Heat Controller EKTC07-2G, EKTC09-1G, EKTC09-2G, EKTC12-2G, EKTC15-2G Owner's Manual

...
OWNER’s MANUAL
Packaged Terminal
Air Conditioners & Heat Pumps
7,000-15,000 BTUH
Cooling with Electric Heat
EKTC07-1G EKTC09-1G EKTC12-1G EKTC15-1G
Heat Pump with Electric Heat
EKTH07-1G EKTH09-1G EKTH12-1G EKTH15-1G
EKTC07-2G EKTC09-2G EKTC12-2G EKTC15-2G
EKTH07-2G EKTH09-2G EKTH12-2G EKTH15-2G
Heat Controller, Inc. • 1900 Wellworth Ave. • Jackson, MI 49203 • (517)787-2100 • www.heatcontroller.com
Packaged Terminal A/C OWNER’S MANUAL Heat Controller, Inc.
...........................1
................................... 2
.................................
4
................................. 8
........................... 9
...............................
13
.......................
14
...............................
15
................. ..............
12
............................1
.....................................5
CONTENTS
SYSTEM CONFIGURATION
HOW TO CONNECT
SAFETY CONSIDERATIONS
GENERAL INFORMATION
UNIT FEATURES
ELECTRICAL DATA
INSTALLATION
OPERATION
CARE AND CLEANING
PREVENTATIVE MAINTENANCE
TROUBLESHOOTING
........
TABLE OF CONTENTS
Safety Considerations ........................................................................................................ 2
General Information .......................................................................................................... 2
Unit Features ...................................................................................................................... 3
Electrical Data .................................................................................................................... 5
Installation .......................................................................................................................... 6
How to Connect ..................................................................................................................9
System Conguration .......................................................................................................10
Operation ..........................................................................................................................13
Care and Cleaning ............................................................................................................ 14
Preventative Maintenance ............................................................................................... 15
Troubleshooting ................................................................................................................16
The figures in this manual may be different with the material objects, please refer to the material objects for reference.
This symbol stands for the items should be forbidden
This symbol stands for the items should be followed
Do not dispose this product as unsorted municipal waste. Collection of such waste separately for special treatment
is necessary.
1
Heat Controller, Inc. OWNER’S MANUAL Packaged Terminal A/C
Safety Considerations
Recognize safety information. This is the safety-alert symbol .When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury. Understand these signal words: DANGER, WARNING, and CAUTION. These words are used with the safety-alert symbol.
DANGER identies the most serious hazards which will result in severe personal injury or death.
WARNING signies hazards which could result in personal injury or death.
CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage.
NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
WARNING
!
!
PERSONAL INJURY AND/OR PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage. For your safety, the
information in this manual must be followed to minimize the risk of re or explosion, electric shock, or to prevent
property damage, personal injury, or loss of life.
This unit must be properly installed in accordance with the Installation Instructions before it is used.
Immediately repair or replace all electric service cords that have become frayed or otherwise damaged.
• Unplug or disconnect the unit at the fuse box or circuit breaker before making any repairs.
NOTE: We strongly recommend that any servicing be performed by a qualied individual.
GENERAL INFORMATION
Heat Controller, Inc., package terminal air conditioners and heat pumps provide a high standard of quality in performance, work­manship, durability and appearance as they heat and cool the occupied air space year round. This manual provides information for ease of installation, operation and maintenance. All models are designed for through-the­wall installation. Separate installation instructions are included with all accessory components.
BEFORE YOU BEGIN
Read these instructions completely and carefully.
IMPORTANT: Save these instructions for local inspector’s use. IMPORTANT: Observe all governing codes and ordinances.
NOTE TO INSTALLER
Be sure to leave these instructions with the owner.
NOTE TO OWNER
Keep these instructions for future reference. Be sure to write down the model and serial number of unit on space provided on back page. The model and serial number can be located on the serial number plate attached to unit. These numbers are required for service. See Fig. 1.
Fig. 1 – Sample Data Information Plate
2
Packaged Terminal A/C OWNER’S MANUAL Heat Controller, Inc.
UNIT FEATURES
This unit has many exciting features which are different than those found on
standard PTAC models. The owner must be familiar with these features in order to fully understand the operation and capability of the unit.
