Heat Controller REG-71A, REG-123A User Manual

+($7&21752//(5,1&
webs
5RRP$LU&RQGLWLRQHU
02'(/65EG-71A
SERVICE MANUAL
6HUYLFH$QG3DUWV0DQXDO
5EG-123A
CAUTION
• BEFORE SERVICING THE UNIT, READ THE SAFETY PRECAUTIONS IN THIS MANUAL.
Air Conditioner Service Manual
TABLE OF CONTENTS
Safety Precautions..........................................................................................................................................3
Dimensions .....................................................................................................................................................5
Symbols Used in this Manual......................................................................................................................5
Outside Dimensions...................................................................................................................................5
Product Specifications ..................................................................................................................................6
Installation.......................................................................................................................................................7
Select the Best Location ...........................................................................................................................7
Installation Check.......................................................................................................................................7
How to Secure the Drain Pipe(When using drain pipe)..............................................................................7
How to Install(Models without Installation Kit)............................................................................................8
How to Install(Models with Installation Kit).................................................................................................9
Suggested Tool Requirements .................................................................................................................11
Operation ......................................................................................................................................................14
Features...................................................................................................................................................14
Control Locations Function of Controls....................................................................................................14
Disassembly..................................................................................................................................................15
Mechanical Parts......................................................................................................................................15
Air Handling Parts ....................................................................................................................................16
Electrical Parts .........................................................................................................................................17
Refrigerating Cycle...................................................................................................................................19
Schematic Diagram.......................................................................................................................................22
Wiring Diagram.........................................................................................................................................22
Troubleshooting Guide.................................................................................................................................23
Piping System ..........................................................................................................................................23
Troubleshooting Guide .............................................................................................................................24
Room Air Conditioner Voltage Limits........................................................................................................26
2 Room Air Conditioner
Service Manual 3
Safety Precautions
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be followed.
Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following indications.
Meanings of symbols used in this manual are as shown below.
WARNING
CAUTION
This symbol indicates the possibility of death or serious injury. This symbol indicates the possibility of injury or damage to property only.
WARNING
Installation
Do not use damaged power cord plugs, or a loose socket.
• There is risk of fire or electric shock.
Always use the power plug and socket with the ground terminal.
• There is risk of electric shock.
Be sure not to do.
Be sure to follow the instruction.
4 Room Air Conditioner
Safety Precautions
Do not modify or extend the power cord.
• There is risk or fire or electric shock.
Do not install, remove, or re-install the unit by yourself(customer).
• There is risk of fire, electric shock, explosion, or injury.
Be cautious when unpacking and installing the product.
• Sharp edges could cause injury. Be especially careful
of the case edges and the fins on the condenser and evaporator.
Do not store or use flammable gas or com­bustibles near the air conditioner.
• There is risk of fire or failure of product.
Be sure the installation area does not deterio­rate with age.
• If the base collapses, the air conditioner could fall with
it, causing property damage, product failure, and per­sonal injury.
Gasolin
Sharp edges
Dimensions
Dimensions
H
W
D
Outside Dimensions
This symbol alerts you to the risk of electric shock.
This symbol alerts you to hazards that could cause harm to the air conditioner.
This symbol indicates special notes.
NOTICE
Symbols Used in this Manual
Service Manual 5
Model
Dimension
W mm(inch) 471(189/16
H mm(inch) 352(13 7/8) 380(14 31/22)
Dmm(inch)525(20 11/16)576(22 1/16)
REG-71A REG-123A
) 600(23
Heat
5
/8)
6 Room Air Conditioner
Specfications
Product Specifications
MODELS
ITEMS
OPERATING
CONDITION
COOLING
HEATING
* DB:Dry Bulb **
WB:Wet Bulb
NOTE: Please refer to Label Quality on the produst since this specification may be changed for improving performance.
