• Important operating
and maintenance
instructions included.
• Read, understand and follow
these instructions for safe
installation and operation.
Owner’s Manual
Installation and Operation
DO NOT
DISCARD
• Leave this manual with
party responsible for use
and operation.
WARNING: If the information in these
instructions is not followed exactly, a fi re
or explosion may result causing property
damage, personal injury, or death.
• DO NOT store or use gasoline or other fl am-
mable vapors and liquids in the vicinity of this
or any other appliance.
• What to do if you smell gas
- DO NOT try to light any appliance.
- DO NOT touch any electrical switch. DO
NOT use any phone in your building.
- Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions.
- If you cannot reach your gas supplier, call
the fi re department.
• Installation and service must be performed
by a qualifi ed installer, service agency, or the
gas supplier.
This appliance may be installed as an OEM installation in
manufactured home (USA only) or mobile home and must be
installed in accordance with the manufacturer’s instructions
and the manufactured home construction and safety standard,
Title 24 CFR, Part 3280 or Standard for Installation in Mobile
Homes, CAN/CSA Z240MH, in Canada .
This appliance is only for use with the type(s) of gas indicated
on the rating plate.
WARNING
HOT SURFACES!
Glass and other surfaces are hot during
operation AND cool down.
Hot glass will cause burns.
• DO NOT touch glass until it is cooled
• NEVER allow children to touch glass
• Keep children away
• CAREFULLY SUPERVISE children in same room as
fi replace.
• Alert children and adults to hazards of high temperatures.
High temperatures may ignite clothing or other fl ammable
materials.
• Keep clothing, furniture, draperies and other fl ammable
materials away.
This appliance has been supplied with an integral barrier
to prevent direct contact with the fi xed glass panel. DO
NOT operate the appliance with the barrier removed.
Contact your dealer or Hearth & Home Technologies if the
barrier is not present or help is needed to properly install one.
In the Commonwealth of Massachusetts installation must be
performed by a licensed plumber or gas fi tter.
See Table of Contents for location of additional Commonwealth
of Massachusetts requirements.
Installation and service of this appliance should be
performed by qualifi ed personnel. Hearth & Home
Technologies suggests NFI certifi ed or factory trained
professionals, or technicians supervised by an NFI
certifi ed professional.
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/081
Page 2
Read this manual before installing or operating this appliance.
Please retain this owner’s manual for future reference.
A. Congratulations
Congratulations on selecting a Heatilator gas fi replace, an
elegant and clean alternative to wood burning fi replaces.
The Heatilator gas fi replace you have selected is designed
to provide the utmost in safety, reliability, and effi ciency.
As the owner of a new fi replace, you’ll want to read and
carefully follow all of the instructions contained in this
Owner’s Manual. Pay special attention to all cautions and
warnings.
Homeowner Reference Information
This Owner’s Manual should be retained for future reference.
We suggest that you keep it with your other important
documents and product manuals.
The information contained in this Owner’s Manual, unless
noted otherwise, applies to all models and gas control
systems.
Your new Heatilator gas fi replace will give you years of
durable use and trouble-free enjoyment. Welcome to the
Heatilator family of fi replace products!
We recommend that you record the following pertinent
information about your fi replace.
Model Name: ___________________________________________ Date purchased/installed: __________________
Serial Number: __________________________________________ Location on fi replace: _____________________
GAS TYPE/TYPE DE GAZ NATURAL/NATUREL PROPANE
ALTITUDE 0-2000 2000-4000 FT/PI 0-2000 2000-4000 FT/PI
MAX INPUT/DÉBIT XX,XXX XX,XXX BTUH XX,XXX XX,XXX BTUH
MIN INPUT/DÉBIT XX,XXX XX,XXX BTUH XX,XXX XX,XXX BTUH
MANIFOLD PRESSURE/PRESSION TUBULAIRE
MAX. XX IN. W.C./C. D'EAU XX IN. W.C./C. D'EAU
MIN. XX IN. W.C./C. D'EAU XX IN. W.C./C. D'EAU
MIN. INLET PRESS. XX IN. W.C./C. D'EAU 1XX IN. W.C./C. D'EAU
FOR THE PURPOSE OF INPUT ADJUSTMENT
PRESS. MIN. D'ALIMENTATION
ORIFICE SIZE
DIAM. DE L'INJECTEUR XX/XX DIA. in./mm XX/XX DIA. in./mm
LESS THAN/MOINS DE 3 AMPÈRES., 115V., 60 Hz
DO NOT REMOVE OR COVER THIS LABEL.
VENTED GAS FIREPLACE - NOT FOR USE WITH SOLID FUEL.
FOYER À GAZ À ÉVACUATION - NE DOIT PAS ÊTRE UTILISÉ
AVEC UN COMBUSTIBLE SOLIDE.
XXXXXX
The model information regarding your specifi c fi replace can be found on
the rating plate usually located in the control area of the fi replace.
Gas Type
SERIAL
NO. DE SÉRIE
Serial #
XXXXXXXXX
XXXX
CERTIFIED
FOR CANADA
CERTIFIÉ POUR LE
CANADA
Orifice
Size
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/082
Page 3
Safety Alert Key:
• DANGER! Indicates a hazardous situation which, if not avoided will result in death or serious injury.
• WARNING! Indicates a hazardous situation which, if not avoided could result in death or serious injury.
• CAUTION! Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
• NOTICE: Used to address practices not related to personal injury.
Table of Contents
A. Congratulations 2
B. Limited Lifetime Warranty 5
1 Listing and Code Approvals
A. Appliance Certifi cation 6
B. Tempered Glass Specifi cations 6
C. BTU Specifi cations 6
D. High Altitude Installations 6
E. Non-Combustible Materials Specifi cation 6
F. Combustible Materials Specifi cation 6
G. Requirements for the
Commonwealth of Massacusetts 7
User Guide
2 Operating Instructions
A. Gas Fireplace Safety 8
B. Your Fireplace 8
C. Fan Kit (optional) 9
D. Clear Space 9
E. Decorative Doors and Fronts 9
F. Fixed Glass Assembly 9
G. Remote Controls, Wall Controls and Wall Switches 9
H. Before Lighting Fireplace 9
I. Intermittent Pilot Ignition (IPI) 10
J. Standing Pilot Ignition 11
K. After Appliance is Lit 12
L. Frequently Asked Questions 12
3 Maintenance and Service
A. Maintenance Tasks-Homeowner 13
B. Maintenance Tasks-Service Technician 14
Installer Guide
4 Getting Started
A. Typical Appliance System 16
B. Design and Installation Considerations 17
C. Tools and Supplies Needed 17
D. Inspect Appliance and Components 17
5 Framing and Clearances
A. Select Appliance Location 18
B. Constructing the Appliance Chase 19
C. Clearances 19
D. Mantel and Wall Projections 20
6 Termination Locations
A. Vent Termination Minimum Clearances 21
7 Vent Information and Diagrams
A. Approved Pipe 23
B. Vent Table Key 23
C. Use of Elbows 23
D. Measuring Standards 23
E. Vent Diagrams 24
8 Vent Clearances and Framing
A. Pipe Clearances to Combustibles 33
B. Wall Penetration Framing 33
C. Install the Ceiling Firestop 34
D. Install Attic Insulation Shield 35
9 Appliance Preparation
A. Top Vent 36
B. Rear Vent 37
C. Secure and Level the Appliance 38
10 Installing Vent Pipe
A. Assemble Vent Sections (DVP only) 39
B. Assemble Vent Sections (SLP Pipe Only) 40
C. Assemble MI Sections (DVP only) 40
D. Assemble Slip Sections 41
E. Secure the Vent Sections 42
F. Disassemble Vent Sections 42
G. Install Decorative Ceiling Components (SLP only) 43
H. Install Metal Roof Flashing 44
I. Install RF4-8 45
J. Install Vertical Termination Cap 46
K. Assemble and Install Storm Collar 46
L. Install Heat Shields and
Horizontal Termination Cap 47
11 Gas Information
A. Fuel Conversion 49
B. Gas Pressure 49
C. Gas Connection 49
D. High Altitude Installations 49
12 Electrical Information
A. Wiring Requirements 50
B. Standing Pilot Ignition System Wiring 50
C. Intellifi re Ignition System Wiring 50
D. Optional Accessories Requirements 50
E. Electrical Service and Repair 51
F. Junction Box Installation 52
G. Wall Switch Installation for Fan (Optional) 52
13 Finishing
A. Mantel and Wall Projections 53
B. Facing Material 54
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/083
Page 4
14 Appliance Setup
A. Remove the Packaging 55
B. Open Front Screen Assembly 55
C. Remove the Shipping Materials 55
D. Remove Fixed Glass Assembly 55
E. Clean the Appliance 55
F. Accessories 55
G. Place the Rockwool 56
H. Place the Lava Rock 56
I. Place the Vermiculite 56
J. Remove Screen Protector 56
K. Unpackage the Hood & Floor Cover 57
L. Install Hood 57
M. Install Floor Cover 58
N. Fixed Glass Assembly 58
O. Close the Screen Assembly 58
P. Air Shutter Setting 59
15 Troubleshooting
A. Standing Pilot Ignition System 60
B. Intellifi re Ignition System 62
16 Reference Materials
A. Appliance Dimension Diagram 64
B. Vent Components Diagrams 65
C. Service Parts 72
D. Optional Components 80
E. Contact Information 84
Î = Contains updated information.
