Heat Controller Water Source Heat Pump User Manual

WHP - Water Source Heat Pump
Design, Installation &
Operations Manual
Revision 02A
WattMaster WHP
Installation & Operations Manual
Section 1.................................................................................... Design Guide
Section 2...................................................................Installation and Wiring
Section 4....................................................... Start-Up and Troubleshooting
This document is subject to change without notice.
WattMaster Controls, Inc. assumes no responsibility
for errors, or omissions herein.
WHP Installation & Operations Manual - Form WM-WHP-IO-02A
Copyright 2004 WattMaster Controls, Inc.
All rights reserved.
Section 1
Table of Contents
Conventions .....................................................................1
General Information......................................................... 2
Water Source Heat Pump Units.......................................................................................2
Water Source Heat Pump Systems ..................................................................................3
WattMaster WHP Control System...................................................................................4
WHP Controller...........................................................................................................4
Make Up Air Controller...............................................................................................5
WHP Sequence of Operation ........................................... 6
HVAC Mode of Operation...............................................................................................6
Occupied/Unoccupied Mode of Operation......................................................................7
Vent Mode Operation ......................................................................................................7
Off Mode of Operation ....................................................................................................7
HVAC Operation w/ Reversing Relay.............................................................................8
HVAC Operation w/ Heat/Cool Relays...........................................................................9
WHP Loop Controller Sequence of Operations .............10
Summary........................................................................................................................10
Pump Control.............................................................................................................10
Pump VFD Control....................................................................................................11
Compressor Control...................................................................................................11
Heat Rejection Control ..................................................................................................12
Staged Heat Rejection................................................................................................12
Heat Addition Control ...................................................................................................12
Staged Heat Addition.................................................................................................13
Proportional Heat Addition........................................................................................13
Water Temperature Alarming........................................................................................14
Fire Alarm......................................................................................................................14
Notes:............................................................................. 16
Table of Figures
Figure 1-1: Typical Water Source Heat Pump..............................................................3
Figure 1-2: Typical Water Source Heat Pump System.................................................3
Figure 1-3: Typical WattMaster WHP System...........................................................15
Design Guide
WattMaster WHP Section 1
Conventions
This document uses the following definitions throughout as a guide to the user in determining the nature of the information presented:
Note: Additional information which may be helpful.
Tip: Suggestion to make installation, set-up, and troubleshooting easier.
Caution: Items which may cause the equipment not to function correctly but will
not otherwise damage components.
Warning: Errors which can result in damage to equipment and void warranties.
Design Guide 1-1
Section 1 WattMaster WHP
General Information
Water Source Heat Pump Units
A water source heat pump is a self-contained water-cooled packaged heating and cooling unit with a reversible refrigerant cycle. Its components are typically enclosed in a common casing, and include a tube-in-tube heat exchanger, a heating/cooling coil, a compressor, a fan, a reversing valve and controls
.
1-2 Design Guide
WattMaster WHP Section 1
Figure 1-1:
Typical Water Source Heat Pump
During the cooling mode, the tube-in-tube heat exchanger functions as a condenser and the coil as an evaporator. In heating mode, the tube-in-tube heat exchanger functions as an evaporator and the coil as a condenser. A reversing valve is installed in the refrigerant circuit permitting changeover from heating to cooling, and vice versa. The condenser and evaporator tubes are designed to accept hot and cold refrigerant liquid or gas.
Water Source Heat Pump Systems
The water source heat pump system is, by definition, a heat recovery system. It is best applied to buildings that have simultaneous cooling and heating loads. This is the case during winter months when the interior zones of a typical building require cooling while the exterior zones require heating. When a water source heat pump system is used, the heat rejected by the cooling units is used to warm the zones calling for heat. A water heater is generally used for adding heat to the condensing water during peak heating periods, if necessary. The system also utilizes a water cooling tower to reject the heat energy from the condenser water loop during periods of high cooling demand.
Water source heat pump units can be suspended in the ceiling plenum, floor mounted behind walls or placed directly in the occupied space as a console unit. There are also rooftop and unit ventilator type water source heat pumps.
Figure 1-2:
Typical Water Source Heat Pump System
Water source heat pump systems generally cost less to install than central built-up systems. They offer individual zone control with the added flexibility of being able to
Design Guide 1-3
Section 1 WattMaster WHP
accommodate changes in location and sizes as thermal zones or zone occupancy change. This system is often installed in ceiling plenums, which frees up valuable floor space.
Another valuable benefit of water source heat pumps is that they can accommodate simultaneous calls from zones requiring heating or cooling. Depending on the climate, outside air may require preheat or cooling prior to being introduced to the unit. In the example of ceiling mounted water source heat pumps, put outside air ducts near each unit to improve indoor air quality.
Normally, multiple units serve an occupied space. This gives component redundancy to the system so if one unit were to fail, the other units could back it up until the unit was repaired. The packaged design of most unit types allows quick change-out by service personnel so maintenance can typically be performed off site.
As with any HVAC system, there is a negative side as the water source heat pump system often requires higher maintenance costs than conventional air side systems. The system also typically has a shorter replacement life than other systems because of continuous fan and compressor operation during heating and cooling modes. The system can also create room noise since the compressor and fan are commonly located close to the zone occupant. Placing units away from the occupied space and ducting the supply air to the zone can minimize potential noise problems.
WattMaster WHP Control System
The WattMaster WHP system is used to control the water loop and the individual water source heat pumps installed in a typical water source heat pump system. The WHP system is an excellent alternative over programmable thermostats. The WHP control system provides one central location to monitor and program all the water source heat pumps on the system instead of having to program each water source heat pumps thermostat individually. The system has many features typically not found with programmable thermostats such as: central operators interface, heating/cooling failure alarm, auxiliary alarm, and holiday scheduling, to name but a few.
WHP Controller
The Water Source Heat Pump Controller (WHP) is used for controlling individual water source heat pump units. The WHP Controller can operate stand-alone or it can be used with the Water Source Heat Pump Loop Controller and in this configuration shares common data, such as outside air temperature, proof of flow etc., over a network. A System Manager is connected to the WHP Controller to provide a central operators interface to all WHP Controllers on the network. WHP Controllers are designed with Room Temperature, Room Setpoint Adjust, Discharge Air Temperature, Leaving Water Temp or Dirty Filter Alarm and Auxiliary Lockout inputs. Relay outputs provided are; Fan (Continuous or Cycling), Reversing Valve-ON/OFF, Compressor-ON/OFF, Heat
1-4 Design Guide
WattMaster WHP Section 1
Pump Reset and Aux. Heating or Cooling. An internal seven day schedule and holiday schedule functions are also built into each WHP Controller.
With the WHP system the sometimes complex control requirements of a large water source heat pump system can be handled with an off the shelf controls system that has most of the features of a full blown building automation system but at a much lower cost. Included with the WHP system is a communications interface module, which allows you to connect a computer to the system onsite and a modem connection for remote monitoring.
