Heat Controller, Inc. • 1900 Wellworth Ave. • Jackson, MI 49203 • (517)787-2100 • www.heatcontroller.com
Installation, Operation & Maintenance VMH 30/36 SERIESHeat Controller, Inc.
SAFETY PRECAUTIONS
Please read this installation manual completely before installing the product.
If the power cord is damaged, replacement work shall be performed by authorized personnel only.
Installation work must be performed in accordance with all local and national codes by authorized
personnel only.
Contact an authorized service technician for repair, maintenance or installation of this unit.
All the pictures in the instructions are for explanation purposes only, and may differ from the actual
product you purchased.
The design and specifications are subject to change without prior notice for product improvement.
Consult with the sales agency or manufacturer for details.
The seriousness of safety precautions is classified by the following indications:
WA RNI NG
CAUT ION
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to property.
WARNING
1) Install according to this installation instructions strictly. If installation is defective, it will cause water
leakage, electrical shock fire, and may void the warranty.
2) Use the manufacturer’s specified and supplied parts only
3) Install in a strong and firm location which is able to withstand the unit’s weight. If the strength is
insufficient or installation is not properly done, the units can fall and cause injury.
4) For electrical work, follow all local
An independent circuit and single outlet must be used. If electrical circuit capacity is not enough or a
defect found in electrical work, it may cause electrical shock or fire.
and National electrical codes and these installation instructions.
5) Use the specified cable, connect tightly and clamp the cable so that no external force will be acted
on the terminal. If connection is loose, it may cause excessive heat build up.
6) Wiring
cover is not fixed perfectly, it will cause heat build up at connection point of terminal, fire or electrical shock.
When carrying out piping connection, take care not to let air substances other than the specified
7)
refrigerant go into refrigeration circuit. Otherwise, it will cause lower capacity, abnormal high pressure
in the ref
routing must be properly arranged so that control board cover is fixed properly. If control board
rigeration cycle, explosion and injury.
8) Do not modify the length of the power supply cord or use an extension cord, and do not share the
single outlet with other electrical appliances. Otherwise, it may cause fire or electrical shock.
.
CAUTION
1) This equipment must be properly grounded and installed with and ground leakage current breaker,
otherwise it may cause
2) Do not install the unit in place where leakage of flammable gas may occur. If gas leaks and
accumulates near or surroundings the unit, it may cause fire.
3) Carry out drainage piping as mentioned in installation instructions. If drainage is not properly done,
water may enter the room and damage the furniture.
electrical shock.
2
Heat Controller, Inc. VMH 30/36 SERIESInstallation, Operation & Maintenance
There should not be any heat source near the unit.
There should not be any obstacles blocking the
air circulation.
A place where air circulation in the room is good.
A place where drainage can be easily done.
A place where noise prevention is taken into
consideration.
Do not install the unit near a door way.
Ensure the clearness indicated by arrows
in the figure on the right are adhered to
leaving space away from any walls, ceiling,
or other obstacles.
There should not be any direct sunlight.
If unavoidable, sunlight prevention should be
taken into consideration. Direct su
nlight may
block the ability of the unit to reduce the signal
from the remote controller.
SELECT THE BEST LOCATION
In door unit
Ou tdoo r u nit
If an awning is built over the unit to prevent
direct sunlight or rain, be careful that heat
radiating from the condenser is not obstructed.
There should not be any animals or plants kept
near the unit which could be affected by hot air
discharged.
Ensure the clearances indicated by the arrows on
the right are adhered to, leaving space away from
any walls, fences, plants, or other obstacles.
See outdoor installation precautions on
page 7 for additional information.
NOTE:
1
2
3
4
5
6
7
8
Installation Plate
Clip Anchor
Self-tapping Screw A ST3.9x25
Seal
Drain Joint
Remote controller
Self-tapping Screw B ST2.9x10
1
5-8 ()dep e nding o n model s
5-8 ()dep e nding o n model s
1
1
1
2
1
In addition to the parts above, other parts may need to be purchased locally.
such as copper line sets, etc.
