Heatcontroller CMA36SB-1 User Manual

INSTALLATION, OPERATION
& MAINTENANCE MANUAL
Horizontal/Side Discharge
Condensing Units
Models:
CMA18SB-1 CMA24SB-1 CMA30SB-1 CMA36SB-1
Heat Controller • 1900 Wellworth Ave. • Jackson, MI 49203 • (517)787-2100 • www.heatcontroller.com
Horizontal/Side Discharge Condensing Units:
Installation, Operation and Maintenance
TABLE OF CONTENTS
Safety Precautions ................................................................................................................... 3
General Operating Instructions................................................................................................. 4
General Product Information .................................................................................................... 5
Outdoor Unit Installation ........................................................................................................ 6-7
Unit Wiring ........................................................................................................................... 8-10
Wiring Diagrams .................................................................................................................. 8-10
Refrigerant Piping ................................................................................................................... 11
Leak Test, Evacuation & Release of Refrigerant .................................................................... 11
Initial Start-Up & Checks ........................................................................................................ 12
Field Charging ........................................................................................................................ 12
Field Inspection ...................................................................................................................... 12
2
Heat Controller Horizontal/Side Discharge Condensing Units
SAFETY PRECAUTIONS
Please read this installation manual completely before installing the product. If the power cord is damaged, replacement work shall be performed by authorized personnel only. Installation work must be performed in accordance with all local and national codes by authorized personnel only. Contact an authorized service technician for repair, maintenance or installation of this unit.
All the pictures in the instructions are for explanation purposes only, and may differ from the actual
product you purchased.
The design and specifications are subject to change without prior notice for product improvement.
Consult with the sales agency or manufacturer for details.
The seriousness of safety precautions is classified by the following indications:
WA R NI NG
CA UT ION
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to property.
WAR N ING
1) Install according to this installation instructions strictly. If installation is defective, it will cause water leakage, electrical shock fire, and may void the warranty.
2) Use the manufacturer’s specified and supplied parts only
3) Install in a strong and firm location which is able to withstand the unit’s weight. If the strength is
insufficient or installation is not properly done, the units can fall and cause injury.
4) For electrical work, follow all local An independent circuit and single outlet must be used. If electrical circuit capacity is not enough or a
defect found in electrical work, it may cause electrical shock or fire.
and National electrical codes and these installation instructions.
5) Use the specified cable, connect tightly and clamp the cable so that no external force will be acted on the terminal. If connection is loose, it may cause excessive heat build up.
6) Wiring cover is not fixed perfectly, it will cause heat build up at connection point of terminal, fire or electrical shock.
When carrying out piping connection, take care not to let air substances other than the specified
7)
refrigerant go into refrigeration circuit. Otherwise, it will cause lower capacity, abnormal high pressure in the ref
routing must be properly arranged so that control board cover is fixed properly. If control board
rigeration cycle, explosion and injury.
8) Do not modify the length of the power supply cord or use an extension cord, and do not share the single outlet with other electrical appliances. Otherwise, it may cause fire or electrical shock.
.
CAUTION
1) This equipment must be properly grounded and installed with and ground leakage current breaker, otherwise it may cause
2) Do not install the unit in place where leakage of flammable gas may occur. If gas leaks and
accumulates near or surroundings the unit, it may cause fire.
3) Carry out drainage piping as mentioned in installation instructions. If drainage is not properly done,
water may enter the room and damage the furniture.
electrical shock.
3
OPERATING INSTRUCTIONS
Air conditioners are designed to provide comfort cooling at outside temperatures above 65°F (18°C) but less than 109°F (43°C). Operating the air conditioner outside of this temperature range may cause unit failure and will void the warranty. If you have need for cooling at lower outdoor
temperatures a “low ambient cooling” can be eld
installed. Contact your local contractor or call the factory.
TO OPERATE:
NOTE: The thermostat operation may vary
by type and model used. Please consult the operating manual that was provided with the thermostat. The instructions below are generalized for most standard thermostat models.
1. Set the switch on your wall thermostat to the ‘cool’ position.
2. Set the desired temperature (between 63-86°F or 17-30°C) you want to maintain by moving the temperature setting on your thermostat. If the room is warmer than the setting, the unit will turn on and begin to blow cool air after a few minutes. A warm, humid room or building may take several hours of continuous operation to
cool to the thermostat set point the rst time.
Once the set temperature is reached the unit will cycle on and off.
3. Set the ‘Fan’ switch on the thermostat to ‘auto’ if you want the fan to run only when cooling is needed or to ‘on’ if you want continuous air circulation. The ‘on’ setting of the fan generally provides better temperature control by eliminating stagnant air.