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/084
Page 5
B. Limited Lifetime Warranty
Gas Appliance (Fireplace)
Limited Lifetime Warranty
HEARTH & HOME TECHNOLOGIES INC. (“HHT”) extends the following warranty for HEATILATOR® gas appliances installed in
the United States of America or Canada (the "Appliance"). Dealers and employees of HHT have no authority to make any warranty
or authorize any remedies in addition to or inconsistent with the terms of this warranty.
Limited Lifetime Warranty
HHT warrants the Appliance for component failure due to a manufacturing defect of any of the following components: combustion chamber, burner
pan, and logs. The Limited Lifetime Warranty specifi ed above is subject to the conditions, exclusions and limitations listed below, is for the period
the Appliance is owned by the original homeowner only, and is nontransferable.
1 Year Limited Warranty
HHT warrants the Appliance to be free from failure of any of the following components for a period of one year after installation: valve, fl exible gas
line connector, glass panel, fan, direct vent chimney components, factory paint, gasket, piezo ignitor, thermopile, thermocouple, junction box, pilot
assembly, shutoff valve, high limit switch, refractory liners, transformer, and control box. If the Heatilator Appliance is found to be defective in either
material or workmanship within one year of the date of original installation, HHT will provide replacement parts at no charge and pay reasonable
labor and freight costs, and is for the period of one year following the date of original installation of the Appliance.
Conditions, Exclusions, & Limitations of Liability
A. Both the Limited Lifetime and 1 Year Limited Warranties supplied by HHT apply only while the Appliance is in its location of original
installation. HHT’s obligation under this warranty does not extend to damages resulting from (1) installation, operation or maintenance of
the Appliance not in accordance with the Installation Instructions, Operating Instructions, and the Listing Agent Identifi cation Label furnished
with the Appliance; (2) installation which does not comply with local building codes; (3) shipping, improper handling, improper operation,
abuse, misuse, accident or unworkmanlike repairs; (4) environmental conditions, inadequate ventilation or drafting caused by tight sealing
construction of the structure, air handling devices such as exhaust fans or forced air furnaces, or other causes; (5) use of fuels other than
those specifi ed in the Operating Instructions; (6) installation or use of components not supplied with the Appliance or any other components
not expressly authorized and approved by HHT; and/or (7) modifi cation of the Appliance not expressly authorized and approved by HHT in
writing. This warranty is limited to only the component parts manufactured or supplied by HHT.
B. HHT’s liability under both the Limited Lifetime Warranty and the 1 Year Limited Warranty is limited to the replacement and repair of
defective components or workmanship during the applicable period. HHT may fully discharge all of its obligations under such warranties
by repairing the defective component(s) or at HHT’s discretion, providing replacement parts at no charge and paying reasonable labor and
freight costs.
C. EXCEPT TO THE EXTENT PROVIDED BY LAW, HHT MAKES NO EXPRESS WARRANTIES OTHER THAN THE WARRANTY
SPECIFIED HEREIN. THE DURATION OF ANY IMPLIED WARRANTY IS LIMITED TO DURATION OF THE WARRANTY SPECIFIED
ABOVE.
D. Some states do not allow exclusions or limitations of incidental or consequential damages, so those limitations may not apply to you. This
warranty gives you specifi c rights; you may also have other rights which vary from state to state.
How to Obtain Service
To obtain service under this warranty you must:
1. Send written notice of the claimed condition to Heatilator Technical Service Department, Hearth & Home Technologies, 1915 W. Saunders
Street, Mt. Pleasant, Iowa 52641-1563. You may also register your claim online at www.heatilator.com.
2. Provide proof of purchase, model number, serial number, and manufacturing date code to HHT.
3. Provide HHT reasonable opportunity to investigate the claim, including reasonable opportunity to inspect the Appliance prior to any repair
or replacement work and before the Appliance or any component of the Appliance has been removed from the place of original installation.
4. Obtain HHT’s consent to any warranty work before the work is done.
ADDITIONAL INFORMATION:
If you would like information on current HEATILATOR products or want to locate a dealer in your area, call 1-800-927-6841.
LABORATORY: Underwriters Laboratories, Inc. (UL)
TYPE: Direct Vent Gas Appliance
STANDARD: ANSI Z21.88a-2007/CSA 2.33a-2007,
CGA 2.17-M91, UL 307B
This product is listed to ANSI standards for “Vented Gas
Appliance Heaters” and applicable sections of “Gas Burning Heating Appliances for Manufactured Homes and Recreational Vehicles”, and “Gas Fired Appliances for Use at
High Altitudes”.
NOTICE: This installation must conform with local codes.
In the absence of local codes you must comply with the
National Fuel Gas Code, ANSI Z223.1-latest edition in
the U.S.A. and the CAN/CGA B149 Installation Codes in
Canada.
C. BTU Specifi cations
Novus NDVNDV3630NDV3933
Standing Pilot or IPI
Max/Min Input Rate (NG)20,000/14,00022,000/15,000
Orifi ce Size (NG)0.0830.089/#43
Max/Min Input Rate (LP)20,000/15,00022,000/15,000
Orifi ce Size (LP)0.0530.055/#54
Novus NDVNDV4236NDV4842
Standing Pilot or IPI
Max/Min Input Rate (NG)25,000/17,00030,000/20,500
Orifi ce Size (NG)0.093/#420.104/#37
Max/Min Input Rate (LP)25,000/17,00030,000/20,500
Orifi ce Size (LP)0.0580.063/#52
D. High Altitude Installations
NOTICE: If the heating value of the gas has been reduced,
these rules do not apply. Check with your local gas utility or
authorities having jurisdiction.
NOT INTENDED FOR USE AS A PRIMARY HEAT SOURCE.
This appliance is tested and approved as either supplemental
room heat or as a decorative appliance. It should not be factored as primary heat in residential heating calculations.
