Heat Controller DXM2 User Manual

APPLICATION, OPERATION
& MAINTENANCE MANUAL
DXM2 Digital
Heat Pump Controller
Heat Controller, Inc. • 1900 Wellworth Ave. • Jackson, MI 49203 • (517)787-2100 • www.heatcontroller.com
Application, Operation, & Maintenance Manual DXM2 UNIT CONTROLS Heat Controller, Inc.
Table of Contents
DXM2 Physical Dimensions & Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
DXM2 Layout and Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
DXM2 Controls. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
DXM2 Service & Application Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Basic Troubleshooting Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Advanced Troubleshooting and Confi guration Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Troubleshooting Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
DXM2 Wiring Diagram with Motorized Modulating Water Valve - Optional 96B0005N62 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
DXM2 Wiring Diagram (Standard Installation) - 96B0005N56 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Functional Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Performance Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
2
Heat Controller, Inc. DXM2 UNIT CONTROLS Application, Operation, & Maintenance Manual
DXM2 Electronic Heat Pump Controls
DXM2 OVERVIEW
The manufacturer’s next generation control board, DXM2, is the geothermal industry’s fi rst two-way communication.
The DXM2 electronic control is a robust, microprocessor based heat pump controller that is advanced and feature­laden for maximum application fl exibility. The DXM2 Control has relay outputs for Compressor, Compressor Speed, Reversing Valve, Alarm Relay, and 2 confi gurable relays for Fan, Fan Speed, HWG Pump, and Loop Pump, and 2 confi gurable accessory relay outputs. For on board diagnostics, there are 2 LED’s to provide status indication.
There are inputs for safety pressure switches, low temperature protection thermistors, condensate overfl ow sensor, DIP switch selection inputs, thermostat inputs, night setback inputs, and emergency shutdown input. Additional confi gurable temperature sensor inputs are available that may be used for hot water, compressor discharge, leaving air, leaving water, and entering water temperature sensors.
The DXM2 has an RS485 communications port to interface with a communicating thermostat or other compatible controls.
DXM2 Controller Part Number:
17B0002N02 DXM2 Control Board
General Operating Parameters
The following are general operating parameters for the DXM2 Control:
• Operating Environment: -40°F to 176°F and up to 95% relative humidity, non-condensing.
• Storage Environment: -40°F to 185°F and up to 95% relative humidity, non-condensing.
Power Requirements
DXM2 only power draw -
• Normally 8 VA draw at 24VAC
• Maximum 12 VA draw at 24VAC. A dedicated 24VAC, 50-60Hz, 1Ph, 40VA transformer minimum is required for typical WSHP application.
Grounding
The control board must be grounded from one of the C terminals.
Basic Control Features
• Single or two–stage compressor control
• Anti-short cycle protection
• High pressure cut-out
• Loss of charge cut-out
• High and low voltage cut-outs
• Water coil low temperature cut-out
• Air coil low temperature cut-out
• Random start
• Status LED and Fault LED
• Reset lockout at unit or disconnect
• Condensate overfl ow sensor
• Intelligent fault retry
• Test Mode
• Multiple blower confi guration options
• Electric heat outputs
• Accessory water valve connection
Advanced Control Features
• Direct control of ECM blower
• Intelligent hot water generator control
• Two accessory relays confi gurable for multiple applications
• Internal Flow Center output
• Proportional valve output
• Night setback with override capability
• Emergency shutdown capability
• Removable thermostat connector for ease of installation and service
• Accepts conventional heat pump (Y,O) or heat/cool (Y,W) thermostat types
• RS–485 port to interface with a communicating thermostat or other compatible controls
• Boilerless electric heat
• Confi gurable inputs and outputs for advanced functions
Relay and Connection Contact Ratings
The following relays are mounted on the DXM2 Control:
• Compressor Relay: 40VA at 24VAC
• Compressor Speed Relay: 28VA at 24VAC
• Alarm Relay: 28VA at 24VAC
• Reversing Valve: 28VA at 24VAC
• Accessory Relay 1: 28VA at 24VAC
• Accessory Relay 2: 28VA at 24VAC
• Fan Enable / Loop Pump Relay: 1 HP at 240VAC
• Fan Speed / HWG Pump Relay: 1 HP at 240VAC
• Connection ratings on the DXM2 Control:
• ‘A’ terminal: 20VA at 24VAC. Larger solenoid valve draw should be controlled with accessory relays.