Remote controller holder
ACCES SORIES
Nu mber
Na me of Acc ess ories
Qt y
NOTE
:
opt i onal
par t s
6 inches
8 feet
6 inches
5 inches
2 feet
1 foot
2 feet
1 foot
7 feet
P-Trap
3
Installation, Operation & Maintenance VMH 30/36 SERIESHeat Controller, Inc.
INDOOR SECTION
FIT THE INSTALLATION PLATE
1
NOTE:
The installation plate provided
with the machine may differ from
appliance to appliance.
(Use wall studs for best anchorage)
Fi t th e I nsta llatio n P lat e
1. Fit the installation plate horizontally
on structural parts of the wall with
the appropriate clearance around the
installation plate.
2. Drill holes in the wall according to the
wall structure and corresponding
mounting points on the installation
5 inches (120mm)
or more from
the wall
plate. If the wall is made of brick,
concrete or the like, drill eight 3/16”(5mm)
diameter holes in the wall. Insert Clip
anchor for appropriate mounting screws.
3. Fit the installation plate on the wall
with eight (8) type “A” screws.
NOTE: Dimensions are in inches (mm)
unless otherwise stated.
Ø ” Ø2.6 ( 65)
1.8 (45)”
Pipe hole
3.7 (Ø95)”
1.4 (35)”
6.1 155)”
Correct orientation
of Installation Plate
6 inches (150mm) or more
from the ceiling
6”(150)
1.25 (32)”
4.75ft.(1250)
Model A
16.84 (426)”16.6 (422)”
2.8 (70)”
12.5 (318)”
Model B
Flange
Indoor unit outline
4.75ft.(1450)
3.36ft.(1023)
12.5”(318)
Flange
5.2 (133)”
Ø2.6”(Ø65)
Pipe
hole
1.25 (32)”
5 inches (120mm)
from the wall
”
12.8 (325)
”
1.8 (45)
7.5 (190)”
2.8 (71)”
0.98 (25)”
6.9”(174)
0.79 (20)”
13.4 340)”(
DRILL A HOLE IN THE WALL
2
1. Determine hole positions according to left and right
side of the installation pla
te. The hole center is obtained
by measuring the distance as shown in the diagram above.
2. Drill the piping plate hole with Ø2.55in(65mm) hole-core drill.
3. Drill the piping hole at either the right or the left and the
hole should be slightly slanted to the outdoor side.
4. Always use wall hole conduit when drilling metal grid,
metal plate or the like.
4
Heat Controller, Inc. VMH 30/36 SERIESInstallation, Operation & Maintenance
INDOOR SECTION
CONNECTIVE PIPE AND DRAINAGE INSTALLATION
3
Dr a ina ge
1. Run the drain hose sloping downward.
The figures on the right show improper
installation methods.
2. When conne
insulate the connections, do not let
the drain hose slack.
Co nne cti ve pip e in sta llation
1. For the left-hand and right-hand piping,
remove the pipe cover from the side panel.
2. For the rear-right-hand and rear-left-hand
piping, install the piping as shown.
3. Bundle the tubing, connecting cable, and
drain hose with tape securely, evenly as
shown in Figure on the right.
Because the condensed water from rear
of the indoor unit drains to the ponding
box before drainage through the drain
hose, be sure not to place anything inside
the ponding box.
cting extension drain hose,
CAUT ION
Connect the indoor unit first, then the
outdoor unit.
Do not allow the piping to come out from the
back of the indoor unit.
Be careful not to let the drain hose slack.
Heat insulate both the auxiliary piping.
Be sure that the drain hose is located at
the lowest side of the bundle. Locating at
the upper side can cause drain pan to
overflow inside the unit.
Never intertwine the condensate piping the power
the power
Run the drain hose slopped downward to
drain out the condensed water freel
wire with any other wiring.
y.
In doo r un it installat ion
1. Pass the piping through the hole in the wall.
2. Hook the indoor unit onto the upper portion
of installation plate(Engage the indoor unit with
the upper edge of the installation plate). Ensure
the slots are properly seated on the installation
plate hooks by moving it in left and left.
3. Piping installation can easily be done by placing
a temporary piece of styrofoam between the
unit and the wall. After piping is complete, be
sure to remove the styrofoam.
