This document uses the following definitions throughout as a guide to the user in
determining the nature of the information presented:
Note: Additional information which may be helpful.
Tip: Suggestion to make installation, set-up, and troubleshooting easier.
Caution: Items which may cause the equipment not to function correctly but will
not otherwise damage components.
Warning: Errors which can result in damage to equipment and void warranties.
Design Guide1-1
Section 1WattMaster WHP
General Information
Water Source Heat Pump Units
A water source heat pump is a self-contained water-cooled packaged heating and cooling
unit with a reversible refrigerant cycle. Its components are typically enclosed in a
common casing, and include a tube-in-tube heat exchanger, a heating/cooling coil, a
compressor, a fan, a reversing valve and controls
.
1-2Design Guide
WattMaster WHPSection 1
Figure 1-1:
Typical Water Source Heat Pump
During the cooling mode, the tube-in-tube heat exchanger functions as a condenser and
the coil as an evaporator. In heating mode, the tube-in-tube heat exchanger functions as
an evaporator and the coil as a condenser. A reversing valve is installed in the refrigerant
circuit permitting changeover from heating to cooling, and vice versa. The condenser and
evaporator tubes are designed to accept hot and cold refrigerant liquid or gas.
Water Source Heat Pump Systems
The water source heat pump system is, by definition, a heat recovery system. It is best
applied to buildings that have simultaneous cooling and heating loads. This is the case
during winter months when the interior zones of a typical building require cooling while
the exterior zones require heating. When a water source heat pump system is used, the
heat rejected by the cooling units is used to warm the zones calling for heat. A water
heater is generally used for adding heat to the condensing water during peak heating
periods, if necessary. The system also utilizes a water cooling tower to reject the heat
energy from the condenser water loop during periods of high cooling demand.
Water source heat pump units can be suspended in the ceiling plenum, floor mounted
behind walls or placed directly in the occupied space as a console unit. There are also
rooftop and unit ventilator type water source heat pumps.
Figure 1-2:
Typical Water Source Heat Pump System
Water source heat pump systems generally cost less to install than central built-up
systems. They offer individual zone control with the added flexibility of being able to
Design Guide1-3
Section 1WattMaster WHP
accommodate changes in location and sizes as thermal zones or zone occupancy change.
This system is often installed in ceiling plenums, which frees up valuable floor space.
Another valuable benefit of water source heat pumps is that they can accommodate
simultaneous calls from zones requiring heating or cooling. Depending on the climate,
outside air may require preheat or cooling prior to being introduced to the unit. In the
example of ceiling mounted water source heat pumps, put outside air ducts near each unit
to improve indoor air quality.
Normally, multiple units serve an occupied space. This gives component redundancy to
the system so if one unit were to fail, the other units could back it up until the unit was
repaired. The packaged design of most unit types allows quick change-out by service
personnel so maintenance can typically be performed off site.
As with any HVAC system, there is a negative side as the water source heat pump system
often requires higher maintenance costs than conventional air side systems. The system
also typically has a shorter replacement life than other systems because of continuous fan
and compressor operation during heating and cooling modes. The system can also create
room noise since the compressor and fan are commonly located close to the zone
occupant. Placing units away from the occupied space and ducting the supply air to the
zone can minimize potential noise problems.
WattMaster WHP Control System
The WattMaster WHP system is used to control the water loop and the individual water
source heat pumps installed in a typical water source heat pump system. The WHP
system is an excellent alternative over programmable thermostats. The WHP control
system provides one central location to monitor and program all the water source heat
pumps on the system instead of having to program each water source heat pumps
thermostat individually. The system has many features typically not found with
programmable thermostats such as: central operators interface, heating/cooling failure
alarm, auxiliary alarm, and holiday scheduling, to name but a few.
WHP Controller
The Water Source Heat Pump Controller (WHP) is used for controlling individual water
source heat pump units. The WHP Controller can operate stand-alone or it can be used
with the Water Source Heat Pump Loop Controller and in this configuration shares
common data, such as outside air temperature, proof of flow etc., over a network. A
System Manager is connected to the WHP Controller to provide a central operators
interface to all WHP Controllers on the network. WHP Controllers are designed with
Room Temperature, Room Setpoint Adjust, Discharge Air Temperature, Leaving Water
Temp or Dirty Filter Alarm and Auxiliary Lockout inputs. Relay outputs provided are;
Fan (Continuous or Cycling), Reversing Valve-ON/OFF, Compressor-ON/OFF, Heat
1-4Design Guide
WattMaster WHPSection 1
Pump Reset and Aux. Heating or Cooling. An internal seven day schedule and holiday
schedule functions are also built into each WHP Controller.
With the WHP system the sometimes complex control requirements of a large water
source heat pump system can be handled with an off the shelf controls system that has
most of the features of a full blown building automation system but at a much lower cost.
Included with the WHP system is a communications interface module, which allows you
to connect a computer to the system onsite and a modem connection for remote
monitoring.
Prism, a Windows based software package is available at no additional charge. Some of
Prism’s features include graphics, trend logging, and remote alarm call out capabilities.
WHP Loop Controller
The Water Source Heat pump Loop Controller can be supplied with the system to control
the water loop and its various pieces of equipment. The Loop Controller can operate
stand-alone or used with the Water Source Heat Pump Controller (WHP) and in this
configuration communicates common data, such as outside air temperature, proof of flow
etc., over a network. A System Manager is connected to the Loop Controller to provide a
central operator’s interface to the Loop Controller’s setpoints and operating
configurations. The Loop Controller is designed with inputs for Supply and Return W ater
Temperature, Outdoor Air Temperature, Loop Water Pressure Switch or 0-50 PSI Loop
Pressure Sensor (4-20ma), Manual Reset Contact, Phase Loss Contact, Request to Run
Relay, and Fire/Smoke Relay. Analog outputs (0-10VDC) are supplied for Pump VFD
and Proportional Heat. Binary outputs are provided for Compressor Enable, Main Pump
Relay, Standby Pump Relay, Alarm Contacts and (8) Relays that can be configured for
Heat Rejection or Heat Addition.
Make Up Air Controller
A Make Up Air Controller, for treating 100% outdoor air, is available for use with the
Water Source Heat Pump system. Please consult factory for more information on this
product.
Design Guide1-5
Section 1WattMaster WHP
WHP Sequence of
Operation
HVAC Mode of Operation
There are four possible modes of operation. These are Cooling Mode, Heating Mode,
Vent Mode, and the Off Mode. The HVAC mode of operation is calculated the same way
in both occupied and unoccupied modes of operation.
Off ModeThe schedule is off and no overrides are active. There is no heating or
cooling demand in the space. Under these conditions, all outputs will be
off and the analog output will be set to 0.0 vdc.
Vent ModeNo heating or cooling demand exists during the occupied mode of
operation. The fan will be on if the WHP is programmed for Constant Fan
operation. The compressor demand request will not be sent to the Loop
Controller. If no WHP units are sending a request, the Loop Controller
will discontinue operation after 15 minutes.
Cool ModeA cooling demand is generated when the space temperature rises half the
amount of the Deadband Setpoint above the currently active Cooling
Setpoint. The space is considered satisfied when it drops that amount
below the Cooling Setpoint.
Heat ModeA heating demand is generated when the space temperature drops half the
amount of the Deadband Setpoint below the currently active Heating
Setpoint. The space is considered satisfied when it rises that amount above
the Heating Setpoint.
1-6Design Guide
WattMaster WHPSection 1
Occupied/Unoccupied Mode of
Operation
Since the WHP contains its own built in Real Time Clock, it can operate from its own
internal scheduling system. This schedule supports two Start & Stop events per day and
up to 14 Holiday periods. The Holidays all use the same special Holiday Start/Stop times
programmed by the user.
If the current operating mode is unoccupied, the WHP can accept a push-button override
back to the occupied mode. Push-button overrides are not recognized if the current mode
is already occupied. The push-button override duration is user programmed. If the user
wants to extend the current override without reprogramming the Duration, they can reinitialize the existing programmed period by pressing the override button anytime during
the current override. If the current override had been active for 1 hour and 45 minutes and
the user presses the push-button again, the override will reset for another 2 hour period (ifthey programmed a 2 hour period), bringing the total override time to 3 hours and 45
minutes. If the user wants to cancel an override before it can time-out, simply hold the
push-button for a period of time between 3 and 10 seconds.
The WHP calculates its current heating and cooling setpoints based on the current mode
of operation. If the command is for unoccupied mode, the WHP adds the unoccupied
setbacks to the occupied heating and cooling setpoints.
Vent Mode Operation
During occupied hours when there is no heating or cooling demand, the WHP reverts to a
Vent Mode of operation. The fan is running and the heating and cooling outputs are held
off.
See the section titled HVAC Mode of Operation for a graphical description of how the
Vent Mode is calculated.
Off Mode of Operation
After the schedule goes unoccupied and both heating and cooling demands go away, the
fan stops running, all relay outputs are turned off. No outputs are allowed to activate in
the Off Mode until a heating or cooling demand occurs. During occupied hours this
would be the Vent Mode.
Design Guide1-7
Section 1WattMaster WHP
HVAC Operation w/ Reversing Relay
If the user has configured the WHP to control a Reversing Valve and a Compressor, the
following sequence of operation occurs during a heating or cooling demand.
Note: If you configure the WHP to look for a proof of flow Enable signal from the
Loop Controller then the following sequence assumes a request was made by
the WHP during a demand condition and that the Loop Controller gave
permission for the WHP to start its compressor. Otherwise, the WHP will
ignore the Enable signal and operate anytime there is a heating or cooling
demand.
a. If the last mode was the opposite of the current demand mode, make sure
the Changeover Delay has been satisfied.
b. If the unit is configured to control an Isolation Valve, the valve relay is
activated ( Relay #5 ). The Minimum Off Timer is reset to ZERO and
must be satisfied before any further operations are allowed.
c. If the current mode requires the Reversing Valve to be activated, its relay
contact is closed and a 10 second delay is started.
d. Ten seconds after the Reversing Valve is activated, the Compressor relay
is activated.
e. If the Space Temperature continues to exceed the affected setpoint by the
full amount of Deadband and you have configured for 2 stages in the
current mode of operation, relay #5 will activate for the second stage of
heating and/or cooling. A second stage of either implies that no Isolation
Valve exists!
f. Once the Space Temperature has crossed back over the affected setpoint,
stage 2 will be turned off if the unit has a stage 2.
g. As the Space Temperature continues to cross back over the affected
setpoint by half the Deadband value, the compressor will then be allowed
to turn off if the Minimum Run Time has been satisfied.
1-8Design Guide
WattMaster WHPSection 1
HVAC Operation w/ Heat/Cool Relays
If the user has configured the WHP to control Individual Heating and Cooling relays the
following sequence of operation occurs during a heating or cooling demand.
NOTE: If you configure the WHP to look for a proof of flow Enable signal from the
Loop Controller then the following sequence assumes a request was made by
the WHP during a demand condition and that the Loop Controller gave
permission for the WHP to operate its heating or cooling. Otherwise, the WHP
will ignore the Enable signal and operate anytime there is a heating or cooling
demand.
Once a heating or cooling demand exists, the following conditions must be met before
any relays can be activated:
a. Make sure any stages of the opposite mode are staged off.
b. Verify the system has been configured for at least one stage of heating or
cooling.
c. Make sure the Minimum Cycle Time has been satisfied.
d. If the last mode was the opposite demand mode, make sure the
Changeover Delay has been satisfied.
e. Check the current Minimum Off Timer to make sure this stage has been
off long enough since the last time it was cycled on and back off.
f. If there is more than 1 stage, check the Minimum Run Time from the
previous stage to be sure it has elapsed before activating the second stage.
g. Make sure the Space Temperature Demand is the full amount of Deadband
from the setpoint before activating the second stage.
h. Once the compressor or stage 2 has been turned off, a Minimum Off Time
must be satisfied before it can stage on again. A Minimum Cycle time can
also be utilized to limit the number of times per hour that the compressor
can be activated. If you don’t need this limitation, set the Minimum Cycle
Time to be shorter than the Minimum Run Time setpoint.
i. If the Reversing Valve was configured to cycle with the compressor, it will
now turn off also. It can be configured to remain active until the opposite
mode of operation is called for to reduce wear on the valve.
Design Guide1-9
Section 1WattMaster WHP
WHP Loop Controller
Sequence of Operations
Summary
The Water Source Heat Pump Loop Controller waits for a Request to Run signal from a
Heat Pump or from a Binary Contact Closure. Once the request is received the Loop
Controller activates a Pump to initiate water flow to the Heat Pumps. Once the pump is
activated and proof of flow has been determined, a Global is broadcast to all Heat Pumps
to enable them to go ahead and run their compressors. The main goal of the Loop
Controller is to provide water flow and to maintain the loop water temperature by
monitoring either the Loop Inlet or Loop Outlet temperature. If a higher temperature is
required, Heat Addition is enabled. If the temperature needs to be lowered, Heat
Rejection is enabled.
Once the Loop Controller has been activated by a request, it will run for a minimum of 15
minutes to prevent cycling on and off due to borderline requests from the Heat Pumps.
If a Fire Alarm is detected, the Loop Controller generates a Global broadcast to all Heat
Pumps to turn off.
If the High Pressure option is configured, the Loop Controller can generate a Global
broadcast to force the Heat Pumps to open their Isolation Valves to reduce loop pressure
if the high limit has been exceeded.
Pump Control
If WattMaster Water Source Heat Pump Controllers are used in conjunction with the
Loop Controller, a Global Binary signal from the attached Heat Pumps sends a Request to
run or Enable to Run command to the Loop Controller. If the Loop Controller is used in a
stand alone configuration, a contact closure on the AIN 2 of the Analog Expansion board
gives the controller a request to run. When a request to run is received, the Loop
Controller activates a pump to initiate water flow to the heat pumps. The pumps can
either be constant flow or controlled by a VFD. If the request goes away for at least one
minute, the request to run command is removed. If the loop controller has been running a
minimum of 15 minutes then it can be turned off, since there is no longer a request to run.
If the proof of flow is lost while the pumps are running, the pump is shut off immediately
if the changeover to the Standby Pump had already been made.
The pumps are Lead/Lag controlled based on a user definable number of hours. If one
pump exceeds the other pumps run time by this amount, the lead is changed until that
1-10Design Guide
WattMaster WHPSection 1
pump exceeds the first pumps run time by the same amount. This keeps both pumps with
roughly the same number of hours on each pump. Changeover occurs at the time the run
time setpoint is exceeded. The running pump is shut off at the same time the standby
pump is energized, this prevents any down time or alarms. The unit can be configured to
control either the Loop Inlet temperature or the loop outlet temperature.
A user adjustable low outdoor air temperature setting of XX degrees will allow the unit to
run the pumps continuously for protection against freezing.
If the pump is constant volume, and the pump has been started, it has 3 seconds to
generate flow or the standby pump is activated. If the pump is controlled by a VFD, once
it starts, it has 60 seconds to generate flow and if it doesn’t the standby pump is activated.
If the standby pump fails, an alarm is generated and the Loop controller deactivates any
active heat rejection or addition stages. At the same time an alarm is generated, we
energize relay #5 on the Loop Controller board so that it may used to turn on a local
alarm signal.
Loop flow can be determined by a binary contact closure on input #3 or a 0 to 50 PSI
pressure sensor on input #3. If a pressure sensor is used, the user can program the
pressure setpoint that needs to be met for proof of flow.
Pump VFD Control
An optional Pump VFD signal can be modulated if the system is configured for
proportional control and a pressure sensor is attached to analog input #3.
At a user defined rate, the VFD signal is ramped up when the pressure is below
a user defined setpoint by a user defined deadband. The signal ramps down when the
pressure exceeds the setpoint by the deadband value. If the pressure ever exceeds the high
pressure setpoint, an emergency override activates and begins cutting the VFD signal in
half each time the control loop is polled by the software. This protects against run away
over-pressurization.
The pump relay outputs are still activated and Lead/Lagged as described above
and the pump relay remains on until the Request signal is removed, provided it
has been operating for at least 15 minutes.
Compressor Control
Anytime a pump is running and proof of flow has been established, the compressor output
is activated.
Design Guide1-11
Section 1WattMaster WHP
Heat Rejection Control
If the compressor is not running, no heat rejection can be active. If any heat rejection is
still active when the compressor is turned off, the heat rejection will be immediately
removed, without regard to any minimum run or off times.
Heat rejection cannot be active at the same time as heat addition, so any heat addition is
removed or staged off before the heat rejection can be started.
A maximum of 8 stages of heat rejection can be controlled.
Staged Heat Rejection
Heat Rejection is staged up based on a different deadband level for each stage. Basically,
if the user programmed a 2° deadband, then the first stage could activate at the setpoint,
stage 2 would activate 2° above the setpoint, stage 3 would activate 4° above the setpoint,
etc...
Staging down is calculated in the same manner, except the water temperature would need
to drop below the setpoint by the deadband amount. If stage 3 was activated at 4° above
setpoint, it would de-activate when the temperature fell to within 2° of setpoint, stage 2
would de-activate at setpoint and stage 1 would de-activate 2° below setpoint.
A user defined staging up and down interval must be met before any heat rejection stages
can be added or removed. If the selected Water Temperature is above the current staging
level and the timer has been satisfied, an additional stage can be added, up to the
maximum available 8 stages. If the selected Water Temperature is below the staging
down level and the timer has been satisfied, a stage can be removed.
Heat Addition Control
If the compressor is not running, no heat addition can be active. If any heat addition is
still active when the compressor is turned off, the heat addition will be immediately
removed, without regard to any minimum run or off times.
Heat addition cannot be active at the same time as heat rejection, so any heat rejection is
removed or staged off before the heat addition can be started.
A maximum of 4 stages of heat addition can be controlled or proportional heating can be
configured, and an analog output signal will be modulated to control the heat.
1-12Design Guide
WattMaster WHPSection 1
Staged Heat Addition
Heat Addition is staged up based on a different deadband level for each stage. Basically,
if the user programmed a 2° deadband, then the first stage could activate at the setpoint,
stage 2 would activate 2° below the setpoint, stage 3 would activate 4° below the setpoint,
etc...
Staging down is calculated in the same manner, except the water temperature would need
to increase above the setpoint by the deadband amount. If stage 3 was activated at 4°
below setpoint, it would de-activate when the temperature rises t o within 2° of setpoint,
stage 2 would de-activate at setpoint and stage 1 would de-activate 2° above setpoint.
