Heat Controller EKTH, EKTC User Manual

Page 1
HEAT CONTROLLER, INC.
Installation Operation and Maintenance
Packaged Terminal
AC/Heat Pumps
M Series
HEAT CONTROLLER, INC.
1900 Wellworth Ave., Jackson, Michigan 49203 • Ph. 517-787-2100 • Fax 517-787-9341 • www.heatcontroller.com
THE QUALITY LEADER IN CONDITIONING AIR
Page 2
PACKAGE TERMINAL
AIR CONDITIONER/HEAT PUMP
Made in USA
ATTENTION INSTALLING PERSONNEL
As a professional installer you have an obligation to know the product better than the customer. This includes all safety precautions and related items.
Prior to actual installation, thoroughly familiarize yourself with this Instruction Manual. Pay special attention to all safety warnings. Often during installation or repair it is possible to place yourself in a position which is more hazardous than when the unit is in operation.
Remember, it is your responsibility to install the product safely and to know it well enough to be able to instruct a customer in its safe use.
Safety is a matter of common sense...a matter of thinking before acting. Most dealers have a list of specific good safety practices...follow them.
The precautions listed in this Installation Manual are intended as supplemental to existing practices. However, if there is a direct conflict between existing practices and the content of this manual, the precautions listed here take precedence.
Page 3
Contents
Unit Features ........................................................................................... 3
General Information ................................................................................ 5
Installation Instructions.......................................................................... 6
Wiring ....................................................................................................... 8
Operating Instructions............................................................................ 9
Obtaining Service.................................................................................. 16
Normal Operating Sounds and Conditions ........................................ 17
Configuration Settings ......................................................................... 17
RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION.
IMPORTANT NOTE TO THE OWNER
This equipment is to be serviced by professionally trained personnel only. If this equipment is improperly installed, adjusted or altered by an unqualified person, a safety hazard may result.
IMPORTANT NOTE TO THE SERVICER
Read this manual and familiarize yourself with the specific items which must be adhered to before attempting to service this unit. The precautions listed in this Installation Manual are intended as supplemental to existing practices. However, if there is a direct conflict between existing practices and the content of this manual, the precautions listed here take precedence.
Your warranty certificate is also supplied with the unit. Read the warranty carefully and note what is covered. Keep the warranty certificate in a safe place, so you can find it, if necessary.
Before using this manual, check the serial plate for proper model identification.
THE INSTALLATION AND SERVICING OF THIS EQUIPMENT MUST BE PERFORMED BY QUALIFIED,
EXPERIENCED TECHNICIANS ONLY.
Due to policy of continual product improvement, the right is reserved to change
specifications and design without notice.
2
Page 4
Unit Features
This unit has many features which are different than those found on conventional PTAC units. The servicer must be familiar with these features in order to properly service the unit.
LCDI or AFCI Power Cords - Underwrites Laboratories and the National Electric Code (NEC) now require power cords that sense current leakage and can open the electrical circuit to the unit on units rated at 250 volts or less. In the event that unit does not operate, check the reset button located on or near the head of the power cord as part of the normal troubleshooting procedure.
LCDI power Cord
Automatic 3-minute compressor lockout - Af ter the compres­sor cycles off, it will not restart for three minutes.
Automatic 2 falls to 4°F below the set point temperature, the reverse cycle heat is shut off and the electric strip heat is turned on.
Automatic freeze protection - Whenever power is supplied to the unit and the master switch is in the ON position, automatic freeze protection is active. If the unit senses temperature below 40°F, the fan motor and electric strip heat are turned on. Freeze protection can be turned off, if required.
Random restart delay - To help eliminate power surges after a power outage, the unit is equipped with a two to four minute random restart delay feature. Whenever the unit is plugged in with the master switch turned on and the mode switch set in the cool or heat mode, a random restart will occur. A random restart condition can be avoided by setting the mode switch in the fan only or off position before applying power to the unit.
Fuse holder - On all 265 volt units, fuse holders are factory in­stalled. Check for blown fuse if unit does not operate. Fuse holder is located behind the front. Replacement fuses may be purchased from the Parts Department or contact your sales rep­resentative for part numbers.
nd
stage electric heat - If the room temperature
Indication LEDs - The touch pad has LEDs that corre­spond to fan operation and to indicate unit status. The LEDs next to the selections OFF, COOL, and HEAT in­dicate which operational mode is active. The LED lo­cated in the lower left corner is a status LED. This LED indicates the status of the unit. See Diagnostic Mainte- nance & Status Report section for further details.
Status LED
Touch Pad
Load shedding - An LS terminal has been added for load shedding operations. If at any time a switch is closed between the LS and IN terminals, the compres­sor and electric heater will lockout until the switch is opened.
Transfer fan - Terminals TF(-) and TF(+) on the low voltage terminal board allow for an external (transfer) fan connection. A user-supplied relay is required and, depending upon the type used, an approved external transformer kit may be required for installation.
NOTE: The PTAC Wire Harness Kit (PWHK01C) is required when using either the transfer fan or load shedding option.
Front mounting hole - A mounting hole is provided to give the owner the option of securing the front to the chassis. The mounting hole is located behind the air intake grille. The owner must supply one 1/2 inch long #8 sheet metal screw per unit. The screw must be re­moved before the front can be removed.
