General Data
TPR Series ............................................................................................... 5
Performance Data
TPR Series ........................................................................................... 6-10
Airflow Performance
TPR Series ..........................................................................................1
Electrical Data
TPR Series ................................................................................................13
Electric Heater Kits ..................................................................................14-15
Dimensional Data ....................................................................................
T
ypical Installations ......................................................................................18
Accessories ............................................................................................19-26
Typical Wiring ...............................................................................................27
1-12
16-17
Page 3
UNIT FEATURES & BENEFITS—TPR SERIES
4
5
3
These quality features are included in the HEAT CONTROLLER Outdoor Package Heat Pumps
Page 4
UNIT FEATURES & BENEFITS—TPR SERIES
4
Features Below Correspond to Photos on Page 3
1. All models feature Copeland®Scroll®compressors for maximum efficiency and quiet operation.
2. Louvered condenser compartment for protecting the coil against yard hazards and/or weather extremes.
3. One-piece top with a deep flange to help keep water out of the unit.
4. Supply and return air openings feature a one-inch tall flange to prevent water migration into the ductwork.
5. Access panels have “weep holes” and channels to further help manage water run-off.
6. Side and down discharge options available on all models. (Shipped Downflow Standard).
7. Easily accessible blower section complete with slide­out blower. All units feature a system matched indoor coil with low static pressure drop and excellent cooling capacities.
8. Refrigerant connections are conveniently located for easy service diagnostics.
9. Condenser and evaporator coils feature enhanced fins for better heat transfer and rifled copper tubing for greater efficiency.
10. Supplemental electric heat strips up to 10 kW are
available (field or factory installed) for periods of extreme cold temperatures. Single point wiring makes installation even easier.
11. All units feature an internal trap on the condensate line eliminating the need for installing an on-site external trap.
12. Easily accessible control box.
Page 5
5
GENERAL DATA-TPR SERIES
NOMINAL SIZES 2-4 TONS
Model
Cooling Performance
Gross Cooling Capacity Btuh 24400 31400 36600 44500 50000 EER/SEER
Nominal CFM/ARI Rated CFM 800/800 1000/1050 1200/1200 1400/1400 1600/1600 ARI Net Cooling Capacity Btuh 23600 30200 35400 43500 48500 Net Sensible Capacity Btu 17900 22100 26300 31800 36000 Net Latent Capacity Btuh 5700 8100 9100 11700 12500 Net System Power kW 2.14 2.74 3.22 3.96 4.41
2
1
Heating Performance (Heat Pump)
Heating Input Btuh Rating 23000 29000 34200 39500 46000 System Power kW/COP 1.95/3.40 2.44/3.40 2.91/3.40 3.34/3.40 4.11 Low Temp. Btuh Rating 12900 16100 19500 22800 28000 System Power kW/COP 1.89/2.0 2.29/2.00 2.72/2.11 3.18/2.10 3.86/2.08 HSPF (Btu/Watt-hr) 7.7 7.7 7.7 7.7 7.7
Compressor
Qty/Type
Outdoor Sound Rating (dB)
3
Outdoor Coil—Fin Type
Tube Type Rifled Rifled Rifled Rifled Rifled Tube Size in. OD 0.375 0.375 0.375 0.375 0.375 Face Area sq. ft. 14.51 16.32 11.2 16.32 16.32 Rows / Fins per inch 1/22 1/22 2/22 2/22 2/22 Refrigerant Control TXV TXV TXV TXV TXV
Indoor Coil—Fin Type
Tube Type Rifled Rifled Rifled Rifled Rifled Tube Size in. 0.375 0.375 0.375 0.375 0.375 Face Area sq. ft. 5.54 7.39 7.39 7.39 7.39 Rows / Fins per inch 2/15 2/15 2/15 2/15 2/15 Refrigerant Control TXV TXV TXV TXV TXV Drain Connection Qty/Size in. 1/1 1/1 1/1 1/1 1/1
Outdoor Fan—Type
Qty Used/Diameter in. 1/22 1/22 1/22 1/22 1/22 Drive Type/Speeds Direct/1 Direct/1 Direct/1 Direct/1 Direct/1 CFM 2700 2700 2700 3300 3000 Qty Motors-HP 1-1/5 1-1/5 1-1/5 1-1/3 1-1/3 Motor RPM 1075 1075 1075 1075 1075
Indoor Fan—Type
Qty Used/Diameter in. 1/9x7 1/10x9 1/10x9 1/10x9 1/10x9 Drive Type/Speeds Direct/2 Direct/3 Direct/1 Direct/2 Direct/2 Motor Qty 11111 Motor HP 1/4 1/2 1/3 3/4 3/4 Motor RPM 1075 1075 1075 1075 1075 Motor Frame Size 48 48 48 48 48
Filter—Type
Furnished No No No No No (Qty) Size Recommended in. (1) 20x20x1 (1) 24x24x1 (1) 24x24x1 (1) 24x24x1 (1) 24x24x1
Refrigerant Charge Oz. Weights
Net Weight lbs. 391 444 468 505 510 Ship Weight lbs. 401 455 479 516 521
Notes:
1. Cooling performance is rated at 95ºF ambient, 80ºF/67ºF entering dry bulb/wet bulb temperatures. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation in air flow range shown in fan performance tables. Heating performance is at 47ºF/43ºF entering dry bulb/wet bulb (high temp) and 17ºF/15ºF entering dry bulb/wet bulb (low temp) ambient and 70ºF room side temperature. Units are certified and rated per ARI Standard 210/240.
2. EER/SEER are rated ARI condition and accordance with DOE test procedures.
3. Outdoor sound ratings are in accordance with ARI Standard 270.
TPR24C-1K TPR30C-1K TPR36C-1K TPR42C-1K TPR48C-1K
11/13 11/13 11/13 11/13 11/13
1
1/Copeland Scroll
76 76 76 76 78
Louvered
Louvered
Propeller
Forward Curved Centrifugal
Field Supplied
86 93 122 158 150
Page 6
SYSTEM PERFORMANCE
6
COOLING PERFORMANCE DATA—TPR24C-1K
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE
1.5
1.6
1.7
1.8
1.9
2.0
2.1
2.2
2.2
30.0 [8.79]
16.2 [4.75]
1.5
29.2 [8.56]
16.0 [4.69]
1.6
28.2 [8.26]
15.7 [4.60]
1.7
27.1 [7.94]
15.2 [4.45]
1.8
26.1 [7.65]
14.7 [4.31]
1.9
25.1 [7.36]
14.1 [4.13]
2.0
24.3 [7.12]
13.6 [3.99]
2.0
23.7 [6.95]
13.2 [3.87]
2.1
23.4 [6.86]
12.8 [3.75]
2.2
29.1 [8.53]
21.6 [6.33]
1.6
28.2 [8.26]
21.4 [6.27]
1.6
27.2 [7.97]
21.0 [6.15]
1.7
26.1 [7.65]
20.4 [5.98]
1.8
25.0 [7.33]
19.9 [5.83]
1.9
24.0 [7.03]
19.2 [5.63]
2.0
23.1 [6.77]
18.7 [5.48]
2.1
22.5 [6.59]
18.1 [5.30]
2.2
22.2 [6.51]
17.8 [5.22]
2.3
O U T D O O R
D R Y
B U
L
B
T E M P E R A T U R E
°F
[°C]
wbE 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C]
CFM [L/s] 900 [425] 800 [378] 700 [330] 900 [425] 800 [378] 700 [330] 900 [425] 800 [378] 700 [330]
75
[23.9]
80
[26.7]
85
[29.4]
90
[32.2]
95
[35]
100
[37.8]
105
[40.6]
110
[43.3]
115
[46.1]
DR
Total BTUH [kW] Sens BTUH [kW] Power
Total BTUH [kW] Sens BTUH [kW] Power
Total BTUH [kW] Sens BTUH [kW] Power
Total BTUH [kW] Sens BTUH [kW] Power
Total BTUH [kW] Sens BTUH [kW] Power
Total BTUH [kW] Sens BTUH [kW] Power
Total BTUH [kW] Sens BTUH [kW] Power
Total BTUH [kW] Sens BTUH [kW] Power
Total BTUH [kW] Sens BTUH [kW] Power
.19 .16 .11 .19 .16 .11 .19 .16 .11
31.4 [9.20]
18.2 [5.33]
30.7 [9.00]
17.2 [5.04]
1.6
30.5 [8.94]
18.0 [5.28]
29.8 [8.73]
17.0 [4.98]
1.6
29.5 [8.65]
17.6 [5.16]
28.8 [8.44]
16.6 [4.86]
1.7
28.4 [8.32]
17.1 [5.01]
27.8 [8.15]
16.1 [4.72]
1.8
27.3 [8.00]
16.5 [4.84]
26.7 [7.83]
15.6 [4.57]
1.9
26.3 [7.71]
15.9 [4.66]
25.7 [7.53]
15.0 [4.40]
2.0
25.4 [7.44]
15.3 [4.48]
24.9 [7.30]
14.5 [4.25]
2.1
24.8 [7.27]
14.8 [4.34]
24.3 [7.12]
14.0 [4.10]
2.2
24.5 [7.18]
14.4 [4.22]
24.0 [7.03]
13.6 [3.99]
2.3
28.4 [8.32]
20.4 [5.98]
1.5
27.6 [8.09]
20.2 [5.92]
1.6
26.6 [7.80]
19.8 [5.80]
1.7
25.5 [7.47]
19.3 [5.66]
1.8
24.5 [7.18]
18.8 [5.51]
1.9
23.5 [6.89]
18.2 [5.33]
2.0
22.6 [6.62]
17.6 [5.16]
2.1
22.0 [6.45]
17.1 [5.01]
2.2
21.7 [6.36]
16.8 [4.92]
2.2
27.8 [8.15]
19.2 [5.63]
1.5
27.0 [7.91]
19.0 [5.57]
1.6
26.0 [7.62]
18.7 [5.48]
1.7
25.0 [7.33]
18.2 [5.33]
1.8
23.9 [7.00]
17.7 [5.19]
1.9
22.9 [6.71]
17.1 [5.01]
2.0
22.1 [6.48]
16.6 [4.86]
2.0
21.5 [6.30]
16.1 [4.72]
2.1
21.3 [6.24]
15.8 [4.63]
2.2
28.6 [8.38]
23.3 [6.83]
1.5
27.8 [8.15]
23.1 [6.77]
1.6
26.8 [7.85]
22.7 [6.65]
1.7
25.7 [7.53]
22.1 [6.48]
1.8
24.6 [7.21]
21.6 [6.33]
1.9
23.5 [6.89]
20.9 [6.13]
2.0
22.7 [6.65]
20.4 [5.98]
2.1
22.1 [6.48]
19.8 [5.80]
2.2
21.8 [6.39]
19.5 [5.71]
2.3
28.0 [8.21]
22.0 [6.45]
1.5
27.2 [7.97]
21.8 [6.39]
1.6
26.2 [7.68]
21.4 [6.27]
1.7
25.1 [7.36]
20.9 [6.13]
1.8
24.0 [7.03]
20.4 [5.98]
1.9
23.0 [6.74]
19.8 [5.80]
2.0
22.2 [6.51]
19.2 [5.63]
2.1
21.6 [6.33]
18.7 [5.48]
2.1
21.3 [6.24]
18.4 [5.39]
2.2
27.4 [8.03]
20.7 [6.07]
1.5
26.5 [7.77]
20.5 [6.01]
1.6
25.6 [7.50]
20.2 [5.92]
1.7
24.5 [7.18]
19.7 [5.77]
1.8
23.5 [6.89]
19.2 [5.63]
1.9
22.5 [6.59]
18.6 [5.45]
2.0
21.7 [6.36]
18.1 [5.30]
2.0
21.1 [6.18]
17.7 [5.19]
2.1
20.8 [6.10]
17.3 [5.07]
2.2
DR —Depression ratio dbE —Entering air dry bulb wbE—Entering air wet bulb
Total —Total capacity x 1000 BTUH Sens —Sensible capacity x 1000 BTUH Power—KW input
NOTES:
When the entering air dry bulb is other than 80°F [27°C], adjust the sensible
capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].
