Heat Controller SDAH 24, SDAH 48, SDAH 36 Installation Instructions Manual

INSTALLATION
INSTRUCTIONS
SMALL DUCT HIGH VELOCITY:
SDAH 24 / 36 / 48 Fan-Coil Units
Heat Controller, Inc. • 1900 Wellworth Ave. • Jackson, MI 49203 • (517)787-2100 • www.heatcontroller.com
Bulletin 100-155 Installation Manual
GENERAL
The information on the following pages is to help the installer save time by provide the best possible installa­tion and ensure continuous trouble-free operation.
SCOPE
These instructions apply to the Heat Controller SDAH Series. Installation instructions for the air distribution system are covered in Bulletin 100-145. Before begin­ning any installation a detailed system layout must be done in accordance with the System Sizing and Layout
Procedure, Bulletin 100-255 and the Component Layout Instructions, Bulletin 100-250.
NOTICE TO INSTALLER AND EQUIPMENT OWNER: RETAIN THIS MANUAL AT THE JOB.
FULL BUILDING INSULATION IS ESSENTIAL FOR THE MOST ECONOMICAL OPERATION
GENERAL PRECAUTIONS AND SAFETY TIPS
Do not attempt to install or startup unit without first reading and understanding the appropriate sections in this manual.
Before operating, be sure the unit is properly grounded.
Installation should be in accordance with all local codes and regulations and with the National Board of Fire Un­derwriters regulations. In case of conflict, local codes take precedence.
All electrical wiring should be in accordance with the latest edition of the National Electrical Code and all lo­cal codes and regulations. The unit is safety certified to UL 1995 and listed with ETL.
Always install a secondary drain pan when an overflow of condensate could cause damage.
HEAT CONTROLLER
INSTALLATION MANUAL
FOR
SDAH SERIES
TABLE OF CONTENTS
INTRODUCTION ................................................................... 1
OPTIONS ............................................................................. 2
UNPACKING ......................................................................... 2
LOCATION ............................................................................ 2
UNIT ASSEMBLY .................................................................. 3
Anti-Frost Switch Wires .................................................. 3
Fastening Modules Together .......................................... 3
Horizontal Installation ..................................................... 3
Control Box ..................................................................... 4
Secondary Drain Pan ..................................................... 4
MOUNTING ........................................................................... 4
Horizontal Platform Mounting ......................................... 4
Horizontal Suspended Mounting .................................... 5
DUCT CONNECTIONS ........................................................ 5
Supply Plenum ............................................................... 5
Return Duct .................................................................... 6
Multiple Returns .............................................................. 7
PIPING .................................................................................. 7
Condensate Lines .......................................................... 7
Refrigerant Lines ............................................................ 7
Water Connections ......................................................... 9
Coil Cleaning ................................................................. 10
WIRING ............................................................................... 10
Ventilation Speed Mode ............................................... 10
STARTUP ........................................................................... 10
Sequence of Operation ................................................ 10
Checking Airflow ........................................................... 11
How To Measure Air Flow ............................................. 12
How to Measure Static Pressure ................................... 12
Charging the System .................................................... 13
Low Ambient Control Kit ............................................... 13
R-410A Refrigerant ............................................................. 13
Maintenance ...................................................................... 14
Module Configuration Illustrations ........................................ 15
Blower Performance ............................................................. 15
Specifications ...................................................................... 16
PART NUMBERS
This manual does not always include the latest revision letter when referring to SD part numbers. Refer to the latest Price List and Spec Sheets for the current SD revi­sion letter. For example, in SD-00x the ‘x’ indicates the latest revision.
INTRODUCTION
Heat Controller offers a complete indoor comfort system that includes an indoor air handling unit and small duct system. The air handler and duct system were designed to operate together to provide the proper airflow in every installation. The conditioned air is supplied through a
© Copyright 2010 Heat Controller, Inc.
Bulletin 100-155 — Page 2
series of 2-inch or 2 ½ inch ducts as a stream of air that entrains and mixes the room air. This process of aspira­tion produces a more even temperature distribution in the room.
The SDAH Series consist of a motor, blower wheel, housing, controls, and an option of either a heat pump or chilled water coil. For additional options, the SDAH series features a latching mechanism for easy installation of a Hot Water Coil module and/or Horizontal Return Air Module. This series of air handlers must be installed in the horizontal flow position to allow for proper drai­nage (See Fig. 1).
All insulated modules feature closed-cell insulation for improved sound attenuation. There is no exposed fiber­glass insulation.
SDAH module is available in three sizes: 24, 36, and 48. The SDAH24 is sized for 1.5-2.0 tons, SDAH36 is sized for2.5- 3 ton, and the SDAH48 is sized for a 3.5-4 tons.
The coils can be arranged to provide only the options needed as shown in Figure 1 (with details on page 14). Heating-only systems require the blower with a heat pump coil, and a hot water coil. Cooling-only systems include the blower with the heat pump coil used for cooling. For heating and cooling use the refrigerant coil with the hot water coil module or electric furnace.
Heat Controller blowers feature direct drive motors that are located in the air stream. Each blower wheel is ba­lanced to Heat Controller specifications. The blowers feature a quick twist-and-lock motor mount for easy maintenance (see page 16). The motorized blower as­sembly consists of the motor, which is mounted to the inlet ring, and the wheel, which is fastened to the motor shaft.
OPTIONS
Other options and modules are also available to add additional features or to simplify installation. These in­clude an electric duct furnace, hot water coil module, and a horizontal return air module. Please refer to the latest Heat Controller Catalog for information on these and other options.
UNPACKING
Open each carton and inspect unit for visible signs of concealed damage and notify carrier of any such dam­age.
All materials are sold FOB Factory and it is the respon­sibility of the consignee to file any claims with the deli­vering carrier for materials received in damaged condi­tion.
LOCATION
Design the system layout to minimize the number of plenum elbows and fittings while keeping the supply duct runs as short as possible. (See Bulletin 100-250, Component Duct Layout Design). Provide minimum clearance on both sides for servicing the unit as shown in Fig. 2.