FUSE
HOLDERS
Front Mounting
Hole
Control Panel
Chassis Front
3
Page 5
Unit Features
Energy Management System Features Temperature Setback - This option can save energy dollars
for unrented or unoccupied rooms by automatically setting back the operational temperatures. This mode of operation is selected through the configuration routine (see Configu- ration Settings section). If none of the keys on the control pad have been pressed for an 18-hour period. The unit will automatically go into a 3-stage setback routine; after 30 minutes, a 1 degrees setback; after 3 hours, 3 degrees, and at 8 hours, a 7-degree setback. NOTE: Temperature set­back does not work with a wired remote thermostat .
Door Switch and Motion Sensor Low Voltage Terminals (DS1, DS2, MS1, MS2) - The door switch and motion sen­sor operate as a unit, the door switch terminals allows for wired connection of a door sensor to the control board. The motion sensor interprets any door movement as a signal of occupancy . If the switch between DS1 and DS2 is closed, the door control will interpret the room door as closed. If the switch between MS1 and MS2 terminals is opened (or closed if unit is configured for normally open) the control will interpret the action as a signal of occupancy. If thirty min­utes pass without any door activity, Energy Management Temperature setback activates.
Serial Port Interfaces - Two serial ports located on the con­trol board provide easy access for two-way communications to the control board from handheld PDA devices. An op­tional RF antennae can be attached for wireless communi­cations.
4
Page 6
TRANSPORTATION DAMAGE
All units are securely packed in shipping containers tested according to International Safe Transit Association specifications. The carton must be checked upon arrival for external damage. If damage is found, a written request for inspection by the carrier’s agent must be made immediately.
In the event of damage, the consignee must:
1. Make notation on delivery receipt of any visible damage to shipment or container.
2. Notify carrier promptly and request an inspection.
3. In case of concealed damage, carrier should be notified as soon as possible—preferably within 5 days.
4. File the claim with the following supporting documents within the 6 month statute of limitations. a. Original Bill of Lading, certified copy, or indemnity bond. b. Original paid freight bill or indemnity in lieu thereof. c. Original invoice or certified copy thereof, showing trade and other discounts or reductions. d. Copy of the inspection report issued by carrier’s representative at the time damage is reported to the carrier.
The carrier is responsible for making prompt inspection of damage and for a thorough investigation of each claim. The distributor or manufacturer will not accept claims from dealers for transportation damage.
UNIT ACCESSORIES
This unit is designed for through-the-wall installation in new or existing buildings. To complete the installation of this PTAC, an insulated wall sleeve and an outdoor grille (either the stamped aluminum grille or the architectural grille) are required.
The chassis and the cabinet front are shipped in one carton.
5
Page 7
Installation Instructions
r
To ensure that the unit operates safely and efficiently, it must be installed, operated and maintained according to these installation and operating instructions and all local codes and ordinances or, in their absence, with the latest edition of the National Electric Code. The proper installation of this unit is described in the following sections. Following the steps in the order presented should ensure proper installation.
WARNING
T
O PREVENT PROPERTY DAMAGE, PERSONAL INJURY OR DEATH DUE TO
ELECTRICAL SHOCK, YOU MUST:
AKE SURE THE ELECTRICAL ACCESSORIES ARE INSTALLED
M
PRE-DRIL LED MOUNTING HOLES.
AKE SURE THE ELECTRICAL WIRING IS NOT INSTALLED AND DOES NOT
M
BELOW
HANG BASE PAN.
THE PRE-DRILLED MOUNTING HOLES OR LIE IN THE UNIT
ONLY
IN THE
SLEEVE STIFFENER AND REAR CLOSURE PANEL REMOVAL
Before the chassis can be installed in the wall sleeve, the sleeve stiffener and the rear closure panel must be removed.
1. Remove the zigzag folded cardboard sleeve stiffener.
2. Remove the rear closure panel by folding the four flaps.
3. Grasping the top and bottom flanges of the rear closure panel
pull the entire panel out diagonally from one side.
DRAIN KIT INSTALLATION (Optional Accessory)
During normal reverse cycle heating operation, condensate water will drain out of the rear of the wall sleeve. If this water is objectionable, a drain kit should be installed. The drain kit has provisions for draining the water from either the right or left side of the sleeve externally or from the bottom of the sleeve inter­nally. The drain kit must be installed before the outdoor grille is installed. Refer to the Installation Instructions supplied with the drain kit for a complete description of the installation procedure.
Rear Closure
Panel
Flaps
Stiffener Removal
Rear Enclosure Panel Removal
Sleeve
Stiffene
Wall Sleeve with Stiffener
6
Page 8
Installation Instructions
SLEEVE INSTALLATION
In order for condensate water to drain properly inside the unit, the sleeve must be installed properly:
• Level from right to left.
• A slight downward pitch from the indoor side to the outdoor side as shown below.
Refer to the Installation Instructions supplied with the PTAC wall sleeve for a complete description of the installation procedure.
OutsideInside
Wall
Sleeve
Level
1/4 Bubble
Tilt To
Outside
Outside
Wall
Proper Sleeve Tilt
OUTDOOR GRILLE
2. Pull the bottom of the cabinet front away from the chassis until the retaining clips disengage. NOTE: If front is secured with screws, remove front mounting screw, then follow front re­moval procedure.
Cabinet Front Removal View 2
Front Mounting
Hole
An outside grille must be installed to direct air flow for proper unit operation and also protect the outdoor coil. The grille must be installed before installing the chassis. Refer to the Installation Instructions supplied with the outdoor grille kit for a complete description of the installation procedure.
This model requires either a Stamped Grille Kit (Model SGK--B), a Polymer Grille Kit (Model PGK) or an Architectural Grille Kit (Model AGK--B). When replacing an old chassis with an existing grille or using a specialized grille in a new installation, please check with your sales representative to determine if the new chassis should be used with the non-standard specialized grille. An improper outdoor grille can decrease cooling or heating capacity, increase energy usage and shorten compressor life and possibly void the warranty.