HEATING PERFORMANCE DATA— TPR24C-1K
IDB 60°F [15.5°C] 70°F [21.1°C] 80°F [26.7°C]
CFM [L/s] 900 [425] 800 [378] 700 [330] 900 [425] 800 [378] 700 [330] 900 [425] 800 [378] 700 [330]
0
O U T D O O R
D R Y
B U
L
B
T E
M
P E R A T U R E
°F
[°C]
[-17.8]
5
[-15]
10
[-12.2]
15
[-9.4]
20
[-6.7]
25
[-3.9]
30
[-1.1]
35
[1.7]
40
[4.4]
45
[7.2]
50
[10]
Total BTUH [kW] Power
Total BTUH [kW] Power
Total BTUH [kW] Power
Total BTUH [kW] Power
Total BTUH [kW] Power
Total BTUH [kW] Power
Total BTUH [kW] Power
Total BTUH [kW] Power
Total BTUH [kW] Power
Total BTUH [kW] Power
Total BTUH [kW] Power
7.8 [2.29]
1.2
9.4 [2.75]
1.3
10.9 [3.19]
1.3
12.4 [3.63]
1.3
13.9 [4.07]
1.3
15.4 [4.51]
1.4
17.0 [4.98]
1.4
18.6 [5.45]
1.4
20.3 [5.95]
1.4
22.2 [6.51]
1.5
24.3 [7.12]
1.5
7.7 [2.26]
1.2
9.3 [2.73]
1.3
10.8 [3.17]
1.3
12.3 [3.60]
1.3
13.8 [4.04]
1.4
15.3 [4.48]
1.4
16.8 [4.92]
1.4
18.4 [5.39]
1.4
20.2 [5.92]
1.5
22.0 [6.45]
1.5
24.1 [7.06]
1.5
7.6 [2.23]
1.3
9.2 [2.70]
1.3
10.7 [3.14]
1.3
12.2 [3.58]
1.4
13.6 [3.99]
1.4
15.1 [4.43]
1.4
16.7 [4.89]
1.4
18.3 [5.36]
1.5
20.0 [5.86]
1.5
21.8 [6.39]
1.5
23.9 [7.00]
1.5
7.1 [2.08]
1.4
8.7 [2.55]
1.4
10.2 [2.99]
1.5
11.7 [3.43]
1.5
13.2 [3.87]
1.5
14.7 [4.31]
1.6
16.3 [4.78]
1.6
17.9 [5.25]
1.6
19.7 [5.77]
1.6
21.5 [6.30]
1.7
23.6 [6.92]
1.7
7.0 [2.05]
1.4
8.6 [2.52]
1.5
10.1 [2.96]
1.5
11.6 [3.40]
1.5
13.1 [3.84]
1.6
14.6 [4.28]
1.6
16.1 [4.72]
1.6
17.7 [5.19]
1.6
19.5 [5.71]
1.7
21.3 [6.24]
1.7
23.4 [6.86]
1.7
7.0 [2.05]
1.5
8.5 [2.49]
1.5
10.0 [2.93]
1.5
11.5 [3.37]
1.5
13.0 [3.81]
1.6
14.4 [4.22]
1.6
16.0 [4.69]
1.6
17.6 [5.16]
1.7
19.3 [5.66]
1.7
21.2 [6.21]
1.7
23.2 [6.80]
1.7
5.8 [1.70]
1.5
7.4 [2.17]
1.6
8.9 [2.61]
1.6
10.4 [3.05]
1.6
11.9 [3.49]
1.7
13.4 [3.93]
1.7
15.0 [4.40]
1.7
16.6 [4.86]
1.7
18.4 [5.39]
1.8
20.3 [5.95]
1.8
22.3 [6.54]
1.8
5.8 [1.70]
1.6
7.3 [2.14]
1.6
8.9 [2.61]
1.6
10.3 [3.02]
1.7
11.8 [3.46]
1.7
13.3 [3.90]
1.7
14.9 [4.37]
1.7
16.5 [4.84]
1.8
18.2 [5.33]
1.8
20.1 [5.89]
1.8
22.1 [6.48]
1.8
5.7 [1.67]
1.6
7.3 [2.14]
1.6
8.8 [2.58]
1.6
10.2 [2.99]
1.7
11.7 [3.43]
1.7
13.2 [3.87]
1.7
14.7 [4.31]
1.8
16.3 [4.78]
1.8
18.1 [5.30]
1.8
19.9 [5.83]
1.8
21.9 [6.42]
1.9
IDB—Indoor air dry bulb [ ] Designates Metric Conversions
Page 7
7
SYSTEM PERFORMANCE
COOLING PERFORMANCE DATA—TPR30C-1K
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE
1.9
2.0
2.2
2.3
2.4
2.5
2.6
2.8
2.9
35.9 [10.52]
19.9 [5.83]
1.9
35.7 [10.46]
19.9 [5.83]
2.0
35.1 [10.29]
19.6 [5.74]
2.1
34.2 [10.02]
19.0 [5.57]
2.3
33.0 [9.67]
18.3 [5.36]
2.4
31.7 [9.29]
17.6 [5.16]
2.5
30.4 [8.91]
16.8 [4.92]
2.6
29.2 [8.56]
16.3 [4.78]
2.7
28.3 [8.29]
15.9 [4.66]
2.8
35.2 [10.32]
26.5 [7.77]
1.9
35.0 [10.26]
26.5 [7.77]
2.1
34.4 [10.08]
26.1 [7.65]
2.2
33.3 [9.76]
25.5 [7.47]
2.3
32.1 [9.41]
24.7 [7.24]
2.4
30.8 [9.03]
23.8 [6.98]
2.5
29.4 [8.62]
23.0 [6.74]
2.7
28.2 [8.26]
22.3 [6.54]
2.8
27.2 [7.97]
21.9 [6.42]
2.9
O U T D O O R
D R Y
B U
B
T E M P E R A T U R E
°F
[°C]
wbE 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C]
CFM [L/s] 1180 [557] 1050 [496] 920 [434] 1180 [557] 1050 [496] 920 [434] 1180 [557] 1050 [496] 920 [434]
DR
Total BTUH [kW]
75
Sens BTUH [kW]
[23.9]
Power Total BTUH [kW]
80
Sens BTUH [kW]
[26.7]
Power Total BTUH [kW]
85
Sens BTUH [kW]
[29.4]
Power Total BTUH [kW]
90
Sens BTUH [kW]
[32.2]
Power
95
[35]
100
[37.8]
105
[40.6]
110
[43.3]
115
[46.1]
Total BTUH [kW] Sens BTUH [kW] Power
Total BTUH [kW] Sens BTUH [kW] Power
Total BTUH [kW] Sens BTUH [kW] Power
Total BTUH [kW] Sens BTUH [kW] Power
Total BTUH [kW] Sens BTUH [kW] Power
L
.19 .16 .11 .19 .16 .11 .19 .16 .11
37.6 [11.02]
22.4 [6.56]
36.8 [10.79]
21.2 [6.21]
1.9
37.4 [10.96]
22.4 [6.56]
36.6 [10.73]
21.2 [6.21]
2.1
36.7 [10.76]
22.0 [6.45]
35.9 [10.52]
20.8 [6.10]
2.2
35.7 [10.46]
21.4 [6.27]
34.9 [10.23]
20.2 [5.92]
2.3
34.5 [10.11]
20.6 [6.04]
33.7 [9.88]
19.5 [5.71]
2.4
33.2 [9.73]
19.7 [5.77]
32.4 [9.50]
18.6 [5.45]
2.5
31.8 [9.32]
18.9 [5.54]
31.1 [9.11]
17.9 [5.25]
2.7
30.6 [8.97]
18.3 [5.36]
29.9 [8.76]
17.3 [5.07]
2.8
29.6 [8.67]
17.9 [5.25]
29.0 [8.50]
16.9 [4.95]
2.9
34.4 [10.08]
25.0 [7.33]
1.9
34.2 [10.02]
25.0 [7.33]
2.0
33.6 [9.85]
24.7 [7.24]
2.2
32.6 [9.55]
24.1 [7.06]
2.3
31.4 [9.20]
23.3 [6.83]
2.4
30.1 [8.82]
22.5 [6.59]
2.5
28.8 [8.44]
21.7 [6.36]
2.6
27.6 [8.09]
21.1 [6.18]
2.7
26.6 [7.80]
20.7 [6.07]
2.9
33.6 [9.85]
23.6 [6.92]
1.9
33.5 [9.82]
23.6 [6.92]
2.0
32.8 [9.61]
23.2 [6.80]
2.1
31.9 [9.35]
22.7 [6.65]
2.3
30.7 [9.00]
21.9 [6.42]
2.4
29.4 [8.62]
21.2 [6.21]
2.5
28.1 [8.24]
20.5 [6.01]
2.6
26.9 [7.88]
19.9 [5.83]
2.7
26.0 [7.62]
19.5 [5.71]
2.8
34.1 [9.99]
28.8 [8.44]
1.9
33.9 [9.94]
28.8 [8.44]
2.1
33.2 [9.73]
28.4 [8.32]
2.2
32.2 [9.44]
27.8 [8.15]
2.3
31.0 [9.09]
27.0 [7.91]
2.4
29.6 [8.67]
26.1 [7.65]
2.5
28.3 [8.29]
25.3 [7.41]
2.6
27.1 [7.94]
24.7 [7.24]
2.8
26.1 [7.65]
24.3 [7.12]
2.9
INTRODUCTION
33.3 [9.76]
27.2 [7.97]
1.9
33.1 [9.70]
27.2 [7.97]
2.0
32.5 [9.52]
26.9 [7.88]
2.1
31.5 [9.23]
26.3 [7.71]
2.3
30.3 [8.88]
25.5 [7.47]
2.4
29.0 [8.50]
24.7 [7.24]
2.5
27.7 [8.12]
23.9 [7.00]
2.6
26.5 [7.77]
23.3 [6.83]
2.7
25.5 [7.47]
22.9 [6.71]
2.9
32.5 [9.52]
25.6 [7.50]
1.9
32.4 [9.50]
25.6 [7.50]
2.0
31.7 [9.29]
25.3 [7.41]
2.1
30.8 [9.03]
24.7 [7.24]
2.2
29.6 [8.67]
24.0 [7.03]
2.4
28.3 [8.29]
23.3 [6.83]
2.5
27.0 [7.91]
22.5 [6.59]
2.6
25.9 [7.59]
21.9 [6.42]
2.7
24.9 [7.30]
21.6 [6.33]
2.8
DR —Depression ratio dbE —Entering air dry bulb wbE—Entering air wet bulb
Total —Total capacity x 1000 BTUH Sens —Sensible capacity x 1000 BTUH Power—KW input
NOTES:
When the entering air dry bulb is other than 80°F [27°C], adjust the sensible
capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].