A user defined staging up and down interval must be met before any heat addition stages
can be added or removed. If the selected Water Temperature is below the current st aging
level and the timer has been satisfied, an additional stage can be added, up to the
maximum available 8 stages. If the selected Water Temperature is above the staging
down level and the timer has been satisfied, a stage can be removed.
Proportional Heat Addition
If the Water Temperature is below the addition setpoint, a Boiler Enable relay is
activated. If the Water Temperature rises 1° above the setpoint the Boiler Enable relay is
de-activated.
At a user defined rate, the analog output signal is proportionally controlled from 0.0 VDC
at 1° above setpoint to the full 10.0 VDC signal as the water temperature drops below the
setpoint by the user defined deadband amount. If a 5° deadband was entered, the
maximum voltage would be reached at 4° below the setpoint and the minimum volt age
would be set at 1° above the setpoint. Since this is strictly proportional control, at 1.5°
below setpoint the controller would set 5.0 VDC since that would be half the deadband
amount.
Design Guide1-13
Section 1WattMaster WHP
Water Temperature Alarming
The controlling water temperature is monitored to prevent it from exceeding both a user
defined High and Low Alarm Limit. If either limit is exceeded for a user defined length of
time, an alarm is generated and the compressor output is de-activated. If the high limit is
exceeded, the heat addition outputs are de-activated and if the low limit is exceeded, the
heat rejection outputs are de-activated. The alarming and shutdown only pertains to the
controlling water temperature. This does not affect the pump operation.
If a external manual alarm reset button is connected between ground and input #5, All
outputs are turned off and ALL timers are reset. This forces the loop controller to stage
off. This reset WILL shut down the pumps and force them to restart!
Fire Alarm
If the Fire Alarm is activated on input #1 of the Analog Input Expansion Board (Contact
OPENS for Alarm!) then ALL outputs and timers are reset and held off for the duration of
the Fire Alarm signal.
If the Fire Alarm is not required, input #1 of the Analog Input Expansion Board must
have a shorting wire to ground to allow the equipment to operate.
1-14Design Guide
WattMaster WHPSection 1
COMPUTER
(OPTIONAL)
RS-485
Comm Loop
32K
8K
COMM
RELAY
OUTPUT
T
Room Sensor
with Optional
Override & Adj.
COM
1-3
SHLD
OUT
R
1
OUT
RAM EPROM
485
LD4
2
COMM
OUT
3
REC.
OUT
OUT
4
OUT
5
COM
CPU
4-5
4-5
COMM
12V
TEST
ADDRESS ADD
AIN
1
AIN
2
AIN
3
EWDOG
AIN
4
AIN
5
GND
GND
0-5
VDC
AOUT
PWR
PRESSURE
GND
SENSOR
YS101564
0-1
VDC
24VAC
24 VAC
110/24 VAC
Power Pak
Modem
(Optional)
M
R
T
R
S
D
R
D
O
H
C
D
A
A
H
S
CommLink II
Multiple Loop
Interface
C
COMM
O
M
M
L
LINK
IN
K
I
II
I
L
O
C
O
O
M
P
M
O
D
P
E
M
WCLI
AT
T
M
A
S
T
E
R
O
N
T
R
O
S
,
N
C
MiniLink
Loop # 1
K
N
I
L
I
N
I
M
MINILINK
N
NETWORK
1
2
E
4
T
T
8
W
16
SH
O
32
R
R
K
24VAC24VAC
GND
L
LOOP
T
O
O
SH
P
R
24VAC
MiniLink
Loop # 2
K
N
I
L
I
N
I
M
MINILINK
N
NETWORK
1
2
E
4
T
T
8
W
16
SH
O
32
R
R
K
24VAC24VAC
GND
L
LOOP
T
O
O
SH
P
R
24VAC
Typical Network & Local Loop Wiring
2 Conductor Twisted Pair with Shield
(Beldon #82760 or Equivalent)
MiniLink
Loop # 3
K
N
I
L
I
N
I
M
MINILINK
N
NETWORK
1
2
E
4
T
T
8
W
16
SH
O
32
R
R
K
24VAC
GND
L
LOOP
T
O
O
SH
P
R
24VAC
NOTE: * Only One Outside Air Sensor
is Required per WHP System
MiniLink
Loop # 4
K
N
I
L
I
N
I
M
MINILINK
N
NETWORK
1
2
E
4
T
T
8
W
16
SH
O
32
R
R
K
24VAC
GND
GND
L
LOOP
T
O
O
SH
P
R
Loop # 4
Notes:
1.) 24 VAC Must Be Connected
So That All Ground Wires
Remain Common.
2.) All Wiring To Be In Accordance
With Local And National Electrical
Codes and Specifications.
24VAC
110/24 VAC
Power Pak
Network Loop
RS-485
19200 Baud
Local Loop
RS-485
9600 Baud
Local Loop
RS-485
9600 Baud
Local Loop
RS-485
9600 Baud
*OutsideAir
Sensor
Supply
Air
or Leaving Water Temp
F
Sensor
Typical WHP Controller Wiring
#1
32K
8K
COMM
RELAY
OUTPUT
T
COM
1-3
SHLD
OUT
R
1
OUT
RAM EPROM
485
LD4
2
COMM
OUT
3
REC.
OUT
OUT
4
OUT
5
COM
CPU
4-5
4-5
COMM
12V
TEST
ADDRESS ADD
AIN
1
AIN
2
AIN
3
EWDOG
AIN
4
AIN
5
GND
GND
0-5
VDC
AOUT
PWR
PRESSURE
GND
SENSOR
YS101564
0-1
VDC
24VAC
System Manager
#1
32K
8K
COMM
RELAY
OUTPUT
T
COM
1-3
SHLD
OUT
R
1
OCCUPIED
ALARMS
03/31/04 03:38PM WED
NO
OUT
RAM EPROM
485
LD4
2
COMM
OUT
3
REC.
OUT
OUT
4
OUT
5
COM
CPU
4-5
4-5
COMM
12V
TEST
ADDRESS ADD
AIN
1
AIN
2
AIN
3
EWDOG
AIN
4
AIN
5
GND
GND
0-5
VDC
AOUT
PWR
PRESSURE
GND
SENSOR
YS101564
0-1
VDC
24VAC
24VAC
#1
32K
8K
COMM
RELAY
OUTPUT
T
COM
1-3
SHLD
OUT
R
1
OUT
RAM EPROM
485
LD4
2
COMM
OUT
3
REC.
OUT
OUT
4
OUT
5
COM
CPU
4-5
4-5
COMM
12V
TEST
ADDRESS ADD
AIN
1
AIN
2
AIN
3
EWDOG
AIN
4
AIN
5
GND
GND
0-5
VDC
AOUT
PWR
PRESSURE
GND
SENSOR
YS101564
0-1
VDC
24VAC
WHP Loop
Controller
C21
1
U3
D
3
CX1
X
CX2
U2
RN1
C
CX4
1
U1
U4
1
2
G
Y
4
L
N
V
TB1
COMM
T
SHLD
R
CX5
LD6
COMM
LD7
PWR
LD8
LED1
LD9
LED2
R1
TESTPOINT
U7
RV1
VREFADJ
INPUTS
+VDC
AIN1
AIN2
AIN3
AIN4
AIN5
GND
GND
AOUT1
AOUT2
AIN7
GND
PJ1
TB3
PRESSURE
SENSOR
EXPANSION
V1
R
A
D
C
2
D
V2
V3
2
Y
L
R
COM1-3
3
D
U5
PAL
R1
RS-485
1
EPROM
RAM
R2
COMM
3
Y
TUC-5RPLUS
1
L
HH
R
R3
(1MEG)
4
YS101816REV.2
2
U6
D
3
N
YS101790
4RLYIOBD.
R4
N
R
R
C1
R5
P1
4
COM4-5
Y
L
R
+VREF
TB2
CX6
5
5.11V
D
2
V4
C
S
IP
EWDOG
1
IL
X
V5
H
P
5
R28
Y
L
3
R
C
1
ADD
ADDRESS
U8
1
4
4RLYIOBD.
N
2
R
RN5
4
NE5090NPB3192
8
PU1
X
0PS
8
C
U9
D6
16
PU2
32
D7
TOKEN
PU3
NETWORK
D8
SW1
PU4
D9
PU5
D11
C
C
C10
PU7
-1
-5
D
D
0
0
V
V
JP1
D14
C12
U13
CX13
D15
C17
U15
C20
CX15
R26
3
2
J
J
P
P
AIN1
CX10
C7
AIN2
R6
AIN3
0
7
1
U10
R
D
AIN4
0
3
1
1
L1
C9
R
D
GND
CX12
1
1
1
D12
C
1
1
X2
AOUT1
9936
1
R13
R
U
MC34064A
SC1
C13
R15
U12
CX14
C14
C16
R19
U14
TB4
C15
D19
GND
R22
7
2
6
R24
R
R
1
E
D
8
7
6
R25
1
1
W
V
9
8
D
D
O
1
1
P
C
C
7824CT
24VAC
M
VR1
VR2
T'STAT
3.) The Local Loop With The Loop Controller
Installed Can Only Have Up To 29
WHP Controllers Attached As The WHP
Loop Controller Occupies Address #30.
4.) Systems may consist of up to 20 Local
Loops (600 WHP Controllers). Consult
factory for systems that exceed these quantities.
4ANALOGIN MOD I/O BD.
YS101784
COMM
T
SHLD
R
LD4
YS101790
REC.
12V
AIN
1
AIN
2
AIN
3
AIN
4
AIN
5
GND
GND
AOUT
PRESSURE
SENSOR
#1
RAM EPROM
485
COMM
ADDRESS ADD
EWDOG
YS101564
32K
8K
COM
1-3
COM
CPU
4-5
4-5
COMM
TEST
0-5
VDC
0-1
VDC
See Note #3
RELAY
OUTPUT
OUT
1
OUT
2
OUT
3
OUT
OUT
4
OUT
5
PWR
GND
24VAC
Dirty Filter Alarm
Loop #1
WHP
Controllers
Loop #2
WHP
Controllers
Loop #3
WHP
Controllers
Loop #4
WHP
Controllers
Local Loop
RS-485
9600 Baud
COMM
COMM
LD4
REC.
PRESSURE
SENSOR
COMM
T
SHLD
R
LD4
REC.
12V
AIN
AIN
AIN
AIN
AIN
GND
GND
AOUT
PRESSURE
SENSOR
T
SHLD
R
12V
AIN
1
AIN
2
AIN
3
AIN
4
AIN
5
GND
GND
AOUT
#30
T
SHLD
R
LD4
REC.
12V
AIN
1
AIN
2
AIN
3
AIN
4
AIN
5
GND
GND
AOUT
PRESSURE
SENSOR
#30
1
2
3
4
5
YS101564
COMM
T
SHLD
R
LD4
REC.
PRESSURE
SENSOR
YS101564
485
COMM
YS101564
RAM EPROM
485
COMM
ADDRESS ADD
EWDOG
#30
12V
AIN
1
AIN
2
AIN
3
AIN
4
AIN
5
GND
GND
AOUT
YS101564
#29
RAM EPROM
485
COMM
ADDRESS ADD
EWDOG
32K
8K
RELAY
OUTPUT
COM
1-3
OUT
1
OUT
RAM EPROM
2
OUT
3
OUT
OUT
4
OUT
5
COM
CPU
4-5
4-5
COMM
TEST
ADDRESS ADD
EWDOG
0-5
VDC
PWR
GND
0-1
VDC
24VAC
32K
8K
RELAY
OUTPUT
COM
1-3
OUT
1
OUT
2
OUT
3
OUT
OUT
4
OUT
5
COM
CPU
4-5
4-5
COMM
TEST
0-5
VDC
PWR
GND
0-1
VDC
24VAC
32K
8K
RELAY
OUTPUT
COM
1-3
OUT
1
OUT
RAM EPROM
485
2
COMM
OUT
3
OUT
OUT
4
OUT
5
COM
CPU
4-5
4-5
COMM
TEST
ADDRESS ADD
EWDOG
0-5
VDC
PWR
GND
0-1
VDC
24VAC
32K
8K
RELAY
OUTPUT
COM
1-3
OUT
1
OUT
2
OUT
3
OUT
OUT
4
OUT
5
COM
CPU
4-5
4-5
COMM
TEST
0-5
VDC
PWR
GND
0-1
VDC
24VAC
Figure 1-3:
Typical WattMaster WHP System
Design Guide1-15
Section 1WattMaster WHP
Notes:
1-16Design Guide
Section 2
Table of Contents
Tips Before Beginning Installation.................................. 1
Figure 2-16: Supply Air Temperature Sensor..............................................................21
Figure 2-17: Water Temperature Sensor .....................................................................22
Figure 2-18: Water Temperature Sensor .....................................................................22
Installation and Wiring
WattMaster WHPSection 2
Tips Before Beginning
Installation
Take a few moments to review the following before beginning installation of the
WattMaster WHP System.
• Familiarize yourself with all system components and review all documentation. Pay
special attention to “Cautions” and “Warnings” since these may keep you from
experiencing unnecessary problems.
• Before installing controllers, be sure to tag it with its appropriate location. It is also
best to set the controller address switches before mounting. Use the WHP Address
Worksheet to list all WHP unit locations. This will assist you greatly when setting up
the system.
• Be sure and install all wiring according to local, state, and national electric codes.
• Pay close attention to communication wiring since the most common mistakes are
made in this area. Polarity is the most important rule. Make notes on your wiring
diagrams as to which color wire you will be using on each terminal.
• When in doubt - ask! Contact your local WattMaster distributor if you have any
questions. The only dumb questions are the ones you don’t ask.
• Remember - each electronic device contains only one puff of smoke. If you release it,
you have voided the warranty! So please be careful and pay attention.
Installation and Wiring2-1
Section 2WattMaster WHP
COMPUTER
(OPTIONAL)
RS-485
Comm Loop
32K
8K
COMM
RELAY
OUTPUT
T
Room Sensor
with Optional
Override & Adj.
COM
1-3
SHLD
OUT
R
1
OUT
RAM EPROM
485
LD4
2
COMM
OUT
3
REC.
OUT
OUT
4
OUT
5
COM
CPU
4-5
4-5
COMM
12V
TEST
ADDRESS ADD
AIN
1
AIN
2
AIN
3
EWDOG
AIN
4
AIN
5
GND
GND
0-5
VDC
AOUT
PWR
PRESSURE
GND
SENSOR
YS101564
0-1
VDC
24VAC
24 VAC
110/24 VAC
Power Pak
Modem
(Optional)
M
R
T
R
S
D
R
D
O
H
C
D
A
A
H
S
CommLink II
Multiple Loop
Interface
C
COMM
O
M
M
L
LINK
IN
K
I
II
I
L
O
C
O
O
M
P
M
O
D
P
E
M
WCLI
AT
T
M
A
S
TE
R
O
N
T
R
O
S, N
C
MiniLink
Loop # 1
K
N
I
L
I
N
I
M
MINILINK
N
NETWORK
1
2
E
4
T
T
8
W
16
SH
O
32
R
R
K
24VAC
GND
L
LOOP
T
O
O
SH
P
R
24VAC
MiniLink
Loop # 2
K
N
I
L
I
N
I
M
MINILINK
N
NETWORK
1
2
E
4
T
T
8
W
16
SH
O
32
R
R
K
24VAC
GND
L
LOOP
T
O
O
SH
P
R
24VAC
Typical Network & Local Loop Wiring
2 Conductor Twisted Pair with Shield
(Beldon #82760 or Equivalent)
MiniLink
Loop # 3
K
N
I
L
I
N
I
M
MINILINK
N
NETWORK
1
2
E
4
T
T
8
W
16
SH
O
32
R
R
K
24VAC
GND
L
LOOP
T
O
O
SH
P
R
24VAC
NOTE: * Only One Outside Air Sensor
is Required per WHP System
MiniLink
Loop # 4
K
N
I
L
I
N
I
M
MINILINK
N
NETWORK
1
2
E
4
T
T
8
W
16
SH
O
32
R
R
K
24VAC24VAC
GND
L
LOOP
T
O
O
SH
P
R
Loop # 4
Notes:
1.) 24 VAC Must Be Connected
So That All Ground Wires
Remain Common.
2.) All Wiring To Be In Accordance
With Local And National Electrical
Codes and Specifications.
24VAC
110/24 VAC
Power Pak
Network Loop
RS-485
19200 Baud
Local Loop
RS-485
9600 Baud
Local Loop
RS-485
9600 Baud
Local Loop
RS-485
9600 Baud
*OutsideAir
Sensor
Supply
Air
or Leaving Water Temp
F
Sensor
Typical WHP Controller Wiring
#1
32K
8K
COMM
RELAY
OUTPUT
T
COM
1-3
SHLD
OUT
R
1
OUT
RAM EPROM
485
LD4
2
COMM
OUT
3
REC.
OUT
OUT
4
OUT
5
COM
CPU
4-5
4-5
COMM
12V
TEST
ADDRESS ADD
AIN
1
AIN
2
AIN
3
EWDOG
AIN
4
AIN
5
GND
GND
0-5
VDC
AOUT
PWR
PRESSURE
GND
SENSOR
YS101564
0-1
VDC
24VAC
System Manager
D
E
W
M
P
8
3
:
3
D
0
E
I
4
S
P
0
M
U
/
R
C
1
A
C
3
L
O
/
A
3
0
O
N
24VAC
#1
32K
8K
COMM
RELAY
OUTPUT
T
COM
1-3
SHLD
OUT
R
1
OUT
RAM EPROM
485
LD4
2
COMM
OUT
3
REC.
OUT
OUT
4
OUT
5
COM
CPU
4-5
4-5
COMM
12V
TEST
ADDRESS ADD
AIN
1
AIN
2
AIN
3
EWDOG
AIN
4
AIN
5
GND
GND
0-5
VDC
AOUT
PWR
PRESSURE
GND
SENSOR
YS101564
0-1
VDC
24VAC
#1
32K
8K
COMM
RELAY
OUTPUT
T
COM
1-3
SHLD
OUT
R
1
OUT
RAM EPROM
485
LD4
2
COMM
OUT
3
REC.