FRONT REMOVAL
1. Grasp the cabinet front.
`
Front Mounting Screw
3. Lift the cabinet front off the chassis. Reverse this procedure to reinstall the cabinet front.
CHASSIS INSTALLATION
1. Remove the cabinet front from the chassis as described in Front Removal.
2. Insert the chassis into the wall sleeve.
Wall Sleeve
Chassis
Slide Chassis In
Outside
Wall
Chassis Installation View 1
Cabinet Front Removal View 1
3. Slide the chassis into the wall sleeve until the chassis flanges contact the front edge of the wall sleeve.
7
Page 9
Installation Instructions
Screws
Wall Sleeve
(3 on each
side of unit)
Chassis
Chassis Installation View 2
Outside
Wall
4. Secure the chassis to the wall sleeve using three screws on each side of the chassis to ensure a proper seal between the chassis and the wall sleeve. The screws are supplied in a plastic bag attached to the power cord.
IMPORTANT NOTES:
1. The unit is equipped with a rubber grommet mounted com­pressor. These grommets are factory set and require no ad­justment.
2. If a standard subbase is used, be sure the right hand subbase cover is removed before the chassis is installed in the sleeve.
3. On 230V,30A units installed with an existing subbase, use the subbase cover extension kit.
4. Check the indoor and outdoor grilles for obstructions to air flow. The unit must be located where curtains, furniture, trees, or other objects do not block the air flow to and from the unit. If air is obstructed and/or deflected back into the unit, the air conditioner compressor may cycle on and off rapidly. This could damage the compressor or possibly void the warranty.
Wiring
WARNING
T
O AVOID PROPERTY DAMAGE, PERSONAL INJURY OR DEATH DUE TO ELECTRICAL SHOCK, DO NOT SERVICE THIS UNIT WITHOUT FIRST SHUTTING OFF POWER TO THE UNIT FROM THE CIRCUIT BREAKER AND/OR REMOVING THE UNIT CORD SET PLUG FROM THE WALL OUTLET.
CAUTION
O AVOID PROPERTY DAMAGE, PERSONAL INURY OR DEATH DUE TO
T
ELECTRICAL SHOCK, DO NOT USE AN EXTENSION CORD WITH THIS UNIT.
CAUTION
O AVOID THE RISK OF PROPERTY DAMAGE, PERSONAL INURY OR FIRE,
T
USE ONLY COPPER CONDUCTORS.
CAUTION
O AVOID THE RISK OF PERSONAL INURY, WIRING TO THE UNIT MUST BE
T
PROPERLY POLARIZED AND GROUNDED.
Cord connection to a wall socket is not permitted for 265-volt units. All 265-volt units must be hard wired using the hard wire kit or make use of the plug-in receptacle in the standard subbase.
230/208V and 115V units are equipped with LCDI or AFCI power cords and can open the electrical circuit to the unit. In the event the unit does not operate, check the reset button located on or near the head of the power cord as part of the normal trouble­shooting procedure.
WARNING
T
HIS AIR CONDITIONER IS NOT MEANT TO PROVIDE UNATTENDED COOLING OR LIFE SUPPORT FOR PERSONS OR ANIMALS WHO ARE UNABLE TO REACT TO THE FAILURE OF THIS PRODUCT.
T
HE FAILURE OF AN UNATTENDED AIR CONDITIONER MAY RESULT IN EXTREME HEAT IN THE CONDITIONED SPACE CAUSING OVERHEATING OR DEATH OF PERSONS OR ANIMALS.
P
RECAUTIONS MUST BE TAKEN TO WARN OFF OR GUARD AGAINST SUCH AN OCCURRENCE.
PTAC WIRE HARNESS KIT (PWHK01C)
See PTAC Wire Harness Kit Installation Instructions for proper wire orientation and location for low voltage wiring.
HEATERLESS UNITS
If a heaterless unit is ordered, field provisions must be made for adding supplemental heat. Refer to the Installation Instructions supplied with the heater kit for a complete description of the installation procedures. All 208/230 volt heaterless units are shipped with a 15 Amp power cord and all heaterless 265 volt units are shipped with a 20 Amp power cord.
When adding a heater kit to a heatless unit, the power cord supplied with the heater kit must be used in place of the power cord supplied with the unit. Table 1 specifies power cord rating requirements for the various heater kits.
8
Page 10
Wiring
Power Cord Requirements
230/208 Volt Units 265 Volt Units
Heater Size
(kW )
Power Cord
Rating (amp)
Power Cord
Rating (amp)
1.5 15 20
2.5 15 20
3.5 20 Not Applicable
3.7 Not Applicable 20
5.0 30 30
Table 1 - Power Cord Requirements
NOTE: Heaterless units are shipped with an auxiliary data label
on the front side of the mid-partition panel. If an electric heater kit is field installed, the installer must mark the appropriate box on the label to indicate the electric heater capacity. If no heater is installed, the box labeled “None” must be marked. Refer to the unit nameplate for over current protection data.
VOLTAGE MEASUREMENTS
Once the unit is properly wired, measure the unit supply voltage. Voltage must fall within the voltage utilization range given in Table 2.
Operating Voltage
Unit Voltage
Voltage Utilization Range
Rating Minimum Maximum
230/208 197 253
265 238 292 115 103.5 126.5
Table 2 - Operating Voltage
Operating Instructions
USERS CONTROLS
A six button touch key pad located behind the control door controls both temperature and operation mode. The key pads can be used alone or in combination.
