NOTE: Above model nomenclature is a general reference. Consult individual specication catalogs for detailed information.
www.heatcontoller.com
3
HEAT CONTROLLER, INC. WATER-SOURCE HEAT PUMPS
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
Safety
Safety
Warnings, cautions and notices appear throughout this
manual. Read these items carefully before attempting any
installation, service or troubleshooting of the equipment.
DANGER: Indicates an immediate hazardous situation, which
if not avoided will result in death or serious injury. DANGER
labels on unit access panels must be observed.
WARNING: Indicates a potentially hazardous situation, which
if not avoided could result in death or serious injury.
CAUTION: Indicates a potentially hazardous situation or an
unsafe practice, which if not avoided could result in minor or
moderate injury or product or property damage.
NOTICE: Notication of installation, operation or
maintenance information, which is important, but which is not
hazard-related.
WARNING! All refrigerant discharged from this unit must be
recovered WITHOUT EXCEPTION. Technicians must follow
industry accepted guidelines and all local, state, and federal
statutes for the recovery and disposal of refrigerants. If a
compressor is removed from this unit, refrigerant circuit oil will
remain in the compressor. To avoid leakage of compressor oil,
refrigerant lines of the compressor must be sealed after it is
removed.
CAUTION!
these units as a source of heating or cooling during the
construction process. The mechanical components and
lters will quickly become clogged with construction dirt and
debris, which may cause system damage.
x WARNING! x
x CAUTION! x
To avoid equipment damage, DO NOT use
x WARNING! x
WARNING! Verify refrigerant type before proceeding.
Units are shipped with R-22 and R-410A refrigerants. The
unit label will indicate which refrigerant is provided. The
EarthPure® Application and Service Manual should be read
and understood before attempting to service refrigerant
circuits with R-410A.
x WARNING! x
WARNING! To avoid the release of refrigerant into the
atmosphere, the refrigerant circuit of this unit must be
serviced only by technicians who meet local, state, and
federal prociency requirements.
4
Heat Controller, Inc. Water-Source Heating and Cooling Systems
The Quality Leader in Conditioning Air
Inspection
Upon receipt of the equipment, carefully check the shipment
against the bill of lading. Make sure all units have been
received. Inspect the packaging of each unit, and inspect each
unit for damage. Insure that the carrier makes proper notation
of any shortages or damage on all copies of the freight bill
and completes a common carrier inspection report. Concealed
damage not discovered during unloading must be reported
to the carrier within 15 days of receipt of shipment. If not led
within 15 days, the freight company can deny the claim without
recourse. Note: It is the responsibility of the purchaser to le
all necessary claims with the carrier. Notify your equipment
supplier of all damage within fteen (15) days of shipment.
Storage
Equipment should be stored in its original packaging in a
clean, dry area. Store units in an upright position at all times.
Stack units a maximum of 3 units high.
Unit Protection
Cover units on the job site with either the original packaging
or an equivalent protective covering. Cap the open ends of
pipes stored on the job site. In areas where painting, plastering,
and/or spraying has not been completed, all due precautions
must be taken to avoid physical damage to the units and
contamination by foreign material. Physical damage and
contamination may prevent proper start-up and may result in
costly equipment clean-up.
Examine all pipes, ttings, and valves before installing any of
the system components. Remove any dirt or debris found in
or on these components.
Pre-Installation
Installation, Operation, and Maintenance instructions are
provided with each unit. Horizontal equipment is designed for
installation above false ceiling or in a ceiling plenum. Other
unit congurations are typically installed in a mechanical
room. The installation site chosen should include adequate
service clearance around the unit. Before unit start-up,
read all manuals and become familiar with the unit and its
operation. Thoroughly check the system before operation.
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
General Information
rides freely on the springs. Remove shipping restraints.
6. REMOVE COMPRESSOR SUPPORT PLATE 1/4”
SHIPPING BOLTS (2 on each side) TO MAXIMIZE
VIBRATION AND SOUND ATTENUATION (R22 indoor
units only).
7. Locate and verify any hot water generator (HWG) or
other accessory kit located in the compressor section.
x CAUTION! x
CAUTION! DO NOT store or install units in corrosive
environments or in locations subject to temperature or
Corrosive conditions and high temperature or humidity can
signicantly reduce performance, reliability, and service life.
Always move and store units in an upright position. Tilting
units on their sides may cause equipment damage.