B. Tempered Glass Specifi cations
Hearth & Home Technologies appliances manufactured
with tempered glass may be installed in hazardous locations such as bathtub enclosures as defi ned by the Con-
sumer Product Safety Commission (CPSC). The tempered
glass has been tested and certifi ed to the requirements of ANSI Z97.1 and CPSC 16 CFR 1202 (Safety Glazing Certifi cation Council SGCC# 1595 and 1597. Architectural Test-
ing, Inc. Reports 02-31919.01 and 02-31917.01).
This statement is in compliance with CPSC 16 CFR Sec-tion 1201.5 “Certifi cation and labeling requirements” which
refers to 15 U.S. Code (USC) 2063 stating “…Such certifi cate shall accompany the product or shall otherwise be
furnished to any distributor or retailer to whom the product
is delivered.”
Some local building codes require the use of tempered
glass with permanent marking in such locations. Glass
meeting this requirement is available from the factory.
Please contact your dealer or distributor to order.
When installing above 2000 feet elevation:
• In the USA: Reduce burner orifi ce 4% for each 1000 feet
above 2000 feet.
• In CANADA: Reduce burner orifi ce 10% for elevations
between 2000 feet and 4500 feet. Above 4500 feet,
consult local gas utility.
E. Non-Combustible Materials Specifi cation
Material which will not ignite and burn. Such materials are
those consisting entirely of steel, iron, brick, tile, concrete,
slate, glass or plasters, or any combination thereof.
Materials that are reported as passing ASTM E 136, Stan-
dard Test Method for Behavior of Materials in a Vertical
Tube Furnace at 750 ºC and UL763 shall be considered
non-combustible materials.
F. Combustible Materials Specifi cation
Materials made of or surfaced with wood, compressed paper, plant fi bers, plastics, or other material that can ignite
and burn, whether fl ame proofed or not, or plastered or un-
plastered shall be considered combustible materials.
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/086
Page 7
Note: The following requirements reference various
Massachusetts and national codes not contained in this
document.
G. Requirements for the Commonwealth of Massacusetts
For all side wall horizontally vented gas fueled equipment
installed in every dwelling, building or structure used in
whole or in part for residential purposes, including those
owned or operated by the Commonwealth and where the
side wall exhaust vent termination is less than seven (7)
feet above fi nished grade in the area of the venting, in-
cluding but not limited to decks and porches, the following
requirements shall be satisfi ed:
Installation of Carbon Monoxide Detectors
At the time of installation of the side wall horizontal vented
gas fueled equipment, the installing plumber or gas fi tter
shall observe that a hard wired carbon monoxide detector
with an alarm and battery back-up is installed on the fl oor
level where the gas equipment is to be installed. In addition, the installing plumber or gas fi tter shall observe that
a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of
the dwelling, building or structure served by the side wall
horizontal vented gas fueled equipment. It shall be the
responsibility of the property owner to secure the services
of qualifi ed licensed professionals for the installation of
hard wired carbon monoxide detectors.
In the event that the side wall horizontally vented gas
fueled equipment is installed in a crawl space or an attic,
the hard wired carbon monoxide detector with alarm and
battery back-up may be installed on the next adjacent
fl oor level.
In the event that the requirements of this subdivision can
not be met at the time of completion of installation, the
owner shall have a period of thirty (30) days to comply
with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon
monoxide detector with an alarm shall be installed.
Approved Carbon Monoxide Detectors
Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA
720 and be ANSI/UL 2034 listed and IAS certifi ed.
Signage
A metal or plastic identifi cation plate shall be permanently
mounted to the exterior of the building at a minimum height
of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled
heating appliance or equipment. The sign shall read, in
print size no less than one-half (1/2) inch in size, “GAS
VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
Inspection
The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the
installation unless, upon inspection, the inspector ob-
serves carbon monoxide detectors and signage installed
in accordance with the provisions of 248 CMR 5.08(2)(a)1
through 4.
Exemptions
The following equipment is exempt from 248 CMR
5.08(2)(a)1 through 4:
• The equipment listed in Chapter 10 entitled “Equipment
Not Required To Be Vented” in the most current edition
of NFPA 54 as adopted by the Board; and
• Product Approved side wall horizontally vented gas fueled
equipment installed in a room or structure separate from
the dwelling, building or structure used in whole or in part
for residential purposes.
MANUFACTURER REQUIREMENTS
Gas Equipment Venting System Provided
When the manufacturer of Product Approved side wall
horizontally vented gas equipment provides a venting
system design or venting system components with the
equipment, the instructions provided by the manufacturer
for installation of the equipment and the venting system
shall include:
• Detailed instructions for the installation of the venting
system design or the venting system components; and
• A complete parts list for the venting system design or
venting system.
Gas Equipment Venting System NOT Provided
When the manufacturer of a Product Approved side
wall horizontally vented gas fueled equipment does not
provide the parts for venting the fl ue gases, but identi-fi es “special venting systems”, the following requirements
shall be satisfi ed by the manufacturer:
• The referenced “special venting system” instructions shall
be included with the appliance or equipment installation
instructions; and
• The “special venting systems” shall be Product
Approved by the Board, and the instructions for that
system shall include a parts list and detailed installation
instructions.
A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting
instructions, and/or all venting design instructions shall
remain with the appliance or equipment at the completion
of the installation.
See Gas Connection section for additional Commonwealth of Massachusetts requirements.
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/087
Page 8
2
User Guide
2
Operating Instructions
A. Gas Fireplace Safety
WARNING
HOT SURFACES!
Glass and other surfaces are hot during
operation AND cool down.
Hot glass will cause burns.
• DO NOT touch glass until it is cooled
• NEVER allow children to touch glass
• Keep children away
• CAREFULLY SUPERVISE children in same room as
fi replace.
• Alert children and adults to hazards of high temperatures.
High temperatures may ignite clothing or other fl ammable
materials.
• Keep clothing, furniture, draperies and other fl ammable
materials away.
This appliance has been supplied with an integral barrier
to prevent direct contact with the fi xed glass panel. DO
NOT operate the appliance with the barrier removed.
Contact your dealer or Hearth & Home Technologies if the barrier
is not present or help is needed to properly install one.
• Install a switch lock or a wall/remote control with child
protection lockout feature.
• Keep remote controls out of reach of children.
• Never leave children alone near a hot fi replace, whether
operating or cooling down.
• Teach children to NEVER touch the fi replace.
• Consider not using the fi replace when children will be
present.
Contact your dealer for more information, or visit: www.
hpba.org/staysafe.
To prevent unintended operation when not using your fi re-
place for an extended period of time (summer months, vacations/trips, etc):
• Remove batteries from remote controls.
• Turn off wall controls.
• Unplug 3 volt adapter plug and remove battieres on IPI
models.
• Turn off gas controls valve on standing pilot models.
When lighting the pilot light on fi replaces with a standing
pilot, remove the fi xed glass assembly so you can detect
presence of residual gas build-up. See Standing Pilot Lighting instructions and Maintenance Tasks.
If you expect that small children or vulnerable adults may
come into contact with this fi replace, the following precau-
tions are recommended:
• Install a physical barrier such as:
- A decorative screen.
- Adjustable safety gate.
DECORATIVE DOORS
(NOT SHOWN)
SECTION 2.E.
HEARTH
CLEAR SPACE
SECTION 2.D.
B. Your Fireplace
WARNING! DO NOT operate fi replace before reading
and understanding operating instructions. Failure to
operate fi replace according to operating instructions could
cause fi re or injury.
MANTEL
FIXED GLASS ASSEMBLY
SECTION 14.K.
Figure 2.1 General Operating Parts
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/088
Page 9
C. Fan Kit (optional)
• Refer to Figure 2.1 for location of control.
F. Fixed Glass Assembly
See Section 14.K.
