Heat Controller MGD90-E5A, MGD75-E5A, MGD90-E3A, MGD75-E3A, MGD60-E3A User Manual

...
MGD Series Gas Furnace Installation Instructions
INSTALLATION INSTRUCTIONS
SEALED COMBUSTION DOWNFLOW MGD SERIES GAS FURNACE SIZES 60, 75, 90
FOR INSTALLATION IN: MANUFACTURED (MOBILE) CAUTION: READ ALL SAFETY GUIDES
GENERAL INFORMATION
These down flow sealed combustion furnaces install in Manufactured Homes, Recreational Vehicles or Modular Construction. The furnaces conform to Part 3280 (a) (2) of HUD Manufactured Homes Construction and Safety Standards. They must be installed only with listed RJ-Roof Jack, Sealed Combustion venting system.
NOTE: These instructions are intended to assist qualified individuals experienced in the installation of heating equipment. Some state and local codes require installation personnel to be licensed. Read all instructions before starting the installation.
SAVE THIS MANUAL
WARNING-RISK OF FIRE OR ELECTRICAL SHOCK
Only qualified service personnel shall be used to install and provide maintenance of this furnace.
NOTICE – Furnace set-up and any adjustment needed is responsibility of the installer/ retailer/ contractor and is not covered by the furnace manufacturers warranty.
CHECKLIST: FURNACE START-UP
1. Has furnace roof jack crown been correctly installed?
2. Has the furnace gas valve and burner orifice been cleaned?
3. Is the gas line outlet pressure set for the fuel used?
4. If the home uses a crossover air connector duct, is it
installed per homebuilders installation instructions?
5. Has furnace been operated through complete heating cycle?
Heat Controller, Inc. Jackson, MI 49203 MGD Installation Instructions 1
MGD Series Gas Furnace Installation Instructions
SPECIFICATIONS
80 AFUE- AUTOMATIC HOT SURFACE IGNITION
Model No. MGD60-E3A MGD75-E3A MGD90-E3A MGD60-E5A MGD75-E5A MGD90-E5A Input, BTUH 60,000 75,000 90,000 60,000 75,000 90,000 Output, BTUH 48,000 60,000 72,000 48,000 60,000 72,000 AFUE, % 80.0 81.0 80.0 80.0 81.0 80.0 With A-Coil Cabinet YES YES YES YES YES YES Ignition Type Auto-Elect Auto-Elect Auto-Elect Auto-Elect Auto-Elect Auto-Elect Air Temperature Rise, Range-F 40-70 45-75 50-80 40-70 45-75 50-80 Blower 10 X 8, 1/3 HP, 3 SPD 10 X 8, 3/4 HP, 4 SPD Designed Max Outlet Air Temp-F Max. External SP (Duct),In. W.C. .30 Heating Factory Equipped Fuel Natural Gas (Factory Equipped) - LP Orfice Furnished High Altitude For elevations above 2,000 feet, reduce input 4% for each 1,000 ft. elevation above sea level Furnace Flue Pipe Must Use RJS Roof Jack for Sloped Roof or RJF Roof Jack for Flat Roof Gas Connection 1/2" FPT Electric Service 115 VAC, 60 HZ, 1 PH Fuse or Circuit Breaker 15 Amp Thermostat Circuit 24VAC, 60Hz, 40VA Filters 1-16"x40"x1" Washable
PRODUCT CODE
165 °
PART NO. DESCRIPTION NOTES
90-RJF1729-AL Body, Roof Jack, Gas-FLAT Height 94 1/2 X 106 1/2 90-RJF2551-AL Body, Roof Jack, Gas-FLAT Height 102 1/2 X 128 1/2 90-RJS1729-AL Body, Roof Jack, Gas-SLOPE 3/12 Height 94 1/2 X 106 1/2 90-RJS2551-AL Body, Roof Jack, Gas-SLOPE 3/12 Height 102 1/2 X 128 1/2 90-RJS3868-AL Body, Roof Jack, Gas-SLOPE 3/12 Height 115 1/2 X 145 1/2 90-RJS6399-AL Body, Roof Jack, Gas-SLOPE 3/12 Height 140 1/2 X 176 1/2 90-RJCRWN-AL Crown, Roof Jack, Gas Use w/ Gas Roof Jack Body 90-TRN-RNG Ceiling Trim Ring, Roof Jack Trim out to inside RJ - Pipe 90-OUTXT16-AL Roof Jack Outdoor Extension - Gas 16" Extend pipes / crown - 16 in. 90-INXST10-AL Roof Jack Indoor Extension - Gas 10" Extend pipes / crown - 10 in. 90-RJS56 5-6/ 12 Slope, Roof Saddle Adapter Add to RJS 3/12 Roof Jack 90-DCU0-01 86AA0013 Duct Conn + 87FB0005 Flr Base Floor to Duck 1 in. - 4 in. 90-DCU0-02 86AA0014 Duct Conn + 87FB0005 Flr Base Floor to Duck 6 in. - 8 in. STD 90-DCU0-03 86AA0015 Duct Conn + 87FB0005 Flr Base Floor to Duck 8 in. - 12 in. 90-CABEXT4 White, Top, Cabinet Extender Plate Fill alcove 76" top opening 87-1008-3/12A1 A/C Blower, 3 Speed - 1/3 HP 2 - 4 Ton A/C 87-1008-4/16A1 A/C Blower, 3 Speed - 3/4 HP 2 - 5 Ton A/C
Heat Controller, Inc. Jackson, MI 49203 MGD Installation Instructions 2
MGD Series Gas Furnace Installation Instructions
SAFETY CONSIDERATIONS INSTALLATION STANDARDS
ELECTRIC POWER - turn off all electrical power to furnace before performing any maintenance or service on unit. Failure to take this precaution may result in personal injury due to electrical shock.
