Heat Controller HPV Quick Start Manual

INSTALLATION, OPERATION
& MAINTENANCE MANUAL
Residential Packaged
Geothermal Heat Pump
HP Series
1
1
Heat Controller, Inc. • 1900 Wellworth Ave. • Jackson, MI 49203 • (517)787-2100 • www.heatcontroller.com
Installation, Operation & Maintenance HP SerieS Heat Controller, Inc.
Table of Contents
Model Nomenclature ............................................................................................2
Safety Instructions ................................................................................................3
Pre-Installation......................................................................................................4
Physical Data........................................................................................................5
Vertical Unit Dimensions....................................................................................6-7
Vertical Installation.............................................................................................8-9
Water Connection Installation .............................................................................10
Ground-Loop Heat Pump Applications ..........................................................10-12
Ground-Water Heat Pump Applications ..............................................................13
Water Quality Standards ....................................................................................14
Hot Water Generator .....................................................................................15-17
Electrical Data ...............................................................................................18-22
Blower Performance Data ..................................................................................23
Wiring Diagrams ............................................................................................24-25
CXM Controls ................................................................................................26-28
Unit Start-Up and Operating Conditions ........................................................29-36
Preventive Maintenance .....................................................................................37
Troubleshooting .............................................................................................38-42
1
Heat Controller, Inc. HP SerieS Installation, Operation & Maintenance
DRAWINGNO:
Decoder HP
S = STRAIGHT DISCHARGE, HORIZONTAL ONLY
Unit Nomenclature
HEAT CONTROLLER SERIES
TRH/TRV HPH/HPV
MODEL TYPE
HP = HEAT CONTROLLER RESIDENTIAL 410A
1 2 3 4 5 6 7
H P H A0 3 6 C1 5 0 A L B
CONFIGURATION
V=VERTICAL
H = HORIZONTAL V = VERTICAL
V
UNIT SIZE
018 024 030 036 042 048 060
REVISION LEVEL
A = CURRENT REVISION
C = CXM (CSA/NRTL for USA & CANADA)
VOLTAGE
1 = 208-230/60/1
CONTROLS
9 10 11 12 13 14
8
WATER CIRCUIT OPTIONS
0 = NONE 1 = HWG w/ INTERNAL PUMP
CABINET INSULATION
0 = RESIDENTIAL 5 = RESIDENTIAL w/ULTRA QUIET
T
SUPPLY AIR OPTIONS
T=TOP DISCHARGE
B = BACK DISCHARGE, HORIZONTAL ONLY T = TOP DISCHARGE, VERTICAL ONLY
RETURN AIR OPTIONS
L = LEFT RETURN R = RIGHT RETURN
HEAT EXCHANGER OPTIONS
A = Copper Water Coil w/E-Coated Air Coil J = Cupro-Nickel Water Coil w/E-Coated Air Coil
NOTE: Above model nomenclature is a general reference. Consult individual specication catalogs for detailed information.
2
Installation, Operation & Maintenance HP SerieS Heat Controller, Inc.
Safety
Warnings, cautions and notices appear throughout this manual. Read these items carefully before attempting any installation, service or troubleshooting of the equipment.
DANGER: Indicates an immediate hazardous situation, which if not avoided will result in death or serious injury. DANGER labels on unit access panels must be observed.
WARNING: Indicates a potentially hazardous situation, which if not avoided could result in death or serious injury.
WARNING!
WARNING! Verify refrigerant type before
proceeding. Units are shipped with R-22 refrigerant.
R-410A
CAUTION: Indicates a potentially hazardous situation or an unsafe practice, which if not avoided could result in minor or moderate injury or product or property damage.
NOTICE: Notification of installation, operation or maintenance information, which is important, but which is not hazard-related.
WARNING!
WARNING! All refrigerant discharged
from this unit must be recovered WITHOUT EXCEPTION. Technicians must follow industry accepted guidelines and all local, state, and federal statutes for the recovery and disposal of refrigerants. If a compressor is removed from this unit, refrigerant circuit oil will remain in the compressor. To avoid leakage of compressor oil, refrigerant lines of the compressor must be sealed after it is removed.