Prism, a Windows based software package is available at no additional charge. Some of Prism’s features include graphics, trend logging, and remote alarm call out capabilities. WHP Loop Controller The Water Source Heat pump Loop Controller can be supplied with the system to control the water loop and its various pieces of equipment. The Loop Controller can operate stand-alone or used with the Water Source Heat Pump Controller (WHP) and in this configuration communicates common data, such as outside air temperature, proof of flow etc., over a network. A System Manager is connected to the Loop Controller to provide a central operator’s interface to the Loop Controller’s setpoints and operating configurations. The Loop Controller is designed with inputs for Supply and Return W ater Temperature, Outdoor Air Temperature, Loop Water Pressure Switch or 0-50 PSI Loop Pressure Sensor (4-20ma), Manual Reset Contact, Phase Loss Contact, Request to Run Relay, and Fire/Smoke Relay. Analog outputs (0-10VDC) are supplied for Pump VFD and Proportional Heat. Binary outputs are provided for Compressor Enable, Main Pump Relay, Standby Pump Relay, Alarm Contacts and (8) Relays that can be configured for Heat Rejection or Heat Addition.
Make Up Air Controller
A Make Up Air Controller, for treating 100% outdoor air, is available for use with the Water Source Heat Pump system. Please consult factory for more information on this product.
Design Guide 1-5
Section 1 WattMaster WHP
WHP Sequence of Operation
HVAC Mode of Operation
There are four possible modes of operation. These are Cooling Mode, Heating Mode, Vent Mode, and the Off Mode. The HVAC mode of operation is calculated the same way in both occupied and unoccupied modes of operation.
Off Mode The schedule is off and no overrides are active. There is no heating or
cooling demand in the space. Under these conditions, all outputs will be off and the analog output will be set to 0.0 vdc.
Vent Mode No heating or cooling demand exists during the occupied mode of
operation. The fan will be on if the WHP is programmed for Constant Fan operation. The compressor demand request will not be sent to the Loop Controller. If no WHP units are sending a request, the Loop Controller will discontinue operation after 15 minutes.
Cool Mode A cooling demand is generated when the space temperature rises half the
amount of the Deadband Setpoint above the currently active Cooling Setpoint. The space is considered satisfied when it drops that amount below the Cooling Setpoint.
Heat Mode A heating demand is generated when the space temperature drops half the
amount of the Deadband Setpoint below the currently active Heating Setpoint. The space is considered satisfied when it rises that amount above the Heating Setpoint.
1-6 Design Guide
WattMaster WHP Section 1
Occupied/Unoccupied Mode of Operation
Since the WHP contains its own built in Real Time Clock, it can operate from its own internal scheduling system. This schedule supports two Start & Stop events per day and up to 14 Holiday periods. The Holidays all use the same special Holiday Start/Stop times programmed by the user.
If the current operating mode is unoccupied, the WHP can accept a push-button override back to the occupied mode. Push-button overrides are not recognized if the current mode is already occupied. The push-button override duration is user programmed. If the user wants to extend the current override without reprogramming the Duration, they can re­initialize the existing programmed period by pressing the override button anytime during the current override. If the current override had been active for 1 hour and 45 minutes and the user presses the push-button again, the override will reset for another 2 hour period (if they programmed a 2 hour period), bringing the total override time to 3 hours and 45 minutes. If the user wants to cancel an override before it can time-out, simply hold the push-button for a period of time between 3 and 10 seconds.
The WHP calculates its current heating and cooling setpoints based on the current mode of operation. If the command is for unoccupied mode, the WHP adds the unoccupied setbacks to the occupied heating and cooling setpoints.
Vent Mode Operation
During occupied hours when there is no heating or cooling demand, the WHP reverts to a Vent Mode of operation. The fan is running and the heating and cooling outputs are held off.
See the section titled HVAC Mode of Operation for a graphical description of how the Vent Mode is calculated.
Off Mode of Operation
After the schedule goes unoccupied and both heating and cooling demands go away, the fan stops running, all relay outputs are turned off. No outputs are allowed to activate in the Off Mode until a heating or cooling demand occurs. During occupied hours this would be the Vent Mode.
Design Guide 1-7
Section 1 WattMaster WHP
HVAC Operation w/ Reversing Relay
If the user has configured the WHP to control a Reversing Valve and a Compressor, the following sequence of operation occurs during a heating or cooling demand.
Note: If you configure the WHP to look for a proof of flow Enable signal from the
Loop Controller then the following sequence assumes a request was made by the WHP during a demand condition and that the Loop Controller gave permission for the WHP to start its compressor. Otherwise, the WHP will ignore the Enable signal and operate anytime there is a heating or cooling demand.
a. If the last mode was the opposite of the current demand mode, make sure
the Changeover Delay has been satisfied.
b. If the unit is configured to control an Isolation Valve, the valve relay is
activated ( Relay #5 ). The Minimum Off Timer is reset to ZERO and must be satisfied before any further operations are allowed.
c. If the current mode requires the Reversing Valve to be activated, its relay
contact is closed and a 10 second delay is started.
d. Ten seconds after the Reversing Valve is activated, the Compressor relay
is activated.
e. If the Space Temperature continues to exceed the affected setpoint by the
full amount of Deadband and you have configured for 2 stages in the current mode of operation, relay #5 will activate for the second stage of heating and/or cooling. A second stage of either implies that no Isolation Valve exists!
f. Once the Space Temperature has crossed back over the affected setpoint,
stage 2 will be turned off if the unit has a stage 2.
g. As the Space Temperature continues to cross back over the affected
setpoint by half the Deadband value, the compressor will then be allowed to turn off if the Minimum Run Time has been satisfied.
1-8 Design Guide
WattMaster WHP Section 1
HVAC Operation w/ Heat/Cool Relays
If the user has configured the WHP to control Individual Heating and Cooling relays the following sequence of operation occurs during a heating or cooling demand.
NOTE: If you configure the WHP to look for a proof of flow Enable signal from the
Loop Controller then the following sequence assumes a request was made by the WHP during a demand condition and that the Loop Controller gave permission for the WHP to operate its heating or cooling. Otherwise, the WHP will ignore the Enable signal and operate anytime there is a heating or cooling demand.
Once a heating or cooling demand exists, the following conditions must be met before any relays can be activated:
a. Make sure any stages of the opposite mode are staged off.
b. Verify the system has been configured for at least one stage of heating or
cooling.
c. Make sure the Minimum Cycle Time has been satisfied.
d. If the last mode was the opposite demand mode, make sure the
Changeover Delay has been satisfied.
e. Check the current Minimum Off Timer to make sure this stage has been
off long enough since the last time it was cycled on and back off.
f. If there is more than 1 stage, check the Minimum Run Time from the
previous stage to be sure it has elapsed before activating the second stage.
g. Make sure the Space Temperature Demand is the full amount of Deadband
from the setpoint before activating the second stage.
h. Once the compressor or stage 2 has been turned off, a Minimum Off Time
must be satisfied before it can stage on again. A Minimum Cycle time can also be utilized to limit the number of times per hour that the compressor can be activated. If you don’t need this limitation, set the Minimum Cycle Time to be shorter than the Minimum Run Time setpoint.
i. If the Reversing Valve was configured to cycle with the compressor, it will
now turn off also. It can be configured to remain active until the opposite mode of operation is called for to reduce wear on the valve.