HEATING PERFORMANCE DATA—TPR30C-1K
O U T D O O R
D R Y
B U
B
T E
M
P E R A T U R E
°F
[°C]
L
CFM [L/s]
0
[-17.8]
5
[-15]
10
[-12.2]
15
[-9.4]
20
[-6.7]
25
[-3.9]
30
[-1.1]
35
[1.7]
40
[4.4]
45
[7.2]
50
[10]
IDB
Total BTUH [kW] Power
Total BTUH [kW] Power
Total BTUH [kW] Power
Total BTUH [kW] Power
Total BTUH [kW] Power
Total BTUH [kW] Power
Total BTUH [kW] Power
Total BTUH [kW] Power
Total BTUH [kW] Power
Total BTUH [kW] Power
Total BTUH [kW] Power
1180 [557] 1050 [496] 920 [434] 1180 [557] 1050 [496] 920 [434] 1180 [557] 1050 [496] 920 [434]
9.7 [2.84]
1.5
11.8 [3.46]
1.5
13.8 [4.04]
1.5
15.7 [4.60]
1.6
17.6 [5.16]
1.6
19.5 [5.71]
1.7
21.5 [6.30]
1.7
23.6 [6.92]
1.7
25.8 [7.56]
1.8
28.1 [8.24]
1.8
30.7 [9.00]
1.8
60°F [15.5°C]
9.7 [2.84]
1.5
11.7 [3.43]
1.5
13.7 [4.02]
1.6
15.6 [4.57]
1.6
17.5 [5.13]
1.6
19.4 [5.69]
1.7
21.3 [6.24]
1.7
23.4 [6.86]
1.8
25.5 [7.47]
1.8
27.9 [8.18]
1.8
30.4 [8.91]
1.9
9.6 [2.81]
1.5
11.6 [3.40]
1.6
13.6 [3.99]
1.6
15.4 [4.51]
1.6
17.3 [5.07]
1.7
19.2 [5.63]
1.7
21.1 [6.18]
1.7
23.2 [6.80]
1.8
25.3 [7.41]
1.8
27.6 [8.09]
1.9
30.2 [8.85]
1.9
8.7 [2.55]
1.7
10.7 [3.14]
1.7
12.7 [3.72]
1.8
14.7 [4.31]
1.8
16.6 [4.86]
1.9
18.5 [5.42]
1.9
20.4 [5.98]
1.9
22.5 [6.59]
2.0
24.7 [7.24]
2.0
27.1 [7.94]
2.0
29.6 [8.67]
2.1
70°F [21.1°C]
8.6 [2.52]
1.7
10.7 [3.14]
1.8
12.6 [3.69]
1.8
14.5 [4.25]
1.8
16.4 [4.81]
1.9
18.3 [5.36]
1.9
20.3 [5.95]
2.0
22.3 [6.54]
2.0
24.5 [7.18]
2.0
26.8 [7.85]
2.1
29.4 [8.62]
2.1
8.5 [2.49]
1.8
10.6 [3.11]
1.8
12.5 [3.66]
1.8
14.4 [4.22]
1.9
16.3 [4.78]
1.9
18.1 [5.30]
2.0
20.1 [5.89]
2.0
22.1 [6.48]
2.0
24.3 [7.12]
2.1
26.6 [7.80]
2.1
29.1 [8.53]
2.1
8.0 [2.34]
1.9
10.1 [2.96]
1.9
12.0 [3.52]
2.0
14.0 [4.10]
2.0
15.9 [4.66]
2.0
17.8 [5.22]
2.1
19.8 [5.80]
2.1
21.8 [6.39]
2.1
24.0 [7.03]
2.2
26.4 [7.74]
2.2
28.9 [8.47]
2.3
80°F [26.7°C]
7.9 [2.32]
1.9
10.0 [2.93]
1.9
11.9 [3.49]
2.0
13.8 [4.04]
2.0
15.7 [4.60]
2.1
17.6 [5.16]
2.1
19.6 [5.74]
2.1
21.6 [6.33]
2.2
23.8 [6.98]
2.2
26.1 [7.65]
2.3
28.7 [8.41]
2.3
7.8 [2.29]
1.9
9.9 [2.90]
2.0
11.8 [3.46]
2.0
13.7 [4.02]
2.1
15.6 [4.57]
2.1
17.5 [5.13]
2.1
19.4 [5.69]
2.2
21.4 [6.27]
2.2
23.6 [6.92]
2.2
25.9 [7.59]
2.3
28.4 [8.32]
2.3
IDB—Indoor air dry bulb [ ] Designates Metric Conversions
Page 8
SYSTEM PERFORMANCE
8
COOLING PERFORMANCE DATA—TPR36C-1K
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE
2.4
2.5
2.6
2.8
2.9
3.0
3.1
3.2
3.4
44.3 [12.98]
23.7 [6.95]
2.4
43.2 [12.66]
22.9 [6.71]
2.5
41.9 [12.28]
22.4 [6.56]
2.6
40.5 [11.87]
21.9 [6.42]
2.7
39.0 [11.43]
21.5 [6.30]
2.9
37.5 [10.99]
21.0 [6.15]
3.0
36.2 [10.61]
20.5 [6.01]
3.1
35.0 [10.26]
19.8 [5.80]
3.2
34.1 [9.99]
18.9 [5.54]
3.3
43.0 [12.60]
31.7 [9.29]
2.4
41.9 [12.28]
30.9 [9.06]
2.5
40.6 [11.90]
30.2 [8.85]
2.6
39.1 [11.46]
29.7 [8.70]
2.8
37.5 [10.99]
29.2 [8.56]
2.9
36.0 [10.55]
28.7 [8.41]
3.0
34.5 [10.11]
28.1 [8.24]
3.1
33.3 [9.76]
27.3 [8.00]
3.2
32.4 [9.50]
26.3 [7.71]
3.4
O U T D O O R
D R Y
B U
L
B
T E
M
P E R A T U R E
°F
[°C]
wbE 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C]
CFM [L/s] 1350 [637] 1200 [566] 1050 [496] 1350 [637] 1200 [566] 1050 [496] 1350 [637] 1200 [566] 1050 [496]
75
[23.9]
80
[26.7]
85
[29.4]
90
[32.2]
95
[35]
100
[37.8]
105
[40.6]
110
[43.3]
115
[46.1]
DR
Total BTUH [kW] Sens BTUH [kW] Power
Total BTUH [kW] Sens BTUH [kW] Power
Total BTUH [kW] Sens BTUH [kW] Power
Total BTUH [kW] Sens BTUH [kW] Power
Total BTUH [kW] Sens BTUH [kW] Power
Total BTUH [kW] Sens BTUH [kW] Power
Total BTUH [kW] Sens BTUH [kW] Power
Total BTUH [kW] Sens BTUH [kW] Power
Total BTUH [kW] Sens BTUH [kW] Power
.19 .16 .11 .19 .16 .11 .19 .16 .11
46.3 [13.57]
26.6 [7.80]
45.3 [13.28]
25.1 [7.36]
2.4
45.2 [13.25]
25.8 [7.56]
44.2 [12.95]
24.4 [7.15]
2.6
43.9 [12.87]
25.1 [7.36]
42.9 [12.57]
23.8 [6.98]
2.7
42.4 [12.43]
24.6 [7.21]
41.4 [12.13]
23.3 [6.83]
2.8
40.8 [11.96]
24.1 [7.06]
39.9 [11.69]
22.8 [6.68]
2.9
39.3 [11.52]
23.6 [6.92]
38.4 [11.25]
22.3 [6.54]
3.0
37.8 [11.08]
23.0 [6.74]
37.0 [10.84]
21.7 [6.36]
3.2
36.6 [10.73]
22.2 [6.51]
35.8 [10.49]
21.0 [6.15]
3.3
35.7 [10.46]
21.3 [6.24]
34.9 [10.23]
20.1 [5.89]
3.4
42.1 [12.34]
29.9 [8.76]
2.4
41.0 [12.02]
29.2 [8.56]
2.5
39.7 [11.63]
28.5 [8.35]
2.6
38.2 [11.20]
28.0 [8.21]
2.7
36.7 [10.76]
27.6 [8.09]
2.8
35.2 [10.32]
27.1 [7.94]
3.0
33.8 [9.91]
26.5 [7.77]
3.1
32.6 [9.55]
25.8 [7.56]
3.2
31.7 [9.29]
24.9 [7.30]
3.3
41.1 [12.05]
28.2 [8.26]
2.3
40.1 [11.75]
27.5 [8.06]
2.5
38.8 [11.37]
26.9 [7.88]
2.6
37.3 [10.93]
26.4 [7.74]
2.7
35.8 [10.49]
26.0 [7.62]
2.8
34.4 [10.08]
25.5 [7.47]
2.9
33.0 [9.67]
25.0 [7.33]
3.0
31.8 [9.32]
24.3 [7.12]
3.2
30.9 [9.06]
23.4 [6.86]
3.3
41.4 [12.13]
33.4 [9.79]
2.4
40.3 [11.81]
32.6 [9.55]
2.5
38.9 [11.40]
31.9 [9.35]
2.7
37.4 [10.96]
31.4 [9.20]
2.8
35.8 [10.49]
30.9 [9.06]
2.9
34.3 [10.05]
30.4 [8.91]
3.0
32.9 [9.64]
29.8 [8.73]
3.1
31.6 [9.26]
29.0 [8.50]
3.3
30.7 [9.00]
28.0 [8.21]
3.4
40.4 [11.84]
31.5 [9.23]
2.4
39.4 [11.55]
30.8 [9.03]
2.5
38.0 [11.14]
30.2 [8.85]
2.6
36.6 [10.73]
29.7 [8.70]
2.7
35.0 [10.26]
29.2 [8.56]
2.9
33.5 [9.82]
28.7 [8.41]
3.0
32.1 [9.41]
28.1 [8.24]
3.1
30.9 [9.06]
27.4 [8.03]
3.2
30.0 [8.79]
26.5 [7.77]
3.3
39.5 [11.58]
29.7 [8.70]
2.4
38.5 [11.28]
29.0 [8.50]
2.5
37.2 [10.90]
28.4 [8.32]
2.6
35.7 [10.46]
27.9 [8.18]
2.7
34.2 [10.02]
27.5 [8.06]
2.8
32.8 [9.61]
27.0 [7.91]
2.9
31.4 [9.20]
26.5 [7.77]
3.1
30.2 [8.85]
25.8 [7.56]
3.2
29.3 [8.59]
25.0 [7.33]
3.3
DR —Depression ratio dbE —Entering air dry bulb wbE—Entering air wet bulb
Total —Total capacity x 1000 BTUH Sens —Sensible capacity x 1000 BTUH Power—KW input
NOTES:
When the entering air dry bulb is other than 80°F [27°C], adjust the sensible
capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].