CAUTION! �
WARNING! �
WARNING! To avoid the release of refrigerant into the atmosphere, the refrigerant circuit of this unit must be serviced only by technicians who meet local, state, and federal proficiency requirements.
CAUTION!
To avoid equipment damage, DO NOT use these units as a source of heating or cooling during the construction process. The mechanical components and filters will quickly become clogged with construction dirt and debris, which may cause system damage.
3
Heat Controller, Inc. HP SerieS Installation, Operation & Maintenance
6. Loosen compressor bolts on units equipped with compressor spring vibration isolation until the compressor rides freely on the springs. Remove shipping restraints.
7.
REMOVE COMPRESSOR SUPPORT PLATE 1/4” SHIPPING BOLTS (2 on each side) TO MAXIMIZE VIBRATION AND SOUND ATTENUATION.
GENERAL INFORMATION
Inspection
Upon receipt of the equipment, carefully check the shipment against the bill of lading. Make sure all units have been received. Inspect the packaging of each unit, and inspect each unit for damage. Insure that the carrier makes proper notation of any shortages or damage on all copies of the freight bill and completes a common carrier inspection report. Concealed damage not discovered during unloading must be reported to the carrier within 15 days of receipt of shipment. If not filed within 15 days, the freight company can deny the claim without recourse. Note: It is the responsibility of the purchaser to file all necessary claims with the carrier. Notify Heat Controller of all damage within fifteen (15) days of shipment.
Storage
Equipment should be stored in its original packaging in a clean, dry area. Store units in an upright position at all times. Stack units a maximum of 3 units high.
Unit Protection
Cover units on the job site with either the original packaging or an equivalent protective covering. Cap the open ends of pipes stored on the job site. In areas where painting, plastering, and/or spraying has not been completed, all due precautions must be taken to avoid physical damage to the units and contamination by foreign material. Physical damage and contamination may prevent proper start-up and may result in costly equipment clean-up.
Examine all pipes, fittings, and valves before installing any of the system components. Remove any dirt or debris found in or on these components.
Pre-Installation
Installation, Operation, and Maintenance instructions
Installation, Operation and Maintenance
are provided with each unit. Horizontal equipment is
instructions are provided with each unit. Vertical unit
designed for installation above false ceiling or in a ceiling
congurations are typically installed in a mechanical
plenum. Other unit configurations are typically installed
room. The installation site chosen should include
in a mechanical room. The installation site chosen
adequate ervice clearance around the unit. Before
should include adequate service clearance around the
unit start-up, read all manuals and become familiar
unit. Before unit start-up, read all manuals and become
with the unit and its operation. Thoroughly check the
familiar with the unit and its operation. Thoroughly check
system before operation.
the system before operation.
Prepare units for installation as follows:
1. Compare the electrical data on the unit nameplate with ordering and shipping information to verify that the correct unit has been shipped.
2. Keep the cabinet covered with the original packaging until installation is complete and all plastering, painting, etc. is finished.
3. Verify refrigerant tubing is free of kinks or dents and that it does not touch other unit components.
4. Inspect all electrical connections. Connections must be clean and tight at the terminals.
5. Remove any blower support packaging.
6. Loosen compressor bolts on units equipped with compressor spring vibration isolation until the compressor rides freely on the springs. Remove shipping restraints. REMOVE COMPRESSOR SUPPORT PLATE 1/4”
7.
7.
8. Some airflow patterns are field convertible (horizontal SHIPPING BOLTS (2 on each side) TO MAXIMIZE
units only). Locate the airflow conversion section of
VIBRATION AND SOUND ATTENUATION.
this IOM.
8. Some airflow patterns are field convertible (horizontal
9. Locate and verify any hangers, or other accessory
8.
units only). Locate the airflow conversion section of
kits located in the compressor section or blower
this IOM.
section.
9. Locate and verify any hangers, or other accessory kits located in the compressor section or blower section.
CAUTION!