Design Guide 1-9
Section 1 WattMaster WHP
WHP Loop Controller Sequence of Operations
Summary
The Water Source Heat Pump Loop Controller waits for a Request to Run signal from a Heat Pump or from a Binary Contact Closure. Once the request is received the Loop Controller activates a Pump to initiate water flow to the Heat Pumps. Once the pump is activated and proof of flow has been determined, a Global is broadcast to all Heat Pumps to enable them to go ahead and run their compressors. The main goal of the Loop Controller is to provide water flow and to maintain the loop water temperature by monitoring either the Loop Inlet or Loop Outlet temperature. If a higher temperature is required, Heat Addition is enabled. If the temperature needs to be lowered, Heat Rejection is enabled.
Once the Loop Controller has been activated by a request, it will run for a minimum of 15 minutes to prevent cycling on and off due to borderline requests from the Heat Pumps.
If a Fire Alarm is detected, the Loop Controller generates a Global broadcast to all Heat Pumps to turn off.
If the High Pressure option is configured, the Loop Controller can generate a Global broadcast to force the Heat Pumps to open their Isolation Valves to reduce loop pressure if the high limit has been exceeded.
Pump Control
If WattMaster Water Source Heat Pump Controllers are used in conjunction with the Loop Controller, a Global Binary signal from the attached Heat Pumps sends a Request to run or Enable to Run command to the Loop Controller. If the Loop Controller is used in a stand alone configuration, a contact closure on the AIN 2 of the Analog Expansion board gives the controller a request to run. When a request to run is received, the Loop Controller activates a pump to initiate water flow to the heat pumps. The pumps can either be constant flow or controlled by a VFD. If the request goes away for at least one minute, the request to run command is removed. If the loop controller has been running a minimum of 15 minutes then it can be turned off, since there is no longer a request to run. If the proof of flow is lost while the pumps are running, the pump is shut off immediately if the changeover to the Standby Pump had already been made.
The pumps are Lead/Lag controlled based on a user definable number of hours. If one pump exceeds the other pumps run time by this amount, the lead is changed until that
1-10 Design Guide
WattMaster WHP Section 1
pump exceeds the first pumps run time by the same amount. This keeps both pumps with roughly the same number of hours on each pump. Changeover occurs at the time the run time setpoint is exceeded. The running pump is shut off at the same time the standby pump is energized, this prevents any down time or alarms. The unit can be configured to control either the Loop Inlet temperature or the loop outlet temperature.
A user adjustable low outdoor air temperature setting of XX degrees will allow the unit to run the pumps continuously for protection against freezing.
If the pump is constant volume, and the pump has been started, it has 3 seconds to generate flow or the standby pump is activated. If the pump is controlled by a VFD, once it starts, it has 60 seconds to generate flow and if it doesn’t the standby pump is activated. If the standby pump fails, an alarm is generated and the Loop controller deactivates any active heat rejection or addition stages. At the same time an alarm is generated, we energize relay #5 on the Loop Controller board so that it may used to turn on a local alarm signal.
Loop flow can be determined by a binary contact closure on input #3 or a 0 to 50 PSI pressure sensor on input #3. If a pressure sensor is used, the user can program the pressure setpoint that needs to be met for proof of flow.
Pump VFD Control
An optional Pump VFD signal can be modulated if the system is configured for proportional control and a pressure sensor is attached to analog input #3. At a user defined rate, the VFD signal is ramped up when the pressure is below a user defined setpoint by a user defined deadband. The signal ramps down when the pressure exceeds the setpoint by the deadband value. If the pressure ever exceeds the high pressure setpoint, an emergency override activates and begins cutting the VFD signal in half each time the control loop is polled by the software. This protects against run away over-pressurization.
The pump relay outputs are still activated and Lead/Lagged as described above and the pump relay remains on until the Request signal is removed, provided it has been operating for at least 15 minutes.
Compressor Control
Anytime a pump is running and proof of flow has been established, the compressor output is activated.
Design Guide 1-11
Section 1 WattMaster WHP
Heat Rejection Control
If the compressor is not running, no heat rejection can be active. If any heat rejection is still active when the compressor is turned off, the heat rejection will be immediately removed, without regard to any minimum run or off times.
Heat rejection cannot be active at the same time as heat addition, so any heat addition is removed or staged off before the heat rejection can be started.
A maximum of 8 stages of heat rejection can be controlled.
Staged Heat Rejection
Heat Rejection is staged up based on a different deadband level for each stage. Basically, if the user programmed a 2° deadband, then the first stage could activate at the setpoint, stage 2 would activate 2° above the setpoint, stage 3 would activate 4° above the setpoint, etc...
Staging down is calculated in the same manner, except the water temperature would need to drop below the setpoint by the deadband amount. If stage 3 was activated at 4° above setpoint, it would de-activate when the temperature fell to within 2° of setpoint, stage 2 would de-activate at setpoint and stage 1 would de-activate 2° below setpoint.
A user defined staging up and down interval must be met before any heat rejection stages can be added or removed. If the selected Water Temperature is above the current staging level and the timer has been satisfied, an additional stage can be added, up to the maximum available 8 stages. If the selected Water Temperature is below the staging down level and the timer has been satisfied, a stage can be removed.
Heat Addition Control
If the compressor is not running, no heat addition can be active. If any heat addition is still active when the compressor is turned off, the heat addition will be immediately removed, without regard to any minimum run or off times.
Heat addition cannot be active at the same time as heat rejection, so any heat rejection is removed or staged off before the heat addition can be started.
A maximum of 4 stages of heat addition can be controlled or proportional heating can be configured, and an analog output signal will be modulated to control the heat.
1-12 Design Guide
WattMaster WHP Section 1
Staged Heat Addition
Heat Addition is staged up based on a different deadband level for each stage. Basically, if the user programmed a 2° deadband, then the first stage could activate at the setpoint, stage 2 would activate 2° below the setpoint, stage 3 would activate 4° below the setpoint, etc...
Staging down is calculated in the same manner, except the water temperature would need to increase above the setpoint by the deadband amount. If stage 3 was activated at 4° below setpoint, it would de-activate when the temperature rises t o within 2° of setpoint, stage 2 would de-activate at setpoint and stage 1 would de-activate 2° above setpoint.
A user defined staging up and down interval must be met before any heat addition stages can be added or removed. If the selected Water Temperature is below the current st aging level and the timer has been satisfied, an additional stage can be added, up to the maximum available 8 stages. If the selected Water Temperature is above the staging down level and the timer has been satisfied, a stage can be removed.
Proportional Heat Addition
If the Water Temperature is below the addition setpoint, a Boiler Enable relay is activated. If the Water Temperature rises 1° above the setpoint the Boiler Enable relay is de-activated.
At a user defined rate, the analog output signal is proportionally controlled from 0.0 VDC at 1° above setpoint to the full 10.0 VDC signal as the water temperature drops below the setpoint by the user defined deadband amount. If a 5° deadband was entered, the maximum voltage would be reached at 4° below the setpoint and the minimum volt age would be set at 1° above the setpoint. Since this is strictly proportional control, at 1.5° below setpoint the controller would set 5.0 VDC since that would be half the deadband amount.
