Heat Controller MMH18DA-1, MMH24DA-1, MMC36TA-1, MMH36TA-1, MMC24DA-1 User Manual

...
HEAT CONTROLLER, INC.
Wall Mounted Multi-Zone Split System
MMC18DA-1 MMH18DA-1 MMC24DA-1 MMH24DA-1 MMC36TA-1 MMH36TA-1
Air Conditioning / Heat Pump
2 Wall Mounted Multi-Zone Split System Air Conditioner
Wall Mounted Multi-Zone Split System Air Conditioner Installation Manual
Installation Parts Provided.........................................3
Safety Precautions......................................................4
Installation of Indoor, Outdoor Unit...........................7
Select the best location ...........................................7
Seaside Applications and Installation.......................8
Piping length and elevation ......................................9
Mounting Installation Plate .....................................10
Drilling the hole in the wall .....................................10
Flaring Work and Connection of Piping..................11
Flaring work............................................................11
Connecting the Piping ............................................12
Connecting the Cable between Indoor Unit
and Outdoor Unit.......................................................18
Connect the cable to the Indoor unit. .....................18
Connect the cable to the Outdoor unit. ..................19
Methods of connecting the cable ...........................20
Connect the cable to the indoor unit ......................21
Checking the Drainage, Insulating the pipe and
Special piping applications......................................22
Checking the drainage............................................22
Insulating the pipe and Special piping applications.
................................................................................23
Air Purging and Evacuation.....................................24
Leak Checking........................................................24
Evacuation..............................................................25
Charging.....................................................................26
Test Running..............................................................27
Level gauge
Screw driver
Electric drill
Hole core drill (ø 70 mm/ø 1.97 inch)
Flaring tool set
Specified torque wrenches
1.8 kg.m, 4.2 kg.m, 5.5 kg.m, 6.6 kg.m (13 lbf.ft, 30 lbf.ft, 47.7 lbf.ft) (different depending on model No.)
Adjustable wrench
A glass of water
Hexagonal wrench(4 mm/0.16 inch)
Refrigerant Gas Leak Detector
Vacuum pump
Gauge manifold
Owner's manual
Thermometer
Remote Control Holder
Installation Requirements
Required Tools
Installation Manual 3
Installation Parts Provided
Installation Parts Provided
Type "A" screws and plastic anchors
Type "B" screws
Remote Control Holder
Installation plate
Standard Type
more than
70 cm
(27.6 inch)
more than
30 cm
(11.8 inch)
more than
30 cm
(11.8 inch)
Air Outlet
Air Intake
(side, rear)
Connection pipe Drain hose
Connecting wire
Control cover
more than 30 cm
(11.8 inch)
more than
70 cm
(27.6 inch)
more than
60 cm
(23.6 inch)
more than
60 cm
(23.6 inch)
18/24K BTU/h
36K BTU/h
more than
30 cm
(11.8 inch)
more than
30 cm
(11.8 inch)
Air Outlet
Air Intake
(side, rear)
Connection pipe Drain hose
Connecting wire
Control cover
more than 30 cm
(11.8 inch)
4 Wall Mounted Multi-Zone Split System Air Conditioner
Do not use a defective or underrated circuit breaker. Use this appliance on a dedicated circuit.
There is risk of fire or electric shock.
For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized Service Center.
Do not disassemble or repair the product. There is risk of fire or electric shock.
Always electrically ground the product.
There is risk of fire or electric shock.
Install the panel and the cover of control box securely.
There is risk of fire or electric shock.
Always install a dedicated circuit and breaker.
Improper wiring or installation may cause fire or electric shock.
Use the correctly rated breaker or fuse.
There is risk of fire or electric shock.
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be followed.
Incorrect operation due to ignoring instructions will cause harm or damage. The seriousness is classified by the following indications.
Meanings of symbols used in this manual are as shown below.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage.
WARNING
Be sure not to do.
Be sure to follow the instruction.
Safety Precautions
Installation
WARNING
CAUTION
Installation Manual 5
Safety Precautions
Do not modify or extend the power cable.
There is risk of fire or electric shock.
Be cautious when unpacking and installing the product.
Sharp edges could cause injury. Be especially careful of the case edges and the fins on the condenser and evaporator.
For installation, always contact the dealer or an Authorized Service Center.
There is risk of fire, electric shock, explosion, or injury.
Do not install the product on a defective installation stand.
It may cause injury, accident, or damage to the product.