CAUTION! DO NOT store or install units
in corrosive environments or in locations subject to temperature or humidity extremes
CAUTION! DO NOT store or install units
(e.g., attics, garages, rooftops, etc.).
in corrosive environments or in locations
Corrosive conditions and high temperature
subject to temperature or humidity extremes
or humidity can significantly reduce
(e.g., attics, garages, rooftops, etc.).
performance, reliability, and service life.
Corrosive conditions and high temperature
Always move units in an upright position.
or humidity can significantly reduce
Tilting units on their sides may cause
performance, reliability, and service life.
equipment damage.
Always move units in an upright position.
CAUTION!
Tilting units on their sides may cause equipment damage.
NOTICE! Failure to remove shipping brackets from spring-mounted compressors will cause excessive noise, and could cause component
NOTICE! Failure to remove shipping brackets
failure due to added vibration.
from spring-mounted compressors will cause excessive noise, and could cause component failure due to added vibration.
CAUTION!
CAUTION! CUT HAZARD - Failure to follow
this caution may result in personal injury. Sheet metal parts may have sharp edges
CAUTION! CUT HAZARD - Failure to follow
or burrs. Use care and wear appropriate
this caution may result in personal injury.
protective clothing, safety glasses and
Sheet metal parts may have sharp edges
gloves when handling parts and servicing
or burrs. Use care and wear appropriate
heat pumps.
protective clothing, safety glasses and gloves when handling parts and servicing heat pumps.
CAUTION!
4
Installation, Operation & Maintenance HP SerieS Heat Controller, Inc.
Physical Data
HP Series
Compressor (1 Each) Rotary Scroll
Factory Charge R410A (oz) 43 43 48 50 70 74 82
PSC Fan Motor & Blower
Fan Motor Type/Speeds PSC/3 PSC/3 PSC/3 PSC/3 PSC/3 PSC/3 PSC/3
Fan Motor (hp) 1/6 1/4 3/4 1/2 3/4 3/4 1
Blower Wheel Size (Dia x w) 8x7 9x7 9x7 9x8 9x8 10x10 11x10
Water Connection Size 1” Swivel
Hx Water Volume (gal.) .45 .286 .323 .323 .890 .738 .939
Vertical
Air Coil Dimensions (H x W) 20x17.25 20x17.25 20x17.25 24x21.75 24x21.76 28x25 28x25
Filter Standard - 1" Throwaway 20x20 20x20 20x20 24x24 24x24 28x28 28x28
Weight - Operating (lbs.) 168 184 192 213 228 283 298
Weight - Packaged (lbs.) 173 194 197 219 234 290
018 024 030 036 042 048 060
305
Maximum Working Water Pressure
Pressure PSIG (kPa)
Unit Source Circuit 500 (3,447)
HWG Circuit 125 (862)
5
Heat Controller, Inc. HP SerieS Installation, Operation & Maintenance
HP - Vertical Upow Dimensional Data
Vertical
uplow
Model
018 - 030
036 - 042
048 - 060
Vertical
Upow
Model
018
024 -
030
036 -
042
048 -
060
in
cm
in
cm
in
cm
in
cm
in
cm
in
cm
in
cm
Overall Cabinet
A
WidthBDepthCHeight
22.4
56.9
22.4
56.9
25.4
64.5
Loop
In D
3.7
9.4
3.7
9.4
3.7
9.4
3.7
9.4
22.4
56.9
25.4
64.5
29.1
73.9
1 2 3 4 5
Loop
In E
1.9
4.8
1.9
4.8
1.8
4.6
1.8
4.6
40.5
102.9
46.5
118.1
50.5
128.3
Water Connections - Standard Units
Loop
Out
F
9.7
24.6
9.7
24.6
12.7
32.3
12.7
32.3
Loop
Out
E
1.9
4.8
1.9
4.8
1.8
4.6
1.8
4.6
Cond. 3/4” HWG In HWG Out
H I DD EE FF EE
7.0
17.8
7.0
17.8
8.0
20.3
8.0
20.3
1.9
4.8
1.9
4.8
1.8
4.6
1.8
4.6
11.7
29.7
12.4
31.5
15.2
38.6
15.2
38.6
1.6
4.1
1.6
4.1
1.6
4.1
1.6
4.1
14.9
37.8
15.7
39.9
18.4
46.7
18.4
46.7
1.6
4.1
1.6
4.1
1.6
4.1
1.6
4.1
Electrical Knockouts
Vertical
018 - 060
Model
in
cm
J
1/2”
Low
Voltage
4.0
10.2
K
1/2”
Low
Voltage
7.0
17.8
L
3/4”
Power
Supply
10.0
25.4
Notes:
1. While clear access to all removable panels is not required, installer should take care to comply with all building codes and allow
adequate clearance for future eld service.
