Heat Controller BGE-123A, BGE-103A User Manual

Through-The-Wall
Air Conditioner
Service Manual
CAUTION
-Before servicing the unit, read the "safety precautions" in this manual.
-Only for authorized service personnel.
HEAT CONTROLLER, INC.
BGE-123A
Air Conditioner Service Manual
TABLE OF CONTENTS
Safety Precautions..........................................................................................................................................3
Installation.......................................................................................................................................................7
Installation requirements ...........................................................................................................................7
Installation..................................................................................................................................................8
How to Install..............................................................................................................................................8
Procedure A ...............................................................................................................................................9
Procedure B .............................................................................................................................................11
Procedure C.............................................................................................................................................12
Operating Instructions .................................................................................................................................14
Controls....................................................................................................................................................14
Remote control.........................................................................................................................................15
How to insert batteries .............................................................................................................................16
Ventilation Control....................................................................................................................................16
Air Direction..............................................................................................................................................16
Disassembly instructions.............................................................................................................................17
Mechanical Parts......................................................................................................................................17
Air Handling Parts ....................................................................................................................................18
Electrical Parts .........................................................................................................................................19
Refrigeration Cycle...................................................................................................................................21
Schematic Diagram.......................................................................................................................................24
Wiring Diagram.........................................................................................................................................24
Troubleshooting Guide.................................................................................................................................25
Piping System ..........................................................................................................................................25
Troubleshooting Guide .............................................................................................................................26
Room Air Conditioner Voltage Limits........................................................................................................29
Product specifications..................................................................................................................................31
2 Room Air Conditioner
Service Manual 3
Safety Precautions
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be followed.
Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following indications.
Meanings of symbols used in this manual are as shown below.
WARNING
CAUTION
This symbol indicates the possibility of death or serious injury. This symbol indicates the possibility of injury or damage to property only.
WARNING
Installation
Don’t use a power cord, a plug or a loose socket which is dam­aged.
• Otherwise, it may cause a fire or
electrical shock.
Always plug into a gr ounded outlet.
• Otherwise, it may cause a fire or electrical shock.
Do not modify or extend the power cord length.
• It will cause electric shock or fire due to heat generation.
Do not disassemble or modify products.
• It may cause failure and electric shock.
Be caution when unpacking and installing.
• Sharp edges may cause injury.
Do not use the power cord near flam­mable gas or combustibles such as gasoline, benzene, thinner, etc.
• It may cause explosion or fire.
Be sure not to do.
Be sure to follow the instruction.
M O D E
T I M E R
P O W E
R
F A N
S P E E D
F a n H e a t
E
n e r g y
S a v e r
C o o l
T i m e r
T E M P
'
F
F 1 L O W
F 2 H I G H
M
O D E
T I M E R
P O W E R
F A N
S P E E D
F a n H e a t
E
n e r g y
S a v e r
C oo l
T im er
T E M P
'
F
F 1 L O W
F 2 H IG H
M
O D E
T I M E R
P O W E
R
F
A N
S P
E E D
F a n
H
e a t
E n
e r g y
S
a v e r
C
o o l
T i m e r
T
E M P
'
F
F 1 L O W
F 2 H I G H
M
O D E
T I M E R
P O W E R
F A N
S P E E
D
F a n H e a t
E
n e r g y
S a v e r
C o o l
T i m e r
T E M
P
'
F
F 1 L
O W
F 2 H
IG H
Gasolin
M
O D E
T I M E R
P O W
E R
F A N
S P
E E D
F a n
H
e a t
E n
e r g y
S
a v e r
C
o o l
T i m e r
T
E M P
'
F
F 1 L O W
F 2 H I G H
4 Room Air Conditioner
Safety Precautions
Operation
Do not place heavy object on the power cord and take care so that the cord should not be pressed.
• There is danger of fire or electric shock.
Do not share the outlet with other appliances.
• It will cause electric shock or fire due to heat generation.
Take the power plug out if neces­sary, holding the head of the plug and do not touch it with wet hands.
• Otherwise, it may cause a fire or electrical shock.
Do not place the power cord near a heater.
• It may cause fire and electric shock.
Do not allow water to run into electric parts.
• It will cause failure of machine or electric shock.
Use a soft cloth to clean. Do not use wax, thinner, or a strong detergent.
• The appearance of the air condi­tioner may deteriorate, change color, or develop surface flaws.
Unplug the unit if strange sounds, odors, or smoke come from it.
• Otherwise it may cause fire and electric shock accident.
Do not open the suction inlet grill of the product during opera­tion.
• Otherwise, it may electrical shock and failure.
If water enters the product, turn off the the power switch of the main body of appliance. Contact service center after taking the power-plug out from the socket.
Ventilate the room well when using this appliance together with a stove, etc.
• An oxygen shortage may occur.
Turn off the power and breaker firstly when cleansing the unit.
• Since the fan rotates at high speed during operation, it may cause injury.
Turn off the main power switch when not using it for a long time.
• Prevent accidental startup and the possibility of injury.
M O
D E
T I M E R
P O W E R
F A
N
S P E
E D
F a n
H
e a t
E n e
r g y
S a
v e r
C
o o l
T i m e r
T E
M P
'
F
F
1 L O W
F
2 H I G H
M
O D E
T I M E R
P
O W E R
F A N
S P E E D
F an H e a t
E n
e r g y
S
a v e r
C o o l
T i m e r
T E M P
'
F
F 1 L O W
F 2 H I G
H
M
O D E
T I M E R
P O W E R
F A N
S P E E
D
F a n H e a t
E
n e r g y
S a v e r
C o o l
T i m e r
T E M
P
'
F
F 1
L O W
F 2
H I G H
M
O D E
T I M E R
P
O W E R
F A N
S P E E D
F a n H e a t
E n
e r g y
S
a v e r
C o o l
T i m e r
T E M P
'
F
F 1 L O
W
F 2 H I G
H
Wax
Thinner
MODE
TI M E R
POW
E R
F A N
S
P E E D
F a n
H
e a t
E n
e r g y
S
a v e r
C
o o l
T i m e r
T E M P
'
F
F 1 L O W
F 2 H I G H
M O
D E T
I M E R
P O
W E R
FA N
SP E ED
F
a n
H
e a t
E n e
r g y
S a
v e r
C
o o l
T
i m e r
T E M
P
'
F
F 1 L O
W
F 2 H I
G H
M
O D E
T I M E R
P O W E
R
F
A N
S P
E E D
F a n
H
e a t
E n
e r g y
S
a v e r
C
o o l
T i m e r
T
E M P
'
F
F 1 L O W
F 2 H I G H
M
O D E
T I M E R
P O W E
R
F A
N
S P
E E D
Fa n
He
a t
E n
e r g y
S
a v e r
Co
ol
Ti mer
T
E M P
'
F
F 1 L O W
F 2 H I G H
M
O D E
T I M E R
P O W E R
F A
N
S P E
E D
F a n H e a t
E
n e r g y
S a v e r
C o o l
T i m e r
T E
M P
'
F
F 1
L O W
F 2
H I G H
M
O D E
T I M E R
P
O W E R
F A N
S P E E D
F a n H e a t
E n
e r g y
S
a v e r
C o o l
T im e r
T E M P
'
F
F 1 L O W
F 2 H I G
H
M
O D E
T I M E R
P O W
E R
F A N
S
P E E D
F a n
H
e at
E ne
r g y
S
av er
C
o o l
T im e r
T E M P
'
F
F 1 L O W
F 2 H I G H
Service Manual 5
Safety Precautions
Do not operate or stop the unit by inserting or pulling out the power plug.