If installing the unit in an attic, avoid placing the unit above a bed. The ideal location is above a central hall, a closet, a bathroom, or any normally unoccupied space.
The unit can also be installed in a closet, crawlspace, or basement. If the local codes allow, the unit may be in­stalled in the garage provided the ductwork is well sealed, especially the return duct. Although the unit is not designed for outdoor use, it may be located outside provided adequate weather protection is used; typically a roof installation requires mounting on blocks with a sheet metal cover or cap to protect the unit from rain and extreme weather conditions.
Be sure to position the return air box and filter near the unit allowing at least one 90° bend in the return duct for proper acoustical performance (refer to figure 3 for a typical attic installation). The section on Return Air Ducts in the manual provides more details.
Table 1. Return Air Box Opening
Models
24 SD-01-24
36 SD-01-36
48 SD-01-48
Return Air Box
Part No.
Size of opening
inches (mm)
3
× 25 ½ (365 × 648)
14
8
3
1
× 30
14
8
2
3
8
× 30
1
2
24
(365 × 775)
(619 × 775)
All Heat Controller products are inspected prior to shipping and are carefully packaged in individual car­tons. Inspect all cartons prior to unpacking. Notify car­rier of any damage.
Heating or Cooling w/ Heat Pump Coil
Horizontal Flow
Figure 1. Basic Module Arrangement (refer to detail figures shown on Page 15)
© Copyright 2010 Heat Controller, Inc.
Heating or Cooling w/ Chilled Water Coil Only
Heat Pump C oil w/ Hot Water Coi
IL00010E.cvx
Bulletin 100-155 — Page 3
A
UNIT ASSEMBLY
The units should be assembled horizontally. Refer to Fig. 1 for your particular flow arrangement. If you use a refrigerant coil, the anti-frost switch wires must be routed to the control box during installation.
Anti-Frost Switch Wires
Remove the coil access panel and unravel the anti-frost switch wires. Feed the wires through the bushing in the motor partition panel and connect to the condenser ter­minal block on the SIB.
Fastening Modules Together
To fasten the modules together tilt the units to insert the connection flange over the mating flange as shown in Fig. 4. It may be necessary to squeeze the units together as you are inserting the flange to compress the rubber gaskets. If the hook flange has a small gap, use a large flat bladed screwdriver to pry the gap apart. Secure the modules together with the latches, compressing the gasket further.
Figure 2. Minimum Clearances
All SDAH modules except are designed to fit through a 14-inch (356 mm) opening, typical of a joist spaced at 16-inch (406 mm) center distance. If no access is pro­vided, an opening must be cut. It is suggested to use the opening required for the return air box, especially in an attic installation. The opening for the return air module is listed in Table 1. If the joists or studs are less than 16­inches (406-mm) center-to-center or running the wrong direction it will be necessary to cut and header the joists.
Blower Module
Control Box
Plenum
dapter
(SD-61-xx)
Isolation Pads
Secondary Drain Pan (SD-20x or 24x)
Platform
Figure 3. Typical Horizontal Attic Installation
(SDAHxx)
HP or CWC (SDAHxxB)
or
(SDAHxxC)
Heating Module (SDCMxxH)
Figure 4. Module Flange Connection
All systems are to be installed in the horizontal configu­ration, with the air going from right to left when looking at the connections (as shown in figure 1).
ReturnAir Adapter (SD-104-xx)
Band (supplied with return air box)
Typical 10 foot (3.6 m) Return Duct
Use at least one 90° bend.
Return Air Box (SD-01-xx)
Horizontal Installation
Return Air Duct (SD-04-xx)
Band
IL00009.CVS
IL00039D.CVS
© Copyright 2010 Heat Controller, Inc.
Bulletin 100-155 — Page 4
Control Box
The control box is shipped with all SDAH models. It can be installed on either the discharge side of the blower cabinet or on top of the blower cabinet, depending on what is most convenient.
To install, first remove the two knockouts on the side or top of the cabinet, where it will be installed. Mount the control box using four (4) sheet metal screws as shown in Fig. 5. Feed the wires from the anti-frost switch through the hole and bushing nearest the side of the unit and connect the leads to the AFS terminals on the SIB (System Interface Board) condenser terminal strip. The motor wiring harness will slip through the other hole. Then simply connect the plug on the motor wiring har­ness. (For additional information see section on wiring.)
Figure 5. Mounting the Control Box.
Secondary Drain Pan
Where an overflow of condensate could cause water damage, a secondary drain pan MUST BE INSTALLED. Place the drain pan on the mounting base, platform or angle iron support frame. Be sure to allow enough room for the drain line and connection (refer to Table 3). The assembled unit should be placed over the secondary drain pan supported by rails with rubber pads for isola­tion to raise the unit above the 1.5-inch (38mm) sides of the secondary drain pan.
Table 2 shows the secondary drain pans to be used for horizontally mounted modules.
Table 2. Secondary Drain Pan Dimensions, inches (mm)
Unit
Part No.
Size
24 SD-20B
36 SD-27B
SDAH SDAH + Hot Water Coil
Dimensions
inches (mm)
29 × 31.5†
(737 × 800)
34 × 31.5†
(864 × 800)
Part No.
SD-20C
SD-27C
Dimensions
inches (mm)
29 × 43.75†
(737 × 1111)
34 × 43.75†
(864 × 1111)
Like the modules, all the secondary drain pans except SD-24C will fit through the return air opening. For these drain pans it will be necessary to fold the pans in order to pass through the return opening.
Horizontal Platform Mounting
It is easiest to mount the unit on a platform but care must be taken to assure proper drain line pitch (see Table 3).
Rafter, Joist or Floor
B
*
A
IL00036a.CNV
Figure 6. Typical Platform Installation
The platform height must allow for proper pitch of the condensate drain lines — at least ¼ inch drop per lineal foot (20 mm per meter). The platform can be built from a sheet of ½ inch (13 mm) plywood and stud frame. Ta­ble 3 lists the maximum horizontal drain line run for various framing materials and still provide adequate drainage.
