Heat Controller 7602-443 User Manual

INSTALLATION MANUAL
7602-443 Communicating,
Programmable Thermostat
Heat Controller, Inc. • 1900 Wellworth Ave. • Jackson, MI 49203 • (517)787-2100 • www.heatcontroller.com
TABLE OF CONTENTS
Section Title Page Safety/Installation Considerations 3
1.0 User Menu Settings 4
2.0 Installer Menu Settings 6
2.1 Installer Menu Settings Access 6
3.0 System Confi guration 7
3.1 Airfl ow Selection 7
3.2 Option Selection 7
4.0 Accessory Confi guration 10
4.1 Air Filter 10
4.2 Humidifi er 10
4.3 UV Lamp 10
4.4 Air Cleaner 10
5.0 Input Dealer Information 10
6.0 Humidity Confi guration 10
7.0 Temperature Algorithm 10
8.0 Demand Reduction Confi guration 1 1
9.0 Service Mode 11
9.1 Manual Operation 11
9.2 Control Diagnostics 12
9.3 Dipswitch Confi guration 12
9.4 Fault History 13
9.5 Clear Fault History 14
9.6 Multi-Unit Diagnostics 14
9.7 Multi-Unit Fault Information 14
10.0 Restore Defaults 14
11.0 Revision History 16
Heat Controller, Inc. 7602-443 COMMUNICATING, PROGRAMMABLE THERMOSTAT Installation Manual
The 7602-443 Communicating, Programmable Thermostat is the perfect compliment to a Geothermal Heat Pump System and represents a signifi cant advancement in thermostat communicating technology. For homeowners, the 7602­443 provides highly customizable climate control features designed to maximize comfort and reduce the amount of energy consumed by the Geothermal Heat Pump System. For dealers, it represents a signifi cant advancement in con- guration, monitoring and diagnostics from the thermostat. Please read the following instructions carefully to maximize the comfort and cost-saving potential of your Geothermal Heat Pump System.
SAFETY CONSIDERATIONS
Improper wiring or installation may damage thermostat. Wir­ing must conform to local and national electrical codes
WARNING!
WARNING! power to unit. There may be more than one power disconnect. Electrical shock can cause personal injury or death.
INSTALLATION CONSIDERATIONS
The thermostat requires no batteries. The thermostat is not a power stealing device and MUST have both R and C termi­nals connected. See Diagram 1.
Before installing thermostat, turn off all
a time. Be careful not to allow wires to fall back into the wall.
C. As each wire is disconnected, record wire color
and terminal marking.
D. Discard or recycle old thermostat.
NOTE: Mercury is a hazardous waste and MUST be dis­posed of properly.
3. Separate the thermostat from base.
4. Route thermostat wires through hole in base. Level base against wall (for aesthetic value only - thermo­stat need not be leveled for proper operation) and mark wall through 2 mounting holes.
5. Drill two 3/16-in. mounting holes in wall where marked. (Note: Mounting holes on thermostat are designed to fi t on a horizontal J-box).
6. Secure base to wall with 2 anchors and screws provided making sure all wires extend through hole in base.
7. Connect wires to proper terminal of the connector block in the thermostat.
8. Push any excess wire back into wall. Excess wire inside the thermostat case can interfere with proper air fl ow across the temperature sensor. Seal hole in wall to prevent air leaks. Leaks can affect operation.
9. Install thermostat on base.
10. Turn on power to the unit.
III. WIRING DIAGRAMS
All excess wire should be pushed back into the wall as far as possible. Excess wire inside the thermostat plastic case may interfere with the air fl ow across the temperature sensor.
Diagram 1: Thermostat Connections
INSTALLATION I. THERMOSTAT LOCATION
Thermostat should be mounted:
• Approximately 5 ft. (1.5m) above fl oor .
• Close to or in a frequently used room, preferably on an inside partitioning wall.
• On a section of wall without pipes or duct work.
Thermostat should NOT be mounted:
• Close to a window, on an outside wall, or next to a door leading to the outside.
• Exposed to direct light and heat from a lamp, sun, replace, or other temperature-radiating object which may cause a false reading.
• Close to or in direct airfl ow from supply registers.
• In areas with poor air circulation, such as behind a door or in an alcove.