POWER SUPPLY
COOLING CAPACITY (Btu/h)
INPUT (W)
RUNNING CURRENT (A)
E.E.R (BTU/W.h)
HEATING CAPACITY (Btu/h)
INPUT (W)
RUNNING CURRENT (A)
REFRIGERANT (R-22) CHARGE
EVAPORATOR
CONDENSER
FAN, INDOOR
FAN, OUTDOOR
FAN SPEEDS, FAN/COOLING/HEATING
FAN MOTOR
OPERATION CONTROL
ROOM TEMP. CONTROL
AIR DIRECTION CONTROL
CONSTRUCTION
ELECTRIC HEATER
PROTECTOR FAN MOTOR
POWER CORD
DRAIN SYSTEM
NET WEIGHT (lbs/kg)
OUTSIDE DIMENSION (inch)
(W x H x D) (mm)
COMPRESSOR
ELECTRIC HEATER
INDOOR(°C)
OUTDOOR(°C)
INDOOR(°C)
OUTDOOR(°C)
REG-71A REG-123A
1Ø,115V, 60Hz 1Ø, 208/230V, 60Hz
6,900 11,500/12,000
710 1,170/1,220
6.6 5.5/5.8
9.7 9.8/9.8
3850 9,200/11,200
1,260 2,900/3,500
11.0 14.0/15.3
26.7 (DB)* 19.4 (WB)**
35 (DB)* 23.9 (WB)**
21.1 (DB)* 15.6 (DB)**
8.3 (DB)* 6.1 (DB)**
385(13.6 oz) 605(21.3 oz)
2ROW 14STACKS 2ROW 13STACKS
2ROW 16STACKS 2ROW 17STACKS
BLOWER
PROPELLER TYPE FAN WITH SLINGER-RING
1 / 2 / 2
6 POLES
TOUCH PANEL
THERMISTOR
VERTICAL LOUVER(RIGHT&LEFT)
HORIZONTAL LOUVER(UP&DOWN)
SLIDE IN-OUT CHASSIS
1.2KW, 115V 3.5KW, 230V
OVERLOAD PROTECTOR
INTERNAL THERMAL PROTECTOR
FUSE LINK, BIMETAL THERMOSTAT
1.6m(3 WIRE WITH GROUNDING)
ATTACHMENT PLUG(CORD-CONNECTED TYPE)
DRAIN PIPE OR SPLASHED BY FAN SLINGER
60/27 87/39
18 X 13 7/8 X 20 11/16 235/8 X 14 31/22 X 22 5/16
470 X 353 X 525 600 X 380 X 525
Service Manual 7
Installation
Installation
Select the Best Location
Installation Check
How to Secure the Drain Pipe(When using drain pipe)
1.To prevent vibration and noise, make sure the unit is installed securely and firmly.
2.Install the unit where the sunlight does not shine directly on the unit.
3.The outside of the cabinet must extend outward for at least 12" and there should be no obstacles, such as a fence or wall, within 20" from the back of the cabinet because it will prevent heat radiation of the condenser. Restriction of outside air will greatly reduce the cooling efficiency of the air conditioner.
CAUTION: All side louvers of the cabinet
must remain exposed to the outside of the structure.
4.Install the unit a little slanted so the back is slightly lower
than the front (about 1/2"). This will help force condensed water to the outside.
5.Install the unit from the bottom about 30"~60" above the
floor level.
The setting conditions must be checked prior to initial starting. The following items are especially important checking points when the installation is finished.
1. Grounding wire (Green or Green and Yellow) is provided in the power cord. The green wire must be grounded.
2. Connect to a single-outlet 15A circuit.
(or 20A circuit for Electric Heater Model)
3. To avoid vibration or noise, make sure the air conditioner is installed securely.
4 Avoid placing furniture or draperies in front of the air inlet and outlet.
In humid weather, excess water may cause the BASE PAN to overflow. To drain the water, remove the DRAIN CAP and secure the DRAIN PIPE to the rear hole of the BASE PAN. Press the drain pipe into the hole by pushing down and away from the fins to avoid injury.
Optional
1. Install the drain pan over the corner of the cabinet where you removed the plug with 4 (or 2) screws.
2. Connect the drain hose to the outlet located at the bottom of the drain pan. You can purchase the drain hose or tubing locally to satisfy your particular needs. (Drain hose is not supplied).
3. Select the most appropriate connection from among the following figures (by considering the hole of the unit) to fit drain pan to your own unit.
AWNING
COOLED AIR
HEAT
RADIATION
30"~60"
ABOUT 1/2"
Over 20"
FENCE
Drain pipe
Drain cap
Fig. 4
Fig. 3
Fig. 2
DRAIN PAN
DRAIN HOSE
Fig. 1
CABINET
SCREW
Figure 1
8 Room Air Conditioner
Installation
How to Install(Models without Installation Kit)
1. Remove the screws that fasten the cabinet at both sides and at the back.
2. Slide the unit from the cabinet by gripping the base pan handle and pulling forward while bracing the cabinet.
3. Remove EPS Material.
4. Slide the unit into the cabinet.
CAUTION: For security pur­pose, reinstall screw at cabi­net's sides.
5. Attach the front grille to the cabinet by inserting the tabs on the grille into the tabs on the fornt of the cabinet. Push the grille in until it snaps into place.
6. Lift the inlet grille and secure it with a screw through the front grille.
Shipping screws
T
IM E
R
ENERGY SAVER
M O
D E
On/Off
On/Off
Fan Cool
Heat
TIMER
E N
E R G
Y S A
V E R
MODE
On/Off
On/Off
Fan
Cool Heat
EPS Material
TIMER
E N E
R G
Y S A V
E
R
MODE
O n
/O
ff
O n /O
ff
F a
n C o
o
l H e
a
t
Power cord
Screw
Screw
TIMER
E N E
R G
Y S A
V
E
R
MODE
O
n
/O
ff
O n
/O f f
F a n
C o o l H e a t
T
IM
E
R
ENERGY SAVER
M
O
D
E
O
n
/
O
f
f O
n
/
O
f
f
F
a
n
C
o
o
l
H
e
a
t
Service Manual 9
Installation
How to Install(Models with Installaion Kit)
When Using Gasket
When Using Installation Kits
1. Window Requirements
This unit is designed for installation in standard double hung windows with actual opening widths from 27" to 39". The top and bottom window sash must open suffi­ciently to allow a clear vertical opening of 16" from the bottom of the upper sash to the window stool.
