Heat & Glo LifeStyle 6000XLT-CDN, 6000TR, 6000ARCH, 6000XLS User Manual

Models:
6000TR
Installers Guide
Underwriters
Laboratories Listed
WARNING: IF THE INFORMATION IN THESE INSTRUCTIONS IS NOT FOLLOWED EXACTLY, A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY, OR DEATH.
-Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
-What to do if you smell gas
•Do not try to light any appliance.
•Do not touch any electrical switch.
•Do not use any phone in your building.
•Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
•If you cannot reach your gas supplier, call the fire department.
-Installation and service must be performed by a qualified installer, service agency, or the gas supplier.
Printed in U.S.A. Copyright 2000,
READ THIS MANUAL BEFORE INSTALLING OR OPERATING THIS APPLIANCE. THIS INSTALLERS GUIDE MUST BE LEFT WITH THE APPLIANCE FOR FUTURE REFERENCE.
WARNING: IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE OR MAINTENANCE CAN CAUSE INJURY OR PROPERTY DAMAGE. REFER TO THIS MANUAL. FOR ASSISTANCE OR ADDITIONAL INFORMATION CONSULT A QUALIFIED INSTALLER, SERVICE AGENCY, OR THE GAS SUPPLIER.
1.This appliance may be installed in an aftermarket, permanently located, manufactured (mobile) home, where not prohibited by local codes.
2.This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
Please contact your
This product is covered by one or more of the following patents: (United States) 4,112,913; 4,408,594; 4,422,426; 4,424,792;1 4,520,791; 4,793,322; 4,852,548; 4,875,464; 5,000,162; 5,016,609; 5,076,254 5,191,877; 5,218,953; 5,328,356; 5,429,495; 5,452,708; 5,542,407; 5,613,487; (Australia) 543790; 586383; (Canada) 1,123,296; 1,297,746; 2,195,264; (Mexico)

SAFETY AND WARNING INFORMATION
!READ andUNDERSTAND all instructions carefully before starting the installation.FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the warranty.
Prior to the first firing of the fireplace, READ the Using Your Fireplace section of the
!Owners Guide.
DO NOT USE this appliance if any part has been under water. ImmediatelyCALL a
!qualified service technician to inspect the unit and to replace any part of the control system and any gas control which has been under water.
!THIS UNIT IS NOT FOR USE WITH SOLID FUEL.
Installation and repair should be PERFORMED by a qualified service person. The
!appliance and venting system should be INSPECTED before initial use and at least annually by a professional service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc. It isIMPERATIVE that the unit’s control compartment, burners, and circulating air passagewaysBE KEPT CLEAN to provide for adequate combustion and ventilation air.
!Always KEEP the appliance clear and free from combustible materials, gasoline, and other flammable vapors and liquids.
NEVER OBSTRUCT the flow of combustion and ventilation air. Keep the front of the
!appliance CLEAR of all obstacles and materials for servicing and proper operations. Due to the high temperature, the appliance should beLOCATED out of traffic areas
!and away from furniture and draperies. Clothing or flammable material SHOULD NOT BE PLACED on or near the appliance.
Children and adults should be ALERTED to the hazards of high surface temperature
!and should STAY AWAY to avoid burns or clothing ignition. Young children should beCAREFULLY SUPERVISED when they are in the same room as the appliance.
!These units MUST use one of the vent systems described in the Installing the Fireplace section of theInstallers Guide.NO OTHER vent systems or componentsMAY BE USED.
!This gas fireplace and vent assembly MUST be vented directly to the outside andMUST NEVER be attached to a chimney serving a separate solid fuel burning appliance. Each gas applianceMUST USE a separate vent system. Common vent systems arePROHIBITED.
!INSPECT the external vent cap on a regular basis to make sure that no debris is interfering with the air flow.
!The glass door assembly MUST be in place and sealed, and the trim door assemblyMUST be in place on the fireplace before the unit can be placed into safe operation.
DO NOT OPERATE this appliance with the glass door removed, cracked, or broken.
!Replacement of the glass door should be performed by a licensed or qualified service person. DO NOT strike or slam the glass door.
!The glass door assembly SHALL ONLY be replaced as a complete unit, as supplied by the gas fireplace manufacturer.NO SUBSTITUTE material may be used.
!DO NOT USE abrasive cleaners on the glass door assembly.DO NOT ATTEMPT to clean the glass door when it is hot.
Turn off the gas before servicing this appliance. It is recommended that a qualified
!service technician perform an appliance
Any safety screen or guard removed for servicing must be replaced before operating
!this appliance.
2

Safety and Warning Information ......................... | 2 | |
Section 1: Approvals and Codes ...................... | 4 | |
Approval Listings and Codes ................................... | 4 | |
Appliance Certification ............................................. | 4 | |
Installation Codes .................................................... | 4 | |
HighAltitude Installations.......................................... | 4 | |
Section 2: Getting Started ................................ | 5 | |
Introducing the | 5 | |
5 | ||
Section 3: Installing the Fireplace .................... | 8 | |
Step 1 | Locating the Fireplace ............................... | 8 |
Step 2 | Framing the Fireplace ............................... | 9 |
Step 3 | Installing the Vent System ........................ | 10 |
| A. Vent System Approvals ........................ | 10 |
| B. Installing Vent Components ................. | 20 |
| C. Vent Termination ................................. | 26 |
Step 4 | Positioning, Leveling, and |
|
| Securing the Fireplace ............................. | 31 |
Step 5 | The Gas Control Systems ....................... | 31 |
Step 6 | The Gas Supply Line ............................... | 32 |
Step 7 | Gas Pressure Requirements ................... | 33 |
Step 8 | Wiring the Fireplace ................................ | 34 |
Step 9 | Finishing ................................................. | 36 |
Step 10 | Installing Trim, Logs, and |
|
| Ember Material ........................................ | 37 |
| Installing the Trim..................................... | 37 |
| Positioning the Logs ................................ | 38 |
| Placing the Ember Material ...................... | 38 |
Step 11 Before Lighting the Fireplace.................... | 40 | |
Step 12 Lighting the Fireplace ............................... | 40 | |
Step 13 Heating Control - | 41 | |
Step 14 | Relief Ports - 6000ARCH ......................... | 41 |
After the Installation ............................................... | 41 | |
Section 4: Maintenance and Servicing .......... | 42 | |
Section 5: Replacement Parts |
| |
and Accessories ................................................. | 44 | |
Replacement Parts ............................................... | 44 | |
Accessories ......................................................... | 48 |
TABLE
OF
CONTENTS
3