NOTICE! Failure to remove shipping brackets from springmounted compressors will cause excessive noise, and could
cause component failure due to added vibration.
x CAUTION! x
CAUTION! CUT HAZARD - Failure to follow this caution
may result in personal injury. Sheet metal parts may have
sharp edges or burrs. Use care and wear appropriate
protective clothing, safety glasses and gloves when
handling parts and servicing heat pumps.
Prepare units for installation as follows:
1. Compare the electrical data on the unit nameplate with
ordering and shipping information to verify that the
correct unit has been shipped.
2. Keep the cabinet covered with the original packaging
until installation is complete and all plastering, painting,
etc. is nished.
3. Verify refrigerant tubing is free of kinks or dents and that
it does not touch other unit components.
4. Inspect all electrical connections. Connections must be
clean and tight at the terminals.
5. Loosen compressor bolts on units equipped with
compressor spring vibration isolation until the compressor
www.heatcontoller.com
5
HEAT CONTROLLER, INC. WATER-SOURCE HEAT PUMPS
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
Equipment Selection
The installation of geothermal heat pump units and all
associated components, parts, and accessories which make
up the installation shall be in accordance with the regulations
of ALL authorities having jurisdiction and MUST conform to
all applicable codes. It is the responsibility of the installing
contractor to determine and comply with ALL applicable
codes and regulations.
General
Proper indoor coil selection is critical to system efficiency.
Using an older-model coil can affect efficiency and may not
provide the customer with rated or advertised EER and COP.
Coil design and technology have dramatically improved
operating efficiency and capacity in the past 20 years.
Homeowners using an older coil are not reaping these cost
savings and comfort benefits. NEVER MATCH AN R-22
INDOOR COIL WITH AN R-410A COMPRESSOR SECTION.
Newer indoor coils have a larger surface area, enhanced fin
design, and grooved tubing. These features provide a larger
area for heat transfer, improving efficiency and expanding
capacity. Typical older coils may only have one-third to onehalf the face area of these redesigned coils.
Table 1a: GeoMax 2 (HTS) Air Handler Matches for ARI Ratings
Indoor Coil Selection - HTS GeoMax 2
HCI split system heat pumps are rated in the ARI directory
with a specific indoor coil match. GeoMax 2 (HTS) models
are rated with Carrier/Bryant FV4 or FE4 series variable
speed air handlers as shown in Table 1a. Other brands of
air handlers may attain the same ARI ratings providing that
the specifications meet or exceed those listed in Table 1a
AND Table 1b. An ECM motor and TXV is required. Cap
tubes and fixed orifices are not acceptable. PSC fans may
be used if matched to Table 1b, but will not meet ARI ratings.
If using PSC fan, compressor section must be operated as a
single stage unit (i.e. wired for either 1st stage or 2nd stage).
Without the ability to vary the airflow, supply air temperatures
may not be acceptable if the compressor is allowed to
change stages when used with a PSC fan motor.
Compressor Section024036048060
Air Handler
Model FV4
003005006006
RefrigerantR-410A
Metering DeviceTXV (required)
Air Coil
Type
Rows - Fins/in.
Face Area (sq. ft.)
Cabinet Configuration
ECM Settings for
ARI Ratings
(FV4 Fan Coil)
Slope
3 - 14.5
3.46
Upflow/Downflow/Horizontal (Multipoise)
AC/HP size: 036
System Type:
Comfort AC/HP
CFM Adjust: Nom
A
3 - 14.5
5.93
AC/HP size: 036
System Type:
HP-Effic AC/HP
CFM Adjust: High
A
3 - 14.5
7.42
AC/HP size: 048
System Type:
Comfort AC/HP
CFM Adjust: High
A
3 - 14.5
7.42
AC/HP size: 060
System Type:
Comfort AC/HP
CFM Adjust: High
Fan Motor Type - HPECM - 1/2ECM - 1/2ECM - 3/4ECM - 3/4
6
Heat Controller, Inc. Water-Source Heating and Cooling Systems
The Quality Leader in Conditioning Air
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
Equipment Selection
Table 1b: GeoMax 2 (HTS) Air Handler Characteristics for Brands other than Above Models
Model*
Nominal
Tons*
024 - Part Load1.55053019.2 - 22.4
024 - Full Load2.05288024.2 - 28.2
036 - Part Load2.55170025.2 - 29.2
036 - Full Load3.050120034.5 - 40.1
048 - Part Load3.547100034.3 - 39.9
048 - Full Load4.048165046.3 - 53.8
060 - Full Load5.048185054.5 - 63.3
* Nominal tons are at ARI/ISO 13256-1 GLHP conditions. Two-stage units may be operated in single-stage mode if desired, where smaller
capacity is required. For example, a model 026 may be used as a 1-1/2 ton unit if “locked” into 1st stage operation only. If PSC fan is used,
unit must be “locked” into either 1st or 2nd stage. An ECM fan is required for two-stage operation and for ARI ratings. Size air handler for
“Full Load” if operating in two-stage mode.