SERVICE - a qualified service technician should service this unit. Fuel burning appliances can generate toxic flue products. Modification of the appliance can cause carbon monoxide in deadly amounts. To prevent a safety hazard, maintain this appliance in a safe operating manner and do not modify.
DO NOT modify vent or operate the unit with a blocked vent or inlet air pipe.
DO NOT re-drill a burner orifice. If the orifice size must be changed, use only a new orifice.
DO NOT use matches, lighters, candles, or other sources of open flame to check for gas leaks.
PROPER maintenance for this unit requires certain mechanical skills and tools. If you are at all uncertain, contact your Heating Service Co. for maintenance and service.
CONSULT with a service technician for any problems or questions you may have pertaining to this appliance.
ALWAYS inspect the appliance before starting a new heating season, paying special attention to vent pipes and fuel lines.
NOTE: The words “Shall” or “Must” indicate a requirement, which is essential to satisfactory and safe furnace performance.
The words “Should” or “May” indicate a recommendation which may be helpful or enhance performance.
CODE COMPLIANCE
The installer shall become familiar with and follow all local codes and regulations which govern the installation of this furnace. Where applicable, local codes may take precedence.
Federal Manufactured Home Construction and Safety Standards – HUD Title 24, Part 3280.
National Fuel Gas Code – ANSI-Z223.1/NFPA-54
Unit electrical wiring and grounding shall comply with
National Electrical Code – ANSI/NFPA-70
“M anufactured Housing” – NFPA-501 and Fi re Safety Crit eria for Mobile Home Installations – NFPA 501A
“Recreational Vehicles” – ANSI – 119/NFPA – 501C
HIGH ALTITUDE INSTALLATION
For elevations above 2,000 feet derate furnace input 4% for each 1,000 feet of elevation above sea level. Furnace deration is accomplished by reducing the burner orifice size. See DERATING CHART for orifice size and CONVERSION INSTRUCTIONS, Page 16.
INSTALLATION CLEARANCES
These furnaces are design certified for the following minimum clearances from combustible materials in alcove or close instllations.
Top ……………………………….6 in. Sides ……………………………...0 in. Back ………………………………0 in. Alcove-front of furnace ………….18 in. Closet-front of furnace ……………6 in. Duct ……………………………….0 in. Vent/Roof Jack ……………………0 in.
* If the return air opening is below the top of the furnace, clearance to the side or rear shall be 6”.
** See Return Air for clearances less than 6”.
Locate furnace to ensure adequate room for service access to all vent connections, controls and the heat exchanger. A front clearance of 18” minimum (24” recommended) shall be provided by a closet door or spacing away from a facing wall or partition.
For installation on combustible flooring (except carpeting) using manufacturers supplied floor base P/N 87FB0005 and duct Connector Series P/N 86AA001, included in 90-DCU0-01/03 kits.
Heat Controller, Inc. Jackson, MI 49203 MGD Installation Instructions 3
MGD Series Gas Furnace Installation Instructions
RETURN AIR ALCOVE INSTRUCTION
The furnace may be installed free standing or in an alcove with a free flow of air back to the furnace. A minimum of 18” shall be provided at the front for return air and service access.
CLOSET INSTALLATION – 6 in.
Note: If return air is through a side wall, there must be a minimum of 6-in. clearance from side wall to furnace in addition to 6-in. minimum clearance from inside of closet door to front of furnace.
If a louvered door complying with the minimum air requirements is used, the front clearance my be reduced to 1”.