3
Application, Operation, & Maintenance Manual DXM2 UNIT CONTROLS Heat Controller, Inc.
DXM2 Physical Dimensions & Layout
5"
C
Gnd
B-
P1
Y1 Y2
W O G R C
AL1
R
P2
AL2
R
NSB
C
7"
ESD OVR
H A
P3
R NO1 NC1
COM
NO2 NC2
COM
R
COH
COM
Alarm Relay
Factory Use
JW1
Acc1
Relay
Acc2 Relay
Off On
P11
AO2
Fault
S3
1 2 3 4
Off On
Gnd
P4
A+ 24V
P5
(240Vac)
Com
Micro
U1
Status
Off On
1 2 3 4 5 6 7 8
S2
A0-1 A0-2
S1
T1
T2 T2 T3 T3 T4 T4
N.O.
Fan Enable
Test
JW3
1 2 3 4 5 6 7 8
Relay
P10
CCH
(240Vac)
Fan Speed
P12
RV
Relay
Comp Relay
P9
T5
T5
N.C. N.O.
T6 T6
12
1
1
4
P8
12V
IN OUT Gnd
NC
HP
HP
LP
LP
LT1 LT1
LT2 LT2
RV
RV
CO CO
P7
24Vdc
EH1 EH2
P6
CCG
CC
6 1/2"
Factory low voltage molex connection for
unit harness
Factory low voltage molex connection for
electric heat
harness
3/8” standoff
Note: There is only one T1 connection
1.5
5 1/2"
Use 4 mounting screws
#6 sheet metal screw 1” long
4
Heat Controller, Inc. DXM2 UNIT CONTROLS Application, Operation, & Maintenance Manual
DXM2 Layout and Connections
Conventional
stat connection
Cabinet
temperature
sensor (with variable speed pump)
Communications
and HWG
Settings
Accessory
relays refer
to DXM2 AOM
for configuration
P1
Y1 Y2
W O G R C
AL1
P2
AL2
R
NSB
C ESD OVR
H
A
P3
R
NO1 NC1
COM1
NO2 NC2
COM2
R
COH
COM
Service tool
connection
C
R
JW1
Alarm Relay
Acc1
F
Relay
sU yrotca
e
Acc2
Relay
Communicating stat connection
Gnd
B-
A+ 24V
P5
Fault
Status
Off On
1 2 3 4
S3
Off On
1 2 3 4 5 6 7 8
S1
P11
T1
Gnd
AO2
P4
(240Vac)
N.O.
Com
Fan Enable
Test
Micro
U1
Off On
S2
A0-1 A0-2
JW3
1 2 3 4 5 6 7 8
CCH
Relay
P10
T2 T2 T3 T3 T4 T4
(240Vac)
Fan Speed
P12
RV
Relay
Comp Relay
P9
T5
T5
N.C. N.O.
T6 T6
12
1
1
4
P8
12V
IN OUT Gnd
NC
HP HP
LP
LP
LT1 LT1
LT2 LT2
RV RV CO CO
P7
24Vdc
EH1 EH2
P6
CCG
CC
Test Button to Speed up Time Delays
ECM Motor Connection
Water Coil Low Temp Limit Setting. JWT-LT1 jumper should be clipped for low temp (antifreeze) operation
Factory low voltage molex connection for
unit harness
Electric heat connection
Configure
Confi gure
modulating valve
Modulating V alve
or variable
(Optional)
speed pump
24V to compressor
second-stage solenoid
for Y2/full
load capacity
Variable
speed pump
water temp
Entering
water temp
5
air temp
Leaving
Leaving
Entering Hot water
Compressor Discharge
Temperature
Use 4 mounting screws
temperature
#6 sheet metal screw 1” long
Application, Operation, & Maintenance Manual DXM2 UNIT CONTROLS Heat Controller, Inc.