THERMOSTAT SETTING
Pressing the COOL thermostat control and the up or down arrows will provide a cooler room temperature, respectively. Pressing the HEAT thermostat control and the up or down arrow keys will provide a warmer room temperature.
LCDI OR AFCI POWER CORD
230/208V and 115V units are equipped with LCDI or AFCI power cords and can open the electrical circuit to the unit. In the event the unit does not operate, check the reset button located on or near the head of the power cord as part of the normal trouble­shooting procedure.
Fan Operation HIGH or LOW with HEAT or COOL mode selected
- The selected fan speed shall run in the selected speed. Fan Operation AUTO with HEAT or COOL mode selected - The
fan will run in low and high speed. The changes in fan speed are automatic.
DIAGNOSTIC LIGHT
The green diagnostic light located in the lower left hand corner of the touchpad and indicates operation warnings. This light usually indicates that either the filter or coils need cleaning. Please refer to the Maintenance and Cleaning section for the proper cleaning procedure. If this light is still on after cleaning, please refer to the Diagnostic & Status Report section for assistance.
FAN SPEED
The fan speed touch key will deliver high, low or auto fan speed to circulate room air. NOTE: The AUTO selection will not be available if a fan speed is selected without COOL or Heat selection.
Status LE D
User Controls
9
Page 11
g
Operating Instructions
SW2
M1
ON / OFF
MASTER SWITCH
P10
COM A COM B
P11
DS1 DS2 MS1 MS2 EH IN LS FD1 F D2 TF- TF+ C R GL W2 Y/W1 B GH
P12
Control Board User Inputs*
*NOTE: The PTAC Wire Harness Kit (PWHK01C) is required for the auxiliary or remote thermostat options.
ADDITIONAL CONTROL INPUTS
The control inputs shown above provide additional unit control and features. To access these control inputs, the cabinet front must be removed (see Front Removal).
MASTER SWITCH
The master switch disconnects power to all of the system components. When this switch is in the off position, the compres­sor, fan motor, reversing valve, and electric resistance heater will all be de-energized.
WARNING
T
O PREVENT PROPERTY DAMAGE, PERSONAL INJURY OR DEATH DUE TO ELECTRIC SHOCK, UNPLUG THE UNIT AT THE WALL OUTLET OR TURN OFF POWER AT THE FUSE BOX OR CIRCUIT BREAKER BEFORE SERVICING THE
L
INE VOLTAGE WILL BE PRESENT AT THE CONTROL BOARD, TERMINALS
UNIT.
1 AND L2, WHENEVER POWER IS APPLIED TO THE UNIT REGARDLESS OF
L
THE MASTER SWITCH POSITION.
REMOTE THERMOSTATAUXILIARY
P13
IAT
BLACK
M2
installation of a front desk switch. The following figure shows a wiring schematic for connecting the front desk switch to the unit.
If the unit is configured for wired unrented setback energy management (see Configuration Settings section c2), EH and IN terminals are used instead of FD1 and FD2. If EH and IN are shorted, the unit will go into setback temperatures for cooling and heating as configured in c3 and c4 (see Configuration Settings). Unit operation will be disabled. “Fd” (see Diagnostic Codes) will appear on the display. This allows the room to quickly recover to a comfortable temperature when the room is occupied.
Maximum Wire
th
Len
Wire Size
(AWG)
Maximum Le ngth
Allowed #24 400 ft #22 600 ft #20 900 ft #18 1500 ft #16 2000 ft
REMOTE CONTROL INPUTS
The C, R, GL, W2, Y/W1, B/O, and GH terminals provide control inputs for a “manufacturer-approved” remote wall mounted thermostat. The “B” terminal can be configured to become “O” if needed see Configuration Settings For remote control thermostat operation, refer to the Remote Thermostat Operation section.
FRONT DESK CONTROL (FD1, FD2, EH, IN)
The FD1, FD2, EH and IN terminals provide control inputs for a front desk switch. Shorting across the FD1 and FD2 terminals will disable unit operation. The only control function which will remain active when these terminals are shorted is freeze protec­tion. Any switch which will produce a short circuit across these two terminals can be used as a front desk switch. The contact resistance of the switch, when closed, must be less than 200 ohms for the front desk feature to operate properly. Table 3 shows the maximum wire length and corresponding gage size for
10
Table 3 - Maximum Wire Length for
Front Desk Switch
DS1 DS2 MS1 MS2 EH IN LS FD1 FD2 TF- TF+ C R GL W2 Y/W1 B GH
REMOTE THERMOSTATAUXILIARY
FRONT DESK SWITCH
BLACK
Front Desk Switch Wiring Schematic
M2
IAT
Page 12
Operating Instructions
No holes are permitted in chassis basep an or wallsleeve when routing low voltage wire. Route the low voltage wires through the indention on the front of the basepan.
Low Voltage Wires Routing
VENT CONTROL
The vent control allows outside air to be drawn into the condi­tioned area. This outside air can provide ventilation when the blower is operating, but it will increase the heating or cooling load and operating costs.
To obtain access to the vent control:
1. Remove the cabinet front (see Front Removal).
2. Remove the shipping screw (if installed) from the vent door.
3. Remove the label (if present) from over the vent control lever on the left side of the chassis. Remove the vent door ship­ping screw.
Vent Open
Vent Closed
Vent Door Lever Positions
Hydronic Heat Installations
To avoid the risk of freezing the steam or water coil during prolonged shut down periods, the vent door must be left closed when the outdoor temperature might fall below freezing.