CLOSET INSTALLATIONS Additional Requirements
Concerning under floor or ceiling return air systems, the following item (1 – 10) must be adhered to:
1. The return-air opening into the closet, regardless of location, is to be sized not less than specified on the appliance rating plate.
2. If the return-air opening is located in the floor of the closet (versus the vertical front or side wall), the opening is to be provided with means to prevent its inadvertent closure by a flat object placed over the opening.
3. The cross-sectional area of the return system (when located in the floor or ceiling of the manufactured home) leading into the closet is to be not less than that of the opening specified on the appliances rating plate.
4. The total free area of openings in the floor or ceiling registers serving the return-air duct system is to be not less than 150% of the size opening specified on the appliance rating plate. At least one such register is to be located where the likelihood of its being covered by carpeting, boxes, and other objects is minimized.
5. Materials located in the return duct system have a flame spread classification of 200 or less.
6. Non-combustible pans having one-inch upturned flanges are located beneath openings in the floor return duct system.
7. Wiring materials located in the return d uct system conform to Article 300-22 (B&C) of the National Electric Code, ANSI / NFPA-70.
8. Gas piping is not run in or through the return duct system.
9. The negative pressure in the closet, as determined by test with the air-circulating fan operating at high heating speed and the closet door closed, is to be not more negative than minus 0.05-inch water column.
10. For floor return systems, the manufactured home manufacturer or installer shall affix a prominent warning where it is easily read when the closet door is open.
The marking shall read:
Heat Controller, Inc. Jackson, MI 49203 MGD Installation Instructions 4
MGD Series Gas Furnace Installation Instructions
Heat Controller, Inc. Jackson, MI 49203 MGD Installation Instructions 5
MGD Series Gas Furnace Installation Instructions
Heat Controller, Inc. Jackson, MI 49203 MGD Installation Instructions 6
MGD Series Gas Furnace Installation Instructions
SEALED COMBUSTION ROOF JACK – (REQUIRED)
Heat Controller, Inc. Jackson, MI 49203 MGD Installation Instructions 7
MGD Series Gas Furnace Installation Instructions
CUTTING ROOF JACK OPENING
A proper installation of the roof jack requires that openings in roof and ceiling be on the same vertical centerline as the furnace flue collar. See FIG. 1
Mark the center point on the ceiling and scribe a 4” radius (8” diameter) around this mark. If furnace is in place during this step, cover the furnace and flue opening to prevent debris from entering flue.
INSTALLING ROOF JACK
The roof jack body should be secured to the furnace before the roof flashing is secured to the roof.
1. Insert roof jack body into opening in the roof.
2. From above, canter the roof jack body aligning with the furnace collar.
3. From inside the home, pull down 4-3/16” D flue pipe seating the pipe fully and firmly over the furnace flue collar.
4. Next pull down the 7” D combustion air pipe seating it over the mating furnace collar. Rotate the combustion air pipe lining up to the screw hole on the 7” collar.
5. Check and make sure the combustion air pipe is fully seated. Then drive a # 10 sheet metal screw, attaching pipe firmly to furnace collar.
6. Install optional ceiling trim ring, 90-TRM-RNG
7. On the roof, caulk liberally under the roof jack flashing.
8. Drive nails or screws through the flashing onto the roof surface about 1 – 11/2” apart. Caulk again to ensure a leak tight joint.
9. Install roof jack crown and fasten to roof jack body with three (3) screws (provided) using pre-punched holes.
.
INSTALLATION IN SNOW REGIONS
When the combustion air inlet to the roof jack is blocked with snow, the furnace will not operate properly due to the depleted combustion air supply.
Therefore, if the furnace will be located in regions where snow accumulation on the roof exceeds 7” or in H.U.D. Snow Load Zones, a roof jack extension – Part5 No. 90­OUTXT16-AL is recommended.
ROOF JACK ON HI-PITCH ROOF
To install the RJS (3/12) Series Roof Jack on roofs which have a slope between 4.5/12 – 6/12, install a Part No. 90­RJS56 Roof Saddle, FIG. J. The combined assembly of the RJS Roof Jack and Roof Saddle will conform to the higher roof pitch. If roof pitch is greater than 6/12, field fabricate a suitable adapter, or consult with factory.
Heat Controller, Inc. Jackson, MI 49203 MGD Installation Instructions 8
MGD Series Gas Furnace Installation Instructions
CONNECT POWER SUPPLY
1. Remove the furnace control panel cover.
2. Insert 115 V wiring through a strain relief bushing on the left side of the furnace.
3. Connect the HOT wire to the black pigtail lead; connect the NEUTRAL wire to the WHITE pigtail lead. Secure the connections with suitable wire nuts and wrap with electrical tape. Refer to Wiring Diagram on Pg. 11 for connections.