NOTE: A properly installed and sized unit will not cycle more than 10 times per hour. If you notice more frequent starts call your service contractor.
4. For energy conservation reasons, you may want to set your thermostat at a higher temperature when you are away. Do not raise the temperature setting by more than 5 degrees. Changing the temperature by more than 5 degrees or shutting the unit ‘off’ can actually cost more than leaving the setting at a constant temperature.
IMPORTANT
Wait at least 3 minutes after turning your air conditioner off before trying to restart it. This gives the unit the time needed to stabilize before restarting. Failure to do so may cause unit damage and failure.
MAINTENANCE:
Only simple periodic maintenance is required:
1. Change or clean the indoor unit air ler monthly
or more frequently if unusual conditions are encountered. If you have a disposable type, throw the old one away and install a fresh one of the same size and type. If your unit has a washable type then vacuum and wash with soap and water. Flush thoroughly and dry before re-installing.
2. Keep the coil in the outdoor unit clean.
Periodically ush the coil thoroughly with a
garden hose. Clean away all foreign materials such as dust, leaves, grass clippings, papers, etc.
WARNING
Turn the power off rst! Serious injury or death
may result if water spray is directed at live electrical connections or power sources.
IMPORTANT!
Alterations and replacement parts:
Altering the product or replacing parts with non-authorized parts will void the factory Warranty and may result in adverse operational performance and/or a possible hazardous safety condition to service personnel and occupants. If you are in doubt
as to how to service this unit or where to nd
factory replacement parts, call Heat Controller at (517) 787-2100 for assistance.
4
Heat Controller Horizontal/Side Discharge Condensing Units
GENERAL PRODUCT INFORMATION
UNPACKING AND INSPECTION:
The condensing unit is shipped completely assembled and in it’s own package. All goods are inspected at the factory and released to the freight company in good condition. When received at the site, a visual inspection of all packages should be made immediately. Any evidence of rough handling or apparent damage should be noted on the delivery receipt and the material inspected in the presence of the carrier’s representative. If damage
is found a claim should be immediately le with the
freight company.
COOLING OPERATION TEMPERATURE LIMITS:
Heat Controller Condensing units are designed to operate in cooling at outside temperatures between 65°F (18°C) and 109°F (43°C). If the condensing unit will be used to cool at temperatures below 65°F (18°C), a low ambient
control must be eld installed. Operation below
65°F (18°C) without low ambient control will void the warranty.
INDOOR UNIT USE AND SYSTEM EFFICIENCY:
Heat Controller condensing units are designed to
be compatible with most major brands of domestic
evaporator coils/air handlers. Imported ductless air handlers maybe used but often do not include an expansion device. A properly sized thermostatic expansion valve is recommended. Consult AHRI’s
directory of certied products for indoor matches.
THERMOSTAT AND INDOOR FAN TIME DELAY:
All indoor units should include a fan time delay. This may be accomplished by using a digital wall thermostat or installation of a 60 second fan time
delay designed to work with your specic furnace/
air handler.
Most brands of electronic thermostats include a
fan delay. Properly specied thermostats are the
responsibility of the installer. Proper temperature control and unit operation depends on proper thermostat selection and location. Refer to the thermostat manufacturer’s installation instructions
for specied recommendations. Good practice is
to avoid outside walls, locations where the sun may shine directly on the thermostat, and locations where the air from supply registers or unit outlets blow on the thermostat. Also avoid locations where
the thermostat could be jarred by a closing door or high trafc area.
WARNING: An in-line lter drier is required when the unit is installed. The lter drier is
not provided by the factory, therefore a locally
purchased lter drier must be used to remove
any particulates or moisture that may be present in the system. Installations without an
in-line lter drier may void the warranty.
5
OUTDOOR UNIT INSTALLATION
UNIT LOCATION AND MOUNTING:
Choose a location that places the condensing unit as close to the indoor unit as possible. The maximum unit separation and vertical lift (compressor above evaporator) must be taken into account [See Fig 1]. Do not exceed allowable pipe lengths.
Fig. 1
Refrigerant Piping
Liquid-Gas In. 1/4 - 1/2 3/8 - 3/4
Max. Refrigerant Line Length*
Max. Elevation Vertical Lift**
CMA 18 CMA 24 CMA 30 CMA 36
Ft. 82 98
Ft. 33 49
*Minimum pipe length must not be less that 15 feet. ** “P” trap risers every 10 ft. when outdoor unit is installed above indoor unit.
NOTE: Oil traps must be installed every 10ft. when the outdoor unit is installed above the indoor unit.
Model No.
An awning can be built over the outdoor unit to prevent direct sunlight or rain exposure or snowfall. Ensure that the awning is at least 2 ft. above the top of the unit’s housing.