**When selecting an air handler based upon the above conditions, choose entering WB temperature of 67ºF. Use evaporator temperature,
CFM and capacity requirements as listed above. The air handler capacity must be at least at the minimum capacity shown in the table in
order for the ARI rating condition to be valid. See Figure 1 for an example selection.
Evaporator
Temp (ºF)
CFM
Capacity
(MBtuh)**
Indoor Coil Selection - For HSS R-22 Units
Geothermal split system heat pumps with R-22 refrigerant are rated in the ARI directory with a “generic” indoor coil match and
PSC fan. Selection of air handlers that attain the published ARI ratings must meet or exceed the specifications listed in Table
2. A TXV is required. Cap tubes and fixed orifices are not
acceptable.
Table 2: R-22 Air Handler Characteristics
Model*
Nominal
Tons*
0181.55060018.5 - 21.3
0242.04780025.5 - 29.3
0302.549100031.5 - 36.2
0363.048120037.0 - 42.5
0423.545140042.2 - 48.5
0484.046160050.0 - 57.5
0605.045200058.0 - 66.7
* Nominal tons are at ARI/ISO 13256-1 GLHP conditions.
**When selecting an air handler based upon the above conditions, choose entering WB temperature of 67ºF. Use evaporator temperature,
CFM and capacity requirements as listed above. The air handler capacity must be at least at the minimum capacity shown in the table in
order for the ARI rating condition to be valid. See Figure 1 for an example selection.
Evaporator
Temp (ºF)
CFM
Capacity
(MBtuh)**
www.heatcontoller.com
7
HEAT CONTROLLER, INC. WATER-SOURCE HEAT PUMPS
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
Equipment Selection
Air Handler Selection Example
Figure 1 shows a typical performance table for a heat pump air
handler. Suppose the evaporator temperature required is 50ºF,
the capacity required is 35,000 Btuh and the airow required
is 1,200 CFM. Each evaporator temperature listed in the table
shows three wet bulb temperatures. As recommended in the
table notes above, select the 67ºF WB column. At 1,200 CFM,
the model 003 capacity is 36 MBtuh, which is higher than the
minimum capacity required of 35,000 Btuh. In this example,
model 003 would be the appropriate match.
Figure 1: Selecting Air Handler
Utilizing the Existing Air Handler or Coil (R22 units only)
It is recommended that a new coil or air handler be installed
with any geothermal split system compressor section due to the
low initial cost of the additional equipment versus the reliability
and benet of new technology, increased reliability and
warranty. However, if the existing air handler must be used (R22
systems only), the following conditions apply:
• If the existing coil currently uses an orice, the orice must be
removed and replaced with a TXV. If the coil utilizes capillary
tubes, it will not operate properly with the geothermal split
system and should be replaced.
• If life expectancy of indoor coil (and associated components
- fan, cabinet, etc.) is less than 7-10 years, indoor section
should be replaced.
8
Heat Controller, Inc. Water-Source Heating and Cooling Systems
The Quality Leader in Conditioning Air
NOTICE! Failure to remove shipping
brackets from spring-mounted compressors
will cause excessive noise, and could cause
component failure due to added vibration.
The installation of water source heat pump units and all
associated components, parts and accessories which make
up the installation shall be in accordance with the regulations
of ALL authorities having jurisdiction and MUST conform to
all applicable codes. It is the responsibility of the installing
contractor to determine and comply with ALL applicable
codes and regulations.
Removing Existing Condensing Unit (Where Applicable)
1. Pump down condensing unit. Close the liquid line service
valve of existing condensing unit and start compressor
to pump refrigerant back into compressor section. Then,
close suction service valve while compressor is still
running to trap refrigerant in outdoor section. Immediately
kill power to the condensing unit.