D. Clear Space
WARNING! DO NOT place combustible objects in front of
the fi replace or block louvers. High temperatures may start
a fi re. See Figure 2.2.
Avoid placing candles and other heat-sensitive objects on
mantel or hearth. Heat may damage these objects.
3 FT
CLEAR SPACE
. IN FR
ONT OF F
IRE
PLA
CE
G. Remote Controls, Wall Controls and Wall
Switches
Follow the instructions supplied with the control installed to
operate your fi replace:
For safety:
• Install a switch lock or a wall/remote control with child
protection lockout feature.
• Keep remote controls out of reach of children.
See your dealer if you have questions.
H. Before Lighting Fireplace
Before operating this fi replace for the fi rst time, have a
qualifi ed technician:
• Verify all shipping materials have been removed from
inside and/or underneath the fi rebox.
• Review proper placement of logs, ember material and/or
other decorative materials.
• Check the wiring.
• Check the air shutter adjustment.
• Ensure that there are no gas leaks.
• Ensure that the glass is sealed and in the proper position
and that the integral barrier is in place.
Figure 2.2 Clear Space
E. Decorative Doors and Fronts
WARNING! Risk of Fire! Install ONLY doors or fronts
approved by Hearth & Home Technologies. Unapproved
doors or fronts may cause appliance to overheat.
This appliance has been supplied with an integral barrier
to prevent direct contact with the fi xed glass panel. DO
NOT operate the appliance with the barrier removed.
Contact your dealer or Hearth & Home Technologies if the
barrier is not present or help is needed to properly install
one.
For more information refer to the instructions supplied with
your decorative door or front.
WARNING! Risk of Fire/Asphyxiation! DO NOT operate
fi replace with fi xed glass assembly removed.
Determine if this fi replace has a standing pilot or an
Intellifi re ignition system. Ask your dealer or open control
access panel, look at valve assembly.
• A standing pilot ignition will have a red or black ignitor
button (refer to Figure 2.3).
• An Intellifi re ignition system will not have a button.
Red or Black
Button
Figure 2.3 Ignitor Button
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/089
Page 10
I. Intermittent Pilot Ignition (IPI)
The IPI system may be operated with two D-cell batteries. When using batteries, unplug the transformer. To prolong battery
life, remove them when using the transformer.
Improper installation,
This appliance must be properly connected to a
venting system in accordance with the
This appliance must be installed in accordance with
local codes, if any; if not, follow ANSI Z223.1 or, in
This appliance needs fresh air for safe operation
and must be installed so there are provisions for
adequate combustion and ventilation air.
Canada, current CAN/CGA-B149.
manufacturer's installation instructions.
WARNING:
adjustment, alteration, service or maintenance can
cause injury or property damage. Refer to the
owner's information manual provided with the
appliance. For assistance or additional information
consult a qualified installer, service agency or the
department.
valve or turn the gas control knob. Never use tools. If the
lever or knob will not move by hand, don't try to repair it, call
a qualified service technician. Force or attempted repair may
result in a fire or explosion.
Immediately call a qualified service technician to inspect the
appliance and to replace any part of the control system and
C. Use only your hand to push in and move the gas control
• If you cannot reach your gas supplier, call the fire
D. Do not use this appliance if any part has been under water.
Hot while in operation. Do
CAUTION:
not touch. Keep children, clothing, furniture,
gas supplier.
any gas control which has been under water.
WARNING RISK OF FIRE
gasoline and other liquids having flammable vapors
away.
This appliance is intended to burn a specified gas
fuel only. Do not attempt to use with solid wood fuel
or another type of fuel. Do not attempt to modify or
use any other type of gas burner system.
Follow "B" in the safety information above on this label. If you don't
smell gas, go to the next step.
turn on the wall switch or set the thermostat to the desired setting.
GAS TO APPLIANCE" and call your service technician or gas supplier.
5. Wait five minutes to clear out any gas. If you then smell gas, STOP!
6. To turn on the burner, turn on all electric power to this appliance and
7. If the appliance will not operate, follow the instructions "TO TURN OFF
NATURAL GAS
For use with natural gas or propane. A conversion kit
before servicing. If for any reason the original wire
WARNING: Disconnect the electric power
as supplied by the manufacturer shall be used to
supplied with the appliance must be replaced, it must
be replaced with 105° C or its equivalent.
or push the gas control lever to the "OFF" position. Do not
force.
3. Push the gas control lever in and move to the "OFF" position
bed-sitting room.
convert this appliance to the alternative fuel.
* Also certified for installation in a bedroom or a
* For U.S. only!
33631D
4. Replace the control access panel.
or explosion may result causing property damage,
personal injury or loss of life.
WARNING: If you do not follow these instructions exactly, a fire
FOR YOUR SAFETY READ BEFORE LIGHTING
automatically lights the pilot. Do not try to light the pilot by
hand.
gas. Be sure to smell next to the floor because some gas is
heavier than air and will settle on the floor.
A. This appliance is equipped with an ignition device which
B. BEFORE LIGHTING smell all around the appliance area for
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0810
your building.
• Immediately call your gas supplier from a neighbor's
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any phone in
WHAT TO DO IF YOU SMELL GAS
LIGHTING INSTRUCTIONS
phone. Follow the gas supplier's instructions.
lowest setting.
automatically lights the pilot. Do NOT try to light the pilot by
hand.
1. STOP! Read the safety information above on this label.
2. Turn wall switch to the "OFF" position or thermostat to the
3. Turn off all electric power to the appliance.
4. This appliance is equipped with an ignition device which
TO TURN OFF GAS TO APPLIANCE
performed.
Due to high surface temperatures, keep children, clothing and furniture away.
1. Turn off wall switch or set thermostat to lowest setting.
2. Turn off all electric power to the appliance if service is to be
Keep burner and control compartment clean. See installation and operating instructions accompanying the appliance.
Page 11
J. Standing Pilot Ignition
Improper installation,
This appliance must be properly connected to a
venting system in accordance with the
This appliance must be installed in accordance with
local codes, if any; if not, follow ANSI Z223.1 or, in
This appliance needs fresh air for safe operation
and must be installed so there are provisions for
adequate combustion and ventilation air.
Canada, current CAN/CGA-B149.
manufacturer's installation instructions.
adjustment, alteration, service or maintenance can
cause injury or property damage. Refer to the owner's
information manual provided with the appliance. For
assistance or additional information consult a
WARNING:
qualified installer, service agency or the gas supplier.
Hot while in operation. Do
not touch. Keep children, clothing, furniture,
gasoline and other liquids having flammable vapors
CAUTION:
WARNING RISK OF FIRE
away.
This appliance is intended to burn a specified gas
fuel only. Do not attempt to use with solid wood fuel
or another type of fuel. Do not attempt to modify or
Disconnect the electric power
use any other type of gas burner system.
WARNING:
For use with natural gas or propane. A conversion
before servicing. If for any reason the original wire
supplied with the appliance must be replaced, it must be
replaced with 105° C or its equivalent.
VENT
OFF
NATURAL GAS
bed-sitting room.
* Also certified for installation in a bedroom or a
PILOT
OFF
ON
11
OFF
PILOT
ON
8
ON
OFF
PIL
OT
5
5
* For U.S. only!
29097D
kit as supplied by the manufacturer shall be used to
convert this appliance to the alternative fuel.
ON
7
the manual gas valve will not push in or turn by hand, don't try
to repair it; call a qualified service technician. Force or
attempted repair may result in a fire or explosion.
Immediately call a qualified service technician to inspect the
appliance and to replace any part of the control system and any
gas control which has been under water.
C. Use only your hand to push in or turn knob. Never use tools. If
• If you cannot reach your gas supplier, call the fire department.
explosion may result causing property damage, personal
injury or loss of life.