AIR DISCHARGE GRILLE
The discharge grille can be adjusted to expel air at either a 15° or 40° angle.
15° Discharge
Angle
40° Discharge
Angle
Discharge Grille Orientation Options
Label
Vent
Control
Lever
Vent Control
Vent Door Shipping Screw
Vent Control Lever
4. Rotate the vent control lever to either open or close the damper.
Use the following procedure to change the angle of the discharge air flow:
1. Remove the front cabinet (see Front Removal).
2. Position the front so that the backside is accessible (see fig­ure below).
Discharge Air Flow
11
Page 13
Operating Instructions
3. Remove the four (4) nuts which secure the discharge air grille to the cabinet front.
Discharge Air Flow Grille Removal
4. Rotate the grille 180° clockwise.
5. Reinstall the nuts securing the discharge air grille to the cabi­net front. Reinstall the cabinet front on the unit.
REMOTE THERMOSTAT
To operate this unit with a “manufacturer-approved” remote thermostat, configure the control to be operated by the remote thermostat. Enter configuration mode C1 and then select option Code L5 (see Configuration Settings in back of manual). When in the remote mode, the unit will only respond to the thermostat inputs (terminal strip positions GL (or GH), W2, Y/W1, and B* shown in “Control Board User Inputs” illustration). NOTE: Once configuration C1 with option code L5 has been selected, the control touchpad will no longer accept inputs other than configu­ration and diagnostics modes. The room occupant must operate the unit at the remote mounted thermostat.
NOTE: In remote mode, the 3-minute compressor time delay, the random restart feature and the freeze protection feature are all active (see Unit Features section).
THERMOSTAT LOCATION
This unit is designed to be operated with remote wall mounted thermostats. For further information on thermostats approved for use with this unit, contact your sales representative.
For best performance results, the thermostat should be located approximately five feet above the floor on a vibration free, inside wall in an area with good air circulation.
Do not install the thermostat where it may be affected by the following:
• Dead spots behind doors, in corners or under cabinets
• Hot or cold drafts from air ducts
• Radiant heat from the sun, appliances, or fireplaces
• Concealed pipes and chimneys
• Unheated (uncooled) areas behind the thermostat, such as an outside walls
Consult the instruction sheet packaged with the thermostat for further details on mounting and operation.
REMOTE THERMOSTAT OPERATION
Approved thermostats vary slightly in construction and, with few exceptions, are operated similarly. The following operational description pertains to approved nonprogrammable thermostats that energize G in Heat and Cool mode.
HEAT/OFF/COOL Switch
• OFF - cooling and heating functions are defeated.
• HEAT - the selected room temperature is maintained by cy­cling either in the heat pump mode or electric strip heat. A PTH unit is switched from the heat pump mode to electric strip heat when the coil temperature is 20°F or when the heat pump cannot keep up with the heating load and a two stage thermostat is used.
• COOL - the selected room temperature is maintained by cycling the air conditioner.
Table 4 summarizes the thermostat input combinations and the respective unit functions. The following wiring schematic illustra­tions show wiring schematics for heat pump and straight cool units with electric resistance heat, respectively.
Heat Pump
Uni t Function
OFF HEAT COOL
*or GH depending on speed required **If configured, B and O can be used interchangeably.
Stage 1 GL*, Y/W1, B**, O GL* Y/W1, B**, or GL*, W2, O Stage 2 GL*, W2 n/a
Thermostat
Input
R Terminal to: R Terminal to:
NONE NONE
GL*, Y/W1, B**, O GL*, Y/W1
Electric Heat
Thermostat
Input
Table 4 - Remote Control Inputs
NOTE: The PTAC Wire Harness Kit (PWHK01C) is required for
remote thermostat options.
ADDITIONAL NOTES:
1. For heat pump operation, a room thermostat with a B** (heat­ing changeover) terminal is required. This will mean that some “auto changeover” thermostats cannot be used, as many of them either do not have a B** terminal, or else energize the B** terminal continuously when in the “auto” position.
2. Additional wiring should be run for future changeover to Heat Pump or thermostat options.
**If configured, B and O input terminals can be used interchangeably.
12
Page 14
g
Operating Instructions
3. Run 6 to 8 wires during initial installation. Tape or cap off any unused wires.
REMOTE THERMOSTATAUXILI ARY
DS1 DS2 MS1 MS2 EH IN LS FD1 FD 2 TF - TF+ C R GL W 2 Y/W1 B GH
Control Board
Connections
X1
O
B**
Y
W1
W2
G*
R
Thermostat
Connections
Wiring Schematic for Straight Cool Unit
*NOTE: For high speed fan operation, connect “G” to “GH”.
REMOTE THERMOSTATAUXILI ARY
DS1 DS2 MS1 MS2 EH IN LS FD1 FD 2 TF - TF+ C R GL W 2 Y/W1 B GH
Control Board
Connections
X1
O
B**
Y
W1
W2
G*
R
Thermostat
Connections
Wiring Schematic for Remote Heat Pump
*NOTE: For high speed fan operation, connect “G” to “GH”.
Table 5 shows the maximum wire length and corresponding gage size for installation of a remote thermostat.
Maximum Wire
th
Len
Wire Size
(AWG)
Maximum Le ngth
Allowed #24 400 ft #22 600 ft #20 900 ft #18 1500 ft #16 2000 ft
Table 5 - Maximum Wire Length for Remote
Control Connection
WARNING
T
O PREVENT PROPERTY DAMAGE, PERSONAL INJURY OR DEATH DUE TO ELECTRIC SHOCK, DISCONNECT THE ELECTRICAL POWER SUPPLY BEFORE CLEANING THIS UNIT.