1
Approvals
and Codes
4
Approval Listings | Appliance Certification | |||
and Codes | The | |||
|
| Guide have been tested to certification standards | ||
|
| and listed by the applicable laboratories. | ||
|
|
|
|
|
|
|
|
| CERTIFICATION |
MODEL | LABORATORY | TYPE | STANDARD | |
6000TR & | Underwriters |
| Vented Gas | ANSI Z21.50• CGA2.22/IR#41 |
6000ARCH | Laboratories |
| Fireplace |
|
Underwriters |
| Vented Gas Fireplace | ANSI Z21.50• CGA2.22 | |
| Laboratories |
| & Vented Gas | ANSI Z21.88• CSA2.33 |
|
|
| Fireplace Heater |
|
|
|
|
|
|
6000XLS | Underwriters |
| Vented Gas | ANSI Z21.88• CSA2.33 |
|
|
| Fireplace Heater |
|
|
|
|
|
|
Installation Codes
The fireplace installation must conform to local codes. Before installing the fireplace, consult the local building code agency to ensure that you are in compliance with all applicable codes, including permits and inspections.
In the absence of local codes, the fireplace installation must conform to the National Fuel Gas Code ANSI Z223.1 (in the United States) or the CAN/CGAB149 Installation Codes (in Canada). The appliance must be electrically grounded in accordance with local codes or, in the absence of local codes with the National Electric Code ANSI/NFPA No. 70 (in the United States), or to the CSA C22.1 Canadian Electric Code (in Canada).
These models may be installed in a bedroom or
High Altitude Installations
U.L. Listed gas fireplaces are tested and approved for elevations from 0 to 2,000 feet in the U.S.A. and from 0 to 4,500 feet in Canada.
When installing this fireplace at an elevation above 2,000 feet (in the United States), it may be necessary to decrease the input rating by changing the existing burner orifice to a smaller size. Input should be reduced four percent (4%) for each 1,000 feet above sea level, unless the heating value of the gas has been reduced, in which case this general rule will not apply. To identify the proper orifice size, check with the local gas utility.
When installing this fireplace at an elevation between 2,000 and 4,500 feet (in Canada), the input rating must be reduced by ten percent (10%).
When installing this fireplace at an elevation above 4,500 feet (in Canada), check with local authorities.
Consult your local gas utility for assistance in determining the proper orifice for your location.

Introducing the
Gas Fireplaces
Preparation
The information contained in this Installers Guide, unless noted otherwise, applies to all models and gas control systems.
Gas fireplace diagrams, including the dimensions, are shown in this section.
This gas fireplace and its components are tested and safe when installed in accordance with this Installers Guide. Report to your dealer any parts damaged in shipment, particularly the condition of the glass.Do not install any unit with damaged, incomplete, or substitute parts.
NOTE: FOR MODEL 6000TR ONLY:
These fireplaces are shipped from the factory with a BTU rating of 27,000 BTU’s. The fireplace can be installed with the vent pipe coming off the top of the unit or the rear of the unit. If you install the unit with the vent pipe coming off the top of the unit, you may run the unit at 31,000 BTU (NG) (30,000 BTU LP), replace the burner orifice with the orifice included in the manual bag. DO NOT REPLACE THE ORIFICE
IF YOU ARE USING THE REAR SET OF VENT COLLARS.
Changing the orifice when venting out the top.
1.Remove the glass door.
2.Using a 1/4” socket, remove the sheetmetal screws holding the long refractory clip in place. Remove the logs and refractory as one piece.
3.Remove the protective plastic from the logs.
4.Remove the two sheetmetal screws holding the burner and remove the burner.
5.Replace the burner orifice with the orifice included in the plastic manual bag (#36DMS for natural gas or #51DMS for propane). Be careful to hold the brass elbow so you don’t kink the aluminum tube.
6.Reverse the steps to replace the burner, logs, refractory, and clip.
The vent system components and trim doors are shipped in separate packages. The gas logs may be packaged separately and must be field installed.
Read all of the instructions before starting the installation. Follow these instructions carefully during the installation to ensure maximum safety and benefit. Failure to follow these instructions will void the owner’s warranty and
may present a fire hazard.
2
Getting
Started
5

The
•Installation of any damaged fireplace or vent system component.
•Modification of the fireplace or direct vent system.
•Installation other than as instructed by
•Improper positioning of the gas logs or the glass door.
•Installation and/or use of any component part not manufactured and approved by
ANY SUCH ACTION MAY POSSIBLY CAUSE A FIRE HAZARD.
When planning a fireplace installation, it’s necessary to determine:
•Where the unit is to be installed.
•The vent system configuration to be used.
•Gas supply piping.
•Electrical wiring.
•Framing and finishing details.
•Whether optional
If the fireplace is to be installed on carpeting or tile, or on any combustible material other than wood flooring, the fireplace should be installed on a metal or wood panel that extends the full width and depth of the fireplace.
NOTE:
6000TR has top and rear collars.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Left Side |
|
|
|
|
|
|
|
| Front | Right Side |
| |||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
6
Figure 1. Diagram of the 6000TR,

Figure 2. Diagram of the 6000ARCH
7

3
Installing the
Fireplace
8
Step 1
Locating the
Fireplace
The diagram below shows space and clearance requirements for locating a fireplace within a room.
MODEL | A | B | C | D | E | |
6000TR & | 42 | 22 | 37 1/8 | 52 1/2 | 74 1/4 | |
6000XLS | ||||||
|
|
|
|
| ||
42 | 22 | 35 1/4 | 49 3/4 | 70 3/8 | ||
6000ARCH | 42* | 22 | 35 1/4 | 49 3/4 | 70 3/8 |
481/4**
* SURROUND IN FRONT OF FINISHED WALL
**SURROUND FLUSH WITH FINISHED WALL. NOTE: DIMENSIONS SHOWN IN INCHES.
Figure 3. Fireplace Dimensions, Locations, and
Space Requirements
Clearance Requirements
The top, back, and sides of the fireplace are defined by
Minimum Clearances from the Fireplace to
Combustible Materials
Glass |
| Rear of | Sides of | Top of |
|
Front | Floor | Fireplace | Fireplace | Fireplace | Ceiling |
|
|
|
|
|
|
36 inches | 0 | 1/2 inch | 1/2 inch | 31 inches | |
(914 mm) |
| (13 mm) | (13 mm) | (89 mm) | (787 mm) |
|
|
|
|
|
|
The minimum clearance to a perpendicular wall extending past the face of the fireplace is one inch (25 mm).
The back of the fireplace may be recessed 21 1/2 inches (546 mm) into combustible construction.

|
| Minimum Clearances from the Vent Pipe to |
|
| |||||
|
|
| Combustible Materials |
|
|
| |||
|
|
|
|
|
|
|
|
| |
|
|
|
| For Vertical |
|
|
|
| |
For Horizontal Sections | Sections | At Wall Firestops | |||||||
|
|
|
|
|
|
|
|
| |
Top |
| Bottom | Sides |
| Top | Bottom | Sides | ||
|
|
|
|
|
|
|
|
| |
3 inches |
| 1 inch | 1 inch | 1 inch | 1/2 inch | 1 inch | |||
(75 mm) |
| (25 mm) | (25 mm) | (25 mm) | (63.7 mm) | (13 mm) | (25 mm) | ||
|
|
|
|
|
|
|
|
| |
|
|
| For minimum clearances, see the direct vent | ||||||
|
|
| termination clearance diagrams on pages 28 and 30 in | ||||||
|
|
| this manual. |
|
|
|
| ||
Step 2 |
| Fireplace framing can be built before or after the | |||||||
Framing the | fireplace is set in place. Framing should be positioned | ||||||||
Fireplace | to accommodate wall coverings and fireplace facing | ||||||||
material. The diagram below shows framing reference | |||||||||
|
|
| |||||||
|
|
| dimensions. |
|
|
|
| ||
CAUTION |
| MEASURE FIREPLACE DIMENSIONS, AND | |||||||
|
|
| VERIFY FRAMING METHODS AND WALL | ||||||
|
|
| COVERING DETAILS, BEFORE FRAMING | ||||||
|
|
| CONSTRUCTION BEGINS. |
|
|
|
SHOWS CENTER OF12" X 12"
VENT FRAMING HOLES FOR
TOP & REAR VENTING.
|
|
|
| B |
|
|
|
|
|
| C |
|
| Framing should be | A |
| |
|
|
|
| ||
E D |
| constructed of 2 X 4 |
|
| |
|
| lumber or heavier. |
|
| |
Model | A | B | C | D | E |
6000TR | 42 | 38 1/4 | 22 | 42 | 26 1/4 |
6000XLS | 42 | 38 1/4 | 22 | N/A | 26 1/4 |
42 | 38 1/4 | 22 | 42 | N/A | |
6000ARCH | 42* | 41 7/8 | 22 | 53 5/8 | N/A |
| 48 1/4** |
|
|
| |
* SURROUND IN FRONT OF FINISHED WALL |
|
|
| ||
** SURROUND FLUSH WITH FINISHED WALL |
|
|
| ||
NOTE: DIMENSIONS SHOWN IN INCHES |
|
|
| ||
Figure 4. Framing Dimensions |
|
|
| 9 | |
|
|
|
|