D. Do not use this appliance if any part has been under water.
Stop! Read the safety information above on this label.
LIGHTING INSTRUCTIONS
WARNING: If you do not follow these instructions exactly, a fire or
FOR YOUR SAFETY READ BEFORE LIGHTING
lighting the pilot, follow these instructions exactly.
Be sure to smell next to the floor because some gas is heavier
than air and will settle on the floor.
A. This appliance has a pilot which must be lighted by hand. When
B. BEFORE LIGHTING smell all around the appliance area for gas.
building.
Follow the gas supplier's instructions.
• Immediately call your gas supplier from a neighbor's phone.
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any phone in your
WHAT TO DO IF YOU SMELL GAS
lowest setting.
clear out any gas. If you then smell gas, STOP! Follow "B" in the
safety information above on this label. If you don't smell gas, go
to next step.
depressed to pass "PILOT" position.)
1. Turn wall switch to the "OFF" position or thermostat to the
2. Remove control access panel.
3. Turn manual gas valve to CLOSED. Wait five [5] minutes to
4. Turn gas line to "OPEN".
5. Turn pilot knob clockwise to "OFF". (Knob may have to be
6. Locate pilot assembly inside appliance.
7. Locate red ignitor button.
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0811
4. OPEN
3. CLOSED
3. Turn manual gas valve to "CLOSED position. Do not force.
4. Replace control access panel.
TO TURN OFF GAS TO APPLIANCE
12-15 times until small blue pilot flame appears.
should remain lit. If pilot goes out, wait 5 minutes and repeat
Steps 3-9.
OFF GAS TO APPLIANCE" and call your service technician or
gas supplier.
hand.
1. Turn off wall switch or set thermostat to lowest setting.
2. Remove control access panel.
Due to high surface termperatures, keep children, clothing and furniture away.
8. Turn pilot knob to "PILOT" and push in.
9. Continue to hold in pilot knob and push the red ignitor button
10. Continue to hold in pilot knob for approximately one minute. Pilot
11. Release and turn knob counterclockwise to "ON".
12. If appliance will not operate, follow the instructions "TO TURN
NOTE: To light main burner, turn wall switch to "ON". Do not light by
Keep burner and control compartment clean. See installation and operating instructions accompanying the appliance.
Page 12
K. After Appliance is Lit
Initial Break-in Procedure
• The appliance should be run three to four hours
continuously on high.
• Turn the appliance off and allow it to completely cool.
• Remove and clean fi xed glass assembly. See Section 3.
• Replace the fi xed glass assembly and run continuously
on high an additional 12 hours.
This cures the materials used to manufacture the fi re-
place.
NOTICE! Open windows for air circulation during appliance break-in.
• Some people may be sensitive to smoke and odors.
• Smoke detectors may activate.
L. Frequently Asked Questions
ISSUESOLUTIONS
Condensation on the glass
Blue fl ames
Odor from appliance
This is a result of gas combustion and temperature variations. As the appliance warms, this
condensation will disappear.
This is a result of normal operation and the fl ames will begin to yellow as the appliance is
allowed to burn for 20 to 40 minutes.
When fi rst operated, this appliance may release an odor for the fi rst several hours. This is
caused by the curing of materials from manufacturing. Odor may also be released from fi nishing
materials and adhesives used near the appliance. These circumstances may require additional
curing related to the installation environment.
Film on the glass
Metallic noise
This is a normal result of the curing process of the paint and logs. Glass should be cleaned
within 3 to 4 hours of initial burning. A non-abrasive cleaner such as gas appliance glass cleaner
may be necessary. See your dealer.
Noise is caused by metal expanding and contracting as it heats up and cools down, similar to
the sound produced by a furnace or heating duct. This noise does not affect the operation or
longevity of the appliance.
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0812
Page 13
3
3
Maintenance and Service
Any safety screen or guard removed for servicing must be replaced prior to operating the appliance.
When properly maintained, your appliance will give you
many years of trouble-free service. We recommend annual service by a qualifi ed technician.
A. Maintenance Tasks-Homeowner
Installation and repair should be done by a qualifi ed technician
only. The appliance should be inspected before use and at least
annually by a professional service person.
The following tasks may be performed annually by the homeowner. If you are uncomfortable performing any of the
listed tasks, please call your dealer for a service appointment.
More frequent cleaning may be required due to lint from
carpeting or other factors. Control compartment, burner
and circulating air passageway of the appliance must be
kept clean.
CAUTION! Risk of Burns! The appliance should be
turned off and cooled before servicing.
• Vacuum and wipe out dust, cobwebs, debris or pet hair.
Use caution when cleaning these areas. Screw tips that
have penetrated the sheet metal are sharp and should
be avoided.
broom, fl ashlight, voltmeter, indexed drill bit set, and a
manometer.
• Verify burner is properly secured and aligned with pilot
or igniter.
• Clean off burner top, inspect for plugged ports, corrosion
or deterioration. Replace burner if necessary.
• Replace ember materials with new dime-size pieces.
DO NOT block ports or obstruct lighting paths. Refer to
Section 14 for proper ember placement.
• Verify batteries have been removed from battery backup IPI systems to prevent premature battery failure or
leaking.
• Check for smooth lighting and ignition carryover to all
ports. Verify that there is no ignition delay.
• Inspect for lifting or other fl ame problems.
• Verify air shutter setting is correct. See Section 14.N. for
required air shutter setting. Verify air shutter is clear of
dust and debris.
• Inspect orifi ce for soot, dirt and corrosion. Verify orifi ce
size is correct. See Service Parts List for proper orifi ce
sizing.
• Verify manifold and inlet pressures. Adjust regulator as
required.
• Inspect pilot fl ame pattern and strength. See Figures 3.1
and 3.2 for proper pilot fl ame pattern. Clean or replace
orifi ce spud as necessary.
• Inspect thermocouple/thermopile or IPI fl ame sensing rod
for soot, corrosion and deterioration. Clean with emery
cloth or replace as required.
• Verify thermocouple/thermopile or IPI millivolt output.
Replace as necessary.
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0814
Page 15
(Either cobrahead or SIT)
PRODUCT SPECIFIC
Figure 3.1 IPI Flame Patterns
Figure 3.2 Standing Pilot Flame Patterns
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0815
Page 16
4
4
A. Typical Appliance System
NOTICE: Illustrations and photos refl ect typical installations and are for design purposes only. Illustrations/diagrams are not
drawn to scale. Actual product may vary from pictures in manual
Getting Started
VERTICAL TERMINATION CAP
(SECTION 10.F. )
NOTE: An installation will have either a
vertical termination or a horizontal
termination. It will not have both (as
NON-COMBUSTIBLE ROOF FLASHING
MAINTAINS MINIMUM CLEARANCE
AROUND PIPE (SECTION 10.E.)
shown).
STORM COLLAR
(SECTION 10.E. )
VENT PIPE PENETRATES ROOF
PREFERABLY WITHOUT AFFECTING
ROOF RAFTERS
Installer Guide
VENT PIPE (SECTION 8)
CEILING FIRESTOP
ON FLOOR OF ATTIC
(SECTION 8.C.)
HORIZONTAL TERMINATION CAP
(SECTION 10.H.)
FRAMING/HEADER
(SECTION 5)
ATTIC INSULATION SHIELD (NOT SHOWN) MUST
BE USED HERE TO KEEP INSULATION AWAY
FROM VENT PIPE IF ATTIC IS INSULATED
(SECTION 8.E.)
FRAMING HEADED OFF
IN CEILING JOISTS
(SECTION 8.C.)
OPTIONAL
WALL SW IT CH
(Section 12.G.)