During heating and defrost modes, the condensate should be properly drained away from the unit.
Insure free ow of air into and out of the unit.
Inlets/outlets should stay clear of obstructions such as walls and shrubs. Minimum clearances must be adhered to [See Fig. 4 & 5 on page 7].
Do not locate two or more units in a way that will
block air ow or in a way that hot air from one unit
will blow into a nearby unit [See Fig. 3].
Install the outdoor unit on a rigid surface, able to withstand the unit’s weight, such as a concrete slab.
If the installation location allows the unit to be exposed to strong winds (such as sea side applications), ensure that the unit has a barrier from the wind [See Fig. 2]. This will assist with the proper operation of the fan by obstructing strong gusts of wind from entering the unit’s cabinet.
Avoid areas where water, snow, or ice may fall from a roof onto the unit. In climates where snow is a consideration, locate the unit away from areas prone to drifting. Ensure the location of the unit will
not be subject to snow drifts, heavy accumulation
of snow or leaves or other seasonal debris. If unavoidable, provide the awning for the unit.
6
Heat Controller Horizontal/Side Discharge Condensing Units
OUTDOOR UNIT INSTALLATION continued
Clearances
1. Ensure that there is sufcient clearance
around the unit for installation and maintenance. Clearance must be maintained to ensure that the air inlets and outlets are not obstructed.
[See Fig. 4].
Anchor the outdoor unit with a 10mm (3/8 inch) diameter bolt and nut tightly on a concrete or rigid surface [See Fig. 5]. Anchoring is especially recommended in seaside/high wind applications and/or areas prone to earthquakes.
1. Split type outdoor unit clearances
Fig. 4
1. Split type outdoor unit dimensions
Fig. 5
LQFK
LQFK
LQFK
LQFKHV
Units in inches
7
UNIT WIRING
ELECTRICAL WIRING AND SUPPLY VOLTAGE:
All electrical wiring must be done according to NEC and local codes. Nameplate data indicates the operating voltage, phase, ampacity, maximum over current protection, and minimum voltage.
The contractor is to provide an individual branch circuit for over current protection for the unit as required by code. Run power supply wiring through a weatherproof disconnect box and conduit to the unit connection. Disconnects are required to be within sight and easy reach of the unit (usually within 3 feet).
Check the unit wiring diagram for the number of conductors required. Route neatly and protect from sharp edges and damage.
Inadequate wiring and/or improper electrical supply will likely result in failure of the compressor and other electrical components and voids the warranty.
NOTE: The supply voltage must be consistent with the rated voltage of the air conditioner, not to exceed +/- 10%. Ensure the unit is properly grounded.
Outdoor unit wiring connection
1. Remove the electrical control cover from the outdoor unit.
2. Connect the cables to the terminals as
identied with their respective designated
terminal spaces on the terminal block of indoor and outdoor units. 600V THHN 14 AWG/4 conductor unshielded stranded copper cable is recommended, however NEC/local codes prevail.
3. To prevent the entrance of water into outdoor unit, form a loop in the cable [See Fig. 6].
4. Insulate any unused conductors with PCV/ Electrical tape, so that they do not touch any other exposed electrical or metal parts.
CAUTION
Incorrect wiring connections may cause electrical parts to malfunction. All wiring must comply with local and national electrical
codes and be installed by qualied and skilled
electricians.
8
Heat Controller Horizontal/Side Discharge Condensing Units
OUTDOOR UNIT WIRING CONNECTION continued
TERMINAL bLOCk OF OUTDOOR UNIT
*NOTE: Please refer to the installation instructions of the 24V
thermostat used in conjunction with this unit for additional wiring
instructions.
9
OUTDOOR UNIT WIRING CONNECTION continued
CMA18SB-1 & CMA24SB-1
CMA30SB-1
CMA36SB-1
10
Heat Controller Horizontal/Side Discharge Condensing Units
REFRIGERANT PIPING
The length of refrigerant lines and the number of bends determine the pressure drop which affects
capacity and efciency of the system and oil return
to the compressor. The outdoor unit connections
are are type. Tube size should always be the
same diameter as the connections provided at the service valves. Up sizing of lines can result in inadequate oil return to the compressor and excessive refrigerant charge and will void the warranty [See Table 1].
Refrigerant Piping
Liquid-Gas In. 1/4 - 1/2 3/8 - 3/4
Max. Refrigerant Line Length*
Max. Elevation Vertical Lift**
*Minimum pipe length must not be less that 15 feet. ** “P” trap risers every 10 ft. when outdoor unit is installed above indoor unit.