2. Disconnect power and low voltage and remove old
condensing unit. Cut or unbraze line set from unit.
Remove condensing unit.
3. If condensing unit is not operational or will not pump
down, refrigerant should be recovered using appropriate
equipment.
4. Replace line set, especially if upgrading system from
R-22 to R-410A refrigerant. If line set cannot be replaced,
it must be thoroughly flushed before installing new
compressor section. R-410A compressors use POE
oil instead of mineral oil (R-22 systems). Mineral oil is
not compatible with POE oil, and could cause system
damage if not completely flushed from the line set.
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
Installation
2. Provide adequate clearance for maintenance and
service. Do not block access panels with piping, conduit
or other materials.
3. Provide access for servicing the compressor and coils
without removing the unit.
4. Provide an unobstructed path to the unit within the closet
or mechanical room. Space should be sufficient to allow
removal of the unit, if necessary.
5.
In limited side access installations, pre-removal of the
control box side mounting screws will allow control box
removal for future servicing (R22 units only).
6. Provide access to water valves and fittings and
screwdriver access to the unit side panels and all
electrical connections.
Air Handler Installation
This manual specifically addresses the compressor section
of the system. Air handler location and installation should be
according to the instructions provided with the air handling
unit.
“Indoor” Compressor Section Location
Both “indoor” and “outdoor” versions of the geothermal split
system compressor section are available. “Indoor” version
is not designed for outdoor installation. Locate the unit in
an INDOOR area that allows enough space for service
personnel to perform typical maintenance or repairs without
removing unit. Units are typically installed in a mechanical
room or closet. Never install units in areas subject to freezing
or where humidity levels could cause cabinet condensation
(such as unconditioned spaces subject to 100% outside air).
Consideration should be given to access for easy removal
of service access panels. Provide sufficient room to make
water, electrical, and line set connections.
Any access panel screws that would be difficult to remove
after the unit is installed should be removed prior to setting the
unit. Refer to Figure 2 for an illustration of a typical installation.
Refer to “Physical Dimensions” section for dimensional data.
Conform to the following guidelines when selecting unit
location:
1.
Install the unit on a piece of rubber, neoprene or other
mounting pad material for sound isolation. The pad should
be at least 3/8” [10mm] to 1/2” [13mm] in thickness. Extend
the pad beyond all four edges of the unit.
www.heatcontoller.com
9
HEAT CONTROLLER, INC. WATER-SOURCE HEAT PUMPS
Gas ke t
Sw ive l Nut
Sta in les s s tee l
sna p rin g
Brass Ada p tor
Hand Tighten
Only !
Do Not
Ov e rtighte n !
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
Installation
Figure 2: HTS/HSS Installation
External Flow Controller Mounting
The Flow Controller can be mounted beside the unit
as shown in Figure 7. Review the Flow Controller
installation manual for more details.
Water Connections-Residential (Distributor) Models
Residential models utilize swivel piping ttings for
water connections that are rated for 450 psi (3101 kPa)
operating pressure. The connections have a rubber
gasket seal similar to a garden hose gasket, which when
mated to the ush end of most 1” threaded male pipe
ttings provides a leak-free seal without the need for
thread sealing tape or joint compound. Insure that the
rubber seal is in the swivel connector prior to attempting
any connection (rubber seals are shipped attached to the
swivel connector). DO NOT OVER TIGHTEN or leaks may
occur.
The female locking ring is threaded onto the pipe threads
which holds the male pipe end against the rubber gasket,
and seals the joint. HAND TIGHTEN ONLY! DO NOT
OVERTIGHTEN!
Figure 4: Water Connections (Indoor Compressor Section)
10
Heat Controller, Inc. Water-Source Heating and Cooling Systems
The Quality Leader in Conditioning Air
GROUND-LOOP HEAT PUMP APPLICATIONS
x CAUTION! x
CAUTION! The following instructions represent industry
accepted installation practices for closed loop earth coupled
heat pump systems. Instructions are provided to assist the
contractor in installing trouble free ground loops. These
instructions are recommendations only. State/provincial
and local codes MUST be followed and installation MUST
conform to ALL applicable codes. It is the responsibility of
the installing contractor to determine and comply with ALL
applicable codes and regulations.