• It will cause electric shock or fire due to heat generation.
Do not damage or use an unspecified power cord.
• It will cause electric shock or fire.
Do not operate with wet hands or in damp environment.
• It will cause electric shock.
Hold the plug by the head when taking it out.
• It may cause electric shock and damage.
When gas leaks, open the win­dow for ventilation before oper­ating the unit.
• Otherwise, it may cause explo­sion, and a fire.
Never touch the metal parts of the unit when removing the fil­ter.
• They are sharp and may cause injury.
Install the product so that the noise or hot wind from the outdoor unit may not cause any damage to the neighbors.
• Otherwise, it may cause dispute with the neighbors.
Keep level parallel in installing the product.
• Otherwise, it may cause vibration or water leakage.
M O D
E T I M E
R
P O W
E R
F A N
S P E E
D
F a n H e a t
E n e r g y
S a v e r
C o o l
T i m e r
T E M
P
'
F
F 1 L
O W
F 2 H
I G H
M
O D E
T I M E R
P O W E R
F
A N
S P
E E D
F a n H e a t
E
n e r g y
S a v e r
C o o l
T i m e r
T
E M P
'
F
F1 L OW
F 2 H IG H
M
O D E
T I M E R
P
O W E R
F A N
S P E E D
F a n H e a t
E n
e r g y
S
a v e r
C o o l
T i m e r
TE M P
'
F
F 1 L O
W
F 2 H I G
H
M
O D E
T I M E R
P O W E R
F
A N
S P
E E D
F a n H e a t
E
n e r g y
S a v e r
C o o l
T i m e r
T
E M P
'
F
F 1 L OW
F 2 H IG H
M
O D E
T I M E R
P O W E R
F
AN
SP
E E D
F a n H e a t
E
n e r g y
S a v e r
C o o l
T i m e r
T
E M P
'
F
F 1 L O W
F 2 HI G H
CAUTION
Installation
6 Room Air Conditioner
Safety Precautions
Do not put a pet or house plant where it will be exposed to direct air flow.
• It may cause injury.
Do not block the inlet or outlet of air flow.
• It may cause product failure.
Use a soft cloth to clean. Do not use wax, thinner, or a strong detergent.
• The appearance of the air condi-
tioner may deteriorate, change color, or develop surface flaws.
Do not step on the indoor/out­door unit and do not put any­thing on it.
• It may cause an injury through dropping of the unit or falling down.
Always insert the filter securely. Clean it every two weeks.
• Operation without filters will cause failure.
Do not drink water drained from air conditioner.
• It contains containments and will make you sick.
Be cautious not to touch the sharp edges when installing.
• It may cause injury.
Avoid excessive cooling and perform ventilation sometimes.
• Otherwise, it may do harm to your health.
Do not insert the hands or bars through the air inlet or outlet during operation.
• Otherwise, it may cause person­al injury.
Operation
M
O D E
T I M E R
P O W E R
F
A N
S P
E E D
F a n H e a t
E
n e r g y
S a v e r
C o o l
T i m e r
T
E M P
'
F
F1 LOW F2 HI GH
M
O D E
T I M E R
P O W E R
F
AN S PE
E
D
F a n H e a t
E
n e r g y
S a v e r
C o o l
T i m e r
T
E
M
P
'
F
F1 L
O
W
F2
H
I
G
H
M
O D E
T I M E R
P O W E R
FA
N
S P
E
E
D
F a n H e a t
E
n e r g y
S a v e r
C o o l
T i m e r
T
E
M
P
'
F
F
1
L
O
W
F2
HI
GH
M O D
E T I M E
R
P O W
E R
F
A
N
S
P
E
E
D
F a n H e a t
E n e r g y
S a v e r
C o o l
T im e r
T
E
M
P
'
F
F
1
L
O W
F
2
H
I G H
M
O D E
T I M E R
P O W E R
F
A
N
S P
E
E
D
F a n H e a t
E
n e r g y
S a v e r
C o o l
T i m e r
T
E
M
P
'
F
F1
L
O
W
F
2
H
I
G
H
M
O D E
T I M E R
P O W E R
F A
N
S P E
E
D
F a n H e a t
E
n e r g y
S a v e r
C o o l
T i m e r
T E
M
P
'
F
F
1
L
O
W
F
2
H
I
G
H
M
O D E
T I M E R
P O W E R
F
A
N
S P
E
E
D
F a n H e a t
E
n e r g y
S a v e r
C o o l
T i m e r
T
E
M
P
'
F
F
1 L
OW
F
2 H
IG
H
Service Manual 7
Installation
Installation
Remove packing sheet from the back of the sleeve, and packing corner and blue tape from the air condi­tioner.
Installation requirements
If you use an existing wall sleeve, you should mea­sure its dimensions.
Install the new air conditioner according to these instal­lation instructions to achieve the best performance. All wall sleeves used to mount the new air conditioner must be in good structural condition and have a rear grille to securely attach the new air conditioner. (FIG. 1)
With the HCI sleeve(optionally supplied with your unit), you can maintain the best performance of the new air conditioner. (FIG. 2)
21
/32"
19-
(499 mm)
24-21/32"
(626 mm)
C o
o
E
l n e r
g S
y a v
e
r F a
n H e
a
t
F 1 L F
O
2
W
H
I G
T
H
im
M
e
r
O
D
E
'
F
TEMP
T I M
E R
F A S N P E E
D
P O W E
R
14-13/32" (366 mm)
INSTALLATION HARDWARE
1
2
4
2 Size options
7
8
3
5
6
2 Size options
ITEM NAME OF PARTS Q'TY
1 PLASTIC GRILLE 1
2 HORIZONTAL INSULATION STRIPS 2
3 AROUND INSULATION STRIPS 2
4 SUPPORT BLOCK 2
5 BAFFLE 1
6 TRIM FRAME 2
7 SHIM 2 8 PLASTIC NUTS AND WASHER SCREWS 4
Air Conditioner
Expanded aluminum metal grille
LGE Wall Sleeve
18"(458 mm)
25-7/8"
(656 mm)
15-17/32" (394 mm)
16-23/32" (425 mm)
FIG. 1
FIG. 2
ELECTRICAL SERVICE
Check your available electrical service. The power supply available must be the same as that shown on the unit nameplate (found on left side of cabinet).