HEATING PERFORMANCE DATA—TPR36C-1K
O U
T D O O R
D R Y
B U
L B
T E M P E R A
T U R E
°F
[°C]
CFM [L/s]
0
[-17.8]
5
[-15]
10
[-12.2]
15
[-9.4]
20
[-6.7]
25
[-3.9]
30
[-1.1]
35
[1.7]
40
[4.4]
45
[7.2]
50
[10]
IDB
Total BTUH [kW] Power
Total BTUH [kW] Power
Total BTUH [kW] Power
Total BTUH [kW] Power
Total BTUH [kW] Power
Total BTUH [kW] Power
Total BTUH [kW] Power
Total BTUH [kW] Power
Total BTUH [kW] Power
Total BTUH [kW] Power
Total BTUH [kW] Power
1350 [637] 1200 [566] 1050 [496] 1350 [637] 1200 [566] 1050 [496] 1350 [637] 1200 [566] 1050 [496]
13.9 [4.07]
1.8
15.8 [4.63]
1.8
17.6 [5.16]
1.9
19.4 [5.69]
1.9
21.2 [6.21]
2.0
23.0 [6.74]
2.0
25.1 [7.36]
2.1
27.3 [8.00]
2.1
29.9 [8.76]
2.2
32.8 [9.61]
2.2
36.3 [10.64]
2.3
60°F [15.5°C]
13.8 [4.04]
1.8
15.7 [4.60]
1.9
17.5 [5.13]
1.9
19.2 [5.63]
2.0
21.0 [6.15]
2.0
22.8 [6.68]
2.1
24.8 [7.27]
2.1
27.1 [7.94]
2.2
29.6 [8.67]
2.2
32.6 [9.55]
2.3
35.9 [10.52]
2.3
13.6 [3.99]
1.8
15.5 [4.54]
1.9
17.3 [5.07]
1.9
19.1 [5.60]
2.0
20.8 [6.10]
2.0
22.6 [6.62]
2.1
24.6 [7.21]
2.1
26.8 [7.85]
2.2
29.4 [8.62]
2.2
32.3 [9.47]
2.3
35.6 [10.43]
2.3
13.0 [3.81]
2.0
14.9 [4.37]
2.1
16.7 [4.89]
2.1
18.5 [5.42]
2.2
20.3 [5.95]
2.2
22.1 [6.48]
2.3
24.1 [7.06]
2.3
26.4 [7.74]
2.4
29.0 [8.50]
2.4
31.9 [9.35]
2.5
35.4 [10.37]
2.5
70°F [21.1°C]
12.9 [3.78]
2.1
14.8 [4.34]
2.1
16.6 [4.86]
2.2
18.3 [5.36]
2.2
20.1 [5.89]
2.3
21.9 [6.42]
2.3
23.9 [7.00]
2.4
26.2 [7.68]
2.4
28.7 [8.41]
2.5
31.7 [9.29]
2.5
35.0 [10.26]
2.6
12.7 [3.72]
2.1
14.7 [4.31]
2.2
16.4 [4.81]
2.2
18.2 [5.33]
2.3
19.9 [5.83]
2.3
21.7 [6.36]
2.4
23.7 [6.95]
2.4
25.9 [7.59]
2.5
28.5 [8.35]
2.5
31.4 [9.20]
2.6
34.7 [10.17]
2.6
12.1 [3.55]
2.3
14.1 [4.13]
2.4
15.9 [4.66]
2.4
17.7 [5.19]
2.5
19.4 [5.69]
2.5
21.3 [6.24]
2.6
23.3 [6.83]
2.6
25.6 [7.50]
2.7
28.1 [8.24]
2.7
31.1 [9.11]
2.8
34.5 [10.11]
2.8
80°F [26.7°C]
12.0 [3.52]
2.4
14.0 [4.10]
2.4
15.8 [4.63]
2.5
17.5 [5.13]
2.5
19.3 [5.66]
2.6
21.1 [6.18]
2.6
23.1 [6.77]
2.6
25.3 [7.41]
2.7
27.9 [8.18]
2.7
30.8 [9.03]
2.8
34.2 [10.02]
2.8
11.9 [3.49]
2.4
13.8 [4.04]
2.4
15.6 [4.57]
2.5
17.3 [5.07]
2.5
19.1 [5.60]
2.6
20.9 [6.13]
2.6
22.9 [6.71]
2.7
25.1 [7.36]
2.7
27.6 [8.09]
2.8
30.6 [8.97]
2.8
33.9 [9.94]
2.9
IDB—Indoor air dry bulb [ ] Designates Metric Conversions
Page 9
SYSTEM PERFORMANCE
9
COOLING PERFORMANCE DATA—TPR42C-1K
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE
3.1
3.2
3.4
3.6
3.7
3.9
4.0
4.2
4.3
54.9 [16.09]
29.6 [8.67]
3.1
51.8 [15.18]
28.1 [8.24]
3.2
49.7 [14.57]
27.0 [7.91]
3.4
48.3 [14.16]
26.3 [7.71]
3.5
47.4 [13.89]
25.8 [7.56]
3.7
46.8 [13.72]
25.5 [7.47]
3.8
46.1 [13.51]
25.1 [7.36]
4.0
45.2 [13.25]
24.8 [7.27]
4.1
43.7 [12.81]
24.2 [7.09]
4.3
53.3 [15.62]
38.9 [11.40]
3.1
50.0 [14.65]
37.2 [10.90]
3.2
47.8 [14.01]
36.1 [10.58]
3.4
46.4 [13.60]
35.2 [10.32]
3.6
45.5 [13.33]
34.7 [10.17]
3.7
44.8 [13.13]
34.3 [10.05]
3.9
44.1 [12.92]
33.9 [9.94]
4.0
43.2 [12.66]
33.5 [9.82]
4.2
41.6 [12.19]
32.9 [9.64]
4.3
O U
D O O R
D R Y
B U
B
E M P E R A
U R E
°F
[°C]
wbE 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C]
CFM [L/s] 1580 [746] 1400 [661] 1220 [576] 1580 [746] 1400 [661] 1220 [576] 1580 [746] 1400 [661] 1220 [576]
DR
Total BTUH [kW]
75
Sens BTUH [kW]
[23.9]
Power Total BTUH [kW]
80
T
L
T
T
[26.7]
85
[29.4]
90
[32.2]
95
[35]
100
[37.8]
105
[40.6]
110
[43.3]
115
[46.1]
Sens BTUH [kW] Power
Total BTUH [kW] Sens BTUH [kW] Power
Total BTUH [kW] Sens BTUH [kW] Power
Total BTUH [kW] Sens BTUH [kW] Power
Total BTUH [kW] Sens BTUH [kW] Power
Total BTUH [kW] Sens BTUH [kW] Power
Total BTUH [kW] Sens BTUH [kW] Power
Total BTUH [kW] Sens BTUH [kW] Power
.19 .16 .11 .19 .16 .11 .19 .16 .11
57.5 [16.85]
33.3 [9.76]
56.2 [16.47]
31.4 [9.20]
3.1
54.2 [15.88]
31.6 [9.26]
53.0 [15.53]
29.8 [8.73]
3.3
52.0 [15.24]
30.4 [8.91]
50.8 [14.89]
28.7 [8.41]
3.4
50.5 [14.80]
29.6 [8.67]
49.4 [14.48]
27.9 [8.18]
3.6
49.6 [14.54]
29.0 [8.50]
48.5 [14.21]
27.4 [8.03]
3.7
49.0 [14.36]
28.6 [8.38]
47.9 [14.04]
27.0 [7.91]
3.9
48.3 [14.16]
28.3 [8.29]
47.2 [13.83]
26.7 [7.83]
4.1
47.3 [13.86]
27.8 [8.15]
46.3 [13.57]
26.3 [7.71]
4.2
45.8 [13.42]
27.2 [7.97]
44.8 [13.13]
25.7 [7.53]
4.4
52.1 [15.27]
36.8 [10.79]
3.1
48.9 [14.33]
35.2 [10.32]
3.2
46.7 [13.69]
34.1 [9.99]
3.4
45.3 [13.28]
33.3 [9.76]
3.5
44.5 [13.04]
32.8 [9.61]
3.7
43.8 [12.84]
32.4 [9.50]
3.8
43.2 [12.66]
32.0 [9.38]
4.0
42.2 [12.37]
31.7 [9.29]
4.1
40.7 [11.93]
31.1 [9.11]
4.3
51.0 [14.95]
34.6 [10.14]
3.0
47.8 [14.01]
33.1 [9.70]
3.2
45.7 [13.39]
32.1 [9.41]
3.3
44.3 [12.98]
31.3 [9.17]
3.5
43.5 [12.75]
30.9 [9.06]
3.6
42.8 [12.54]
30.5 [8.94]
3.8
42.2 [12.37]
30.2 [8.85]
3.9
41.2 [12.07]
29.8 [8.73]
4.1
39.8 [11.66]
29.3 [8.59]
4.2
51.4 [15.06]
41.3 [12.10]
3.1
48.2 [14.13]
39.6 [11.61]
3.2
45.9 [13.45]
38.4 [11.25]
3.4
44.5 [13.04]
37.6 [11.02]
3.6
43.6 [12.78]
37.0 [10.84]
3.7
42.9 [12.57]
36.6 [10.73]
3.9
42.3 [12.40]
36.3 [10.64]
4.0
41.3 [12.10]
35.8 [10.49]
4.2
39.7 [11.63]
35.3 [10.35]
4.3
50.3 [14.74]
39.0 [11.43]
3.1
47.1 [13.80]
37.4 [10.96]
3.2
44.9 [13.16]
36.3 [10.64]
3.4
43.5 [12.75]
35.5 [10.40]
3.5
42.6 [12.48]
35.0 [10.26]
3.7
42.0 [12.31]
34.6 [10.14]
3.8
41.3 [12.10]
34.3 [10.05]
4.0
40.4 [11.84]
33.9 [9.94]
4.1
38.9 [11.40]
33.3 [9.76]
4.3
49.2 [14.42]
36.7 [10.76]
3.0
46.0 [13.48]
35.2 [10.32]
3.2
43.9 [12.87]
34.2 [10.02]
3.3
42.5 [12.46]
33.4 [9.79]
3.5
41.7 [12.22]
32.9 [9.64]
3.6
41.0 [12.02]
32.6 [9.55]
3.8
40.4 [11.84]
32.3 [9.47]
3.9
39.5 [11.58]
31.9 [9.35]
4.1
38.0 [11.14]
31.4 [9.20]
4.2
DR —Depression ratio dbE —Entering air dry bulb wbE—Entering air wet bulb
Total —Total capacity x 1000 BTUH Sens —Sensible capacity x 1000 BTUH Power—KW input
NOTES:
When the entering air dry bulb is other than 80°F [27°C], adjust the sensible
capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].