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
Installation
Pre-Installation
Prior to installation, locate and mark all existing underground
utilities, piping, etc. Install loops for new construction before
sidewalks, patios, driveways, and other construction has
begun. During construction, accurately mark all ground loop
piping on the plot plan as an aid in avoiding potential future
damage to the installation.
Piping Installation
The typical closed loop ground source system is shown in
Figures 7 and 8. All earth loop piping materials should be
limited to polyethylene fusion only for in-ground sections of
the loop. Galvanized or steel ttings should not be used at
any time due to their tendency to corrode. All plastic to metal
threaded ttings should be avoided due to their potential to
leak in earth coupled applications. A anged tting should
be substituted. P/T plugs should be used so that ow can be
measured using the pressure drop of the unit heat exchanger.
www.heatcontoller.com
11
HEAT CONTROLLER, INC. WATER-SOURCE HEAT PUMPS
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
Ground-Loop Heat Pump Applications
Earth loop temperatures can range between 25 and 110°F
[-4 to 43°C]. Flow rates between 2.25 and 3 gpm per ton
[2.41 to 3.23 l/m per kW] of cooling capacity is recommended
in these applications.
Test individual horizontal loop circuits before backfilling.
Test vertical U-bends and pond loop assemblies prior to
installation. Pressures of at least 100 psi [689 kPa] should be
used when testing. Do not exceed the pipe pressure rating.
Test entire system when all loops are assembled.
Flushing the Earth Loop
Once piping is completed between the unit, Flow Controller
and the ground loop (Figures 7 and 8), the loop is ready for
final purging and charging. A flush cart with at least a 1.5 hp
[1.1 kW] pump is required to achieve enough fluid velocity
in the loop piping system to purge air and dirt particles. An
antifreeze solution is used in most areas to prevent freezing.
All air and debris must be removed from the earth loop piping
before operation. Flush the loop with a high volume of water
at a minimum velocity of 2 fps (0.6 m/s) in all piping. The
steps below must be followed for proper flushing.
1. Fill loop with water from a garden hose through the flush
cart before using the flush cart pump to insure an even
fill.
2. Once full, the flushing process can begin. Do not allow
the water level in the flush cart tank to drop below the
pump inlet line to avoid air being pumped back out to the
earth loop.
3. Try to maintain a fluid level in the tank above the return
tee so that air cannot be continuously mixed back into
the fluid. Surges of 50 psi (345 kPa) can be used to help
purge air pockets by simply shutting off the return valve
going into the flush cart reservoir. This “dead heads” the
pump to 50 psi (345 kPa). To purge, dead head the pump
until maximum pumping pressure is reached. Open the
return valve and a pressure surge will be sent through
the loop to help purge air pockets from the piping system.
4. Notice the drop in fluid level in the flush cart tank when
the return valve is shut off. If air is adequately purged
from the system, the level will drop only 1-2 inches (2.5 5 cm) in a 10” (25 cm) diameter PVC flush tank (about a
half gallon [2.3 liters]), since liquids are incompressible.
If the level drops more than this, flushing should continue
since air is still being compressed in the loop fluid.
Perform the “dead head” procedure a number of times.
Note: This fluid level drop is your only indication of air in
the loop.
the loop to a homogenous temperature. This is a good time
for tool cleanup, piping insulation, etc. Then, perform final
flush and pressurize the loop to a static pressure of 50-75 psi
[345-517 kPa] (winter) or 35-40 psi [241-276 kPa] (summer).
After pressurization, be sure to loosen the plug at the end
of the Grundfos loop pump motor(s) to allow trapped air to
be discharged and to insure the motor housing has been
flooded. This is not required for Taco circulators. Insure
that the Flow Controller provides adequate flow through the
unit by checking pressure drop across the heat exchanger
and compare to the pressure drop tables at the back of the
manual.
Antifreeze
In areas where minimum entering loop temperatures drop
below 40°F [5°C] or where piping will be routed through
areas subject to freezing, antifreeze is required. Alcohols
and glycols are commonly used as antifreeze; however
your local sales manager should be consulted for the
antifreeze best suited to your area. Freeze protection
should be maintained to 15°F [9°C] below the lowest
expected entering loop temperature. For example, if 30°F
[-1°C] is the minimum expected entering loop temperature,
the leaving loop temperature would be 25 to 22°F [-4 to
-6°C] and freeze protection should be at 15°F [-10°C].