Table 3. Horizontal Distance of Drain Piping for Different Framing Materials
Frame Lumber:
Max. Horizontal Run, ft. (m)
The platform size must allow for the number of modules being used. For dimensions for minimum platform size see Fig. 6.
Unit 24 36 48 24 36 48
A 25 (635) 30 (762) 38 (965) 25 (635) 30 (762) 38 (965)
B 26 (660) 38 (965)
Place secondary drain pan on platform and unit on top of isolation pads inside of secondary drain pan. Be sure that the unit is raised above the height of the drain pan side to allow duct connections.
2 × 4 2 × 6 2 × 8 2 × 10
18 (5) 26 (8) 34 (10) 42 (13)
SDAH SDAH + Hot Water Coil
48
SD-24B
† NOTE — The drain fitting extends 7/8 inch (22 mm) beyond this dimension.
© Copyright 2010 Heat Controller, Inc.
42 × 31.5†
(1067 × 800)
SD-24C
42 × 43.75†
(1067 × 1111)
Horizontal Suspended Mounting
CAUTION
Do not hang unit from top of unit cabi­net as this could distort unit.
The modules can also be suspended from the ceiling or rafters. A typical suspension method is shown in Fig. 7. Screw four (4) “J” hooks into rafters. Suspend four (4) chains from “J” hooks and attach eyebolts to chains. Secure angle iron to eyebolts and place secondary drain pan on top. Put isolation pads in drain pan, making sure unit sits above sides of drain pan.
As an alternative, rest the unit on the angle iron supports, and hang the secondary drain pan from the same sup­ports. As above, install “J” hooks, chains, and angle iron. Secure angle iron to eyebolts and put isolation padding on angle iron.
Adjust the length of the eyebolts and chains so there is a slight pitch towards the drain end.
HOOK
RAFTER
CHAIN
Bulletin 100-155 — Page 5
Figure 8. Round Supply Plenum Adapter Dimensions
Measure the motor amperage and use this to ensure the 200-250 CFM per nominal ton (27-34 L/s per nominal kW) has been achieved. If elevated sound levels are no­ticed at the outlets and there is more that 250 CFM per nominal ton (34 L/s per nominal kW), the airflow may be reduced with the restrictor plate. Always measure the system airflow by the motor amperage (see Table 4). Refer to the airflow-amperage charts provided with the blower.
UNIT
SECONDARY DRAIN PAN
ANGLE IRON
Figure 7. Typical Suspended Mounting
IL00038C.CVN
DUCT CONNECTIONS
Supply Plenum
Heat Controller has a complete line of round plenum adapters available as shown in figures 8. In addition, all blowers include a restrictor plate to be installed between the supply adapter and the unit. The purpose of the re­strictor plate is to eliminate objectionable outlet noise because the blower is delivering more air than required. In most cases where the maximum airflow is required, the restrictor may be omitted.
To attach the plenum adapter, first install the restrictor plate. Then install the adapter with eight (8) sheet metal screws as shown in Fig. 9. Sheet metal screws for instal­ling both are provided with the blower.
The restrictor plate is used to set the system airflow (see Fig. 10). The full open position corresponds to the high­est airflow the installed duct system will allow. Set the restrictor plate to the full open position and measure the system airflow. The required system airflow is 200-250 CFM per nominal ton (27-34 L/s per nominal kW).
Note: Do not use restrictor plate to adjust plenum static pressure. Adjust the restrictor to the proper amperage. This will assure proper airflow.
Attach the plenum to the adapter by inserting it over the supply adapter. If using sheet metal duct, use three (3) or four (4) equally spaced sheet metal screws or nails to secure the duct to the supply adapter. Then tape around the seam with UL 181A aluminum tape. Then wrap the outside of the plenum adapter with the supplied blanket insulation and secure the insulation seams with UL 181A tape.
Blower Module
Restrictor Plate
Plenum Adapter
Plenum
Insulation Wrap
Figure 9. Supply Plenum Adapter Installation
IL00308.CVX
© Copyright 2010 Heat Controller, Inc.
Bulletin 100-155 — Page 6
X
FRAMING
RETURN AIR BO
FILTER FRAME
FILTER
FILTER GRILLE
Figure 10. Restrictor Setting
Return Duct
Heat Controller supplies a return duct system but any return duct system is acceptable provided the pressure loss does not exceed 0.15 inches of water (37 Pa), in­cluding filters. The return duct should have at least one 90° bend between the unit and filter box to reduce sound transmission directly from the unit.
The return duct system has a single return that includes the return air box with filter, the return duct, and the return air adapter (refer to Fig. 3). Multiple returns or extra long returns are possible so long as the maximum pressure loss is not exceeded.
The typical return duct is 10-foot (3 m) in length so it may have to be cut to avoid bunching if the distance to the unit is significantly less than 100-inches. The mini­mum length should be 7-feet (2 m). When given a choice, the shorter distances should be avoided as this may increase sound transmission from the unit.
Cut an opening for the return box as specified in Table 1. For the 24 and 36, if the joists or studs are on 16-inch (410mm) centers, there is no need to build a frame to hold the return air box. Otherwise, it will be necessary to construct a frame around the opening.
Center the return air box so the filter frame flange covers all the gaps and make sure the flange is flush against the wall or ceiling. Install the return air box against the frame using nails or screws.
Screw holes are provided in the return air box. Use the holes nearest the corners. The other holes are for mount­ing the filter grille. See Fig. 11.
IL00048.CNV
Figure 11. Return Air Box and Filter
Install filter frame into the return air box using four nails or screws. Use the holes furthest from the corners. Insert filter and hold in place by rotating metal clips. Close grille and secure with clips.
Refer to Table 4 for correct Return Duct Adapter selec­tion. Attach the proper return duct adapter to either the Heating or Cooling Module. Then attach the return duct to the adapter and to the return air box using the Q-bands and Q-clips.
The return air adapter ships with an insulation blanket that must be wrapped around the adapter. Tape the seams with UL 181A aluminum tape.