**If configured, B and O input terminals can be used interchangeably.
13
Page 15
Maintenance and Cleaning
WARNING
T
O AVOID THE RISK OF PROPERTY DAMAGE, ELECTRICAL SHOCK OR PERSONAL INJURY, CLEAN AIR FILTERS AND COILS REGULARLY. OR SEVERLY RESTRICTED FILTERS OR COILS REDUCE AIRFLOW WHICH CAN CAUSE DRASTIC EFFICIENCY LOSS AS WELL AS SEVERE COMPONENT DAMAGE TO COMPRESSORS, ELECTRIC HEATER OR FAN MOTOR. CLOGGED FILTERS AND/OR COILS MAY CREATE A FIRE HAZARD AND WILL VOID THE WARRANTY.
N EXTREM E CASES,
I
WARNING
S
OME LOCAL CONDITIONS AND ENVIRONMENTS CAN CAUSE FUNGI AND OTHER MATERIA L TO GROW INSIDE THE AS WELL AS OTHER FOREIGN MATERIAL, SIMILAR TO DRYER LINT IN YOUR CLOTHES DRYER, ARE FIRE HAZARDS. CLEAN THE UNIT'S COILS, BLOWER WHEEL AND BASEPAN PER THE INSTRUCTIONS CONTAINED IN THIS MANUAL.
UNIT. THIS MATERIAL WHEN DRIED,
PTAC
B
E SURE TO THOROUGHLY CHECK AND
MONTHLY MAINTENANCE AND CLEANING
Intake Air Filter
To properly maintain the operational performance of your PTAC unit, it is extremely important that the inlet air filter be cleaned once per month or more often if operated in dusty or dirty locations or conditions. The intake air filter is constructed of durable polypropylene. The “air intake” air filter can be easily inserted into the cabinet front using the cabinet filter guides. The intake air grille swings out for easy access to the filter. Before cleaning the intake filter, turn the unit off by setting the mode switch to the OFF position. Filter should be cleaned as required.
The following procedure is used to remove the intake filter:
1. Open the intake grille by grasping the top intake louver.
2. Pull the intake grille open.
3. Slide filter upward and remove.
4. Clean filter with vacuum or with running water. Reverse this procedure to reinstall the filter.
NOTE: Available accessory filter kits are FK10B (air intake filter ­10 per pack) and CFK10B (charcoal filter - 10 per pack). The charcoal filters will greatly improve the quality of the air by absorbing odors from tobacco smoke, mold, mildew, etc. Both filters are permanent and cleanable. Contact your sales person for details.
LOGGED
C
`
Intake Filter Removal
Vent Screen
Before cleaning the vent screen, disconnect power to the unit by unplugging the power cord at the wall outlet or subbase, or disconnect power at the fuse box or circuit breaker. If unit is operated with vent door closed, the vent screen does not need to be cleaned.
1. Remove the cabinet front as described in Front Removal.
2. Remove the six screws securing the chassis to the wall sleeve.
3. Slide the chassis out of the wall sleeve far enough so that the vent screen is accessible.
4. Remove the three screws securing the vent mesh screen to the partition panel.
5. Clean and replace the vent screen, slide the chassis back into the wall sleeve, secure it in place with six screws and reinstall the front cabinet.
14
Vent - (Left Side Unit)
Page 16
Maintenance and Cleaning
Cabinet Front
The cabinet front and discharge air grille can be cleaned with a water dampened cloth . Under no circumstances should hydro­carbon-based cleaners (e.g. acetone, benzene, naphtha gaso­line, etc.) be used to clean the front or air grilles. Use care when cleaning the control area.
YEARLY MAINTENANCE AND CLEANING
NOTE: Use a mild biodegradable detergent such as Simple
Green when cleaning the unit. Special care must be taken to protect the unit’s control board and other electrical components from getting any water on them while cleaning. The use of harsh or caustic cleaning agents or materials such as bleach or coil cleaners that are not designed for PTAC products will cause damage or deterioration of the aluminum fin or coil material and is not recommended. Care must be taken not to bend the aluminum fin stock.
Routine Scheduled Maintenance
To achieve continuing top performance and high efficiency, establish a “once a year” cleaning/inspection schedule for the unit. Take the unit out of the sleeve and thoroughly clean and rinse. Be sure to include in the yearly cleaning the evaporator coils, and condenser coils, basepan, and drain passages. Scheduled maintenance can be accomplished by either local maintenance staff or by an authorized servicer. They must follow the instructions described in this manual.
Adverse Operating Conditions Maintenance
Units operating in dusty or corrosive locations; i.e. dusty con­struction site or sea coast, must be cleaned more often. A minimum of four (4) times a year will maintain proper operational conditions and protect unit components.
Wall Sleeve
Clean the wall sleeve while cleaning the unit. The caulking around the sleeve should be checked to make sure that any potential air and water openings around the sleeve are properly sealed. The wall sleeve’s level should also be rechecked. Proper leveling for most installations are a ¼ bubble tilt to the outside and level from right to left. Contact your sales person for detailed maintenance or cleaning instructions.
Basepan and Condenser Coil
CAUTION
O NOT USE COMMERCIAL GRADE COIL CLEANERS. SOME OF THESE
D
CLEANERS MAY CONTAIN WHICH CAN SHORTEN THE LIFE OF THE CONDENSER COIL.
THYLENE DIAMINE TETRACETIC ACID (
E
EDTA
Before cleaning the basepan and condenser coil, turn OFF unit mode switch and disconnect power to the unit. To disconnect power, either unplug the power cord at the wall outlet or subbase, or disconnect power at the fuse box or circuit breaker.