Calculation is as follows:
30°F - 15°F = 15°F [-1°C - 9°C = -10°C].
All alcohols should be premixed and pumped from a reservoir
outside of the building when possible or introduced under
the water level to prevent fumes. Calculate the total volume
of fluid in the piping system. Then use the percentage
by volume shown in Table 2 for the amount of antifreeze
needed. Antifreeze concentration should be checked from a
well mixed sample using a hydrometer to measure specific
gravity.
Low Water Temperature Cutout Setting
CXM Control
When antifreeze is selected, the FP1 jumper (JW3) should
be clipped to select the low temperature (antifreeze 13°F
[-10.6°C]) set point and avoid nuisance faults (see “Low
Water Temperature Cutout Selection” in this manual). NOTE:
Low water temperature operation requires extended range
equipment.
Antifreeze may be added before, during or after the flushing
procedure. However, depending upon which time is chosen,
antifreeze could be wasted when emptying the flush cart
tank. See antifreeze section for more details.
Loop static pressure will fluctuate with the seasons.
Pressures will be higher in the winter months than during
the cooling season. This fluctuation is normal and should be
considered when charging the system initially. Run the unit in
either heating or cooling for a number of minutes to condition
12
Heat Controller, Inc. Water-Source Heating and Cooling Systems
The Quality Leader in Conditioning Air
Ground-Loop Heat Pump Applications
Table 1: Approximate Fluid Volume (U.S. gal. [L]) per
100' of Pipe
Fluid Volume (gal [liters] per 100’ [30 meters) Pipe)
NOTICE! Cabinet opening around loop piping (outdoor
compressor section) must be sealed to prevent entry of
rodents that could potentially damage unit wiring by chewing
on the insulation.
NOTICE! Outdoor compressor section may not be tilted
more than 5 degrees from level. Damage to the compressor
or stress on the loop piping could result if unit is tilted. A
concrete pad, anchor posts and/or soil compaction may be
required to avoid tilting as ground settles.
Minimum Temperature for Low Temperature Protection
21%
25%
25%
16%
22%
20%
10%
15%
14%
www.heatcontoller.com
13
HEAT CONTROLLER, INC. WATER-SOURCE HEAT PUMPS
Residential Split - 60Hz R22 &R410A
Rev.: 5 June, 2008
Ground-Water Heat Pump Applications -
“Indoor” Compressor Section Only
Open Loop - Ground Water Systems
(“Indoor” Compressor Section Only)
The “outdoor” version of the compressor section may not
be used with open loop systems due to potential freezing of
water piping. Typical open loop piping is shown in Figure 9.
Shut off valves should be included for ease of servicing. Boiler
drains or other valves should be “tee’d” into the lines to allow
acid flushing of the heat exchanger. Shut off valves should
be positioned to allow flow through the coax via the boiler
drains without allowing flow into the piping system. P/T plugs
should be used so that pressure drop and temperature can be
measured. Piping materials should be limited to copper or PVC
SCH80. Note: Due to the pressure and temperature extremes,
PVC SCH40 is not recommended.
Water quantity should be plentiful and of good quality.
Consult Table 3 for water quality guidelines. The unit can
be ordered with either a copper or cupro-nickel water
heat exchanger. Consult Table 3 for recommendations.
Copper is recommended for closed loop systems and open
loop ground water systems that are not high in mineral
content or corrosiveness. In conditions anticipating heavy
scale formation or in brackish water, a cupro-nickel heat
exchanger is recommended. In ground water situations
where scaling could be heavy or where biological growth
such as iron bacteria will be present, an open loop system
is not recommended. Heat exchanger coils may over time
lose heat exchange capabilities due to build up of mineral
deposits. Heat exchangers must only be serviced by a
qualified technician, as acid and special pumping equipment
is required. Desuperheater coils can likewise become scaled
and possibly plugged. In areas with extremely hard water,
the owner should be informed that the heat exchanger
may require occasional acid flushing. In some cases, the
desuperheater option should not be recommended due to
hard water conditions and additional maintenance required.
Water Quality Standards
Table 3 should be consulted for water quality requirements.