OUT
OUT
4
OUT
5
COM
CPU
4-5
4-5
COMM
12V
TEST
ADDRESS ADD
AIN
1
AIN
2
AIN
3
EWDOG
AIN
4
AIN
5
GND
GND
0-5
VDC
AOUT
PWR
PRESSURE
GND
SENSOR
YS101564
0-1
VDC
24VAC
WHP Loop
Controller
C21
1
U3
D
3
CX1
X
CX2
U2
RN1
C
CX4
1
U1
U4
1
2
G
Y
4
L
N
V
TB1
COMM
T
SHLD
R
CX5
LD6
COMM
LD7
PWR
LD8
LED1
LD9
LED2
R1
U7
RV1
VREFADJ
INPUTS
+VDC
AIN1
AIN2
AIN3
AIN4
AIN5
GND
GND
AOUT1
AOUT2
AIN7
GND
PJ1
TB3
PRESSURE
SENSOR
V1
R
A
D
C
2
D
V2
V3
2
Y
L
R
COM1-3
3
D
U5
PAL
R1
RS-485
1
EPROM
RAM
R2
COMM
3
Y
TUC-5RPLUS
1
L
HH
R
R3
(1MEG)
4
YS101816REV.2
2
U6
D
3
N
YS101790
4RLYIOBD.
R4
N
R
R
C1
R5
P1
4
COM4-5
Y
L
R
+VREF
TB2
CX6
5
5.11V
D
TESTPOINT
2
V4
C
S
IP
EWDOG
1
IL
X
V5
H
P
5
R28
Y
L
3
R
C
1
ADD
ADDRESS
U8
1
4
4RLYIOBD.
N
2
R
RN5
4
NE5090NPB3192
8
PU1
X
0PS
8
C
U9
D6
16
PU2
32
D7
TOKEN
PU3
NETWORK
D8
SW1
PU4
D9
PU5
D11
C
C
C10
PU7
-1
-5
D
D
0
0
V
V
JP1
D14
C12
U13
CX13
D15
C17
U15
C20
CX15
R26
3
2
J
J
P
P
EXPANSION
AIN1
CX10
C7
AIN2
R6
AIN3
0
7
1
U10
R
D
AIN4
0
3
1
1
L1
C9
R
D
GND
CX12
1
1
1
D12
C
1
1
X2
AOUT1
9936
1
R13
R
U
MC34064A
SC1
C13
R15
U12
CX14
C14
C16
R19
U14
TB4
C15
D19
GND
R22
7
2
6
R24
R
R
1
E
D
8
7
6
R25
1
1
W
V
9
8
D
D
O
1
1
P
C
C
7824CT
24VAC
M
VR1
VR2
T'STAT
3.) The Local Loop With The Loop Controller
Installed Can Only Have Up To 29
WHP Controllers Attached As The WHP
Loop Controller Occupies Address #30.
4.) Systems may consist of up to 20 Local
Loops (600 WHP Controllers). Consult
factory for systems that exceed these quantities.
4ANALOGIN MOD I/O BD.
YS101784
COMM
T
SHLD
R
LD4
YS101790
REC.
12V
AIN
1
AIN
2
AIN
3
AIN
4
AIN
5
GND
GND
AOUT
PRESSURE
SENSOR
#1
RAM EPROM
485
COMM
CPU
ADDRESS ADD
EWDOG
YS101564
32K
8K
RELAY
OUTPUT
COM
1-3
OUT
1
OUT
2
OUT
3
OUT
OUT
4
OUT
5
COM
4-5
4-5
COMM
TEST
0-5
VDC
PWR
GND
0-1
VDC
24VAC
See Note #3
Dirty Filter Alarm
Loop #1
WHP
Controllers
Loop #2
WHP
Controllers
Loop #3
WHP
Controllers
Loop #4
WHP
Controllers
Local Loop
RS-485
9600 Baud
#30
32K
8K
COMM
RELAY
OUTPUT
T
COM
1-3
SHLD
OUT
R
1
OUT
RAM EPROM
485
LD4
2
COMM
OUT
3
REC.
OUT
OUT
4
OUT
5
COM
CPU
4-5
4-5
COMM
12V
TEST
ADDRESS ADD
AIN
1
AIN
2
AIN
3
EWDOG
AIN
4
AIN
5
GND
GND
0-5
VDC
AOUT
PWR
PRESSURE
GND
SENSOR
YS101564
0-1
VDC
24VAC
#30
32K
8K
COMM
RELAY
OUTPUT
T
COM
1-3
SHLD
OUT
R
1
OUT
RAM EPROM
485
LD4
2
COMM
OUT
3
REC.
OUT
OUT
4
OUT
5
COM
CPU
4-5
4-5
COMM
12V
TEST
ADDRESS ADD
AIN
1
AIN
2
AIN
3
EWDOG
AIN
4
AIN
5
GND
GND
0-5
VDC
AOUT
PWR
PRESSURE
GND
SENSOR
YS101564
0-1
VDC
24VAC
#30
32K
8K
COMM
RELAY
OUTPUT
T
COM
1-3
SHLD
OUT
R
1
OUT
RAM EPROM
485
LD4
2
COMM
OUT
3
REC.
OUT
OUT
4
OUT
5
COM
CPU
4-5
4-5
COMM
12V
TEST
ADDRESS ADD
AIN
1
AIN
2
AIN
3
EWDOG
AIN
4
AIN
5
GND
GND
0-5
VDC
AOUT
PWR
PRESSURE
GND
SENSOR
YS101564
0-1
VDC
24VAC
#29
32K
8K
COMM
RELAY
OUTPUT
T
COM
1-3
SHLD
OUT
R
1
OUT
RAM EPROM
485
LD4
2
COMM
OUT
3
REC.
OUT
OUT
4
OUT
5
COM
CPU
4-5
4-5
COMM
12V
TEST
ADDRESS ADD
AIN
1
AIN
2
AIN
3
EWDOG
AIN
4
AIN
5
GND
GND
0-5
VDC
AOUT
PWR
PRESSURE
GND
SENSOR
YS101564
0-1
VDC
24VAC
Figure 2-1:
System Overview
2-2Installation and Wiring
WattMaster WHPSection 2
Communications Loops
The Communications Loop is two wire shielded RS-485. The loop is best connected in
daisy chain configuration, meaning the loop is connected from one controller to another.
It is not necessary to sequentially address the WHP Controllers in relation to their
location on the loop. Cable must be Belden No. 82760 or equivalent.
Tip: Incorrect wiring of the communications loop is the most common mistake made
during installation. Before beginning installation, write down the wire color used
on each terminal connection and consistently maintain that color code. It is
recommended that a continuous wire run be made between devices. Anytime a
splice is made in the cable you increase your chance of problems.
Caution: Make sure when you are inserting wires into the terminal blocks that
strands of wire do not stick out and touch the next terminal. This could
cause a short or erratic operation.
Installation and Wiring2-3
Section 2WattMaster WHP
STANDARD WALL MOUNT
120/24 VAC POWER SUPPLY
( MAY ALSO BE POWERED FROM 2 4VAC )
(NETWORK TERMINAL S ONLY)
Y
SYSTEM MANAGER POWER SUPPLY
GND
24VAC
POWER
LOOP
A
A
4
T
3
A
4
Y
CPU
A
A
4
T
3
A
4
Y
CPU
A
A
A
A
Y
4
4
4
2
4
V
A
C
G
N
D
U6
C1
U2
U3
U4
V1V2V3V5V4
L1
R6
C9
6
M
U8
U9
C7
CX10
CX12
CX14
CX13
X2
INPUTS
+
A
A
A
A
A
RS-485
S
COMM
COMM
U1
COMM
LED1
LED2
R1
U7
VREF ADJ
TEST POINT
C
C
CX15
Communications Loop Wiring Overview
03/31/04 03:38PM WED
OCCUPIED
COMPUTER
(OPTIONAL)
NO ALARMS
SYSTEM MANAGER
(SET TO MULTIPLE LOOP)
COMMUNICATIONS
T
SHLD
R
RS-485
COMM LINK II
INTERFACE
UNIT COMES WITH
S101716 REV. 1
Remote Link
(OPTIONAL)
2K
COMM
TSHLDR
LD4
REC.
12V
IN1
AIN
2
AIN
3
AIN
4
AIN
5GNDGND
OUT
PRESSURESENSOR
COMM
TSHLDR
LD4
REC.
12V
IN1AIN2AIN3AIN4AIN5GND
GND
OUT
PRESSURESENSOR
NETWORK
T
C21
CX1
RN1
1
TB1
T
HLD
R
CX5
U5
LD6
LD7
1
PWR
LD8
RN3
LD9
P1
+VREF
5.11V
EWDOG
RV1
R28
VDC
RN5
IN1
IN2
IN3
IN4
IN5
C10
GND
GND
C12
AOUT1
AOUT2
AIN7
D15
C17
GND
PJ1
TB3
C20
R26
PRESSURE
SENSOR
GND
24VAC
R
SH
T
R
SH
EXPANSION
D1
CX2
CX3
CX4
RLY1
D2D3D4D5
RLY2RLY3RLY4RLY5
OM1-3
PAL
R1
1
EPROM
RAM
HH
PHILIPS
ADD
ADDRESS
1
2
4
PU1
8
D6
16
PU2
32
D7
TOKEN
PU3
NETWORK
D8
SW1
PU4
D9
PU5
D11
PU7
0-5
0-1
VDC
VDC
D14
JP1
U13
U15
PJ3
PJ2
R2
TUC-5R PLUS
R3
(1 MEG)
YS101816 REV. 2
R4
RN2
R5
OM4-5
TB2
CX6
C2
X1
C3
1
RN4
NE5090NPB3192
0PS
CX8
U10
R7
D10
R10
D13
D12
C11
993
R13
R11
U11
MC34064A
SC1
C13
R15
U12
C14
C16
R19
U14
C15
R22
R24
R25
TB4
D19
GND
R27
D16
V6
D18
D17
POWER
C19
C18
7824CT
24VAC
VR1
VR2
T'STAT
RLY IO BD.
RLY IO BD.
IN1
IN2
IN3
IN4
GND
AOUT1
YS101790
YS101790
ANALOG IN MOD I/O BD.
S101784
TO OTHER MINILINKS
Figure 2-2:
Communication Loop Wiring, Daisy-Chain Configuration
8K
RELAY
OUTPUTCOM1-3OUT
1
RAMEPROM
85
COMM
DDRESSADD
EWDOG
S101564
RAMEPROM
85
COMM
DDRESS ADD
EWDOG
S101564
OUT
2OUT
3OUT
OUT
4OUT
5COM4-5
-5
COMM
EST
0-5
VDC
PWR
GND
0-1
VDC
24VAC
2K8K
RELAY
OUTPUTCOM1-3OUT
1OUT
2OUT
3OUT
OUT
4OUT
5COM4-5
-5
COMM
EST
0-5
VDC
PWR
GND
0-1
VDC
24VAC
TO OTHER WHP CONTROLLERS
2-4Installation and Wiring
WattMaster WHPSection 2
The daisy chain is the best method for running a communications loop since there is only
one starting point and one ending point for each of the communications loops. Even
though the daisy chain configuration is preferred, the star configuration can also be used.
If required, a combination of the two can also be used. Remember, the best
communication loop wiring is the one which utilizes the minimum number of ends while
using the shortest wiring path.
Note: The loop does not have to follow the controller address sequence.
Caution: If the comm loop is not installed in conduit, be careful to position the
cable away from high noise devices like fluorescent lights, transformers,
VFD’s, etc. Conduit is not required for comm loop wiring unless
required by local codes.
Make sure CommLink jumper is set for “Multi”.
Installation and Wiring2-5
Section 2WattMaster WHP
RLY1D1D
2D3D4D5CX
3
C3C
2
R11U1
1
D13
6
M
R10
CX8U9X1R7D10
RN4
R
N
2
R
LY2RLY3RLY4RLY5
6.2’’
WHP Loop Controller Expansion Board
WHP Loop Controller Main Board
.20 Dia.
W
VA
J
V
T
T
A/
V
Y
VJ
V
T
V
X
X
V
Y
T
V
X
X
JO3JO4JO2J
A
T
A
A
A
WHP Loop Controller
The WHP Loop Controller may be installed in any convenient protected location. It is
recommended that the loop controller be mounted indoors in a secure location, that is not
subject to extremes in temperature or moisture.
Typ. of 4
7.3”
TB1
COMM
T
SHLD
R
LD6
COMM
LD7
PWR
LD8
LED1
LD9
LED2
R1
U7
INPUTS
+VDC
AIN1
AIN2
AIN3
AIN4
AIN5
GND
GND
AOUT1
AOUT2
AIN7
GND
PJ1
TB3
PRESSURE
SENSOR
C21
RN1
1
CX5
1
RN3
+VREF
TEST POINT
RV1
VREF ADJ
RN5
C10
C17
EXPANSION
CX1
U1
U5
RS-485
COMM
HH
C1
P1
5.11V
EWDOG
R28
ADDRESS
PU1
D6
PU2
D7
PU3
D8
PU4
D9
PU5
D11
PU7
D14
C12
U13
D15
C20
R26
PJ2
U3
CX2
U2
RAM
YS101816 REV. 2
U6
PHILIPS
ADD
1
2
4
8
16
32
TOKEN
NETWORK
SW1
X2
0-5
0-1
VDC
VDC
JP1
R15
C14
R19
CX13
U15
C15
R22
R24
R25
CX15
PJ3
EPROM
TUC-5R PLUS
U10
C11
U14
CX10
U12
CX14
D17
T'STAT
6.7”
(1 MEG)
CX4
U4
PAL
1
CX6
1
C7
CX12
D18
L1
D12
R13
SC1
D19
C19
C18
7824CT
VR1
VR2
D16
COM1-3
COM4-5
NE5090NPB3192
0PS
R6
R27
V6
C9
993
R1
R2
R3
R4
R5
U8
MC34064A
C13
C16
GND
POWER
24VAC
V1
V2
V3
TB2
V4
V5
9.5”
6.6”
TB4
B1
B1
B1
R8
C8
R20
1K1
4
4RLY IO BD.
1K1
4
4RLY IO BD.
IN1
IN2
IN3AIN4
GND
OUT1
R10
TC4287
S101782
2.12”
T
T
B
B
2
1
+
G
G
2
2
N
4
N
4
D
D
P
D
L
C
D
C
-
P
1
I
R
-
N
O
2
K
U
2
UL
5A250VAC
5A250VAC
UL
CONTACT:
CONTACT:
24VDC
24VDC
G5L-114P-PS
G5L-114P-PS
OMRON
OMRON
UL
UL
5A250VAC
5A250VAC
CONTACT:
CONTACT:
24VDC
24VDC
G5L-114P-PS
G5L-114P-PS
OMRON
OMRON
K
K
4
3
YS101790
K2
UL
5A250VAC
5A250VAC
UL
CONTACT:
CONTACT:
24VDC
24VDC
G5L-114P-PS
G5L-114P-PS
OMRON
OMRON
UL
UL
5A250VAC
5A250VAC
CONTACT:
CONTACT:
24VDC
24VDC
G5L-114P-PS
G5L-114P-PS
OMRON
OMRON
K
K
4
3
S101790
PU1
O1
R5
C2
R1
PU2
R6
R7
R8R9
D5
SLO
MODULRIOBD.
D1
C3
R2
PU3
D2
C4
R3
PU4
D3
C5
R4
C1
D4
C
U
Q
X
2
LM358
2
1
C7
4
K1
K2
K3
RN1
K4
K1
K2
K3
RN1
K4
4ANALOG IN MOD. I/O BD.YS101784
R9
R
R
1
1
6
R18
C1
P1
ULN2803A/
PHILIPS
T LHAANI D
U1
C
74HC04N
2
U2
PCF8574P
CX3
U3
C1
P1
ULN2803A/
PHILIPS
T LHAANI D
U1
C
74HC04N
2
U2
PCF8574P
CX1
PCF8591P
R10R11R12
8.29”
CX3
U3
P1
U1
T LHA
PHILIPS
ANI D
P4
P4
8.96”
0.28”
4.24”
4.0”
Figure 2-3:
WHP Loop Controller
2-6Installation and Wiring
WattMaster WHPSection 2
R (24 VAC By Others)
WHP Loop Controller Expansion Board
WHP Loop Controller Expansion Board
R10
R11
Fire Alarm Contact (N.C.)(See Note 5)
4.)When a Water Pressure Transmitter
Required VA For T ransformer
A
A
A
A
A
Y
4
4
4
2
4
V
A
C
G
N
D
24 VAC
24 VAC
Heating/Cooling #4
Heating/Cooling #4
Heating/Cooling #3
Heating/Cooling #3
Heating/Cooling #2
Heating/Cooling #2
Heating/Cooling #1
Heating/Cooling #1
RLY1D1D2D3D4D5CX3
E
C3C
2
PHILIPS
C
PALC
T
Y
T
N
A
GND
24VAC
L
D16
R6C9S
R11U1
1
D13
C
6
V
M
T
C
R10
V
C18
N
U
CX8U9X1R7D10
R13D
U
U12U
PJ3
EXPANSION
R
R
R
C15R19R15C
D18D1
7
0-5VDC0-1VD
C
C11
RN4
1
RN3
RN2
1
RLY2RLY3RLY4RLY
5
(
Return Water
Temp Sensor
See Note 4
Optional Pressure
Transmitter
Manual
Reset
Pump VFD
Optional
Modulating Heat
Notes:
1.)24 VAC Must Be Connected So
2.)All Wiring To Be In Accordance
3.)All Communication Wiring To Be
Connect T o Next WHP Controller
And/Or MiniLink On Local Loop
Local Loop RS-4 85
9600 Baud
Outside Ai r
Temp. Sensor
Supply Water
Temp Sensor
Proof of
Flow
Phase
Loss
+
+
That All Ground Wires Remain
Common.
With Local And National Electrical
Codes And Specifications.
2 Conductor Twisted Pair With
Shield. Use Belden #82760 Or
Equivalent.
TB1
COMM
T
SHLD
R
LD6
COMM
LD7
PWR
LD8
LED1
LD9
LED2
R1
INPUTS
+VDC
AIN1
AIN2
AIN3
AIN4
AIN5
GND
GND
AOUT1
AOUT2
AIN7
GND
PJ1
TB3
PRESSURE
SENSOR
CX5
U7
RV1
VREF ADJ
C21
RN1
1
1
+VREF
TEST POINT
CX1
CX2
U2
U1
U5
RS-485
RAM
COMM
HH
U6
C1
P1
5.11V
EWDOG
R28
ADD
DDRESS
1
RN5
C10
C12
C17
R26
2
4
PU1
8
D6
16
PU2
32
D7
TOKEN
ETWORK
PU3
SW1
PU4
D9
PU5
D11
PU7
D14
JP1
U13
14
CX13
D15
U15
C20
CX15
PJ2
Request to Run Contact (N.O.)