1. Create a water-tight seal by tightly covering the entire control panel area and fan motor with plastic. Creating this seal pre­vents water from entering the control area or the fan motor and damaging the unit.
2. Spray condenser coil and basepan down with water. Next spray a mild biodegradable detergent such as Simple Green onto the condenser coil and basepan. Let set for five (5) minutes.
3. Rinse condenser coil and basepan with water again. NOTE: Ensure water pressure is no higher than that of an ordinary garden hose and the water temperature no higher than 120°F.
4. Tilt the non-compressor side of the unit up no higher than 45 degrees and allow water to drain out the other side of the unit.
5. Remove excess water left in the basepan by wiping the basepan with a dry cloth.
6. Remove the water-tight seal from the motor and control panel area.
7. Reinstall unit back into wall sleeve.
8. Allow unit to dry for 24 hours before reapplying power. When power is reapplied test unit for proper operation.
9. Place a non-acidic algaecide in the basepan to inhibit bacteria growth. Ensure the algaecide is compatible with wet coil op­eration and is not corrosive to the coil.
CAUTION
IGH PRESSURE AND HIGH TEMPERATURE CLEANING IS NOT RECOMMENDED.
H
OING SO COULD DAMAGE THE ALUMINUM FIN STOCK AND ELECTRICAL
D
COMPONENTS.
Clearance Check
Clearances around the unit should also be checked to make sure that the intake air and discharge air paths have not become blocked or restricted. A minimum of eight inches clearance is needed from unit to furniture , beds, or other objects for proper operation. Restricted discharge or intake air will reduce the unit’s operational performance. In severe airflow restrictions damage can occur to unit components such as the compressor, electric heater or fan motor.
)
15
Page 17
Obtaining Service
In the event this unit requires repair or servicing beyond what is covered in this manual, contact an authorized service organization.
To obtain an authorized servicer, contact your sales representative or agency.
Normal Operating Sounds and Conditions
Water trickling sounds
Water is picked up and distributed over the coil. This improves the efficiency and helps with water removal.
Water dripping
Water will collect in the base pan during high humidity days. This can cause overflow and drip from the outside of the unit.
Air sounds
The fan cycle switch sets the operational mode of the fan in the ON position. The fan will run continuously whenever power is applied in this mode. In the AUTO position, the fan will cycle on and off with the compressor or electric heater.
Starting delay
You may notice a few minutes delay in the starting if you try to restart the unit too soon after turning it off or if you adjust the thermostat right after the compressor has shut off. This is due to a built in delay to protect the compressor.
16
Page 18
Configuration Settings
t
e
The control can be configured to operate a wide range of options. The options listed below with the * are the factory default settings. If these are acceptable, then the unit does not require any additional configuration and is fully operable. To configure the unit, first
select the configuration feature code setting and then an option code to change from the factory default setting. To enter configuration feature mode:
1. Press and continue to hold the up and down
arrow keys and quickly press the OFF key twice within a two (2) sec-
ond time frame. The display will alternate between displaying the feature code C1 and the option code 0 (factory default set-
. The lower right dot on the display will flash. To enter the other option codes for C1 (rE and L5) press either the up or down
ting) arrow key.
To select a configuration feature code other than C1, press the HEAT
key until the desired configuration comes up. To scroll to a previously viewed configuration codes press the COOL key. Once you have scrolled to the correct feature, then to select the option code for your desired configuration, press either the up or
down key
to scroll through the options of the selected feature code.
To exit configuration mode:
1. Press the OFF
key. Configuration feature mode will also exit if no keys are pressed for a period of two (2) minutes. Below are the most common configuration settings. Additional codes are present and may be accessed within this menu. Contact the manufacturer for additional information.
Feature
Code
C1
Interf ac e Usage 0* Unit is only cont r olled by the touc hpa d behin d t he door .
C2 F an O peration
C4 Room Indentif ication f irst two
digits (00 to 99) 00-99 Set first two digits of room identification
C5 Room Identification last two
digit s (00 to 99) 00-99 S et last t wo di gits of room identific ation
C6 Occupancy
C7 Motio n S e nsor Type
C8 Cooling T e mperature Limiting
C9 Heat i ng T emperature Limiting
C0 Reverse Cycle "B" or "O"
selection for thermostat
c1
Wired Unrented Set Backc2
c3 Unrented Cooling T emper ature c4 Unrented Heatin g Temperatur e CA Twinned Unit
Dehum i di ficationCb
CC Dehumidistat call for a drop in temperatur
Cd English/Metric Temperature
CE Freeze Prot ection
Description
* Indicates fact ory default.
Option
Code
Unit is both controlled by a wireless thermostat
rE
and/or the touchpad behi nd the door. Unit is controlled by a wired t hermostat only via
L5
on the l ow voltage terminals. Au* The fan only runs with the call for heating or co oling . On The fan runs continuously except in the OFF posit i on.