Table 4. Return Duct Adapter
Blower Module +
Unit Size
24 - SD-104-24
36 - SD-104-36
48 SD-59-48 SD-104-48
Table 5. Approximate Amperages at Given Airflows
Unit Size
24
36
48
*multiply by 1.1 if 208V † for more exact airflow use the chart included with the blower
Cooling Module
Airflow,
CFM (L/s)
600 (280)
500 (240)
400 (190) 1.4
800 (380) 3.2
700 (330) 2.9
600 (280) 2.7
1000 (470) 3.2
900 (425) 2.9
800 (377) 2.8
Heating Module
+ Cooling Module
SDAHxxx-A1
Amps
@230V †*
1.9
1.6
© Copyright 2010 Heat Controller, Inc.
Bulletin 100-155 — Page 7
(ship
p
t
h
)
Multiple Returns
If more than one return is desired, Heat Controller has a return plenum (HM) module. The HM module is availa­ble in three sizes: 24, 36, 48, and it includes a central filter. The HM module is easily fitted to the air handling unit and multiple return openings may be cut in the top back or sides of the box. Refer to Bulletin 100-30, Re- turn Plenum Module, for additional information.
PIPING
All piping must be in accordance with all local codes and ordinances.
Condensate Lines
The primary drain pan condensate connection is a ¾­inch (19mm) female pipe thread fitting and the second­ary drain pan connection is a ¾-inch (19mm) PVC sock­et fitting. Elevate the unit so the condensate lines are pitched at least ¼-inch per lineal foot (20 mm per me­ter). Trap the condensate line near the unit using U-trap A00924-G03 as shown in Figure 12. In some cases it may be necessary to wrap the condensate line near the unit with insulation to prevent water condensation on the outside of the pipe. In some climates or locations it may be necessary to protect trap from freezing in the winter.
Refrigerant Coil Connections
Note
All refrigerant coils are shipped from our factory pressurized with nitrogen. They do not contain any refrigerant.
WARNING
To prevent injury to eyes, face away from the Schrader valve when releasing nitrogen gas.
The refrigerant coils are equipped with a Schrader valve port to relieve the pressure and for factory testing pur­poses. It can also be used to check for leaks prior to in­stallation. Unscrew the Schrader cap and press the de­pressor. If there is no nitrogen pressure present, the
coil may have developed a leak during shipment and should be returned to the point of purchase for ex­change. If pressure is present, then go ahead and relieve
the pressure in the coil by continuing to press on the depressor. When all the pressure is removed, cut the ends of the connections off.
Pitch ¼ inch per foot (2 cm perm)
53/8
(137 mm)
IL00046a.cvx
U-TRAP (SD-00924-G03)
ed wi
Figure 12. Typical Condensate Trap
21/4
(57 mm)
SDAH modules
Do not trap the secondary drain line and do not terminate line into the primary drain line. Run secondary drain line so that any drainage will be immediately known without causing damage to property. A typical location is to ter­minate the secondary drain line above a windowsill so that the drainage splashes on the window. This will serve as an indicator that there is a problem with the primary drain. In cases where a secondary drain line cannot be run, add a float switch or a micro switch with a paper fuse.
Cut end of connection as shown.
Connection after the end has been cut off.
© Copyright 2010 Heat Controller, Inc.
Bulletin 100-155 — Page 8
WARNING
To prevent injury, remove all pressure from coil before removing connection end caps.
CAUTION
When brazing, purge with nitrogen gas to prevent the formation of oxides.
The refrigerant lines are copper sweat connections. The liquid line is 3/8-inch (9.5mm) OD and the suction line is 7/8-inch (22mm) OD. Refer to the condensing unit manufacturer’s instruction for proper line sizing infor­mation based on distance from condenser.
Install a liquid line filter drier as close to the coil module as possible to protect the evaporator from foreign object debris. For attic installations or when using long line sets, an optional moisture indicating sight glass should also be installed between the filter-drier and expansion valve, near the indoor unit.
All refrigerant coils require a thermostatic expansion valve. The valve is shipped loose and should be attached prior to charging. For replacement expansion valves, refer to table 6. Always use new Teflon seals when re­placing the TXV.
Remove side panels as shown.
Table 4. Expansion Valve Model numbers
Model
Heat Pump Coils
SDAH24B
SDAH36B
SDAH48B
Nominal
Condenser
2 to 2.5-ton
(7 to 9 kW)
3 ton
(10 kW)
3.5 to 4 ton (12 to 13.6
Size
kW)
Valve Part Number
R-410a
A00808-013 2
A00808-014 3
A00808-015 4
Remove nut as shown.
Nom. Valve
Size
Attach and tighten lower connecting nut as shown.
Attach and tighten upper connecting nut as shown.
© Copyright 2010 Heat Controller, Inc.
Bulletin 100-155 — Page 9
Route both the pressure and temperature tubes as shown.
Tighten the pressure tube nut as shown.
Secure bulb with cork tape as shown.
Water Connections
If you are installing the hot water coil, remove the side coil access panel and cut away the insulation. Slide the coil into the cabinet and secure with brackets supplied with the hot water coil. Install the access panel after the coil is in place.
The thermal measuring bulb is placed as shown. It
needs to be in contact with copper tube.
(a) Hot Water Coil
BLEED VALVE (VENT)
IN
OUT
BLEED VALVE (DRAIN)
(b) Chilled Water Coil
Figure 13. Water Coil Connections
© Copyright 2010 Heat Controller, Inc.
AIRFLOW
IL00054b.CVN
Bulletin 100-155 — Page 10
All water connections are 7/8-inch (22mm) sweat con­nections. Sweat the water connections, than fill the sys­tem. Bleed the air from the coil by backing off the screw inside the bleed valve for venting (Fig. 13).
If unit is in an unconditioned space below freezing, care must be taken not to freeze the water in the coil. The best method is to use a glycol-water antifreeze solution with a freezing point below the coldest temperature expected.
After venting the chilled water coil, replace the access panel and seal around the connections with the rubber gasket provided.
Coil Cleaning
The coil should be sprayed with liquid detergent, or any commercially available evaporator cleaner solution, tho­roughly and rinsed thoroughly before installation to as­sure proper drainage of condensate from the coil. This will eliminate blow-off and assure maximum coil per­formance. If not sprayed, approximately 50 hours of break-in time are required to achieve the same results.