DXM2 Controls
THERMOSTAT COMPATABILITY - IT IS STRONGLY RECOM­MENDED THAT A COMMUNICATING THERMOSTAT (7602-443) BE USED WITH GEOMAX COMMUNICATING SYSTEMS FOR:
1. Four-wire connections between the thermostat, compres­sor section (HTS), and air handler (WDG).
2. Confi guring, monitoring and diagnosing the system in PLAIN ENGLISH on the thermostat.
FIELD SELECTABLE INPUTS Test mode: Test mode allows the service technician to
check the operation of the control in a timely manner. By momentarily pressing the TEST pushbutton, the DXM2 control enters a 20 minute test mode period in which all time delays are sped up 15 times. Upon entering test mode, the Status and Fault LED displays will change. The Status LED will either fl ash rapidly to indicate the control is in the test mode, or display a numeric fl ash code representing the current airfl ow if an ECM blower is connected and operating. The Fault LED will display the most recent fault condition in memory. Note: A fl ash code of 1 indicates there have been no faults stored in memory. For diagnostic ease at conventional thermostats, the alarm relay will also cycle during test mode. The alarm relay will cycle on and off similar to the Fault LED to indicate a code representing the last fault, at the thermostat. The test mode can be exited by pressing the TEST pushbutton for 3 seconds. The test Mode can also be entered and exited by cycling the G input, 3 times within a 60 second time period.
During Test Mode, the control monitors to see if the LT1 and LT2 thermistors are connected and operating properly. If the control is in Test Mode, the control will lockout, with Code 9, after 60 seconds if:
a) the compressor is On in Cooling Mode and the LT1
sensor is colder than the LT2 sensor. or,
b) the compressor is On in Heating Mode and the LT2
sensor is colder than the LT1 sensor.
Retry Mode: If the control is attempting a retry of a fault, the Fault LED will slow fl ash (slow fl ash = one fl ash every 2 seconds) to indicate the control is in the process of retrying.
Field Con guration Options - Note: In the following fi eld confi guration options, jumper wires should be clipped ONLY when power is removed from the DXM2 control.
Note: Jumper 3 must not be clipped prior to adding antifreeze to the water loop. Antifreeze protection to 10°F required. Clipping JW3 without antifreeze may result in freeze damage and will void the unit warranty.
Water coil low temperature limit setting: Jumper 3 (JW3-
LT1 Low Temp) provides fi eld selection of temperature limit
setting for LT1 of 30°F or 10°F [-1°F or -12°C] (refrigerant temperature). Not Clipped = 30°F. Clipped = 10°F.
Alarm Relay Setting - Jumper 1 (JW1-AL2 Dry) provides eld selection of alarm function when Alarm Relay is energized. Not Clipped = AL1 connected to R (24VAC) with Alarm Relay active. Clipped = Dry contact connection between AL1 and AL2 with Alarm Relay active.
JUMPERS (Set at Factory) A0-2: Confi gure Modulating Valve (Optional)
Set A0-2 jumper (see Figure on page 5) to “IOV” if using Internal Modulating Motorized Valve (optional).
DIP SWITCHES Note: In the following fi eld confi guration options, DIP switches should only be moved when power is removed from the DXM2 Control to ensure proper operation.
DIP Package #1 (S1)
DIP Package #1 is 8 position and provides the following setup selections.
DIP 1.1: Unit Performance Sentinel Disable - Provides fi eld selection to disable the UPS feature.
On = Enabled. Off = Disabled. DIP 1.2: Compressor Relay Staging Operation - Provides
selection of Compressor Relay staging operation. The Compressor Relay can be selected to turn on with Stage 1 or Stage 2 call from the thermostat. This is used with Dual Stage units (2 compressors where 2 DXM2 Controls are being used) or with master/slave applications. In master/slave applications, each compressor and fan will stage according to its appropriate DIP 1.2. If set to stage 2, the compressor will have a 3 second on-delay before energizing during a Stage 2 demand. Also, if set for stage 2, the Alarm Relay will NOT cycle during Test Mode.
On = Stage 1. Off = Stage 2. DIP 1.3: Thermostat Type (Heat/Cool) - Provides selection
of thermostat type. Heat Pump or Heat/Cool thermostats can be selected. When in Heat/Cool Mode, Y1 is input call for Cooling Stage 1, Y2 is input call for Cooling Stage 2, W1 is input call for Heating Stage 1, and O/W2 is input call for Heating Stage 2. In Heat Pump Mode, Y1 is input call for Compressor Stage 1, Y2 is input call for Compressor Stage 2, W1 is input call for Heating Stage 3 or Emergency Heat, and O/W2 is the input call for RV (heating or cooling dependent upon DIP 1.4).
6
Heat Controller, Inc. DXM2 UNIT CONTROLS Application, Operation, & Maintenance Manual
DXM2 Controls
On = Heat Pump. Off = Heat/Cool. DIP 1.4: Thermostat Type (O/B) - Provides selection of
thermostat type. Heat pump thermostats with “O” output on with Cooling or “B” output on with Heating can be selected.