Choose a location that places the condensing unit as close to the indoor unit as possible. The maximum separation is dependent on model. Use only clean refrigeration grade tubing. Avoid piping on wet or rainy days. Always keep the tube
ends capped until you are ready to make the nal
connections. Remove burrs from cut ends of tubing. Use tube benders to avoid kinking.
Insulate the suction line with Armaex or equivalent
with a wall thickness of at least 3/8”. Support the tubing adequately to avoid sags that can trap oil. Isolate the tubing so as not to transmit noise to the building structure. Avoid sharp edges that could cut the tubes. Maximum vertical lift (compressor above evaporator) is dependent on model. Trap risers with a ‘P’ trap every 10 feet.
CMA 18 CMA 24 CMA 30 CMA 36
Ft. 82 98
Ft. 33 49
Model No.
WARNING
It is illegal to discharge refrigerant into the atmosphere. Use proper reclaiming methods and equipment when working on the refrigerant containing parts of the unit. Service should be performed by a QUALIFIED service agency and
certied technicians.
LEAk TEST, EVACUATION & RELEASE OF REFRIGERANT
The condensing unit is supplied with R-410a
charge sufcient for most matching evaporator
units. Charge must be added for interconnecting tubing.
The unit’s service valves are shipped in the closed
position and should not be opened until nal
connections and evacuation are completed.
The recommended procedure for leak test, evacuation, and release of refrigerant is outlined below:
1. Complete the nal piping connections to the
indoor and outdoor units using high temperature brazing alloy.
2. Connect a charging manifold to the service ports provided at the service valves.
3. Pressurize the lines and evaporator with nitrogen and leak check all connections with soap bubbles. Repair as necessary any
faulty joints. If brazing is required be sure to
RELEASE THE NITROGEN FIRST. Re-test as needed.
4. Connect a vacuum pump to the manifold center connection, start the pump and open the manifold valves.
5. Evacuate to 500 microns or less for a minimum of 30 minutes. Close the manifold valves and shut off the pump. Note the vacuum reading and wait 15 minutes. Take a new vacuum reading. A reading of 800 microns or higher indicates the presence of moisture or a leak.
6. Repair as necessary and repeat steps 3, 4 & 5.
7. Conrm that manifold valves are closed and
disconnect the vacuum pump.
8. Remove the caps from the services valves. Open the valves to the fully ‘back-seat’ position. Replace service valve caps and tighten.
11
INITIAL START-UP & CHECkS
Operation of the unit is automatic and will provide cooling depending on the setting of the thermostat.
IMPORTANT!
All panels must be installed, main power turned on and the thermostat properly connected before operating the unit.
1. System check - set thermostat system switch to “Off” position and fan switch to “Auto” position. Turn the power supply breaker on.
2. Set the fan switch to “On,” blower should operate.
3. Return the fan switch to “Auto”. Blower should shut off. Set the system switch to “Cool” and lower thermostat set point to coldest setting. The compressor, condenser fan, and evaporator blower should all come on. Cool air will be supplied after a couple of minutes of run time.
4. Proceed to the “FIELD CHARGING” section of these instructions.
FIELD CHARGING
Unit performance, efciency, and life depends,
to a large extent, on a proper system charge. Time spent on getting the charge right at start-up will payoff in the long run. Operating conditions
such as voltage, air ow, evaporator coil size,
and indoor and outdoor temperature and humidity all have an effect on the system pressures and superheat conditions.
FINAL INSPECTION
Do a nal visual inspection of the entire installation
and complete any nal details and clean up.
Review Unit Operation with the homeowner/user.
The pressure/temperature chart can be used as a
reference to ensure performance.
2XWGRRU$PELHQW7HPSHUDWXUH963UHVVXUH
2XWGRRU7HPSHUDWXUH
36,
1RWH³,'7´ ,QGRRU7HPSHUDWXUH
³2'7´ 2XWGRRU7HPSHUDWXUH
5HPRYHUHIULJHUDQWLIWKHSUHVVXUHLVDERYHWKHFKDUWYDOXH $GGUHIULJHUDQWLIWKHSUHVVXUHLVEHORZWKHFKDUWYDOXH
Charge must be added for the interconnecting tubing. Evaporator coils require thermostatic expansion valves. These units should be critically charged to ensure proper performance. Some systems may require additional charging of refrigerant, depending on line set lengths.
12
R(oz): Additional refrigerant to be charged L(ft): The length of the liquid pipe T(oz): The quantity of the charged refrigerant per additional foot
oz/ft
0.16 0.32
Heat Controller Horizontal/Side Discharge Condensing Units

4/2014
Design, material, performance specications and components
subject to change without notice.
:HOOZRUWK$YH-DFNVRQ0,3KZZZKHDWFRQWUROOHUFRP
13
Loading...