Design Guide 1-13
Section 1 WattMaster WHP
Water Temperature Alarming
The controlling water temperature is monitored to prevent it from exceeding both a user defined High and Low Alarm Limit. If either limit is exceeded for a user defined length of time, an alarm is generated and the compressor output is de-activated. If the high limit is exceeded, the heat addition outputs are de-activated and if the low limit is exceeded, the heat rejection outputs are de-activated. The alarming and shutdown only pertains to the controlling water temperature. This does not affect the pump operation.
If a external manual alarm reset button is connected between ground and input #5, All outputs are turned off and ALL timers are reset. This forces the loop controller to stage off. This reset WILL shut down the pumps and force them to restart!
Fire Alarm
If the Fire Alarm is activated on input #1 of the Analog Input Expansion Board (Contact OPENS for Alarm!) then ALL outputs and timers are reset and held off for the duration of the Fire Alarm signal.
If the Fire Alarm is not required, input #1 of the Analog Input Expansion Board must have a shorting wire to ground to allow the equipment to operate.
1-14 Design Guide
WattMaster WHP Section 1
COMPUTER (OPTIONAL)
RS-485
Comm Loop
32K
8K
COMM
RELAY OUTPUT
T
Room Sensor
with Optional
Override & Adj.
COM 1-3
SHLD
OUT
R
1 OUT
RAM EPROM
485
LD4
2
COMM
OUT 3
REC.
OUT
OUT 4 OUT 5 COM
CPU
4-5
4-5
COMM
12V
TEST
ADDRESS ADD
AIN 1 AIN 2 AIN 3
EWDOG
AIN 4 AIN 5 GND
GND
0-5 VDC
AOUT
PWR
PRESSURE
GND
SENSOR
YS101564
0-1 VDC
24VAC
24 VAC
110/24 VAC
Power Pak
Modem
(Optional)
M
R
T R
S D
R
D
O
H
C
D
A A
H
S
CommLink II
Multiple Loop
Interface
C
COMM
O
M
M
L
LINK
IN
K
I
II
I
L O
C
O
O
M
P
M
O D
P
E M
WCLI
AT
T
M
A
S
T
E
R
O
N
T
R
O
S
,
N
C
MiniLink
Loop # 1
K
N
I
L
I
N
I
M
MINILINK
N
NETWORK
1 2
E
4
T
T
8
W
16
SH
O
32
R
R
K
24VAC24VAC
GND
L
LOOP
T
O O
SH
P
R
24VAC
MiniLink
Loop # 2
K
N
I
L
I
N
I
M
MINILINK
N
NETWORK
1 2
E
4
T
T
8
W
16
SH
O
32
R
R
K
24VAC24VAC
GND
L
LOOP
T
O O
SH
P
R
24VAC
Typical Network & Local Loop Wiring 2 Conductor Twisted Pair with Shield (Beldon #82760 or Equivalent)
MiniLink
Loop # 3
K
N
I
L
I
N
I
M
MINILINK
N
NETWORK
1 2
E
4
T
T
8
W
16
SH
O
32
R
R
K
24VAC
GND
L
LOOP
T
O O
SH
P
R
24VAC
NOTE: * Only One Outside Air Sensor
is Required per WHP System
MiniLink
Loop # 4
K
N
I
L
I
N
I
M
MINILINK
N
NETWORK
1 2
E
4
T
T
8
W
16
SH
O
32
R
R
K
24VAC
GND
GND
L
LOOP
T
O O
SH
P
R
Loop # 4
Notes:
1.) 24 VAC Must Be Connected So That All Ground Wires Remain Common.
2.) All Wiring To Be In Accordance With Local And National Electrical Codes and Specifications.
24VAC
110/24 VAC
Power Pak
Network Loop
RS-485
19200 Baud
Local Loop
RS-485
9600 Baud
Local Loop
RS-485
9600 Baud
Local Loop
RS-485
9600 Baud
*OutsideAir
Sensor
Supply
Air
or Leaving Water Temp
F
Sensor
Typical WHP Controller Wiring
#1
32K
8K
COMM
RELAY OUTPUT
T
COM 1-3
SHLD
OUT
R
1
OUT
RAM EPROM
485
LD4
2
COMM
OUT
3
REC.
OUT
OUT
4
OUT
5
COM
CPU
4-5
4-5
COMM
12V
TEST
ADDRESS ADD
AIN 1 AIN 2 AIN 3
EWDOG
AIN 4 AIN 5 GND
GND
0-5 VDC
AOUT
PWR
PRESSURE
GND
SENSOR
YS101564
0-1 VDC
24VAC
System Manager
#1
32K 8K
COMM
RELAY OUTPUT
T
COM 1-3
SHLD
OUT
R
1
OCCUPIED
ALARMS
03/31/04 03:38PM WED
NO
OUT
RAM EPROM
485
LD4
2
COMM
OUT 3
REC.
OUT
OUT 4 OUT 5 COM
CPU
4-5
4-5
COMM
12V
TEST
ADDRESS ADD
AIN
1
AIN
2
AIN
3
EWDOG
AIN
4
AIN
5 GND
GND
0-5
VDC
AOUT
PWR
PRESSURE
GND
SENSOR
YS101564
0-1
VDC
24VAC
24VAC
#1
32K 8K
COMM
RELAY OUTPUT
T
COM 1-3
SHLD
OUT
R
1 OUT
RAM EPROM
485
LD4
2
COMM
OUT 3
REC.
OUT
OUT 4 OUT 5
COM
CPU
4-5
4-5
COMM
12V
TEST
ADDRESS ADD
AIN
1
AIN
2
AIN
3
EWDOG
AIN
4
AIN
5 GND
GND
0-5
VDC
AOUT
PWR
PRESSURE
GND
SENSOR
YS101564
0-1 VDC
24VAC
WHP Loop Controller
C21
1
U3
D
3
CX1
X
CX2
U2
RN1
C
CX4
1
U1
U4
1
2
G
Y
4
L
N
V
TB1 COMM
T
SHLD
R
CX5
LD6
COMM
LD7 PWR
LD8 LED1
LD9 LED2
R1
TESTPOINT
U7
RV1 VREFADJ
INPUTS
+VDC
AIN1
AIN2 AIN3
AIN4
AIN5
GND GND AOUT1
AOUT2 AIN7 GND
PJ1
TB3
PRESSURE SENSOR
EXPANSION
V1
R
A
D
C
2 D
V2
V3
2 Y L R
COM1-3
3 D
U5
PAL
R1
RS-485
1
EPROM
RAM
R2
COMM
3 Y
TUC-5RPLUS
1
L
HH
R
R3
(1MEG)
4
YS101816REV.2
2
U6
D
3
N
YS101790
4RLYIOBD.
R4
N
R
R
C1
R5
P1
4
COM4-5
Y L R
+VREF
TB2
CX6
5
5.11V
D
2
V4
C S IP
EWDOG
1
IL
X
V5
H P
5
R28
Y L
3
R
C
1
ADD
ADDRESS
U8
1
4
4RLYIOBD.