Do not let the air conditioner run for a long time when the humidity is very high and a door or a window is left open.
Moisture may condense and dampen or damage furniture.
Be sure the installation area does not deteriorate with age.
If the base collapses, the air conditioner could fall with it, causing property damage, product failure, and personal injury.
Install the indoor unit on the wall where the height from the floor is more than 8 ft. (2.4m).
There are sharp moving parts that could cause personal injury.
Do not handle the pipe by yourself(customer)
High-Pressure refrigent may cause personal injury.
8ft(2.4m)
6 Wall Mounted Multi-Zone Split System Air Conditioner
Safety Precautions
CAUTION
Installation
Always check for gas (refrigerant) leakage after installation or repair of product.
Low refrigerant levels may cause failure of product.
Install the drain hose to ensure that water is drained away properly.
A bad connection may cause water leakage.
Keep level even when installing the product.
To avoid vibration or water leakage.
Do not install the product where the sound or hot air from the outdoor unit could be offensive to neighbors.
It may cause a problem for your neighbors.
Use two or more people to lift and transport the product.
Avoid personal injury.
Do not install the product where it will be exposed to salt spray directly.
It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient operation.
Do not store or use flammable gas or combustibles near the product.
There is risk of fire or failure of product.
Operation
Gasolin
90°
Installation Manual 7
Installation of Indoor, Outdoor Unit
Installation of Indoor, Outdoor Unit
Read completely, then follow step by step.
Indoor unit
1. Does not have any heat or steam near the unit.
2. Select a place where there are no obstacles in front of the unit.
3. Make sure that condensation drainage can be conveniently routed away.
4. Do not install near a doorway.
5. Ensure the unit is unobstructed, allow proper space on all sides according to the arrows and distance measurements in the figures.
6. Use a stud finder to locate studs to prevent unnecessary damage to the wall.
Outdoor unit
1. If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that heat radiation from the condenser is not restricted.
2. Ensure the unit is unobstructed, allow proper space on all sides according to the arrows and distance measurements in the figures.
3. Do not place animals and plants in the path of the warm air.
4. Take the air conditioner weight into account and select a place where noise and vibration are minimum.
5.
Select a place so that the warm air and sound from the air conditioner does not disturb neighbors.
Rooftop Installations:
If the outdoor unit is installed on a roof structure, be sure to level the unit. Ensure the roof structure and anchoring method are adequate for the unit location. Consult local codes regarding rooftop mounting.
Select the best location
More than 20 cm
(7.9 inch)
More than 10 cm
(3.9 inch)
More than 10 cm
(3.9 inch)
More than 2.4m
(8 ft)
CAUTION: Install the indoor unit on the wall where the height from the floor is more than 2.4 m (8 ft).
18/24K BTU/h
Indoor Unit
36K BTU/h
more than 30 cm
(11.8 inch)
more than 70 cm
(27.6 inch)
more than 30 cm
(11.8 inch)
more than 70 cm
(27.6 inch)
more than 30 cm
(11.8 inch)
more than 60 cm
(23.6 inch)
more than 30 cm
(11.8 inch)
more than 60 cm
(23.6 inch)
Seaside Applications and Installation
8 Wall Mounted Multi-Zone Split System Air Conditioner
Installation of Indoor, Outdoor Unit
1.
Air conditioners should not be installed in areas where corrosive gases, such as acid or alkaline gas, are produced.
2. Do not install the product where it could be exposed to sea wind (salty wind) directly. It can result in corrosion to the product. Particularly on the condenser and evaporator fins, could cause product malfunction or inefficient performance.
3.
If the outdoor unit is installed close to the seaside, ensure that it is not exposed directly to the sea wind.
1) If the outdoor unit is to be installed close to the seaside, direct exposure to the sea wind should be avoided. Install the outdoor unit on the opposite side of the sea wind direction.
2) To install the outdoor unit on the seaside, set up a windbreaker/barrier, to lessen the unit's exposure to sea air
3) Select a well-drained place.
It should be strong enough (like concrete) to obstruct the wind from the sea.
The height and width should be more than 150% of the outdoor unit.
A minimum of 70cm (27.6inches)
of space between outdoor unit and the windbreaker/ barrier for easy air flow.
Sea wind Sea wind
Sea wind
Windbreaker/Barrier
Periodic ( more than once/year ) cleaning of the dust or salt particles stuck on the heat exchanger using water is recommended.