| Step 3 | A. Vent System Approvals |
| Installing the | These models are approved to use |
| Vent System | pipe components and terminations. Approved vent |
|
| system components are labeled for identification. NO |
|
| OTHER VENTING SYSTEMS OR COMPONENTS |
|
| MAY BE USED. Detailed installation instructions are |
|
| included with each vent termination kit and should be |
|
| used in conjunction with this Installers Guide. The |
|
| drawing below shows vent system components and |
|
| terminations. |
|
| The flame and ember appearance may vary based on the |
|
| type of fuel burned and the venting configuration used. |
|
| Identifying Vent Components |
|
| The vent systems installed on this gas fireplace may |
|
| include one, two, or three 90° elbow assemblies. The |
|
| relationships of vertical rise to horizontal run in vent |
|
| configurations using 90° elbows MUST BE strictly |
|
| adhered to. The rise to run relationships are shown in |
|
| the venting drawings and tables. Refer to the diagrams |
|
| on the next several pages. |
|
| NOTE: TWO 45° ELBOWS MAY BE USED IN PLACE |
|
| OF ONE 90° ELBOW. RISE TO RUN RATIOS IN THE |
|
| VENT SYSTEM MUST BE FOLLOWED IF 45° |
|
| ELBOWS ARE USED. |
|
| This model has vent starting collars on both the top and |
|
| the back of the unit. Depending upon the installation, |
|
| decide which ONE set of starting collars will be used to |
|
| attach the vent system. The starting collar sealing cap |
|
| must remain on the starting collar NOT used. |
|
| VENT SYSTEM COMPONENTS |
| VENT SYSTEM |
|
| TERMINATION KITS |
|
10 | Figure 5. Vent Components and Terminations |

7
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| 7/16 |
|
| ||
| (156 mm) |
|
|
|
|
|
| (164 mm) |
|
| |
| 5/32 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| (216 mm) |
|
|
|
|
|
|
|
|
|
|
| ||
|
|
| 8 | /12 |
|
|
|
| |||
|
|
| (216 mm) | 11 5/8 |
|
|
|
| |||
|
|
| (295 mm) | 11 | 1/16 |
|
|
|
| ||
|
|
| (281 mm) |
|
|
| |||||
3/8 | 5 7/8 |
|
|
|
|
| |||||
(187 mm) (149 mm) |
|
|
|
|
|
| 6 1/2 |
| |||
|
|
|
|
|
|
|
| (165 mm) | 5 | 1/16 | |
|
|
|
|
| (129 mm) | ||||||
|
|
|
|
|
|
| |||||
| 8 | 5/8 |
|
|
|
|
|
|
|
| |
| (220 mm) |
|
|
|
|
|
|
| |||
|
|
|
|
|
| ||||||
| 11 | 15/16 |
|
|
| 8 | 5/8 |
|
| ||
| (303 mm) |
|
|
| (220 mm) |
|
| ||||
|
|
|
|
|
|
|
|
47 | 3/4 |
(1.2 m)
35 | 3/4 |
(908 mm)
|
|
|
| |
|
|
| ||
11 3/4 |
|
|
| |
|
|
|
| |
(298 mm) | 8 3/4 |
| ||
|
| (222 mm) |
| 5 3/4 |
|
|
|
| (146 mm) |
NOTE: PIPES OVERLAP
Figure 6.
11

STRAIGHT UP
VERTICAL VENTING
V (FT.)
40' MAX. (12.4 M)
NOTE: Model 6000ARCH
A
Figure 7. Straight Up Vertical Venting
12

HORIZONTALVENTING
| H |
Kit No. | Max. Run |
| |
24" (610 mm) |
NOTE: Models 6000TR and 6000XLS are tested and approved to use 45° elbows in corner installations. However, 90° elbows will result in better performance.
Figure 8. Corner Installation
13

VENTING WITH ONE (1) 90° ELBOW
V (FT.) |
| H (FT.) | |
1' MIN. (305mm) | 2' | MAX. (610mm) | |
2' MIN. (610mm) | 4' | MAX. (1.22m) | |
3' MIN. (914mm) | 6' | MAX. | (1.86m) |
4' MIN. (1.22m) | 8' | MAX. | (2.4m) |
H = 8' MAX. (2.4m)
V+H = 40' MAX. (12.4m)
Figure 9. Venting with One 90° Elbow
14

FOR 6000TR &
NOTE: If a 90o elbow is first attached to the unit, the maximum horizontal run is
VENTING WITH ONE (1) 90° ELBOW
V (FT.) | H (FT.) |
1' MIN. (305mm) | 5' MAX. (1.52m) |
2' MIN. (610mm) | 10' MAX. (3.1m) |
3' MIN. (914mm) | 15' MAX. (4.65m) |
4' MIN. (1.22m) | 20' MAX. (6.2m) |
H = 20' MAX. (6.2m)
V + H = 40’ MAX. (12.4mm)
NOTE: MODEL 6000ARCH |
|
A |
|
pipe MUST be the first vent |
|
component attached to the unit. |
|
Figure 10. Venting with One 90° Elbow |
|
NOTE: For corner installations: A | |
pipe must be attached to the fireplace before 90o | elbow. This will allow the vent |
pipe to clear the top standoffs. | 15 |

VENTING WITH TWO (2) 90° ELBOWS | |||
V | H |
| H + H1 |
1´ MIN. (305 mm) | 2´ MAX. (610 mm) | 5´ MAX. (1.52m) | |
2´ MIN. (610 mm) | 4´ MAX. (1.22 m) | 10´ MAX. (3.1m) | |
3´ MIN. (914 mm) | 6´ MAX. (1.86 m) | 15´ MAX. (4.65m) | |
4´ MIN. (1.22 m) | 8´ MAX. (2.48 m) | 20´ MAX. (6.2m) | |
V+H+H1 = 40´ MAX. (12.4 m) | H = 8´ MAX. (2.48 m) | H+H1 = 20´ MAX. (6.2m) |
Figure 11. Venting with Two 90° Elbows
16

VENTING WITH TWO (2) 90o ELBOWS | ||
V (FT.) | H + H1 (FT.) | |
1' MIN. | (305mm) | 5´ MAX. (1.52m) |
2' MIN. | (610mm) | 10´ MAX. (3.1m) |
3' MIN. | (914mm) | 15´ MAX. (4.65m) |
4' MIN. | (1.22m) | 20´ MAX. (6.2m) |
V+H+H1= 40' MAX.(12.4m) | H+H1= 20´ MAX. (6.2m) | |
NOTE: MODEL |
| |
6000ARCH |
| |
A |
| |
of straight vent |
| |
pipe MUST be |
| |
the first vent |
| |
component |
| |
attached to |
| |
the unit. |
| |
VENTING WITH TWO (2) 90o ELBOWS | ||
V (FT.) |
| H (FT.) |
1' MIN. | (305mm) | 5´ MAX. (1.52m) |
2' MIN. | (610mm) | 10´ MAX. (3.1m) |
3' MIN. | (914mm) | 15´ MAX. (4.65m) |
4' MIN. | (1.22m) | 20´ MAX. (6.2m) |
|
| H = 20´ MAX. (6.2m) |
V+V1+H= 40' MAX.(12.4m) |
Figure 12. Venting with Two 90° Elbows | 17 |