2. Front & Side access is preferred for service access. However, all components may be serviced from the front access panel if side access is not available.
3. Discharge ange is eld installed.
4. Condensate is 3/4” socket.
5. Source water and optional HWG connections are 1” swivel.
6
Installation, Operation & Maintenance HP SerieS Heat Controller, Inc.
HP - Vertical Upow Dimensional Data
Vertical
Model
018 - 030
036 - 042
048 - 060
in
cm
in
cm
in
cm
Duct Flange Installed (+/- 0.10 in, +/- 2.5mm)
M N
7.2
18.3
7.2
18.3
8.2
20.8
Legend: CAP = Control Access Panel BSP = Blower Service Panel CSP = Compressor Access Panel ASP = Alternative Service Panel
P
Discharge Connection
Supply
Width
4.2
10.7
6.0
15.2
5.7
14.5
14.0
35.6
14.0
35.6
16.0
40.6
N
Return Connection
Using Return Air Opening
O
N
P
Supply
Depth
14.0
35.6
14.0
35.6
18.0
45.7
B
P
Q R
5.4
13.7
5.2
13.2
5.2
13.2
2.2
5.6
2.1
5.3
2.1
5.3
S
Return
Depth
Return Height
18.4
46.7
22.9
58.2
26.2
66.5
Standard Filter Bracket
Air Coil
T
20.3
51.6
24.3
61.7
28.3
71.9
Field Installed Discharge Flange
U
1.1
2.8
1.1
2.8
1.1
2.8
Access Panels
BSP
ASP
Front
O
Q
Top View-Right Return
R
U
T
C
Right Return Right View
- Air Coil Opening
Air Coil Side
S
Opptional
2' [61cm]
Service Access Left Rtn
(Right Rtn Opposite
Side)
Air Coil Side
Top View-Left Return
S
O
Front
M
R
A
CSP
2' [61cm]
Service
CAP
Isometric
View
U
Air Coil
Air Coil
T
C
Power Supply
3/4" [19.1 mm] HV
Knockout
Low Voltage
1/2" [12.7 mm] LV
Knockout
CSPCSP
BackFront
Left Return Left View
- Air Coil Opening
FrontBack
Low Voltage
1/2" [12.7 mm] LV
Knockout
CSP
L
K
J
U
A
EE
5
4 3
2
2
3
1
D
FF
DD
F
H
E
7
Heat Controller, Inc. HP SerieS Installation, Operation & Maintenance
VERTICAL INSTALLATION
Vertical Unit Location
Units are not designed for outdoor installation. Locate the unit in an INDOOR area that allows enough space for service personnel to perform typical maintenance or repairs without removing unit from the mechanical room/ closet. Vertical units are typically installed in a mechanical room or closet. Never install units in areas subject to freezing or where humidity levels could cause cabinet condensation (such as unconditioned spaces subject to 100% outside air). Consideration should be given to access for easy removal of the filter and access panels. Provide sufficient room to make water, electrical, and duct connection(s).
If the unit is located in a confined space, such as a closet, provisions must be made for return air to freely enter the space by means of a louvered door, etc. Any access panel screws that would be difficult to remove after the unit is installed should be removed prior to setting the unit. Refer to Figures 7 and 8 for typical installation illustrations. Refer to unit specifications catalog for dimensional data.