II. THERMOSTAT INSTALLATION
1. Turn off all power to unit.
2. If an existing thermostat is being replaced:
A. Remove existing thermostat from wall.
B. Disconnect wires from existing thermostat, one at
ATC32U** Thermostat
7602-443
24Vac Common
24Vac Hot
Comm +
C
Comm -
R
Thermostat Connections
C 24V Common for Control Circuit R 24V Supply for Control Circuit A+ Communications (Positive) B – Communications (Negative) GND Ground OD Outdoor Temperature Sensor ID Indoor Temperature Sensor
3
A+
B-
OD
GND
ID
DXM2
Control
Gnd
A+
B-
24V
Outdoor
Sensor
(Optional)
Remote Indoor
Sensor
(Optional)
Installation Manual 7602-443 COMMUNICATING, PROGRAMMABLE THERMOSTAT Heat Controller, Inc.
1.0 User Menu Settings
1.1 OFFSETS
If you fi nd that the temperature displayed on the
thermostat does not accurately represent the room temperature where the thermostat is located, this offset function compensates for the difference. The thermostat will apply an offset between what temperature the thermostat is measuring versus the temperature that is displayed.
1.1.1 TEMPERATURE OFFSET
The Temperature Offset function allows for
calibration of the temperature sensor.
Adjust the Temperature Offset settings using the
up/down arrow buttons. Press the center button to save changes.
• Indoor Temperature (default 0°F): options:
-5°F to +5°F (in 1°F increments)
• Remote Temperature (default 0°F): options:
-5°F to +5°F (in 1°F increments)
• Outdoor Temperature (default 0°F): options:
-5°F to +5°F (in 1°F increments)
1.1.2 ANTICPATOR
If you fi nd that the thermostat is overshooting or
undershooting the temperature setpoint value, the Anticipator setting allows for adjustment to correct the temperature algorithm. When the Anticipator value is set to a lower number, the thermostat becomes more sensitive and when the Anticipator value is raised, the thermostat becomes less sensitive. If the thermostat is overshooting the temperature setpoint, adjust the Anticipator value up to reduce thermostat sensitivity. If the thermostat is undershooting the temperature setpoint, adjust the Anticipator value down to increase thermostat sensitivity.
Adjust the Anticipator setting using the up/down
arrow buttons. Press the center button to save changes.
• Anticipator (default 3): valid range: 1 to 9
1.1.3 DIFFERENTIAL
The Differential adjustment will vary the number of
degrees from the setpoint before a call for heating or cooling is made. Use this function if you fi nd that the thermostat is starting a call too soon/late or staging equipment up/down too quickly/slowly. For example, with a 1 ˚F 1st stage differential and a heating setpoint of 70˚F, your thermostat will not call for heating until the temperature is 69˚F.
Adjust the Differential setting using the up/down
arrow buttons. Navigate between Differentials using the left/right arrow buttons. Press the center button to save changes.
• 1st Stage (default 1°F): options: 1°F to 4°F (in 1°F increments)
• 2nd Stage (default 1°F): options: 1°F to 4°F (in 1°F increments)
• Aux Heat (default 1°F): options: 1°F to 4°F (in 1°F increments)
NOTE 1: The thermostat must be confi gured for
Multistage by installer to access the 2nd Stage Differential setting. The thermostat must be confi gured for Auxiliary Heat by installer to access the Auxiliary Heat Differential setting.
NOTE 2: The temperature control algorithm must
be confi gured for Differential control to access the Differential settings by installer.
1.1.4 HUMIDITY OFFSET
If you fi nd that the Humidity level displayed on
the thermostat does not accurately represent the Humidity level of the room in which the thermostat is located, use the Humidity Offset function to calibrate the humidity sensor.
Adjust the Humidity Offset setting using the up/
down arrow buttons. Press the center button to save changes.
Indoor Humidity (default 0%): options:
-10% to +10% (in 1% increments)
1.2 CYCLES PER HOUR
The thermostat allows the user to adjust the maximum
number of on/off cycles per hour to maintain the desired indoor temperature.
Adjust the Cycles per Hour setting using the up/
down arrow buttons. Press the center button to save changes.
• 4 (default): operation will start no sooner than 15 minutes after the previous call was initiated
• 6: operation will start no sooner than 10 minutes after the previous call was initiated (can provide tighter temperature control)
1.3 AUTO CHANGEOVER TIME
When the thermostat is confi gured for AUTO mode,
the thermostat automatically selects heating or cooling mode depending on the indoor temperature. The Auto Changeover Time is the amount of time that elapses before operation switches from heating to cooling mode or from cooling to heating mode.
Adjust the Auto Changeover Time using the up/
down arrow buttons. Press the center button to save changes.