SELF DIAGNOSITICS—The unit has an onboard computer that utilizes real- time diagnostics to prolong the life of your unit. There is an LED indicator on
the control board located behind the front panel, that will ash an error code
if the unit has detected some kind of fault condition. In many cases, the unit will automatically clear the fault condition and continue operating with no interruption. In some cases, the condition cannot be cleared and the unit will
require service. In those cases, an “Fx” failure mode will be displayed on the digital display. For a detailed list of all error codes and “Fx” conditions, see
Table 6—Status LED Indicator Denitions for further details.
AUTO RESTART—If power is lost, all of the control settings (setpoint, mode, fan speed, on/off and conguration) are stored. So when power is restored, the unit will start back up in the mode (and con­guration) it was in when power was lost.
QUIET OPERATION—The unit has 2 fan motors and a tangential blower wheel to reduce noise. The indoor fan will always run
a minimum of 10 seconds before the compressor, to help reduce any compressor starting noise.
RANDOM COMPRESSOR RESTART—To help prevent power surges after a power outage (from many of your PTAC/HPs starting at the same time), the compressor is equipped with a 2:45 to 3:15 minute random restart delay feature.Whenever the unit is
plugged in, or power has been restarted, a random compressor restart will occur between the random restart time frame.
COMPRESSOR PROTECTION—To prevent short cycling of the compressor and maximize it’s life, there is a random start--up
delay of 3 minutes on the compressor and a minimum compressor run time of 3 minutes.
AUTOMATIC ROOM FREEZE PROTECTION—The unit will automatically will keep the temperature in the room from getting too cold, where water pipes might freeze. If the unit is congured for the freeze protection feature to be active (which is the default condition), and while power is supplied to the unit, if the unit senses temperature below 40°F, the fan motor and electric heater are turned on and will warm the room to 50°F. If Freeze protection is not required, change the conguration switch to turn the feature off (see section on unit conguration).
AUTOMATIC DEFROST PROTECTION (FOR HEAT PUMP MODELS ONLY)—When the outdoor temperature gets too cold (ap- prox. 35°F) and the unit can no longer effectively heat with the compressor, the unit will automatically switch to electric heat­ing. The unit will then heat with electric heat until the outside temperature rises enough (approx. 40°F), so the compressor
can be used to effectively heat again.
AUTOMATIC QUICK WARM-UP (FOR HEAT PUMP MODELS ONLY)—If the room temperature falls to 5°F below the set point temperature, the reverse cycle heat is shut off and the electric strip heat is turned on for one cycle, until heating is satised.
LED INDICATOR’S AND BUTTONS—The touch pad has buttons for MODE, FAN SPEED, ON/OFF, SETPOINT UP and SETPOINT
DOWN. It also has LEDs that correspond to the mode, fan speed and setpoint operation, to indicate the unit’s status. The LEDs below the mode button, FAN, COOL, and HEAT, indicate which operating mode is active. The LEDs below the Fan button, Low, Med and Hi, indicate the fan speed that is selected. The LED located in the lower right corner is the unit On/Off status LED. If the unit is in ON mode, the LED will be green. If the unit is OFF, the LED will be red.
CONFIGURE FAN TO OPTIMIZE SELECTED APPLICATION—This unit can be optimized to specic applications by conguring
the fan to run in a continuous mode or to cycle on and off with the compressor and electric heater (can be different for both
heating and cooling modes). In cycle mode, fan will continue to run after compressor or electric heater stops in order blow off
any residual heat or cool left on coil. In continues mode, the fan remains on at all times even when the compressor is off.
Fig. 2
1 Indoor air temp sensor open/short 7 Segment display ‘F1’, with STATUS light ash 1 time,off 2 seconds
2 Indoor coil sensor open/short 7 Segment display ‘F2’, with STATUS light ash 2 times and off 2 seconds
3 Outdoor coil sensor open/short 7 Segment display ‘F4’, with STATUS light ash 4 times and off 2 seconds
4 Freeze Guard protection 7 Segment display ‘FP’
5 Thermostat wiring error STATUS light ash 9 times and off 3 sec, repeat
6 Indoor coil high temp protection STATUS light ash 8 times and off 3 sec, repeat
7 Defrost (heat pump type) STATUS light ash 7 times and off 3 sec, repeat
8 Outdoor coil high temp protection STATUS light ash 6 times and off 3 sec, repeat
9 Indoor coil freeze protection STATUS light ash 5 times and off 3 sec, repeat
NOTE: When status light is ashing, it will be ON for 0.5 seconds and OFF for another 0.5 seconds.