1. Install the unit on a piece of rubber, neoprene or other mounting pad material for sound isolation. The pad should be at least 3/8” [10mm] to 1/2” [13mm] in thickness. Extend the pad beyond all four edges of the unit.
2. Provide adequate clearance for filter replacement and drain pan cleaning. Do not block filter access with piping, conduit or other materials. Refer to unit specifications for dimensional data.
3. Provide access for fan and fan motor maintenance and for servicing the compressor and coils without removing the unit.
4. Provide an unobstructed path to the unit within the closet or mechanical room. Space should be sufficient to allow removal of the unit, if necessary.
5. Provide access to water valves and fittings and screwdriver access to the unit side panels, discharge collar and all electrical connections.
Figure 7: Vertical Unit Mounting
Air Pad or Extruded polystyrene insulation board
Figure 8: Typical Vertical Unit Installation
Using Ducted Return Air
Internally insulate supply duct for first 4’ [1.2m] each way to reduce noise
Use turning vanes in supply transition
Flexible canvas duct connector to reduce noise and vibration
Rounded return transition
The installation of water source heat pump units and all associated components, parts and accessories which make up the installation shall be in accordance with the regulations of ALL authorities having jurisdiction and MUST conform to all applicable codes. It is the responsibility of the installing contractor to determine and comply with ALL applicable codes and regulations.
Internally insulate return transition duct to reduce noise
8
Rev 3/27/00
Installation, Operation & Maintenance HP SerieS Heat Controller, Inc.
VERTICAL INSTALLATION
Sound Attenuation for Vertical Units
Sound attenuation is achieved by enclosing the unit within a small mechanical room or a closet. Additional measures for sound control include the following:
1. Mount the unit so that the return air inlet is 90° to the return air grille. Refer to Figure 9. Install a sound baffle as illustrated to reduce line-of sight sound transmitted through return air grilles.
2.
Mount the unit on a rubber or neoprene isolation pad to minimize vibration transmission to the building structure.
Figure 9: Vertical Sound Attenuation

Condensate Piping – Vertical Units
Vertical units utilize a condensate hose inside the cabinet as a trapping loop; therefore an external trap is not necessary. Figure 10a shows typical condensate connections. Figure 10b illustrates the internal trap for a typical vertical heat pump. Each unit must be installed with its own individual vent and a means to flush or blow out the condensate drain line. Do not install units with a common trap and/or vent.
Figure 10a: Vertical Condensate Drain








1/4” per foot (21mm per m) slope to drain

 

Figure 10b: Vertical Internal Condensate Trap
9
Heat Controller, Inc. HP SerieS Installation, Operation & Maintenance
WATER CONNECTION INSTALLATION
External Flow Controller Mounting
The Flow Controller can be mounted beside the unit as shown in Figure 12. Review the Flow Controller installation manual for more details.
Water Connections-Residential HR Models
Models utilize swivel piping fittings for water connections that are rated for 450 psi (3101 kPa) operating pressure. The connections have a rubber gasket seal similar to a garden hose gasket, which when mated to the flush end of most 1” threaded male pipe fittings provides a leak­free seal without the need for thread sealing tape or joint compound. Insure that the rubber seal is in the swivel connector prior to attempting any connection (rubber seals are shipped attached to the swivel connector). DO NOT OVER TIGHTEN or leaks may occur.
The female locking ring is threaded onto the pipe threads
HP
GROUND-LOOP HEAT PUMP APPLICATIONS
CAUTION!
CAUTION! The following instructions
represent industry accepted installation practices for closed loop earth coupled heat pump systems. Instructions are provided to assist the contractor in installing trouble free ground loops. These instructions are recommendations only. State/provincial and local codes MUST be followed and installation MUST conform to ALL applicable codes. It is the responsibility of the installing contractor to determine and comply with ALL applicable codes and regulations.
Pre-Installation
Prior to installation, locate and mark all existing underground utilities, piping, etc. Install loops for new construction before sidewalks, patios, driveways, and other construction has begun. During construction, accurately mark all ground loop piping on the plot plan as an aid in avoiding potential future damage to the installation.