VENTING WITH THREE (3) 90° ELBOWS | |||
V |
| H | H + H1 |
1´ MIN. (305 mm) |
| 2´ MAX. (610 mm) | 5´ MAX. (1.52 m) |
2´ MIN. (610 mm) |
| 4´ MAX. (1.22 m) | 10´ MAX. (3.1 m) |
3´ MIN. (914 mm) |
| 6´ MAX. (1.86 m) | 15´ MAX. (4.65 m) |
4´ MIN. (1.22 m) |
| 8´ MAX. (2.48 m) | 20´ MAX. (6.2 m) |
V1+V+H+H1=40´MAX.(12.4m) H=8´MAX.(2.48m) H+H1=20´MAX.(6.2m) | |||
VENTING WITH THREE (3) 90° ELBOWS | |||
V | H |
| H + H1 + H2 |
1´ MIN. (305 mm) | 2´ MAX. (610 mm) | 5´ MAX. (1.52 m) | |
2´ MIN. (610 mm) | 4´ MAX. (1.22 m) | 10´ MAX. (3.1 m) | |
3´ MIN. (914 mm) | 6´ MAX. (1.86 m) | 15´ MAX. (4.65 m) | |
4´ MIN. (1.22 m) | 8´ MAX. (2.48 m) | 20´ MAX. (6.2 m) | |
V+H+H1+H2 = 40´ MAX.(12.4 m) | H=8´MAX.(2.48 m) | H+H1+H2 =20´ MAX. (6.2 m) |
Figure 13. Venting with three 90° elbows
18

VENTING WITH THREE (3) 90° ELBOWS
V (FT.) | H (FT.) |
1' MIN. (305mm) | 5' MAX. (1.52m) |
2' MIN. (610mm) | 10' MAX. (3.1m) |
3' MIN. (914mm) | 15' MAX. (4.65m) |
4' MIN. (1.22m) | 20' MAX. (6.2m) |
NOTE: H + H1 = 20' MAX. (6.2m)
V + V1 + H + H1= 40' MAX. (12.4m)
VENTING WITH THREE (3) 90° ELBOWS
V (FT.) | H + H1 (FT.) |
1' MIN.(305mm) | 5' MAX. (1.52m) |
2' MIN. (610mm) | 10' MAX. (3.1m) |
3' MIN. (914mm) | 15' MAX. (4.65m) |
4' MIN. (1.22m) | 20' MAX. (6.2m) |
H + H1 = 20' MAX. (6.2m)
NOTE: V+V1+H+H1 = 40' MAX. (12.4m)
NOTE: MODEL 6000ARCH
A
Figure 14. Venting with three 90° elbows | 19 |
|

B. Installing Vent Components
For Model 6000TR
After determining which set of starting collars will be used (top or rear), follow venting instructions accordingly.
Venting Out the Rear Vent
Remove the installed rear seal cap from the rear starting collars by cutting the strap at each end. (See Figure 15). Follow the vent configuration tables accordingly.
Remove the insulation from the REAR five inch flue. Pull the heat shield out from outside of the firebox.
!WARNING: THE TOP HEAT SHIELD (INSIDE THE FIREBOX) MUST REMAIN ATTACHED IF THE VENT SYSTEM IS ATTACHED TO THE REAR STARTING COLLARS. SEE FIGURE 15.
Venting Out the Top Vent
Remove the top vent collar seal cap and the two pieces of insulation inside the top two starting collars (See Figure 15). Next remove the glass door.
Remove the heat shield from inside the TOP five inch flue from outside of the firebox.
You have to take the glass off again for positioning the logs when the unit is finally installed in place and finished around it. Reinstall the glass door. Attach vent system to
the top starting collars.
!WARNING: THE REAR VENT COLLAR SEAL CAP MUST REMAIN ATTACHED TO THE REAR VENT COLLARS IF THE VENT SYSTEM IS ATTACHED TO THE TOP STARTING COLLARS. SEE FIGURE 15.
!WARNING: FAILURE TO REMOVE INSULATION IN THE SET OF COLLARS YOU ARE USING COULD CAUSE A FIRE.
!WARNING: YOU MUST LEAVE THE INSULATION IN PLACE IN THE SET OF COLLARS YOU ARE NOT USING.
20
Figure 15 For Model 6000TR

1.Apply the stove cement.
2.Line up the internal beads and rotate the pipe sections clockwise until locked.
3.Lock the vent components into place.
4.Check the seal on the rope gasket.
1.Attach the First Vent Component to the Starting Collars
To attach the first vent component to the starting collars of the fireplace:
•Apply a 3/8 inch (9.5 mm) bead of stove cement around the 5 inch (127 mm) fireplace starting collar.
•Make sure that the fireplace rope gasket supplied with the fireplace seals between the first
•Lock the vent components into place by sliding the concentric pipe sections with four (4) equally spaced interior beads into the fireplace collar or previously installed component end with four (4) equally spaced indented sections.
•When the internal beads of each
•The first 90° elbow installed in the vent system of a rear venting fireplace MUST BE in a vertical position.
STARTING
COLLAR
STOVE
SEALANT
BEAD
FIRST VENT
COMPONENT
1 INCH (25.4mm)
Figure 16. Attaching the First Vent Component to the Starting Collars
!WARNING: A 3/8 INCH (9.5MM) BEAD OF STOVE CEMENT MUST BE PLACED AROUND THE 5 INCH (127MM) FIREPLACE STARTING COLLAR BEFORE ATTACHING THE FIRST VENT COMPONENT. FAILURE TO SEAL THIS JOINT MAY CAUSE THE FIREPLACE TO OPERATE IMPROPERLY. SEE THE ABOVE DIAGRAM .
!WARNING: ENSURE THAT THE FIBERGLASS ROPE GASKET SUPPLIED WITH THE FIREPLACE SEALS BETWEEN THE FIRST VENT COMPONENT & THE OUTER
FIREPLACE WRAP. | 21 |

!
90° elbows may be installed and rotated to any point around the preceding component’s vertical axis. If an elbow does not end up in a locked position with the preceding component, attach with a minimum of two (2) sheet metal screws.
Continue adding vent components, locking each succeeding component into place.
22
If the installation is for a termination cap attached directly to the fireplace, skip to the sections, Install Firestops andVent Termination.
WARNING: FOR MODEL 6000ARCH: MAKE CERTAIN THAT THE FIBERGLASS INSULATION BAND IS PACKED INTO THE SPACE BETWEEN THE
Figure 17.
2. Continue Adding Vent Components
To continue adding vent components in accordance with the
•Ensure that each succeeding vent component is securely fitted and locked into the preceding component in the vent system.
Figure 18. Adding Venting Components
3. Install Support Brackets
For Horizontal Runs - The vent system must be supported every five (5) feet of horizontal run by a horizontal pipe support.
To install support brackets for horizontal runs:
•Place the pipe supports around the vent pipe.
•Nail the pipe supports to the framing members.