All models are equipped with a 3-prong service plug to provide proper service and safe positive grounding. Do not change plug in any way. Do not use an adapter plug. If your present wall outlet does not match your plug, call a qualified electrician to make the necessary corrections. SAVE CARTON for storage and this OWNER'S MANUAL for future reference. The carton is the best way to store unit during winter or when not in use.
To avoid risk of personal injury, property damage, or product damage due to the weight of this device and sharp edges that may be exposed:
Air conditioners covered in this manual pose an excessive weight hazard. Two or more people are needed to move and install the unit. To prevent injury or strain, use proper lifting and carrying techniques when moving unit.
Carefully inspect location where air conditioner will be installed. Be sure it will support the weight of the unit over an extended period of time.
Handle air conditioner with care. Wear protective gloves whenever lifting or carrying the unit. AVOID the sharp metal fins of front and rear coils.
Make sure air conditioner does not fall during instal­lation.
REQUIRED TOOLS:
Tight Fitting gloves
Standard screwdriver
Phillips screwdriver
Pliers
Sharp knife
3/8-inch open end
wrench or adjustable wrench
1/4-inch hex socket and ratchet
Tape measure
Electric drill
1/4-inch drill bit
NOTICE
8 Room Air Conditioner
Installation
Installation
FIG. 3
We strongly recommend the removal of the old wall sleeve and the installation of a new HCI Wall Sleeve.
If you decide to keep the existing wall sleeve, you have to redirect the louvers at the back of the wall sleeve illus­tration. The use of pliers is recommended. If you DO NOT redirect, you run the risk of poor performance or product failure. This is not covered under the terms of the Heat Controller warranty.
Pick a location which will allow the conditioned air to blow into the area you want. Good installation with special attention to the proper position of the unit will lessen the chance that service will be needed.
ITEMS IN INSTALLATION HARDWARE
You may not need all parts in the kit. Discard unused parts
ITEM (inches)
Plastic grille 263/4 x 161/2 1
Horizontal Insulation Strips
Around Insulation Strips
Support Block 13/4 x 1 3/8 x 45/16 2 Baffle 14 x 41/2 x 1/8 1 Shim 13 x 1 x 3/4 2 Trim Frame 2 Washer Screw 4 Nuts(Plastic) 4
13/8 x 5/8 x 273/16 1 13/8 x 1 3/8 x 27 3/16 1 13/8 x 3/4 x 611/2 1 13/8 x 1 3/8 x 61 1/2 1
Qty.
All wall sleeves used to mount the new Air Conditioner must be in sound structural condition and have a rear grille that securely attaches to sleeve, or rear flange that serves as a stop for the Air Conditioner,
2. Remove old air conditioner from existing wall sleeve.
3. Clean the interior of an existing sleeve. (Do not disturb seals.)
4. Wall sleeve must be securely fastened in wall before installing the air conditioner. Use the nails or screws through sleeve into wall, if needed. Repaint sleeve if needed.
5. Prepare the wall sleeve for installation of the unit. If you plan to use your existing wall sleeve, and it is not LGE, use procedure B or C below.
Procedure Brand
A LGE 16-23/32
White-Westinghouse Frigidaire Carrier (52F series)
B
C
6. Install new unit into wall sleeve.
General Electric /Hotpoint Whirlpool 17-1/8 or 23 Carrier (51S series)
Fedders/Emerson Emerson/Fedders 15
Friedrich 16-3/4
Depth(inches)
16, 17-1/2
or 22
16-7/8
18-5/8 16-3/4
or 19-3/4
How to Install
1. Identify the existing wall sleeve before installing the unit from the listed below.
Brand
White-Westinghouse Frigidaire Carrier (52F series) General Electric /Hotpoint
Whirlpool 25-7/8 16-1/2 Fedders/Emerson 27 16-3/4
LGE 25-7/8 15-17/32 16-23/32 Emerson/Fedders 26-3/4 15-3/4 15 Carrier (51S Series) 25-3/4 16-7/8 18-5/8 Friedrich 27 16-3/4 16-3/4
Wall Sleeve Dimensions (inches)
Width Height Depth 25-1/2 15-1/4
26 15-5/8 16-7/8
16, 17-1/2
or 22
17-1/8
or 23
16-3/4
or 19-3/4
When installation is completed, replacement unit MUST have a rearward slope as shown. To achieve 1/4" slope, remove the backing from the 11-13/16" shim strips and attach them as shown below in Fig. 3. Place the higher portion of shim to the front of the rib on base of wall sleeve.
1" high
Shim
6" 6"
SHIM PLACEMENT UNIT INSTALLATION
FRONT
1/4"
3
/4" High
UNIT
Wall Sleeve
Service Manual 9
Installation
Procedure A
1. If you are using the new sleeve (optionally supplied with your unit),skip to step 3. Otherwise, install the plastic grille from the kit. Cut the plastic grille to 25­1/2" wide and 15-1/4" high. Place the plastic grille to the inside of the wall sleeve at the rear flange.
2. Fasten the 4 washer screws to secure the grille to the wall sleeve. If you need plastic nuts to mount plastic grille to the inside of the wall sleeve, there are plastic nuts in the installation kit. The nuts are installed from the inside of the sleeve and are pressed into the square holes of the rear flanges.
3. Remove the backing from the Horizontal Insulation strip 1
3
/
8
x
3
/
8
8 x 27
3
/
16
and attach that to the inside bottom of the sleeve as shown below. Remove the backing from the Around Insulation strip 1
3
/
8
x
3
/
4
x
61
1
/
2
and attach that to the inside front of the sleeve
as shown below.
4. Install the new unit into the wall sleeve.
FIG. 4
Around Insulation
Horizontal Insulation
FIG. 6
or
FIG. 5
Wall
Trim (2 ea)
M O
D E
T IM E
R
P O W
E R
FAN SPEED
F
a n
H
e a t
E n e
r g y
S a
v e r
C
o o l
T im e
r
T E M
P
'
F
F 1 L O
W
F 2 H I
G H
Air conditioners covered in this manual pose an excessive weight hazard. Two or more people are needed to move and install the unit. To prevent injury or strain, use proper lifting and carrying techniques when moving unit.
When handling the air conditioner, be careful to avoid cuts from sharp metal fins on front and rear coils.
Make sure air conditioner does not fall during removal.
FIG. 7
5. To assemble trim, snap the tab of each piece into the slot of the other piece as shown below. Slide
trim over the front of the air conditioner until trim is
flush with sleeve as shown below.