Piping Installation
The typical closed loop ground source system is shown in Figure 12. All earth loop piping materials should be limited to polyethylene fusion only for in-ground sections of the loop. Galvanized or steel fittings should not be used at any time due to their tendency to corrode. All plastic to metal threaded fittings should be avoided due to their potential to leak in earth coupled applications. A flanged fitting should be substituted. P/T plugs should be used so that flow can be measured using the pressure drop of the unit heat exchanger.
which holds the male pipe end against the rubber gasket, and seals the joint. HAND TIGHTEN ONLY! DO NOT OVERTIGHTEN!
Figure 11: Water Connections
Hand Tighten
Only!
Swivel Nut
Stainless steel
snap ring
Gasket
Earth loop temperatures can range between 25 and 110°F [-4 to 43°C]. Flow rates between 2.25 and 3 gpm per ton [2.41 to 3.23 l/m per kW] of cooling capacity recommended in these applications.
Test individual horizontal loop circuits before backfilling. Test vertical U-bends and pond loop assemblies prior to installation. Pressures of at least 100 psi [689 kPa] should be used when testing. Do not exceed the pipe pressure rating. Test entire system when all loops are assembled.
Flushing the Loop
Once piping is completed between the unit, Flow Controller and the ground loop (Figure 12), the loop is ready for final purging and charging. A flush cart with at least a 1.5 hp [1.1 kW] pump is required to achieve enough fluid velocity in the loop piping system to purge air and dirt particles. An antifreeze solution is used in most areas to prevent freezing. All air and debris must be removed from the earth loop piping before operation. Flush the loop with a high volume of water at a minimum velocity of 2 fps (0.6 m/s) in all piping. The steps below must be followed for proper flushing.
1. Fill loop with water from a garden hose through the flush cart before using the flush cart pump to insure an even fill.
2. Once full, the flushing process can begin. Do not allow the water level in the flush cart tank to drop below the pump inlet line to avoid air being pumped back out to the earth loop.
3. Try to maintain a fluid level in the tank above the return tee so that air cannot be continuously mixed back into the fluid. Surges of 50 psi (345 kPa) can be used to help purge air pockets by simply shutting off the return valve going into the flush cart reservoir. This “dead heads” the pump to 50 psi (345 kPa). To purge, dead head the pump until maximum pumping
Do Not
Overtighten!
Brass Adaptor
10
Installation, Operation & Maintenance HP SerieS Heat Controller, Inc.
GROUND-LOOP HEAT PUMP APPLICATIONS
pressure is reached. Open the return valve and a pressure surge will be sent through the loop to help purge air pockets from the piping system.
4. Notice the drop in fluid level in the flush cart tank when the return valve is shut off. If air is adequately purged from the system, the level will drop only 1-2 inches (2.5 - 5 cm) in a 10” (25 cm) diameter PVC flush tank (about a half gallon [2.3 liters]), since liquids are incompressible. If the level drops more than this, flushing should continue since air is still being compressed in the loop fluid. Perform the “dead head” procedure a number of times.
Note: This fluid level drop is your only indication of air in the loop.
Antifreeze may be added before, during or after the flushing procedure. However, depending upon which time is chosen, antifreeze could be wasted when emptying the flush cart tank. See antifreeze section for more details.
Loop static pressure will fluctuate with the seasons. Pressures will be higher in the winter months than during the cooling season. This fluctuation is normal and should be considered when charging the system initially. Run the unit in either heating or cooling for a number of minutes to condition the loop to a homogenous temperature. This is a good time for tool cleanup, piping insulation, etc. Then, perform final flush and pressurize the loop to a static pressure of 50-75 psi [345-517 kPa] (winter) or 35-40 psi [241-276 kPa] (summer). After pressurization, be sure to loosen the plug at the end of the Grundfos loop pump motor(s) to allow trapped air to be discharged and to insure the motor housing has been flooded. This is not required for Taco circulators. Insure that the Flow Controller provides adequate flow through the unit by checking pressure drop across the heat exchanger and compare to the pressure drop tables at the back of the manual.