Table 6—STATUS LED Indicator Denitions
3
Heat Controller, Inc. OWNER’S MANUAL Packaged Terminal A/C
Unit Features CONTINUED
Unit Conguration —There are many different conguration possibilities, through both dipswitches and the digital keypad, that allow you to congure the unit for your exact application. See section on unit conguration for more details. Following are the conguration selections that have not previously been mentioned:
°F or °C—The unit can display in either °F or °C
Indoor Temperature Sensor Biasing —Optimize the room temperature sensor reading to your exact application (one for cooling and another for heating).
Emergency Heat (forHeat Pump Only)—Disable the compressor during heating mode operation (heat only with Electric Heat).
Display Setpoint OR Room Temperature—The unit can be congured to display the room temperature OR setpoint only, during heating and cooling modes. See section on unit conguration for more details.
Limit the Setpoint Range—The unit can be congured to limit the controlling setpoint range.The display will always show the complete setpoint range, but the controlling setpoint will be limited to the congured minimum and maximum setpoint selected. See section on unit conguration for more details.
Energy Management—Sometimes known as Front Desk Control, an input is provided so that the unit can
be manually disabled from a different location. If the unit detects 24 vac on this input, it will automatically turn itself off. If no voltage is detected on the input, the unit will run normally.
Wall Thermostat Control—A wired wall thermostat can be connected to the unit. If it is, the unit must be congured to disable the keypad. See section on wired inputs and unit conguration for more details.
UNIT NOMENCLATURE
EKTC—Cooling only with Electric Heat
EKTH—Heat Pump with Electric Heat
E K T C 0 7 - 1 G
BTU/H
07K 09K 12K 15K
Fig. 3 – Unit Nomenclature
MODEL REVISION G=Green R-410A
Refrigerant Gas
VOLTAGE CODE 1=208/230V-60Hz 2=265V-60Hz (consult factory)
4
Packaged Terminal A/C OWNER’S MANUAL Heat Controller, Inc.
ELETRICAL DATA
WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death and/or property damage. DO NOT alter cord or plug or use an extension cord.
POWER CONNECTION OPTIONS
Appropriate power cord accessory kit is determined by the voltage, and amperage of the branch circuit. The unit does not come with a power cord (or hard wire kit). An accessory power cord kit must be ordered to connect the unit to the outlet. If the unit is
to be hard wired, an accessory hard wire kit must be ordered.
IMPORTANT: For 265V units, if a power cord is selected, it must plug into the 265V subbase accessory.
Be sure that your outlet matches the appropriate blade conguration of the plug and that it is within reach of the service cord.All
wiring, including installation of the receptacle, must be in accordance with the NEC and local codes, ordinances and regulations.
National codes require the use of an arc fault or leakage current detection device on all 208/230V power cords. Be sure to select
the correct cord for your installation.
ALL UNITS
Wire Size
Use recommended wire size given in Table 1 and install a single branch circuit.All wiring must comply with local and national codes. All units are designed to operate off ONE single branch circuit only.
NOTE: Use copper conductors only.
Table 1—SUGGESTED BRANCH CIRCUITWIRE SIZES*
NAMEPLATE AMPS
7.0 to 12 14
12.1 to 16 12
16.1 to 24 10
AWG WIRE SIZE
LEGEND
AWG --- American Wire Gauge
* Single circuit from main box.
Based on copper wire at 60°C temperature rating.
Grounding
For safety and protection, the unit is grounded through the service cord plug or through separate ground wire provided on hard wired units. Be sure that the branch circuit or general purpose outlet is grounded.
VOLTAGE SUPPLY
Check voltage supply at outlet. For satisfactory results, the voltage range must always be within the ranges found on the data information plate.
Cord-connected Units
The 250V eld supplied outlet must match the plug for the standard 208/230V units and be within reach of the service cord. The standard cord-connected 265V units require an accessory electrical subbase for operation. Refer to Table 2 for
proper receptacle and fuse type.
Power Cord Protection
The power cord for 230/208v units provide power cord re protection.Unit power automatically disconnects when unsafe condi­tions are detected. Power to the unit can be restored by pressing the reset button on plug head. Upon completion of unit instal-
lation for 230/208V models, an operational check should be performed using the TEST/RESET buttons on the plug head.
NOTE: The 265V models do not incorporate this feature as they require use of the electrical subbase accessory.