10 Room Air Conditioner
Installation
Procedure B
1. Redirect the louvers at the back of the wall sleeve to 60° angle as shown in the FIG 8. The use of pliers is recommended.
2. If the wall sleeve already has a rear grille, skip to step 4. If the wall sleeve does not have a rear grille or louvered panel, install the plastic grille from the kit. Cut the plastic grille to 25-1/2" wide and 15-1/4" high. Place the plastic grille to the inside of the wall sleeve at the rear flange.
3. Fasten the 4 washer screws to secure the grille to the wall sleeve. If you need plastic nuts to mount plastic grille to the inside of the wall sleeve, there are plastic nuts in the installation kit. The nuts are installed from the inside of the sleeve and are pressed into the square holes of the rear flanges.
4. Remove the backing from the Horizontal Insulation strip 1
3
/
8
x
5
/
8
x 27
3
/
16
and attach that to the inside bot­tom of the sleeve as shown below. Remove the backing from the Around Insulation strip 1
3
/
8
x
3
/
4
x
61
1
/
2
and attach that to the inside front of the sleeve
as shown below.
5.If the depth of your existing wall sleeve is less than or equal to 18", skip to step 6. Otherwise, cut the baffles and the support blocks according to length
Rear Louvers
(Top View)
60°
60°
7
5
/
16
"
FIG. 8
FIG. 9
Place the plastic grille
or
FIG. 10
Fasten the screws
Around Insulation
Horizontal Insulation
FIG. 11
Depth"D" of the existing wall sleeve (inches)
Length "A"
(inches)
Support Block
Baffle
A
A
3
/4
1-3/4
4
18 D 18-5/
8
18-5/
8
D 19-3/
4
19-3/4 D 22
FIG. 12
"A" in the table below.
Service Manual 11
Installation
6. Remove the backing from the support blocks and attach them to the inside of the wall sleeve as shown FIG 13. Slide the baffle into slots of the sup­port blocks.
7.Install the new unit into the wall sleeve.
8.To assemble trim, snap the tab of each piece into the
slot of the other piece as shown below. Slide trim over the front of the air conditioner until trim is flush with sleeve as shown below.
Wall
Wall
Sleeve
Baffle
(7
5
/
16
")
Front
Support Block
FIG. 13
Wall
Trim (2 ea)
M O
D E
T I M E
R
P O W
E R
F A N
S P E E D
F
a n
H
e a t
E n e
r g y
S a
v e r
C
o o l
T i m e
r
T E M
P
'
F
F 1 L O
W
F 2 H I
G H
FIG. 14
Air conditioners covered in this manual pose an excessive weight hazard. Two or more people are needed to move and install the unit. To prevent injury or strain, use proper lifting and carrying techniques when moving unit.
When handling the air conditioner, be careful to avoid cuts from sharp metal fins on front and rear coils.
Make sure air conditioner does not fall during removal.
12 Room Air Conditioner
Installation
Procedure C
1. Redirect the louvers at the back of the wall sleeve to 60° angle as shown in the FIG 15. The use of pliers is recommended.
2. If the wall sleeve already has a rear grille, skip to step 4. If the wall sleeve does not have a rear grille or louvered panel, install the plastic grille from the kit. Cut the plastic grille to 26-1/2" wide and 15-1/2" high. Place the plastic grille to the inside of the wall sleeve at the rear flange.
3. Fasten the 4 washer screws to secure the grille to the wall sleeve. If you need plastic nuts to mount plastic grille to the inside of the wall sleeve, there are plastic nuts in the installation kit. The nuts are installed from the inside of the sleeve and are pressed into the square holes of the rear flanges.
4. Remove the backing from the Horizontal Insulation strip 1
3
/
8
x 1
3
/
8
x 27
3
/
16
and attach that to the inside bottom of the sleeve as shown below. Remove the backing from the Around Insulation strip 1
3
/
8
x 1
3
/
8
x
61
1
/
2
and attach that to the inside front of the sleeve
as shown below.
5. If the depth of your existing sleeve is less than or equal to 18", skip to step 7. Otherwise, cut the baf­fles and the support blocks according to Length "A" in the table below.
6. Remove the backing from the support blocks and attach them to the inside of the wall sleeve as shown FIG 20. Slide the baffle into slots of the sup­port blocks
FIG. 16
or
FIG. 17
Rear Louvers
(Top View)
60°
7
13
/
16
"
60°
FIG. 15
Place the plastic grille
Fasten the screws
Around Insulation
Horizontal Insulation
FIG. 18
Depth"D" of the existing wall sleeve (inches)
Length "A"
(inches)
Support Block
Baffle
A
A
3
/4
1-3/4
4
18 D 18-5/
8
18-5/
8
D 19-3/
4
19-3/4 D 22
Wall
Wall
Sleeve
Baffle
Front
Support Block
(
7
13
/
16
"
)
FIG. 20
FIG. 19
Service Manual 13
Installation
7. Remove the backing from the 13" shim strips and attach them as shown below in Fig. 22. The higher portion of shim is to be placed in front of the rib on the base of wall sleeve.
8. Install the new unit into the wall sleeve
FIG. 21
1" high
3
/4" High
FIG. 22
Wall
Trim (2 ea)
M O
D E
T I M
E R
P O W
E R
FA N
SPE ED
Fa
n
H
ea t
E n e
r g y
S a
v e r
C
oo l
T im er
T E M
P
'
F
F 1 L O
W
F 2 H
I G H
FIG. 23
Air conditioners covered in this manual pose an excessive weight hazard. Two or more people are needed to move and install the unit. To prevent injury or strain, use proper lifting and carrying techniques when moving unit.
When handling the air conditioner, be careful to avoid cuts from sharp metal fins on front and rear coils.
Make sure air conditioner does not fall during removal.
Shim (2EA)
6" 6"
9. To assemble trim, snap the tab of each piece into the slot of the other piece as shown below. Slide
trim over the front of the air conditioner until trim is flush with sleeve as shown below.
14 Room Air Conditioner
Operating Instructions
Operating Instructions
Controls
The controls will look like one of the following.
MODE TIMER POWER
FAN
SPEED
Fan
Heat
Energy
Saver
Cool
Timer
TEMP
'
F
F1 LOW F2 HIGH
REMOTE CONTROL SIGNAL RECEIVER
POWER
MODE
-
Push this button to shift mode of operation from COOL ENERGY SAVER FAN HEAT
- COOL:
Fan runs continually for normal cooling operation.
- ENERGY SAVER:
The fan stops when the compressor stops cooling. Approximately every 3 minutes the fan will turn on and the unit will check the room air temperature to determine if cooling is needed.
- FAN:
Fan-only operation.
- HEAT:
Fan runs continually for normal heating operation.
TIMER
- SHUT-OFF TIME
You will usually use shut-off time while you sleep.
If unit is running, use Timer to set number of hours until shut-off.