• Auto Change Over Time (default 15 minutes): options: 0 to 120 minutes (in 15 minute increments)
4
Heat Controller, Inc. 7602-443 COMMUNICATING, PROGRAMMABLE THERMOSTAT Installation Manual
1.4 DEMO MODE
Demo mode is designed to showcase heat pump
operation when the unit is connected to an above ground water loop with the supply air being blown directly over the water loop.
1.4.1 ENTER DEMO MODE
To enter Demo Mode, navigate to the Service
Information screen (Menu>Settings>Service Information) then press and hold the right arrow for 5 seconds
SERVICE INFORMATION
FAULT STATUS
TEMPERATURE STATUS CLEAR FAULT HISTORY SYSTEM STATUS
SELECT OPTION
PREVIOUS
1.4.2 DEMO MODE OPERATION
Control Demo Mode operation parameters from the
Demo Operation screen shown below.
The starting mode (heating or cooling) depends
on the loop temperature at the time when Demo Mode is entered. The unit will operate in heating or cooling based upon the following algorithm.
Start in Cooling Mode Start in Heating Mode
90°F
70°F
50°F
Solid lines represent heating operation. Dashed lines represent cooling operation.
1.4.3 EXITING DEMO MODE
To exit demo mode, remove power to the
thermostat.
DEMO OPERATION
OUTDOOR FAN AUTO
78% HEATING
RH 36% HUMID ON
72%
AUTO
SETPOINT HEAT 70 COOL 74
RH TEMP MODE FAN MENU
5
Installation Manual 7602-443 COMMUNICATING, PROGRAMMABLE THERMOSTAT Heat Controller, Inc.
2.0 Installer Menu Settings
2.1 INSTALLER MENU SETTINGS ACCESS
The Installer Settings can be accessed at any time from the Main Operating screen by holding the up/down arrows simul­taneously for 5 seconds while the thermostat is in OFF Mode.
Installer Menu Settings Overview
Thermostat Confi guration System Confi guration Airfl ow Selection Option Selection Unit Confi guration Valve Confi guration Accessory Confi guration Air Filter Humidifi er UV Lamp Air Cleaner Input Dealer Information Humidity Confi guration T emperature Algorithm Demand Reduction Confi guration Service Mode Manual Operation Control Diagnostics Dipswitch Confi guration Fault History Clear Fault History Restore Defaults
2.2.1 STAGING
Adjust the staging option using the up/down arrow buttons. Press the center button to save changes.
• Single Stage – for control of a single stage compressor applications
• Multi-Stage (default) – for control of multi- stage compressor applications
THERMOSTAT
CONFIGURATION
SINGLE STAGE
MULTI STAGE
SELECT OPTION
PREVIOUS SAVE
2.2.2 AUXILIARY HEAT
Adjust the Auxiliary Heat options using the up/down arrow buttons. Press the center button to save changes.
• Electric (default) – for control of a system with electric auxiliary heat
• Multi-Fuel – for control of a system with furnace for auxiliary heat
• No Auxiliary Heat – for control of a system with no auxiliary heat
THERMOSTAT
CONFIGURATION
ELECTRIC
MULTI FUEL
NO AUXILIARY HEAT
2.2 THERMOSTAT CONFIGURATION
Upon initial power up, the communicating thermostat will prompt the installer for the thermostat confi guration settings.
INSTALLER SETTINGS
THERMOSTAT CONFIG
SYSTEM CONFIG ACCESSORY CONFIG INPUT DEALER INFO HUMIDITY CONFIG TEMPERATURE CONTROL DEMAND REDUCTION CNFG SERVICE MODE RESTORY DEFAULTS
DXM2 1.0 ATC32U01 C 2.1 SELECT OPTION
PREVIOUS
SELECT OPTION
PREVIOUS SAVE
2.2.2.1 AUXILIARY HEAT CONFIGURATION
Select Electric Auxiliary Heat mode
• Auxiliary Heat to Supplement Pump
• Auxiliary Heat for Emergency Heat Only
THERMOSTAT
CONFIGURATION
AUXILIARY HEAT TO SUPPLEMENT HEAT PUMP
AUXILIARY HEAT FOR EMERGENCY HEAT ONLY
SELECT OPTION
PREVIOUS SAVE
6
Heat Controller, Inc. 7602-443 COMMUNICATING, PROGRAMMABLE THERMOSTAT Installation Manual
2.2.3 PROGRAMMING
Adjust the Programming options using the up/down arrow buttons. Press the center button to save changes.
• Programmable (default) – enables 7-day programming
• Non-Programmable – disables 7-day programming
• Night Setback – enables night setback programming NOTE: When the thermostat is confi gured for non- programmable mode, the Display Date and Time setting defaults to NO.