Table 2—RECEPTACLES AND FUSE TYPES: 250, 265 VOLTS
RECEPTACLE
AMPS 15 20 30 15 20 30
RATED VOLTS 250 250 250 265 265 265
T I M E --- D E L A Y T Y P E F U S E (or HA CR Circuit Breaker)
LEGEND HACR—Heating, Air Conditioning, Refrigeration * May be used for 15 amp applications
15 20* 30 15 20 30
5
Heat Controller, Inc. OWNER’S MANUAL Packaged Terminal A/C
INSTALLATION
Proper installation is the responsibility of the installer. Product failure due to improper installation is not covered under the Warranty. See the warranty card enclosed with your unit for more details.
CHASSIS INSTALLATION
Units are shipped without a sleeve. In applications where unit is a replacement, it is recommended that a Heat Controller sleeve be used.
These units can retrot General Electric, Amana, Carrier, Trane, Friedrich and many other eld installed sleeves/grilles (be sure outdoor grille is installed on the sleeve). See Table 3 for details. For any sleeve retrot applications, be sure that the foam seals (factory--installed on the tube sheets) provide a good seal be­tween the grille and outdoor coil tube sheets. These foam seals provide a barrier to separate outdoor coil leaving air from mixing with the outdoor incoming air (known as air recirculation).
Table 3—Retrot Wall Sleeves
CAUTION
!
UNIT DAMAGE AND/OR OPERATION HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
For retrot applications, foam seals on outdoor coil tube
sheets must make a seal between the coil and the grille or loss of performance and premature damage to the major components can result.
Manufacturer Wall Sleeve Part Number
General Electric
Carrier
Amana
Trane
Friedrich
* FR-SLEEVE-EXT accessory is required for retrot into Friedrich (T -Series)
wall sleeves.
Metal Sleeve RAB71
Plastic Sleeve RAB77
Metal Sleeve SLEEVE-STEEL-1PK
Plastic Sleeve SLEEVE-INSUL-1PK
Metal Sleeve WS900B
Metal Sleeve SLV149
T---Series Metal 111/2---in. Deep Wall
Sleeve*
Standard Depth Wall Sleeve
16 X 42 X 133/4---in. PXWS
INDOOR-AIR INLET FILTERS
FRONT
PANEL
DISCHARGE GRILLE
WIRE SCREEN
OUTDOOR ORIFICE
COIL SHEETS
INDOOR COIL
Fig. 4—Unit Components
TUBE
BASEPAN
ACCESSOR
WALL
SLEEVE
ACCESSOR
OUTDOOR
Y
Y
GRILLE
6
Packaged Terminal A/C OWNER’S MANUAL Heat Controller, Inc.
RETROFIT SLEEVE PREPARATION
IMPORTANT: Inspect wall sleeve thoroughly prior to installation. Manufacturer does not assume responsibility for costs
or damages due to defects in sleeve or for improper installation.
WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Disconnect all power to unit to avoid possible electrical shock during installation.
NOTE: See installation instructions included with wall sleeve for information on installation.
NOTE: Wall sleeves with a depth of 13.75” to 13.88” can be
used in combination with competitive grilles.
7
Heat Controller, Inc. OWNER’S MANUAL Packaged Terminal A/C
INSTALL UNIT INTO WALL SLEEVE
1. Carefully remove shipping tape from the front panel and vent door. See Fig. 5.
2. Remove shipping screw from the vent door, if present. See Fig. 6.
3. Remove front panel. See Fig. 7.
4. Lift unit level and slide unit into wall sleeve until foam seal rests rmly against front of wall sleeve.
5. Secure with four screws (supplied) through the unit ange holes. See Fig. 8.
6. Reinstall front panel. See Fig. 9.
CAUTION
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Failure to remove shipping tape and screw will prevent fresh air vent door from opening and may result in damage to vent door cable
Shipping
tape
Fig. 5—Shipping Tape Location
6
Remove shipping screw if present
Pull out at the bottom to release it from the tabs (1). Then lift up (2).
Fig. 7—Removing Front Panel
Fig. 8—Securing Unit
Place tabs over top rail (1). Push Inward at bottom until panel snaps into place (2).
Fig. 9—Replacing Front Panel
8
Packaged Terminal A/C OWNER’S MANUAL Heat Controller, Inc.
r
HOW TO CONNECT
IMPORTANT: Please read following electrical safety data carefully.