Use wall brackets to support vertical runs every 8 feet (2.4 m) above the fireplace flue outlet.
NOTE
For Vertical Runs - The vent system must be supported every eight (8) feet (2.4 m) above the fireplace flue outlet by wall brackets.
To install support brackets for vertical runs:
•Attach wall brackets to the vent pipe and secure the wall bracket to the framing members with nails or screws.
WALL BRACKET
WALL STUD
8 FT. (2.4mm)
FLUE
OUTLET
1 INCH MIN. (25.4mm)
Figure 19. Installing Support Brackets 4. Install Firestops
For Horizontal Runs - Firestops are REQUIREDon both sides of a combustible wall through which the vent passes.
Model
To install firestops for horizontal runs that pass through either interior or exterior walls:
•Cut a
23

1.Cut the
2.Position the firestops.
3.Place the heat shield to the top.
4.Continue the vent run.
24
•Position the firestops on both sides of the hole previously cut and secure the firestops with nails or screws.
•The heat shields of the firestops MUST BE placed towards the top of the hole.
•Continue the vent run through the firestops.
Figure 20. 12" x 12" Hole and Vent Pipe
TRIM HEAT HEAT SHIELD SHIELD IF TOO
LONG, ADD TO
SHIELD IF TOO SHORT
EXTERIOR
FIRESTOP
INTERIOR
FIRESTOP
Figure 21. Heat Shield, Interior & Exterior Firestops
For Vertical Runs - One ceiling firestop isREQUIRED at the hole in each ceiling through which the vent passes.
To install firestops for vertical runs that pass through ceilings:
•Position a plumb bob directly over the center of the vertical vent component.
•Mark the ceiling to establish the centerpoint of the vent.

1.Cut the
2.Add the new framing members.
This shows a ceiling installation.
•Drill a hole or drive a nail through this centerpoint.
•Check the floor above for any obstructions, such as wiring or plumbing runs.
•Reposition the fireplace and vent system, if necessary, to accommodate the ceiling joists and/or obstructions.
•Cut an
•Frame the hole with framing lumber the same size as the ceiling joists.
Figure 22. 11" x 11" Hole and New Framing Members
If the area above the ceiling is NOT an attic, position and secure the ceiling firestop on the ceiling side of the previously cut and framed hole.
JOIST |
CEILING |
NAILS (4 REQUIRED) |
CEILING FIRESTOP |
Figure 23. Ceiling Firestop (Ceiling Side)
25

This shows an attic installation.
1.Keep insulation away from the vent pipe at least 1 inch (25 mm).
26
If the area above the ceiling IS an attic, position and secure the firestop on top of the previously framed hole.
JOIST |
CEILING |
NAILS (4 REQUIRED) |
CEILING FIRESTOP |
Figure 24. Attic Firestop
C. Vent Termination
For Horizontal Terminations - To attach and secure the termination to the last section of horizontal vent:
•Rotate and interlock the ends as described at the beginning of the Installing Vent Components section.
•The termination kit should pass through the wall firestops from the exterior of the building.
•Adjust the termination cap to its final exterior position on the building.
!WARNING
THE TERMINATION CAP MUST BE POSITIONED SO THAT THE ARROW IS POINTING UP.
For roundcap termination kits:
•Use the exterior pipelock hole provided on the round flange of the wall firestop to secure the vent pipe in place.
For trapezoidal cap termination kits:
•Using screws, secure the cap to the exterior wall through the flanges built into the cap.

For round cap termination:
1.Secure the
For trapezoidal termination:
1.Screw the cap to the exterior wall through the flanges in the cap.
2.Seal the joint between the pipe and the exterior firestop.
ROUND CAP TERMINATION
PERFORATION CANNOT BE
INSIDE THE WALL
7 1/2" (191mm) MINIMUM
TRAPEZOID CAP TERMINATION
7 1/4" (184mm)
Figure 25. Round & Trapezoid Termination Caps
!WARNING: THE BOTTOM OF THE VENT TERMINATION CAP MUST BE A MINIMUM OF 12 INCHES (305MM) ABOVE GROUND LEVEL (GRADE). THE TOP OF THE CAP MUST BE A MINIMUM OF 18 INCHES (457MM) BELOW COMBUSTIBLE MATERIAL, SUCH AS A DECK, AND THE SIDE OF THE CAP MUST BE A MINIMUM OF 6 INCHES (152MM) AWAY FROM A PARALLEL OUTSIDE WALL. VENTING TERMINALS SHALL NOT BE RECESSED INTO A WALL OR SIDING. SEE THE FOLLOWING DIAGRAM FOR VENT TERMINATION CLEARANCES.
27

|
|
| G |
|
|
|
|
| v |
|
|
| D |
| A | H |
|
|
|
|
|
| |
| E |
|
|
|
|
| v |
|
|
|
|
| L | C | openable fixed closed |
|
|
| v B |
|
| ||
| v |
| v |
|
|
|
|
|
|
| |
| F v |
| B |
| M |
|
| v | I | ||
|
| B | B | v X | |
|
|
| |||
|
|
|
| ||
V | =VENT TERMINAL |
| A |
| J or K |
| 234 |
|
| ||
|
|
| 234 |
|
|
X | =AIR SUPPLY INLET |
| 234 =AREA WHERE TERMINAL IS NOT PERMITTED | ||
| 234 |
|
|
A= 12" clearances above grade, veranda, porch, deck or balcony
B= 12" clearances to window or door that may be opened
C | = | 9" (U.S.A.) | clearance to permanently closed window |
|
| 12" (Canada) |
|
*D | = | 18" | vertical clearance to ventilated soffit located above the |
|
|
| terminal within a horizontal distance of 2 feet (60 cm) |
|
|
| from the |
*E | = | 18" | clearance to unventilated soffit |
F | = | 9" | clearance to outside corner |
G | = | 6" | clearance to inside corner |
H | = | 3 ft. (Canada) | not to be installed above a gas meter/regulator assembly |
|
|
| within 3 feet (90 cm) horizontally from the |
|
|
| the regulator |
I | = | 3 ft. (U.S.A.) | clearance to service regulator vent outlet |
|
| 6 ft. (Canada) |
|
J | = | 9" (U.S.A.) | clearance to |
|
| 12" (Canada) | or the combustion air inlet to any other appliance |
K | = | 3 ft. (U.S.A.) | clearance to a mechanical air supply inlet |
|
| 6 ft. (Canada) |
|
**L | = | 7 ft. | clearance above paved sidewalk or a paved driveway |
|
|
| located on public property |
***M = | 18" | clearance under veranda, porch, deck or balcony |
*30” minimum for vinyl clad soffits.
**a vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings.
***only permitted if veranda, porch, deck or balcony is fully open on a minimum of 2 sides beneath the floor.
NOTE: Local Codes or Regulations may require different clearances.
Figure 26. Vent Termination Minimum Clearances | |
CAUTION | IF EXTERIOR WALLS ARE FINISHED WITH |
| VINYL SIDING, IT IS NECESSARY TO INSTALL |
| THE VINYL PROTECTOR KIT TO THE TOP OF |
28 | THE EXTERIOR FIRESTOP (FOR ALL ROUND |
| TERMINATION CAPS). |