THERMOSTAT
CONFIGURATION
PROGRAMMABLE
NON PROGRAMMABLE
NIGHT SETBACK
SELECT OPTION
PREVIOUS SAVE
3.0 System Confi guration
Use the System Confi guration option on the start-up screen to adjust critical equipment settings.
The System Confi guration information will be automatically obtained from each communicating control in the system.
Note 1: The Airfl ow Selection menu (section 3.1) will not be present if the connected communicating control is confi gured for No Blower.
Note 2: The Valve Confi guration menu (section 3.4) will not be present if the connected communicating control is confi gured for No Loop Confi guration (OTHER).
SYSTEM CONFIGURATION AIRFLOW SELECTION OPTION SELECTION UNIT CONFIG HE024 PUMP CONFIGURATION
SELECT OPTION
PREVIOUS SAVE
3.1 AIRFLOW SELECTION Adjust the airfl ow settings for each system operating mode using the up/down arrow buttons. Press the center button to select each item.
Airfl ow Settings (defaults stored in control) - valid range: obtained from control (in 25 CFM increments)
• Blower Off Delay (default 60 seconds) – valid range: 0 to 255 seconds (in 5 second increments)
NOTE 1: The Airfl ow Settings will only be present if the connected communicating control is confi gured for ECM blower.
NOTE 2: If multiple units are connected to one thermostat, refer to section 3.5 for unit selection.
CFM
AIRFLOW SELECTION
HEAT STAGE 1 600
HEAT STAGE 2 750 AUXILIARY HEAT 850 EMERGENCY HEAT 850 COOL STAGE 1 525 COOL STAGE 2 700 COOL DEHUMID 1 425 COOL DEHUMID 2 550 CONTINUOUS FAN 350 HEAT OFF DELAY 60 COOL OFF DELAY 30
PREVIOUS NEXT
INSTALLER SETTINGS
THERMOSTAT CONFIG
SYSTEM CONFIG
ACCESSORY CONFIG INPUT DEALER INFO HUMIDITY CONFIG TEMPERA TURE ALGORITHM DEMAND REDUCTION CNFG SERVICE MODE RESTORY DEFAULTS
ATC32U01 SELECT OPTION
PREVIOUS
3.2 OPTION SELECTION
This option allows the confi guration of heat pump options to be modifi ed.
Adjust the Option settings using the up/down arrow buttons. Press the center button to select each item.
• Motorized Valve (defaults stored in control) valid range: Off, On
“On” delays compressor start until the valve is fully open.
NOTE: “Motorized V alve” used here refers to a two-position motorized water valve, not to be confused with the modulating motorized water valve found in the LOOP CONFIG.
7
Installation Manual 7602-443 COMMUNICATING, PROGRAMMABLE THERMOSTAT Heat Controller, Inc.
Compressor ASCD (Anti-Short Cycle Delay (default stored in control) – valid range: 5 to 8
(in 1 minute increments)
NOTE 1: The Compressor Anti-Short Cycle Delay setting provides equipment protection by forcing the compressor to wait a few minutes before restarting.
NOTE 2: If multiple units are connected to one thermostat, refer to section 3.5 for unit selection.
CAUTION!
CAUTION! This is a Commercial option only and does not alter Residential unit operation.
OPTION SELECTION
MOTORIZED VALVE OFF
COMPRESSOR ASCD 5
3.4 VALVE CONFIGURATION
Confi gure temperature differentials at the thermostat for Integrated Variable Speed Water Flow Control units with a motorized modulating valve.
Adjust the Valve Confi guration settings using the up/down arrow buttons. Press the center button to select each item.
• Heating Delta T (default stored in control) –
valid range: 4 to 12ºF (in 1ºF increments)
• Cooling Delta T (default stored in control) –
valid range: 9 to 20ºF (in 1ºF increments) NOTE 1: Minimum and Maximum degree values are shown
only when the control is confi gured with the appropriate values.
NOTE 2: Refer to section 3.6.3 for multi-unit confi guration instructions.
MODULATING VALVE
CONFIGURATION
DEG
HEATING DELTA T 8
COOLING DELTA T 15
PREVIOUS NEXT
3.3 UNIT CONFIGURATION
Adjust the Unit Confi guration settings including Heat Pump Family, Heat Pump Size, Blower Type, and Loop Confi guration using the up/down arrow buttons. Press the center button to select each item.