WIRING
WARNING
Disconnect electrical supply before wiring unit to prevent injury or death from electrical shock.
All electrical wiring must comply with all local codes and ordinances. Blower module controls and compo­nents are bonded for grounding to meet safety standards UL Standard 1995 and CAN/CSA-C22.2 No. 236 and are listed by ETL.
Use a separate 1 ph - 230/208V – 60/50 Hz power supply with a 15 amp breaker and appropriate wire gauge per code.
The System Control Box comes standard with all SDAH series blower/coil module. The control box is designed to operate with a two speed motor with full speed being used for heating and cooling. The second speed operates at 50% of full speed and is used for ventilation mode only. The SIB includes a 24-volt transformer, a capaci­tor, and the controlling circuit board. Refer to bulletin 100-180 for installation instructions for the SIB.
STARTUP
! IMPORTANT !
The most important step when installing the small duct high velocity system is making sure it has the correct airflow. Be sure to record the amperage and voltage of every system in order to verify the air­flow through the unit. Also, measure the airflow at each outlet to verify the airflow in each room. Both methods are de­scribed later in this section.
Sequence of Operation
The sequence of operation depends greatly on the op­tions installed and type of control thermostat used. Most thermostats have a fan AUTO-ON switch. When the fan switch is set to ON, the “G” circuit is closed and the blower relay is energized. The indoor blower starts after about a 20 second delay. The following paragraphs de­scribe the sequence of operation when the fan is set to AUTO. If the fan switch is set to ON, the sequence is the same except the “G” circuit is always closed and the indoor fan is always operating.
Cooling Cycle (Heat Pump). When the thermostat calls for cooling, the “Y” and the “G” circuits are closed, and a 24 V signal is sent to the compressor contactor in the outdoor unit and fan relay in the indoor unit. After about 20 seconds, the indoor blower starts. At the same time, the compressor and outdoor fan also start. Depend­ing on the control circuitry in the outdoor unit, there may be a time delay before the outdoor unit starts. If the sys­tem was just turned off, the time delay could be as much as five minutes. The cooling system is now operating.
For heat pump thermostats, setting the switch to ‘cool­ing’ immediately closes the “O” circuit, which is used to energize the reversing valve solenoid if required by the heat pump. Otherwise, the “B” circuit, which closes when switched in heating, is used to energize the revers­ing valve solenoid. (Refer to the heat pump manufactur­er’s instructions to see which mode the solenoid needs to be energized – whether in heating or cooling.)
When the thermostat is satisfied, the 24 V signals are opened and the outdoor unit stops. The indoor blower continues to operate for about 40 seconds, then stops. The system is now off.
Heating Cycle (Heat Pump). Setting the thermostat to HEATING will automatically switch the reversing valve solenoid. This setting closes the “B” circuit which sends a 24V signal to energize the solenoid if required by the heat pump. Otherwise the “B” circuit is not used and the solenoid is not energized during heating.
When the thermostat calls for heating, the “Y” and “G” circuits are closed, sending a 24 V signal to the compres­sor contactor in the outdoor unit and the fan relay in the indoor unit. This starts the indoor blower and the out­door compressor. There is a time delay of about 20 seconds for the indoor unit. The heating system is now operating in stage one.
If the first stage does not satisfy the thermostat, the second stage thermostat calls for more heat. This closes the “W2” contacts and energizes the sequencer for elec­tric heat (if installed). When the second stage thermostat is satisfied, the “W2” circuit is broken and the sequencer is de-energized. The electric heating system is now off.
When the first stage thermostat is satisfied, the 24 V signals are opened and the outdoor unit stops. The in­door blower continues to operate for about 40 seconds, then stops. The system is now off.
© Copyright 2010 Heat Controller, Inc.
Bulletin 100-155 — Page 11
Heating Cycle (Electric Heat-Only). When the thermostat calls for heating, the “W” and “G” circuits are closed. The W circuit completes the 24V signal to the sequencer in the electric duct heater, which cycles on the electric heating elements. The G circuit completes the 24V signal to the fan relay in the indoor unit, which starts the indoor blower after a time delay of about 20 seconds. The heating system is now operating.
When the thermostat is satisfied, the 24 V signals are opened and the indoor blower stops after about 40 seconds. At the same time the sequencer cuts the power to the electric elements. The system is now off.
Note: Use a thermostat designed for electric heat. A normal heating-cooling thermostat will not close the “G” circuit on heating.
Ventilation Cycle. When the thermostat is satisfied and the fan switch is set to “AUTO”, the “G” circuit is open and the motor will slowly come to a stop.
Checking Air Flow
CAUTION
Do not operate blower with free dis­charge or low static pressures (below .5-inch w.c. to prevent motor from over­loading.
After the system is installed and before charging the system, check for proper airflow. Record the position of the restrictor plate, the plenum static pressure, and the motor amperage. With this information, the amount of airflow can be determined.
As a recommended further check on airflow, use a velo­ci-meter to measure the airflow from each outlet. The most convenient instrument to use is a hand held vane type velocity meter that fits directly over the outlet. The Turbo-Meter (Davis Instruments Catalog No. DS105I07) or equivalent meter will give a direct LED readout on the Knots (FPM x 100) setting. For a 2-inch outlet, mul­tiply the knots by 2 to get the CFM of the outlet. For a 2 ½ inch outlet, multiply the knots by 2.37 to get the CFM of the outlet. The CFM will have an accuracy of within 10%. (Multiply ‘knots’ by 0.94 to obtain L/s.)
By measuring and totaling the airflow of all outlets, the total airflow of the system can be closely approximated and provide a crosscheck for the airflow determined from the motor amperage using the airflow-amperage table that is shipped with all SDAH blower/coil modules.
Note: These tables are for the specific mo­tor installed in each blower module. Be sure the table used applies to the correct model number that is shown on the table.
Use Table 5 to correct the airflow.
Check Static Pressure Measure the external static pressure in the supply plenum at least two feet (610 mm) from the unit and verify that it is within the allowable range.