HEATING PERFORMANCE DATA—TPR42C-1K
O U T D O O R
D R Y
B U
B
T E
M
P E R A T U R E
°F
[°C]
L
CFM [L/s]
0
[-17.8]
5
[-15]
10
[-12.2]
15
[-9.4]
20
[-6.7]
25
[-3.9]
30
[-1.1]
35
[1.7]
40
[4.4]
45
[7.2]
50
[10]
IDB
Total BTUH [kW] Power
Total BTUH [kW] Power
Total BTUH [kW] Power
Total BTUH [kW] Power
Total BTUH [kW] Power
Total BTUH [kW] Power
Total BTUH [kW] Power
Total BTUH [kW] Power
Total BTUH [kW] Power
Total BTUH [kW] Power
Total BTUH [kW] Power
1580 [746] 1400 [661] 1220 [576] 1580 [746] 1400 [661] 1220 [576] 1580 [746] 1400 [661] 1220 [576]
16.0 [4.69]
2.2
18.0 [5.28]
2.3
20.3 [5.95]
2.3
22.9 [6.71]
2.4
25.6 [7.50]
2.4
28.5 [8.35]
2.5
31.4 [9.20]
2.5
34.2 [10.02]
2.6
37.0 [10.84]
2.6
39.5 [11.58]
2.7
41.8 [12.25]
2.7
60°F [15.5°C]
15.8 [4.63]
2.2
17.8 [5.22]
2.3
20.1 [5.89]
2.4
22.7 [6.65]
2.4
25.4 [7.44]
2.5
28.2 [8.26]
2.5
31.1 [9.11]
2.6
33.9 [9.94]
2.6
36.6 [10.73]
2.7
39.2 [11.49]
2.7
41.5 [12.16]
2.8
15.7 [4.60]
2.3
17.7 [5.19]
2.3
20.0 [5.86]
2.4
22.5 [6.59]
2.4
25.2 [7.39]
2.5
28.0 [8.21]
2.6
30.8 [9.03]
2.6
33.6 [9.85]
2.7
36.3 [10.64]
2.7
38.8 [11.37]
2.8
41.1 [12.05]
2.8
14.4 [4.22]
2.5
16.4 [4.81]
2.6
18.7 [5.48]
2.6
21.3 [6.24]
2.7
24.1 [7.06]
2.7
26.9 [7.88]
2.8
29.8 [8.73]
2.8
32.6 [9.55]
2.9
35.4 [10.37]
2.9
38.0 [11.14]
3.0
40.3 [11.81]
3.0
70°F [21.1°C]
14.3 [4.19]
2.6
16.3 [4.78]
2.6
18.6 [5.45]
2.7
21.1 [6.18]
2.7
23.8 [6.98]
2.8
26.7 [7.83]
2.8
29.5 [8.65]
2.9
32.4 [9.50]
2.9
35.1 [10.29]
3.0
37.6 [11.02]
3.0
39.9 [11.69]
3.1
14.2 [4.16]
2.6
16.1 [4.72]
2.7
18.4 [5.39]
2.7
20.9 [6.13]
2.8
23.6 [6.92]
2.8
26.4 [7.74]
2.9
29.3 [8.59]
2.9
32.1 [9.41]
3.0
34.8 [10.20]
3.0
37.3 [10.93]
3.1
39.6 [11.61]
3.1
13.4 [3.93]
2.8
15.4 [4.51]
2.9
17.7 [5.19]
2.9
20.3 [5.95]
3.0
23.0 [6.74]
3.0
25.9 [7.59]
3.1
28.8 [8.44]
3.1
31.6 [9.26]
3.2
34.4 [10.08]
3.3
36.9 [10.81]
3.3
39.2 [11.49]
3.4
80°F [26.7°C]
13.3 [3.90]
2.9
15.2 [4.45]
2.9
17.6 [5.16]
3.0
20.1 [5.89]
3.0
22.8 [6.68]
3.1
25.7 [7.53]
3.1
28.5 [8.35]
3.2
31.3 [9.17]
3.3
34.1 [9.99]
3.3
36.6 [10.73]
3.4
38.9 [11.40]
3.4
13.1 [3.84]
2.9
15.1 [4.43]
3.0
17.4 [5.10]
3.0
19.9 [5.83]
3.1
22.6 [6.62]
3.1
25.4 [7.44]
3.2
28.3 [8.29]
3.2
31.1 [9.11]
3.3
33.8 [9.91]
3.4
36.3 [10.64]
3.4
38.5 [11.28]
3.5
IDB—Indoor air dry bulb [ ] Designates Metric Conversions
Page 10
SYSTEM PERFORMANCE
10
COOLING PERFORMANCE DATA—TPR48C-1K
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE
3.3
3.5
3.7
3.9
4.0
4.2
4.4
4.5
4.7
58.6 [17.17]
32.1 [9.41]
3.3
57.3 [16.79]
31.7 [9.29]
3.5
55.9 [16.38]
31.1 [9.11]
3.6
54.4 [15.94]
30.3 [8.88]
3.8
52.9 [15.50]
29.5 [8.65]
4.0
51.5 [15.09]
28.7 [8.41]
4.2
50.2 [14.71]
27.9 [8.18]
4.3
49.1 [14.39]
27.3 [8.00]
4.5
48.2 [14.13]
27.0 [7.91]
4.7
57.1 [16.73]
42.7 [12.51]
3.3
55.8 [16.35]
42.2 [12.37]
3.5
54.3 [15.91]
41.5 [12.16]
3.7
52.7 [15.44]
40.7 [11.93]
3.8
51.2 [15.01]
39.7 [11.63]
4.0
49.7 [14.57]
38.8 [11.37]
4.2
48.3 [14.16]
37.9 [11.11]
4.4
47.2 [13.83]
37.3 [10.93]
4.5
46.3 [13.57]
36.9 [10.81]
4.7
O
U
T
D
O
O
R
D
R
Y
B
U
B
T
E M
P
E
R
A
T
U
R
E
°F
[°C]
wbE 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C]
CFM [L/s] 1800 [850] 1600 [755] 1400 [661] 1800 [850] 1600 [755] 1400 [661] 1800 [850] 1600 [755] 1400 [661]
DR
Total BTUH [kW]
75
Sens BTUH [kW]
[23.9]
Power Total BTUH [kW]
80
Sens BTUH [kW]
[26.7]
Power Total BTUH [kW]
85
Sens BTUH [kW]
[29.4]
Power Total BTUH [kW]
90
Sens BTUH [kW]
[32.2]
Power
95
[35]
100
[37.8]
105
[40.6]
110
[43.3]
115
[46.1]
Total BTUH [kW] Sens BTUH [kW] Power
Total BTUH [kW] Sens BTUH [kW] Power
Total BTUH [kW] Sens BTUH [kW] Power
Total BTUH [kW] Sens BTUH [kW] Power
Total BTUH [kW] Sens BTUH [kW] Power
L
.19 .16 .11 .19 .16 .11 .19 .16 .11
61.3 [17.97]
36.1 [10.58]
60.0 [17.58]
34.1 [9.99]
3.4
60.0 [17.58]
35.7 [10.46]
58.7 [17.20]
33.7 [9.88]
3.5
58.5 [17.14]
35.0 [10.26]
57.2 [16.76]
33.0 [9.67]
3.7
56.9 [16.68]
34.1 [9.99]
55.7 [16.32]
32.2 [9.44]
3.9
55.4 [16.24]
33.2 [9.73]
54.1 [15.86]
31.3 [9.17]
4.1
53.9 [15.80]
32.2 [9.44]
52.7 [15.44]
30.4 [8.91]
4.2
52.5 [15.39]
31.4 [9.20]
51.3 [15.03]
29.6 [8.67]
4.4
51.3 [15.03]
30.7 [9.00]
50.2 [14.71]
29.0 [8.50]
4.6
50.5 [14.80]
30.3 [8.88]
49.3 [14.45]
28.7 [8.41]
4.8
55.9 [16.38]
40.3 [11.81]
3.3
54.6 [16.00]
39.9 [11.69]
3.4
53.1 [15.56]
39.3 [11.52]
3.6
51.6 [15.12]
38.4 [11.25]
3.8
50.0 [14.65]
37.5 [10.99]
4.0
48.6 [14.24]
36.6 [10.73]
4.1
47.2 [13.83]
35.8 [10.49]
4.3
46.1 [13.51]
35.2 [10.32]
4.5
45.2 [13.25]
34.9 [10.23]
4.7
54.6 [16.00]
38.0 [11.14]
3.2
53.3 [15.62]
37.6 [11.02]
3.4
51.9 [15.21]
37.0 [10.84]
3.6
50.4 [14.77]
36.2 [10.61]
3.7
48.9 [14.33]
35.3 [10.35]
3.9
47.5 [13.92]
34.5 [10.11]
4.1
46.2 [13.54]
33.7 [9.88]
4.3
45.1 [13.22]
33.2 [9.73]
4.4
44.2 [12.95]
32.8 [9.61]
4.6
54.2 [15.88]
44.8 [13.13]
3.3
52.9 [15.50]
44.4 [13.01]
3.5
51.4 [15.06]
43.7 [12.81]
3.6
49.8 [14.59]
42.8 [12.54]
3.8
48.3 [14.16]
41.8 [12.25]
4.0
46.8 [13.72]
40.9 [11.99]
4.2
45.4 [13.31]
40.0 [11.72]
4.3
44.3 [12.98]
39.4 [11.55]
4.5
43.4 [12.72]
39.0 [11.43]
4.7
53.0 [15.53]
42.3 [12.40]
3.2
51.7 [15.15]
41.9 [12.28]
3.4
50.3 [14.74]
41.2 [12.07]
3.6
48.7 [14.27]
40.4 [11.84]
3.8
47.2 [13.83]
39.5 [11.58]
3.9
45.7 [13.39]
38.6 [11.31]
4.1
44.4 [13.01]
37.8 [11.08]
4.3
43.3 [12.69]
37.2 [10.90]
4.5
42.4 [12.43]
36.9 [10.81]
4.6
51.8 [15.18]
39.9 [11.69]
3.2
50.5 [14.80]
39.5 [11.58]
3.4
49.1 [14.39]
38.8 [11.37]
3.6
47.6 [13.95]
38.1 [11.17]
3.7
46.1 [13.51]
37.2 [10.90]
3.9
44.7 [13.10]
36.4 [10.67]
4.1
43.4 [12.72]
35.6 [10.43]
4.2
42.3 [12.40]
35.0 [10.26]
4.4
41.4 [12.13]
34.7 [10.17]
4.6
DR —Depression ratio dbE —Entering air dry bulb wbE—Entering air wet bulb
Total —Total capacity x 1000 BTUH Sens —Sensible capacity x 1000 BTUH Power—KW input
NOTES:
When the entering air dry bulb is other than 80°F [27°C], adjust the sensible
capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].