For your sleeping comfort, once Time is set, the Temperature
setting will raise 2°F after 30 min., and once again after another 30 min.
Push Timer button to advance setting from 1Hour → 2Hours → ... 12Hours maximum.
- START TIME
If unit is off, use Timer to set number of hours before unit starts.
Push Timer button to advance setting from 1Hour 2Hours ...
12Hours maximum.
TEMPERATURE SETTING
Use this button to automatically control the temperature of the room. The temperature can be set within a range of 60°F to 86°F by increments of 1°F.
The setting appears in the display.
To turn the air conditioner ON, push this button.
To turn the air conditioner OFF, push the button again.
This button takes priority over any other button.
FAN SPEED
Every time you push this button, it advances the setting as follows:
{High[ F2 ] Low[ F1 ] High[ F2 ]}
AUTO RESTART
When power is restored after an electrical power failure, the unit will begin to run at its last setting.
Service Manual 15
Operating Instructions
Remote control
The remote control and control panel will look like one of the following pictures.
Power
Temp
Fan Speed
Timer Mode
POWER
To turn the air conditioner ON, push this button. To turn the air conditioner OFF, push the button again.
This button takes priority over any other button.
TEMPERATURE SETTING
Use this button to automatically control the temperature of the room. The temperature can be set within a range of 60°F to 86°F by increments of 1°F.
The setting appears in the display.
FAN SPEED
Every time you push this button it advances the setting as follows:
{High[ F2 ] Low[ F1 ] High[ F2 ]}
TIMER
- SHUT-OFF TIME
You will usually use shut-off time while you sleep.
If unit is running, use Timer to set number of hours until shut-off.
For your sleeping comfort, once Time is set, the Temperature setting will
raise 2°F after 30 min, and once again after another 30 min.
Push Timer button to advance setting from 1Hour
2Hours → ... →
12Hours maximum.
- START TIME
If unit is off, use Timer to set of hours before unit starts.
Push Timer button to advance setting from 1Hour
2Hours → ... →
12Hours maximum.
MODE
- Push this button to shift mode of operation from COOL → ENERGY SAVER → FAN → Heat.
- COOL:
Fan runs continually for normal cooling operation.
- ENERGY SAVER:
The fan stops when the compressor stops cooling. Approximately every 3 minutes the fan will turn on and the unit will check the room air temperature to determine if cooling is needed.
- FAN:
Fan-only operation.
- HEAT:
Fan runs continually for normal heating operation.
When the air conditioner has been performed its cooling or heating operation and is turned off or set to the fan posi­tion, wait at least 3 minutes before resetting to the cooling operation again.
A slight heat odor may come from the unit when first switching to HEAT after the cooling season is over. This odor, caused by fine dust particles on the heater, will disappear quickly. This is harmless.
16 Room Air Conditioner
Operating Instructions
How to insert Batteries
1. Remove the cover from the back of the remote controller.
2. Insert two batteries.
Be sure that the (+) and (-) directions are correct.
Be sure that both batteries are new.
3. Re-attach the cover.
Do not use rechargeable batteries. Such batteries differ from standard dry cells in shape, dimensions, and performance.
Remove the batteries from the remote controller if the air conditioner is not going to be used for an extend­ed length of time.
Ventilation Control
Air Direction
Push the lever to the "CLOSE" position to cool, heat or recirculate room air only. Pull the lever to the "OPEN" position to exhaust smoke or stale air from the room. This feature is best used in conjunction with the FAN ONLY position.
The direction of air can be controlled by adjusting the horizontal and ver­tical louvers.
• HORIZONTAL AIR-DIRECTION CONTROL
The horizontal air direction is adjusted by moving the vertical louver. The lever for the vertical louver is located in the right and left side of the air discharge.
VERTICAL AIR-DIRECTION CONTROL
The vertical air direction is adjusted by moving the horizontal louver.
M
O
D E
T
I M
E
R
P
O
F A
N
S
P E
E
D
F a
n
H
e
a t
E
n
e r
g y
S
a v
e r
C
o
o l
T i
m
e r
T E
M
P
F 1 L
O W
F 2 H
I G H
PULL OPEN / PUSH CLOSE
M
O
D
E
T
I
M
E
R
FAN SPEE
F a
n
H
e
a t
E
n
e rg
y
S
a v
e r
C
o
o l
T
i m
e r
T
E
M
F
1 L
O
F
2 H
I
M
O D E
T
I M E
R
P
O W
E R
F A N
S
P E E
D
F a n H e a t
E n
e r g y
S
a v e r
C o o l
T
i m e r
T E M
P
'
F
F1 LOW F2 HI
GH
M
O D E
T
I M E
R
P
O W
E R
F A
N
S
P E
E D
F a n H e a t
E n
e r g y
S
a v e r
C o o l
T
i m e
r
T E
M P
'
F
F 1
L O W
F 2
H I G H
Service Manual 17
Disassembly Instructions
Disassembly Instructions
Mechanical Parts
Before the following disassembly, POWER SWITCH is set to OFF and disconnected the power cord.
1.
FRONT GRILLE
1. Open the inlet grille upward or downward.
2. Remove the screw which fastens the front grille.
3. Pull the front grille from the right side.
4. Remove the front grille. (See Fig. 24)
5. Re-install the component by referring to the removal procedure.
2. CABINET
1. After disassembling the FRONT GRILLE, remove the 9 screws which fasten the cabinet at the both sides and the top. (See Fig. 25) Keep these for later use.
3. CONTROL BOX
1. Remove the front grille. (Refer to section 1)
2. Remove the screw which fasten the control box. (See Fig. 26)
3. Pull the control box from the barrier.(See Fig.26)
4. Discharge the capacitor by placing a 20,000 ohm resistor across the capacitor terminals.
5. Disconnect two wire housings in the control box.
6. Pull the control box forward completely.
7. Re-install the components by referring to the removal procedure. (See Fig. 26) (Refer to the circuit diagram found on pages 24 in this manual and on the control box.)