It is not necessary to measure the return duct static pres­sure unless it was field fabricated. The maximum return static pressure (including filters) should be 0.15 inches of water (37 Pa). If it is greater than 0.15 inches of water column, add the return system pressure drop to the supply plenum static pressure to get the total static pres­sure drop.
For example: If the supply static pressure is measured to be 1.6 inches w.c. and the return system pressure drop is 0.25 inches w.c, the total static pressure drop is: 1.6 +
0.25 = 1.85. In this case the static pressure is too high.
Check Motor Amperage. Remove the control box cover and measure the current with an amp meter. This should be measured on the purple wire between the con­trol box and the motor with the letters “clmpmter” printed on the wire. Compare this reading to the Motor Amperage-Airflow table enclosed as a separate sheet in the Blower Module carton.
Table 5. Airflow Troubleshooting Chart
Problem Probable Cause Remedy
Low Static, Low Amperage Restrictor set too low.
Blocked filters, restriction in return duct. Low Voltage. Blower Wheel not aligned properly.
Dirty blower wheel.
Low static, high amperage Large number of outlets.
High Static, Low Amperage
Restrictor setting to high.
Restrictive duct system. Add outlets, add splitter vane in tee, reduce the number of
Open restrictor to table setting. Clear restriction. Check with local utility.
Center wheel inside of inlet ring. Position on shaft for 1/8 inch (3 mm) clearance from inlet ring.
Clean wheel.
Close restrictor to proper amperage, or Add balancing orifices to outlets.
Close restrictor to obtain proper amperage.
tees and elbows in plenum, increase plenum size to 9” equivalent, or Open restrictor to proper amperage.
© Copyright 2010 Heat Controller, Inc.
Bulletin 100-155 — Page 12
How to Measure Outlet Airflow
The Davis TurboMeter is the ideal instrument for mea­suring airflow for both the 2 and 2 ½ inch round outlets. This instrument can be used to determine how much air duct leakage is in the system by comparing the total air­flow using the turbo meter to the motor amperage chart that comes with the SDAH.
How to Measure Static Pressure
Measure the supply plenum static pressure at least 18­inches (457mm) from the unit, but before any tee or el­bow. A distance of between 2 and 3-feet (0.6 to 0.9m) is best. Use an inclined manometer capable of reading at least 2.5 inches of water column (622 Pa), such as Dwyer Instrument’s model 109 manometer. Be sure to zero the scale and level the manometer.
A magnehelic gauge that measures up to at least 2.5 inches of water may also be used.
Use a metal tube, typically ¼-inch (6mm) diameter, to measure the static pressure. Determine where you want it and cut or punch a small hole in the duct. Make the hole the same size as the metal tube to prevent leakage. Insert the metal tube 1-inch (25mm) so that the tip of the tube is flush to inside wall of the duct and perpendicular to the air stream as shown in Fig. 14.
Attach the metal tube to the manometer using a rubber hose (usually supplied with the manometer). Record the pressure.
Note: If the tube is not perpendicular to the air stream, the reading will be in error. You will get a higher reading if the tube is angled toward the air stream.
To assure an accurate measurement, follow the proce­dure listed below.
1. Slide the ON switch to the Knots position. This is roughly equal to 100 ft-per-min.
2. Place the meter against the outlet with the fan cen­tered over the outlet.
3. Record the KNOTS reading.
4. For a 2 inch outlet, multiply the KNOTS by 2.0 to obtain CFM. For a 2 ½ inch outlet, multiply the KNOTS by 2.37 to obtain CFM.
5. Use the Heat Controller Service Report Form to record your system readings and to determine the system total airflow.
Example:
A 2-inch round outlet reads 16.3 knots. Multiply 16.3 by 2 to obtain 32.6 CFM.
Repeat this for each outlet in the system and add them together to determine the total CFM. This value can then be compared to the blower amperage charts to in­sure minimal air leakage.
Figure 14. Measuring Plenum Static Pressure
In the absence of a manometer you can build a simple but less accurate manometer in one of two ways. One way is to use a short piece of ruler or yardstick and clear plastic tubing as shown in Fig. 15.
© Copyright 2010 Heat Controller, Inc.
Figure15. U-Tube Manometer
Bulletin 100-155 — Page 13
Charging the System
Charging
Cooling Mode. DO NOT VENT
REFRIGERANT TO THE ATMOSPHERE!! It is a
violation of federal law and in some cases local ordin­ances also. Always use a refrigerant recovery or recy­cling device.
The following procedure is only valid for charging the system during the cooling mode.
To check for proper charge record the refrigerant pres­sures and temperatures. Check the refrigerant charge by measuring the amount of sub-cooling (or ‘approach’ temperature for some condensing units). If the outdoor manufacturer does not have sub-cooling or “approach” temperature charts, then be sure that the sub-cooling is between 3 and 8 °F (2 to 5°C). For long refrigerant lines or when the evaporator is above the condenser, the sub­cooling should be close to 8°F; otherwise, aim for the low end of the range.
After the refrigerant lines and evaporator have been carefully leak tested and evacuated, release the R-410a operating charge in the condensing unit. The system is now ready for refrigerant charge adjustment. If the coil is equipped with a threaded TXV, always verify that the threads are tight and do not leak.
Start up the system and check line voltage to assure it is within acceptable limits for the system as dictated by the condensing unit manufacturer. Run the system for 20 to 30 minutes to get reasonably stabilized conditions. Do not attempt to adjust charge with outdoor temperature below 75°F (24°C). An outdoor temperature of 75 to 85°F (24 to 29°C) is preferred.
If the system charge must be checked when the outdoor temperature is below 75°F (23.9°C), block the condenser coil until the head pressure is approximately equal to what its charging chart specifies for an 85°F (29°C) day.
For heat pumps always check the charge in cooling mode. If this is not possible because of low outdoor tem­peratures, charge the system in the heating mode, but return later when the weather is warmer before the sys­tem is switched to cooling.
Charge and operate the heat pump in accordance with these instructions and the instructions provided by the manufacturer of the outdoor unit.