X2
22
24
25
U3
PROM
UC-5R PLUS
S101816 RE V. 2
10
14
T'STAT
X4
U4
1 MEG)
X6
CX10
C7
CX12
CX14
1
12
C1
D19
C19
7824CT
R1
R2
N.C. Pilot Duty Relays
COM1-3
R1
R2
R3
R4
R5
COM4-5
8
E5090NPB3192
0PS
993
R27
V6
(By Others)
V1
V2
V3
R1
Compressor Enable
R2
Main Pump
R3
B2
V4
V5
N.C. Pilot Duty Relays
(By Others)
Standby Pump
Alarm Indicator
MC34064A
13
16
Loop Controller = 8VA Min.
B4
GND
POWER
24VAC
Line Voltage
See Note 1
R4
R5
R6
R7
RLY IO BD.
YS101790
R8
R9
YS101790
RLY IO BD.
IN1
IN2
IN3
IN4
GND
OUT1
Relay Contacts
(By Others)
ANALOG IN MOD I/O BD.
S101784
Is Used, a 250 Ohm Resistor is
Installed Between AIN3 & GND and
The Pull Up Resistor PU3 is
Removed.
5.)If a Fire Alarm Contact is Not
Connected to AIN1 on The Analog
Expansion Board, Then a Jumper
Must Installed Between AIN1 and
GND.
Figure 2-4:
WHP Loop Controller Wiring
Installation and Wiring2-7
Section 2WattMaster WHP
Warning: Polarity is very important when connecting power to the controllers!
The grounded side of the control transformer must be connected to
the terminal labeled GND on the controller. If a single transformer is
used to power more than one controller you must connect GND-toGND and 24VAC-to-24VAC on each controller. Failure to
observe polarity will result in damage to one or
more components in your system.
The WHP Loop Controller requires the following electrical connections:
Tip: After making all electrical connections it is advised to unplug all terminal blocks
on the WHP Loop Controller until you are ready to begin the checkout
procedure. This may help to prevent damage if wiring errors occur elsewhere in
the system during installation or start-up.
2-8Installation and Wiring
WattMaster WHPSection 2
GND
24VAC
L
R6C
S
R11
U11D1
3
C16V
T
C
R10
V
R7D
1
0
R13D
C7C
U
C
U12U
C
C
X
D
C
TOKEN
NETWORK
Note:
The Power To The Controller Must Be Removed And
Settings In Order For Any Changes To Take Effect.
Disconnect All Communication Loop Wiring From The
Controller Before Removing Power From The Controller.
WHP Loop Controller
Addressing
The WHP Loop Controller must be set for address #30. See address setting instructions
for the WHP Loop Controller that follow. A maximum of 29 WHP Controllers are
allowed on the loop that contains the WHP Loop Controller. All other loops may have 30
WHP Controllers.
This Switch Should Be
In The OFF Position
As Shown
ADDRESS ADD
Controller
Address Switch
INPUTS
+VDC
AIN1
AIN2
AIN3
AIN4
AIN5
GND
GND
AOUT1
AOUT2
AIN7
GND
PJ1
TB3
PRESSURE
SENSOR
EXPANSION
1
2
4
8
16
32
Reconnected After Changing The Address Switch
Address Swit ch Must Be Set For
Address 30 As Shown
ADD
ADDRESS
RN5
PU1
D6
PU2
D7
PU3
D8
PU4
D9
PU5
D11
C10
PU7
D14
C12
D15
C17
C20
R26
PJ2
1
2
4
8
16
32
TOKEN
NETWORK
SW1
0-5
0-1
VDC
VDC
JP1
U13
C14
X13
U15
C15
X15
PJ3
X10
10
C11
2
R15
X14
R19
14
R22
R24
R25
D18
D17
Caution
Reconnect Power And Then Reconnect Communication
Loop Wiring.
X12
C18
R1
1
12
C1
19
C19
R2
9
13
R27
D16
V6
POWER
B4
Figure 2-5:
Installation and Wiring2-9
WHP Loop Controller Address Switch Setting
Section 2WattMaster WHP
5
OE291 Stainless Steel Thermowell
Butt Splice Leads To 24 Gauge
Supply & Return Water
Temperature Sensors
Sensors for monitoring supply and return water temperature are available in two main
types, fluid immersion temperature sensors (See Figure 2-6) and strap-on sensors (See
Figure 2-7). Both are 0-10000 ohm thermistor type sensors. The fluid immersion sensor
generally has better accuracy than the strap-on type but either is suitable for typical water
source heat pump temperature requirements. The fluid immersion type sensor requires
that a thermowell be installed in the pipe and the strap-on type, as its name implies,
simply straps around the outside of the pipe. The fluid immersion sensor requires that the
pipe be at least 4” in diameter in order to accept the thermowell . The strap-on type sensor
is adjustable for use on 1/2” to 6” or larger diameter pipe.
The fluid immersion sensor is provided with a 4” long stainless steel thermowell. It has
½” MPT external threads and ½” FPT internal threads. A ½” FPT fitting to accept the
thermowell must be provided by others in the pipe to be monitored, for connection of the
thermowell. The thermowell is screwed into the ½” FPT fitting installed by others in the
pipe and the sensor probe is then screwed into the ½” FPT fitting on the thermowell.
Leads Are Non-polarized.
Wire Minimum. Connect Leads
To "Analog In" And "Ground"
At Controller.
1/8-27 NPT External Thread
5.50
OE230 Duct Sensor
The OE230 Duct Sensor Threads In to The OE291 St ainless
Steel Thermowell. The OE291 Thermow ell Threads Into A 1/2”
FPT Elbow or Tee in the Water Piping of the Water Coil
Where You Wish to Measure the Water Temperature. The
Pipe must be a minimum of 4” Diameter or an Extende d Tee
and Bushing Configuration Must be Used to Accommodate the
Length of the Thermowell Assembly.
Figure 2-6:
Duct Sensor with Thermowell
1/8-27 NPSM Internal Thread
1/2" NPT External Thread
0.
3.25
4.94
5.13
2-10Installation and Wiring
WattMaster WHPSection 2
Thermal Mastic Strip
Supply Or Return
The strap-on type sensor has a brass housing that senses the water temperature through
contact with the exterior surface of the pipe. The sensor should be mounted in contact
with the underside of the pipe in order to insure accurate temperature readings. The
sensor assembly is secured to the pipe by using the supplied wire ties to wrap and secure
the sensor to the pipe. Thermal conductive compound is also supplied to insure a good
thermal connection with the pipe. The sensors are supplied with 3 foot long wire leads.
Sensing Element
(Supplied)
Figure 2-7:
Wire Tire
(Supplied)
(Supplied)
Strap-On Water Temperature Sensor
Water Pipe.
Installation and Wiring2-11
Section 2WattMaster WHP
Closure Plug
0.21" Dia. x 0.73
4
.
5
0”2
.25
”
Front View
Side View
Back View
Mounting Tab
& Screws - Typ.
2.70”
1.13”
2.30”
Outside Air Temperature
Sensor
The outside air sensor must be located where it will not be affected by direct sun or heat
producing equipment. Mounting under the eve of a roof is often a good choice.
Caution: Complaints of inaccurate outside sensor readings are very common and
can almost always be shown to be the result of poor sensor location.
Note: All temperature sensors supplied with the system utilize the same thermistor
type sensing element. For troubleshooting sensor problems refer to the
TEMPERATURE SENSOR RESISTANCE CHART at the end of Section 4.
Gasketed Cover
Figure 2-8:
Cover
Mounting
3.00”
3.00”
Screw - Typ.
Sensor Tube
Outside Air Temperature Sensor
Mounting Tab
& Screw - Typ.
Closure Plug
Lg. Slot - Typ.
2-12Installation and Wiring
WattMaster WHPSection 2
STANDARD WALL MOUNT
120/24 VAC POWER SUPPLY
( MAY ALSO BE POWERED FROM 24VAC )
(NETWORK TERMINALS ONLY)
YS101716 REV. 1
SYSTEM MANAGER POWER SUPPLY
GND
24VAC
POWER
LOOP
A
A
T
3
A
4
Y
CPU
A
A
T
3
A
4
Y
CPU
A
A
A
A
Y
4
4
4
2
4
V
A
C
G
N
D
U6
C1
U2
U3
U4
V1
V2V3V5
V4
L1
R6
C9
6
M
U8
U9
C7
CX10
CX12
CX14
CX13
X2
INPUTS
+
A
A
A
A
A
RS-485
S
COMM
COMM
U1
COMM
LED1
LED2
R1
U7
VREF ADJ
TEST POINT
C
C
CX15
CommLink II Interface
The CommLink II Interface provides for communications between the MiniLink
communication interfaces installed on the system. The CommLink II is required for
proper communications, even if a PC is not used. Locate the CommLink II near the
computer or modem if they are installed on the system. The cable connections between
the CommLink II and the computer or modem should be kept to less than twenty-five
feet. The CommLink II comes complete with computer and modem cables, and a plug-in
power supply.
03/31/04 03:38PM WED
OCCUPIED
COMPUTER
(OPTIONAL)
NO ALARMS
COMMUNICATIONS
T
SHLD
R
RS-485
SYSTEM MANAGER
COMM LINK II
INTERFACE
(MULTIPLE LOOP)
UNIT COMES WITH
Remote Link
(OPTIONAL)
2K
COMM
TSHLDR
LD4
C21
RN1
1
TB1
T
HLD
R
CX5
LD6
LD7
1
PWR
LD8
RN3
LD9
+VREF
RV1
VDC
RN5
IN1
IN2
IN3
IN4
IN5
C10
GND
GND
AOUT1
AOUT2
AIN7
C17
GND
PJ1
TB3
PRESSURE
SENSOR
GND
24VAC
NETWORK
T
R
SH
T
R
SH
EXPANSION
D1
CX1
CX2
CX3
CX4
RLY1
D2D3D4D5
RLY2RLY3RLY4RLY5
U5
HH
P1
5.11V
EWDOG
R28
ADDRESS
PU1
D6
PU2
D7
PU3
D8
PU4
D9
PU5
D11
PU7
D14
C12
D15
C20
R26
PJ2
OM1-3
PAL
R1
1
EPROM
RAM
SW1
0-5
VDC
U13
U15
R2
TUC-5R PLUS
R3
(1 MEG)
YS101816 REV. 2
R4
RN2
R5
OM4-5
TB2
CX6
C2
X1
PHILIPS
C3
1
ADD
1
2
RN4
4
NE5090NPB3192
0PS
8
CX8
16
32
TOKEN
NETWORK
U10
R7
D10
R10
D13
D12
C11
993
R11
R13
0-1
U11
VDC
MC34064A
JP1
SC1
C13
R15
U12
C14
C16
R19
U14
TB4
C15
D19
GND
R22
R24
R27
D16
R25
V6
D18
D17
POWER
C19
C18
7824CT
24VAC
PJ3
VR2
VR1
T'STAT
RLY IO BD.
RLY IO BD.
IN1
IN2
IN3
IN4
GND
AOUT1
YS101790
YS101790
ANALOG IN MOD I/O BD.
S101784
REC.
12V
AIN
AINAIN
AIN
GNDGND
PRESSURE
SENSOR
COMM
TSHLDR
LD4
REC.
12V
1AIN2AIN3AIN4AIN5GND
GND
PRESSURESENSOR
TO OTHER MINILINKS
8K
RAMEPROM
85COMM
COMM
EST
DDRESSADD
IN1
23
EWDOG
45
0-5
VDC
OUT
S101564
COMM
IN
OUT
S101564
GND
0-1
VDC
24VAC
2K8K
RAMEPROM
85
COMM
EST
DDRESS ADD
EWDOG
0-5
VDC
GND
0-1
VDC
24VAC
TO OTHER WHP CONTROLLERS
RELAY
OUTPUTCOM1-3OUT
1
OUT
2
OUT
3
OUT
OUT
4
OUT
5COM4-5
4-5
PWR
RELAY
OUTPUTCOM1-3OUT
1OUT
2OUT
3OUT
OUT
4OUT
5COM4-5
4-5
PWR
Figure 2-9:
CommLink Interface Wiring
Installation and Wiring2-13
Section 2WattMaster WHP
2
EWDOG
DIAGNOSTIC BLINK
RAM SIZE
24 VAC Common for Inputs 1 - 3
Aux. Heating or Cooling (Cool 2)
24 VAC Common for Inputs 1 - 3
Mounting Backplate
WHP Controller
The WHP Controller may be installed in any convenient protected location. Observe the
recommended environmental limitations for the WHP Controller when selecting a
installation location. The environmental limitations are a temperature range of 10°F to
149°F, and a maximum operating humidity of 90% RH non-condensing.
The WHP Controller may be mounted by fastening to a flat surface through the mounting
plate. The unit is mounted by four (4) screws in the corners. Select the correct screws or
other fasteners for the type of mounting material being utilized.
Connection To
AUX Terminal is Reqd
Only When Sensor
Is Specified With
Slide Adjust Option
Dirty Filter
Alarm Contact
Thermowell
Or Surface Mount
Temp Sensor
(Leaving Water Temp)
Optional Features
Figure 2-11:
Lockout
WHP Controller Wiring
(UP TO 30 UNI TS P E R LOCAL LOOP)
LOOP CONTROLLER CONNECTED.
THE LOOP CONTROLLER ADDRESS
CAUTION!
WHP CONTROLLERS
SET BETWEEN 1 AND 30
EXCEPT ON THE LOOP WITH THE
IS 30, WHICH ALLOWS FOR ONLY
29 WHP CONTROLLERS ON THIS
LOCAL LOOP.
Warning: Polarity is very important when connecting power to the controllers!
The grounded side of the control transformer must be connected to
the terminal labeled GND on the WHP Controller. If a single
transformer is used to power more than one WHP Controller you
must connect GND-to-GND and 24VAC-to-24VAC on each WHP
Controller. Failure to observe polarity will result in
damage to one or more components in your
system.
Warning: Use extreme care not to damage any of the electronic components
while mounting the backplate. Mark the holes then remove the WHP
Controller from the backplate before drilling.
Do not allow metal shavings to fall onto the circuit boards.
Installation and Wiring2-15
Section 2WattMaster WHP
The WHP Controller requires the following electrical connections:
18 Gauge minimum unless otherwise noted.
-Communications Loop ...................................... 2 Conductor twisted pair with shield
(WattMaster Cable, Belden #82760 or equivalent)
-Discharge Air Temperature Sensor..................................(24 ga. Min.) 2 Conductors
-Room Air Temperature Sensor...........(24 ga. Min.) 2 Conductors for standard sensor
3 Conductors for sensors with setpoint adjustment
-Outside Air Temperature Sensor.......................................(24 ga. Min.) 2 Conductors
-WHP Unit Control Wiring .........................................................(24 ga.Min.) 24 VAC
Fan- ON/OFF
Rev Valve-ON/OFF
Compressor-ON/OFF
Heat Pump Reset
Aux. Heating or Cooling
Tip: After making all electrical connections it is advised to unplug all terminal blocks
on the WHP Controller until you are ready to begin the checkout procedure. This
may help to prevent damage if wiring errors occur elsewhere in the system
during installation or start-up.
2-16Installation and Wiring
WattMaster WHPSection 2
IN ORDER FOR ANY CHANGES TO TAKE EFFECT.
POWER AND THEN RECONNECT THE COMMUNICATIONS
WHP Controller
Addressing
IGNORE ANY MARKINGS
OR NUMBERS ON THE SWITCH
To determine the boards address,
add the values of all the switches
which are toggled down in the
NOTE:
USE THE CHART!
direction of the arrow
Figure 2-12:
Installation and Wiring2-17
WHP Controller Address Switch Setting
NOTE:
ADDRESS 30 CANNOT BE USED
ON THE LOOP THAT HAS THE WHP LOOP
CONTROLLER A TTACHED. ADDRESS 30
ON THAT LOOP IS RESERVED FOR THE
WHP LOOP CONTROLLER.
CAUTION:
YOU MUST POWER DOWN THE CONTROLLER
AFTER CHANGING THE ADDRESS SWITCHES
ALWAYS REMOVE THE COMMUNICATIONS LOOP
PRIOR TO DISCONNECTING POWER. RECONNECT
LOOP TO THE CONTROLLER.
Section 2WattMaster WHP
16
32
The Power To The MiniLink Must Be Removed And
Reconnected A fter Changi ng The Addre ss Switch
Settings In Order For Any Changes To Take Effect.
ADD
The Address For Each MiniLink
Must Be Unique To The Other MiniLink s
On The Network Loop. Loop #1 MiniLink
T
O
Connect To Next
Equivalent.
MiniLink Addressing
MiniLink And /Or
CommLink On
Network Loop
Network Loop
RS-485
19200 Baud
All Communication Loop
Wiring Is Straight Through
T
T
T
Note:
T
SH
SH
R
R
SH
SH
R
R
Local Loop
RS-485
9600 Baud
Connect To Next
Controller or
System Manager
Caution!
The MiniLinks Must Have Address Switches Set Between 1
And 30 (Up To 30 MiniLinks Are Allowed Per WHP System
System). The MiniLinks Should Be Addressed In
Consecutive Order Starting With Address #1. Address #1
Must Be Present On The Loop For The System To Function.
MiniLink Communications Interface
ADD
1
NETWORK
LOOP
2
4
8
16
32
FF >
T
SH
R
SH
R
1
2
4
8
24VAC
GND
24VAC
Required VA For Transforme r
MiniLink = 6VA Min.
See Note 1.
These Switches Must B e
In The OFF Positio n
As Shown
Line Voltage
Caution:
Disconnect All Communication Loop Wiring
From The MiniLink Before Removing Power
From The MiniLink. Reconnect Power And Then
Reconnect Comm un i c at io n Loop Wiring.
Notes:
1.)24 VAC Must Be Connected So
That All Ground Wires Remain
Common.
2.)All Wiring To Be In Accordance
With Local And National Electrical
Codes And Specifications.
3.) All Communication Wiring To Be
2 Conductor Twisted Pair With
Shield. Use Belden #82760 Or
Figure 2-13:
MiniLink Address Switch Setting
Address Switch Shown Is
Set For Addr ess 1
Loop #2 MiniLi nk Should Be Addressed
MiniLink
Address Switch
Should Be Addressed As #1
As #2 Etc..
Address Switch Shown Is
Set For Addr ess 4
2-18Installation and Wiring
WattMaster WHPSection 2
A
A
Y
ADJUSTABLE
ROOM SENSOR WITH OVERRIDE
WHP CONTROLLER
SETPOINT
Room Sensors
The room sensor uses a patented flush mount design to isolate the temperature sensing
element from the housing which mounts flush with the wall surface.
Room sensors should be located on an inside wall away from direct sunlight or heat
producing equipment such as computers, copiers, etc. Such devices can adversely affect
the accuracy of the sensor.