2. Installation Kits Contents
A
B
DE
F
H
2
3
I
4
2
1
A
RIGHT SIDE
HORIZONTAL LINE
B
1. WINDOW (WIDTH-A, HEIGHT-B)
2. GASKET
3. WALL
4. DETAILS 5.1 x 30 ROUND HEAD WOOD SCREWS
ABCDE F HI
625mm 392mm 280mm 30mm 0~25mm OVER 420mm 5~10mm -5~5mm
(245/
8") (15
7
/
16") (11
1
/
32") (1
1
/
16") (0~1") (OVER 16
17
/
32") (
3
/
16"~
3
/
8") (-
3
/
16"~
3
/
16")
27" to 39"
16" min
Stool
Interior wall
235
/8" min
(Without frame curtain)
Offset
1
/2" to 11/4"
Sill
Exterior
Top retainer bar is in the product package.
NO. NAME OF PARTS Q'TY
1 FRAME CURTAIN 2 2 SILL SUPPORT 2 3 BOLT 2 4 NUT 2 5
SCREW(TYPE A) (10mm(
2
/
5"))
16
6
SCREW(TYPE B)
3
7
SCREW(TYPE C)
5 8 FOAM-STRIP 1 9
FOAM-PE (920mm x 30mm x 2mm)
1
10
UPPER GUIDE
1
11
FOAM-PE
(600mm x 25mm x 2mm)
1
12 FRAME GUIDE 2 13
WINDOW LOCKING BRACKET
1
14 DRAIN PIPE 1
D5.1mm(0.2")/16mm(0.63")
D4.1mm(0.17")/16mm(0.63")
REG-123A
1
5
13
14
12
2 3 4
76
8 9
11
10
Installation
10 Room Air Conditioner
When Using Installation Kits
1. Window Requirements
This unit is designed for installation in standard double hung windows with actual opening widths from 22" to 36". The top and bottom window sash must open suffi­ciently to allow a clear vertical opening of 15" from the bottom of the upper sash to the window stool.
REG-71A
A
B
D
E
F
C
HJ
2
3
4
2
1
G
A
RIGHT SIDE
HORIZONTAL LINE
B
I
TIMER
ENERGY SAVER
MODE
On/OffOn/Off FanCool
Heat
TIMER
E
N
E
R
G
Y S
A
V
E
R
MODE
O
n
/
O
f
f
O
n
/
O
f
f
F
a
n
C
o
o
l
H
e
a
t
1. WINDOW (WIDTH-A, HEIGHT-B)
2. GASKET
3. WALL
4. DETAILS 5.1 x 30 ROUND HEAD WOOD SCREWS
ABCDE F GH J K
495mm 366mm 250mm 30mm 0~25mm OVER 420mm 12mm 32mm 5~10mm 0~5mm
(191/
2") (14
7
/
16") (10") (1
1
/
16") (0~1") (OVER 16
17
/
32") (1/2") (1
1
/
4") (
3
/
16"~
3
/
8") (0~
3
/
16")
2. Installation Kits Contents
22" to 36"
Stool
Interior wall
181/2" min
(Without frame curtain)
Offset
1
/2" to 11/4"
Sill
Exterior
15" min
(With frame curtain)
Top retainer bar is in the product package.
NO. NAME OF PARTS Q'TY
1 FRAME CURTAIN 2 2 SILL SUPPORT 2 3 BOLT 2 4 NUT 2 5
SCREW(TYPE A) (10mm(2/5"))
16
6
SCREW(TYPE B)
3
7
SCREW(TYPE C)
5 8 FOAM-STRIP 1 9
FOAM-PE (920mm x 30mm x 2mm)
1
10
UPPER GUIDE
1
11
FOAM-PE
(600mm x 25mm x 2mm)
1
12 FRAME GUIDE 2 13
WINDOW LOCKING BRACKET
1
14 DRAIN PIPE 1
D5.1mm(0.2")/16mm(0.63") D4.1mm(0.17")/16mm(0.63")
1
13
14
12
2 3 4
8 9
5
76
11
10
Service Manual 11
Suggested Tool Requirements
SCREWDRIVER (+, -), RULER, KNIFE, HAMMER, PENCIL, LEVEL
Installation
Preparation of Chassis
1. Remove the screws that fasten the cabinet at both sides and at the back.
2. Slide the unit out from the cabinet by gripping the base pan handle and pulling forward while bracing the cabinet.
3. Remove EPS Material.
4. Cut the window sash seal to the proper length. Peel off the backing and attach the foam-pe to the underside of the window sash.