On = HP Stat with O output with cooling. Off = HP Stat with B output with heating.
DIP 1.5: Dehumidifi cation Mode - Provides selection of normal or Dehumidifi cation Fan Mode. In Dehumidifi cation Mode, the fan speed will be adjusted for Cooling. In Normal Mode, the fan speed will be normal during Cooling.
On = Normal Fan Mode. Off = Dehumidifi cation Mode. DIP 1.6: DDC Output at EH2 - DIP Switch 1.6 provides
selection for DDC operation. If set to DDC Output at EH2, the EH2 terminal will continuously output the last fault code of the controller. If set to EH2 normal, then the EH2 will operate as standard electric heat output.
On = EH2 Normal. Off = DDC Output at EH2. DIP 1.7: Boilerless Operation - Provides selection
of Boilerless Operation. In Boilerless Mode, only the compressor is used for Heating Mode when LT1 is above the temperature specifi ed by the setting of DIP 1.8. If DIP
1.8 is set for 50°F, then the compressor is used for heating as long as LT1 is above 50°F. Below 50°F, the compressor is not used and the control goes into Emergency Heat Mode, staging on EH1 and EH2 to provide heating.
On = normal. Off = Boilerless operation. DIP 1.8: Boilerless Changeover Temperature - Provides
selection of boilerless changeover temperature setpoint. On = 50°F. Off = 40°F.
DIP Package #2 (S2) DIP Package #2 (S2) - A combination of dip switches 2.1,
2.2, 2.3, and 2.4, 2.5, 2.6 deliver confi guration of ACC1 and ACC2 relay options respectively. See Table 2 for description and functionality.
DIP 2.7: Auto Dehumidifi cation Fan Mode or High Fan Mode - Provides selection of Auto Dehumidifi cation Fan Mode or High Fan Mode. In Auto Dehumidifi cation Mode, the Fan Speed will be adjusted during Cooling IF the H input is active. In High Fan Mode, the Fan will operate on high speed when the H input is active.
DIP Package #3 (S3)
DIP Package #3 is 4 position and provides the following setup selections.
DIP 3.1: Communications confi guration: Provides selection of the DXM2 operation in a communicating system. The DXM2 may operate as a communicating master or slave device depending on the network confi guration. In most confi gurations, the DXM2 will operate as a master device.
On = Communicating Master device (default). Off = communicating Slave device.
Table 1: Accessory Relay 1 Confi guration
DIP 2.1 DIP 2.2 DIP 2.3 ACC1 Relay Option
ON ON ON Cycle with fan
OFF ON ON Digital night setback
ON OFF ON Water valve – Slow opening ON ON OFF Outside air damper
OFF ON OFF
OFF OFF OFF option – Humidistat OFF OFF ON Hydronic Economizer – 1st Stage
ON OFF OFF
All other DIP combinations are invalid
Whole House Dehumidifi cation
option – Dehumidistat
Hydronic Economizer – Both
Stages
Table 2: Accessory Relay 2 Confi guration
DIP 2.4 DIP 2.5 DIP 2.6 ACC2 Relay Option
ON ON ON Cycle with compressor
OFF ON ON Digital night setback
ON OFF ON Water valve – Slow opening
OFF OFF ON Humidifi er
ON ON OFF Outside air damper
All other DIP combinations are invalid
DIP 3.2: HWG Test Mode: Provides forced operation of the HWG pump output, activating the HWG pump output for up to fi ve minutes.
On = HWG test mode. Off = Normal HWG mode (default). DIP 3.3: HWG Temperature: Provides the selection of the
HWG operating setpoint. On = 150°F [66°C]. Off = 125°F [52°C] (default).
On = Auto Dehumidifi cation Mode (default). Off = High Fan Mode.
DIP 2.8: Factory Setting - Normal position is On. Do not change selection unless instructed to do so by the Factory.
DIP 3.4: HWG Status: Provides HWG operation control. On = HWG mode enabled. Off = HWG mode disabled
(default)
7
Application, Operation, & Maintenance Manual DXM2 UNIT CONTROLS Heat Controller, Inc.
DXM2 Controls
SAFETY FEATURES
The following safety features are provided to protect the compressor, heat exchangers, wiring and other components from damage caused by operation outside of design conditions.