N
2
R
RN5
4
NE5090NPB3192
8
PU1
X
0PS
8
C
U9
D6
16
PU2
32
D7
TOKEN
PU3
NETWORK
D8
SW1 PU4
D9 PU5
D11
C
C
C10
PU7
-1
-5 D
D
0
0
V
V
JP1
D14
C12
U13
CX13
D15
C17
U15
C20
CX15
R26
3
2
J
J
P
P
AIN1
CX10
C7
AIN2
R6
AIN3
0
7
1
U10
R
D
AIN4
0
3
1
1
L1
C9
R
D
GND
CX12
1 1
1
D12
C
1
1
X2
AOUT1
9936
1
R13
R
U
MC34064A
SC1
C13
R15
U12
CX14
C14
C16
R19
U14
TB4
C15
D19
GND
R22
7 2
6
R24
R
R
1
E
D
8
7
6
R25
1
1
W
V
9
8
D
D
O
1
1
P
C
C
7824CT
24VAC
M
VR1
VR2
T'STAT
3.) The Local Loop With The Loop Controller Installed Can Only Have Up To 29 WHP Controllers Attached As The WHP Loop Controller Occupies Address #30.
4.) Systems may consist of up to 20 Local Loops (600 WHP Controllers). Consult factory for systems that exceed these quantities.
4ANALOGIN MOD I/O BD.
YS101784
COMM
T
SHLD
R
LD4
YS101790
REC.
12V AIN
1
AIN
2
AIN
3
AIN
4
AIN
5 GND
GND
AOUT
PRESSURE SENSOR
#1
RAM EPROM 485 COMM
ADDRESS ADD
EWDOG
YS101564
32K 8K
COM 1-3
COM
CPU
4-5
4-5
COMM
TEST
0-5
VDC
0-1
VDC
See Note #3
RELAY OUTPUT
OUT 1 OUT 2 OUT 3 OUT
OUT 4 OUT 5
PWR
GND
24VAC
Dirty Filter Alarm
Loop #1
WHP
Controllers
Loop #2
WHP
Controllers
Loop #3
WHP
Controllers
Loop #4
WHP
Controllers
Local Loop
RS-485
9600 Baud
COMM
COMM
LD4
REC.
PRESSURE SENSOR
COMM
T
SHLD
R
LD4
REC.
12V AIN
AIN
AIN
AIN
AIN
GND
GND
AOUT
PRESSURE SENSOR
T
SHLD
R
12V AIN 1 AIN 2 AIN 3 AIN 4 AIN 5 GND
GND
AOUT
#30
T
SHLD
R
LD4
REC.
12V AIN 1 AIN 2 AIN 3 AIN 4 AIN 5 GND
GND
AOUT
PRESSURE SENSOR
#30
1
2
3
4
5
YS101564
COMM
T
SHLD
R
LD4
REC.
PRESSURE SENSOR
YS101564
485 COMM
YS101564
RAM EPROM 485 COMM
ADDRESS ADD
EWDOG
#30
12V AIN 1 AIN 2 AIN 3 AIN 4 AIN 5 GND
GND
AOUT
YS101564
#29
RAM EPROM 485 COMM
ADDRESS ADD
EWDOG
32K 8K
RELAY OUTPUT COM 1-3 OUT 1 OUT
RAM EPROM
2 OUT 3 OUT
OUT 4 OUT 5 COM
CPU
4-5
4-5
COMM
TEST
ADDRESS ADD
EWDOG
0-5 VDC
PWR
GND
0-1 VDC
24VAC
32K 8K
RELAY OUTPUT COM 1-3 OUT 1 OUT 2 OUT 3 OUT
OUT 4 OUT 5 COM
CPU
4-5
4-5
COMM
TEST
0-5
VDC
PWR
GND
0-1
VDC
24VAC
32K
8K
RELAY
OUTPUT COM 1-3 OUT
1 OUT
RAM EPROM
485
2
COMM
OUT
3 OUT
OUT
4 OUT
5 COM
CPU
4-5
4-5
COMM
TEST
ADDRESS ADD
EWDOG
0-5
VDC
PWR
GND
0-1
VDC
24VAC
32K 8K
RELAY
OUTPUT COM 1-3 OUT 1 OUT 2 OUT
3 OUT
OUT 4 OUT
5 COM
CPU
4-5
4-5
COMM
TEST
0-5 VDC
PWR
GND
0-1 VDC
24VAC
Figure 1-3:
Typical WattMaster WHP System
Design Guide 1-15
Section 1 WattMaster WHP
Notes:
1-16 Design Guide
Section 2
Table of Contents
Tips Before Beginning Installation.................................. 1
Communications Loops ...................................................3
Communications Loop Wiring Overview....................................................4
WHP Loop Controller .......................................................6
WHP Loop Controller Addressing ....................................9
Supply & Return Water Temperature Sensors.............. 10
Outside Air Temperature Sensor................................... 12
CommLink II Interface................................................... 13
WHP Controller ..............................................................14
WHP Controller Addressing ...........................................17
MiniLink Addressing ...................................................... 18
Room Sensors ................................................................ 19
Supply Air Temperature Sensor .................................... 21
Leaving Water Temperature Sensors............................ 22
Installation and Wiring
Section 2
Table of Figures
Figure 2-1: System Overview........................................................................................2
Figure 2-2: Communication Loop Wiring, Daisy-Chain Configuration .......................4
Figure 2-3: WHP Loop Controller.................................................................................6
Figure 2-4: WHP Loop Controller Wiring ....................................................................7
Figure 2-5: WHP Loop Controller Address Switch Setting..........................................9
Figure 2-6: Duct Sensor with Thermowell...................................................................10
Figure 2-7: Strap-On Water Temperature Sensor ........................................................11
Figure 2-8: Outside Air Temperature Sensor...............................................................12
Figure 2-9: CommLink Interface Wiring.....................................................................14
Figure 2-10: WHP Controller .....................................................................................14
Figure 2-11: WHP Controller Wiring.........................................................................15
Figure 2-12: WHP Controller Address Switch Setting...............................................17
Figure 2-13: MiniLink Address Switch Setting.........................................................18
Figure 2-14: Room Sensor Wiring..............................................................................19
Figure 2-15: Room Sensor..........................................................................................20
Figure 2-16: Supply Air Temperature Sensor..............................................................21
Figure 2-17: Water Temperature Sensor .....................................................................22
Figure 2-18: Water Temperature Sensor .....................................................................22
Installation and Wiring
WattMaster WHP Section 2
Tips Before Beginning Installation
Take a few moments to review the following before beginning installation of the WattMaster WHP System.
Familiarize yourself with all system components and review all documentation. Pay
special attention to “Cautions” and “Warnings” since these may keep you from experiencing unnecessary problems.
Before installing controllers, be sure to tag it with its appropriate location. It is also
best to set the controller address switches before mounting. Use the WHP Address Worksheet to list all WHP unit locations. This will assist you greatly when setting up the system.
Be sure and install all wiring according to local, state, and national electric codes.
Pay close attention to communication wiring since the most common mistakes are
made in this area. Polarity is the most important rule. Make notes on your wiring diagrams as to which color wire you will be using on each terminal.