• Heat Pump Family (default stored in control) –
valid range: HTS, HE
• Heat Pump Size (default stored in control) – valid range: depends on Heat Pump Family setting
• Blower Type (default stored in control) – valid
range: NONE, ECM
Loop Confi g (default stored in control) – valid range: Other, MOD VALVE
NOTE: Refer to section 3.5.3 for multi-unit con guration
instructions.
UNIT CONFIGURATION CURRENT CONFIG HE024
HEAT PUMP FAMILY HE
HEAT PUMP SIZE 024 BLOWER TYPE ECM LOOP CONFIG OTHER
PREVIOUS NEXT
3.4.1 MODULATING VALVE OFF POSITION
Click Next from section 3.5 to select the off position
value for the modulating valve.
NOTE: For certain commercial multi-unit
applications, the modulating valve can be kept slightly open by choosing values 3.3-4.0.
MODULATING VALVE
CONFIGURATION
OFF POSITION 3.8
PREVIOUS SELECT
SELECT OPTION
PREVIOUS SAVE
8
Heat Controller, Inc. 7602-443 COMMUNICATING, PROGRAMMABLE THERMOSTAT Installation Manual
3.5 MULTI-UNIT CONFIGURATION
If multiple units are connected to one ATC thermostat upon unit start-up, the thermostat will automatically register the serial numbers of all units connected to it.
NOTE: Multiple units may be connected directly to the ATC thermostat or connected to one another in series, as shown by the fi gure below.
Or
3.5.2 MULTI-UNIT OPTION SELECTION
In section 3.2, when an installer selects “Option
Selection” from the System Confi guration menu, the installer may choose the unit to confi gure by the last 4 digits of its serial number from the following screen.
OPTION SELECTION
HE024 S N - - - - - 1 2 3 4 HE024 S N - - - - - 5 6 7 8 HE036 S N - - - - - 9 0 1 2
PREVIOUS SELECT
3.5.3 Multi-Unit, Unit, & Valve Confi guration
To confi gure Unit and Valve options in sections 3.3-
3.4, the thermostat must be connected to only one unit at a time.
Two connections on DXM2 board to allow for multi-unit installation
3.5.1 MULTI-UNIT AIRFLOW SELECTION
In section 3.1, when an installer selects “Airfl ow
Selection” from the System Confi guration menu, the installer may choose the unit to confi gure by the last 4 digits of its serial number from the following screen.
AIRFLOW SELECTION
HE024 S N - - - - - 1 2 3 4 HE024 S N - - - - - 5 6 7 8 HE036 S N - - - - - 9 0 1 2
PREVIOUS SELECT
9
Installation Manual 7602-443 COMMUNICATING, PROGRAMMABLE THERMOSTAT Heat Controller, Inc.
4.0 Accessory Confi guration
A service message will fl ash at the top of the Main screen when a service timer expires to alert the user that it is time to service these options. Refer to DXM2 AOM for instructions on confi guring DIP switches to confi gure accessories. Follow the instructions below to set service timers.
INSTALLER SETTINGS
THERMOSTAT CONFIG SYSTEM CONFIG
ACCESSORY CONFIG
INPUT DEALER INFO HUMIDITY CONFIG TEMPERA TURE ALGORITHM DEMAND REDUCTION CNFG SERVICE MODE RESTORY DEFAULTS
ATC32U01 SELECT OPTION
PREVIOUS
4.1 AIR FILTER
This feature displays an alert to remind the user to change the air fi lter after the selected time has passed.
Adjust the Air Filter Reminder settings using the up/down arrow buttons. Press the center button to save changes.
• Cumulative Run Time (default Off) – valid range: Off, 400 to 3600 hours (in 100 hour increments)
• Calendar Time (default Off) – valid range: Off, 3 to 48 months (in 3 month increments)
4.2 HUMIDIFIER
This feature displays an alert to remind the user to change the humidifi er pad after the selected time has passed.
Adjust the Humidifi er Reminder settings using the up/down arrow buttons. Press the center button to save changes.
• Cumulative Run Time (default Off) – valid range: Off, 400 to 3600 hours (in 100 hour increments)
• Calendar Time (default Off) – valid range: Off, 3 to 24 months (in 3 month increments)
Adjust the Air Cleaner Reminder settings using the up/down arrow buttons. Press the center button to save changes.
• Cumulative Run Time (default Off) – valid range: Off, 400 to 3600 hours (in 100 hour increments)
• Calendar Time (default Off) – valid range: Off, 3 to 24 months (in 3 month increments)
5.0 Input Dealer Information
Enter/edit the Dealer Information settings, including Brand Name, Model Number, Serial Number, Contractor Name, and Contractor Phone number, using the up/down arrow buttons. Press the center button to save changes.