5. Remove the backing from the top upper guide Foam PE and attach it to the bottom of the upper guide .
6. Attach the upper guide onto the top of the cabinet with 3 type A screws.
7. Insert the frame guides into the bottom of the cabinet.
8. Insert the Frame Curtain into the upper guide and frame guides .
9. Fasten the curtains to the unit with 4 Type A screws at the both sides.
Shipping screws
O n
/ O f f
O
n / O f f
F a n
C o o
l
TIM
ER
E N
H e
E
a
R
t
G
Y S A
V E R
M O
D E
O n / O
f f
O n / O f
f
F a n
C o o l
TIM E
R
E
N
H e
E
a
R
t
G
Y
S
A V E
R
M O
DE
EPS Material
O
n / O f f
O
n / O f f
F a
n C
o o l
TIM
ER
E N
H
e
E
a
R
t
G
Y S A
V
E
R
M
O D
E
10
9
11
Cabinet Installation
1. Open the window. Mark a line on center of the win­dow sill(or desired air conditioner location). Carefully place the cabinet on the window sill and align the center mark on the bottom front with the center line marked in the window sill.
2. Pull the bottom window sash down behind the upper guide until it meets.
NOTICE
Do not pull the window sash down so tightly that the movement of Frame Curtain is restricted.
10
5
(Type A)
5
Upper Guide
Window Sash
Cabinet
Frame Curtain
(Type A)
5
12
Window sill
12
Front Angle
Upper guide
1
10
Figure 2
Figure 3
12 Room Air Conditioner
INDOOR OUTDOOR
Sill Support
Nut
Bolt
2
4
3
INDOOR OUTDOOR
12
6
7
2
5
Frame Guide
About 1/2"
Screw(Type A)
Cabinet
6
2
About 1/2"
Screw(Type B)5Screw(Type A)
Sill support
Sash track
Front Angle
Type C
Screw(Type B)
Sill support
3. Loosely assemble the sill support using the parts in Figure 4.
4. Select the position that will place the sill support near the outer most point on sill (See Figure 4)
Be careful when you install the cabinet (Frame Guides are broken easily).
5. Attach the sill support to the cabinet track hole in relation to the selected position using 2 Type A screws in each support (See Figure 5).
6. The cabinet should be installed with a very slight
tilt (about 1/
2") downward toward the outside
(See Figure 6). Adjust the bolt and the nut of Sill Support for bal­ancing the cabinet.
7. Attach the cabinet to the window stool by driving the screws
(Type B) through the front
angle into window stool (5/8").
8. Pull each Frame Curtain properly to each window sash track, and repeat step 2.
9. Attach each Frame Curtain to the window sash by using screws (Type C).(See Figure 7)
NOTICE
Figure 4
Figure 5
Figure 6
Figure 7
Installation
Service Manual 13
Installation
13
8
Foam-Strip
Screw(Type A)
Screw(Type A)
Power cord
TIMER
E N E R G
Y S A V E
R
MODE
O n /O f
f
O n /O ff
Fa
n C o o l H e a t
T
I
M
E
R
E
N
E
R
G
Y S
A
V
E
R
M
O
D
E
On/OffOn/Off
FanCool
Heat
TIMER
ENERGY SAVER
MODE
On/OffOn/Off FanCool
Heat
10. Slide the unit into the cabinet.(See Fig. 8)
CAUTION:
For security purpose, reinstall
screws (Type A) at the cabinet's sides.
11. Cut the Foam-Strip to the proper length and insert between the upper and lower window sash. (See Fig. 9)
12. Attach the window Locking Bracket with a type C screw. (See Fig. 10)
13. Attach the front grille to the cabinet by inserting the tabs on the grille into the tabs on the front of the cab­inet. Push the grille in until it snaps into place. (See Fig. 11)
14. Lift the inlet grille and secure it with a type A screw through the front grille.(See Fig. 12)
Figure 11
Figure 8
Figure 9
Figure 10
Figure 13
Figure 12
14 Room Air Conditioner
Designed for COOLING and HEATING.
Powerful and whispering cooling.
Slide-in and slide-out chassis for the simple instal-
lation and service.
Side air-intake, side cooled-air discharge.
Built-in adjustable THERMOSTAT
Washable one-touch filter
Compact size
Reliable and efficient rotary compressor
Operation
Operation
Features
Control Locations Function of Controls
CLOSE VENT OPEN
Power
Temp
Fan Speed
Timer Mode
Energy
Saver
1
4
2
7
3
5
Power
Temp
Fan Speed
Timer Mode
Energy
Saver
Auto
Swing
1
4
2
8
7
3
5
REMOTE CONTROLLER
1. POWER BUTTON
To turn the air conditioner ON, push the button. To turn the air conditioner OFF, push the button again. This button takes priority over any other buttons.
2. OPERATION MODE SELECTION BUTTON
Everytime you push this button, it will toggle COOL, FAN and HEAT.
3. ON/OFF TIMER BUTTON
Everytime you push this button, timer is set as follows.(1Hour 2Hours 3Hours 4Hours 5Hours
6Hours 7Hours 8Hours 9Hours 10Hours 11Hours 12Hours Cancel)
4. FAN SPEED SELECTOR
Everytime you push this button, it is set as follows.
(Hi[ ] Low[ ] Hi[ ]....)
5. ROOM TEMPERATURE SETTING BUTTON
This button can automatically control the temperature of the room. The temperature can be set within a range of 60°F to 86°F by 1°F.