0* "No Occupancy " detection devices
1 Wir ed Doo r Switc h and Motion Sensor p r esent
Ent er "No O ccupancy" rout i ne 18 hours after last control
18
selection
1 Normally Closed Device
0* Normally Open Device
60-72 (65*)
74-90 (80*)
60-90 ( 79* ) Select temperatur e between 60 and 90 u nrented c o oling set p oint 60-90 ( 63* ) Select temperatur e between 60 and 90 u nrented hea ting set poin
Select temperature between 60 and 72 for minimum
cooling set poi nt
Select temperature between 74 and 90 for maximum
heati ng set point
8* Mating thermostat has a "B" terminal
0 Mating thermostat ha s an " O" t e r minal
Not us ed
0* Not Active
AActive
0* Not Twinned
5 Twinned (Slave)
0* Not Active
1Active U Active in No occupanc y / Unrented St ate
3-8 3 -8
F* F ahr en heit Scale
C Celsius Scale
1* On
0Off
Description
17
Page 19
Diagnostic Maintenance & Status Report
The Diagnostic Maintenance & Status Report provides detailed information on PTAC control operation and operational status includ­ing present modes, failures, airflow restriction warnings, operating temperatures, and past failures. The lower right hand dot on the center display flashes in this mode. In some cases the green LED located in the lower left hand corner of the touchpad below the OFF key will also be lit. This Green LED “Status Light“ only illuminates if there is an status code that has been activated and should be reviewed. In most cases, this light indicates that the indoor room filter is dirty should be cleaned or replaced. NOTE: Dirty filters cause the unit to consume more energy than normally needed to condition a room. Once the filter has been cleaned or replaced, the LED should go out. If the LED is still illuminated after the filter has been cleaned, activate the Diagnostic and Status mode to view
any active codes. The unit may need additional cleaning or maintenance of the evaporator or condenser coils. Please perform this step before calling a servicer. A servicer should be called only if cleaning the filter or coils does not clear the status code or
the code indicates that servicer should be called.
DIAGNOSTIC STATUS REPORT MODE.
To enter Diagnostic Status Report mode, press and hold the up and down arrows and, while holding, quickly press the COOL key
ACTIVE FAILURES.
• If there are no active failures or lockouts, the display will show a double dash, “- -”. If there is a code listed, see the unit “Diag­nostic Codes” chart for a list of definitions.
OPERATING TEMPERATURES.
• If not in Diagnostic Status Report Mode, enter as instructed above and press the Fan Speed key .
• If already in Diagnostic Status Report mode, press the Fan Speed key. The display will show the temperature of the de­sired set point, SP; the temperature at the wireless thermostat, rL; the indoor ambient temperature behind the filter, IA; the indoor
coil temperature, IC; the indoor discharge air temperature, Id; the outdoor coil temperature, OC; the outdoor ambient tempera­ture, OA; and the spare probe temperature, IH. If any of the probes are not populated the display will show the corresponding failure code.
twice.
PAST FAILURE LOG
• If not in Diagnostic Status Report Mode, enter as instructed above and press the Fan Speed key twice.
• If already in Diagnostic Status Report mode, press the Fan Speed tures, the last 10 failure codes active or past can be requested by pressing the Fan Speed key again. The codes are dis-
played last entry first followed subsequently by each preceding code.
Note that modes F1 and Fd are also displayed in the normal control operation (see “Diagnostic Codes” chart).
To exit Diagnostic Status Report mode, press the OFF key.
key. While the display is showing operating tempera-
18
Page 20
Diagnostic Codes
STATUS DISPLAY
ERROR
SUGGESTED ACTION
FP
Freeze Protection Engaged. The room tempera ture
measured by the wireless remote thermostat or indoor
YN
the room temperature rises above 43°F.
Fd
Front Desk
switch is closed. All outputs are switched off.
YN
Open fron t desk switch to allow occupant unit
operation.
On
Control is configured to respond to a wired thermostat Y N
No action if a wired thermostat is being used.
Otherwise, see Configuration Settings.
Indoor Ambient Thermistor reads outside the range -20°F to 200°F & the wireless thermostat is not communicating to the unit control or
Indoor Ambient Thermistor (IAT) without a wireless remote thermostat reads outside the range -20°F to 200°F.
F2
Configuration Error N N Set C1 Configuration Code to 0 or L5.
F3
Indoor Ambient Thermistor reads outside the range -20°F to 200°F
Y N Replace black Indoor Ambient Thermistor.
F4
Indoor Coil Thermistor either above or below operating tolerances.
N Y Replace Red Indoor Coil Thremistor .
F5
Configuration Error N Y Set C1 Configuration Code to 0 or L5.
F6
Indoor Discharge Thermistor either above or below operating tolerances.
NY
Replace Yellow Indoor Discharge Thermistor.
Fb
Configuration Error N Y Set C1 Configuration Code to 0 or L5.
br
Brown Out Protection enga ged. Power was lost or voltage is low.
N N Check for incoming power at cor rect voltage.
L6
Discharge Air Too Hot. N Y Clean Filter or Remove Air Blockage.
L8
Air Restrict ion in Heating. N Y Clean Filter or Evaporator Coil.
L9
Air Restriction in Cooling. N Y Clean Filter or Evaporator Coil.
LC
Outdoor Coil Thermistor temperature high. N Y
Clean Condensor Coils, Check Fan
fault code. Code will reset after cleaning.
C1
Clean Indoor Coil / Filter. N Y Check for Blocked Indoor Air.
C0
Clean Outdoor Coil. N Y Check for Blocked Outdoor Air.
CODE
M O D
E S
A
I
R
F
L O W
W
A R N
I N G
S
Replace black Indoor Ambient Thermistor or
Wireless Remote Thermostat.
YY
F A
I
L U R
E
S
F1
ambient thermistor active sensor falls below 40°F.
LIGHT
No Action required. This setting will disengage when
19
Page 21
12/06
Design, specifications, performance data and materials subject to change without notice.
1900 Wellworth Ave., Jackson, Michigan 49203 • Ph. 517-787-2100 • Fax 517-787-9341
www.heatcontroller.com
THE QUALITY LEADER IN CONDITIONING AIR
Loading...