6.0 Humidity Confi guration
Confi gure humidity control settings (dehumidifi cation/ humidifi cation).
Adjust the Humidity Control settings using the up/down arrow buttons. Press the center button to save changes.
• Dehumidi cation – This logic will communicate a Dehumidifi cation output when the humidity is greater than the setpoint (acts as a dehumidistat). The Dehumidifi cation output will not be communicated when the humidity is below the setpoint.
• Humidi cation – This logic will communicate a Humidifi cation output when the humidity is less than the setpoint (acts as a humidistat). When the Humidifi cation output is active, the fan output will also be active. The Humidifi cation output will not be communicated when the humidity is above the setpoint.
• Both – Incorporates both Dehumidifi cation and Humidifi cation logic.
• None (default) – Dehumidifi cation and Humidifi cation outputs will not be communicated.
7.0 Temperature Algorithm
4.3 UV LAMP
This feature displays an alert to remind the user to change the UV lamps after the selected time has passed.
Adjust the UV Lamp Reminder settings using the up/down arrow buttons. Press the center button to save changes.
• Cumulative Run Time (default Off) – valid range: Off, 400 to 3600 hours (in 100 hour increments)
• Calendar Time (default Off) – valid range: Off, 3 to 48 months (in 3 month increments)
4.4 AIR CLEANER
This feature displays an alert to remind the user to clean the lter(s) after the selected time has passed.
Confi gure the logic the thermostat uses to meet the temperature setpoints.
• Proportional Integral (default) – This logic will use a combination of temperature differential and operating time to determine the appropriate heating or cooling stages for operation (see NOTE 1).
• Proportional Integral (No Down Staging) – This logic includes the Proportional Integral logic, but in addition the logic keeps all active heating or cooling stages energized until the demand is fully satisfi ed (see NOTE 1).
• Differential – This logic will only use temperature differential to determine the appropriate heating or
10
Heat Controller, Inc. 7602-443 COMMUNICATING, PROGRAMMABLE THERMOSTAT Installation Manual
cooling stages for operation. This logic will keep all active heating or cooling stages energized until the demand is fully satisfi ed (see NOTE 2).
NOTE 1: The Proportional Integral options require fi rst stage heating or cooling to be active for a minimum of 5 minutes, before energizing second stage when confi gured for multi stage operation.
NOTE 2: The Differential option will activate fi rst stage heating or cooling when the temperature is more than the fi rst stage differential value (User Manual section 5.6.2.3), below or above the setpoint. Second stage heating or cooling will be activated when the temperature is more than the fi rst and second stage differential values combined (User Manual section 5.6.2.3), below or above the setpoint. Third stage heating will be activated when the temperature is more than the fi rst, second, and third stage differential values combined (User Manual section 5.6.2.3), below the setpoint.
8.0 Demand Reduction Confi guration
Demand Reduction is activated by an input signal at the unit control board to reduce the electric load while peak utility rates are high. The Demand Reduction Confi guration mode selects which of the available unit control inputs is to be used as the activation signal. While a physical input signal is present at the selected input, the thermostat will implement load reduction by limiting operation or capacity. Refer to section 5.6.9 in the User Manual for more details on Demand Reduction.
9.0 Service Mode
SERVICE MODE MANUAL OPERATION CONTROL DIAGNOSTICS DIPSWITCH CONFIG FAULT HISTORY CLEAR FAULT HISTORY
SELECT OPTION
PREVIOUS SELECT
9.1 MANUAL OPERATION
Manual Operation mode allows the service personnel to manually command operation for any of the thermostat outputs, blower speed or valve position to help troubleshoot specifi c components.
NOTE 1: The ECM Airfl ow adjustment will not be present if the connected communicating control (DXM2) is not confi gured for ECM (section 3.3).
NOTE 2: The Valve Position adjustment will not be present if the connected communicating control (DXM2) is confi gured for V alve (section 3.1).
NOTE 3: If multiple units are connected to one thermostat, refer to section 9.6
Adjust the Demand Reduction Confi guration setting using the up/down arrow buttons. Press the center button to save changes.
• No Demand Reduction (default) – Demand Reduction operating mode will not be activated by a DXM2 input.
• DXM2 Inputs – Assigns a DXM2 input to activate Demand Reduction operating mode.