Although the sensor eliminates most of the effects of thermal coupling to the walls, try to
avoid walls which retain large amounts of thermal energy (such as marble or steel). Walls
containing either cold or warm air currents should also be avoided whenever possible.
Avoid locating the sensor in dead air areas of a room. This will result in slow response to
temperature changes in the space.
Mount the sensor approximately 50-60 inches from the floor for best results.
The room sensor is designed to mounted vertically in a standard 2 by 4 inch electrical
box. The sensor may be mounted directly into the drywall where electrical codes do not
require low voltage wiring to be enclosed in conduit. See enclosed sheet for dimensional
and installation data.
Tip: Be careful when cutting the hole for the sensor or the plastic bezel of the sensor
may not completely cover the opening.
AND ADJUSTABLE SETPOINT
PRESSURESENSOR
12V
AIN
AIN
AIN
AIN
GND
GND
IN
12
3
4
5
OUT
S
W
A
R
M
E
R
C
O
O
OVR
L
E
R
TMP
GND
AUX
SETPOINT
OVERRIDE
ONLY REQUIRED WHEN
USING ADJUSTABLE
Figure 2-14:
Room Sensor Wiring
Installation and Wiring2-19
Section 2WattMaster WHP
0.25“
2.75“
2.00“
W
s
Handy Box (By Others)
4.50“
2.50"
Connect the terminal labeled GND on the zone sensor to the terminal labeled GND on the
WHP Controller Analog Input terminal block. Connect the terminal labeled TMP on the
zone sensor to the terminal labeled AIN 1 on the WHP Controller Analog Input terminal
block. If the zone sensor has a setpoint adjust slider, then connect the sensor terminal
labeled AUX to the WHP Controller AIN 2 terminal block.
Tip: If sensors must be installed on walls which are solid and cannot be penetrated,
surface mounted boxes and raceway can be purchased from your local electrical
distributor.
3.25“
Figure 2-15:
2.75“
W
A
R
M
E
R
C
O
O
L
E
R
Room Sensor
0.88“
TMP
GND
AUX
OUT
all Cut-Out Dimension
When Sensor Is To Be
Mounted Without
2-20Installation and Wiring
WattMaster WHPSection 2
Mounting Plate
1/4" Hex Head Sheet Metal Screws
Drill 5/16" Hole In Ductwork For Probe
Leads Are Non-polarized.
Supply Air Temperature
Sensor
The supply air temperature sensor should be located in the duct, as close to the rooftop
unit discharge as possible for best response.
Locate the sensor in the center of the widest part of the duct. Use the supplied template
and a 5/16" drill to make a hole for the sensor. Install the gasket over the probe and
mount securely to the duct using the supplied sheet metal screws. Be sure the gasket is
compressed to provide an air tight seal.
For best accuracy, apply insulation on the outside of the duct, over the sensor. This will
help prevent thermal gradients from affecting the sensor.
Thread
Together
Butt Splice Leads To 24 Gauge
Wire Minimum. Connect Leads
To "Analog In" And "Ground"
At Controller.
4.0"
3/4"
5-1/2" (OE230)
11-1/2" (OE231)
Mounting Plate
Gasket
Adhesive Backed Drill Guide
Mounting Template
Duct Work
Figure 2-16:
Installation and Wiring2-21
Supply Air Temperature Sensor
Section 2WattMaster WHP
5
OE291 Stainless Steel Thermowell
Butt Splice Leads To 24 Gauge
At Controller.
Thermal Mastic Strip
Supply Or Return
Leaving Water
Temperature Sensors
The leaving water temperature sensor (optional) when used should be located on the
leaving water piping close to the water source heat pump unit. Either a thermowell type or
a surface mount sensor may be used depending on job requirements.
Leads Are Non-polarized.
Wire Minimum. C onnect Leads
To "Analog In" And "Ground"
1/8-27 NPT External Thread
5.50
OE230 Duct Sensor
The OE230 Duct Sensor Threads Into The OE291 Stainless
Steel Thermowell. The OE291 Thermowell Threads Into A 1/2”
FPT Elbow or Tee in the Water Piping of the Water Coil
Where You Wish to Measure the Water Temperature. The
Pipe must be a minimum of 4” Diameter or an Extended Tee
and Bushing Configuration Must be Used to Accommodate the
Length of the Thermowell Assembly.
Tuesday Operations 04/13/04 09:15 AM Outdoor Air 58.7°F
The Water Source Heat Pump System Manager i s the operator’s interface to the status
and setpoints of any WattMaster Water Source Heat Pump (WHP) component on your
communications loop. With the System Manager, you can view any temperature or output
condition and change any setpoint to fine tune the operations of the total system. All
keypad operations are simple and straight-forward, utilizing non-cryptic plain English
messages. The System Manager automatically detects the type of unit that has been
selected, and displays the appropriate status and setpoint screens. The attractive plastic
case of the System Manager allows for placement in any area of your building.
The remainder of this document will lead the user through the system menus and keypad
operation.
All user functions are accessed by pressing the Menu button. Once the button is pressed,
the Main User Menu is displayed.
Programming3-1
Section 3WattMaster WHP
System Manager Layout
Heat Pump v2.11
Wednesday Operations
7/21/04 04:35 PM
Outdoor Air 85.6
°
Keypad Functions
The System Manager keypad is labeled either numerically or as to actual function for that
key. Below is a summary of the labeled keys and their functions.
MENU
ESC
CLEAR
ENTER
DEC
MINUS
UP/DOWN
Arrows
LEFT/RIGHT
Arrows
This key is used to gain access to the first menu, and the user will be
notified, on the LCD, if any subsequent use of the key will be
required for further access.
The ESCape key allows the user to abort what they are doing or exit
back to previous menus. Also, anytime you want to leave the system
unattended you should press the ESC key until the Main Screen
appears.
If you make a mistake while entering setpoint data, you can clear the
bad data from the display by pressing the Clear key.
Use the Enter key to close out a data entry. It can also be used to
advance to the next field or screen.
If entering a setpoint that requires a decimal point, press this key
where the decimal is located while entering the value.
If you need to enter a negative value, you must press the Minus key
before entering the digits for that value.
Use these keys to step forward or backward through Status Screens or
Setpoint Data Fields.
If the screen prompts you to use these keys, it is used normally to
toggle modes of operation.
3-2Programming
WattMaster WHPSection 3
System Manager LED Indicators
There are two LED indicators located on the right hand side of the System Manager.
The top LED indicates an Alarm condition if the Manager detects an alarm condition
while polling the system.
The bottom LED is active during actual communications or packet transfers. This LED
will normally “flicker” and not remain on constantly.
Main User Menu
1) View Status Only
2) View Alarms MENU) Setpoints ESC) Main Screen
1) View Status OnlyFor quick access to an
individual heat pump or the
loop controller, select this menu
item. No passcode is required to
access the status of any unit
installed on your system.
2) View AlarmsIf the System Manager has been
configured for Alarm Polling,
the user can select this item to
get a list of unit addresses that
are currently in alarm. If an
alarm exists, the Alarm LED
will be active on the right side
of the panel.
MENU) SetpointsIf you are a Level 2 user, all system
setpoints are available to you.
These setpoints are accessed via
this Menu button.
ESC) Main ScreenWhen you have finished viewing
the system you can exit this menu
and return to the Main Screen by
pressing the ESC button.
Programming3-3
Section 3WattMaster WHP
Heat Pump Status
Screens
View Status Only
Status Only View [ Enter Unit ID# ] Selected Unit: 101
By selecting the View Status Only menu item, you can
access any heat pump or the loop controller and read all
available temperatures, outputs, and operating conditions
for the selected unit. No passcode is required to access
these status screens, and no setpoints are available to the
user from these screens. To access a unit, enter the Unit ID
you wish to view. The Unit ID is actually two separate
numbers, combined into one value. The first part of the
number contains the Loop Address at which the zone is
located. The second part of the number contains the actual
Board Address.
EXAMPLE:You would like to view the 3rd heat pump
on the 5th loop. Enter 503 as the Unit ID
You would like to view the 12th heat pump
on the 24th loop. Enter 2412 as the Unit ID
3-4Programming
WattMaster WHPSection 3
If you selected menu item #1 View Status Only and you entered the Unit ID of an
installed WHP Controller, the following Status Screens are available.
Current Zone Temperature
Current Cooling Setpoint ( CSP ) and Heating
Setpoint ( HSP )
Status Screen #2
WSHPRV 1 V2.03 Supply Air.:xxx.x°F Water Temp.:xxx.x°F Outdoor Air:xxx.x°F
Line 4 -
Line 2 Line 3 -
Line 4 -
Effect of optional Sensor Slide Adjustment on the
current operating setpoints.
Current Supply Air Temperature
Current Leaving Water Temperature if Sensor is
installed.
Current Outdoor Air Temperature.
Programming3-5
Section 3WattMaster WHP
Status Screen #3
WSHPRV 1 V2.03 Occupied Mode Fan Status...: ON Operations Enabled
Status Screen #4
Line 2 -
Line 3 -
Line 4 -
Current Operating Status
Unoccupied Mode
Occupied Mode
Pushbutton Override
Forced Occupied
Forced Unoccupied
Forced Fan Only Mode
Current Fan Status
Fan Start Delay!
ON
OFF
Current Enable Status from Loop
Controller
Operations Disabled
Operations Enabled
WSHPRV 1 V2.03 Compressor...: ON Reverse Valve: OFF Aux / Stage#2: OFF
Status Screen #5
WSHPRV 1 V2.03
Cooling Mode
Line 2 Line 3 Line 4 -
Line 2 -
Line 3 Line 4 -
Current Compressor ON/OFF Status
Current Reversing Valve ON/OFF Status
Current Status of Relay #5. Operation
depends on how the user configures this
output.
Current HVAC Operating Mode
Neutral Mode
Cooling Mode
Heating Mode
Reserved for future option.
Reserved for future option.
3-6Programming
WattMaster WHPSection 3
Status Screen #6
WSHPRV 1 V2.03 Space Temp Sensor OK Filter OK Cooling Failure
Line 2 -
Bad Space Sensor
Hi Space Temp Alarm!
Lo Space Temp Alarm!
Space Temp Sensor OK
Line 3 -
Dirty Filter Alarm
Filter OK
Line 4 -
Cooling Failure!
Heating Failure!
Note: If no alarms exist, then the screen displays the message shown for No Alarms!
If ANY alarm exists then the three lines display one of the messages shown
above.
The Cooling Failure and Heating Failure alarms are generated as follows:
As the unit enters the cooling mode, the current Supply Air Temperature reading
is stored in memory. After 10 minutes, if the temperature hasn’t changed by 5°F a
Cooling Failure alarm is generated.
A Heating Failure is generated in the same manner, only during the heating mode
instead of the cooling mode.
The Hi Space Temp and Lo Space Temp Alarms are generated as follows:
If the space temperature gets 5°F above the cooling setpoint, a Hi Space Temp
Alarm is generated. If the space temperature gets 5°F below the heating setpoint,
a Lo Space Temp Alarm is generated.
Programming3-7
Section 3WattMaster WHP
View Alarms
Alarm Address Locations
SYSTEM ALARM STATUS Alarm @ Unit ID 118
Alarm Clearing
SYSTEM ALARM STATUS Clear Alarms? YES To Change Response Use Left/Right Arrow
The System Manager can be programmed to poll all the
units on your heat pump system for alarm information. This
allows the centrally located System Manager to display an
Alarm Indicator whenever an alarm condition exists
anywhere on your system. The actual alarms are not
displayed on this screen, only the Unit ID where the alarm
is located. The example screen shows that a unit at location
118 has experienced an alarm condition. This alarm may or
may not be current, as the System Manager latches the
condition. This makes it possible to determine if any
intermittent alarm conditions have occured. To find out
what the alarm is, if it is still current, access the status
screens for the Unit IDs that are displayed on the SYSTEM
ALARM STATUS screens.
If all the alarm conditions have been corrected at the
individual units, you can clear these alarms from the
System Manager on the following screen. Use the
Left/Right arrow keys to select the YES/NO response
desired. If you clear the alarms, but some still exist, the
System Manager will show an alarm indication, when the
affected unit is polled again.
3-8Programming
WattMaster WHPSection 3
Menu Setpoints
Full Setpoint Access
1) Set Time & Date
2) Access Units
3) New Passcodes
4) Rebuild Alarm Map
If you selected the Menu key from the first menu screen you
can access all setpoints available from any unit on your system.
You must be a Level 2 user to access these setpoints. If you
haven’t already been asked to enter the passcode, you will be
asked before the Full Setpoint Access menu is displayed. This
prevents the casual user from being able to affect the operation
of your heat pump system.
Set Time & Date
The System Manager has its own built in Real Time Clock. It broadcasts this time once a
day, at midnight, to synchronize all of the WHPs on your system. Although the times are
displayed on the Main Screen in a standard 12-hour format, they are programmed using
the 24-hour Military format. Once the time has been entered, it is also broadcast
immediately to all other units on the system. That means that you only need to program
the System Manager time to set the Real Time Clocks for all units on your system. In
order for the System Manager to broadcast the time and date to all controllers, they must
be powered up and communicating.
Programming Time
Program Time/Date Day (Sunday=0): 1 Enter Hr. (0-23): 9 Enter Minutes : 53
Programming3-9
Day-Enter the Day of the Week (0 to 6) with
Sunday = 0
Hours (Hr)-Enter Hours in 24-Hour Military Format
(1700 = 5:00 PM)
Minutes-Enter the Minutes (0 to 59)
Section 3WattMaster WHP
Programming Date
Program Time/Date Month (1-12): 4 Day (1-31): 18 Year (00-99): 04
Month-Enter the Month (1 to 12)
Day-Enter the Day of the Month (1 to 31)
Year-Enter the current Year with 2 digits (00
to 99)
Daylight Savings Adjustments
Daylight Savings Adjustments Enabled
Use Left/Right Arrow
If your area of the country requires Daylight Savings changes,
you can enable the System Manager to automatically reset its
own clock during the Daylight Savings changeover. If you
enable this operation, it knows to changeover the first Sunday
in April and then switch back the last Sunday in October. No
other programming is required for this function.
Use the Left or Right arrow keys to toggle the second line of
the display between Adjustments Enabled and AdjustmentsDisabled.
3-10Programming
WattMaster WHPSection 3
New Passcodes
Programming Passcodes
Enter New Passcode
Level 1....: XXXX
Level 2....: XXXX
[Must Be 4 Digits]
The System Manager has two levels of passcode.
Level 1 users are limited to viewing Setpoints and Alarms only.
Level 2 users have complete system access. Any status or
setpoint field can be read or reset from WHP System Manager.
The default passcode is “1111” for level 1 and “2222” for level
2. If you need to change these defaults you can enter any 4 digit
number between 1000 and 9999.
If you “forget” the passcode you programmed, you can still
access the system with a built in backdoor code. This backdoor
code is “9288” and is not programmable. It is not recommended
that you give out this backdoor code since it would allow the
user access without regard to the standard programmable
passcode that most operators should be using.
The actual digits in your passcodes are never displayed. An "X"
is used as a place holder for each digit entered. Passcodes must
always be four digits in length.
Programming3-11
Section 3WattMaster WHP
Rebuild Alarm Map
Rebuilding Screens
Clearing Old Map
....................
................
Build New Map?
(ESC = NO)
Building New Map Loop: 1 Unit: 1 Dec) Go To Next Loop ESC) Abort Process
Alarm Unit Map Built Press Any Key To Continue
If you would like the LED Alarm Indicator to function on the
front of your System Manager, you must enable Alarm Polling
by building an Alarm Map. This map keeps track of which
units exist on your communications loop so the System
Manager will poll only those units. That means you will need
to rebuild this map anytime units are added or removed from
your system. It also means you can disable alarm polling. To
do this, disconnect the RS-485 communications plug from the
back of your Comm Link II. Then, select the Rebuild Alarm
Map menu. The System Manager will not find any units to poll
for alarms since none are connected. This is useful during
building startup, when you don't want nuisance alarms
bothering you.
The screen will display each address it is testing and if a unit is
found at that address. If you don't want to wait for the System
Manager to check for all 30 loops, you can press the ESC key
as soon as the number of loops on your system are exceeded
and the test will conclude. All units found up to that point will
be saved in memory.
The System Manager does not rebuild this map
automatically on powerup! You must do this manually. This
rebuild need only be performed one time, when all units are up
and running. It is not a regular requirement. As mentioned
above, only when the number of units connected changes
should the alarm map be rebuilt.
3-12Programming
WattMaster WHPSection 3
A
of
Heat Pump Setpoints
Heat Pump Setpoint Menu
1) WHP Setpoints
2) WHP Schedules
3) Reset Pumps ESC) To Exit
From the main menu screen select MENU on the keypad,
select MENU again for Setpoints. Then select “Access Unit s”
(keypad #2) and finally enter the loop and zone number for the
desired unit.
s the screen above shows, there are three areas
programming available for each WHP Controller. Menu item
#1 accesses all the standard temperature and configuration
settings for the heat pump. Menu item #2 accesses the week
schedule and holiday programming for the individual unit.
Menu item #3 can be selected to force the heat pump to
manually reset in the case of an operating problem.
The Occupied Heating and Cooling Setpoints are
programmed on this screen. The setpoints must be at least one
degree apart. If you try to enter the same value or to cross the
cooling and heating setpoints, the value you enter will not be
accepted.
The Unoccupied Heating and Cooling Setbacks are programmed
on this screen. The Cooling SetUp is added to the Occupied
Cooling Setpt to create the Unoccupied Cooling Setpoint. The
Heating SetBack is added to the Occupied Heating Setpt to
create the Unoccupied Heating Setpt.
If the Space Temperature Sensor has the optional slide
adjustment, then the Slide Effect is the maximum amount of
change that it can have on the Heating and Cooling Setpoint and
it is programmed here.
The SP Deadband is divided in half across the current heating
and cooling setpoint, and is used in staging the heating and
cooling on or off.
MinimumDefaultMaximum
If you have an override pushbutton on the space sensor, the OV
Duration is the length of time the unit will be in the occupied
mode after pushing the button
Slide Effect0°F3°F5°F
SP Deadband0°F1°F20°F
OV Duration0.0 Hr1.0 Hr8.0 Hr
Setpoint Screen #4
WHP #1 Setpoints Cooling Stages: x Heating Stages: x
If the Heat Pump is configured to operate with a Reversing
Valve, relay #5 can be configured as a second stage for either
heating or cooling or both. If the Heat Pump is configured for
individual heating and cooling, this determines how many of
each stage there are.