1. Selecting the location(Outdoor Unit)
Installation Manual 9
Installation of Indoor, Outdoor Unit
Multi-Zone Piping Recommendations:
Piping length and elevation
18K BTU/h 30 m (100 ft) 15 m (50 ft) 3 m (10 ft) 7.5 m (25 ft) 7.5 m (25 ft)
24K BTU/h 30 m (100 ft) 15 m (50 ft) 3 m (10 ft) 7.5 m (25 ft) 7.5 m (25 ft)
36K BTU/h 45 m (150 ft) 15 m (50 ft) 3 m (10 ft) 7.5 m (25 ft) 7.5 m (25 ft)
Capacity
Max total length
of all pipes
(A+B/A+B+C)
Max length of
each pipe
(A/B/C)
Min length of
each pipe
(A/B/C)
Max Elevation between each
indoor unit and
outdoor unit (h1)
Max elevation
between indoor
units (h2)
h2
h2
h1
A
B
B
C
h2
h1
A
B
h1
h1
h1
CAUTION: Capacity is based on standard length and maximum allowance length based on reliability.
9K BTU/h 9.52 mm (3/8") 6.35 mm (1/4") 7.5 m (25 ft) 20 g/m (0.22 oz/ft)
12K BTU/h 9.52 mm (3/8") 6.35 mm (1/4") 7.5 m (25 ft) 20 g/m (0.22 oz/ft)
Gas (Flare) Liquid (Flare) Standard Length
Additional
Refrigerant
Indoor Capacity
Pipe Size
18/24K BTU/h
36K BTU/h
Drill the piping hole with a Ø 70 mm (Ø 2.75 inch) hole core drill. Drill the piping hole at either the right or the left with the hole slightly slanted to the outdoor side.
Drilling the hole in the wall
5-7 mm
(0.2"~0.3")
Indoor
WALL
Outdoor
10 Wall Mounted Multi-Zone Split System Air Conditioner
Installation of Indoor, Outdoor Unit
The wall you select should be strong and solid enough to prevent vibration
1. Mount the installation plate on the wall with
type "A" screws. If mounting the unit on a concrete wall, use anchor bolts.
Mount the installation plate horizontally by aligning the centerline using a level.
2. Measure the wall and mark the centerline. It
is also important to use caution concerning the location of the installation plate-routing of the wiring to power outlets is through the walls typically.
Mounting Installation Plate
Installation Plate
Type "A" screw
Chassis
Hook
ABCD
9K BTU/h 50 (1.97) 105 (4.13) 59 (2.32) 105 (4.13)
12K BTU/h 65 (2.56) 110 (4.33) 85 (3.35) 110 (4.33)
CHASSIS
(Grade)
Distance mm (inch)
D
C
Ø 70 mm
Ø 2.75 inch
Left rear piping Right rear piping
Installation plate
A
B
Ø 70 mm
Ø 2.75 inch
Installation Manual 11
Flaring Work and Connection of Piping
Flaring Work and Connection of Piping
Flaring work
Main cause for gas leakage is due to defect in flaring work. Carry out the correct flaring work by using the following procedures.
Cut the pipes
1. Use the piping kit accessory or the pipes purchased locally.
2. Measure the distance between the indoor and the outdoor unit.
3. Cut the pipes a little longer than measured distance.
4. Cut the cable 1.5 m (5.0 ft) longer than the pipe length.
Burrs removal
1. Completely remove all burrs from the cut cross section of pipe/tube.
2. Put the end of the copper tube/pipe in a downward direction as you remove burrs in order to avoid dropping burrs into the tubing.
Putting flare nuts on
1. Remove flare nuts attached to indoor and outdoor unit, then put them on pipe/tube having completed burr removal. (not possible to put them on after flaring work)
Flaring work
1. Carry out flaring work using flaring tool as shown below.
2. Firmly hold copper pipe in a bar in the dimension shown in the table below.
Copper
pipe
90°
Slanted Uneven Rough
mm inch mm inch
Ø6.35 1/4 1.1~1.3 0.4 - 0.5 Ø9.52 3/8 1.5~1.7 0.6 - 0.7
Outside diameter A
Bar
Copper pipe
Clamp handle
Red arrow mark
Cone
Yoke
Handle
Bar
"A"
Pipe
Reamer
Point down
Flare nut
Copper tube
12 Wall Mounted Multi-Zone Split System Air Conditioner
Flaring Work and Connection of Piping
Check
1. Compare the flared work with the figure on the right.
2. If a flared section is defective, cut it off and repeat the flaring process again.
Indoor
1. Prepare the indoor unit's piping and drain hose for installation through the wall.
2. Remove the plastic tubing retainer(see the illustration on the right) and pull the tubing and drain hose away from chassis.