INSTALLER SETTINGS
THERMOSTAT CONFIG SYSTEM CONFIG ACCESSORY CONFIG INPUT DEALER INFO HUMIDITY CONFIG TEMPERA TURE ALGORITHM
DEMAND REDUCTION CNFG
SERVICE MODE RESTORY DEFAULTS
ATC32U01 SELECT OPTION
PREVIOUS
MANUAL OPERATING MODE
Y1 COMM OUTPUT OFF
Y2 COMM OUTPUT OFF W COMM OUTPUT OFF O COMM OUTPUT OFF G COMM OUTPUT OFF H COMM OUTPUT OFF DH COMM OUTPUT OFF ECM AIRFLOW 0
TEST MODE OFF
PUMP SPEED 0% TEST MODE OFF
SELECT OPTION
PREVIOUS SELECT
11
Installation Manual 7602-443 COMMUNICATING, PROGRAMMABLE THERMOSTAT Heat Controller, Inc.
9.2 CONTROL DIAGNOSTICS
Control Diagnostics mode allows the service personnel to view the status of all physical inputs, switches, temperature sensor readings, as well as the operational status of the pump at the thermostat.
Navigate between diagnostic screens using the left/right arrow buttons.
NOTE 1: If multiple units are connected to one thermostat, refer to section 9.6.
CONTROL DIAGNOSTICS
HP SWITCH CL LOC SWITCH CL Y1 PHYSICAL INPUT ON Y2 PHYSICAL INPUT OFF W PHYSICAL INPUT OFF O PHYSICAL INPUT ON G PHYSICAL INPUT ON H PHYSICAL INPUT OFF EMERG SHUTDOWN OFF NIGHT SETBACK OFF OVR INPUT OFF
PREVIOUS NEXT
CONTROL STATUS
TEMPERATURES
LT1 TEMP 38.1 LT2 TEMP 79.9 COMP DISCHARGE 157.7 HOT WATER EWT 121.5 LEAVING AIR 75.1 LEAVING WATER 73.3 ENTERING WATER 78.5 CONTROL VOLTAGE 26.4 ECM BLOWER RPM 550 ECM TARGET CFM 800 ECM BLWR STATIC N/A
PREVIOUS NEXT
9.3 DIPSWITCH CONFIGURATION
Dipswitch Confi guration mode allows the service personnel to view the status of all dipswitch settings for the connected communicating control (DXM2/AXM) at the thermostat.
Navigate between confi guration screens using the left/right arrow buttons.
NOTE 1: The unit control dipswitch settings cannot be changed from the thermostat.
NOTE 2: If multiple units are connected to one thermostat, refer to section 9.6.
CONTROL CONFIGURATION
DIPSWITCH S1
1 ON UPS ENABLED 2 ON DUAL COMP STG 1 3 ON HEAT PUMP TSTAT 4 ON RV O THERMOSTAT 5 ON DEHUMID OFF 6 ON EH2 AUX HEAT 7 ON BOILERLESS 8 ON SEE DXM2 AOM
PREVIOUS NEXT
CONTROL CONFIGURATION
DIPSWITCH S2
1 ON \ ACCESSORY 1 2 ON ACCESSORY 2 3 ON/
4 ON \ ACCESSORY 2 5 ON ACTIVE W/ COMP 6 ON /
7 ON H DEHUM INPUT 8 ON FACTORY SETTING
PREVIOUS NEXT
CONTROL CONFIGURATION
DIPSWITCH S3
1 ON FACTORY SETTING 2 OFF HWG TEST OFF 3 OFF HWG SP 125 4 OFF HWG DISABLED
JW3 LT1 SETTING WELL
PREVIOUS
12
Heat Controller, Inc. 7602-443 COMMUNICATING, PROGRAMMABLE THERMOSTAT Installation Manual
9.4 FAULT HISTORY
Fault History mode displays the fi ve most recent stored fault codes for the connected communicating control (DXM2).
Navigate between control fault codes using the up/down arrow buttons. Press the center button to view more information about the highlighted fault code.
NOTE: If multiple units are connected to one thermostat, refer to section 9.7.
HE024 SN - - - - - 0 1 2 3
LAST 5 FAULTS LT1 LOW WATER TEMP NO FAULT NO FAULT NO FAULT NO FAULT NEXT
PREVIOUS SELECT
FAULT CONDITION MENU
LT1 LOW WATER TEMP HEAT 1 11:11 AM 11/14
FAULT TEMP CONDITIONS
FAULT FLOW CONDITIONS FAULT I/O CONDITIONS FAULT CONFIG COND FAULT POSSIBLE CAUSES
PREVIOUS SELECT
9.4.1 Temperature Conditions
Displays detailed temperature readings that were recorded at the time the fault occurred.