When in doubt - ask! Contact your local WattMaster distributor if you have any
questions. The only dumb questions are the ones you don’t ask.
Remember - each electronic device contains only one puff of smoke. If you release it,
you have voided the warranty! So please be careful and pay attention.
Installation and Wiring 2-1
Section 2 WattMaster WHP
COMPUTER (OPTIONAL)
RS-485
Comm Loop
32K
8K
COMM
RELAY OUTPUT
T
Room Sensor
with Optional
Override & Adj.
COM 1-3
SHLD
OUT
R
1 OUT
RAM EPROM
485
LD4
2
COMM
OUT 3
REC.
OUT
OUT 4 OUT 5 COM
CPU
4-5
4-5
COMM
12V
TEST
ADDRESS ADD
AIN 1 AIN 2 AIN 3
EWDOG
AIN 4 AIN 5 GND
GND
0-5 VDC
AOUT
PWR
PRESSURE
GND
SENSOR
YS101564
0-1 VDC
24VAC
24 VAC
110/24 VAC
Power Pak
Modem
(Optional)
M
R
T R
S D
R
D
O
H
C
D
A A
H
S
CommLink II
Multiple Loop
Interface
C
COMM
O
M
M
L
LINK
IN
K
I
II
I
L O
C
O
O
M
P
M
O D
P
E M
WCLI
AT
T
M
A
S
TE
R
O
N T
R O
S, N
C
MiniLink
Loop # 1
K
N
I
L
I
N
I
M
MINILINK
N
NETWORK
1 2
E
4
T
T
8
W
16
SH
O
32
R
R
K
24VAC
GND
L
LOOP
T
O O
SH
P
R
24VAC
MiniLink
Loop # 2
K
N
I
L
I
N
I
M
MINILINK
N
NETWORK
1 2
E
4
T
T
8
W
16
SH
O
32
R
R
K
24VAC
GND
L
LOOP
T
O O
SH
P
R
24VAC
Typical Network & Local Loop Wiring 2 Conductor Twisted Pair with Shield (Beldon #82760 or Equivalent)
MiniLink
Loop # 3
K
N
I
L
I
N
I
M
MINILINK
N
NETWORK
1 2
E
4
T
T
8
W
16
SH
O
32
R
R
K
24VAC
GND
L
LOOP
T
O O
SH
P
R
24VAC
NOTE: * Only One Outside Air Sensor
is Required per WHP System
MiniLink
Loop # 4
K
N
I
L
I
N
I
M
MINILINK
N
NETWORK
1 2
E
4
T
T
8
W
16
SH
O
32
R
R
K
24VAC24VAC
GND
L
LOOP
T
O O
SH
P
R
Loop # 4
Notes:
1.) 24 VAC Must Be Connected So That All Ground Wires Remain Common.
2.) All Wiring To Be In Accordance With Local And National Electrical Codes and Specifications.
24VAC
110/24 VAC
Power Pak
Network Loop
RS-485
19200 Baud
Local Loop
RS-485
9600 Baud
Local Loop
RS-485
9600 Baud
Local Loop
RS-485
9600 Baud
*OutsideAir
Sensor
Supply
Air
or Leaving Water Temp
F
Sensor
Typical WHP Controller Wiring
#1
32K
8K
COMM
RELAY OUTPUT
T
COM 1-3
SHLD
OUT
R
1
OUT
RAM EPROM
485
LD4
2
COMM
OUT
3
REC.
OUT
OUT
4
OUT
5
COM
CPU
4-5
4-5
COMM
12V
TEST
ADDRESS ADD
AIN 1 AIN 2 AIN 3
EWDOG
AIN 4 AIN 5 GND
GND
0-5 VDC
AOUT
PWR
PRESSURE
GND
SENSOR
YS101564
0-1 VDC
24VAC
System Manager
D
E
W
M P 8
3
:
3
D
0
E
I
4
S
P
0
M
U
/
R
C
1
A
C
3
L
O
/
A
3
0
O N
24VAC
#1
32K 8K
COMM
RELAY OUTPUT
T
COM 1-3
SHLD
OUT
R
1 OUT
RAM EPROM
485
LD4
2
COMM
OUT 3
REC.
OUT
OUT 4 OUT 5 COM
CPU
4-5
4-5
COMM
12V
TEST
ADDRESS ADD
AIN
1
AIN
2
AIN
3
EWDOG
AIN
4
AIN
5 GND
GND
0-5
VDC
AOUT
PWR
PRESSURE
GND
SENSOR
YS101564
0-1
VDC
24VAC
#1
32K 8K
COMM
RELAY OUTPUT
T
COM 1-3
SHLD
OUT
R
1 OUT
RAM EPROM
485
LD4
2
COMM
OUT 3
REC.
OUT
OUT 4 OUT 5
COM
CPU
4-5
4-5
COMM
12V
TEST
ADDRESS ADD
AIN 1 AIN 2 AIN 3
EWDOG
AIN 4 AIN 5 GND
GND
0-5
VDC
AOUT
PWR
PRESSURE
GND
SENSOR
YS101564
0-1 VDC
24VAC
WHP Loop Controller
C21
1
U3
D
3
CX1
X
CX2 U2
RN1
C
CX4
1
U1
U4
1
2
G
Y
4
L
N
V
TB1 COMM
T
SHLD
R
CX5
LD6
COMM
LD7 PWR
LD8 LED1
LD9 LED2
R1
U7
RV1 VREFADJ
INPUTS
+VDC
AIN1
AIN2 AIN3
AIN4
AIN5
GND GND AOUT1
AOUT2 AIN7 GND
PJ1
TB3
PRESSURE SENSOR
V1
R
A
D
C
2 D
V2
V3
2 Y L R
COM1-3
3 D
U5
PAL
R1
RS-485
1
EPROM
RAM
R2
COMM
3 Y
TUC-5RPLUS
1
L
HH
R
R3
(1MEG)
4
YS101816REV.2
2
U6
D
3
N
YS101790
4RLYIOBD.
R4
N
R
R
C1
R5
P1
4
COM4-5
Y L R
+VREF
TB2
CX6
5
5.11V
D
TESTPOINT
2
V4
C S IP
EWDOG
1
IL
X
V5
H P
5
R28
Y L
3
R
C
1
ADD
ADDRESS
U8
1
4
4RLYIOBD.
N
2
R
RN5
4
NE5090NPB3192
8
PU1
X
0PS
8
C
U9
D6
16
PU2
32
D7
TOKEN
PU3
NETWORK
D8
SW1
PU4
D9 PU5
D11
C
C
C10
PU7
-1
-5 D
D
0
0
V
V
JP1
D14
C12
U13
CX13
D15
C17
U15
C20
CX15
R26
3
2
J
J
P
P
EXPANSION
AIN1
CX10
C7
AIN2
R6
AIN3
0
7
1
U10
R
D
AIN4
0
3
1
1
L1
C9
R
D
GND
CX12
1 1
1
D12
C
1
1
X2
AOUT1
9936
1
R13
R
U
MC34064A
SC1
C13
R15
U12
CX14
C14
C16
R19
U14
TB4
C15
D19
GND
R22
7 2
6
R24
R
R
1
E
D
8
7
6
R25
1
1
W
V
9
8
D
D
O
1
1
P
C
C
7824CT
24VAC
M
VR1
VR2
T'STAT
3.) The Local Loop With The Loop Controller Installed Can Only Have Up To 29 WHP Controllers Attached As The WHP Loop Controller Occupies Address #30.