Antifreeze
In areas where minimum entering loop temperatures drop below 40°F [5°C] or where piping will be routed through areas subject to freezing, antifreeze is required. Alcohols and glycols are commonly used as antifreeze; however your local sales manager should be consulted for the antifreeze best suited to your area. Freeze protection should be maintained to 15°F [9°C] below the lowest expected entering loop temperature. For example, if 30°F [-1°C] is the minimum expected entering loop
temperature, the leaving loop temperature would be 25 to 22°F [-4 to -6°C] and freeze protection should be at 15°F [-10°C]. Calculation is as follows: 30°F - 15°F = 15°F [-1°C - 9°C = -10°C].
All alcohols should be premixed and pumped from a reservoir outside of the building when possible or introduced under the water level to prevent fumes. Calculate the total volume of fluid in the piping system. Then use the percentage by volume shown in Table 1 for the amount of antifreeze needed. Antifreeze concentration should be checked from a well mixed sample using a hydrometer to measure specific gravity.
Low Water Temperature Cutout Setting CXM Control
When antifreeze is selected, the FP1 jumper (JW3) should be clipped to select the low temperature (an­tifreeze 13°F [-10.6°C]) set point and avoid nuisance faults (see “Low Water Temperature Cutout Selection” in this manual). NOTE: Low water temperature operation requires extended range equipment.
Table 1: Approximate Fluid Volume (gal.) per 100' of Pipe
Fluid Volume (gal [L]/100’ Pipe)
Pipe Size Volume (gal) [L]
1” 4.1 [15.5]
Copper
Rubber Hose 1” 3.9 [14.8]
Polyethylene
Unit Heat Exchanger Typical 1.0 [3.8]
Flush Cart Tank
1.25” 6.4 [24.2]
2.5” 9.2 [34.8]
3/4” IPS SDR11 2.8 [10.6]
1” IPS SDR11
1.25” IPS SDR11 8.0 [30.3]
1.5” IPS SDR11 10.9 [41.3]
2” IPS SDR11 18.0 [68.1]
1.25” IPS SCH40 8.3 [31.4]
1.5” IPS SCH40 10.9 [41.3]
2” IPS SCH40 17.0 [64.4]
10” Dia x 3ft
[254mm x 0.9m]
4.5 [17.0]
10 [37.9]
Table 2: Antifreeze Percentages by Volume
Table 3. Antifreeze Percentages by Volume
Type Minimum Temperature for Freeze Protection
10°F [-12.2
Methanol 25% 21% 16% 10%
100% USP food grade Propylene Glycol 38% 30% 22% 15%
°C] 15°F [-9.4°C] 20°F [-6.7°C] 25°F [-3.9°C]
11
Heat Controller, Inc. HP SerieS Installation, Operation & Maintenance
GROUND-LOOP HEAT PUMP APPLICATIONS
Figure 12: Typical Ground-Loop Application
Flow
Controller
Unit Power Disconnect
Insulated Hose Kit
Thermostat Wiring
Air Pad or Extruded polystyrene insulation board
GROUND-WATER HEAT PUMP APPLICATIONS
Open Loop - Ground Water Systems
Typical open loop piping is shown in Figure 14. Shut off valves should be included for ease of servicing. Boiler drains or other valves should be “tee’d” into the lines to allow acid flushing of the heat exchanger. Shut off valves should be positioned to allow flow through the coax via the boiler drains without allowing flow into the piping system. P/T plugs should be used so that pressure drop and temperature can be measured. Piping materials should be limited to copper or PVC SCH80. Note: Due to
the pressure and temperature extremes, PVC SCH40 is not recommended.
Water quantity should be plentiful and of good quality. Consult table 3 for water quality guidelines. The unit can be ordered with either a copper or cupro-nickel water heat exchanger. Consult Table 3 for recommendations. Copper is recommended for closed loop systems and open loop ground water systems that are not high in mineral content or corrosiveness. In conditions anticipating heavy scale formation or in brackish water, a cupro-nickel heat exchanger is recommended. In ground water situations where scaling could be heavy or where biological growth such as iron bacteria will be present, an open loop system is not recommended. Heat exchanger coils may over time lose heat exchange capabilities due to build up of mineral deposits. Heat exchangers must
13.