Cooling Stages012
Heating Stages012
MinimumDefaultMaximum
MinimumDefaultMaximum
3-14Programming
WattMaster WHPSection 3
Setpoint Screen #5
WHP #1 Setpoints Min Run Time: x Min Min Off Time: x Min Min Cycle...:xx Min
The Min Run Time determines how long the compressor
must remain on once it has been activated. The Min Off Time
determines how long the compressor must remain off once it
is de-activated. The Min Cycle time determines how many
times per hour the compressor can be started. If you entered
10 minutes, the compressor could start a maximum of 6 times
in a one hour period.
Min Run Time0 Min1 Min20 Min
Min Off Time0 Min6 Min20 Min
Min Cycle0 Min12 Min60 Min
Setpoint Screen #6
WHP #1 Setpoints Changeover Delay Between Heat/Cool
Modes......:xx Min.
To prevent rapid cycling between heating and cooling modes,
you can enter a time period that must be satisfied before the
changeover can occur.
MinimumDefaultMaximum
Changeover Delay1 Min30 Min60 Min
Setpoint Screen #7
WHP #1 SetpointsEnable Signal Select NO ENABLE REQUIREDUse Left/Right Arrow
Normally you would want to have an Enable Signal that gave
assurance of water flow before you activate the heat pumps
compressor. If you need to operate without this enable signal,
use the arrow keys to select the NO ENABLE REQUIRED
message. Otherwise, select the LOOP FLOW REQUIRED
message so that the signal must be present for the comp ressor
to run.
If your heat pump uses a reversing valve to determine the
heating or cooling mode of operation, select the message
R/VALVE & COMPRESSOR. If you are controlling
separate stages of heating and cooling select the
INDIVIDUAL STAGING message.
Setpoint Screen #9
WHP #1 SetpointsReversing Valve Used During: COOLING MODE Use Left/Right Arrow
If you have configured the system to use the reversing valve,
you must select which mode requires it to be active. Select
either the COOLING MODE or the HEATING MODE
message.
If you have configured the system to use the reversing valve,
you can also set it to cycle on and off with the compressor,
(CYCLES w/COMPRESSOR) or, to remain on once it is
activated, and stay on until the opposite mode or unoccupied
mode is selected (RUNS CONTINUOUS MODE). The
valve always activates 10 seconds before the compressor
starts no matter which method you select.
If your system is configured to use the reversing valve and
you only have one stage of heating and cooling, that last
relay becomes available for other uses. The AUXILIARYRELAY MODE can be used to operate the relay manually
from the Prism computer front end program. If you select
ISOLATION VALVE MODE, the relay activates anytime
the compressor is called for or whenever the Loop Controller
sends an override command to activate and reduce loop
pressure.
If the relay needs to follow an external week schedule, select
the AUXILIARY RELAY MODE and then see the Aux
Relay #5 Schedule assignment screen.
Setpoint Screen #12
WHP #1 Setpoints Fan Mode of Op RUNS CONTINUOUS MODE Use Left/Right Arrow
You can program the fan to run continuously during the
occupied mode, (RUNS CONTINUOUS MODE) or you
can program it to cycle on and off with the compressor
during both the occupied and the unoccupied mode of
operation.
(CYCLES W/COMPRESSOR)
Setpoint Screen #13
WHP 1# Setpoints Aux Relay #5 Uses Uses Schedule #: x
0) None 1-7) Clock
If you configured relay #5 as an Auxiliary Relay, you can
also program it to follow an external schedule command.
You must have an OSS Optimal Start Scheduler installed
somewhere on you communications loop to provide the
external schedule you select here.
Programming3-17
Section 3WattMaster WHP
Setpoint Screen #14
WHP #1 Setpoints Heat Pump Scheduling Uses Schedule #: x
0) Int. 1-7) Clock
The Heat Pump Controller can use the internal time clock for
a setting an occupied schedule, for this the setpoint will be 0.
It can also be programmed to follow an external schedule
command. You must have an OSS Optimal Start Scheduler
installed somewhere on you communications loop to provide
the external schedule, and you select the schedule number
here.
Setpoint Screen #15
WHP Setpoints Startup Delay Period x Seconds Times Board Address Switch
If you entered the same starting time for several heat pumps,
they are prevented from all starting their fans at the same
time by a Startup Delay Period that is determined by their
address switch setting. The address is multiplied by the
number of seconds you enter on this screen, up to a
maximum of 60 seconds per address. This is the time period
the fan must wait before it starts when the schedule goes
occupied.
If you entered 5 seconds and the address was 10 then the fan
would start 5 x 10 or 50 seconds after the schedule goes
occupied.
Setpoint Screen #16
WHP Setpoints Energy Demand Limits Max Effect: xx°F
3-18Programming
An Energy Demand Limit sequence is programmed into all
heat pump controllers. It is currently an option that is notsupported by a controller that can send the Demand Limit
signal to initiate a limiting condition. It is included here for
future use only.
MinimumDefaultMaximum
Max Effect0°F3°F30°F
WattMaster WHPSection 3
the Status screen.
Setpoint Screen #17
WHP # 1 Setpoints Heat Stage #2 SAT Lockout: 60°F
This setpoint is to shut the heating off when the supply air
temperature is too warm. When the supply air temperature is
above this setpoint, it will prevent the second stage of heat
from coming on.
MinimumDefaultMaximum
Max Effect30°F60°F200°F
Setpoint Screen #18
SENSOR CALIBRATION SPC xxx.x° xxxx.x SAT xxx.x°° xxxx.x WAT xxx.x°° xxxx.x
°°
°°
The Thermister Type III Sensor readings can be calibrated.
°°
Enter Positive values to increase the reading or Negative
values to decrease the reading. If no sensor is attached, the
calibration offset will still allow a value to be input and read
for diagnostic purposes.
Space Sensor SPC-100.0°F0.0°F+100.0°F
Supply Air Sensor SAT-100.0°F0.0°F+100.0°F
Water SensorWAT-100.0°F0.0°F+100.0°F
Setpoint Screen #19
WHP #1 Setpoints Alarms: Enabled
Use Left/Right Arrow
Select if you want the notification LED on the front of the
System manager to illuminate when an alarm occurs. If
Enabled is selected, any WHP alarm will cause the Alarm
LED on the front panel to light up. If Disable is selected, the
Alarm LED will not light up but the alarm will still show up in
MinimumDefaultMaximum
Note: You must do a Rebuild Alarm Map after all controllers are powered up and
communicating.
Programming3-19
Section 3WattMaster WHP
2) WHP Schedules
The Water Source Heat Pump controllers contain their own built in scheduling capability
for calculating Occupied/Unoccupied periods. Select item #2 from Schedules menu to
access the following schedule programming menu.
There are two Start / Stop events available per day.
The first line is the start time for event #1 and the next line is
the stop time for event #1.
The screens will step through the Start Time and then the StopTime for each day of the week. You can quit at any point in the
process by pressing the "ESC" key.
If no second event is required, simply leave a ZERO for both
the start and stop times on the event #2 screens.
All times are in 24-hour format, so 5:00 PM would be entered
as 1700.
If both the Start and Stop Times are ZERO, the schedule is in a
Continuous OFF mode.
If both the Start and Stop Times are 2359, the schedule is in a
Continuous ON mode.
3-20Programming
WattMaster WHPSection 3
Holidays
Holiday Day Selection
There are 14 Holiday periods available, organized as a Start Day / Stop Day event. If the
Holiday only lasts one day, enter the same date for the Start & Stop days. There is no
limit to the duration or number of days that can be included in one holiday, other than it
cannot extend past December 31st. If you have a holiday that crosses the end of year
border, you will need to use two holiday periods to accomplish this event.
The 14 holidays all use the same Holiday Start / Stop
time. The start/stop times are programmed back on the
Week Schedule screens. The holiday schedule screen
appears after the Saturday schedule screen, as you are
stepping through the days of the week.
1225 = December 25th
Note: Normally there is no schedule in the Loop Controller device. It simply looks at
all the Water Source Heat Pumps for a request to run signal. Scheduling is
maintained separately in each Water Source Heat Pump. If you want to be able
to schedule all Water Source Heat Pumps on and off at the same time, you can
input a schedule on the Loop Controller and it will broadcast that schedule to all
WHPs.
If one of your heat pumps has tripped off, it can be manually
reset from the following screen. You will have entered the
Unit ID to access the WHP Menu screen, so that is the unit
that will receive this reset command. If you don’t want to
send the command, select the Disabled message with the
arrow keys. If you do want to send the command, select the
Enabled message with the arrow keys and then press the
nter button. This command will automatically clear itse
when the WHP detects it and performs the reset.
There are two methods of resetting:
1. Relay #4, on the WHP will activate with the reset
command and can be wired to provide the reset
action.
2. The compressor relay will be cycled off. On
newer heat pumps, this is all that is required to
reset the operation.
3-22Programming
WattMaster WHPSection 3
Loop Controller Status
Loop Controller Status Menu
1) View Status Only
2) View Alarms Menu) Setpoints ESC) To Exit
From the main menu screen select MENU on the keypad. Then select “View Status
Only” (keypad #1) and finally enter the loop and zone number for the desired unit.
As the screen above shows, there are two areas of status available for the Loop
Controller. Menu item #1 accesses all the status screens for the Loop Controller. Menu
item #2 accesses the alarms for the Loop Controller. “Menu” can be selected to access the
Setpoints screens.
Loop Controller Status
Screens
If you selected menu item #1, View Status Only, and you entered the Unit ID of the Loop
Controller, the following Status Screens are available.
Status Screen #1
Loop Control v1.06 OCCUPIEDReturn Temp: xx.x°FSupply Temp: xx.x°F
Line 2 -
Line 3 Line 4 -
Current operating Mode:
OCCUPIED
UNOCCUPIED
Current Return Water Temperature
Current Supply Water Temperature
Programming3-23
Section 3WattMaster WHP
Status Screen #2
Loop Control v1.06 No Call to Run Water Flow Proved! LOOP ENABLED
Status Screen #3
Loop Control v1.06 LEAD Pump #1: ON STANDBY Pump #2: OFF
Line 2 -
Line 3 -
Line 4 -
Line 2 Line 3 -
Current operating Mode:
No Call To Run
ACTIVE CALL TO RUN
FREEZE PROTECTION!
Current Water Flow Status:
Water Flow Proved!
No Flow Detected
Current Request to Operate Status:
LOOP ENABLED
LOOP DISABLED
LEAD Pump #1 On or Off
STANDBY Pump #2 On or Off
Status Screen #4
Cool Stage # 1.: OFF Cool Stage # 2.: OFF Cool Stage # 3.: OFF Cool Stage # 4.: OFF
Current Loop Water Pressure
Current Variable Speed Pump Voltage Signal
Current Proportional Heat Voltage Signal
Note: If none of the above options have been configured, then the values in this status
screen will be 0.
Programming3-25
Section 3WattMaster WHP
Status Screen #7
Loop Control v1.06
No Alarms!
Line 2 Line 3 -
Pump Failure or Blank Line
Hi Control Water Temp
Lo Control Water Temp
Line 4 -
Fire/Smoke Alarm
Phase Shutdown
Note: If no alarms exist, then the screen displays the message shown for No Alarms! If
ANY alarm exists, then the three lines display one of the messages shown above.
The Fire/Smoke Alarm is generated as follows:
If the NC (normally closed) contact from a firestat or smoke detector th at is wired
between GND and AIN1, on the Analog Input expansion board, opens, the
Fire/Smoke Alarm is generated.
The Phase Shutdown Alarm is generated as follows:
If the NO (normally open) contact from a phase monitoring device, that is wired
between GND and AIN7 is made, the Phase Shutdown Alarm is generated.
Status Screen #8
Loop Control v1.06 Pump Run Times #1: xxxxx Hrs xx Min #2: xxxxx Hrs xx Min
3-26Programming
Line 2 Line 3 Line 4 -
Message Only
Pump #1 Hours and Minutes Run Time
Pump #2 Hours and Minutes Run Time
WattMaster WHPSection 3
Loop Controller Setpoints
Loop Controller Setpoint Menu
1)LC Setpoints
2)LC Schedules
3)LC Force ModesESC) To Exit
Setpoint Screen #1
WHP Loop Setpoints HEAT REJECTION
Setpoint......: xx°F
Stage Deadband: xx°F
If the controlling water temperature rises above this Setpoint,
the Heat Rejection or Cooling Stages begin to stage on. As the
temperature continues to rise above the Setpoint by the
Deadband amount, an additional stage is added. Each
additional stage can only activate if the temperature rises above
the Setpoint by the number of active stages times the deadband
value.
Example: There are 2 stages on, a 3° deadband and the setpoint
is 79°
2 x 3° + 79° = 85° before stage 3 can activate
Setpoint50°F79°F99°F
Stage Deadband1°F3°F10°F
Setpoint Screen #2
WHP Loop Setpoints HEAT REJECTION Stage Delay...: x M
The Staging Delay period must also be satisfied before an
additional stage of cooling or heat rejection can be activated.
The maximum number of heat rejection stages are programmed
on this screen also.
MinimumDefaultMaximum
MinimumDefaultMaximum
Stage Delay1 Minute1 Minute60 Minutes
Programming3-27
Section 3WattMaster WHP
Setpoint Screen #3
WHP Loop Setpoints HEATING ADDITION
Setpoint......: xx°F
Stage Deadband: xx°F
If the controlling water temperature drops below this Setpoint,
the Heat Addition or Boilers begin to stage on. As the
temperature continues to drop below the Setpoint by the
Deadband amount, an additional stage is added. Each
additional stage can only activate if the temperature drops
below the Setpoint by the number of active stages times the
deadband value.
Example: There are 2 stages on, a 3° deadband and the setpoint
is 79°
79° - 2 x 3° = 73° before stage 3 can activate
Setpoint50°F76°F99°F
Stage Deadband1°F3°F10°F
Setpoint Screen #4
MinimumDefaultMaximum
WHP Loop Setpoints HEATING ADDITION Stage Delay...: x M
The Staging Delay period must also be satisfied before an
additional boiler or heat addition stage can be activated.
The maximum number of heat addition stages are programmed
on this screen also.
Stage Delay1 Minute1 Minute60 Minutes
Setpoint Screen #5
WHP Loop Setpoints OA FREEZE PROTECTION
Setpoint.....: xx°F
If the outdoor air temperature drops below this setpoint, the
pump will be energized to prevent the water lines from
freezing.
Setpoint
MinimumDefaultMaximum
MinimumDefaultMaximum
-50°F40°F50°F
3-28Programming
WattMaster WHPSection 3
Setpoint Screen #6
WHP Loop Setpoints Water Hi Limit: xx Water Lo Limit: xx Alarm Delay...: xM
°
°
If the controlling water temperature rises above the Water Hi
Limit setpoint, all heat addition will be removed and one
stage of heat rejection will be activated. If the controlling
water temperature drops below the Water Lo Limit setpoint,
all heat rejection stages will be removed and one heat
addition stage will be activated. An alarm will be generated if
it remains out of limits for the Alarm Delay Time.
The Loop Controller can modulate a Variable Speed Pump.
Select the PRESSURE option in place of th e CONSTANT
option for variable speed pumping.
The water flow proving can be accomplished by a differential
pressure contact closure or an actual pressure sensor. If you
select Variable Speed Pumping, you must select the
PRESSURE option in place of the CONTACT option for
Flow Proof.
MinimumDefaultMaximum
Water Hi Limit0°F120°F120°F
Water Lo Limit0°F0°F120°F
Alarm Delay0 Min30 Min120 Min
Setpoint Screen #8
WHP Loop Setpoints STEP HEATING CONTROL RETURN WATER CONTROL Use Left/Right Arrow
Programming3-29
There are two methods of Heat Addition control, STEP
HEATING CONTROL or PROPORTIONAL HEATING
The Loop Controller can be configured to maintain Return
Water Temperature ( RETURN WATER CONTROL ) or
the Supply Water Temperature ( SUPPLY WATERCONTROL )
Section 3WattMaster WHP
Setpoint Screen #9
WHP Loop Setpoints Lead/Lag Changeover Switch After xxx Hrs
The two pumps will switch after this programmed amount of
time so that each pump accumulates roughly the same
number of run time hours. If a pump is currently running and
this time period is exceeded, the changeover will occur as
soon as pump run time exceeds the setpoint. The current
pump will shut off and the standby pump will start at the
same time.
MinimumDefaultMaximum
Changeover1 Hour40 Hours240 Hours
Setpoint Screen #10
WHP Loop Setpoints Water Loop Proof Of Flow Pr. SP: xxx PSI
If you attached a Pressure Sensor for proof of flow instead of a
differential pressure contact closure for proof of flow, the
controlling pressure is programmed on this screen. This
Setpoint represents the amount of pressure that you set to prove
water flow exists in the system. Otherwise, this screen will not
appear.
If you configured the system for Variable Speed Pumping with
a Pressure Sensor for proof of flow, the controlling pressure,
deadband and control adjust time period are programmed on
this screen. Otherwise, this screen will not appear.
WHP Loop Setpoints Isolation Valves Set Open if PSI is Above Hi Limit...: xxx PSI
If you configured the system for Variable Speed Pumping with a
Pressure Sensor for proof of flow, the Loop Controller can send
a signal to all the Heat Pumps to open their Isolation Valves
whenever a Hi Limit Pressure is exceeded. If the Heat Pumps do
not control an Isolation Valve, then the only reaction is to
reduce the variable speed pump voltage signal.
The Thermister Type III Sensor readings can be calibrated.
°°
Enter a Positive value to increase the reading or a Negative
°°
°°
value to decrease the reading. If no sensor is attached, the
calibration offset will still allow a value to be input and read for
diagnostic purposes.
MinimumDefaultMaximum
Return Water RWT-10.0°F0.0°F+10.0°F
Supply Water SWT-10.0°F0.0°F+10.0°F
Outdoor Air OAT-10.0°F0.0°F+10.0°F
Note: Due to memory limitations in the Loop Controller, the maximum amount of
calibration offset is 10.0°F.
Setpoint Screen #14
WHP Loop Setpoints
Alarms: Enabled
Use Left/Right Arrow
Alarms can be configured to light the LED on the front of the
System Manager by setting Alarms to Enabled, if you do not
wish to report alarms, select Disabled.
Figure 4-11: Comm Driver Chip Replacement............................................................40
Start-Up and Troubleshooting
WattMaster WHPSection 4
1.0Communications
Overview
Perhaps no other portion of the system seems as difficult to diagnose as the communications loop, yet it really can be quite simple if you understand how it works. In fact, much
of the troubleshooting can be done by simple observation. We will lead you through the
system functions and then provide you with detailed instructions for checking each piece
of equipment.