HEATING PERFORMANCE DATA—TPR48C-1K
O U T D O O R
D R Y
B U
L B
T E
M
P E R A T U R E
°F
[°C]
CFM [L/s]
0
[-17.8]
5
[-15]
10
[-12.2]
15
[-9.4]
20
[-6.7]
25
[-3.9]
30
[-1.1]
35
[1.7]
40
[4.4]
45
[7.2]
50
[10]
IDB
Total BTUH [kW] Power
Total BTUH [kW] Power
Total BTUH [kW] Power
Total BTUH [kW] Power
Total BTUH [kW] Power
Total BTUH [kW] Power
Total BTUH [kW] Power
Total BTUH [kW] Power
Total BTUH [kW] Power
Total BTUH [kW] Power
Total BTUH [kW] Power
1800 [850] 1600 [755] 1400 [661] 1800 [850] 1600 [755] 1400 [661] 1800 [850] 1600 [755] 1400 [661]
15.1 [4.43]
2.6
18.3 [5.36]
2.6
21.8 [6.39]
2.7
25.5 [7.47]
2.7
29.3 [8.59]
2.8
33.0 [9.67]
2.9
36.6 [10.73]
2.9
39.8 [11.66]
3.0
42.7 [12.51]
3.0
45.0 [13.19]
3.1
46.5 [13.63]
3.2
60°F [15.5°C]
14.9 [4.37]
2.6
18.1 [5.30]
2.7
21.6 [6.33]
2.7
25.3 [7.41]
2.8
29.0 [8.50]
2.8
32.7 [9.58]
2.9
36.3 [10.64]
3.0
39.5 [11.58]
3.0
42.3 [12.40]
3.1
44.6 [13.07]
3.2
46.1 [13.51]
3.2
14.8 [4.34]
2.6
17.9 [5.25]
2.7
21.4 [6.27]
2.8
25.0 [7.33]
2.8
28.8 [8.44]
2.9
32.4 [9.50]
3.0
35.9 [10.52]
3.0
39.1 [11.46]
3.1
41.9 [12.28]
3.1
44.2 [12.95]
3.2
45.7 [13.39]
3.3
14.3 [4.19]
3.0
17.5 [5.13]
3.1
21.0 [6.15]
3.1
24.7 [7.24]
3.2
28.5 [8.35]
3.3
32.3 [9.47]
3.3
35.8 [10.49]
3.4
39.1 [11.46]
3.5
41.9 [12.28]
3.5
44.2 [12.95]
3.6
45.8 [13.42]
3.6
70°F [21.1°C]
14.2 [4.16]
3.1
17.3 [5.07]
3.1
20.8 [6.10]
3.2
24.5 [7.18]
3.3
28.3 [8.29]
3.3
32.0 [9.38]
3.4
35.5 [10.40]
3.4
38.7 [11.34]
3.5
41.5 [12.16]
3.6
43.8 [12.84]
3.6
45.4 [13.31]
3.7
14.1 [4.13]
3.1
17.2 [5.04]
3.2
20.6 [6.04]
3.2
24.3 [7.12]
3.3
28.0 [8.21]
3.4
31.7 [9.29]
3.4
35.2 [10.32]
3.5
38.4 [11.25]
3.6
41.2 [12.07]
3.6
43.4 [12.72]
3.7
45.0 [13.19]
3.8
13.4 [3.93]
3.4
16.6 [4.86]
3.4
20.1 [5.89]
3.5
23.9 [7.00]
3.5
27.6 [8.09]
3.6
31.4 [9.20]
3.7
34.9 [10.23]
3.7
38.2 [11.20]
3.8
41.0 [12.02]
3.9
43.3 [12.69]
3.9
44.9 [13.16]
4.0
80°F [26.7°C]
13.3 [3.90]
3.4
16.5 [4.84]
3.5
20.0 [5.86]
3.5
23.6 [6.92]
3.6
27.4 [8.03]
3.7
31.1 [9.11]
3.7
34.6 [10.14]
3.8
37.9 [11.11]
3.9
40.7 [11.93]
3.9
42.9 [12.57]
4.0
44.5 [13.04]
4.0
13.2 [3.87]
3.5
16.3 [4.78]
3.5
19.8 [5.80]
3.6
23.4 [6.86]
3.7
27.2 [7.97]
3.7
30.8 [9.03]
3.8
34.3 [10.05]
3.8
37.5 [10.99]
3.9
40.3 [11.81]
4.0
42.5 [12.46]
4.0
44.1 [12.92]
4.1
IDB—Indoor air dry bulb [ ] Designates Metric Conversions
Page 11
1033 [488]
INDOOR AIRFLOW PERFORMANCE—208 VOLTS
NOTE: Effect of electric heat strip on airflow performance is negligible.
[ ] Designates Metric Conversions
11
920 960 995
AIRFLOW PERFORMANCE-TPR SERIES
External Static Pressure—Inches W.C. [kPa]
CFM [L/s] Air Delivery/RPM/Watts—208 Volts Side Discharge—Wet Coil
0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17]
Motor
Speed
Motor
HP [W] &
# of Speeds
Blower Size/
CFM 675 [319] 657 [310] 634 [299] 602 [284] 560 [264] 505 [238] 435 [205]
RPM 695 785 870 905 940 980 1020
Low
9x7
CFM 898 [424] 861 [406] 822 [388] 777 [367] 721 [340] 651 [307] 562 [265]
RPM 940 965 995 1020 1045 1070 1090
Watts 221 214 203 191 171 163 149
High
Motor
2 Speed
1/4 HP [186]
Watts 292 278 266 253 239 221 199
820 865 905 940 975
775
1059 [500] 1032 [487] 996 [470] 950 [448] 896 [423] 832 [393]
CFM 1076 [508]
RPM 730
Watts 356 349 341 331 320 305 287
Low
CFM 1222 [577] 1197 [565] 1179 [556] 1162 [548] 1137 [537] 1097 [518]
RPM 765 810 855 890
Medium
10x9
2 Speed
1/2 HP [372]
Watts 423 415 407 397 386 370 351
Motor
CFM 1514 [715] 1461 [690] 1415 [668] 1370 [647] 1322 [624] 1266 [597] 1197 [565]
RPM 895 930 965 985 1005 1025 1045
Watts 538 514 493 473 454 434 412
High
CFM 1222 [577] 1201 [567] 1173 [554] 1137 [537] 1090 [514] 1030 [486] 954 [450]
RPM 785 805 830 870 905 950 990
High
10x9
1 Speed
1/3 HP [248]
355 352 346 340 331 320 306
CFM 1455 [687] 1431 [675] 1396 [659] 1360 [642] 1315 [621] 1285 [606] 1241 [586]
Watts
Motor
RPM 824 856 889 931 968 1009 1041
Watts 268 280 288 303 311 325 331
Low
10x9
3/4 HP [559]
CFM 1559 [736] 1530 [722] 1488 [702] 1454 [686] 1417 [669] 1375 [649] 1336 [631]
RPM 870 893 932 968 1007 1036 1072
High
Motor
2 Speed
321 327 338 351 364 371 381
Watts
CFM 1675 [791] 1658 [782] 1610 [760] 1580 [746] 1535 [724] 1491 [704] 1422 [671]
RPM 923 944 979 1013 1045 1077 1098
Watts 390 401 412 425 433 440 432
Low
10x9
CFM 1770 [835] 1751 [826] 1706 [805] 1672 [789] 1624 [766] 1555 [734] 1463 [690]
RPM 966 989 1018 1050 1078 1100 1115
High
Motor
2 Speed
3/4 HP [559]
Watts 454 466 473 486 490 481 460
Manufacturer
Recommended
Air-Flow Range
(Min/Max) CFM
from
Motor
Speed
Factory
Cooling
Nominal
Capacity
Tons [kW]
[271/319 L/s]
700 CFM/900 CFM
High
2.0 [7.03]
[413/531 L/s]
875 CFM/1125 CFM
Low
2.5 [8.79]
[496/637 L/s]
1050 CFM/1350 CFM
Low
3.0 [10.55]
[578/743 L/s]
1225 CFM/1575 CFM
Low
3.5 [12.31]
[496/802 L/s]
1350 CFM/1700 CFM
Low
4.0 [14.07]
Page 12
AIRFLOW PERFORMANCE-TPR SERIES
INDOOR AIRFLOW PERFORMANCE—230 VOLTS
[ ] Designates Metric Conversions
NOTE: Effect of electric heat strip on airflow performance is negligible.