4. Press the lower left and right side of the unit
against the installation plate until the slots
hook onto and engage wi
wall plate.
th the installation
Insulation
5
Installation, Operation & Maintenance VMH 30/36 SERIESHeat Controller, Inc.
INDOOR SECTION
I
N
D
O
O
R
4
Electri cal wo r k
Electric safety regulations for the initial Installation should meet all local and national electric codes
1. Voltage power should be in the range of 90%~110%of rated voltage.
2. The creepage protector and main power switch should be at least installed in the power circuit
1.5 times the capacity of Max. Current of the unit should be installed in power circuit.
3. Ensure the air conditioner is grounded well.
4. Use the Electrical Connection Diagram located on t
and indoor unit to connect the wire properly.
5. An individual branch circuit and single receptacle used only for this air conditioner must be available.
6. HCI recommends the use of 600V THHN 14 AWG/4 conductor unshielded stranded copper cable,
however NEC always prevails.
Connect the c a ble to the indoor uni t
NOTE:
Before performing any electrical work, turn off the main power to the system.
1. The inside and outside connecting cable can be connected without removing the front grille.
2. Lift the indoor unit panel up, remove the electrical box cover by loosening the screw.
3. Ensure the color of wires of outdoor unit and the terminal Nos. match the indoor ’s
respectively.
4. Wrap those cables not connected with terminals with insulation tape, so that they will not touch
any electrical components. Secure the cable onto the control board with the cord clamp.
CONNECTING THE COMMUNICATION CABLE
he panel of the outdoor unit
U
N
I
T
Panel
Electrical box
cover
Terminal block of indoor unit
G
2(N)
S
1
To outdoor unit
Or
L2
L1
To outdoor unit
S
6
Heat Controller, Inc. VMH 30/36 SERIESInstallation, Operation & Maintenance
OUTDOOR SECTION
OUTDOOR INSALLATION PRECAUTION
1
Install the outdoor unit on a rigid base to prevent increased noise levels and vibration.
Ensure the air outlet is not blocked by any objects such as plants or walls, etc.
If the installation location is exposed to strong winds, ensure the unit is placed lengthwise along
the wall or provide a switchable baffle to block strong wind gusts from entering the unit.
If suspending the unit with a bracket, follow the bracket manufacturer’s installation instructions.
Use a raised concrete pad or concrete blocks to provide a solid base and level surface - securely
anchor the unit down with bolts
In a snowy area, install the outdoor unit on a raised platform higher than drifting snow.
Se ttlemen t o f outdoor unit
Anchor the outdoor unit with a bolt and nut ( 10mm) or tightly and horizontally
on a concrete or rigid mount.
. See table & figure below.
Ø3/8” ØØ5/16”(Ø8mm)
Out d oor unit d i men s ion
in( mm)( L 1xHx W 1)
26. 4 x21 . 3x9. 8
29. 9 x23 . 2x11.2
30. 5 x21 . 4x12 . 2
32. 3 x23 . 4x13 . 0
33. 3 x27 . 6x12 . 6
35. 4 x33 . 9x12 . 4
(67 0 x54 0 x250 )
(76 0 x59 0 x285 )
(77 5 x54 5 x310 )
(82 0 x59 5 x330 )
(84 5 x70 0 x320 )
(90 0 x86 0 x315 )
Mou n tin g d imen s ions
L2( m m)
18. 9 in. ( 481)
20. 9 in. ( 530)
23. 6 in.( 600)
20. 6 in.( 523)
22. 1 in. ( 560)
23. 2 in.( 590)
W2( m m)
10. 9 in.( 276)
11.4 i n.(2 9 0)
12. 6 in.( 320)
13. 4 in. ( 340)
13. 2 in. ( 335)
13. 1 in. ( 333)
DRAIN JOINT INSTALLATION
2
NOTE:
The pictures of the drain joint may very from the actual
part that come with the unit.
Push the seal onto the end of the drain elbow connector (Fig. A),
then insert the drain elbow connector into the hole in the bottom
of the base pan of the unit (Fig. B) until it makes a click sound
and is firmly in place. Add an additional drain hose to direct the
condensate away from the base of the unit by placing a hose
on the end of the hose barb. This drain hose is not included with
the unit and must be purchased.