FIG. 24
FIG. 26
FIG. 25
M
O
D
E
T
IM
E
R
P O
W E
R
F A
N S P
E
E
D
Fan
Energy Saver
Cool
Timer
T
E
M
P
'
F
F 1 L O
W
F 2 M E
D
F
3 H I G
H
MODE TIMER POWER
FAN
SPEED
Fan Heat
Energy Saver
Cool
Timer
TEMP
'
F
F1 LOW F2 HIGH
MODE
TIMER
POW
ER
F
A
N
S
P
E
E
D
F
a
n
H
e
a
t
E
n
e
r
g
y S
a
v
e
r
C
o
o
l
T
i
m
e
r
T
E
M
P
'
F
F1
LOW F
2
HI
G
H
M O D
E
T I M E R
P
O
W E
R
FA
N S PEED
F
a n
E n
e r g
y
S
a v e
r
C o
o l
T i m e
r
T
E
M P
'
F
F 1
L O W
F 2
M E D
F 3 H
I G H
18 Room Air Conditioner
Disassembly Instructions
4. ORIFICE, HEATER ASSY AND TURBO FAN
1. Remove the front grille. (Refer to section 1)
2. Remove the cabinet. (Refer to section 2)
3. Remove the 2 screws which fasten the evaporator at the left side and the right side. (See Fig. 27)
4. Move the evaporator sideward carefully.
5. Remove the 2 terminals carefully (See Fig. 28, at Electric Heater Model only)
6. Remove the 4 screws which fasten the orifice. (See Fig. 28)
7. Remove the orifice. (See Fig. 28)
8. Remove the clamp which secures the turbo fan with plier. (See Fig. 29)
9. Remove the turbo fan with plier or your hand with­out touching blades. (See Fig. 30)
10. Re-install the components by referring to the removal procedure, above.
5. FAN
1. Remove the cabinet. (Refer to section 2)
2. Remove the brace and shroud cover.
(Refer to section 4)
3. Remove the 6 screws which fasten the condenser.
4. Move the condenser sideways carefully.
5. Remove the clamp which secures the fan.
6. Remove the fan. (See Fig. 31)
7. Re-install the components by referring to the removal
procedure, above.
Air Handling Parts
MODE
TI
MER
P O
W E
R
F
A N
S
P
E E D
F
a n
E n
e r g
y S a
v e
r
C
o o
l
T
i m
e r
T E M
P
'
F
F1
L O W
F 2 M
E D
F 3 H
I G H
FIG. 27
FIG. 28
FIG. 29
FIG. 30
FIG. 31
Service Manual 19
6. SHROUD
1. Remove the fan. (Refer to section 5)
2. Remove the screw which fasten the shroud.
3. Remove the shroud. (See Fig. 32)
4. Re-install the component by referring to the removal procedure, above.
7. MOTOR
1. Remove the cabinet. (Refer to section 2)
2. Remove the clamp cord and disconnect a wire housing in control box. (Refer to section 3)
3. Remove the turbo fan. (Refer to section 5)
4. Remove the fan. (Refer to section 5)
5. Remove the 4 or 2 screws which fasten the motor. (See Fig. 33)
6. Remove the motor.
7. Re-install the components by referring to the removal procedure, above.
8. COMPRESSOR
1. Remove the cabinet. (Refer to section 2)
2. Discharge the refrigerant system using Freon
TM
Recovery System. If there is no valve to attach the recovery system, install one (such as a WATCO A-1) before venting the Freon
TM
. Leave the valve in place after
servicing the system.
3. Disconnect the 3 leads from the compressor.
4. After purging the unit completely, unbraze the suc­tion and discharge tubes at the compressor con­nections.
5. Remove the 3 nuts and the 3 washers which fas­ten the compressor. (See Fig. 34)
6. Remove the compressor.
7. Re-instill the components by referring to the removal procedure, above.
9. CAPACITOR
1. Remove the control box. (Refer to section 3)
2. Remove a screw which fasten the display panel.
3. Remove 2 screws and unfold the control box. (See Fig. 35)
4. Remove the screw and the clamp which fastens the capacitor. (See Fig. 35)
5. Disconnect all the leads of capacitor terminals.
6. Re-install the components by referring to the removal procedure, above.
Disassembly Instructions
Electrical Parts
FIG. 32
FIG. 34
FIG. 35
MODE
TIMER
POWER
FAN
SPEED
Fan
Energy
Saver
Cool
Timer
TEM
P
'
F
F1 LO
W
F2 M
ED F 3 HIG
H
FIG. 33
20 Room Air Conditioner
Disassembly Instructions
10. POWER CORD
1. Remove the control box. (Refer to section 3)
2. Unfold the control box. (Refer to section 9)
3. Disconnect the grounding screw from the control box.
4. Disconnect 2 receptacles.
5. Remove a screw which fastens the clip cord.
6. Pull the power cord. (See Fig. 36)
7. Re-install the component by referring to the removal procedure, above. (Use only one ground-marked hole for ground connection.)
8. If the supply cord of this appliance is damaged, it must be replaced by the special cord. (The special cord means the cord which has the same specification marked on the supply cord fit­ted to the unit.)
11. THERMOSTAT
1. Remove the control box. (Refer to section 3)
2. Unfold the control box. (Refer to section 9)
3. Disconnect the theristor terminals from main P.W.B assembly.
4. Remove the thermostat. (See Fig. 37)
5. Re-install the components by referring to the removal procedure, above.
MODE
TIMER
POWER
FAN
SPEED
Fan
Energy
Saver
Cool
Timer
TEMP
'
F
F 1 L
O W
F 2 M
ED F 3 H
IG
H
MODE
TIMER
POWER
FAN
SPEED
Fan
Energy
Saver
Cool
Timer
TEMP
'
F
F 1 L
O
W
F 2 M
E
D
F 3
H
IG
H
FIG. 36
FIG. 37
Service Manual 21
Disassembly Instructions
12. CONDENSER
1. Remove the cabinet. (Refer to section 2)
2. Remove the brace and the shroud cover. (Refer to section 4)
3. Remove the 5 screws which fasten the condenser.
4. After discharging the refrigerant completely, unbraze the interconnecting tube at the condenser connections.
5. Remove the condenser.
6. Re-install the components by referring to notes. (See Fig. 38)
13. EVAPORATOR
1. Remove the cabinet. (Refer to section 2)
2. Discharge the refrigerant completely.
3. Remove the 2 screws which fasten the evaporator at the left side and the right side.
4. Move the evaporator sideward carefully and then unbraze the interconnecting tube at the evaporator connectors.
5. Remove the evaporator.
6. Re-install the components by referring to notes. (See Fig. 39)
14. CAPILLARY TUBE
1. Remove the cabinet. (Refer to section 2)
2. After discharging the refrigerant completely, unbraze the interconnecting tube at the capillary tube.
3. Remove the capillary tube.
4. Re-install the components by referring to notes.
FIG. 38
FIG. 39
Refrigerating Cycle
Discharge the refrigerant system using Freon
TM
Recovery System. If there is no valve to attach the recovery system, install one (such as a WATCO A-1) before vent­ing the Freon
TM
. Leave the valve in place after
servicing the system.
CAUTION
M O
D
E
T
I M
E R
P O
W E
R
F A
N
S
P E
E D
Fan
Energy Saver
Cool
Timer
T
E
M P
'
F
F 1
L O W
F 2 M
ED F 3
H
IG
H
22 Room Air Conditioner
Disassembly Instructions
Replacement of the refrigeration cycle.