WARNING
!
ELECTRICAL SHOCK AND/OR UNIT OPERATION AND DAMAGE HAZARD
Failure to follow this warning could result in personal injury or death and/or unit operation and damage.
• Follow the National Electrical Code (NEC) or local codes and ordinances.
For personal safety, this unit MUST BE properly grounded.
• Protective devices (fuses or circuit breakers) acceptable for unit installations are specied on the nameplate of each unit.
Do not use an extension cord with this unit.
• Aluminum building wiring may present special problems -- consult a qualied electrician.
When unit is in STOP position, there is still voltage to electrical controls.
Disconnect power to unit before servicing by:
1. Removing power cord (if it has one) from wall receptacle.
2. Removing branch circuit fuses or turning circuit breakers off at panel.
1. Remove front panel. See Fig. 7.
2. Remove junction box.
• Remove junction box cover by removing three screws from front. Remove junction box by taking out top, rear and side
screws. See Fig. 10.
3. Connect accessory power supply cord or hard wire connector to unit connector. See Fig. 11.
Units must be installed using the appropriate power supply kit. See Table 4—POWER CONNECTION CHART. These connections must be followed.
4. Reinstall junction box and cover. S Use wire clamp to attach power cord to basepan. Secure with screws (included) See Fig. 12. S Relace junction box and cover with screws removed from Step 2. Tighten securely.
5. Replace front panel. See Fig. 9.
6. Connect power to unit.
Junction box cover
Junction box
Fig. 10—Junction Box Location
Fig. 12—Wire Clamp
Unit connecto
Wire clamp
Accessory Power Supply Cord or Hard Wire
Fig. 11—Power Connection
Table 4—Power Connection Chart
CODE OF POWER SUPPLY KIT
UNIT MODEL
EKTC07-1G
EKTH07-1G
EKTC09-1G
EKTH09-1G
EKTC12-1G
EKTH12-1G
EKTC15-1G
EKTH15-1G
EKTC07-2G
EKTH07-2G
EKTC09-2G
EKTH09-2G
EKTC12-2G
EKTH12-2G
EKTC15-2G
EKTH15-2G
* Using 30A on these units could result in damage to your unit.
30A 20A 15A
230/208 VOLT
N/A*
7602-530A-230
265 VOLT
N/A*
7602-530A-265
230/208 VOLT
7602-520A-230
265 VOLT
7602-520A-265
230/208 VOLT
7602-515A-230
265 VOLT
7602-515A-265
9
Heat Controller, Inc. OWNER’S MANUAL Packaged Terminal A/C
SYSTEM CONFIGURATION
VENTILATION CONTROL
The ventilation control lever is located at left side of unit, behind front panel.
NOTE: The vent door shipping hardware must be removed before using vent control lever. See Installation Instructions.
Vent Control
(Pull lever through label
to operate.)
When set at CLOSE, only the air inside the room is circulated
and ltered.
When set at OPEN, some outdoor air will be drawn into room.
This will reduce heating or cooling efciency.
Energy Tip:Keep the vent control at CLOSE. Room air will
be ltered and circulated.
Fig. 12—Ventilaiton Control Location
ADJUSTING AIR DIRECTION
To adjust air direction from outward (default) to upward:
1. Remove front panel. See Fig. 7.
2. Remove louver screws that hold louver insert in place (from back side of front panel). See Fig. 13.
3. Turn louver insert and rotate 180°. See Fig. 14.
4. Replace louver insert.
5. Replace screws and front panel.
Open
Close
Louver screws
Louver
screws
Fig. 13—Backside of Front Panel
Air discharge upward
Fig. 14—Adjusting Louvers
Air discharge outward (Default)
10
Packaged Terminal A/C OWNER’S MANUAL Heat Controller, Inc.
DIP SWITCHES
Auxiliary dip switch controls are located behind front panel,
through an opening below the control panel. To access, re­move front panel. See Fig. 7.
Dip switches are accessible without opening the control box.
Unit must be powered OFF to effectively change their status.
Factory settings for dip switches will be in the DOWN position. See Table 5—Dip Switch Functions for functions of each dip switch position.