6. ENERGY SAVER
The fan stops when the compressor stops cooling. Approximately every 3 munutes the fan will turn on and check the room air to determine if cooling is needed.
7. REMOCON SIGNAL RECEIVER
8. AUTO SWING
This button can automatically control the air flow direction.
CAUTION: A slight heat odor may come from the unit when first
switching to HEAT after the cooling season is over. This odor, caused by fine dust particles on the heater, will disappear quickly.
• VENTILATION
The ventilation lever must be in the CLOSE position in order to maintain the best cooling conditions.
When a fresh air is necessary in the room, set the ven­tilation lever to the OPEN position.
The damper is opened and room air is exhausted.
REG-123A
3
2
6
6
4
4
5
5
4
Heat
3
REG-71A
77
3 6 2 5 11
REG-123A REG-71A
Service Manual 15
Disassembly
Disassembly
Mechanical Parts
Before the following disassembly, CONTROL BOX set to OFF and disconnect the power cord.
1. Front Grille
1. Open the lnlet grille upward .
2. Remove the screw that fastens the front grille.
3. Pull the front grille from the right side.
4. Remove the front grille.
5. Re-install the component by referring to the removal
procedure, above.(See Figure 14)
2. Cabinet
1. After disassembling the FRONT GRILLE, remove the 2 screws that fasten the cabinet at both sides.
2. Remove the 2 screws that fasten the cabinet at back.
3. Pull the base pan forward. (See Figure 15)
4. Remove the cabinet.
5. Re-install the component by referring to the removal procedure, above.
3. Control Box
1. Remove the front grille. (Refer to section 1)
2. Remove the cabinet. (Refer to section 2)
3. Remove the 2 screws that fasten the control box cover.
4. Remove two housings that connect compressor wire and motor wire in the control box.
5. Discharge the capacitor by placing a 20,000 ohm resistor across the capacitor terminals.
6. Remove the 2 screws that fasten the control box.
7. Pull the control box forward completely.
8. Re-install the components by referring to the removal procedure, above. (See Figure 16) (Refer to the circuit diagram found on page 23 in this manual and on the control box.)
2
3
4
8
7
6
5
Off
M
e
d F
a
n
H
ig
h
C
oo
l
TIM
ER
ENERGY SAVER
M ODE
On/Off
On/Off
Fan
Cool Heat
TIM
ER
ENERGY SAVER
M
O
DE
On/Off
On/Off
Fan
Cool Heat
Figure 14
Figure 16
Figure 15
16 Room Air Conditioner
Disassembly
TIM
ER
ENERG
Y
SAVER
MODE
On/Off
On/Off
Fan
Cool H
eat
Figure 17
Figure 18
Figure 19
Figure 20
4. Air Guide and Turbo Fan
1. Remove the front grille. (Refer to section 1)
2. Remove the cabinet. (Refer to section 2)
3. Remove the control box. (Refer to section 3)
4. Remove the 4 screws that fasten the brace.
5. Remove the brace.
6. Remove the 2 screws that fasten the evaporator.
7. Move the evaporator forward and pulling it upward slightly. (See Figure 17)
8. Move the evaporator to the left carefully.
9. Remove the 2 terminals carefully. (See Figure 18, at Electric heater Model)
10. Remove the 3 screws that fasten the Heater
Cover. (See Figure 18, at Electric Heater Model)
11. Remove the Heater cover. (See Figure 18, at
Electric Heater Model)
12. Pull out the hook of orifice by pushing the tabs
and remove it. (See Figure 19)
13. Remove the clamp with a hand plier that secures
the blower.
14. Remove the blower.
15. Remove the 4 screws that fasten the air guide
from the barrier.
16. Move the air guide backward, pulling out from
the base pan.
17. Re-install the components by referring to the
removal procedure, above.
5. FAN
1. Remove the cabinet. (Refer to section 2)
2. Remove the brace (Refer to section 4)
3. Remove the 4 screws that fasten the condenser.
4. Move the condenser to the left carefully.
5. Remove the clamp that secures the fan.
6. Remove the fan. (See Figure 20)
7. Re-install by referring to the removal procedure.
Air Handling Parts
Service Manual 17
6. Shroud
1. Remove the fan. (Refer to section 5)
2. Remove the screw that fastens the shroud.
3. Remove the shroud. (See Figure 21)
4. Re-install the component by referring to the removal procedure, above.
7. Overload Protector
1. Remove the cabinet. (Refer to section 2)
2. Remove the nut that fastens the terminal cover.
3. Remove the terminal cover. (See Figure 22)
4. Remove all the leads from the overload protec­tor.
5. Remove the overload protector.
6. Re-install the component by referring to the removal procedure, above.
8. Compressor
1. Remove the cabinet. (Refer to section 2)
2. Discharge the refrigerant system using a FreonRecovery System. If there is no valve to attach the recovery sys­tem, install one (such as a Watco A-1) before venting the Freon.. Leave the valve in place after servicing the system.
