads to carry oil through the discharge line and condenser coil. Reducing the discharge line size would increase the gas velocity suciently at reduced load conditions; however, when operating at full load, the line would be greatly undersized and create an excessive refrigerant pressure drop.
For more complete information, please refer to the ASHRAE Handbook on Systems.
NOTES:
All oil traps are to be as short in radius as possible�
1�
Common practice is to fabricate the trap using three 90-degree ells�
Pressure relief valves are recommended at the condenser
2�
to protect the coil�
A drain line check valve is recommended for applications
3�
where the condenser may be at a lower temperature than the receiver�
See Tables 1, 2, and 3 for discharge and liquid drain line size recommendations for remote condenser selections.
Installation, Refrigerant Piping
Install piping according to standard accepted refrigeration practice. The following recommendations should be adhered to:
Use only refrigeration-grade copper tubing.
1.
Soft solder joints are not acceptable.
2.
Put dry nitrogen through lines while brazing.
3.
Do not leave dehydrated piping or components open to the
4. atmosphere any longer than is necessary.
Remote Air-Cooled Condenser Installation and Operations Manual, August 2007 5
Loading...
+ 11 hidden pages