P/T Plugs
only be serviced by a qualified technician, as acid and special pumping equipment is required. Desuperheater coils can likewise become scaled and possibly plugged. In areas with extremely hard water, the owner should be informed that the heat exchanger may require occasional acid flushing. In some cases, the desuperheater option should not be recommended due to hard water conditions and additional maintenance required.
Water Quality Standards
Table 3 should be consulted for water quality requirements. Scaling potential should be assessed using the pH/Calcium hardness method. If the pH <7.5 and the calcium hardness is less than 100 ppm, scaling potential is low. If this method yields numbers out of range of those listed, the Ryznar Stability and Langelier Saturation indecies should be calculated. Use the appropriate scaling surface temperature for the application, 150°F [66°C] for direct use (well water/open loop) and desuperheater; 90°F [32°F] for indirect use. A monitoring plan should be implemented in these probable scaling situations. Other water quality issues such as iron fouling, corrosion prevention and erosion and clogging should be referenced in Table 3.
12
Installation, Operation & Maintenance HP SerieS Heat Controller, Inc.
GROUND-WATER HEAT PUMP APPLICATIONS
Expansion Tank and Pump
Use a closed, bladder-type expansion tank to minimize mineral formation due to air exposure. The expansion tank should be sized to provide at least one minute continuous run time of the pump using its drawdown capacity rating to prevent pump short cycling. Discharge water from the unit is not contaminated in any manner and can be disposed of in various ways, depending on local building codes (e.g. recharge well, storm sewer, drain field, adjacent stream or pond, etc.). Most local codes forbid the use of sanitary sewer for disposal. Consult your local building and zoning department to assure compliance in your area.
Water Control Valve
Note the placement of the water control valve in
13.
Figure 14. Always maintain water pressure in the heat exchanger by placing the water control valve(s) on the discharge line to prevent mineral precipitation during the off-cycle. Pilot operated slow closing valves are recommended to reduce water hammer. If water hammer persists, a mini-expansion tank can be mounted on the piping to help absorb the excess hammer shock. Insure that the total ‘VA’ draw of the valve can be supplied by the unit transformer. For instance, a slow closing valve can draw up to 35VA. This can overload smaller 40 or 50 VA transformers depending on the other controls in the circuit. A typical pilot operated solenoid valve draws approximately 15VA.
Flow Regulation
Flow regulation can be accomplished by two methods. One method of flow regulation involves simply adjusting the ball valve or water control valve on the discharge line. Measure the pressure drop through the unit heat exchanger, and determine flow rate from Tables 8. Since
Table 10C. Since
the pressure is constantly varying, two pressure gauges may be needed. Adjust the valve until the desired flow of
1.5 to 2 gpm per ton [2.0 to 2.6 l/m per kW] is achieved. A second method of flow control requires a flow control device mounted on the outlet of the water control valve. The device is typically a brass fitting with an orifice of rubber or plastic material that is designed to allow a specified flow rate. On occasion, flow control devices may produce velocity noise that can be reduced by applying some back pressure from the ball valve located on the discharge line. Slightly closing the valve will spread the pressure drop over both devices, lessening the velocity noise. NOTE: When EWT is below 50°F [10°C], 2 gpm
per ton (2.6 l/m per kW) is required.
Water Coil Low Temperature Limit Setting
For all open loop systems the 30°F [-1.1°C] FP1 setting (factory setting-water) should be used to avoid freeze damage to the unit. See “Low Water Temperature Cutout Selection” in this manual for details on the low limit setting.
Figure 13: Typical Open Loop/Well Application
Unit Power Disconnect
Air Pad or Extruded polystyrene insulation board
Thermostat Wiring
Water
Control
Valve
P/T Plugs
Flow
Regulator
Boiler
Drains
Pressure
Tank
Water Out
Optional
Filter
Water In
Shut-Off
Valve
13
Loading...
+ 30 hidden pages