For Vertical Terminations - To locate the vent and install the vent sections:
• Locate and mark the vent centerpoint on the underside of the roof, and drive a nail through the centerpoint.
• Make the outline of the roof hole around the centerpoint nail.
• The size of the roof hole framing dimensions depend on the pitch of the roof. There MUST BE a
• Mark the roof hole accordingly.
• Cover the opening of the installed vent pipes.
• Cut and frame the roof hole.
• Use framing lumber the same size as the roof rafters and install the frame securely. Flashing anchored to the frame must withstand heavy winds.
• Continue to install concentric vent sections up through the roof hole (for inside vent installations) or up past the roof line until you reach the appropriate distance above the roof (for outside terminations).
| ! | WARNING: |
| MAJOR U.S. BUILDING CODES SPECI- | |
|
| FY MINIMUM CHIMNEY AND/OR VENT |
|
| HEIGHT ABOVE THE ROOF TOP. THESE |
|
| MINIMUM HEIGHTS ARE NECESSARY IN |
|
| THE INTEREST OF SAFETY. SEE THE |
|
| FOLLOWING DIAGRAM FOR MINIMUM |
|
| HEIGHTS, PROVIDED THE TERMINA- |
|
| TION CAP IS AT LEAST TWO (2) FEET |
|
| FROM A VERTICAL WALL AND |
|
| BELOW A HORIZONTAL OVERHANG. |
NOTE |
| |
This also pertains to vertical vent systems installed | ||
| on the outside of the building. |
29

1.Attach the flashing and apply sealant around the edges of the flashing base.
2.Attach the storm collar over the flashing joint and apply sealant between the storm collar and vertical pipe.
30
To seal the roof hole, and to divert rain and snow from the vent system:
•Attach a flashing to the roof using nails, and use a
•Attach a storm collar over the flashing joint to form a
•Slide the termination cap over the end of the vent pipe and rotate the pipe clockwise 1/4 turn.
| HORIZONTAL OVERHANG |
TERMINATION |
|
CAP | VERTICAL WALL |
| |
2 FT. | 2 FT. MIN. |
MIN. |
|
| LOWEST |
| DISCHARGE |
TERMINATION CAP | OPENING |
| X |
| 12 |
| ROOF PITCH IS X/ 12 |
| H (MIN.) - MINIMUM HEIGHT FROM ROOF |
| TO LOWEST DISCHARGE OPENING |
Roof Pitch | H (min.) ft. |
flat to 6/12 | 1.0 |
6/12 to 7/12 | 1.25 |
over 7/12 to 8/12 | 1.5 |
over 8/12 to 9/12 | 2.0 |
over 9/12 to 10/12 | 2.5 |
over 10/12 to 11/12 | 3.25 |
over 11/12 to 12/12 | 4.0 |
over 12/12 to 14/12 | 5.0 |
over 14/12 to 16/12 | 6.0 |
over 16/12 to 18/12 | 7.0 |
over 18/12 to 20/12 | 7.5 |
over 20/12 to 21/12 | 8.0 |
Figure 27. Minimum Height from Roof to Lowest Discharge Opening

Step 4
Positioning,
Leveling, and
Securing the
Fireplace
1.Place the fireplace into position.
2.Level the fireplace from side to side and from front to back.
3.Shim the fireplace with
4.Secure the fireplace to the framing by nailing or screwing
Step 5
The Gas Control
Systems
The diagram below shows how to properly position, level, and secure the fireplace.
Figure 28. Proper Positioning, Leveling, and
Securing of a Fireplace
!WARNING: THIS UNIT IS NOT FOR USE WITH SOLID FUEL.
Two types of gas control systems are used with these models: Standing Pilot Ignition andDirect Spark Ignition (DSI). Models
Standing Pilot Ignition System
This system includes millivolt control valve, standing pilot, thermopile/thermocouple flame sensor, and piezo ignitor.
!WARNING:
Direct Spark Ignition (DSI) System
This system includes a 110V control valve, electronic module, and spark ignitor/flame sensor.
!WARNING: CONTINUOUS
!WARNING: DIRECT VENT PROPANE MODELS WITH DSI CONTROL SYSTEMS CANNOT BE USED IN
31

STANDING PILOT | NOTE: FLAMES TOO | DSI IGNITION |
CLOSE TO THE |
| |
| CERAMIC INSULATORS |
|
| CAN CAUSE NUISANCE |
|
| LOCKOUTS AND |
|
| ELECTRODE FAILURE. | IGNITOR |
|
| 3/8” (10mm) |
| CERAMIC |
|
| INSULATOR |
|
| 1/4" (6mm) |
|
Figure 29. Gas Controls Systems
Step 6 | NOTE: Have the gas supply line installed by a | |
The Gas | qualified service technician in accordance with all | |
Supply Line | building codes. | |
NOTE: Before the first firing of the fireplace, the | ||
| ||
| gas supply line should be purged of any trapped air. | |
| NOTE: Consult local building codes to properly size | |
| the gas supply line leading to the 1/2 inch | |
| (13 mm) | |
| This gas fireplace is designed to accept a 1/2 inch | |
| (13 mm) gas supply line. To install the gas supply line: |
•A listed 1/2 inch (13 mm) manual
•The gas line may be run from either side of the fireplace provided the hole in the outer wrap does not exceed 2 inches in diameter and it does not penetrate the airtight box.
•The gap between the supply piping and gas access hole can be plugged with
•Locate the gas line access hole in the outer casing of the fireplace.
•Open the fireplace lower grille, insert the gas supply line through the gas line hole, and connect it to the
•When attaching the pipe, support the control so that the lines are not bent or torn.
•After the gas line installation is complete, use a soap solution to carefully check all gas connections for leaks.
32 | ! | WARNING: DO NOT USE AN OPEN |
FLAME TO CHECK FOR GAS LEAKS. | ||
|
|
|

The gas line should be installed by a qualified service technician.
Step 7
Gas Pressure
Requirements
•At the gas line access hole, use insulation to repack the space around the gas pipe.
•Insert insulation from the outside of the fireplace and pack the insulation tightly to totally seal between the pipe and the outer casing.
CONTROL |
VALVE |
GAS LINE |
ACCESS HOLE |
Figure 30. Gas Supply Line
Pressure requirements for
Pressure | Natural Gas | Propane |
|
|
|
Minimum | 5.0 inches | 11.0 inches |
Inlet Pressure | w.c. | w.c. |
|
|
|
Maximum Inlet | 14.0 inches | 14.0 inches |
Gas Pressure | w.c. | w.c. |
|
|
|
Manifold | 3.5 inches | 10.0 inches |
Pressure | w.c. | w.c. |
|
|
|
A
The fireplace and its individual
The fireplace must be isolated from the gas supply piping system by closing its individual
33