12
1116 [527]
1000 1020 1035
.07 [.017]
1600 [775]
External Static Pressure—Inches W.C. [kPa]
CFM [L/s] Air Delivery/RPM/Watts—230 Volts Side Discharge—Wet Coil
0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17]
Motor
Speed
Motor
HP [W] &
# of Speeds
Blower Size/
CFM 771 [364] 751 [354] 725 [342] 691 [326] 645 [304] 584 [276] 546 [258]
RPM 825 870 910 950 985 1010 1030
Low
9x7
CFM 946 [446] 922 [435] 882 [416] 830 [392] 769 [363] 701 [331] 630 [297]
RPM 990 1015 1035 1055 1070 1085 1100
Watts 253 242 230 217 204 189 181
High
Motor
2 Speed
1/4 HP [186]
Watts 315 303 288 273 257 241 226
870 910 950 975 1000
815
1182 [558] 1157 [546] 1128 [532] 1091 [515] 1044 [493] 983 [464]
CFM 1206 [569]
RPM 760
Watts 419 406 394 381 368 353 334
Low
CFM 1411 [666] 1368 [646] 1327 [626] 1285 [606] 1238 [584] 1183 [558]
RPM 865 900 935 970
Watts 498 498 481 464 447 431 391
Medium
10x9
2 Speed
1/2 HP [373]
CFM 1641 [774] 1577 [744] 1515 [715] 1455 [687] 1393 [657] 1329 [627] 1262 [596]
Motor
RPM 980 1000 1020 1035 1050 1065 1080
High
CFM 1391 [656] 1357 [640] 1312 [619] 1258 [594] 1201 [567] 1145 [540] 1093 [516]
Watts 589 565 543 523 503 481 456
10x9
428 419 406 392 378 365 355
CFM 1467 [692] 1439 [679] 1408 [665] 1360 [642] 1331 [628] 1287 [607] 1259 [594]
RPM 835 875 915 940 965 985 1000
Watts
High
Motor
1 Speed
1/3 HP [249]
RPM 831 854 894 932 972 1005 1042
Watts 276 282 297 307 319 326 341
Low
10x9
3/4 HP [559]
CFM 1550 [732] 1520 [717] 1486 [701] 1449 [684] 1407 [664] 1382 [652] 1337 [631]
RPM 867 890 930 974 1003 1039 1073
High
Motor
2 Speed
317 323 339 355 362 377 385
Watts
CFM 1692 [799] 1661 [784] 1633 [771] 1589 [750] 1560 [736] 1512 [714] 1442 [681]
RPM 931 950 982 1018 1054 1082 1103
Watts 404 409 424 434 450 453 443
Low
10x9
1010 1043 1073 1096 1111
CFM 1748 [825] 1718 [811] 1686 [796] 1647 [777] 1616 [763] 1543 [728] 1472 [695]
RPM 955 978
High
Motor
2 Speed
3/4 HP [559]
Watts 440 446 462 475 484 473 459
Manufacturer
Recommended
Air-Flow Range
(Min/Max) CFM
from
Motor
Speed
Factory
Cooling
Nominal
Capacity
Tons [kW]
[271/319 L/s]
700 CFM/900 CFM
High
2.0 [7.03]
875 CFM/1125 CFM
2.5
[413/531 L/s]
Low
[8.79]
[496/637 L/s]
1050 CFM/1350 CFM
High
3.0 [10.55]
[578/743 L/s]
1225 CFM/1575 CFM
Low
3.5 [12.31]
[496/802 L/s]
1350 CFM/1700 CFM
Low
4.0 [14.07]
CFM [L/s] 600 [283] 800 [378] 1000 [472] 1200 [566] 1400 [661]
Pressure Drop—Inches W.C. [kPa] .00 .01 [.002] .02 [.005] .03 [.007] .05 [.012]
DOWN DISCHARGE PRESSURE DROP (ADD TO EXTERNAL STATIC PRESSURE)
Page 13
ELECTRICAL DATA – TPR SERIES
13
ELECTRICAL DATA
TPR24C-1K TPR30C-1K TPR36C-1K TPR42C-1K TPR48C-1K
Unit Information
Unit Operating Voltage Range 187-253 187-253 187-253 187-253 187-253 Minimum Circuit Ampacity 17/17 21/21 24/24 32/32 37/37 Maximum Overcurrent Protection Device 25/25 30/30 35/35 45/45 50/50
Compressor
Quantity 1 1 1 1 1 Volts 208/230 208/230 208/230 208/230 208/230 Phase 1 1 1 1 1 HP 2 2 1/2 3 3 1/2 4 RPM 3450 3450 3450 3450 3450 Amps (RLA) 10.9/10.9 13.5/13.5 16/16 17.9/17.9 22/22 Amps (LRA) 54/54 72.5/72.5 88/88 95/95 137/137
Condenser Fan Motor
Quantity 1 1 1 1 1 Volts 208/230 208/230 208/230 208/230 208/230 Phase 1 1 1 1 1 HP 1/5 1/5 1/5 1/3 1/3 Amps (FLA) 1.3 1.3 1.3 2 2 Amps (LRA) 2.2 2.2 2.2 3.9 3.9
Evaporator Fan Motor
Quantity 1 1 1 1 1 Volts 208/230 208/230 208/230 208/230 208/230 Phase 1 1 1 1 1 HP 1/4 1/2 1/3 3/4 3/4 Amps (FLA) 1.5 2.4 Amps (LRA) 2.4 5.1 2.5 0 0
1.7 6.8 6.8
Page 14
WARNING
ONLY ELECTRIC HEATER KITS SUPPLIED BY THIS MANU­FACTURER AS DESCRIBED IN THIS PUBLICATION HAVE BEEN DESIGNED, TESTED, AND EVALUATED BY A NATION­ALLY RECOGNIZED SAFETY TESTING AGENCY FOR USE WITH THIS UNIT. USE OF ANY OTHER MANUFACTURED ELECTRIC HEATERS INSTALLED WITHIN THIS UNIT MAY CAUSE HAZARDOUS CONDITIONS RESULTING IN PROP­ERTY DAMAGE, FIRE, BODILY INJURY OR DEATH.
ELECTRIC HEATER KITS—TPR SERIES
14
Unit Model Application Electric Heater Kit Models
TPR24C-1K
TPR30C-1K
TPR36C-1K
TPR42C-1K
TPR48C-1K
RXQJ-A05J (208-240 volt, 1-ph, 5kW) RXQJ-A10J (208-240 volt, 1-ph, 10kW) RXQJ-A05J (208-240 volt, 1-ph, 5kW) RXQJ-A10J (208-240 volt, 1-ph, 10kW) RXQJ-A10J (208-240 volt, 1-ph, 10kW) RXQJ-A15J (208-240 volt, 1-ph, 15kW) RXQJ-B10J (208-240 volt, 1-ph, 10kW) RXQJ-B15J (208-240 volt, 1-ph, 15kW) RXQJ-B10J (208-240 volt, 1-ph, 10kW) RXQJ-B15J (208-240 volt, 1-ph, 15kW)
Page 15
ELECTRIC HEATER KITS—TPR SERIES
15
@ 240 V
Min./Max.
Over Current
@ 208 V
Protective Device Size
Heat Pump
Heater Kit
Separate Power Supply For Both Unit and Heater Kit
Min./Max.
Ampacity
208-240 V
Min. Circuit
Size
208/240V
Max. Fuse
Min. Ckt.
Ampacity
208/240V
17/17 20/25 20/25
22/25 25/25
44/50 45/50
@ 240 V
Min./Max.
Over Current
@ 208 V
Protective Device Size
Heat Pump
Heater Kit
Single Power Supply For Both Unit and Heater Kit
Min./Max.
Ampacity
@ 208-240 V
Unit Min. Ckt.
Amp.
Heater
@ 208-240 V
Heater
KBTU/Hr
@ 208-240 V
Rated
No. of
Heater kW
@ 208-240 V
Steps
Sequence
7.2/9.6
3.6/4.8
2—1
No. of
Elements
208-240 VOLT, SINGLE PHASE, 60 HZ, AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION
A10J 2 24.56/32.75 34.6/40.0 60/67 60/60 70/70
A05J 1 12.28/16.38 17.3/20.0 39/42 40/40 45/45
A05J 1 1 3.6/4.8 12.28/16.38 17.3/20.0 43/46 45/50 50/50 22/25 25/25
RXQJ-
Unit
Model
Heater Kit
Nominal kW
No TPR.
No Heat 17/17 20/25 20/25
24C-1K
No Heat 21/21 25/30 25/30 21/21 25/30 25/30
30C-1K
A10J 2 2 7.2/9.6 24.56/32.75 34.6/40.0 64/71 70/70 80/80 44/50 45/50
No Heat 24/24 30/35 30/35 24/24 30/35 30/35
A10J 2 2 7.2/9.6 24.56/32.75 34.6/40.0 67/74 70/70 80/80 44/50 45/50
A15J 3 2 10.8/14.4 36.84/49.13 51.9/60.0 88/99 90/90 100/100 65/75 70/80
36C-1K
B10J 2 2 7.2/9.6 24.56/32.75 34.6/40.0 74/81 80/80 90/90 44/50 45/50
No Heat 31/31 35/45 35/45 31/31 35/45 35/45
42C-1K
B15J 3 2 10.8/14.4 36.84/49.13 51.9/60.0 96/106 100/100 110/110 65/75 70/80
No Heat 36/36 45/50 45/50 36/36 45/50 45/50
B10J 2 2 7.2/9.6 24.56/32.75 34.6/40.0 79/86 80/90 90/90 44/50 45/50
B15J 3 2 10.8/14.4 36.84/49.13 51.9/60.0 101/111 110/110 125/125 65/75 70/80
48C-1K
Page 16
[ ] Designates Metric Conversions[ ] Designates Metric Conversions
UNIT DIMENSIONS—TPR SERIES
16
UNIT DIMENSIONS SELF-CONTAINED AIR CONDITIONERS
OUTDOOR FAN GRILLE AND COMPRESSOR ACCESS
FILTER ACCESS PANEL (FOR UNIT MOUNTED FILTER ACCESSORY)
OUTDOOR COIL PROTECTIVE GRILLE
THREADED PVC CONDENSATE DRAIN CONNECTION (
3
/
"
[19.05 mm] N.P.T.)
4
29% 2%
CORNER WEIGHTS
% OF TOTAL
UNIT WEIGHT
CONTROL ACCESS PANEL
LIQUID PRESSURE SERVICE PORT
SUCTION PRESSURE SERVICE PORT
THERMOSTAT WIRING ENTRANCE
BLOWER/ EVAPORATOR ACCESS PANEL
ELECTRICAL POWER
20% 2%
30% 2%
ENTRANCE
SIDE RETURN DUCT OPENING
SIDE SUPPLY DUCT OPENING
21% 2%
TOP VIEW
4719/32
"
[1209 mm]
OUTDOOR FAN GRILLE & COMPRESSOR ACCESS
13
50
/16
[1290 mm]
BOTTOM VIEW
1
45
/16
"
[1145 mm]
INSIDE
BOTTOM RETURN DUCT
"
OPENING
14
[362 mm]
TYP.
13
/16
3
[97 mm]
1
/4
"
"
[497 mm]
9
19
/16
"
5
4
/16
"
[95 mm]
13/16
[30 mm]
3
15
/8
[391 mm]
"
TYP.