1. Route the indoor tubing and the drain hose in the direction of rear right.
2.
Insert the connecting cable into the indoor unit from the outdoor unit through the piping hole.
Do not connect the cable to the indoor unit.
Make a small loop with the cable for easy
connection later.
3. Tape the tubing, drain hose, and the connecting on cable. Be sure that the drain hose is located on the lowest side of the bundle. Locating on the upper side can cause the condensation to overflow in the drain pan inside the indoor unit.
If the drain hose is routed inside the room, insulate the hose with an insulation material* so that dripping from "sweating"(condensation) will not damage furniture or floors. *Foamed polyethylene or equivalent is recommended.
Inclined
Inside is shiny without scratches
Smooth all round
Even length
all round
Surface
damaged
Cracked Uneven
thickness
= Improper flaring =
Connecting the Piping
For right rear piping
Drain hose
Tape
Connecting pipe
Drain hose
Connecting cable
Drain hose
Installation Manual 13
Flaring Work and Connection of Piping
4. Indoor unit installation Hook the indoor unit onto the upper portion of the installation plate.(Engage the two hooks of the rear top of the indoor unit with the upper edge of the installation plate.) Ensure that the hooks are properly seated on the installation plate by moving it left and right.
Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(clicking sound).
Connecting the piping to the indoor unit and drain hose to drain pipe.
1. Align the center of the pipes and sufficiently tighten the flare nut by hand.
2. Tighten the flare nut with a wrench.
3. Next, extend the indoor unit's drain hose. Then attach the drain pipe.
Wrap the insulation material around all connections.
1. Overlap the connection pipe insulation material and the indoor unit pipe insulation material. Bind them together with vinyl tape so that there is no gap.
2. Wrap the area which accommodates the rear piping housing section with vinyl tape.
3. Bundle the piping and drain hose together by wrapping them with vinyl tape for enough to cover where they fit into the rear piping housing section.
Drain hose
Connecting
cable
mm inch kgf.m (lbf-ft)
Ø6.35 1/4 1.8 ~ 2.5 (13) Ø9.52 3/8 3.4 ~ 4.2 (20)
Outside diameter Torque
Indoor unit tubing Flare nut Pipes
Open-end wrench (fixed)
Flare nut
Wrench
Indoor unit tubing
Drain pipe
Connection pipe
Connection pipe
Vinyl tape (wide)
Connecting cable
Pipe
Drain hose
Indoor unit drain hose
Vinyl tape(narrow)
Adhesive
Plastic bands
Vinyl tape(narrow)
Wrap with vinyl tape
Insulation material
Wrap with vinyl tape
Vinyl tape(wide)
Indoor unit pipe
Pipe
14 Wall Mounted Multi-Zone Split System Air Conditioner
Flaring Work and Connection of Piping
1. Route the indoor tubing and the drain hose to the required piping hole position.
2. Insert the piping, drain hose, and the connecting cable into the piping hole.
3.
Insert the connecting cable into the indoor unit.
Don't connect the cable to the indoor unit.
Make a small loop with the cable for easy
connection later.
4. Tape the drain hose and the connecting cables.
5. Indoor unit installation
Hang the indoor unit from the hooks at the top of the installation plate.
Insert the spacer between the indoor unit and the installation plate and separate the bottom of the indoor unit from the wall.
Connecting the piping to the indoor unit and the drain hose to drain pipe.
1. Align the center of the pipes and sufficiently tighten the flare nut by hand.
2. Tighten the flare nut with a wrench.
3. Next, extend the indoor unit's drain hose. Then attach the drain pipe.
For left rear piping
mm inch kgf.m (lbf-ft)
Ø6.35 1/4 1.8 ~ 2.5 (13) Ø9.52 3/8 3.4 ~ 4.2 (20)
Outside diameter Torque
Indoor unit
Installation plate
8 cm
(3.15 inch)
Spacer
Connecting
cable
Drain pipe
Wrench
Indoor unit tubing
Indoor unit tubing Flare nut Pipes
Open-end wrench (fixed)
Flare nut
Connection pipe
Drain hose
Indoor unit drain hose
(narrow)
Vinyl tape
Adhesive
Installation Manual 15
Flaring Work and Connection of Piping
Wrap the insulation material around the connecting portion.