Dip Switches
Dipswitch
Fig. 15—Dip Switches
UP
Down
Freeze guard Setpoint Limit 2 Setpoint Limit 1
Fan CON/CYC for cooling Fan CON/CYC for heating Wall Thermostat enable
Electric heat only (for Heat Pumps)
Fig. 16—Dipswitch Location on Unit
Table 5—DIP SWITCH FUNCTIONS
No, UP DOWN REMARKS DEFAULT
1 Electric Heat Only Heat Pump For Heat Pump unit only. DOWN 2 Wall Thermostat Enable Control Panel Enable DOWN 3 Fan Continuous Run for Heating Fan Cycle for Heat DOWN 4 Fan Cycle for Cool Fan Continuous Run for Cooling DOWN
UP*UP
5*6
7 Freeze Guard Disable Freeze Guard Enable DOWN
68--- 75 _F 20--- 24 _C
d
UP*DOWN
63--- 80 _F
18--- 28 _C
d
DOWN*UP
65--- 78 _F
19--- 26 _C
d
DOWN*DOWN
61--- 86 _F 16--- 30 _C
(full range)
d
Two configurations (5*6) combine to select set point range. Whensetpointlimitset,dis­play always shows full range.
DOWN*DOWN
61--- 86 _F
16--- 30 _C
Electric Heating Only / Emergency Heat (For Heat Pump Units Only)
This setting is typically used for EmergencyHeating.
Wall Thermostat Enable
A wired wall thermostat can be connected to the unit. If it is, this dipswitch must be moved to the Wall Thermostat Enable Position, before the wall thermostat will begin control.
Heat and Cool Fan CON/CYC Dip--switches
Allows the fan to operate in continuous or cycle modes while the unit is in heating or cooling mode (continuous or cycle):
CON (Continuous)
Allows fan to run continuously, circulating air even when the temperature setting has been satised. This switch helps to
maintain the room temperature closer to the thermostat setting.
CYC (Cycle)
This setting allows the fan to cycle on and off with the compressor or electric heater. The fan stops a short time after the temperature
setting is satised.
Setpoint Temperature Limits
Provides a restricted range of temperature control.
Room Freeze Protection
If unit senses a room temperature below 40°F, the fan motor and electric strip heat will turn on and warm the room to 50°F. The fan stops a short time after the temperature is satised.
11
Heat Controller, Inc. OWNER’S MANUAL Packaged Terminal A/C
KEYPAD CONFIGURATION
Allows further conguration of system to desired application such as whether th unit displays in °F or °C, whether the display
shows the set point or room air temperature, and to set controls for sensor biasing. Changes do not take affect until power is cycled on the unit.
To enter Keypad conguration
Cycle power to unit. Press and hold the Fan Speed Button and the COOLER button for 5 continuous seconds, within 30
seconds of the unit being powered up. If the unit has had power for more than 30 continuous seconds, keypad conguration cannot be entered. When keypad conguration mode is rst entered, it will default to Fahrenheit/ Celsius Display Mode.
To scroll through the Keypad Conguration Options
Press and release the Fan Speed button. The stored value will be displayed.
To modify conguration settings
Press and release the Setpoint Up or Setpoint Down buttons.
To exit Keypad Conguration
Keypad Congurationwill end on its own 30 seconds after the last button press or when the MODE button on the Keypad is
pressed.
Fahrenheit/ Celsius Display Switch:
Change between degrees Fahrenheit and Celsius on the display. An “F” indicates Fahrenheit display and ‘C’ indicates Celsius. Default is degrees “F”.
Indoor Air Temperature Sensor Biasing for Cooling mode:
Sometimes known as an anticipator, the air temperature sensor bias is used to adjust the room air temperature
reading when in cooling mode. (Not normally required.)
Indoor Air Temperature Sensor Biasing forHeating mode:
Sometimes known as an anticipator, the air temperature sensor bias is used to adjust the room air
temperature reading when in heating mode. (Not normally required.)
Indoor Temperature Display:
Change between showing setpoint only on the display during heating and coolingmodes “SP” or displaying room temperature during heating and cooling modes “AA”. “SP” mode is the default mode.
• If “SP” is selected, only the setpoint will be displayed during heating and cooling modes, regardless of what the
real temperature is in the room.
• If “AA” mode is selected, the room temperature will be displayed during heating, cooling and fan only modes.
— If the mode button has been changed to either heating or coolingmodes, setpoint will be displayed for 10 seconds. After the 10 seconds, the room temperature will again be displayed.