Charging a heat pump, by its nature, is more difficult than a cooling-only refrigerant system. Quite often the ideal charge for cooling is different than the ideal charge for heating, making the system much more sensitive to the amount of charge. In some cases, the compressor will trip on high head pressure during the heating mode be­cause it is overcharged if the system was charged during cooling. Likewise, the system may cycle on the anti-frost control because of a low refrigerant charge if the system was charged during heating.
To compensate for this charge difference some outdoor unit manufacturers have a charge compensator device that stores charge while in heating mode. Unfortunately
there are no add-on devices to accomplish the same thing and only a few (usually the most expensive) model lines will have one. For this reason, it is often necessary to compromise the charge.
Although the unit can be charged in the heating mode, it is best to charge the unit during the cooling mode. Then recheck the charge during the heating season to be sure the system is not over charged.
Charging – Heat Mode. If the system is started up on heating where the return air temperature is significantly lower than the normal operating range of 65 to 75°F (18.2 to 23.8°C), the suction pressure can be very low. Operate the system to bring up the return air tempera­ture, using auxiliary heat if necessary, before checking system charge.
Typically, in the heating mode, a High Velocity System will have a slightly higher discharge (LIQ.) pressure, and in cooling mode a High Velocity System will have a slightly lower suction (SUC.) pressure.
Some outdoor heat pump units include a manual high­pressure switch. With the lower airflow and higher tem­peratures, the discharge pressure will typically run high­er than a conventional system. It is important that the system be operated at pressures below the trip pressure of the high-pressure switch to avoid nuisance shut downs. If this occurs, use a high head kit as described below.
High Head Heat (Mild Weather Kit). When any heat pump is operated during mild weather (temperatures above 50°F [10°C]), the compressor may trip out on the high-pressure limit. High Velocity systems are particu­larly sensitive to this since it operates with a lower air­flow. Contact the manufacturer for more information.
To overcome this problem, install a control to cycle or modulate the outdoor fan based on the compressor dis­charge pressure.
Sub-cooling Method. Many condensing unit manu­facturers publish the amount of sub-cooling that the con­denser will produce. Follow their instructions to charge the unit. Typical sub-cooling values will be between 3 and 8°F (2 to 5°C). The unit should ALWAYS have some amount of sub-cooling. To be sure there is enough sub-cooling, especially if the unit is in a hot attic, check the liquid line sight glass near the evaporator for bubbles or measure the refrigerant liquid line pressure and tem­perature AT THE EVAPORATOR.
To measure sub-cooling use the following procedure:
Measure and record the liquid line pressure using an
1. accurate refrigerant gauge. Record the corresponding saturation temperature for this pressure.
Measure and record the liquid line temperature using
2. an accurate metal or glass thermometer, or thermo­couple. Tape or strap the sensor firmly against the surface of the liquid line and cover with insulation.
© Copyright 2010 Heat Controller, Inc.
Bulletin 100-155 — Page 14
3. Determine the sub-cooling with the following equa­tion:
Saturated Temperature — Liquid Line Temperature = Subcooling
If the sub-cooling temperature at the condenser is low, the system is undercharged and refrigerant must be add­ed.
CAUTION
TO PREVENT DAMAGE TO THE COMPRESSOR, DO NOT ADD LIQUID CHARGE INTO SUCTION PORT.
If it is high, the system is overcharged and some refrige­rant must be removed and collected in an empty refrige­rant container.
DO NOT RELEASE REFRIGERANT INTO THE ATMOSPHERE.
In some cases, such as in a hot attic, the liquid line will pick up heat and lose its sub-cooling. This will be appar­ent if the sub-cooling at the evaporator is low. In these cases, the liquid line should be insulated or strapped to the suction line and both insulated. The same problem can occur for long refrigerant lines; in this case, increase the size of the liquid line to reduce the pressure drop.
CAUTION
TO MAINTAIN PROPER HEAT PUMP OPERATION, DO NOT STRAP THE LIQUID AND SUCTION LINES TOGETHER FOR HEAT PUMP SYSTEMS.
Superheat Method. Do not charge the system based
on superheat. Superheat measurements should only be used to verify that the expansion valve is working prop­erly.
The superheat should be between 8 to 12°F (4 to 7°C) at the indoor coil. In some cases, particularly for the larger capacity match-ups (i.e. 3 ton and 5 ton), a superheat of 15 to 18°F (8 to 10°C) is satisfactory. It is not uncom­mon to measure a superheat above 20 to 25°F (11 to 14°C) at the condensing unit.
Be aware that the superheat value is also dependent on the outdoor air temperature. At lower air temperatures the superheat will be higher than at higher air tempera­tures. If the condenser ambient temperature is between 75 and 85°F (24 to 29°C), superheat should be approx­imately 10 to 12°F (5 to 7°C). If the outdoor temperature is between 85 and 105°F (29 to 40°C), superheat should be approximately 8 to 10°F (4 to 5°C).
To measure the superheat, use the following:
Measure and record the suction pressure at the eva-
1. porator outlet using an accurate refrigerant gauge. If this is not possible, measure the pressure at the ser­vice port on the suction valve fitting at the condens­ing unit and add the estimated pressure loss in the suction line between the condensing unit and evapo­rator. Record the corresponding saturation tempera­ture for this pressure.
Measure the suction line temperature at the evapora-
2. tor outlet using an accurate metal or glass thermome­ter, or thermocouple. Insert the thermometer under the insulation on the suction line and tape firmly against the surface of the suction tube.
Determine the superheat with the following equation:
3.
Suction Line Temperature — Saturated Temperature = Superheat
Charging by Gauge Pressures. It is not possible to charge the system by gauge pressures. Gauge pressure should only be used to verify the system is working properly.
The Heat Controller System will show a lower suction pressure during the cooling mode than a conventional system. Generally, it will be 10 to 15 psi (70 to 100 kPa) less. For example, a normal suction pressure for the Heat Controller System
will be about 130 psig (898 kPa) with an 85 to 95°F (29 to 35°C) outdoor temperature. Expect lower pressures when the outdoor temperatures are low­er.
The head pressures should be similar to a conventional system when in the cooling mode.