4. Connect the GROUND wire to a grounding screw in the control panel.
5. Reinstall and secure the control panel cover with
screws.
Heat Controller, Inc. Jackson, MI 49203 MGD Installation Instructions 9
MGD Series Gas Furnace Installation Instructions
GAS PIPE AND TUBING-MIN SIZES
MODEL TYPE LENGTH PIPE TUBING
MGD OF SIZE SIZE
GAS (FT.) (IN.) (IN. OD) to 20 3/8 5/8 Natural to 60 1/2 -
60 to 70 - 3/4
to 40 3/8 ­ Propane to 70 - 5/8 to 80 1/2 ­ to 20 - 5/8 to 50 1/2 ­ Natural to 60 - 3/4
75 to 80 3/4 -
to 30 3/8 ­ Propane to 60 - 5/8 to 80 1/2 ­ to 40 1/2 3/4 Natural to 50 - 3/4
90 to 30 3/8 ­ Propane to 40 - 5/8 to 60 1/2 3/4
Heat Controller, Inc. Jackson, MI 49203 MGD Installation Instructions 10
MGD Series Gas Furnace Installation Instructions
WIRING DIAGRAM, MGD
Heat Controller, Inc. Jackson, MI 49203 MGD Installation Instructions 11
MGD Series Gas Furnace Installation Instructions
REPLACEMENT PARTS
Heat Controller, Inc. Jackson, MI 49203 MGD Installation Instructions 12
MGD Series Gas Furnace Installation Instructions
MGD Gas Furnace Parts List
ITEM NO. USED ON FURNACE MODEL PART NO. QTY DESCRIPTION
1 All R68DD0010 1 Pressure Switch, -0.20 N.O. 2 All R71CA0006 2 ft. Silicon Tubing 3 All R68CA0005 1 Limit Switch, Manual, Upper-180F 4 All R86GF0050 1 Boost Blower Assembly, w/ Air Orifices 5 All R68GF0001 1 Integrated Control Board, HSI 6 All R68GF0006 1 Gas Valve for HSI Electric Ignition 7 All R68BKN007 1 Valve Bracket & Orifice Holder
MGD60 R86GF0051 1 Heat Exchanger & Gaskets
8
MGD75, 90 R86GF0052 1 Heat Exchanger & Gaskets
9 All R68GF0004 1 Flame Sensor 10 All R68DD0009 1 System Switch - SPST 11 All R68GF0002 1 Transformer (115V-24V, 40VA) 12 All R68CA0004 1 Limit Switch - Open 140 F - Close 110 F 13 All R86GF0054 1 Burner Assembly 14 All R68GF0005 1 Hot Surface Igniter 15 All R76AA0002 2 Filter (16" X 20" X 1") 16 All R86GF0055 1 Door Panel - Upper 17 All R86GF0143 1 Door Panel - Lower
MGD60/90-E3A R65GF0002 1 Motor - 1/3 HP
18 19 MGD60/90-E5A R86GF0056 1 Motor Mount Assembly
20 21 All R69AB0001 1 Blower Wheel - 10 x 8
30 All R86GF0058 4 Door Latch, Set
32 33 All R87NNE001 1 Filter Retainer Bracket
MGD60/90-E5A R65GF0003 1 Motor - 3/4 HP
MGD60/90-E3A R68DE0002 1 Capacitor - 15/370M MGD60/90-E5A R68DE0003 1 Capacitor - 25/370V
MGD60 (Natural Gas) 72AG-144 1 Main Burner Orifice - #27 MGD75 (Natural Gas) 72AG-166 1 Main Burner Orifice - #20 MGD90 (Natural Gas) 72AG-177 1 Main Burner Orifice - #16 MGD60 (Propane) 72AG-089 1 Main Burner Orifice - #43 MGD75 (Propane) 72AG-101 1 Main Burner Orifice - #38 MGD90 (Propane) 72AG-110 1 Main Burner Orifice - #35
Heat Controller, Inc. Jackson, MI 49203 MGD Installation Instructions 13
MGD Series Gas Furnace Installation Instructions
Reference: NFPA No. 54, ANSI Z 223.1 National Fuel Gas Code Table shows 4% Input Reduction per 1,000 feet elevation For Canadian High Altitude (2,000-4,500 feet), reduce gas pressure to burner manifold (manifold Ps.) to 3.0” W.C. and 9.0” W.C. for LP (Propane) Gas
Heat Controller, Inc. Jackson, MI 49203 MGD Installation Instructions 14
Loading...