Step 8 | NOTE: Electrical wiring must be installed by a |
Wiring the | licensed electrician. |
Fireplace | Caution: Disconnect remote controls if you are |
| absent for extended time periods. This will |
| prevent accidental fireplace operation. |
For Standing Pilot Ignition Wiring
Appliance Requirements
•This appliance DOES NOT require
!WARNING
DO NOT CONNECT
Optional Accessories
Optional fan and remote control kits require that 110120 VAC be wired to the factory installed junction box before the fireplace is permanently installed.
Remote Wall Switch
Position the remote wall switch in the desired position on a wall. Run a maximum of 25 feet (7.8 m) or less length of 18 A.W.G. minimum wire and connect it to the fireplace ON/OFF switch pigtails.
!WARNING
DO NOT CONNECT
CAUTION | LABEL ALL WIRES PRIOR TO DISCONNECTION |
| WHEN SERVICING CONTROLS. WIRING |
| ERRORS CAN CAUSE IMPROPER AND |
| DANGEROUS OPERATION. VERIFY PROPER |
| OPERATION AFTER SERVICING. |
NOTE: |
Figure 31. Standing Pilot Ignition Wiring Diagram
34

| VARIABLE SPEED CONTROL | NOTE: IF ANY OF THE ORIGINAL WIRE |
|
| AS SUPPLIED WITH THE APPLIANCE |
|
| MUST BE REPLACED, IT MUST BE |
BLK | BLK | REPLACED WITH TYPE 105OC RATED WIRE. |
JUNCTION BOX |
| |
|
| |
BLK | BLK | BLOWER RECEPTACLE |
| ||
|
| BLK |
BLK |
|
|
| BLK |
|
WHT WHT
BLK
GROUND
TEMPERATURE
SENSOR SWITCH
BLOWER
GRN |
|
| |
BLK | WHT | ||
|
| ||
JUNCTION BOX | TEMPERATURE | ||
SENSOR SWITCH | |||
| |||
|
|
| |
|
|
|
FAN
SPEED CONTROL (RHEOSTAT)
Figure 32. Fan Wiring Diagram
| For Direct Spark Ignition (DSI) Wiring |
|
| Appliance Requirements |
|
| This appliance requires that |
|
| the factory installed junction box. Maintain correct |
|
| polarity when wiring the junction box. |
|
| Optional Accessories |
|
| Optional fan and remote control kits require that 110- |
|
| 120 VAC be wired to the fireplace junction box. |
|
| Remote Wall Switch |
|
| Position the remote wall switch in the desired position |
|
| on a wall. Run a maximum of 25 feet |
|
| (7.8 m) or less of 16 A.W.G. minimum wire and |
|
| connect it to the fireplace ON/OFF switch pigtails. |
|
NOTE | Electrical wiring must be installed by a licensed |
|
| electrician. |
|
CAUTION | LABEL ALL WIRES PRIOR TO DISCONNECTION |
|
| WHEN SERVICING CONTROLS. WIRING |
|
| ERRORS CAN CAUSE IMPROPER AND |
|
| DANGEROUS OPERATION. VERIFY PROPER |
|
| OPERATION AFTER SERVICING. | 35 |

NOTE: |
The microswitch |
is found on model |
6000ARCH only. |
Figure 33. Direct Spark Ignition (DSI) Wiring Diagram
Step 9 | The following diagram shows the minimum vertical |
Finishing | and corresponding maximum horizontal dimensions |
| of fireplace mantels or other combustible projections |
| above the top front edge of the fireplace. See Figures |
| 3 and 4 for other fireplace clearances. |
Only
NOTE: All Dimensions shown in inches.
Figure 34. Minimum Vertical and Maximum
Horizontal Dimensions of
Combustibles above Fireplace
!WARNING
WHEN FINISHING THE FIREPLACE, NEVER OBSTRUCT OR MODIFY THE AIR INLET/OUTLET GRILLES IN ANY
36 | MANNER. |
|

CAUTION
1.Apply only noncombustible facing material to the fireplace surround.
Step 10
Installing Trim,
Logs, and
Ember Material
IF JOINTS BETWEEN THE FINISHED WALLS AND THE FIREPLACE SURROUND (TOP AND SIDES) ARE SEALED, A 300° F. MINIMUM SEALANT MATERIAL MUST BE USED. THESE JOINTS ARE NOT REQUIRED TO BE SEALED. ONLY NONCOMBUSTIBLE MATERIAL (USING 300° F. MINIMUM ADHESIVE, IF NEEDED) CAN BE APPLIED AS FACING TO THE FIREPLACE SURROUND. SEE THE DIAGRAM SHOWN BELOW.
Figure 35. Sealant Material
Hearth Extensions
A hearth extension may be desirable for aesthetic reasons. However, ANSI or CAN/CGA testing standards do not require hearth extensions for gas fireplace appliances.
Installing the Trim
Combustible materials may be brought up to the specified clearances on the side and top front edges of the fireplace, but MUST NEVER overlap onto the front face. The joints between the finished wall and the fireplace top and sides can only be sealed with a 300° F. (149° C) minimum sealant.
!WARNING
WHEN FINISHING THE FIREPLACE, NEVER OBSTRUCT OR MODIFY THE AIR INLET/OUTLET GRILLES IN ANY MANNER.
Install optional marble and brass trim surround kits as desired. Marble, brass, brick, tile, or other noncombustible materials can be used to cover up the gap between the sheet rock and the fireplace.
Do not obstruct or modify the air inlet/outlet grilles. When overlapping on both sides, leave enough space
so that the bottom grille can be lowered and the trim 37 door removed.

Positioning the Logs
If the gas logs have been factory installed they should not need to be positioned.
If the logs have been packaged separately, refer to the installation instructions that accompany the logs. Save the log instructions with this manual.
If sooting occurs, the logs might need to be repositioned slightly to avoid excessive flame impingement.
Placing the Ember Material
Two separate bags of ember material are shipped with this gas fireplace:
•The bag labeled Golden Ember
•The bag labeled Glowing Ember
To place the ember material:
•Turn the tension springs around the glass door 90°.
•Remove the glass door from the unit.
•NOTE: FOR MODEL 6000ARCH ONLY.
Remove wing nuts and glass clips. Pull glass out from bottom and pull downward.
•Cover the top of the burner with a single layer of ember material. Then sprinkle
•Save the remaining ember materials for use during fireplace servicing.
•Replace the glass door and a front trim door on the unit (see Replacement Parts Section of the manual.)
•Pull out and twist the tension springs 90° to lock.
38

1.Lift the trim door up and out of the unit.
1.Lift the top trim door up and out of the unit.
2.Unlatch and remove the glass door from the unit.
1.Place the ember material onto the top of the burner.
CAUTION
EYE BOLT
LATCH BRACKET
GLASS DOOR
Figure 36. Models:
Glass Assembly
6000ARCH does not have the eye bolts.
Figure 37. Model: 6000TR Glass Assembly
Figure 38. Placement of the Ember Material
IT IS STRONGLY RECOMMENDED THAT TRIM DOORS WITH OPTIONAL MESH SCREENS BE INSTALLED ON PROPANE MODELS.
39

Step 11
Before Lighting
the Fireplace
Step 12
Lighting the
Fireplace
40
Before lighting the fireplace, be sure to do the following:
Remove all paperwork and documents from the fireplace.
Review safety warnings and cautions
•Read the Safety and Warning Informationsection at the beginning of this Installers Guide.
•Before lighting the fireplace,
•Before lighting the fireplace,
•Any component that is found to be faulty MUST BE replaced with an approved component. Tampering with the fireplace components isDANGEROUS and voids all warranties.
A small amount of air will be in the gas supply lines. When first lighting the fireplace, it will take a few minutes for the lines to purge themselves of this air. Once the purging is complete, the fireplace will light and will operate normally.
Subsequent lightings of the fireplace will not require this purging of air from the gas supply lines, unless the gas valve has been turned to the OFF position, in which case the air would have to be purged.
NOTE: The fireplace should be run for 8 hours on the inital
You’ve reviewed all safety warnings, you’ve checked the fireplace for gas leaks, you know the vent system is unobstructed, and you’ve checked for faulty components. Now you’re ready to light the fireplace.
WARNING
!PLEASE REFER TO THE USER’S MANUAL FOR ALL CAUTIONS, SAFETY, AND WARNING INFORMATION PERTAINING TO THE LIGHTING AND OPERATION OF THE FIREPLACE.