4.) Systems may consist of up to 20 Local Loops (600 WHP Controllers). Consult factory for systems that exceed these quantities.
4ANALOGIN MOD I/O BD.
YS101784
COMM
T
SHLD
R
LD4
YS101790
REC.
12V AIN
1
AIN
2
AIN
3
AIN
4
AIN
5 GND
GND
AOUT
PRESSURE SENSOR
#1
RAM EPROM 485 COMM
CPU
ADDRESS ADD
EWDOG
YS101564
32K 8K
RELAY
OUTPUT COM 1-3
OUT
1
OUT
2
OUT
3
OUT
OUT
4
OUT
5 COM 4-5
4-5
COMM
TEST
0-5
VDC
PWR
GND
0-1
VDC
24VAC
See Note #3
Dirty Filter Alarm
Loop #1
WHP
Controllers
Loop #2
WHP
Controllers
Loop #3
WHP
Controllers
Loop #4
WHP
Controllers
Local Loop
RS-485
9600 Baud
#30
32K 8K
COMM
RELAY OUTPUT
T
COM 1-3
SHLD
OUT
R
1 OUT
RAM EPROM
485
LD4
2
COMM
OUT 3
REC.
OUT
OUT 4 OUT 5 COM
CPU
4-5
4-5
COMM
12V
TEST
ADDRESS ADD
AIN 1 AIN 2 AIN 3
EWDOG
AIN 4 AIN 5 GND
GND
0-5 VDC
AOUT
PWR
PRESSURE
GND
SENSOR
YS101564
0-1 VDC
24VAC
#30
32K 8K
COMM
RELAY OUTPUT
T
COM 1-3
SHLD
OUT
R
1 OUT
RAM EPROM
485
LD4
2
COMM
OUT 3
REC.
OUT
OUT 4 OUT 5 COM
CPU
4-5
4-5
COMM
12V
TEST
ADDRESS ADD
AIN
1
AIN
2
AIN
3
EWDOG
AIN
4
AIN
5 GND
GND
0-5
VDC
AOUT
PWR
PRESSURE
GND
SENSOR
YS101564
0-1
VDC
24VAC
#30
32K
8K
COMM
RELAY OUTPUT
T
COM 1-3
SHLD
OUT
R
1
OUT
RAM EPROM
485
LD4
2
COMM
OUT
3
REC.
OUT
OUT
4
OUT
5
COM
CPU
4-5
4-5
COMM
12V
TEST
ADDRESS ADD
AIN 1 AIN 2 AIN 3
EWDOG
AIN 4 AIN 5 GND
GND
0-5
VDC
AOUT
PWR
PRESSURE
GND
SENSOR
YS101564
0-1
VDC
24VAC
#29
32K 8K
COMM
RELAY OUTPUT
T
COM 1-3
SHLD
OUT
R
1 OUT
RAM EPROM
485
LD4
2
COMM
OUT
3
REC.
OUT
OUT 4 OUT
5
COM
CPU
4-5
4-5
COMM
12V
TEST
ADDRESS ADD
AIN 1 AIN 2 AIN 3
EWDOG
AIN 4 AIN 5 GND
GND
0-5 VDC
AOUT
PWR
PRESSURE
GND
SENSOR
YS101564
0-1 VDC
24VAC
Figure 2-1:
System Overview
2-2 Installation and Wiring
WattMaster WHP Section 2
Communications Loops
The Communications Loop is two wire shielded RS-485. The loop is best connected in daisy chain configuration, meaning the loop is connected from one controller to another. It is not necessary to sequentially address the WHP Controllers in relation to their location on the loop. Cable must be Belden No. 82760 or equivalent.
Tip: Incorrect wiring of the communications loop is the most common mistake made
during installation. Before beginning installation, write down the wire color used on each terminal connection and consistently maintain that color code. It is recommended that a continuous wire run be made between devices. Anytime a splice is made in the cable you increase your chance of problems.
Caution: Make sure when you are inserting wires into the terminal blocks that
strands of wire do not stick out and touch the next terminal. This could cause a short or erratic operation.
Installation and Wiring 2-3
Section 2 WattMaster WHP
STANDARD WALL MOUNT
120/24 VAC POWER SUPPLY
( MAY ALSO BE POWERED FROM 2 4VAC )
(NETWORK TERMINAL S ONLY)
Y
SYSTEM MANAGER POWER SUPPLY
GND
24VAC
POWER
LOOP
A
A
4
T
3
A
4
Y
CPU
A
A
4
T
3
A
4
Y
CPU
A
A
A
A
Y
4
4
4
2 4 V A C
G N D
U6
C1
U2
U3
U4
V1V2V3V5V4
L1
R6
C9
6
M U8
U9
C7
CX10
CX12
CX14
CX13
X2
INPUTS
+
A
A
A
A
A
RS-485
S
COMM
COMM
U1
COMM
LED1
LED2
R1
U7
VREF ADJ
TEST POINT
C
C
CX15
Communications Loop Wiring Overview
03/31/04 03:38P M WED
OCCUPIED
COMPUTER (OPTIONAL)
NO ALARMS
SYSTEM MANAGER
(SET TO MULTIPLE LOOP)
COMMUNICATIONS
T
SHLD
R
RS-485
COMM LINK II
INTERFACE
UNIT COMES WITH
S101716 REV. 1
Remote Link (OPTIONAL)
2K
COMM
T SHLD R
LD4
REC.
12V
IN 1
AIN
2
AIN
3
AIN
4
AIN
5 GND GND
OUT
PRESSURE SENSOR
COMM
T SHLD R
LD4
REC.
12V
IN 1 AIN 2 AIN 3 AIN 4 AIN 5 GND
GND
OUT
PRESSURE SENSOR
NETWORK
T
C21
CX1
RN1
1
TB1
T HLD
R
CX5
U5
LD6
LD7
1
PWR
LD8
RN3
LD9
P1
+VREF
5.11V
EWDOG
RV1
R28
VDC
RN5
IN1 IN2
IN3 IN4 IN5
C10
GND GND
C12
AOUT1 AOUT2 AIN7
D15
C17
GND
PJ1
TB3
C20
R26
PRESSURE SENSOR
GND
24VAC
R
SH
T
R
SH
EXPANSION
D1
CX2
CX3
CX4
RLY1
D2D3D4D5
RLY2RLY3RLY4RLY5
OM1-3
PAL
R1
1
EPROM
RAM
HH
PHILIPS
ADD
ADDRESS
1 2 4
PU1
8
D6
16
PU2
32
D7
TOKEN
PU3
NETWORK
D8
SW1 PU4 D9 PU5 D11 PU7
0-5
0-1
VDC
VDC
D14
JP1
U13
U15
PJ3
PJ2
R2
TUC-5R PLUS
R3
(1 MEG)
YS101816 REV. 2
R4
RN2
R5
OM4-5
TB2
CX6
C2
X1
C3
1
RN4
NE5090NPB3192 0PS
CX8
U10
R7
D10
R10
D13
D12
C11
993
R13
R11
U11 MC34064A
SC1
C13
R15
U12
C14
C16
R19
U14
C15
R22 R24 R25
TB4
D19
GND
R27
D16
V6
D18
D17
POWER
C19
C18
7824CT
24VAC
VR1
VR2
T'STAT
RLY IO BD.