3. Remove the overload protector. (Refer to sec­tion 7)
4. After purging the unit completely, unbraze the suction and discharge tubes at the compressor connections.
5. Remove the 3 nuts and the 3 washers that fasten the compressor.
6. Remove the compressor. (See Figure 23)
7. Re-install the components by referring to the removal procedure, above.
Disassembly
Electrical Parts
Figure 21
Figure 22
Figure 23
18 Room Air Conditioner
Disassembly
9. Capacitor
1. Remove the control box. (Refer to section 3)
2. Remove the knobs and the screw that fasten control panel from control box.
3. Remove the screw that located in the front.
4. Open the bottom side of control box.
5. Remove the screw and the clamp that fastens the capacitor.
6. Disconnect all the leads of capacitor terminals.
7. Re-install the components by referring to the removal procedure, above. (See Figure 24)
10. Power Cord
1. Remove the control box. (Refer to section 3)
2. Open the control box. (Refer to section 9)
3. Disconnect the grounding screw from the control box.
4. Disconnect the 2 receptacles.
5. Remove a screw which fastens the clip cord. (See Figure 25)
6. Remove the power cord.
7. Re-install the component by referring to the above removal procedure, above. (Use only one ground-marked hole for ground connection.)
8. If the supply cord of this appliance is damaged, it must be replaced by the special cord. (The special cord means the cord that has the same specification marked on the supply cord attached at the unit.)
11. Thermistor
1. Remove the control box. (Refer to section 3)
2. Open the control box. (Refer to section 6)
3. Disconnet the thermistor terminals from main
P.W.B assembly.
4. Remove the thermistor.
5. Re-install the components by refereing to the above removal procedure. (See Figure 26)
12. SYNCHRONOUS MOTOR
1. Remove the control box. (Refer to section 3)
2. Unfold the control box. (Refer to section 10)
3. Remove the crankshaft.
4. Disconnect all the leads of the synchronous motor.
5. Remove the 2 screws which fasten the synchronous motor. (See Fig. 27)
6. Re-install the components by referring to the removal procedure, above.
Figure 24
Figure 25
Figure 26
Figure 27
Service Manual 19
Disassembly
13. Motor
1. Remove the cabinet. (Refer to section 2)
2. Remove the evaporator. (Refer to section 4)
3. Remove the orifice. (Refer to section 4)
4. Remove the blower. (Refer to section 4)
5. Remove the fan. (Refer to section 5)
6. Remove the control box cover and disconnect 5 or 4 wires of motor housing. (Refer to section 3)
7. Remove the 2 or 4 screws that fasten the motor from the mount motor. (See Figure 28)
8. Remove the motor.
9. Re-install the components by referring to the removal procedure, above.(See Figure 28)
CAUTION: Discharge the refrigerant
system using a FreonTMRecovery System. If there is no valve to attach the recovery system, install one (such as a WATCO A-1) before venting the FreonTM. Leave the valve in place after servicing the system.
14. Condenser
1. Remove the cabinet. (Refer to section 2)
2. Remove the 4 screws that fasten the brace.(Refer to section 4)
3. Remove the 5 screws that fasten the condenser and shroud.
4. After discharging the refrigerant completely, unbraze the interconnecting tube at the con­denser connections.
5. Remove the condenser.
6. Re-install the component by referring to notes. (See Figure 29)
15. Evaporator
1. Remove the cabinet. (Refer to section 2)
2. Remove the 2 screws that fasten the evaporator.
3. Move the evaporator sideways carefully. (Refer to section 4)
4. After discharging the refrigerant completely, unbraze the interconnecting tube at the evapo­rator connections.
5. Remove the evaporator.
6. Re-install the component by referring to notes. (See Figure 30)
Figure 28
Figure 29
Figure 30
Refrigerating Cycle
20 Room Air Conditioner
Disassembly
16. Capillary Tube
1. Remove the cabinet. (Refer to section 2)
2. After discharging the refrigerant completely, unbraze the interconnecting tube at the capil­lary tube.(See caution above)
NOTICE
Replacement of the refrigeration cycle.
1. When replacing the refrigeration cycle, be sure to Discharge the refrigerant system using a Freon recovery System. If there is no valve to attach the recovery system, install one (such as a WATCO A-1) before venting the FreonTM. Leave the valve in place after servicing the system.
2. After discharging the unit completely, remove the desired component, and unbraze the pinch-off tubes.
3. Solder service valves into the pinch-off tube ports, leaving the valves open.
4. Solder the pinch-off tubes with Service valves.
5. Evacuate as follows.
1) Connect the vacuum pump, as illustrated figure
31A.
2) Start the vacuum pump, slowly open manifold
valves A and B with two full turns counterclock­wise and leave the valves open. The vacuum pump is now pulling through valves A and B up to valve C by means of the manifold and entire system.
TM
CAUTION: If high vacuum equip-
ment is used, just crack valves A and B for a few minutes, then open slowly with the two full turns counterclockwise. This will keep oil from foaming and being drawn into the vacuum pump.