Step 13
Heating Control
Model
Step 14 Relief Ports
Model 6000ARCH
After the
Installation
This model is equipped with a baffle which will allow you to control usable heat output. The baffle control lever is located at the lower left corner of the unit behind the lower grille. See Figure 39.
FOR MORE HEAT: Pull the baffle lever forward and down. This will close the baffle.
FOR LESS HEAT: Push the baffle lever back and up to lock. This will open the baffle.
FIGURE 39 |
Model 6000 ARCH has a relief port built into the underside of the firebox (behind the lower grille). See Figure 40. The port cover plate is
In the unlikely event of a delayed lighting of the burner, the relief cover plate is designed to open and release the microswitch lever. This will prevent the DSI valve from operating until the cover plate is
FIGURE 40
!LEAVE THIS INSTALLATION MANUAL WITH THE APPLIANCE FOR FUTURE REFERENCE.
41

4
Maintaining and Servicing Your Fireplace
42
Fireplace
Maintenance
Although the frequency of your fireplace servicing and maintenance will depend on use and the type of installation, you should have a qualified service technician perform an appliance
IMPORTANT | TURN OFF THE GAS BEFORE SERVICING | |||
|
| YOUR FIREPLACE. | ||
|
|
|
|
|
Type of |
|
|
|
|
Fireplace |
|
|
| Fireplace Maintenance Task To |
Maintenance | Frequency |
| By | Be Completed |
|
|
|
|
|
Replacing | Once annually, |
| Qualified | Brush away loose ember material near |
Old Ember | during the |
| Service | the burner. Replace old ember |
Material | annual | Technician | material with new | |
|
|
|
| pieces of Golden Ember |
|
|
|
| Glowing Ember |
|
|
|
| material should be placed alternately on |
|
|
|
| top of the |
|
|
|
| Ember, a layer of Glowing Ember, |
|
|
|
| and so on. Save the remaining ember |
|
|
|
| material and repeat this procedure at |
|
|
|
| your next servicing. For more |
|
|
|
| information, see Placing Ember |
|
|
|
| Material in the INSTALLERS GUIDE. |
|
|
|
|
|
Cleaning | Once annually |
| Qualified | Brush or vacuum the control |
Burner |
|
| Service | compartment, fireplace logs, and |
& Controls |
|
| Technician | burner areas surrounding the logs. |
|
|
|
|
|
Checking | Periodically |
| Qualified | Make a visual check of your fireplace’s |
Flame |
|
| Service | flame patterns. Make sure the flames |
Patterns, |
|
| Technician/ | are |
Flame Height |
|
| Owner | the picture in Figure 41. The flame |
|
|
|
| sensor(DSI) or thermopile/thermocouple |
|
|
|
| (standing pilot) tips should be covered |
|
|
|
| with flame. See the picture in Figure 42. |
|
|
|
| |
Checking | Before initial use | Qualified | Inspect the external vent cap on a | |
Vent System | and at least |
| Service | regular basis to ensure that no debris is |
| annually thereafter, | Technician/ | interfering with the flow of air. Inspect | |
| more frequently |
| Owner | entire vent system for proper function. |
| if possible |
|
|
|
|
|
|
|
|
Cleaning | As necessary |
| Homeowner | Clean as necessary, particularly after |
Glass Door |
|
|
| adding new ember (flame colorant) |
|
|
|
| material. Film deposits on the inside of |
|
|
|
| the glass door should be cleaned off |
|
|
|
| using a household glass cleaner. |
|
|
|
| NOTE: DO NOT handle or attempt to |
|
|
|
| clean the door when it is hot and |
|
|
|
| DO NOT use abrasive cleaners. |
|
|
|
|
|

MAKE SURE THE FLAMES
ARE
LIFTING OR FLOATING.
Figure 41. Burner Flame Patterns
| STANDING PILOT |
NOTE: FLAMES | DSI IGNITION |
| |
TOO CLOSE TO |
|
THE CERAMIC |
|
INSULATORS CAN | IGNITOR |
CAUSE NUISANCE |
|
LOCKOUTS AND | 3/8” (10mm) |
ELECTRODE | |
FAILURE. |
|
CERAMIC |
|
INSULATOR |
|
1/4" (6mm) |
|
Figure 42. Pilot/Ignitor Flame Patterns
43

5 |
| All parts listed in this INSTALLERS GUIDE may be | |
| ordered from an authorized dealer. When requesting | ||
| service or replacement parts for your fireplace, please | ||
| provide the model number and the serial number. | ||
Standing Pilot with Robertshaw Controls only | |||
PART | PART DESCRIPTION | PART NUMBER | |
| Valve LP | ||
| Valve NG | ||
Replacement |
|
|
|
Parts and |
|
|
|
Accessories |
|
|
|
|
| Piezo Ignitor | |
|
| Thermopile | |
|
| Thermocouple | |
|
| Pilot Orifice LP | |
|
| Pilot Orifice NG | |
|
| Pilot Assembly LP | |
|
| Pilot Assembly NG | |
|
| Pilot Tube | |
|
| Burner Tube | |
44 |
|
|
|

All parts listed in this INSTALLERS GUIDE may be ordered from an authorized dealer. When requesting service or replacement parts for your stove, please provide the model number and the serial number.
Standing Pilot with S.I.T. controls only
PART | PART DESCRIPTION | PART NUMBER |
| Piezo Ignitor |
Thermopile |
Thermocouple |
Valve LP | |
Valve NG |
Burner Tube |
Pilot Tube |
Pilot Orifice LP | |
Pilot Orifice NG |
Pilot Assembly LP | |
Pilot Assembly NG |
45

DSI Ignition Only |
|
|
PART | PART DESCRIPTION | PART NUMBER |
| DSI Valve | |
| DSI Module | |
| Electrode | |
Both Standing Pilot and DSI Ignition |
| |
PART | PART DESCRIPTION | PART NUMBER |
| Trim Door | |
| Log Set Assembly |
46

Both Standing Pilot and DSI Ignition (Cont.) |
|
| ||
PART | PART DESCRIPTION | PART NUMBER |
| |
High Temperature Limit Switch |
| |||
Burner NG |
|
| ||
Burner LP |
|
| ||
Burner Orifice |
|
|
| |
6000TR NG Rear Venting (#38DMS) |
| |||
6000TR LP Rear Venting (#52DMS) |
| |||
6000TR NG Top Venting (#36DMS) |
| |||
6000TR LP Top Venting (#51DMS) |
| |||
6000ARCH NG (#39DMS) |
|
| ||
6000ARCH LP (#53DMS) |
|
| ||
6000XLS, |
| |||
6000XLS, |
| |||
On/Off Rocker Switch |
|
| ||
Glass Door Assembly |
|
| ||
Grate Assembly |
|
| ||
6000ARCH |
|
|
| |
6000XLS |
|
|
| |
|
|
| ||
Grate Assembly |
|
| ||
6000TR |
|
|
| |
Refractory |
|
|
| |
6000TR |
|
| ||
6000XLS |
|
|
| |
|
|
| ||
6000ARCH |
|
| ||
Glass Spring Fastener |
|
| ||
GLASS SPECIFICATIONS: | 6000TR: | 22” X 34” | TEMPERED |
|
| 6000XLS: | 22” X 34” | CERAMIC |
|
| 22” X 34” | CERAMIC | 47 | |
| 6000ARCH: | 22” X 34” | CERAMIC | |
|
|

Accessories
ACCESSORY | PART DESCRIPTION | PART NUMBER |
| Fan Kit | |
| Remote Control Kit | |
|
| |
|
| |
| Wall Switch Kit |
|
| - Off White | |
| - White | |
| Trim Door Mesh |
48