Using a Low Ambient Control Kit
Since a small duct high velocity system operates at cold­er coil temperatures (in cooling mode), an anti-frost switch is installed on the coil to prevent coil freeze-up. In certain instances, such as when the outdoor ambient temperature is low, the condensing unit will cycle on the anti-frost switch. This may reduce the cooling capacity at a time when the cooling load is still fairly high. To provide better control and comfort, install a low ambient control on the condensing unit. Typically, a low ambient control is necessary when operating the unit at outdoor temperatures below 80°F (26.6 °C), especially for a 5­ton nominal capacity system.
These controls come in different configurations such as the Hoffman Controls Corp. series 800AA-head pressure control. This control modulates the outdoor fan to main­tain a minimum liquid line temperature. Other controls may cycle the fan on/off. In either case check with the outdoor unit manufacturer to determine what controls are compatible with the outdoor unit.
© Copyright 2010 Heat Controller, Inc.
Maintenance
When service is required to the motor or the wheel, the entire assembly may be removed as a unit (see figure
16). The SDAH series units are accessible from the pip­ing connection side of the unit. It is not necessary to access both sides of the unit. Nor is it necessary to dis­connect any module or ducting.
To remove the motor and blower wheel assembly, loo­sen the six (6) screws fastening the motorized blower assembly to the blower housing. Twist the motorized blower assembly counter-clockwise (CCW) and pull the assembly away from the blower housing.
CAUTION
TO PREVENT DAMAGE TO THE WHEEL BALANCE, DO NOT GRAB THE ASSEMBLY BY THE WHEEL OR SET THE ASSEMBLY DOWN SUCH THAT THE WHEEL IS SUPPORTING THE ASSEMBLY. ALWAYS SET THE ASSEMBLY DOWN WITH THE WHEEL ON TOP.
Bulletin 100-155 — Page 15
Once the assembly is removed, the proper service may be preformed. If the wheel is to be changed, it may simp­ly be removed from the motor shaft by loosening the motor set screw and pulling the blower wheel off the motor shaft. If the motor is to be changed, first the blow­er wheel must be removed as mentioned above, and then the screws fastening the motor to the inlet ring must be removed.
Figure 16. Removal of the Motorized Blower Assembly
© Copyright 2010 Heat Controller, Inc.
Bulletin 100-155 — Page 16
Figure 17. Horizontal Configuration Chart
Blower Performance
External Static Pressure, in. water (Pa)
Model CFM (L/s) Amps CFM (L/s) Amps CFM (L/s) Amps CFM (L/s) Amps CFM (L/s) Amps
SDAH24x-A1
SDAH36x-A1
SDAH48x-A1
© Copyright 2010 Heat Controller, Inc.
1.0 (250) 1.25 (310) 1.5 (370) 1.75 (435) 2.0 (500)
760 (360) 2.3 700 (330) 2.1 640 (302) 2.0 550 (260) 1.7 450 (212) 1.5
1380 (617) 5.2 1300 (613) 4.9 1200 (566) 4.5 1090 (514) 4.0 950 (448) 3.6
1480 (698) 5.0 1430 (674) 4.4 1360 (642) 4.5 1220 (575) 4.0 930 (439) 3.1
60 Hz – 230V
Bulletin 100-155 — Page 17
SDAH Specifications
Model No. SDAH24 SDAH36 SDAH48
Electrical Characteristics 208 – 230 Volts / 60 / 1 phase
Size, HP (kW) 1/2 (0.37) 1 (0.75) 1 (0.75)
Motor
Blower Wheel Nom. Diameter, in. (mm) 9.5 (241) 9.5 (241) 9.5 (241)
Blower Wheel Width, inch (mm) 3.75 (95) 5.0 (127)
Nominal* Air Flow Rate, cfm (L/s) 600 (283) 800 (377) 1100 (519)
Plenum Static Pressure, iwc, (Pa) 1.5 (373) 1.5 (373) 1.5 (373)
Sound Pressure Level
Minimum Plenum Size, ID, inch (mm) 7 (178) 9 (229)
Shipping Weight, lb (kg) 82 (37) 94 (43) 111 (50)
Overall Dimensions, in. (mm) H x W x D
Full Load Amps 3.3 4.8 4.8
Capacitor, mfd. 10 10 10
Speed, RPM 1625/800 1625/800 1625/800
dB(A) 56 56 58
NC 50 47 50
17.5 x 25 x 26
(445 x 635 660)
17.5 x 30 x 26
(445 x 762 x 660)
17.5 x 38 x 26
(445 x 965 x 660)
A/C or Heat Pump Coil Option
Model No. 24 36 48
Compatible Condenser Size, Ton (kW) 1.5-2.0 (5.3-7.0) 2.5-3 (8.8-10) 3.5-4 (12.3-14)
Net Face Area, ft
Tube diameter, in. (mm) 3/8 (9.5)
Number of rows 4
Fins per inch (cm) 14 (355)
Heat Pump
Condensate Connection, in. (mm) FPT 3/4 (19)
Refrigerant R-410A*
Suction line O.D., in. (mm) 7/8 (22.2)
Fin Type corrugated
Number of Circuits 6 6 6
Valve, R-410A, Part No. A00808-013 A00808-014 A00808-015
Liquid line, in. (mm) OD 3/8 (9.5)
2
(m2) 1.92 (0.178) 2.34 (0.217) 3.48 (0.32)
Chilled Water Coil Option
Model No. 24 36 48
Net Face Area – sq. ft. (m
Water Coil
Water Connection Size, ODF Sweat – in. (mm) 7/8 (22.2)
Condensate drain connection size, FPT – in. (mm) 3/4 (19)
Tube Diameter – in. (mm) 3/8 (9.5)
No. of Rows 6
Fin Density – fins/in. (fins/m) 15.5 (610)
2
) 1.921 (0.178) 2.338 (0.217) 3.483 (0.324)
© Copyright 2010 Heat Controller, Inc.
Bulletin 100-155 — Page 18
PAGE INTENTIONALLY LEFT BLANK
© Copyright 2010 Heat Controller, Inc.
10/2010
Loading...