1. Overlap the connection pipe insulation and the indoor unit pipe heat insulation material. Bind them together with vinyl tape so that there is no gap.
2. Wrap the area which accommodates the rear piping housing section with vinyl tape.
3. Bundle the piping and drain hose together by wrapping them with vinyl tape over the range within which they fit into the rear piping housing section.
Reroute the piping and the drain hose across the back of the chassis.
Indoor unit installation
1. Remove the spacer.
2. Ensure that the hooks are properly seated on the installation plate by moving it left and right.
3. Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(clicking sound).
Plastic bands
Insulation material
Connection pipe
Vinyl tape (wide)
Connecting cable
Wrap with vinyl tape
Pipe
Vinyl tape(narrow)
Indoor unit piping
Drain hose
Piping for passage through piping hole
Pipe
Vinyl tape(narrow)
Wrap with vinyl tape(wide)
Connecting
cable
Drain hose
16 Wall Mounted Multi-Zone Split System Air Conditioner
Flaring Work and Connection of Piping
Installation Information. For left piping. Follow the instruction below.
Best Practice
Press on the upper side of clamp and unfold the tubing to slowly downward.
Worst Practice
Bending the pipe from right to left may cause damage to the tubing.
Installation Manual 17
Flaring Work and Connection of Piping
Outdoor
Align the center of the piping and sufficiently tighten the flare nut by hand.
Finally, tighten the flare nut with a torque wrench until the wrench clicks.
When tightening the flare nut with the torque
wrench, ensure the direction for tightening follows the arrow on the wrench.
Outdoor unit 36K BTU/h
Outdoor unit 18/24K BTU/h
Outside diameter Torque
mm inch kgf.m (lbf-ft)
Ø6.35 1/4 1.8 ~ 2.5 (13) Ø9.52 3/8 3.4 ~ 4.2 (20)
A-UNIT
Gas side piping
B-UNIT
Liquid side piping
Torque wrench
A-UNIT
Gas side piping
B-UNIT
Liquid side piping
C-UNIT
Torque wrench
18 Wall Mounted Multi-Zone Split System Air Conditioner
Connecting the Cable between Indoor Unit and Outdoor Unit
Connecting the Cable between Indoor Unit and Outdoor Unit
Connect the cable to the indoor unit by connecting the wires to the terminals on the control board individually according to the outdoor unit connection. (Ensure that the color of the wires
of the outdoor unit and the terminal No. are the same as those of the indoor unit.)
The ground wire should be longer than the common wires. The circuit diagram is subject to change without notice. When installing, refer to the electrical diagram behind the front panel of Indoor Unit. The wiring for the outdoor unit can be found on the inside of the Outdoor Unit control cover.
Connect the cable to the Indoor unit
RECOMMENDATION:
• The circuit diagram is subject to change without notice.
• Be sure to connect wires according to the wiring diagram.
• Connect the wires firmly, so that they can not be pulled out easily.
• Connect the wires according to color codes by referring to the wiring diagram.
RECOMMENDATION:
Provide a circuit breaker between power source and the outdoor unit as shown below.
RECOMMENDATION:
The power cord connected to the outdoor unit should comply with the following specifications: ETL recognized and CSA certified.
The power connecting cable connected to the indoor and outdoor unit should be comply with the following specifications: ETL recognized and CSA certified.
Air
Conditioner
Main power source
Circuit Breaker Use a circuit breaker or time delay fuse.
RECOMMENDATION: When using the separate wires as the power cord, please secure the separate wires into the control box panel using tie wraps to hold all wires together in place.
18 / 24K BTU/h 36K BTU/h
Line voltage (208~230V)
AWG14
GN/YL
20 mm
(0.79 inch)
Line voltage (208~230V)
AWG12 (Allowable temperature to the wire rated at least 90C˚)
Low voltage (below 40V)
AWG18
GN/YL
20 mm
(0.79 inch)
GN/YL
20 mm
(0.79 inch)
Installation Manual 19
Connecting the Cable between Indoor Unit and Outdoor Unit
Connect the cable to the Outdoor unit
1. Remove the control cover from the unit by loosening the screws. Connect the wires to the terminals on the control board individually per the following.
2. Secure the cable onto the control board with the holder (clamper).
3. Re-attach the control cover to the original position using the screws.
:
1. Separately wire the high and low voltage lines.
2. Use heat resistant electrical wiring capable of withstanding temperatures up to 75°C(167°F).
3. Use outdoor waterproof connection cable rated for at least 300V for the connection between indoor and outdoor unit. (For example, Type SJO-WA)
WARNING:
Be sure to comply with local and national codes while running the wire from the
indoor unit to the outdoor unit(size of wire and wiring method, etc).