"
3
3
/16
[97 mm]
1
1
/2
"
[38 mm]
TYP.
7
49
/16
"
[1256 mm]
INSIDE
BOTTOM SUPPLY DUCT OPENING
"
Page 17
THERMOSTAT
17
WIRE ENTRANCE
1
1
/8
"
[28.6 mm]
255/16
"
[643 mm]
3
10
/16
"
[259 mm]
1
/16
"
5
[129 mm]
UNIT DIMENSIONS—TPR SERIES
SIDE VIEW SIDE VIEW
FILTER ACCESS PANEL (FOR UNIT MOUNTED FILTER ACCESSORY)
527/16
3
/4
4
[121 mm]
"
ELECTRICAL POWER ENTRANCE
BLOWER/ EVAPORATOR ACCESS PANEL
[1332 mm]
"
OUTDOOR COIL PROTECTIVE GRILLE
FRONT VIEW
THREADED PVC CONDENSATED DRAIN CONNECTION (3/4 N.P.T.)
IMPORTANT:
INSTALLATION MUST NOT INTERFERE WITH DRAINAGE OPENINGS IN BOTTOM OF UNIT UNDER OUTDOOR COIL.
471/2
"
[1207 mm]
SUCTION PRESSURE SERVICE PORT
11
22
/16
[576 mm]
BACK VIEW
CONTROL ACCESS PANEL
7
/8
"
SIDE SUPPLY DUCT OPENING
LIQUID PRESSURE SERVICE PORT
5
/16
"
7
[186 mm]
"
3
13
/4
[349 mm]
4
[113 mm]
"
1
/2
8
[216 mm]
7
/16
"
TYP.
15
[381 mm]
"
SHOWN WITH DUCT COVERS REMOVED.
IMPORTANT:
Model Number Height “A”
UNIT MUST BE LEVEL TO PREVENT WATER MIGRATION.
TPR24
TPR30, 36,
42, 48
3515/16
41
4
[124 mm]
7
/16" [138 mm]
5
"
14
[360 mm]
TYP.
191/8
[486 mm]
3
/16
"
"
SIDE RETURN DUCT OPENING
[ ] Designates Metric Conversions
Page 18
TYPICAL INSTALLATIONS
[ ] Designates Metric Conversions[ ] Designates Metric Conversions
18
Page 19
ACCESSORY EQUIPMENT
19
Accessory
Description
Roofcurbs
Supply & Return Diffusers RXRN-BD15
Economizers (Downflow Only)
Economizers (Sideflow Only) RXRD-CCM10 (Fully Modulating)
Fresh Air Damper
Rectangular to Round Transition (Downflow)
Filter Kit RXRY-B01 High Pressure Control RXAB-A04 Outdoor Thermostat RXPT-A01 Low Ambient Control RXPZ-C01 or RXPZ-F01 Duct Adapter Sideflow Square to Round Transition RXMC-BA01
COMMON SUPPLY/RETURN CONCENTRIC AIR DIFFUSER
ACCESSORIES
Accessory Model No.
RXQG-AAA14 (14" [356 mm] Height)
RXRE-CAA30 (3 Position) RXRD-CAM10 (Fully Modulating)
RXRF-FAB1 (Motorized-35%) RXRF-FAA1 (Fixed-35%)
RXMC-CA02 (16" [406 mm] Ducts) RXMC-CA03 (18" [457 mm] Ducts)
SUPPLY/RETURN DIFFUSER
Designed to convert a side by side or an over and under arrange­ment into a concentric distribution of air. The diffuser is flush mounted, completely insulated, assembled, and internally baffled to provide four way supply air distribution with a center return. To make the assembly complete and ready to fit into a 2' [0.61 m] x 4' [1.22 m] suspended ceiling grid, the diffuser includes adjustable supply louvers, hanging rings, anti-sweat gasket, and round flanges for use with flexible ducts.
Model No.
RXRN-
BD15
Diameter
Inches [mm]
16 [406] 90 [40.82]
Shipping Wt.
Lbs. [kg]
Dimension A Inches [mm]
201/2 [521]
NOTE: The location of the combination supply and return diffuser should
NOTE: The location of the combination supply and return diffuser should
not exceed 10 feet [3.05 m] above the floor level for units @ 1000 CFM
not exceed 10 feet [3.05 m] above the floor level for units @ 1000 CFM [472 L/s] or less and 12 [3.66 m] to 14 feet [4.27 m] above the floor level
[472 L/s] or less and 12 [3.66 m] to 14 feet [4.27 m] above the floor level for units with CFM greater than 1000 [472 L/s]. If the diffuser is installed
for units with CFM greater than 1000 [472 L/s]. If the diffuser is installed with a greater distance than recommended above, the supply air may
with a greater distance than recommended above, the supply air may become stratified above the required comfort area causing uncomforta-
become stratified above the required comfort area causing uncomforta­ble conditions.
ble conditions.
AIRFLOW/PRESSURE DROP INFORMATION (INCHES W.C. [kPa])
Accessory
Approximate CFM [L/s]-Supply Air
1575 [743] 1800 [850]1300 [614]
.12 [.030].07 [.017] .10 [.024]Plenum & Supply/Return Duct .16 [.040].09 [.022] .13 [.032]Diffuser .11 [.027].06 [.015] .09 [.022]Economizer .17 [.042]
2200 [1038]
.17 [.042] .24 [.060]
SUPPLY AIR/PERFORMANCE
Diffuser Airflow CFM [L/s] Range of Throw Ft. [m]
14 [4.27]-16 [4.88]800 [378]-1200 [566] 18 [5.49]-28 [8.53]1600 [755]-2000 [944]
[ ] Designates Metric Conversions
Page 20
ACCESSORIES
DUCT ADAPTERS RECTANGULAR TO ROUND TRANSITIONS (DOWNFLOW)
RXMC-CA03
RXMC-CA02
[ ] Designates Metric Conversions
20
16" Diameter
18" Diameter
Page 21
FRESH AIR DAMPER FOR USE ON
21
TPR SERIES
RXRF-FAA1 (Fixed - 0-35%)
The 0-35% manual outside Air Damper is designed to replace the unit return air duct cover. No drilling or damper assembly is required. The amount of outside air (0-35%) is controlled by sim­ply adjusting the side damper.
RXRF-FAB1 (Motorized - 0-35%)
The 0-35% motorized outside Air Damper is designed to replace the unit return air duct cover. No drilling or damper assembly is required. The control motor opens the adjustable slide damper when the unit blower motor is energized.
ACCESSORIES
ECONOMIZERS
RXRE-CAA30 (3 Position) and RXRD-CAM10 (Fully Modulating) for TPR Series
RXRE-CAA30 (3 Position)
Provided with enthalpy control, and mixed air sensor. Settings include fully open, fully closed and adjustable mid point.
RXRD-CAM10 (Fully Modulating)
Provided with enthalpy control, mixed air sensor and minimum position poten­tiometer for proportioning (modulating) the amount of fresh air.
[
[ ] Designates Metric Conversion
Page 22
ACCESSORIES
22
ECONOMIZERS
RXRD-CCM10 (Fully Modulating) for TPR Series
Horizontal Application
RXRD-CCM10 (Fully Modulating)
Provided with enthalpy control, mixed air sensor and minimum position poten­tiometer for proportioning (modulating) the amount of fresh air.
[ ] Designates Metric Conversions
Page 23
ACCESSORIES
FILTER KIT INSTALLATION RXRY-B01
For use in either vertical or horizontal discharge.
[ ] Designates Metric Conversions
23
CFM [L/s]
Minimum
Airflow
510 [241] 600 [283] 660 [311] 680 [321]
850 [401] 1020 [481] 1190 [562] 1275 [602] 1500 [708] 1700 [802] 2000 [944] 2200 [1039]
Nominal
Airflow
800 [378] 1000 [472] 1200 [566] 1400 [661]
Maximum
Airflow
880 [415] 1100 [519] 1320 [623] 1540 [727] 1650 [779]
Airflow Pressure Drop, Inches W.C. [kPa]
1" Filter 2" FilterCFM [L/s]
500 [236] .02 [.0050] .03 [.0075] 600 [283] .02 [.0050] .03 [.0075] 700 [330] .03 [.0075] .04 [.0010] 800 [378] .04 [.0010] .05 [.0124]
900 [425] .05 [.0124] .06 [.0149] 1000 [472] .07 [.0174] .08 [.0199] 1100 [519] .08 [.0199] .09 [.0224] 1200 [566] .10 [.0249] .12 [.0299] 1300 [614] .13 [.0324] .15 [.0373] 1400 [661] .16 [.0398] .19 [.0473] 1500 [708] .19 [.0473] .21 [.0523] 1600 [755] .20 [.0498] .23 [.0572] 1700 [802] .21 [.0523] .24 [.0598] 1800 [850] .22 [.0548] .25 [.0623] 1900 [897] .24 [.0598] .27 [.0672] 2000 [944] .26 [.0647] .29 [.0722]
Page 24
ACCESSORIES
DUCT ADAPTER SIDEFLOW SQUARE TO ROUND TRANSITION RXMC-BA01
Adapts the side rectangular supply and return openings to 14" [356 mm] diameter round openings. Adapters provided with same finish as unit and also provided with thermal insulation.
24
Page 25
ACCESSORIES
25
Roofcurb (Sloped)
RXQG-AAA14 for TPR Series
Heat pump models must use sloped curbs.
Hinged corners make for fast, easy set-up.
RXQG-AAA14 (14" [356 mm] High)
PACKAGE HEAT PUMP ROOFCURB INSTALLATION (Sloped)
OUTDOOR FAN GRILLE AND COMPRESSOR ACCESS
5
"
OUTDOOR COIL PROTECTIVE GRILLE
LIQUID PRESSURE SERVICE PORT
SUCTION PRESSURE SERVICE PORT
THREADED PVC CONDENSATE DRAIN CONNECTION (3/
[127 mm]
207/8
[530.2 mm]
"
[19.05 mm] N.P.T.)
4
"
IMPORTANT: UNIT MUST BE LEVEL TO PREVENT WATER MIGRATION
CONTROL ACCESS PANEL
[ ] Designates Metric Conversions
Page 26
ACCESSORIES
LIFT KIT—MODEL NO. RXML-A01
The lift kit is intended for temporary installation while the unit is being lifted into position. Kit includes 4 lift brackets.
26
Page 27
WIRING SCHEMATIC—TPR SERIES
27
Page 28
Design, material, performance data and components
1900 Wellworth Ave Jackson, Michigan 49203 • Ph. 517-787-2100 • Fax 517-787-9341
THE QUALITY LEADER IN CONDITIONING AIR
03/26/07
subject to change without notice.
www.heatcontroller.com
Loading...