Anti-Short Cycle Protection - The control features a 5 minute anti-short cycle protection for the compressor.
Note: The 5 minute anti-short cycle also occurs at power up.
Random Start - The control features a 5-80 second
random start upon power up. The random start delay will be present after a control power up and after returning from Night Setback or Emergency Shutdown modes.
Extended Compressor Operation Monitoring - If the compressor relay has been on for 4 continuous hours, then the control will automatically turn off the compressor relay and wait the short cycle protection time. All appropriate safeties will be monitored during the off time. If all operation is normal, and if the compressor demand is still present, the control will turn the compressor back on.
Fault Retry - In Fault Retry Mode, the Fault LED begins slow fl ashing to signal that the control is trying to recover from a fault input. The DXM2 Control will stage off the outputs and then “try again” to satisfy the thermostat call for compressor. Once the thermostat input calls are satisfi ed, the control will continue on as if no fault occurred. If 3 consecutive faults occur without satisfying the thermostat call for compressor, then the control will go to Lockout Mode. The last fault causing the lockout will be stored in memory and is displayed at the Fault LED by entering the Test mode.
CAUTION!
CAUTION!
remedy of faulting condition. Equipment damage may occur.
the DXM2 is in Lockout Mode, and the W input becomes active, then Emergency Heat Mode will occur during Lockout. For Emergency Heat, the fan and auxiliary heat outputs will be activated.
Fault Code 2: High Pressure Switch – When the High Pressure switch opens due to high refrigerant pressures, the compressor relay is de–energized immediately. The High Pressure fault recognition is immediate (does not delay for 30 continuous seconds before de–energizing the compressor). When the Test mode is activated, the Fault LED will display a fault code of 2 for a High Pressure fault.
Fault Code 3: Loss of Charge Switch – The Loss of Charge Switch must be open and remain open for 30 continuous seconds during a compressor “on” cycle to be recognized as a Loss of Charge fault. If the Loss of Charge switch is open for 30 seconds prior to compressor power up it will be considered a Loss of Charge fault. The Loss of Charge Switch input is bypassed for the initial 120 seconds of a compressor run cycle. When the Test mode is active, the Fault LED will display a fault code of 3 for a Loss of Charge fault.
Fault Code 4: Water Coil Low Temperature Cut-Out Limit (LT1) - The control will recognize an LT1 fault, during
a compressor run cycle if:
a) the LT1 thermistor temperature is below the selected
Do not restart units without inspection and
low temperature protection limit setting for at least 50 seconds, AND
Note: LT1 and LT2 faults are factory set for one try, so there will be no “retries” for LT1 and LT2 faults. The control will only try one time for these faults.
FAULT CODES Lockout
ashing. The compressor relay is turned off immediately. The fan output will be turned off after the current blower off delay unless auxiliary heat is active. The Lockout Mode can be “soft” reset via the thermostat by removing the call for compressor, or by a “hard” reset (disconnecting power to the control). The fault code will be stored in non-volatile memory that can be displayed by the Fault LED by entering the Test mode, even if power was removed from the control.
Lockout with Emergency Heat - If the DXM2 is confi gured for Heat Pump thermostat Mode (see DIP 1.3),
- In Lockout Mode, the Fault LED will begin fast
b) the LT1 thermistor temperature is rising (getting
warmer) at a rate LESS than 2°F per 30 second time period.
The LT1 input is bypassed for the initial 120 seconds of a compressor run cycle. When the Test mode is active, the Fault LED will display a fault code of 4 for a LT1 fault.
Fault Code 5: Air Coil Low Temperature Cut-Out (LT2) - The control will recognize an LT2 fault, during a
compressor run cycle if:
a) the LT2 thermistor temperature is below the low
temperature protection limit setting for at least 50 seconds, AND
b) the LT2 thermistor temperature is rising (getting
warmer) at a rate LESS than 2°F per 30 second time period.
The LT2 input is bypassed for the initial 120 seconds of a
8
Heat Controller, Inc. DXM2 UNIT CONTROLS Application, Operation, & Maintenance Manual
DXM2 Controls
compressor run cycle. When the Test mode is active, the Fault LED will display a fault code of 5 for a LT2 fault.
Fault Code 6: Condensate Over ow - The Condensate Overfl ow sensor must sense overfl ow levels for 30 continuous seconds to be recognized as a CO fault. Condensate Overfl ow will be monitored at all times during the compressor run cycle. When the Test mode is active, the Fault LED will display a fault code of 6 for a Condensate Overfl ow fault.