Every wire must be connected firmly.
No wire should be allowed to touch refrigerant tubing, the compressor or any
moving parts.
NOTICE
Outdoor unit
Over 5 mm
(0.2 inch)
Holder for
power supply
cord
Connecting
cable
Control cover
Terminal block
Power supply
cable
18K BTU/h
Teminal on the Indoor Unit
A-UNIT
43
Teminal on the Indoor Unit
B-UNIT
4321
Connecting cable(Low voltage)
4321L1 L2
Teminal on the Indoor Unit
43
43
B-UNIT
Teminal on the Outdoor Unit
B IndoorA Indoor
Teminal on the Indoor Unit
B-UNIT
Teminal on the Outdoor Unit
B IndoorA Indoor
4321
Connecting cable(Low voltage)
4321
Teminal on the Indoor Unit
4321
4321
C-UNIT
Teminal on the Outdoor Unit
C Indoor
4321
Connecting cable(Low voltage)
4321
Teminal on the Outdoor Unit Teminal on the Outdoor Unit
Power Source 208/230V AC (High voltage)
L2L1
Teminal on the Outdoor Unit
Power Source
208/230V AC
(High voltage)
L2L1
Teminal on the Outdoor Unit
Power Source
208/230V AC
(High voltage)
432121
A Indoor B Indoor
24K BTU/h
Teminal on the Indoor Unit
A-UNIT
Teminal on the Outdoor Unit
Teminal on the Indoor Unit
Teminal on the Outdoor Unit
432121
36K BTU/h
A-UNIT
432121
20 Wall Mounted Multi-Zone Split System Air Conditioner
Connecting the Cable between Indoor Unit and Outdoor Unit
(1) Remove two-caps on the conduit panel.
(for low voltage line) (2) Pull the connection cable through conduit. (3) After conduit is through the panel, secure the nut
on the opposite side of panel. (4) Pass the connection cable through the hole. (5) Properly connect the cable onto the terminal
block. (6) Secure the connection cable with cord clamp
provided on the unit to reduce strain at the
terminal when the connection cable is pulled
outside up to a 35 pound weight
WARNING: Loose wiring may cause the terminal to overheat or result in unit malfunction. A fire hazard may also exist. Therefore, be sure all wiring is tightly connected.
When connecting each power wire to the corresponding terminal, follow instructions "How to connect wiring to the terminals" and fasten the wire tightly using the screw on of the terminal plate.
How to connect wiring to the terminals
For strand wiring
(1) Cut the wire end with a wire cutter or wire-
cutting pliers, then strip the insulation to
expose the strand wiring about 10 mm(3/8"). (2) Using a screwdriver, remove the terminal
screw(s) on the terminal plate. (3) Using a round terminal fastener or pliers,
securely clamp each stripped wire end with a
round terminal. (4) Position the round terminal wire, and replace
by tightening the terminal screw using a
screwdriver.
Methods of connecting the cable
High voltage
Low voltage
Strip 10 mm(3/8")
Round terminal
Connecting cable
Loosening the terminal block screw
Fastening the wire tightly
Strand wire
G
Terminal block
Lock nut
Power supply line
(1ø, 230/208V)
Conduit panel
Cap(Reuse)
Cord clamp
Hole (for low voltage line)
Cap(Remove) Taping
(for sealing)
Low voltage line (connecting cable)
Installation Manual 21
Connecting the Cable between Indoor Unit and Outdoor Unit
Connect the cable to the indoor unit
CAUTION: Provide a circuit breaker between power source and the unit as shown below.
Air
Conditioner
Circuit Breaker
Use a circuit breaker or time delay fuse.
Main power source
Model Power source
Fuse or breaker
Capacity
1Ø, 230 / 208V
20 A
1Ø, 230 / 208V
25 A
1Ø, 230 / 208V
40 A
18K BTU/h 24K BTU/h 36K BTU/h
1. Connect the wires to the terminals on the control board individually according to the outdoor unit connection.
Ensure that the color of the wires of outdoor
unit and the terminal No. are the same as those of indoor unit respectively.
2. Attach the Grille onto the cabinet.
Grasp the lower left and right side of the
Grille and engage four tabs on the top inside edge of the chassis.