MANTEL AND MANTEL LEG
(SECTION 5.D. & 13.A.)
SURROUND (SECTION 14.M.)
GAS LINE
(SECTION 11)
Figure 4.1 Typical Appliance System
HEARTH EXTENSION
(Section 13.E.)
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0816
Page 17
B. Design and Installation Considerations
Heatilator direct vent gas appliances are designed to operate with all combustion air siphoned from outside of the
building and all exhaust gases expelled to the outside. No
additional outside air source is required.
Installation MUST comply with local, regional, state and
national codes and regulations. Consult insurance carrier,
local building inspector, fi re offi cials or authorities having
jurisdiction over restrictions, installation inspection and
permits.
Before installing, determine the following:
• Where the appliance is to be installed.
• The vent system confi guration to be used.
• Gas supply piping.
• Electrical wiring requirements.
• Framing and fi nishing details.
• Whether optional accessories—devices such as a fan,
wall switch, or remote control—are desired.
Improper installation, adjustment, alteration, service or
maintenance can cause injury or property damage. For
assistance or additional information, consult a qualifi ed
technician, service agency or your dealer.
C. Tools and Supplies Needed
Before beginning the installation be sure that the following
tools and building supplies are available.
Tape measure Framing material
Pliers High temperature caulking material
Hammer Phillips screwdriver
Gloves Framing square
Voltmeter Electric drill and bits (1/4 in.)
Plumb line Safety glasses
Level Reciprocating saw
Manometer Flat blade screwdriver
Noncorrosive leak check solution
1/2 - 3/4 inch length, #6 or #8 Self-drilling screws
One 1/4 inch female connection (for optional fan).
D. Inspect Appliance and Components
• Carefully remove the appliance and components from
the packaging.
• The vent system components and decorative doors and
fronts may be shipped in separate packages.
• If packaged separately, the log set and appliance grate
must be installed.
• Report to your dealer any parts damaged in shipment,
particularly the condition of the glass.
• Read all of the instructions before starting the instal-
lation. Follow these instructions carefully during the
installation to ensure maximum safety and benefi t.
WARNING! Risk of Fire or Explosion! Damaged parts
could impair safe operation. DO NOT install damaged,
incomplete or substitute components. Keep appliance dry.
Hearth & Home Technologies disclaims any responsibility for,
and the warranty will be voided by, the following actions:
• Installation and use of any damaged appliance or vent
system component.
• Modifi cation of the appliance or vent system.
• Installation other than as instructed by Hearth & Home
Technologies.
• Improper positioning of the gas logs or the glass door.
• Installation and/or use of any component part not approved
by Hearth & Home Technologies.
Any such action may cause a fi re hazard.
WARNING! Risk of Fire,/Explosion/Electric Shock! DO
NOT use this appliance if any part has been under water.
Call a qualifi ed technician to inspect the appliance and to
replace any part of the control system and/or gas control
which has been under water.
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0817
Page 18
5
5
Framing and Clearances
A. Select Appliance Location
When selecting a location for your appliance it is important to
consider the required clearances to walls (see Figure 5.1).
WARNING! Risk of Fire or Burns! Provide adequate
clearance around air openings and for service access.
Due to high temperatures, the appliance should be located out of traffi c and away from furniture and draperies.
B
1/2 in. (13 mm)
min. appliance
to combustibles
Drywall
B
A
Top Vent
One 90° elbow
Horiz Term
In addition to these framing dimensions, also reference the
following sections:
• Clearances and Mantel Projections (Sections 3.C. and 3.D.)
• Vent Clearances and Framing (Section 6)
NOTICE: Illustrations refl ect typical installations and are
FOR DESIGN PURPOSES ONLY. Illustrations/diagrams
are not drawn to scale. Actual installation may vary due to
individual design preference.
1 in. (25 mm)
min. pipe to
combustibles
D
A
G
Alcove
Installation
C
48 in.
(1219 mm)
maximum
Rear vent
One 45° elbow
Horiz Term
D
1/2 in. (13 mm) min.
appliance to
combustibles
A
E
1 in. (25 mm)
min. pipe to
combustibles
ModelABCDEFG
NDV3630 inches3633-1/219-5/843-3/84753-1/437
NDV3933 inches3935-1/219-5/843-3/84753-1/440
NDV4236 inches4237-5/819-5/843-3/84753-1/443
NDV4842 inches4841-7/819-5/843-3/84753-1/449
Figure 5.1 Appliance Locations
A
E
Rear Vent
One 90° elbow
Vert Term
mm914851498110211941353940
mm9919024981102119413531016
mm10679564981102119413531092
mm121910644981102119413531245
No elbows
Horiz Term
A
Rear Vent
Two 90° elbows
Horiz Term
C
A
F
F
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0818
Page 19
B. Constructing the Appliance Chase
A chase is a vertical box-like structure built to enclose the
gas appliance and/or its vent system. In cooler climates the
vent should enclosed inside the chase.
NOTICE: Treatment of ceiling fi restops and wall shield
fi restops and construction of the chase may vary with the
type of building. These instructions are not substitutes for the
requirements of local building codes. Therefore, you MUST
check local building codes to determine the requirements
to these steps.
Chases should be constructed in the manner of all outside
walls of the home to prevent cold air drafting problems.
The chase should not break the outside building envelope
in any manner.
Walls, ceiling, base plate and cantilever fl oor of the chase
should be insulated. Vapor and air infi ltration barriers
should be installed in the chase as per regional codes for
the rest of the home. Additionally, in regions where cold
air infi ltration may be an issue, the inside surfaces may be
sheetrocked and taped for maximum air tightness.
To further prevent drafts, the wall shield and ceiling fi re-
stops should be caulked with high temperature caulk to
seal gaps. Gas line holes and other openings should be
caulked with high temp caulk or stuffed with unfaced insulation. If the appliance is being installed on a cement slab,
a layer of plywood may be placed underneath to prevent
conducting cold up into the room.
C. Clearances
NOTICE: Install appliance on hard metal or wood surfaces
extending full width and depth. DO NOT install directly on
carpeting, vinyl, tile or any combustible material other than
wood.
WARNING! Risk of Fire! Maintain specifi ed air space
clearances to appliance and vent pipe:
• Insulation and other materials must be secured to prevent
accidental contact.
• Failure to maintain airspace may cause overheating and
a fi re.
1/2 in.
(13 mm)
Combustible flooring may be installed next
to the front of the appliance.
Clearance to Ceiling
30 in. (762 mm)
0 in. TO LEVEL
OF STANDOFFS
1/2 in.
(13 mm)
Drywall
0 in.
Note: If the inside of the framed cavity is to be fi nished,
the framing dimensions must include the fi nished surface.
If drywall is to be attached to the rear wall, the depth
must be measured from the drywall surface.
D
B
36 in.
(914 mm)
Combustible Object
Figure 5.2 Clearances to Combustibles
0 in.
Model
NDV363036 in./914 mm34-7/8 in./886 mm19-5/8 in./498 mm10 in./254 mm
NDV393339 in./991 mm34-7/8 in./886 mm19-5/8 in./498 mm10 in./254 mm
NDV423642 in./1067 mm34-7/8 in./886 mm19-5/8 in./498 mm10 in./254 mm
NDV484248 in./1219 mm34-7/8 in./886 mm19-5/8 in./498 mm10 in./254 mm
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0819
Rough Opening
(Width)
C
A
A
B
Rough Opening
(Height)
C
Rough Opening
(Depth)
D
Rough Opening
(DVP Pipe)
Page 20
D. Mantel and Wall Projections
WARNING! Risk of Fire! Comply with all minimum clearances to combustibles as specifi ed. Framing or fi nishing
material closer than the minimums listed must be constructed entirely of noncombustible materials (i.e., steel studs,
concrete board, etc).