— If the on/off button is depressed (when the unit is off) and the last mode was either cooling or heating mode, the setpoint
will be displayed for 10 seconds before displaying room temperature. — During heating and cooling modes, if either the up or down setpoint key is depressed, the display will show the setpoint until 10 seconds after the last up or down key press. Then the room temperature will be displayed again.
12
Packaged Terminal A/C OWNER’S MANUAL Heat Controller, Inc.
OPERATION
ABOUT THE CONTROLS ON YOUR UNIT
NOTE: In case of a power failure, the unit will remember the last programmed settings and will restart to those settings.
IMPORTANT: When unit is rst started, high humidity conditions can cause condensation to form on discharge grille. Keep doors
and windows closed. Room humidity will decrease and moisture will evaporate as the unit operates.
TEMP CONTROL
Fig. 17 – PTAC CONTROLS
1. TEMP CONTROL
Temp Control is used to maintain room temperature. Compressor will cycle on and off to keep room at the requested level of comfort.
COOLER—Lowers temperature. (Minimum temperature setting is 61°F/16°C) WARMER—Raises temperature. (Maximum temperature setting is 86°F/30°C)
2. FAN SPEED, MODE & ON/OFF FAN SPEED—Set fan operation for HI, MED, or LO speed. MODE-COOL—For cooling MODE-HEAT—For heating
NOTE: If unit is a heat pump, raising the heat setting by 5°F will cause unit to use its electric heating elements for one
cycle in order to reach the new requested temperature quickly.
MODE-FAN—For fan--only operation ON/OFF—Turns the unit on or off.
NOTE: The LED above the ON/OFF button will be green when unit is ON and red when the unit is OFF. All other
LEDs will be off when unit is set to OFF mode. NOTE: Power remains connected to unit even when the unit is in the OFF mode.
FAN, MODE& OPERATION
13
Heat Controller, Inc. OWNER’S MANUAL Packaged Terminal A/C
CARE AND CLEANING
FRONT PANEL AND CASE
Turn unit off and disconnect power supply. To clean, use water and a mild detergent. DO NOT use bleach or abrasives. Some commercial cleaners may damage the plastic parts.
OUTDOOR COIL
Coil on outdoor side of unit should be checked regularly. Unit will need to be removed to inspect dirt build-up that will occur on the inside of the coil. If clogged with dirt or soot, coil should be professionally cleaned.
NOTE: Never use a high-pressure spray on coil.
CAUTION
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Coils
Grille
Clean inside and outside of outdoor coils regularly
Fig. 18—Outdoor Coil
.
BASE PAN
In some installations, dirt or other debris may be blown into unit from outside and settle in base pan (bottom of unit). Check
base pan periodically and clean, if necessary.
AIR FILTERS
IMPORTANT: TURN UNIT OFF BEFORE CLEANING
Airow restriction may cause damage to the unit.
CAUTION
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Do not operate unit without lters in place. If a lter becomes torn or damaged, it should be replaced immediately. Operating without lters in place or with damaged lters will allow dirt and dust to reach indoor coil and reduce cooling, heating, airow and efciency of unit. Airow restriction may cause damage to unit.
Themost important thing you can do to maintain unit efciency is to clean the lters at least every 30 days (or sooner depending on application). Clogged lters reduce cooling, heating and airow.
Keeping lters clean will:
Decrease cost of operation.
Save energy.
Prevent clogging the indoor coil.
Reduce risk of premature component failure.
To Clean Air Filters:
• Vacuum off heavy soil.
• Run water through lters.
Air dry thoroughly before replacing.
Pull up
2 Air filters
Dirty filter-
Needs cleaning
Fig. 19—Identifying Clogged Filter
Push down
Clogged filter -
Greatly reduces cooling,
heating and airflow.
Removing Air Filter
Fig. 20—Removing and Replacing Air Filter
Replacing Air Filter
14
Packaged Terminal A/C OWNER’S MANUAL Heat Controller, Inc.
PREVENTATIVE MAINTENANCE
Preventative maintenance is essential to proper unit operation, efciency and longevity. To ensure equipment operates properly, it must be properlymaintained. Equipment operation should be checked and veried
several times during each year. During regular unit inspection and maintenance, follow the guidelines below:
• Clean both sides of outdoor coil. (Never use high pressure spray on coils.)
• Clean basepan and outdoor vent lter.
• Clean outdoor orice and fan.
• Clean indoor coil. (Never use high pressure spray on coils.)
Clean indoor fan, wire screen and front panel.