1. When replacing the refrigeration cycle, be sure to discharge the refrigerant system using a Freon
TM
recovery System. If there is no valve to attach the recovery system, install one (such as a WATCO A-1) before venting the FreonTM. Leave the valve in place after servicing the system.
2. After discharging the unit completely, remove the desired component, and unbrace the pinch-off tubes.
3. Solder service valves into the pinch-off tube ports, leaving the valves open.
4. Solder the pinch-off tubes with Service valves.
5. Evacuate as follows.
1) Connect the vacuum pump, as illustrated Fig.
40A.
2) Start the vacuum pump, slowly open manifold
valves A and B with two full turns counterclock­wise and leave the valves closed. The vacuum pump is now pulling through valves A and B up to valve C by means of the manifold
and entire system.
3) Operate the vacuum pump for 20 to 30 minutes,
until 600 microns of vacuum is obtained. Close valves A and B, and observe vacuum gauge for a few minutes. A rise in pressure would indicate a possible leak or moisture remaining in the system. With valves A and B closed, stop
the vacuum pump.
4) Remove the hose from the vacuum pump and
place it on the charging cylinder. See Fig. 40B. Open valve C. Discharge the line at the manifold connection.
5) The system is now ready for final charging.
6. Recharge as follows :
1) Refrigeration cycle systems are charged from the High-side. If the total charge cannot be put in the High-side, the balance will be put in the suction line through the access valve which you installed as the system was opened.
2)
Connect the charging cylinder as shown in Fig. 40B. With valve C open, discharge the hose at the man­ifold connection.
3) Open valve A and allow the proper charge to enter the system. Valve B is still closed.
4) If more charge is required, the high-side will not take it. Close valve A.
5) With the unit running, open valve B and add the balance of the charge.
a. Do not add the liquid refrigerant to the Low-
side.
b. Watch the Low-side gauge; allow pressure to
rise to 30 lbs. c. Turn off valve B and allow pressure to drop. d. Repeat steps B and C until the balance of the
charge is in the system.
6) When satisfied the unit is operating correctly, use the pinch-off tool with the unit still running and clamp on to the pinch-off tube. Using a tube cutter, cut the pinch-off tube about 2 inches from the pinch-off tool. Use sil-fos solder and solder pinch-off tube closed. Turn off the unit, allow it to set for a while, and then test the leakage of the pinch-off connection.
NOTICE
If high vacuum equipment is used, just crack valves A and B for a few minutes, then open slowly with the two full turns counterclockwise. This will keep oil from foaming and being drawn into the vacuum pump.
CAUTION
Service Manual 23
Disassembly Instructions
Equipment needed: Vacuum pump, Charging cylinder, Manifold gauge, Brazing equipment. Pinch-off tool capa­ble of making a vapor-proof seal, Leak detector, Tubing cutter, Hand Tools to remove components, Service valve.
A
COMPOUND GAUGE
EVAPORATOR (LOW PRESSURE SIDE)
COMPRESSOR
CAPILLARY TUBE
CONDENSER (HIGH PRESSURE SIDE)
SEE INSETS
BELOW
MANIFOLD
GAUGE
B
FIG. 40A-Pulling Vacuum
FIG 40B-Charging
A
B
EXTERNAL VACUUM PUMP
LOW
B
HI
A
CHARGING CYLINDER
C
24 Room Air Conditioner
Schematic Diagram
Schematic Diagram
Wiring Diagram
ELECTRIC HEATING MODEL
Service Manual 25
Troubleshooting Guide
Troubleshooting Guide
Piping System
Following is a brief description of the important components and their functions in the refrigeration system. Refer to Fig. 41 to follow the refrigeration cycle and the flow of the refrigerant in the cooling cycle.
MOTOR
COMPRESSOR
OIL
(LIQUID REFRIGERANT)
CAPILLARY TUBE
OUTSIDE COOLING AIR FOR REFRIGERANT PASS THROUGH
SUCTION LIME COOL LOW PRESSURE VAPOR
COOLED AIR
COMPLETE LIQUID BOIL OFF POINT
LIQUID PRESSURE DROP
ROOM AIR HEAT LOAD
VAPOR INLET
HOT DISCHARGED AIR
LIQUID OUTLET
HIGH PRESSURE VAPOR LIQUID PEFRIGERANT LOW PRESSURE VAPOR
ROOM AIR CONDITIONER
EVAPORATOR COILS CONDENSER COILS
CYCLE OF REFRIGERATION
FIG. 41
CONDENSER COILS
FAN
CAPILLARY TUBE
MOTOR
COMPRESSOR
TURBO FAN
EVAPORATOR COILS
: REFRIGERANT FLOW
26 Room Air Conditioner
Troubleshooting Guide
Troubleshooting Guide
In general, possible trouble is classified in two causes. The one is called Starting Failure which is caused from an electrical defect, and the other is Ineffective Air Conditioning caused by a defect in the refrigeration circuit and improper application.
Unit is running but cooling is ineffective
Ineffective Cooling
Check of outdoor coil (heat exchanger) & the fan operation.
Check gas leakage.
Repair gas leak.
Replacement of unit if the unit is beyond repair.
Satisfactory operation with temperature difference of inlet & outlet air ; 44.6~50˚F
Check heat load increase.
Unexpected residue
Overloaded Circuit
Check of inside gas pressure.
Adjusting of refrigerant charge
Malfunction of compressor
Replacement of compressor
Check of cold air circulation for smooth flow.
Dirty indoor coil (Heat exchanger)
Malfunction of fan
Clogged of air filter
Obstruction at air outlet
Correct above trouble
Stop of auto air-swing
Check clogging in refrigeration circuit.
Repair clogging in refrigeration circuit.
Service Manual 27
Troubleshooting Guide
Fails to Start
Check of circuit breaker and fuse.
Gas leakage of feeler bulb of thermostat
Check of control switch.
Only fan fails to start.
Improper wiring.
Defect of fan motor capacitor.
Irregular motor resistance ( ). Irregular motor insulation ( ).
Replacement of fan motor
Regular but fails to start
Replacement of compressor (locking of rotor, metal)
Improper thermostat setting
Loose terminal connection.
Improper wiring
Irregular motor resistance ( )
Irregular motor insulation ( )
Replacement of compressor (Motor damaged)
Drop of power voltage.
Check capacitor.
Replacement.
Only compressor fails to start.
Defect of compressor capacitor.
Check of power source.
Check of control switch setting.
28 Room Air Conditioner
Troubleshooting Guide
COMPLAINT CAUSE REMEDY
Check voltage at outlet. Correct if none. Check voltage to rotary switch. If none, check
power supply cord. Replace cord if circuit is open. Check switch continuity. Refer to wiring diagram
for terminal identification. Replace switch if defective.
Connect wire. Refer to wiring diagram for terminal identification. Repair or replace loose terminal.
Test capacitor. Replace if not within ±10% of manufacturer's rating. Replace if shorted, open, or damaged.