Scaling potential should be assessed using the pH/Calcium
hardness method. If the pH <7.5 and the Calcium hardness
is less than 100 ppm, scaling potential is low. If this method
yields numbers out of range of those listed, the Ryznar
Stability and Langelier Saturation indecies should be
calculated. Use the appropriate scaling surface temperature
for the application, 150°F [66°C] for direct use (well water/
open loop) and DHW (desuperheater); 90°F [32°F] for
indirect use. A monitoring plan should be implemented in
these probable scaling situations. Other water quality issues
such as iron fouling, corrosion prevention and erosion and
clogging should be referenced in Table 3.
Expansion Tank and Pump
Use a closed, bladder-type expansion tank to minimize
mineral formation due to air exposure. The expansion tank
should be sized to provide at least one minute continuous
run time of the pump using its drawdown capacity rating to
prevent pump short cycling. Discharge water from the unit
is not contaminated in any manner and can be disposed
of in various ways, depending on local building codes (e.g.
recharge well, storm sewer, drain field, adjacent stream
or pond, etc.). Most local codes forbid the use of sanitary
sewer for disposal. Consult your local building and zoning
department to assure compliance in your area.
The pump should be sized to handle the home’s domestic
water load (typically 5-9 gpm [23-41 l/m]) plus the flow rate
required for the heat pump. Pump sizing and expansion
tank must be chosen as complimentary items. For example,
an expansion tank that is too small can causing premature
pump failure due to short cycling. Variable speed pumping
applications should be considered for the inherent energy
savings and smaller expansion tank requirements.
Water Control Valve
Note the placement of the water control valve in figure 9.
Always maintain water pressure in the heat exchanger by
placing the water control valve(s) on the discharge line
to prevent mineral precipitation during the off-cycle. Pilot
operated slow closing valves are recommended to reduce
water hammer. If water hammer persists, a mini-expansion
tank can be mounted on the piping to help absorb the excess
hammer shock. Insure that the total ‘VA’ draw of the valve
can be supplied by the unit transformer. For instance, a slow
closing valve can draw up to 35VA. This can overload smaller
40 or 50 VA transformers depending on the other controls
in the circuit. A typical pilot operated solenoid valve draws
approximately 15VA (see Figure 24). Note the special wiring
diagrams for slow closing valves (Figures 25 & 26).
Flow Regulation
Flow regulation can be accomplished by two methods. One
method of flow regulation involves simply adjusting the ball
valve or water control valve on the discharge line. Measure
the pressure drop through the unit heat exchanger, and
determine flow rate from Tables 11a through 11b. Since the
pressure is constantly varying, two pressure gauges may
be needed. Adjust the valve until the desired flow of 1.5 to
2 gpm per ton [2.0 to 2.6 l/m per kW] is achieved. A second
method of flow control requires a flow control device mounted
on the outlet of the water control valve. The device is typically
a brass fitting with an orifice of rubber or plastic material
that is designed to allow a specified flow rate. On occasion,
flow control devices may produce velocity noise that can be
reduced by applying some back pressure from the ball valve
located on the discharge line. Slightly closing the valve will
spread the pressure drop over both devices, lessening the
velocity noise. NOTE: When EWT is below 50°F [10°C], a
minimum of 2 gpm per ton (2.6 l/m per kW) is required.
14
Heat Controller, Inc. Water-Source Heating and Cooling Systems
The Quality Leader in Conditioning Air
Ground-Water Heat Pump Applications
Water Coil Low Temperature Limit Setting
For all open loop systems the 30°F [-1.1°C] FP1 setting
(factory setting-water) should be used to avoid freeze damage
to the unit. See “Low Water Temperature Cutout Selection” in
this manual for details on the low limit setting.
x CAUTION! x
CAUTION! Many units installed with a factory or field supplied
manual or electric shut-off valve. DAMAGE WILL OCCUR if
shut-off valve is closed during unit operation. A high pressure
switch must be installed on the heat pump side of any field
provided shut-off valves and connected to the heat pump
controls in series with the built-in refrigerant circuit high
pressure switch to disable compressor operation if water
pressure exceeds pressure switch setting. The field installed
high pressure switch shall have a cut-out pressure of 235 psig
and a cut-in pressure of 190 psig. This pressure switch can
be ordered from HCI with a 1/4” internal flare connection as
part number 39B0005N01.
Residential Split - 60Hz R22 &R410A
Figure 9: Water Well Connections
Rev.: 5 June, 2008
x CAUTION! x
CAUTION! Refrigerant pressure activated water regulating
valves should never be used with HCI equipment.
www.heatcontoller.com
15
Loading...
+ 33 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.