3) Operate the vacuum pump vaccum for 20 to 30 minutes, until 600 microns of vacuum is obtained. Close valves A and B, and observe vacuum gauge for a few minutes. A rise in pressure would indicate a possible leak or moisture remaining in the system. With valves A and B closed, stop the vacuum pump.
4) Remove the hose from the vacuum pump and place it on the charging cylinder. See figure 31B. Open valve C. Discharge the line at the manifold connection.
5) The system is now ready for final charging.
3. Remove the capillary tube.
4. Re-install the component by referring to notes.
6. Recharge as follows :
1) Refrigeration cycle systems are charged from the High-side. If the total charge cannot be put in the High-side, the balance will be put in the suction line through the access valve which you installed as the system was opened.
2) Connect the charging cylinder as shown in fig­ure 31B. With valve C open, discharge the hose at the manifold connection.
3) Open valve A and allow the proper charge to enter the system. Valve B is still closed.
4) If more charge is required, the high-side will not take it. Close valve A.
5) With the unit running, open valve B and add the balance of the charge.
a. Do not add the liquid refrigerant to the Low-
side.
b. Watch the Low-side gauge; allow pressure to
rise to 30 lbs. c. Turn off valve B and allow pressure to drop. d. Repeat steps b. and c. until the balance of the
charge is in the system.
6) When satisfied the unit is operating correctly, use the pinch-off tool with the unit still running and clamp on to the pinch-off tube. Using a tube cutter, cut the pinch-off tube about 2 inches from the pinch-off tool. Use sil-fos braze and braze pinch-off tube closed. Turn off the unit, allow it to set for a while, and then test the leak­age of the pinch-off connection.
Service Manual 21
Disassembly
A
COMPOUND GAUGE
EVAPORATOR (LOW PRESSURE SIDE)
COMPRESSOR
CAPILLARY TUBE
CONDENSER (HIGH PRESSURE SIDE)
SEE INSETS
BELOW
MANIFOLD
GAUGE
B
Figure 31A-Pulling Vacuum
Figure 31B-Charging
A
B
EXTERNAL VACUUM PUMP
A
CHARGING CYLINDER
LOW
HI
B
C
Equipment needed: Vacuum pump, Charging cylinder, Manifold gauge, Brazing equipment. Pinch-off tool capable of making a leak-proof seal, Leak detector, Tubing cutter, Hand Tools to remove components, Service valve.
22 Room Air Conditioner
Schematic Diagram
Schematic Diagram
Wiring Diagram
ELECTRIC HEATING MODEL
Service Manual 23
Troubleshooting Guide
Troubleshooting Guide
Piping System
Figure 32 is a brief description of the important components and their function in what is called the refrigeration system. This will help you to understand the refrigeration cycle and the flow of the refrigerant in the cooling cycle.
MOTOR
COMPRESSOR
OIL
(LIQUID REFRIGERANT)
CAPILLARY TUBE
OUTSIDE COOLING AIR FOR REFRIGERANT PASS THROUGH
SUCTION LINE COOL LOW PRESSURE VAPOR
COOLED AIR
COMPLETE LIQUID BOIL OFF POINT
LIQUID PRESSURE DROP
ROOM AIR HEAT LOAD
VAPOR INLET
HOT DISCHARGED AIR
LIQUID OUTLET
HIGH PRESSURE VAPOR LIQUID REFRIGERANT LOW PRESSURE VAPOR
ROOM AIR CONITIONER
EVAPORATOR COILS CONDENSER COILS
CYCLE OF REFRIGERATION
Figure 32
CONDENSER COIL
FAN
CAPILLARY TUBE
MOTOR
COMPRESSOR
BLOWER
EVAPORATOR COIL
24 Room Air Conditioner
Troubleshooting Guide
Troubleshooting Guide
In general, possible trouble is classified in two kinds. The one is called Starting Failure which is caused from an electrical defect, and the other is ineffective Air
Conditioning caused by a defect in the refrigeration circuit and improper application.
Unit runs but poor cooling.
Ineffective Cooling
Check outdoor coil (heat exchanger) & the fan operation.
Check gas leakage.
Repair gas leak.
Replacement of unit if the unit is beyond repair.
Satisfactory operation with temperature difference of inlet & outlet air ; 44~50°F(7~10°C)
Check heat load increase.
Clean condenser.
Not on separate circuit.
Check inside gas pressure.
Adjusting of refrigerant charged.
Malfunction of compressor.
Replacement of compressor.
Check cold air circulation for smooth flow.
Dirty indoor coil (Heat exchanger)
Correct above trouble
Check clogging in refrigera­tion circuit.
Repair clogging in refrigera­tion circuit.
Obstruction at air outlet
Clogged of air filter.
Malfunction of fan
Service Manual 25
Troubleshooting Guide
Fails to Start
Check circuit breaker and fuse.
Gas leakage of feeler bulb of thermostat
Check of control switch.
Fan only fails to start.
Improper wiring.
Defect of fan motor capacitor.
Irregular motor resistance (
). Irregular motor insulation (
).
Replacement of fan motor.
Regular but fails to start.
Replacement of compressor (locking of rotor, metal).