1.1How It Works
WattMaster uses a token-passing loop architecture, which means in simple terms that an
“electronic message” called a token is passed from controller to controller in a roundrobin fashion. A controller must wait to receive the token before it can send or request
any data.
Note: It is very important to know which device is the loop master on the loop
you are troubleshooting.
1.2WattMaster WHP System
The standard WattMaster WHP system may have only one communications loop or as
many as thirty communication loops depending on the number of WHP Controllers to be
connected to the system. It is important to remember that each loop must have its own
master.
If you are using the multiple loop version of the WHP system (for systems with more than
30 WHP Controllers) a loop is required for each group of 30 WHP Controllers. The WHP
Loop Controller may be connected to any of the Local Loops. The Local Loop that has
the WHP Loop Controller installed can only have 29 WHP Controllers on that loop. Each
Local Loop is connected to a MiniLink loop interface. The MiniLink is always themaster on the Local Loops. The MiniLinks are connected to the CommLink II and to
each other via the Network Loop.
The CommLink II is always the master on the Network Loop. You must be sure the
CommLink II is connected and functioning if you are troubleshooting the communications loops. Make sure the CommLink II is set for multiple loops
.
Start-Up and Troubleshooting4-1
WattMaster WHPSection 4
COMPUTER
(OPTIONAL)
RS-485
Comm Loop
32K
8K
COMM
RELAY
OUTPUT
T
Room Sensor
with Optional
Override & Adj.
COM
1-3
SHLD
OUT
1
R
OUT
RAM EPROM
485
LD4
2
COMM
OUT
3
REC.
OUT
OUT
4
OUT
5
COM
CPU
4-5
4-5
COMM
12V
TEST
ADDRESS ADD
AIN
1
AIN
2
AIN
3
EWDOG
AIN
4
AIN
5
GND
GND
0-5
VDC
AOUT
PWR
PRESSURE
GND
SENSOR
YS101564
0-1
VDC
24VAC
24 VAC
110/24 VAC
Power Pak
Modem
(Optional)
M
R
T
R
S
D
R
D
O
H
C
D
A
A
H
S
CommLink II
Multiple Loop
Interface
C
COMM
O
M
M
LINK
L
I
N
K
II
I
I
L
O
C
O
O
M
P
M
O
D
P
E
M
WCLI
AT
TM
A
ST
ER
O
N
TR
O
S
,
N
C
MiniLink
Loop # 1
K
N
I
L
I
N
I
M
MINILINK
N
NETWORK
1
2
E
4
T
T
8
W
16
SH
O
32
R
R
K
24VAC24VAC
GND
LOOP
L
T
O
O
SH
P
R
24VAC
MiniLink
Loop # 2
K
N
I
L
I
IN
M
MINILINK
N
NETWORK
1
2
E
4
T
T
8
W
16
SH
O
32
R
R
K
24VAC
GND
LOOP
L
T
O
O
SH
P
R
24VAC
Typical Network & Local Loop Wiring
2 Conductor Twisted Pair with Shield
MiniLink
Loop # 3
N
NETWORK
E
T
T
W
SH
O
R
R
K
LOOP
L
T
O
O
SH
P
R
(Beldon #82760 or Equivalent)
K
N
I
IL
N
I
M
MINILINK
1
2
4
8
16
32
24VAC24VAC
GND
24VAC
NOTE: * Only One Outside Air Sensor
is Required per WHP System
MiniLink
Loop # 4
K
N
I
L
I
N
I
M
MINILINK
N
NETWORK
1
2
E
4
T
T
8
W
16
SH
O
32
R
R
K
24VAC
GND
LOOP
L
T
O
O
SH
P
R
Loop # 4
24VAC
Notes:
1.) 24 VAC Must Be Connected
So That All Ground Wires
Remain Common.
2.) All Wiring To Be In Accordance
With Local And National Electrical
Codes and Specifications.
110/24 VAC
Power Pak
Network Loop
RS-485
19200 Baud
Local Loop
RS-485
9600 Baud
Local Loop
RS-485
9600 Baud
Local Loop
RS-485
9600 Baud
*OutsideAir
Sensor
Supply
Air
or Leaving Water Temp
F
Sensor
Typical WHP Controller Wiring
#1
32K
8K
COMM
RELAY
OUTPUT
T
COM
1-3
SHLD
OUT
1
R
OUT
RAM EPROM
485
LD4
2
COMM
OUT
3
REC.
OUT
OUT
4
OUT
5
COM
CPU
4-5
4-5
COMM
12V
TEST
ADDRESS ADD
AIN
1
AIN
2
AIN
3
EWDOG
AIN
4
AIN
5
GND
GND
0-5
VDC
AOUT
PWR
PRESSURE
GND
SENSOR
YS101564
0-1
VDC
24VAC
System Manager
#1
32K
8K
COMM
RELAY
OUTPUT
T
COM
1-3
SHLD
OUT
1
R
OCCUPIED
03/31/04 03:38PM WED
NO ALARMS
OUT
RAM EPROM
485
LD4
2
COMM
OUT
3
REC.
OUT
OUT
4
OUT
5
COM
CPU
4-5
4-5
COMM
12V
TEST
ADDRESS ADD
AIN
1
AIN
2
AIN
3
EWDOG
AIN
4
AIN
5
GND
GND
0-5
VDC
AOUT
PWR
PRESSURE
GND
SENSOR
YS101564
0-1
VDC
24VAC
24VAC
#1
32K
8K
COMM
RELAY
OUTPUT
T
COM
1-3
SHLD
OUT
1
R
OUT
RAM EPROM
485
LD4
2
COMM
OUT
3
REC.
OUT
OUT
4
OUT
5
COM
CPU
4-5
4-5
COMM
12V
TEST
ADDRESS ADD
AIN
1
AIN
2
AIN
3
EWDOG
AIN
4
AIN
5
GND
GND
0-5
VDC
AOUT
PWR
PRESSURE
GND
SENSOR
YS101564
0-1
VDC
24VAC
WHP Loop
Controller
C21
1
U3
D
3
CX1
X
CX2
U2
RN1
C
CX4
1
U1
U4
1
2
G
Y
4
L
N
V
TB1
COMM
LD6
R1
INPUTS
TB3
PRESSURE
SENSOR
V1
R
A
D
C
2
D
V2
T
V3
SHLD
2
Y
L
R
R
CX5
COM1-3
3
D
U5
PAL
R1
RS-485
COMM
1
EPROM
RAM
R2
COMM
3
LD7
Y
TUC-5RPLUS
1
L
HH
PWR
R
R3
(1MEG)
4
YS101816REV.2
2
U6
D
3
LD8
N
YS101790
4RLYIOBD.
R4
N
R
LED1
R
C1
R5
LD9
LED2
P1
4
COM4-5
Y
L
R
+VREF
TB2
CX6
5
5.11V
D
TESTPOINT
2
U7
V4
C
S
P
I
EWDOG
1
IL
X
RV1
V5
H
P
VREFADJ
5
R28
Y
L
3
R
C
1
ADD
ADDRESS
U8
1
+VDC
4
N
2
R
RN5
4
NE5090NPB3192
8
PU1
AIN1
X
0PS
8
C
U9
D6
16
CX10
PU2
AIN2
C7
32
D7
TOKEN
PU3
R6
AIN3
NETWORK
0
1
7
D8
U10
D
R
SW1
PU4
AIN4
0
3
1
1
D9
L1
C9
R
D
PU5
AIN5
CX12
1
1
D11
1
D12
C
C
C
1
1
X2
9936
PU7
C10
1
-5
-1
D
D
R13
GND
R
0
0
U
V
V
MC34064A
D14
JP1
SC1
GND
C13
C12
U13
R15
AOUT1
U12
AOUT2
CX14
C14
C16
R19
U14
AIN7
CX13
D15
C17
TB4
GND
U15
C15
D19
PJ1
GND
R22
7
2
6
R24
R
R
1
E
D
8
7
6
R25
1
1
W
V
C20
9
8
CX15
D
D
O
1
1
P
C
C
7824CT
R26
3
24VAC
2
J
J
P
M
P
VR1
EXPANSION
VR2
T'STAT
3.) The Local Loop With The Loop Controller
Installed Can Only Have Up To 29
WHP Controllers Attached As The WHP
Loop Controller Occupies Address #30.
4.) Systems may consist of up to 20 Local
Loops (600 WHP Controllers). Consult
factory for systems that exceed these quantities.
COMM
T
SHLD
R
LD4
YS101790
4RLYIOBD.
REC.
AIN1
AIN2
AIN3
AIN4
GND
AOUT1
4ANALOGIN MOD I/O BD.
YS101784
12V
AIN
1
AIN
2
AIN
3
AIN
4
AIN
5
GND
GND
AOUT
PRESSURE
SENSOR
#1
RAM EPROM
485
COMM
CPU
ADDRESS ADD
EWDOG
YS101564
32K
8K
RELAY
OUTPUT
COM
1-3
OUT
1
OUT
2
OUT
3
OUT
OUT
4
OUT
5
COM
4-5
4-5
COMM
TEST
0-5
VDC
PWR
GND
0-1
VDC
24VAC
See Note #3
Dirty Filter Alarm
Loop #1
WHP
Controllers
Loop #2
WHP
Controllers
Loop #3
WHP
Controllers
Loop #4
WHP
Controllers
Local Loop
RS-485
9600 Baud
#30
32K
8K
COMM
RELAY
OUTPUT
T
COM
1-3
SHLD
OUT
1
R
OUT
RAM EPROM
485
LD4
2
COMM
OUT
3
REC.
OUT
OUT
4
OUT
5
COM
CPU
4-5
4-5
COMM
12V
TEST
ADDRESS ADD
AIN
1
AIN
2
AIN
3
EWDOG
AIN
4
AIN
5
GND
GND
0-5
VDC
AOUT
PWR
PRESSURE
GND
SENSOR
YS101564
0-1
VDC
24VAC
#30
32K
8K
COMM
RELAY
OUTPUT
T
COM
1-3
SHLD
OUT
1
R
OUT
RAM EPROM
485
LD4
2
COMM
OUT
3
REC.
OUT
OUT
4
OUT
5
COM
CPU
4-5
4-5
COMM
12V
TEST
ADDRESS ADD
AIN
1
AIN
2
AIN
3
EWDOG
AIN
4
AIN
5
GND
GND
0-5
VDC
AOUT
PWR
PRESSURE
GND
SENSOR
YS101564
0-1
VDC
24VAC
#30
32K
8K
COMM
RELAY
OUTPUT
T
COM
1-3
SHLD
OUT
1
R
OUT
RAM EPROM
485
LD4
2
COMM
OUT
3
REC.
OUT
OUT
4
OUT
5
COM
CPU
4-5
4-5
COMM
12V
TEST
ADDRESS ADD
AIN
1
AIN
2
AIN
3
EWDOG
AIN
4
AIN
5
GND
GND
0-5
VDC
AOUT
PWR
PRESSURE
GND
SENSOR
YS101564
0-1
VDC
24VAC
#29
32K
8K
COMM
RELAY
OUTPUT
T
COM
1-3
SHLD
OUT
1
R
OUT
RAM EPROM
485
LD4
2
COMM
OUT
3
REC.
OUT
OUT
4
OUT
5
COM
CPU
4-5
4-5
COMM
12V
TEST
ADDRESS ADD
AIN
1
AIN
2
AIN
3
EWDOG
AIN
4
AIN
5
GND
GND
0-5
VDC
AOUT
PWR
PRESSURE
GND
SENSOR
YS101564
0-1
VDC
24VAC
Figure 4-1:
System Wiring Overview
4-2Start-Up and Troubleshooting
WattMaster WHPSection 4
STANDA RD WALL MOUNT
120/24 VAC POWER SUPPLY
( MAY ALSO BE POWERED FROM 24VAC )
(NETWORK TERMINALS ONLY)
Y
SYSTEM MANAGER POWER SU PPLY
GND
24VAC
POWER
L
A
A
A
4
Y
CPU
A
A
A
4
Y
CPU
A
A
A
A
Y
4
4
4
2
4
V
A
C
G
N
D
U6
C1
U2
U3
U4
V1V2V3
V5
V4
L1
R6
C9
6
M
U8
U9
C7
CX10
CX12
CX14
CX13
X2
INPUTS
+VDC
AIN1
AIN2
AIN3
AIN4
AIN5
RS-485
SHLD
COMM
COMM
U1
COMM
LED1
LED2
R1
U7
VREF ADJ
TEST POINT
COM1-3
COM4-5
CX15
All communications wiring should be labeled to avoid confusion and to aid future
servicing.
03/31/04 03:38PM WED
OCCUPIED
COMPUTER
(OPTIONAL)
NO ALARMS
COMMUNICATIONS
RS-485
SYSTEM MANAGER
T
SHLD
R
S101716 REV. 1
COMM LINK II
INTERFACE
(MULTIPLE LOOP)
UNIT COMES WITH
Remote Link
(OPTIONAL)
32K
COMM
TSHLDR
LD4
C21
CX1
RN1
1
TB1
T
R
CX5
U5
LD6
LD7
1
HH
PWR
LD8
RN3
LD9
P1
+VREF
5.11V
EWDOG
RV1
R28
ADDRESS
RN5
PU1
D6
PU2
D7
PU3
D8
PU4
D9
PU5
D11
C10
PU7
GND
D14
GND
C12
U13
AOUT1
AOUT2
AIN7
D15
C17
GND
PJ1
TB3
C20
R26
PJ2
PRESSURE
SENSOR
GND
24VAC
NETWORK
T
SH
OOP
R
T
R
SH
EXPANSION
D1
CX2
CX3
CX4
RLY1
D2D3D4D5
RLY2RLY3RLY4RLY5
PAL
R1
1
EPROM
RAM
PHILIPS
ADD
1
2
4
8
16
32
TOKEN
NETWORK
SW1
0-5
0-1
VDC
VDC
JP1
R15
C14
R19
U15
C15
R22
R24
R25
PJ3
R2
TUC-5R PLUS
R3
(1 MEG)
YS101816 REV. 2
R4
RN2
R5
TB2
CX6
C2
X1
C3
1
RN4
NE5090NPB3192
0PS
CX8
U10
R7
D10
R10
D13
D12
C11
993
R13
R11
U11
MC34064A
SC1
C13
U12
C16
U14
TB4
D19
GND
R27
D16
V6
D18
D17
POWER
C19
C18
7824CT
24VAC
VR2
VR1
T'STAT
RLY IO BD.
RLY IO BD.
IN1
IN2
IN3
IN4
GND
AOUT1
YS101790
YS101790
ANALOG IN MOD I/O BD.
S101784
REC.
12V
IN1
AIN
2
AIN
3
AIN
4
AIN
5
GNDGND
OUT
PRESSURESENSOR
S101564
COMM
TSHLDR
LD4
REC.
12V
IN1AIN2AIN3AIN4AIN5GND
GND
OUT
PRESSURE
SENSOR
S101564
8K
RELAY
OUTPUTCOM1-3
OUT
1
85
RAMEPROM
COMM
DDRESSADD
EWDOG
0-5
0-1
VDC
85
RAMEPROM
COMM
DDRESS ADD
EWDOG
0-5
VDC
0-1
VDC
OUT
2
OUT
3
OUT
OUT
4
OUT
5COM4-5
4-5
COMM
TEST
VDC
PWR
GND
24VAC
32K
8K
RELAY
OUTPUTCOM1-3OUT
1
OUT
2OUT
3
OUT
OUT
4
OUT
5COM4-5
4-5
COMM
TEST
PWR
GND
24VAC
TO OTHER WHP CONTROLLERS
Figure 4-2:
TO OTHER MINILINKS
Communications Loop Routing
Start-Up and Troubleshooting4-3
WattMaster WHPSection 4
2.0WHP Controller
Overview
2.1How It Works
2.1.1Initialization
On system powerup the COMM LED remains extinguished for five seconds. After this
delay, the COMM LED will blink out the address of the controller (Address Switch
Setting). The COMM LED will then extinguish for another five seconds and then begin
to blink for a twenty second startup delay. At the conclusion of this twenty second period,
the COMM LED will begin blinking a diagnostic code every ten seconds. This code is
described later in this document. The duration of a powerup initialization sequence is
roughly one minute.
During this initialization period, the controller retrieves all operating setpoints from its
non-volatile EEPROM memory and initializes all outputs to an OFF condition.
Note: All future references to the Water Source Heat Pump Controller in this docu-
ment use WHP as the designation.
2.1.2Operating Summary
At all times, after the conclusion of the initialization sequence, the WHP performs a
specific set of operating instructions in the following order: (a - g repeat continuously)
a. Read Analog Inputs for Temperatures and Overrides.
b. Check the RS-485 communications port for any new setpoints from the System
Manager and keeps the status updated for the System Manager.
c. If the push-button override is active, it checks the timer to see if the override is
finished.
d. Calculates the current occupied/unoccupied mode from its internal week sched-
uling.
e. Calculates what state the output relays and analog output should be set to.
f.Updates the diagnostic COMM LED blinking.
g. Stores data in the internal trend log if ready for another log.
4-4Start-Up and Troubleshooting
WattMaster WHPSection 4
2
EWD
O
G
DIAGNOSTIC BLINK
RAM SIZE
24 VAC Common for Inputs 1 - 3
Aux. Heating or Cooling (Cool 2)
24 VAC Common for Inputs 1 - 3
Mounting Backplate
2.2Becoming Familiar with the WHP
Controller
COMMUNICATIONS
DRIVER CHIP
RS-485
COMMUNICATIONS
LOOP
COMMUNICATIONS
LED
ADDRESS SWITCH
( ADDRESS 18 SHOWN )
ANALOG INPUTS
Space Sensor
Slide Adjust
Supply Air Temp
Leaving Water
Temp or
Dirty Filter
Lockout
STATIC PRESSURE
SENSOR INPUT
COMM
LD4
REC.
SENSOR
TSHLD
R
12VAIN
AIN
AINAINAIN
GNDGND
AOUT
PRESSURE
123
45
PIN 1
INDICATION
YS101564
RAMEPROM
485COMM
ADDRESS ADD
CPU
RAM
0-5
0-1
SELECT JUMPER
EPROM
32K
COMM
TEST
VDC
VDC
PAL
8K
RELAY
OUTPUTCOM1-3
OUT
OUT
OUT
OUT
OUTOUT
COM4-5
4-5
PWR
12
3
4
5
GND
4VAC
Fan-On/Off
Rev. Valve-On/Off (Heat 1)
Compressor-On/Off (Heat 2)
Heat Pump Reset (Cool 1)
CODE LED
REAL TIME
CLOCK CHIP
POWER LED
24VAC
POWER
INPUT
Figure 4-3:
WHP Controller Component Layout
2.2.124 VAC Power Connector
This connector provides power to the WHP Controller.