Mantel Legs or Wall Projections
Top of
Appliance
Drywall
Mantels
30 in. minimum
to ceiling
18
17
16
14-1/2
15-1/4
16
15
14
13
12-1/4
13-3/4
13
12
11
10
11-1/2
9
10-3/4
8
7
6
5
6-1/4
7-3/4
7
4
3
5-1/2
5
10
9-1/4
8-1/2
Measured from top of hood (in inches)
Figure 5.3 Clearances To Mantels Or Other Combustibles Above
Appliance
A
B
Mantel Leg or
Perpendicular Wall
1 in. (25 mm) min.
A
to perpendicular wall
3-1/2 in. (89 mm) min.
B
from fireplace opening
to perpendicular wall
Figure 5.4 Mantel Leg or Wall Projections (Acceptable on both
sides of opening)
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0820
Page 21
6
6
Termination Locations
A. Vent Termination Minimum Clearances
WARNING
Fire Risk.
Maintain vent clearance to combustibles as
specifi ed.
• DO NOT pack air space with insulation or other
materials.
Failure to keep insulation or other materials away
from vent pipe may cause fi re.
Horizontal
overhang
24 in. min.
(610 mm)
Termination
Cap
20 in.
(508 mm)
Lowest
Discharge
Opening
Vertical
wall
Measure vertical clearances from this surface.
Measure horizontal clearances from this surface.
(See Figure 6.5 for specifi c clearances)
Figure 6.2 Clearance To Horizontal Termination Cap
Direct Vent Gas, Wood or Fuel
Oil Termination
20 in.
(508 mm)
(minimum) to
Perpendicular
Wall
(DV only)
18 in.
(457 mm)
A
B
Storm Collar
Roof
Flashing
H (min.) - Minimum height
from roof to lowest
discharge opening.
Roof Pitch H (Min.) Ft. Roof Pitch H (Min.) Ft.
Flat to 6/12 1.0* Over 11/12 to 12/12 4.0
Over 6/12 to 7/12 1.25* Over 12/12 to 14/12 5.0
Over 7/12 to 8/12 1.5* Over 14/12 to 16/12 6.0
Over 8/12 to 9/12 2.0* Over 16/12 to 18/12 7.0
Over 9/12 to 10/12 2.5 Over 18/12 to 20/12 7.5
Over 10/12 to 11/12 3.25 Over 20/12 to 21/12 8.0
* 3 ft. minimum in snow regions
Figure 6.1 Minimum Height From Roof To Lowest Discharge
Opening
X
12
Roof Pitch
is X / 12
Gas
Termination
Termination Caps Staggered Height
A Gas Termination Wood or Fuel Oil Termination
B 6 in.
Figure 6.3 Staggered Termination Caps
(152 mm) min. 20 in. (508 mm) min.
Direct Vent Gas, Wood or Fuel
Oil Termination
Wood, Gas or
Fuel Oil
Termination
20 in. min. *
(508 mm)
20 in.
(508 mm)
(minimum) to
Perpendicular
Wall
(DV only)
Termination Caps Same Height
* If using decorative cap cover(s), this distance may
need to be increased. Refer to the installation instruc tions supplied with the decorative cap cover.
Figure 6.4 Leveled Termination Caps
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0821
Page 22
H
D
E
V
L
B
C
Fixed
V
Closed
V
F
B
V
Openable
B
V TERMINATION CAP
V
Fixed
Closed
J
A
B
Measure vertical clearances
from this surface
T
Measure horizontal clearances
Covered Alcove
from this surface.
Dimension Descriptions
A Clearance above the ground, a veranda, porch, deck or balcony - 12
in. (30 cm) minimum. *
B Clearance to window or door that may be opened – 10,000 BTUs
or less, 6 in. (15 cm) minimum; 10,000-50,000 BTUs, 9 in. (23 cm)
minimum; over 50,000 BTUs, 12 in. (30 cm) minimum. *
C Clearance to permanently closed window – 12 in. (30 cm) minimum
- recommended to prevent condensation on window.
D Vertical clearance to ventilated soffi t located above the termination
within a horizontal distance of 2 ft (60 cm) from the centerline of the
termination – 18 in. (46 cm) minimum. **
E Vertical clearance to unventilated soffi t - 12 in. (30 cm) minimum. **
F Clearance to outside corner - 6 in. (15 cm) minimum.
G Clearance to inside corner - 6 in. (15 cm) minimum.
H Not to be installed above a meter/regulator assembly within 3 ft (90
cm) horizontally* from the center line of the regulator (Canada only)
I Clearance to service regulator vent outlet – 3 ft (.91 m) U.S. minimum
and 3 ft (.91 m) Canada minimum. *
J Clearance to non-mechanical air supply inlet into building or the
combustion air inlet to any other appliance – 9” (23 cm) U.S. minimum
and 12 in. (30 cm) Canada minimum. *
K Clearance to mechanical air supply inlet - 3 ft (.91 m) U.S. minimum
and 6 ft (1.8 m) Canada minimum. *
L Clearance above a paved sidewalk or paved driveway located on public
property - 7 ft (2.1 m) minimum.
A vent may not terminate directly above a sidewalk or paved driveway
which is located between two single family dwellings and serves both
dwellings.
M Clearance under veranda, porch, deck or balcony - 12 in. (30 cm)
minimum. * Recommended 30 in. (76 cm) for vinyl or plastic.
Only permitted if veranda, porch, deck or balcony is fully open on a
minimum of 2 sides beneath the fl oor. *
N Vertical clearance between two horizontal termination caps – 12 in. (30
cm) minimum.
Figure 6.5 Minimum Clearances for Terminations
O
X
AIR SUPPLY INLET
R
Applications
N
V
V
B
X
GAS METER
Q
P
V
S
M
I
RESTRICTION ZONE
(TERMINATION NOT
ALLOWED)
V
V
Clearances to Electrical Service
K X
U
G
V
A
V
W
lectrical
Service
D*
V
V
U
V
O Horizontal clearance between two horizontal termination caps – 12 in.
(30 cm) minimum.
P 6” - Non-vinyl sidewalls
12” – Vinyl sidewalls
Q 18” – Non-vinyl soffi t and overhang42” – Vinyl soffi t and overhang
S
min
T
1 cap3 ft2 x S actual
2 caps6 ft1 x S actual
3 caps9 ft2/3 x S actual
4 caps12 ft1/2 x S actual
S
= # term caps x 3T
min
= (2/# term caps) x S (actual)
max
R 8 ft.
U 6” min. – Clearance from sides of electrical service.
W 12” min. – Clearance above electrical service.
* As specifi ed in CGA B149 Installation CodesNote: Local codes or regulations may require different clearances.
** Clearance required to vinyl soffi t material – 30 in. (76 cm) minimum.Note: Location of the vent termination must not interfere with access
to the electrical service.
WARNING!
In the U.S.: Vent system termination is NOT permitted in screened
porches. You must follow side wall, overhang and ground clearances
as stated in the instructions.
In Canada: Vent system termination is NOT permitted in screened
porches. Vent system termination is permitted in porch areas with two
or more sides open. You must follow all side wall, overhang and ground
clearances as stated in the instructions.
Hearth & Home Technologies assumes no responsibility for the improper
performance of the appliance when the venting system does not meet
these requirements.
max
CAUTION: IF EXTERIOR WALLS ARE FINISHED WITH VINYL SIDING, IT IS SUGGESTED THAT A VINYL PROTECTOR KIT BE INSTALLED.
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0822
Page 23
7
7
Vent Information and Diagrams
A. Approved Pipe
This appliance is approved for use with Hearth & Home
Technologies DVP and SLP venting systems. Refer to Sec-
Î
tion 16B for vent component information.