Fan blade hitting shroud or blower wheel hitting scroll. Realign assembly.
Units using slinger ring condenser fans must have 1/4to 5/16inch clearance to the base. If it is hitting the base, shim up the bottom of the fan motor with mounting screw(s).
Check fan motor bearings; if motor shaft will not rotate, replace the motor.
Check voltage. See limits on this page. If not within limits, call an electrician.
Test capacitor. Check bearings. Does the fan blade rotate freely? If not, replace fan motor.
Pay attention to any change from high speed to low speed. If the speed does not change, replace the motor.
Check grommets; if worn or missing, replace them. If cracked, out of balance, or partially missing,
replace it. If cracked, out of balance, or partially missing,
replace it. Tighten it. If knocking sounds continue when running or
loose, replace the motor. If the motor hums or noise appears to be internal while running, replace motor.
No power Power supply cord
Rotary switch
Wire disconnected or connection loose
Capacitor (Discharge capacitor before testing.)
Will not rotate
Revolves on overload.
Grommets Fan
Turbo fan
Loose set screw Worn bearings
Fan motor will not run.
Fan motor runs intermittently
Fan motor noise.
Service Manual 29
Troubleshooting Guide
NAME PLATE RATING MINIMUM MAXIMUM
115V 103.5V 126.5V
208/230V 187V 253V
COMPLAINT CAUSE REMEDY
Check voltage. See the limits on the preceding. page. If not within limits, call an electrician.
Check the wire connections, if loose, repair or replace the terminal. If wires are off, refer to wiring diagram for identification, and replace. Check wire locations. If not per wiring diagram, correct.
Check for continuity, refer to the wiring diagram for terminal identification. Replace the switch if circuit is open.
Check the position of knob If not at the coldest setting, advance the knob to this setting and restart unit. Check continuity of the thermostat. Replace thermostat if circuit is open.
Check the capacitor. Replace if not within ±10% of manufacturers rating. Replace if shorted, open, or damaged.
Check the compressor for open circuit or ground. If open or grounded, replace the compres­sor.
Check the compressor overload, if externally mounted. Replace if open. (If the compressor temperature is high, remove the overload, cool it, and retest.)
Voltage
Wiring
Rotary
Thermostat
Capacitor (Discharge capacitor before servicing.)
Compressor
Overload
Compressor will not run, but fan motor runs.
ROOM AIR CONDITIONER VOLTAGE LIMITS
30 Room Air Conditioner
COMPLAINT CAUSE
REMEDY
Check the voltage. See the limits on the preced­ing page. If not within limits, call an electrician.
Check overload, if externally mounted. Replace if open. (If the compressor temperature is high, remove the overload, cool, and retest.)
If not running, determine the cause. Replace if required.
Remove the cabinet. inspect the interior surface of the condenser; if restricted, clean carefully with a vacuum cleaner (do not damage fins) or brush. Clean the interior base before reassembling.
If condenser fins are closed over a large area on the coil surface, head pressures will increase, causing the compressor to cycle. Straighten the fins or replace the coil. Test capacitor. Check the terminals. If loose, repair or replace. Check the system for a restriction. If restricted, clean of replace. Close if open. Determine if the unit is properly sized for the area to be cooled. Check the set screw or clamp. If loose or missing, correct. If the blower or fan is hitting air guide, rearrange the air handling parts. Remove the cabinet and carefully rearrange tubing not to contact cabinet, compressor, shroud, and bar­rier.
Voltage
Overload
Fan motor
Condenser air flow restriction
Condenser fins (damaged)
Capacitor Wiring Refrigerating system Air filter Exhaust damper door Unit undersized
Blower or fan
Copper tubing
Compressor cycles on overload.
Insufficient cooling or heat­ing
Excessive noise.
Troubleshooting Guide
Service Manual 31
Product Specifications
ITEMS
COOLING
HEATING
OPERATING TEMPERATURE
REFRIGERANT (R-22) CHARGE(g) EVAPORATOR CONDENSER FAN, INDOOR FAN, OUTDOOR FAN SPEEDS (FAN/COOLING/HEATING) FAN MOTOR OPERATION CONTROL ROOM TEMP. CONTROL
AIR DIRECTION CONTROL CONSTRUCTION ELECTRIC HEATER
PROTECTOR
POWER CORD DRAIN SYSTEM
NET WEIGHT (lbs/kg)
DIMENSION (W x H x D)
SLEEVE DIMESION (W x H x D)
SLEEVE DEPTH WITH FRONT GRILLE
MODELS
POWER SUPPLY CAPACITY (Btu/h) INPUT (W) RUNNING CURRENT (A) E.E.R. (Btu/W.h) CAPACITY (Btu/h) INPUT (W) RUNNING CURRENT (A)
COOLING
HEATING
COMPRESSOR FAN MOTOR ELECTRIC HEATER
INDOOR (°C) OUTDOOR (°C) INDOOR (°C) OUTDOOR (°C)
(inch) (mm) (inch) (mm) (inch)
(mm)
REMARK BGE-103A  BGE-123A  REMARK
1Ø, 208/ 230V, 60Hz
9,800/10,000
1,040/1,060
5.2/4.7
9.4/9.4 9,200/11,200
2,900/3,500
14.0/15.3
26.7 (DB) 19.4 (WB) 35 (DB) 23.9 (WB)
21.1 (DB) 15.6 (WB)
8.3 (DB) 6.1 (WB)
3 ROW 12 STACKS
2 ROW 17 STACKS, L-BENDED TYPE
TURBO FAN
PROPELLER TYPE FAN WITH SLINGER-RING
2 / 2 / 2
TOUCH PANEL
THERMISTOR
VERTICAL LOUVER (RIGHT & LEFT)
HORIZONTAL LOUVER (UP & DOWN)
TOP-DOWN
3.5KW, 230V
EXTERNAL OVERLOAD PROTECTOR
INTERANL THERMAL PROTECTOR
FUSE LINK, BIMETAL THERMOSTAT
1.92m (3 WIRE WITH GROUDING)
ATTACHMENT PLUG (CORD-CONNECTED TYPE)
SPLASHED BY FAN SLINGER
21/32 x 14 13/32 x 1921/32
24
626 x 366 x 499
257/8 x 1517/32 x 1623/32
656 x 394 x 425
11,200/11,500
1,270/1,310
6.4/6.0
8.8/8.8
500(17.6 OZ)465(16.40 OZ)
LOUVERED-
FIN TYPE
4 POLES6 POLES
80/3678/3
OPTIONA PART
20
510
Specifications and performance data subject to change without notice.
HEAT CONTROLLER, INC.
1900 WELLWORTH AVENUE • JACKSON, MICHIGAN 49203
THE QUALITY LEADER IN CONDITIONING AIR
P/No.: 3828A20040M
04/18/07
Loading...