24VAC - The “hot” side of the control transformer.
GND - The grounded side of the control tran sformer. If the secondary of the con-
trol transformer is not grounded, you must still observe polarity if the transformer powers any other device!
Warning: Connect only the GND terminal to the grounded side of a transformer
- Failure to properly observe polarity will result in
damage to the system. Observe polarity at all points in the
system.
Start-Up and Troubleshooting4-5
WattMaster WHPSection 4
2.2.2Analog Inputs
This connector carries the analog and binary control input signals.
AIN1 - Space Temp - This input accepts a two wire 10K Type III the r m i sto r t e mperature sensor. The sensor measures 10,000 Ohms @ 77°F. The resistance drops
as the temperature increases. The sensor is connected between this terminal and
the GND terminal. This input is also monitored for push-button override commands. The push-button is only active during unoccupied hours so a push during
occupied hours has no effect.
AIN2 - Slide Adjust - If the OE212 or OE213 space temperature sensor is installed, the sensor contains a slide adjust control for varying the current heating
and cooling setpoints. If the OE210 or OE211 sensors are used, this input will not
be used.
AIN3 - Discharge Temp - The discharge temperature reading is used to detect
discharge air temperature and to monitor for equipment failure. Once the compressor has activated, the discharge air temperature has 10 minutes to change by
5°F or the controller assumes a mechanical failure has occurred.
AIN4 - Leaving Water Tempand/or Dirty Filter Alarm - Can provide status
only water temperature and/or dirty filter contact closure. If both are used at the
same time, water temperature will be lost when the dirty filter contact is closed.
AIN5 - Lockout - If this input is active all operations are terminated to protect the
equipment.
GND - Common return wire. This point is tied to ground on the WHP
Controller.
2.2.3Analog Output Description
AOUT - Analog Output - This output is not used.
2.2.4Relay Output Descriptions
COM1-3 - Common 1 thru 3. - This ties the common return of the first 3 outputs
together.
OUT1 - Fan On/Off - The fan is enabled to run when this contact is closed.
OUT2 - Reversing Valve or Heat 1 - This output enables the reversing valve if
you have configured the WHP Controller for a compressor and reversing valve
configuration. If the WHP Controller is configured for individual staging of heating and cooling (no reversing valve) then this output enables heating stage 1.
4-6Start-Up and Troubleshooting
WattMaster WHPSection 4
OUT3 - Compressor or Heat 2 - This output enables the compressor if you have
configured the WHP Controller for a compressor and reversing valve configuration. If the WHP Controller is configured for individual staging of heating and
cooling (no reversing valve) then this output enables heating stage 2.
OUT4 - Heat Pump Reset or Cool 1 - This output can be used to reset a compressor that has gone off line. If the WHP Controller is configured for individual
staging of heating and cooling (no reversing valve) then this output enables cooling stage 1.
OUT5 - Aux. Relay or Cool 2 - If you have configured the WHP Controller for a
compressor and reversing valve configuration this output can be configured as
follows:
1.) Stage 2 for cooling and/or heating mode.
2.) Auxiliary scheduling relay. In this mode it can be programmed to follow an
externally broadcast schedule signal.
3.) Auxiliary relay. In this mode it can be used for any function requiring a man-
ual user intervention.
4.) Isolation valve. May be used to initiate opening of an isolation valve in case of
high loop water pressure even if the WHP Controller is satisfied or in an unoccupied mode. In occupied mode this relay operates in conjunction with the
compressor.
If the WHP Controller is configured for individual staging of heating and cooling
(no reversing valve) then this output enables cooling stage 2.
COM4-5 - Common 4 and 5. - This ties the common return of the last 2 outputs
together. Jumper this terminal to COM1-3 if the unit does not have separate
cooling and heating power supplies.
2.2.5RS-485 Communications Connector
This connector provides the connection point for the Local Loop RS-485 communications
loop. The wiring consists of a twisted pair of wires with a shield.
T - RS-485 (+) Communications terminal
SHLD - Common return wire, this point is internally tied to GND on the WHP
Controller.
R - RS-485 (-) Communications terminal
Start-Up and Troubleshooting4-7
WattMaster WHPSection 4
2.2.6 WHP Controller Wiring
Communication LED
Figure 4-4:
Typical WHP Controller Wiring Diagram
4-8Start-Up and Troubleshooting
WattMaster WHPSection 4
3.0Loop Controller
Overview
3.1How It Works
3.1.1Initialization
On system powerup LED2 remains extinguished for five seconds. After this delay, the
LED2 will blink out the address of the controller (Address Switch Setting). The LED2
will then extinguish for another five seconds and then the LED2 will begin blinking a
diagnostic code every ten seconds. This code is described in the troubleshooting section.
The duration of a powerup initialization sequence is roughly thirty seconds.
During this initialization period, the controller retrieves all operating setpoints from its
non-volatile EEPROM memory and initializes all outputs to an OFF condition.
3.1.2Operating Summary
There is a standard set of operating instructions that are continuously performed over and
over during normal Loop Controller operations. They are listed below.
a Read analog inputs for temperatures, pressures and binary contact closures
b Checks for new setpoints from System Manager or Prism Software and keeps the
status values updated for these interfaces.
c Looks for “request to run” broadcast from any installed WHP Controller or from
an on-board binary input.
d. Set all outputs to match calculations for heat rejection or addition.
e. Store data in internal trend log if ready for another log
f. Broadcasts the operating commands to all WHP Controllers.
g. Tests for lead/lag pump changeover if both pumps are off.
h. Repeat steps a-g continuously
Start-Up and Troubleshooting4-9
WattMaster WHPSection 4
3.2Loop Controller Inputs & Outputs
3.2.1Analog Inputs
AIN1 - Return Water Temp - This input accepts a two wire 10K Type III thermistor temperature sensor. The sensor measures 10,000 Ohms @ 77°F. The resistance drops as the temperature increases. The sensor is connected between this
terminal and the GND terminal.
AIN2 - Supply Water Temp - This input accepts a two wire 10K Type III ther mistor temperature sensor. The sensor measures 10,000 Ohms @ 77°F. The resistance drops as the temperature increases. The sensor is connected between this
terminal and the GND terminal.
AIN3 – Proof of Flow/Loop Pressure - This input accepts a differential pressure
contact closure for proof of flow or a 0-50 PSI (0-5VDC) pressure transducer signal.
AIN4 - Outdoor Air Temp - The OA temperature is used to determine if pumps
should be turned on during off periods, to prevent freezing. When the OA temperature is below 40° F, the pumps will be turned on.
AIN5 - Manual Reset Input - Used to restart equipment after alarm condition
has occurred. When this input is shorted to GND by a momentary pushbutton, a
signal to restart is sent.
AIN7 – Phase Loss – If a phase monitor is being used, a normally open contact is
connected here. When a loss of phase is detected, this contact closes shutting
down the Loop Controller.
GND - Common return wire. This point is tied to ground on the Loop Controller.
3.2.2Analog Output
This connector carries a 0-10 volt control signal for the following items:
AOUT1- Pump VFD Signal - If you have selected the variable speed pump option this output signal is used to control the loop pressure.
AOUT2 - Proportional Heat Signal - This output may be used when a modulating signal is required to control heat addition temperature.
GND - Common return wire, this point is tied to GND on the Loop Controller.
4-10Start-Up and Troubleshooting
WattMaster WHPSection 4
3.2.3Binary Output
R1 – Compressor Enable – Energizes the first stage of cooling.
R2 – Main Pump – Energizes the lead water pump.
R3 – Standby Pump – Energizes the standby pump if the main pump fails to
start.
R4 – Alarm Indicator – Energizes when an alarm occurs on the Loop Controller.
R5 – Not Used – This output is not used.
COM 1-3 - Common – 24 VAC from the AHU is connected to this terminal and
is the common for inputs 1 through 3.
COM 4-5 - Common – 24 VAC from the AHU is connected to this terminal and
is the common for inputs 4 and 5.
3.2.4Relay Expansion Board - Outputs
This connector carries the output relay dry contact open/closed signal.
Relays 1-4 - Heat Addition/Rejection Stages - Can be configured to be used for
either stages of heating or cooling of water when required.
Relays 5-8 - Heat Addition/Rejection Stages – Same as above, can be used for
heating or cooling of the water.
3.2.5Analog Input Expansion Board
The following inputs use dry contact open/closed signals.
AIN1 – Fire Alarm Contact - Used to shut down all equipment in case of a
smoke or fire condition.
AIN2 - Request to Run - Used to initiate system start when a water source heat
pump controller other than the WattMaster WHP Controller is used.
Warning: Fire Alarm Contact input must be connected to the AIN1- GND
terminal if it is not used, a jumper must be connected between AIN1
and GND, since this is a normally closed contact input. If this is not
done the system will not operate.
Start-Up and Troubleshooting4-11
WattMaster WHPSection 4
3.2.6Comm Connector - Communications
RS-485 Communications Connector - This connector provides the connection point for
the Local Loop RS-485 communications loop. The wiring consists of a twisted pair of
wires with a shield.
T - RS-485 (+) Communications terminal
SHLD - Common return wire, this point is internally tied to GND on the WHP
Controller.
R - RS-485 (-) Communications terminal
3.2.7Power Terminal
This connector provides power to the Loop Controller
24 VAC - Connect to the “HOT” side of the control transformer.
GND - The grounded side of the control transformer. If the secondary of the con-
trol transformer is not grounded, you must still observe polarity if the transformer powers any other device!
Warning: Connect only the GND terminal to the grounded side of a transformer
Failure to properly observe polarity will result in damage to the
system. Observe polarity at all points in the system.
4-12Start-Up and Troubleshooting
WattMaster WHPSection 4
Local Loo p R S-485
Connect To Next Controller And/Or
MiniLink On Local Loop
9600 Baud
(See Note 3).
Optional
Pressure sensor
Line Voltage
Figure 4-5: Loop Controller Inputs & Outputs
Start-Up and Troubleshooting4-13
WattMaster WHPSection 4
4.0Start-Up
4.1Blink Codes for WHP Controllers
The WHP Controller uses an on board LED to indicate various diagnostic conditions
during powerup and operation. The WHP Unit LED is labeled “COMM”. Starting with
power up the LED blink codes are as follows:
• Off for five seconds
• COMM LED blinks the board address (Address 14 = 14 blinks)
• Five second pause
• Twenty second time delay - LED blinks twenty times
• Status code is repeatedly blinked every ten seconds to indicate controller
status:
PriorityNo. of BlinksStatus
Lowest1Normal Operation
-2Override Active
-3Bad Space Sensor
-4Heat Pump Lockout
Highest5Communication Failure
Figure 4-6: Diagnostic LED Blink Codes
Only the highest priority failure code will be shown. You must correct the highest priority
alarm before other problems will be indicated.
4-14Start-Up and Troubleshooting
WattMaster WHPSection 4
4.2Blink Codes for Loop Controllers
The Loop Controller uses an on board LED to indicate various diagnostic conditions
during powerup and operation. The Loop Controller Unit LED is labeled “LED2”.
Starting with power up the LED blink codes are as follows:
• Off for five seconds
• COMM LED blinks the board address (Address 14 = 14 blinks)
• Five second pause
• Status code is repeatedly blinked every ten seconds to indicate controller
status:
PriorityNo. of BlinksStatus
Lowest1Normal Operation
-2Pump and/or Flow Failure
-3Bad Water Temp Sensor
-4Single Phase Shutdown
-5Water Pressure Alarm
Highest6Fire Alarm
Figure 4-7: Diagnostic LED Blink Codes
Only the highest priority failure code will be shown. You must correct the highest priority
alarm before other problems will be indicated.
4.3 Communications Checklist
• WHP Controllers are addressed from 1 to 30 on each loop except the loop with the
WHP Loop Controller. This loop can only use address 1 thru 29 for the WHP Controllers. WHP Loop Controller is addressed as 30 on the loop it is connected to.
• Power has been cycled after changing addresses
• A multiple loop CommLink II is powered and connected to the communications loop.
• System Manager is connected to one of the local loops.
• The MiniLinks on each local loop are addressed with a unique address 1 thru 30,
depending on the number of loops on your system.
Start-Up and Troubleshooting4-15
WattMaster WHPSection 4
4.4Installation and Commissioning
Information
Familiarize yourself with the installation manual and system wiring diagrams
before installing!
1. Check to see if you have all the correct components for your installation.
2. Establish the location for the CommLink Interface first. This is where your communi-
cation cable will begin.
3. Layout your communication wiring. For systems with more than 30 WHPs or more
than one MiniLink, there are multiple communication loops:
A. The Network Loop - This loop originates at the CommLink and interconnects
MiniLinks together.
B. The Local Loop – This loop originates at the MiniLink. The WHPs, Loop
Controllers and the System Manager are connected to this loop.
Tip: Using the WattMaster color-coded and labeled Communication Cable insures a
quality installation. It also makes your installation much easier and less likely to
have communications wiring errors!
4
. Communication cable must always be shielded – no exceptions!
5. Mount controllers in appropriate locations according to their operating specification.
6. Address controllers according to location and addressing instructions located in the
system manual.
7. With no power connected, wire controller according to wiring diagrams and in
accordance with local codes. Never apply power until you have completed these procedures in accordance to all system instructions.
8. After completing all wiring connections, unplug the terminals for power and commu-
nications. Always unplug the communications loop first and then the power. When
reconnecting the wiring, connect the power first and then the communication loop.
9. Continue step 8 until all devices have been wired and the power and communication
terminals have been unplugged.
4-16Start-Up and Troubleshooting
WattMaster WHPSection 4
10. Install CommLink and power-up. At this point you are ready to begin commissioning
the system. It is preferred, though not necessary, to use a PC with Prism software to
assist in the commissioning process.
11. Start with the first controller on the communication loop or in multiple loop systems;
start with the MiniLink or with the System Manager. Plug in the Communication
terminal then plug in the Power terminal.
12. Observe the LED indicator for the blink codes as outlined in the troubleshooting
section of the manual. The blink code will first verify the address, then the operation.
If the address is incorrect, reset the dipswitch, then reapply power to the controller.
13. After each controller is connected and completes its initialization sequence, use the
PC or System Manager to verify communication to that device. If you cannot communicate, verify wiring, voltages, etc. in accordance with the troubleshooting section
in the system manual. Do not proceed to the next device until you are properly communicating with the current device.
Continue this process until all controllers are connected and properly communicating.
By following the above steps and procedures, your installation will be much faster and
trouble free. Remember that each controller only contains one puff of smoke. Making
sure that all wiring terminations and voltages are correct prior to applying power to a
controller will insure that you don’t use that one puff.
Start-Up and Troubleshooting4-17
WattMaster WHPSection 4
COMM LINK II
TO OTHER MINILINKS
(NETWORK TERMINALS ONLY)
TO OTHER WHP CONTROLLERS
Y
SYSTEM MANAGER POWER SUPPLY
GND
24VAC
POWER
LOOP
A
A
4
3
A
4
Y
E
W
DOG
CPU
A
A
4
3
A
4
Y
CPU
A
A
A
A
Y
4
4
4
2
4
V
A
C
G
N
D
U6
C1
U2
U3
U4
V1V2V3
V5
V4
L1
R6
C9
3
6
M
U8
U9
C7
CX10
CX12
CX14
CX13
X2
INPUTS
+
A
A
A
A
A
RS-485
S
COMM
COMM
U1
COMM
LED1
LED2
R1
U7
VREF ADJ
TEST POINT
C
C
CX15
03/31/04 03:38PM WED
OCCUPIED
NO ALARMS
INTERFACE
(MULTIPLE LOOP)
COMMUNICATIONS
T
SHLD
R
RS-485
S101716 REV. 1
SYSTEM MANAGER
2K
COMM
TSHLDR
LD4
C21
CX1
RN1
1
TB1
T
HLD
R
CX5
U5
LD6
LD7
1
HH
PWR
LD8
RN3
LD9
P1
+VREF
5.11V
EWDOG
RV1
R28
ADDRESS
VDC
RN5
PU1
IN1
D6
IN2
PU2
D7
IN3
PU3
D8
PU4
IN4
D9
PU5
IN5
D11
C10
PU7
GND
D14
GND
C12
U13
AOUT1
AOUT2
AIN7
D15
C17
GND
PJ1
TB3
C20
R26
PJ2
PRESSURE
SENSOR
GND
24VAC
NETWORK
T
R
SH
T
R
SH
Figure 4-8:
Communications Loop Wiring
EXPANSION
D1
CX2
CX3
CX4
RLY1
D2D3D4D5
RLY2RLY3RLY4RLY5
OM1-3
PAL
R1
1
EPROM
RAM
PHILIPS
ADD
1
2
4
8
16
32
TOKEN
NETWORK
SW1
0-5
0-1
VDC
VDC
JP1
C14
U15
C15
PJ3
R2
TUC-5R PLUS
R3
(1 MEG)
YS101816 REV. 2
R4
RN2
R5
OM4-5
TB2
CX6
C2
X1
C3
1
RN4
NE5090NPB3192
0PS
CX8
U10
R7
D10
R10
D13
D12
C11
99
R13
R11
U11
MC34064A
SC1
R15
R19
R22
R24
R25
C13
U12
C16
U14
TB4
D19
GND
R27
D16
V6
D18
D17
POWER
C19
C18
7824CT
24VAC
VR2
VR1
T'STAT
RLY IO BD.
RLY IO BD.
IN1
IN2
IN3
IN4
GND
AOUT1
YS101790
YS101790
ANALOG IN MOD I/O BD.
S101784
REC.
12V
IN1
AIN
2
AIN
3
AIN
4
AIN
5GNDGND
OUT
PRESSURE
SENSOR
S101564
COMM
TSHLDR
LD4
REC.
12V
IN1
AIN
2
AIN
3
AIN
4
AIN
5GNDGND
OUT
PRESSURESENSOR
S101564
8K
RELAY
OUTPUTCOM1-3OUT
1
RAMEPROM
85
COMM
DDRESSADD
RAMEPROM
85
COMM
DDRESSADD
EWDOG
OUT
2OUT
3
OUT
OUT
4OUT
5COM4-5
-5
COMM
TEST
0-5
VDC
PWR
GND
0-1
VDC
24VAC
2K
8K
RELAYOUTPUT
COM1-3
OUT
1
OUT
2
OUT
3
OUT
OUT
4
OUT
5COM4-5
-5
COMM
TEST
0-5
VDC
PWR
GND
0-1
VDC
24VAC
4-18Start-Up and Troubleshooting
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.