Fault Code 7: Over/Under Voltage Shutdown - An Over/Under Voltage condition exists when the control voltage is outside the range of 18VAC to 31.5VAC. Over/ UnderVoltage Shutdown is self-resetting in that if the voltage comes back within range of 18.5VAC to 31VAC for at least 0.5 seconds, then normal operation is restored. This is not considered a fault or lockout. If the DXM2 is in over/under voltage shutdown for 15 minutes, the Alarm Relay will close. When the Test mode is active, the Fault LED will display a fault code of 7 for an Over/Under Voltage Shutdown.
Fault Code 8: Unit Performance Sentinel – UPS – The UPS feature warns when the heat pump is operating ineffi ciently. A UPS condition exists when:
a) In Heating Mode with compressor energized, if LT2
is greater than 125°F for 30 continuous seconds, or
b) In Cooling Mode with compressor energized, if LT1
is greater than 125°F for 30 continuous seconds, OR LT2 is less than 40°F for 30 continuous seconds.
If a UPS condition occurs, the control will immediately go to UPS warning. The status LED will remain on as if the control is in Normal Mode. (see “LED and Alarm Relay Operation Table”). Outputs of the control, excluding Fault LED and Alarm Relay, will NOT be affected by UPS. The UPS condition cannot occur during a compressor off cycle. During UPS warning, the Alarm Relay will cycle on and off. The cycle rate will be On for 5 seconds, Off for 25 seconds, On for 5 seconds, Off for 25 seconds, etc. When the Test mode is active, the Fault LED will display a fault code of 8 for an UPS condition.
Fault Code 9: Swapped LT1/LT2 Thermistors - During Test Mode, the control monitors to see if the LT1 and LT2 thermistors are connected and operating properly. If the control is in Test Mode, the control will lockout, with Code 9, after 60 seconds if:
a) the compressor is On in Cooling Mode and the LT1
sensor is colder than the LT2 sensor. Or,
b) the compressor is On in Heating Mode and the LT2
sensor is colder than the LT1 sensor.
When the Test mode is active, the Fault LED will display a fault code of 9 for a Swapped Thermistor fault.
Fault Code 10: ECM Blower Fault – When operating an ECM blower, there are two types of ECM Blower fault conditions that may be detected.
a) An ECM blower fault will be detected and the control
will lockout after 15 seconds of blower operation with the blower feedback signal reading less than 100 RPM.
b) An ECM blower fault will be detected when the ECM
confi guration is incorrect or incomplete. For this fault condition, the control will continue to operate using default operating parameters.
When the Test mode is active, the Fault LED will display a fault code of 10 for an ECM Blower fault.
Fault Code 11: Low Air Coil Pressure Switch (Whole House Dehumidifi cation Units Only) – When the Low Air Coil Pressure switch opens due to low refrigerant pressure in the cooling or reheat operating mode, the compressor relay is de–energized immediately. The Low Air Coil Pressure fault recognition is immediate (does not delay for 30 continuous seconds before de–energizing the compressor). When the Test mode is activated, the Fault LED will display a fault code of 11 for a Low Air Coil Pressure fault. Note: Low Air Coil Pressure fault will keep the unit from operating in the cooling or reheat modes, but heating operation will still operate normally.
Fault Code 12: Low Air Temperature (Whole House Dehumidifi cation Units Only) – The control will recognize an Low Air Temperature fault, during cooling, reheat, or constant fan operation if the LAT thermistor temperature is below 35 degrees for 30 continuous seconds. When the Test mode is activated, the Fault LED will display a fault code of 12 for a Low Air Temperature fault. Note: Low Air Temperature fault will keep the unit from operating in the cooling, reheat, or constant fan modes, but heating operation will still operate normally.
Diagnostic Features
The green Status LED and red Fault LED on the DXM2 Control advise service personnel of the current status of the DXM2 Control. The LED’s will indicate the current operating status of the DXM2, as well as the LAST fault in memory. If there is no fault in memory and the fault display is selected, the Fault LED will fl ash Code 1. See Table 3 for a complete listing of codes.
UNIT OPERATION DESCRIPTION Power Up - The unit will not operate until all the inputs and
safety controls are checked for normal conditions.
9
Loading...
+ 19 hidden pages