RLY IO BD. IN1
IN2 IN3
IN4 GND AOUT1
YS101790
YS101790
ANALOG IN MOD I/O BD.
S101784
TO OTHER MINILINKS
Figure 2-2:
Communication Loop Wiring, Daisy-Chain Configuration
8K
RELAY
OUTPUT COM 1-3 OUT
1
RAM EPROM
85
COMM
DDRESS AD D
EWDOG
S101564
RAM EPROM
85
COMM
DDRESS ADD
EWDOG
S101564
OUT
2 OUT
3 OUT
OUT
4 OUT
5 COM 4-5
-5
COMM
EST
0-5
VDC
PWR
GND
0-1
VDC
24VAC
2K 8K
RELAY
OUTPUT COM 1-3 OUT
1 OUT
2 OUT
3 OUT
OUT
4 OUT
5 COM 4-5
-5
COMM
EST
0-5
VDC
PWR
GND
0-1
VDC
24VAC
TO OTHER WHP CONTROLLERS
2-4 Installation and Wiring
WattMaster WHP Section 2
The daisy chain is the best method for running a communications loop since there is only one starting point and one ending point for each of the communications loops. Even though the daisy chain configuration is preferred, the star configuration can also be used. If required, a combination of the two can also be used. Remember, the best communication loop wiring is the one which utilizes the minimum number of ends while using the shortest wiring path.
Note: The loop does not have to follow the controller address sequence.
Caution: If the comm loop is not installed in conduit, be careful to position the
cable away from high noise devices like fluorescent lights, transformers, VFD’s, etc. Conduit is not required for comm loop wiring unless required by local codes.
Make sure CommLink jumper is set for “Multi”.
Installation and Wiring 2-5
Section 2 WattMaster WHP
RLY1D1D
2D3D4D5CX
3
C3C
2
R11U1
1
D13
6
M
R10
CX8U9X1R7D10
RN4
R
N
2
R
LY2RLY3RLY4RLY5
6.2’’
WHP Loop Controller Expansion Board
WHP Loop Controller Main Board
.20 Dia.
W
V A
J
V
T
T
A /
V
Y
V J
V
T
V
X
X
V
Y
T
V
X
X
JO3JO4JO2J
A
T
A
A
A
WHP Loop Controller
The WHP Loop Controller may be installed in any convenient protected location. It is recommended that the loop controller be mounted indoors in a secure location, that is not subject to extremes in temperature or moisture.
Typ. of 4
7.3”
TB1
COMM
T
SHLD
R
LD6
COMM
LD7 PWR
LD8
LED1
LD9
LED2
R1
U7
INPUTS
+VDC AIN1 AIN2 AIN3 AIN4 AIN5 GND GND AOUT1
AOUT2
AIN7 GND
PJ1
TB3
PRESSURE SENSOR
C21
RN1
1
CX5
1
RN3
+VREF
TEST POINT
RV1 VREF ADJ
RN5
C10
C17
EXPANSION
CX1
U1
U5
RS-485
COMM
HH
C1
P1
5.11V
EWDOG
R28
ADDRESS
PU1 D6 PU2 D7 PU3 D8 PU4 D9 PU5 D11 PU7 D14
C12
U13
D15
C20
R26
PJ2
U3
CX2
U2
RAM
YS101816 REV. 2
U6
PHILIPS
ADD
1 2 4 8 16
32 TOKEN
NETWORK
SW1
X2
0-5
0-1
VDC
VDC
JP1
R15
C14
R19
CX13
U15
C15
R22 R24 R25
CX15
PJ3
EPROM
TUC-5R PLUS
U10
C11
U14
CX10
U12
CX14
D17
T'STAT
6.7”
(1 MEG)
CX4
U4
PAL
1
CX6
1
C7
CX12
D18
L1
D12 R13
SC1
D19
C19
C18
7824CT
VR1
VR2
D16
COM1-3
COM4-5
NE5090NPB3192 0PS
R6
R27
V6
C9
993
R1 R2 R3 R4 R5
U8
MC34064A
C13
C16
GND
POWER
24VAC
V1
V2
V3
TB2
V4
V5
9.5”
6.6”
TB4
B 1
B 1
B 1
R 8
C 8
R20
1K1
4
4RLY IO BD.
1K1
4
4RLY IO BD.
IN1
IN2
IN3 AIN4
GND
OUT1
R10
T C 4 2 8 7
S 1 0 1 7 8 2
2.12”
T
T
B
B
2
1
+
G
G
2
2
N
4
N
4
D
D
P
D
L
C
D
C
-
P
1
I
R
-
N
O
2
K
U
2
UL
5A250VAC
5A250VAC
UL
CONTACT:
CONTACT:
24VDC
24VDC
G5L-114P-PS
G5L-114P-PS
OMRON
OMRON
UL
UL
5A250VAC
5A250VAC
CONTACT:
CONTACT:
24VDC
24VDC
G5L-114P-PS
G5L-114P-PS
OMRON
OMRON
K
K
4
3
YS101790
K 2
UL
5A250VAC
5A250VAC
UL
CONTACT:
CONTACT:
24VDC
24VDC
G5L-114P-PS
G5L-114P-PS
OMRON
OMRON
UL
UL
5A250VAC
5A250VAC
CONTACT:
CONTACT:
24VDC
24VDC
G5L-114P-PS
G5L-114P-PS
OMRON
OMRON
K
K
4
3
S101790
PU1
O1
R5
C2
R1
PU2
R6
R7
R8 R9
D5
S L O
M O D U L R I O B D .
D1
C3
R2
PU3
D2
C4
R3
PU4
D3
C5
R4
C1
D4
C
U
Q
X
2
LM358
2
1
C 7
4
K1
K2
K3
RN1
K4
K1
K2
K3
RN1
K4
4 ANALOG IN MOD. I/O BD. YS101784
R 9
R
R
1
1
6
R 1 8
C 1
P 1
ULN2803A/
PHILIPS
T L HA AN I D
U1
C
74HC04N
2
U2
PCF8574P
CX3
U 3
C 1
P 1
ULN2803A/
PHILIPS
T L HA AN I D
U1
C
74HC04N
2
U2
PCF8574P
CX1
P C F 8 5 9 1 P
R10 R11 R12
8.29”
CX3
U 3
P 1
U1
T L HA
PHILIPS
AN I D
P 4
P 4
8.96”
0.28”
4.24”
4.0”
Figure 2-3:
WHP Loop Controller
2-6 Installation and Wiring
Loading...
+ 96 hidden pages