Press the Grille toward the chassis until it
goes back into place.
Connecting cable
22 Wall Mounted Multi-Zone Split System Air Conditioner
Checking the Drainage, Insulating the Pipe and Special Piping Applications
Checking the Drainage, Insulating the Pipe and Special Piping Applications
Checking the drainage
To check the drainage.
1. Pour a glass of water into the evaporator.
2. Ensure the water flows through the drain hose of the indoor unit without any leakage and goes out through the drain exit.
Drain piping
1. The drain hose should point downward for optimum drainage.
2. Incorrect Installation Examples:
Water leakage
Accumulated drain water
Air
Kinking
Water leakage
Do not raise
Water leakage
Tip of drain hose dipped in water
Ditch
Downward slope
Less than 50mm gap
Installation Manual 23
Checking the Drainage, Insulating the Pipe and Special Piping Applications
Insulating the Pipe and Special Piping Applications
Insulate the piping by wrapping the connecting portion of the indoor unit with insulation material and secure it with two kinds of vinyl tape.
If you want to connect an additional drain hose, the end of the drain outlet should be routed above the ground. Secure the drain hose appropriately.
In cases where the outdoor unit is installed below the indoor unit perform the following:
1. Tape the piping, drain hose and connecting
cable from down to up.
2. Secure the taped piping along the exterior
wall using saddle or equivalent.
In cases where the Outdoor unit is installed above the Indoor unit perform the following.
1. Tape the piping and connecting cable from
down to up.
2. Secure the taped piping along the exterior
wall. Form a trap to prevent water entering the room.
3. Secure the piping onto the wall using a
saddle or equivalent.
Seal a small opening around the pipings with gum type sealant.
Trap
Trap
Trap is required to prevent water from entering into electrical parts.
Plastic band
Taping
Drain hose
Pipings
Connecting cable
Power supply cord
Seal a small opening around the pipings with gum type sealant.
24 Wall Mounted Multi-Zone Split System Air Conditioner
Air Purging and Evacuation
Air Purging and Evacuation
Air and moisture remaining in the refrigerant system have undesirable effects as indicated below.
1. Pressure in the system rises.
2. Operating current rises.
3. Cooling(or heating) efficiency drops.
4. Moisture in the refrigerant circuit may freeze and block capillary tubing.
5. Water may lead to corrosion of parts in the refrigeration system. Therefore, the indoor/outdoor unit and connecting tube must be checked for leaks and vacuumed to remove incondensible gas and moisture in the system.
Preparation
Check that each tube(both liquid and gas side tubes) between the indoor and outdoor units have been properly connected and all wiring for the test run has been completed. Remove the service valve caps from both the gas and the liquid sides on the outdoor unit. Check that both the liquid and the gas side service valves on the outdoor unit are kept closed at this stage.
Leakage test
Connect the manifold valve(with pressure gauges) and dry nitrogen gas cylinder to this service port with charge hoses.
CAUTION: Be sure to use a
manifold valve for leak testing. The high side manifold valve must always be kept closed.
Pressurize the system to no more than 150
P.S.I.G. with dry nitrogen gas and close the cylinder valve when the gauge reading reached 150 P.S.I.G. Next, test for leaks with liquid soap.
CAUTION:
To avoid nitrogen
entering the refrigerant system in a liquid state, the top of the cylinder must be higher than its bottom when you pressurize the system. Usually, the cylinder is used in a vertical standing position.
:
Leakage testing should be done for each indoor unit connection set, separately.
1. Do a leakage test of all joints of the tubing(both indoor and outdoor) and both gas and liquid side service valves with soap bubbles. Bubbles indicate a leak. Be sure to wipe off the soap with a clean cloth.
2. After the system is found to be free of leaks, relieve the nitrogen pressure by loosening the charge hose connector at the nitrogen cylinder. When the system pressure is reduced to normal, disconnect the hose from the cylinder.
NOTICE
Leak Checking
Charge hose
Nitrogen gas cylinder(in vertical standing position)
Indoor unit
Outdoor unit
Lo Hi
Manifold valve
Pressure gauge
Installation Manual 25
1. Connect the charge hose end described in the preceding steps to the vacuum pump to evacuate the tubing and indoor unit. Confirm the "Lo" knob of the manifold valve is open. Then, run the vacuum pump. The operation time for evacuation varies with tubing length and capacity of the pump.
[Each Room] The vacuum pump must be operated less than 0.8torr (0.015 psi) of the gage pressure.