7
Drain elbow connector
Seal
(A)
Base pan hole
of outdoor unit
(B)
Installation, Operation & Maintenance VMH 30/36 SERIESHeat Controller, Inc.
U
OUTDOOR SECTION
N
REFRIGERANT PIPE CONNECTION
I
T
Fla ring
1. ut a pipe with a pipe cutter,
a little longer than the required measured distance.
2. Remove flare nuts attached to indoor and outdoor unit, then
put them on the copper pipe, having completed burr removal.
3. Flare the ends of the pipe by firmly holding the copper pipe
in a die per the dimensions shown in the table below.
Tighten ing connecti on
.
.
.
3
Use a line set of copper pipe to connect the indoor and outdoor units.
The line set does not come with the unit and must be purchased separately.
Measure the distance between the indoor and outdoor sections. C
Max.
.05”(1.3
.06”(1.6
.07”(1.8
.08”(2.2
.09”(2.4
A in.(mm)
)
.02”(0.7
)
.04”(1.0
)
.04”(1.0
)
.08”(2.0
)
.08”(2.0
Min.
)
)
)
)
)
epending
Ø1/4”(Ф
Ø3/8”(Ф
Ø1/2”(Ф
Ø5/8”(Ф
Ø3/4”(Ф
Outer
diam.
6.35mm)
9.52mm)
12.7mm)
16mm)
9mm)
Indoor unit tubing Flare nut Pipings
Tightening
(255kgf.cm)
(459kgf.cm)
(663kgf.cm)
Outer diam.
in. (mm)
Ø1/4”(Ф
6.35)
Ø3/8”(Ф
9.52)
Ø1/2”(Ф
12.7)
Ø5/8”(Ф
Align pipes to be connected.
Sufficiently tighten the flare nut with fingers,
and then tighten it with a spanner and torque
wrench as shown.
Excessive torque can break nut d
on installation conditions, use torques
provided in the table to the right.
Ø3/4”(Ф
16)
19)
O
90
Bar
Copper pipe
torque
.
11.07
ft lbf
(153kgf.cm)
.
18.44
ft lbf
.
25.82
ft lbf
(357kgf.cm)
33.20
47.95
.
ft lbf
.
ft lbf
Roughness
Oblique
"A"
Bar
Clamp handle
Additional tightening
torque
.
11.79 ft lbf
(163kgf.cm)
.
19.17
ft lbf
(265kgf.cm)
.
26.55
ft lbf
(367kgf.cm)
(479kgf.cm)
(683kgf.cm)
36.65
49.40
.
ft lbf
.
ft lbf
Handle
Burr
CONNECT THE CABLE TO THE OUTDOOR UNIT
4
1. Remove the electrical control board cover from the outdoor unit by loosening the screw.
2. Connect the connective cables to the terminals as identified with their respective matched numbers
on the terminal block of indoor and outdoor units. See the section of the manual called “connecting
the communication cable” on page. 6.
3. Secure the cable onto the control board with the cord clamp.
4. To prevent water from entering the unit, form a loop or p-trap in the cable as ill
diagram on page 3.
5. Wrap unused wires with electrical tape, so they do not touch any other electrical or metal parts.
Terminal block of outdoor unit
Cover
Screw
L1 L2 S L1 L2
To indoo r unit
To power s upply
To indoo r unit
(1)
ustrated in the
L1 L2 S L1 L2
To power s upply
(2)
8
Heat Controller, Inc. VMH 30/36 SERIESInstallation, Operation & Maintenance
OUTDOOR SECTION
AIR PURGING
5
1. Air pur g ing
Air and moisture in the refrigerant system have undesirable effects. Therefore, the indoor unit
and tubing between the indoor and outdoor unit must be leak tested and evacuated to remove
any noncondensables and moisture from the system.
Check that each tube(both l
been properly connected and all wiring for the test run has been completed.
Pipe length and refrigerant amount:
Units are pre-charged for 16.5 ft. (5m) total line set length, additional charge is needed for longer
line sets lengths. Charge adjustments are not required for line sets less than 16.5 ft (5m)
iquid and gas side tubes) between the indoor and outdoor units have
Capacity
Btu/h
30-36k
Pipe Size
Gas (in) Liquid (in)
5/8 (16mm) 3/8(9.52mm)
Standard
Length (ft)
*16.5 (5m)
Max
Elevation (ft)
32 (9.75m)
Total Line Length (ft)
Min. Max.