NOTE: If multiple units are connected to one thermostat, refer to section 9.6.
FAULT TEMPERATURE CONDITIONS
LT1 LOW WATER TEMP
HEAT 1 11:11 AM 11/14
LT1 TEMP 28.1 LT2 TEMP 97.3 HOT WATER EWT 121.5 COMP DISCHARGE 157.7 LEAVING AIR 92.7 LEAVING WATER 34.9 ENTERING WATER 42.1 CONTROL VOLTAGE 26.4
PREVIOUS
9.4.2 Flow Conditions
Displays detailed blower and valve position readings that were recorded at the time the fault occurred.
NOTE: If multiple units are connected to one thermostat, refer to section 9.7.
FAULT FLOW CONDITIONS
LT1 LOW WATER TEMP HEAT 1 11:11 AM 11/14
ECM TARGET CFM 800 ECM BLOWER RPM 550 FLOW RATE GPM 6.5 PUMP SPEED 60% VALVE POSITION 0%
PREVIOUS
9.4.3 Input/Output Conditions
Displays the status of all physical and communicated inputs, switches, and control outputs that were recorded at the time the fault occurred.
NOTE: If multiple units are connected to one thermostat, refer to section 9.7.
FAULT I / O CONDITIONS LT1 LOW WATER TEMP HEAT 1 11:11 AM 11/14
TSTAT SAFETY OUTPT
CONV COMM HPS
Y1 Y1 LOC CC Y2 Y2 CO RV
WW ACC1
O O OUTPT ACC2 G GFAN AL1 HH HWG EH1
OVR DH PUMP EH2
PREVIOUS
9.4.4 Confi guration Conditions
Displays the status of all dipswitch settings that were recorded at the time the fault occurred.
NOTE: If multiple units are connected to one thermostat, refer to section 9.7.
FAULT CONFG CONDITIONS
LT1 LOW WATER TEMP HEAT 1 11:11 AM 11/14
S1 S2 S3 1 ON 1 ON 1 ON 2 ON 2 ON 2 OFF 3 ON 3 ON 3 OFF 4 ON 4 ON 4 OFF 5 ON 5 ON 6 ON 6 ON LT1 WELL 7 ON 7 ON LT2 WELL 8 ON 8 ON
PREVIOUS
13
Installation Manual 7602-443 COMMUNICATING, PROGRAMMABLE THERMOSTAT Heat Controller, Inc.
9.4.5 Possible Causes
Possible causes as to why the fault occurred NOTE: If multiple units are connected to one thermostat, refer
to section 9.7.
POSSIBLE FAULT CAUSES
LOW WATER COIL TEMP
LOW WATER TEMP - HTG
LOW WATER FLOW - HTG
LOW REFRIG CHARGE - HTG
INCORRECT LT1 SETTING
BAD LT1 THERMISTOR
PREVIOUS
9.5 CLEAR FAULT HISTORY
Clear Fault History will clear all fault codes stored in the thermostat as well as the fault history in any connected communicating controls (DXM2/AXM).
9.6 MULT-UNIT DIAGNOSTICS
If multiple units are connected to one thermostat when Manual Operation, Control Diagnostics, or Dipstick Confi guration is selected, the service personnel will see a screen to select a specifi c unit by the last 4 digits of its serial number.
NOTE: Multiple units may be connected directly to the 7602­443 thermostat or connected to one another in series, as shown by the fi gure below.
CONTROL DIAGNOSTICS
HE024 S N - - - - - 1 2 3 4 HE024 S N - - - - - 5 6 7 8 HE036 S N - - - - - 9 0 1 2
PREVIOUS SELECT
9.7 MULT-UNIT FAULT INFO
When multiple units are connected to one thermostat, UNLIKE Mult-Unit Diagnostics, the service personnel views each units’ fault information by selecting the next option.
HE036 S N - - - - - 0 1 2 3
LAST 5 FAULTS
LT1 LOW WATER TEMP NO FAULT NO FAULT NO FAULT NO FAULT
NEXT
PREVIOUS SELECT
10.0 Restore Defaults
Two connections on DXM2 board to allow for multi-unit installation
The thermostat will reset all settings, excluding the thermostat confi guration settings (section 2), to their factory defaults.
Or
14
Heat Controller, Inc. 7602-443 COMMUNICATING, PROGRAMMABLE THERMOSTAT Installation Manual
15
Revision History
Date Page # Description
17 Sept., 12 All First Published
9/17/12
*97B0055N09*
97B0055N09
Loading...