2. When the desired vacuum is reached, close the "Lo" knob of the manifold valve and stop the vacuum pump.
Finishing the job
1. With a service valve wrench, turn the valve stem of liquid side valve counter-clockwise to fully open the valve.
2. Turn the valve stem of gas side valve counter-clockwise to fully open the valve.
3. Loosen the charge hose connected to the gas side service port slightly to release the pressure, then remove the hose.
4. Replace the flare nut and its bonnet on the gas side service port and fasten the flare nut securely with an adjustable wrench. This process is very important to prevent leakage from the system.
5. Replace the valve caps at both gas and liquid side service valves and fasten them tight.
This completes air purging with a vacuum pump.
The air conditioner is now ready for test running.
: Repeat evacuation procedure for each
indoor unit.
NOTICE
Air Purging and Evacuation
Indoor unit
Outdoor unit
Lo Hi
Manifold valve
Vacuum pump
Pressure gauge
Open
Close
Evacuation
26 Wall Mounted Multi-Zone Split System Air Conditioner
Charging
Each outdoor unit is factory charged (see rating plate) for the evaporator as well as a 7.5 m (25 ft) line set for each indoor line. Any time total line set is used either shorter or longer then the nominal, which is for Single Zone = 7.5m, Dual Zone = 15m, and Tri-Zone = 22.5 (Single Zone = 25ft, Dual Zone = 50ft, and Tri Zone = 75 ft), the line set length the refrigerant charge has to be adjusted.
Whether the line set is made shorter or longer you must adjust the charge based on how many ft of tubing are either added or removed based on 20 g (0.22 oz) of R410A per meter(foot).
Example: A 80 ft line set is used for tri - zone 5 additional ft X 0.22 ounces per foot= add 1.1
ounces of R410A
Important:
If you are ever uncertain of the unit charge, reclaim, evacuate and weigh in the correct charge using the charge amount specified on the unit's rating plate, adjusting for line sets longer or shorter than
7.5 m(25 ft) for each indoor unit.
Charging
18K BTU/h 30 m (100 ft) 15 m (50 ft) 3 m (10 ft) 7.5 m (25 ft) 7.5 m (25 ft) 20 g/m (0.22 oz/ft)
24K BTU/h 30 m (100 ft) 15 m (50 ft) 3 m (10 ft) 7.5 m (25 ft) 7.5 m (25 ft) 20 g/m (0.22 oz/ft)
36K BTU/h 45 m (150 ft) 15 m (50 ft) 3 m (10 ft) 7.5 m (25 ft) 7.5 m (25 ft) 20 g/m (0.22 oz/ft)
Capacity
Max total
length of all
pipes (A+B+C)
Max length of
each pipe
(A/B/C)
Min length of
each pipe
(A/B/C)
Max Elevation between each
indoor unit and
outdoor unit (h1)
Max elevation
between
indoor units
(h2)
Additional
Refrigerant
Test Running
Installation Manual 27
1. Check that all tubing and wiring have been properly connected.
2. Check that the gas and liquid side service valves are fully open.
Prepare remote control
Remove the battery cover by pulling it according to the arrow direction. Insert new batteries making sure that the (+) and (–) of battery are installed correctly. Reattach the cover by pushing it back into position.
:
Use 2 AAA(1.5volt) batteries. Do not use rechargeable batteries.
Remove the batteries from the remote control if the system is not going to be used for a long time.
Evaluation of the performance
Operate all indoor units for 15~20 minutes, then check the system refrigerant charge:
1.Measure the pressure of one of the gas side
service valves.
2. Measure the temperature of the intake and
discharge of air.
3. Ensure the difference between the intake air
temperature and the discharge air is more than 8°C(14.4°F).
4. For reference, optimum gas pressure for
cooling is shown below.
:
If the actual pressure is higher than shown, the system is most likely over-charged, and charge should be removed. If the actual pressure is lower than shown, the system is most likely undercharged, and charge should be added.
NOTICE
NOTICE
Discharge temperature
Discharge air
Intake temperature
R410A 35°C (95°F)
8.5 ~ 9.5 kg/cm2G (120 ~ 135 P.S.I.G)
Outside ambient
TEMP.
Refrigerant
The pressure of the gas side
service valve.
Important:
Individual zones should be all in the same
operation mode (Heating or Cooling mode)
Test Running
Bolt
Tubing connection
P/No. : MFL3905950203-18-08
Specifications and performance data subject to change without notice.
Loading...