10 (3m) 82 (25m)
*Unit charge located on rating plate includes enough refrigerant for 16.5 feet of line set.
* Charge adjustment is not required on line set lengths less than 16.5 feet.
Ensure any R-410A refrigerant is added to the unit in liquid form.
CAUTION
Open the valve stem until it hits against
the stop. Do not try to open it further.
Securely tighten the valve stem cap with
a spanner or wrench.
See tightening torque table on page 8 to
properly tighten and torque the valve stem cap.
Outdoor
unit
Packed valve
Refrigerant
A
Gas side
Liquid side
B
Indoor
unit
C
D
Half union
Valve body
2. W hen using the Vacuum Pump
NOTE: Refer to the manifold valve manufacturer’s instructions before use.
1. Completely tighten the flare nuts, A, B, C, D, (see figure
on page 10) connect the manifold valve charge hose to a
rge port of the low pressure valve on the gas side.
cha
2. Connect the charge hose connection to the vacuum
pump.
3. Fully open the handle of the manifold valve.
Lo
4. Operate the vacuum pump to evacuate. After starting
evacuation, slightly loose the flare nut of the low pressure
Compound meter
-29.92 inHg
*(-76cmHg)
Lo Handle
Charge hose
Manifold valve
valve on the gas side and check that the air is
entering. (Operation noise of the vacuum pump changes
and a compound meter indicates 0 instead of minus)
5. After the evacuation is complete, fully close the lo handle
of the manifold valve and stop the operation of the
vacuum pump.
Low pressure valve
Evacuate for 15 minutes and more and check
at the compound meter indicates -29.92inHg(-76cmHg).
th
6. Turn the stem of the low pressure valve B about 45 counter-
O
clockwise for 6~7 seconds after the gas units out, then
tighten the flare nut again. Make sure the pressure display
in the pressure indicator is a little higher than the atmosphere
pressure.
7. Remove the charge hose from the Low pressure charge hose.
8. Fully open the packed valve stems B and A.
9. Securely tighten the cap of the packed valve.
Additional
Refrigerant oz/ft
.4 (40g/m)
Flare nut
Stop
Valve stem
Pressure gauge
Hi Handle
Charge hose
Vacuum pump
Cap
9
Installation, Operation & Maintenance VMH 30/36 SERIESHeat Controller, Inc.
OUTDOOR SECTION
5
3. Sa fety and le akage ch eck
Use soapy water or a leakage detector to check for leaks as follows:
1. Soap water method:
Apply a soap solution water or a liquid neutral detergent onto the
indoor unit connections and outdoor unit connections with a
soft brush to check for leaks in the connections of the piping.
If bubbles room, it indicates that the pipes have leaks.
2. Leak detector
Use the leak detector per the manufacturer’s instructions
to check for leakage.
TEST OPERATION
Cover
CAUTION NOTE:
A: Lo pressure valve B: Hi pressure valve
C and D are ends of indoor unit connection.
Outdoor unit
check point
Indoor unit
check point
D
B
C
A
4. Test r unning
Perform a test run after completing the leak check:
Check that all tubing and wiring have been properly connected.
Check that the gas and liquid side service valves are fully open.
1. Connect the power, press the ON/OFF button on the remote controller to turn the unit on.
2. Use the MODE button to select COOL, HEAT, AUTO and FAN to check if all the functions work
properly.
3. When the ambient temperature is lower than 6217 C), the unit cannot be controlled by the
remote controller to run in cooling mode, manual operation needs to be used.
Hold the panel sides and lift the panel up to a
Press the Manual control button to select the AUTO or COOL, the unit will operate under Forced
AUTO or COOL mode(see User Manual for details).
4. The manual test operation should last about 30 minutes, giving the installing contractor an
opportunity to check that the unit is operating properly and the installation was done successfully.
O
O
F(
n angle until it remains fixed with a clicking sound.
Manual control
Button
AUTO/COOL
10
Heat Controller, Inc. VMH 30/36 SERIESInstallation, Operation & Maintenance
12/2/11
11
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.