Improper thermostat setting.
Loose terminal connection.
Improper wiring.
Irregular motor resistance ( )
Irregular motor insulation ( )
Replacement of compressor (Motor damaged)
Drop of power voltage.
Capacitor check.
Replacement
Compressor only fails to start.
Defect of compressor capacitor.
Check of power source.
Check of control switch setting.
26 Room Air Conditioner
Troubleshooting Guide
COMPLAINT CAUSE REMEDY
Check voltage at outlet. Correct if necessary. Check voltage to rotary switch. If none, check power
supply cord. Replace cord if circuit is open. Check switch continuity. Refer to wiring diagram for
terminal identification. Replace switch if defective. Connect wire. Refer to wiring diagram for terminal
identification. Repair or replace loose terminal. Test capacitor.
Replace if not within ±10% of manufacturer's rating. Replace if shorted, open, or damaged.
Fan blade hitting shroud or blower wheel hitting scroll. Realign assembly.
Units using slinger ring for condenser fan must have
1
/4to 5/16inch clearance to the base. If it hits the base, shim up the bottom of the fan motor with mounting screw(s).
Check fan motor bearings; if motor shaft will not rotate, replace the motor.
Check voltage. If not within limits, call an electrician. Test capacitor.
Check bearings. Does the fan blade rotate freely? If not, replace fan motor.
Pay attention to any change from high speed to low speed. If the speed does not change, replace the motor.
If cracked, out of balance, or partially missing, replace it.
If cracked, out of balance, or partially missing, replace it.
Tighten it. If knocking sounds continue when running or loose,
replace the motor. If the motor hums or noise appears to be internal while running, replace motor.
Check voltage. If not within limits, call an electrician.
Check the wire connections, if loose, repair or replace the terminal. If wires are off, refer to wiring diagram for identification, and replace. Check wire locations. If not per wiring diagram, correct.
Check for continuity, refer to the wiring diagram for terminal identification. Replace the switch if circuit is open.
No power Power supply cord
Rotary switch
Wire disconnected or con­nection loose
Capacitor (Discharge capacitor before testing.)
Will not rotate
Revolves on overload.
Fan
Blower
Loose clamper Worn bearings
Voltage
Wiring
Rotary
Fan motor will not run.
Fan motor runs intermittently
Fan motor noise.
Compressor will not run, but fan motor runs.
NAME PLATE RATING MINIMUM MAXIMUM
208~230±10% 187V 253V
115±10% 104V 126V
Room Air Conditioner Voltage Limits
Service Manual 27
Troubleshooting Guide
COMPLAINT CAUSE REMEDY
Check the position of knob If not at the coldest set­ting, advance the knob to this setting and restart unit. Check continuity of the thermostat. Replace ther­mostat if circuit is open.
Check the capacitor. Replace if not within ±10% of manufacturers rat­ing. Replace if shorted, open, or damaged.
Check the compressor for open circuit or ground. If open or grounded, replace the compressor.
Check the compressor overload, if externally mounted. Replace if open. (If the compressor tem­perature is high, remove the overload, cool it, and retest.)
Check the voltage. If not within limits, call an electrician.
Check overload, if externally mounted. Replace if open. (If the compressor temperature is high, remove the overload, cool, and retest.)
If not running, determine the cause. Replace if required.
Remove the cabinet. inspect the interior surface of the condenser; if restricted, clean carefully with a vacuum cleaner (do not damage fins) or brush. Clean the interior base before reassembling.
If condenser fins are closed over a large area on the coil surface, head pressures will increase, causing the compressor to overload. Straighten the fins or replace the coil.
Test capacitor. Check the terminals. If loose, repair or replace. Check the system for a restriction. If restricted, clean of replace. Close if open. Determine if the unit is properly sized for the area
to be cooled. Check the set screw or clamp. If loose or missing,
correct. If the blower or fan is hitting air guide, rearrange the air handling parts.
Remove the cabinet carefully and rearrange tubing not to contact cabinet, compressor, shroud, and barrier.
Set the knob to HIGH COOL or LOW COOL while rocker switch is ON. Check terminals. If loose, repair or replace. Check the synchronous motor for open circuit.
Thermostat
Capacitor (Discharge capacitor before servicing.)
Compressor
Overload
Voltage
Overload
Fan motor
Condenser air flow restric­tion
Condenser fins (damaged)
Capacitor Wiring Refrigerating system Air filter Exhaust damper door Unit undersized
Blower or fan
Copper tubing
Rotary switch.
Wiring Synchronous motor.
Compressor will not run, but fan motor runs.
Compressor cycles on overload.
Compressor cycles on overload.
Compressor cycles on overload.
Insufficient cooling or heat­ing
Excessive noise
Auto air-swing fails.
6SHFLILFDWLRQVDQGSHUIRUPDQFHGDWDVXEMHFWWRFKDQJHZLWKRXWQRWLFH
+($7&21752//(5,1&
:(//:257+$9(18(-$&.6210,&+,*$1
7+(48$/,7</($'(5,1&21',7,21,1*$,5
04/18/07
Loading...