• Clean or install new indoor-air inlet lter(s).
Clean wall sleeve and outdoor grille.
Inspect cord and receptacle.
Secure electrical connections.
Ensure front panel is properly mounted and not damaged.
Ensure wall sleeve is installed properly.
Ensure heat and cool cycles operate properly.
15
Heat Controller, Inc. OWNER’S MANUAL Packaged Terminal A/C
TROUBLESHOOTING
TROUBLESHOOTING
POSSIBLE CAUSES SOLUTIONS
UNIT DOES NOT START
Unit may have become unplugged
Fuse may have blown
Circuit breaker may have tripped
Circuit breaker may have been tripped
S Unit may be off or in wall thermostat mode.
Check section on dipswitch settings to verify dipswitches are set properly.
Unit may be in a protection or diagnostic failure
Unit may be in a protection or diagnostic failure
mode. See section on self diagnostics.
mode. See section on Intelligent Self ---checking Control.
UNIT NOT COOLING/HEATING ROOM
Check that plug is plugged securely in wall receptacle.
Note :Plug has a test/reset button on it. Make sure that the plug has not tripped.
Replace the fuse. See Note 1.
Reset circuit breaker. See Note 1.
Turn unit on (bottom right button on keypad).
Note: If the unit turns on, the LED will be green. If the unit is off, the LED will be red. If there is no LED on, there is a problem with power or damage to the control.
Check dipswitch settings
S Unit air discharge section is blocked S Temperature setting is not high or low enough
Note: Setpoint limits may not allow the unit to heat or cool the room to the temperature desired. Check section on dipswitch settings.
S Unit air f ilters are dirty. S Room is excessively hot or cold when unit is started. S Vent door left open S Unit may be in a protection or diagnostic failure
Unit may be in protection or diagnostic failure mode. Check section on self diagnostics.
mode. Check section on Intelligent Self --- checking Control.
Compressor is in time delay mode. There is a protective
S Compressor is in time delay. There is a protective
time delay (approx. 3 minutes) on starting the compressor after a power outage (or restarting after it has been turned off), to prevent tripping of the compressor overload.
DISPLAY HAS STRANGE NUMBERS/CHARACTERS ON IT
UNIT MAKING NOISES Clicking, gurgling and whooshing noises are normal during
WATER DRIPPING OUTSIDE If a drain kit has not been installed, condensation runoff during
WATER DRIPPING INSIDE
Wall sleeve is not installed level Wall sleeve must be installed level for proper drainage of
ICE OR FROST FORMS ON INDOOR COIL
Low outdoor temperature
Dirty filters
S Make sure that curtains, blinds or furniture are not restricting or
blocking unit airflow.
S R eset to a lower or higher temperature setting. S Remove and clean filters. S Allow sufficient amount of time for unit to heat or cool the room.
Start heating or cooling early before outdoor temperature, cooking heat or gatherings of people make room uncomfortable.
S Close vent door. S Check dipswitch settings f or desired comfort.
Wait approximately 3 minutes for compressor to start
The unit may be in a diagnostic condition. Check self diagnostic
The unit may be in a diagnostic condition. Check Intelligent Self ---
section to determine if the unit has had a failure.
checking Control section to determine if unit has had a failure.
The unit may be set for _C (instead of _F), see the keypad configuration section
operation of unit.
very hot and humid weather is normal. See Note 2. If a drain kit has been installed and is connected to a drain system, check gaskets and fittings around drain for leaks and plugs.
condensation. Check that installation is level and make any necessary adjustments.
When outdoor temperature is approximately 55_F or below, frost may form on the indoor coil when unit is in Cooling mode. Switch unit to FAN operation until ice or frost melts.
COMPRESSOR PROTECTION
Power may have cycled, so compressor is in a restart protection.
NOTES:
1. If circuit breaker is tripped or fuse is blown more than once, contact a qualified electrician.
2. If unit is installed where condensation drainage could drip in an undesirable location, an accessory drain kit should be instal led and connected to drain system.
Remove and clean filters.
Random Compressor restart --- Whenever the unit is plugged in,
or power has been restarted, a random compressor restart will occur. After a power outage, the compressor will restart after approximately 3 minutes.
Compressor Protection --- To prevent short cycling of the
compressor, there is a random startup delay of 3 minutes and a minimum compressor run time of 3 minutes.
16
03/2010
Loading...