DO NOT mix pipe, fi ttings or joining methods from different
manufacturers.
The pipe is tested to be run inside an enclosed wall. There
is no requirement for inspection openings at each joint
within the wall.
WARNING! Risk of Fire or Asphyxiation. This appliance
requires a separate vent. DO NOT vent to a pipe serving a
separate solid fuel burning appliance.
B. Vent Table Key
The abbreviations listed in this vent table key are used in
the vent diagrams.
SymbolDescription
V
V
H
H
First section (closest to appliance) of vertical length
1
Second section of vertical length
2
First section (closest to appliance) of horizontal length
1
Subsequent sections of horizontal length
2
D. Measuring Standards
Vertical and horizontal measurements listed in the vent
diagrams were made using the following standards.
• Pipe measurements are shown using the effective length
of pipe (see Figure 7.2).
• Measurements are made from the appliance outer wrap,
not from the standoffs.
• Horizontal terminations are measured to the outside
mounting surface (fl ange of termination cap) (see Figure
Diagonal runs have both vertical and horizontal vent aspects
when calculating the effects. Use the rise for the vertical
aspect and the run for the horizontal aspect (see Figure
7.1).
Two 45º elbows may be used in place of one 90º elbow. On
45º runs, one foot of diagonal is equal to 8-1/2 (216 mm)
inches horizontal run and 8-1/2 (216 mm) inches vertical
run. A length of straight pipe is allowed between two 45º
elbows (see Figure 7.1).
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0823
Page 24
E. Vent Diagrams
To replace the fi rst starter elbow with two 45° elbows, refer
to Figure 7.4. All other 90° elbows can be replaced with
two 45° elbows.
General Rules:
• SUBTRACT 3 ft. from the total H measurement for each
90° elbow installed horizontally.
• SUBTRACT 1-1/2 ft. from the total H measurement for
each 45° elbow installed horizontally.
• A maximum of three 90° elbows (or six 45° elbows) may
be used in any vent confi guration. Some elbows may be
installed horizontally.
• Elbows may be placed back to back anywhere in the
system as long as the fi rst 90° elbow is a starter elbow
except as shown in Figure 7.3.
• When penetrating a combustible wall, a wall shield
fi restop must be installed.
• When penetrating a combustible ceiling, a ceiling fi restop
must be installed.
• Horizontal runs of vent do not require vertical rise;
horizontal runs may be level.
Note: The NDV series appliances can adapt to SLP series
Î
vent pipe when venting off the top of the appliance. You
must use a DVP-SLP24 adapter which can only be attached
to the appliance starting collar.
When looking at horizontal termination diagrams, the
adapter is not counted as part of the minimum vertical
min.) requirements.
(V
1
Whether horizontal or vertical termination, the adapter is
counted as part of the maximum vertical limitations.
All venting rules for the vent run must still be followed.
HORIZONTAL EXAMPLE
V1 = 1 ft.
H
= 11 ft.
1
max.
DVP
1. Top Vent - Horizontal Termination
Two 45° Elbows
Installation requirements to replace the fi rst 90° elbow
with two 45° elbows:
4 ft min.
(1.22 m)
25 ft max.
(7.62 m)
12 ft (3.66 m) min.
60 ft (18.29 m) max.
H
= 11 ft.
1
max
SLP
VERTICAL EXAMPLE
12 ft (3.66 m) min.
60 ft (18.29 m) max.
V1 = 1 ft.
DVP-SLP24
DVP-SLP24
Adapter
Figure 7.3 Minimum Installation Requirements for Two 45°
Elbows-Top Vent-Horizontal Termination
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0824
DVP
SLP
Page 25
1. Top Vent - Horizontal Termination - (continued)
One Elbow
Î
H
1
Figure 7.4
Two Elbows
Î
Note: Subtract 3 ft (914 mm) from the total horizontal
measurement for each 90° elbow installed horizontally.
Subtract 1-1/2 ft (457 mm) from the total horizontal
measurement for each 45° elbow installed horizontally.
V
V1 MinV1 MaxH1 Max.
0*-24 in./635 mm
4 in./102 mm-4 ft/1.22 m
6 in./152 mm-6 ft/1.83 m
12 in./305 mm-11 ft/3.35 m
1
18 in./457 mm-18 ft/5.49 m
24 in./610 mm-25 ft/7.62 m
-25 ft/7.62 m (DVP)25 ft/7.62 m
-23 ft/7.62 m (SLP)25 ft/7.62 m
* You may install the elbow directly on top of the
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0825
1
Page 26
1. Top Vent - Horizontal Termination - (continued)
Î
Three Elbows
H
V1 min.V1+V2 max.H1+H2 max.
12 in./305 mm 24 ft/7.32 m (DVP)19 ft/5.79 m
12 in./305 mm 22 ft/6.71 m (SLP)19 ft/5.79 m
Installed
Vertically
2
V
2
V
1
H
1
Figure 7.6
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0826
Page 27
2. Top Vent - Vertical Termination
No Elbow
12 ft (3.66 m) min.
60 ft (18.29 m) max.
Install Top Vent Flue Visor - No Elbow Confi gura-
Î
tions
• Remove screws holding fl ue visor to fi rebox top. See Figure
7.7b.
• Remove the fl ue visor.
• Using the screws removed and the same holes, install the
top vent fl ue baffl e and fl ue visor.
- The fl ue visor will be turned to install below the level
of the fi rebox top for 12-30 ft vertical runs of vent. See
Figure 7.7c.
- The fl ue visor will be turned to install inside the fl ue for
vertical vent runs of 31-60 ft. See Figure 7.7d.
Figure 7.7a
Two Elbows
12 ft (3.66 m) min.
60 ft (18.29 m) max.
Figure 7.7b Remove Flue Visor
Figure 7.7c 12 to 30 ft Vertical Run
Maximum horizontal
run is 100% of
vertical, but cannot
exceed 26 ft (7.92 m)
Figure 7.8
Figure 7.7d 31 ft to 60 ft Vertical Run
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0827
Page 28
2. Top Vent - Vertical Termination - (continued)
Three Elbows
Note: Subtract 3 ft (914 mm) from the total horizontal
measurement for each 90° elbow installed horizontally.
Subtract 1-1/2 ft (457 mm) from the total horizontal
measurement for each 45° elbow installed horizontally.
Figure 7.9
Maximum horizontal run is
100% of vertical, but cannot
exceed 26 ft (7.92 m)
12 ft (3.66 m) min.
60 ft (18.29 m) max.
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0828
Page 29
3. Rear Vent - Horizontal Termination (DVP only)
No Elbow
18 in. (457 mm) max.
Figure 7.10
One 45° Elbow
18 in. (457 mm) max.
Figure 7.11
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0829
Note: Subtract 3 ft (914 mm) from the total horizontal
measurement for each 90° elbow installed horizontally.
Subtract 1-1/2 ft (457 mm) from the total horizontal
measurement for each 45° elbow installed horizontally.
H
1
ModelH1 Max
NDV
Series
Installed
Horizontally
V
H
3
H
2
1
ft0-213
m0-.610.310.91
ft426
m1.220.611.83
ft639
m1.830.912.74
ft8412
m2.441.223.66
ft8515
m2.441.524.57
ft8618
m2.441.835.49
Total Vert V
Min.
Total Horiz H
+ H2 + H3
1
Figure 7.13
H
1
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0830
Page 31
4. Rear Vent - Vertical Termination (DVP only)
One Elbow
12 ft (3.66 m) min.
60 ft (18.29 m) max.
0 min.
6 ft (1.83 m) max.
Figure 7.14
Two Elbows
12 ft (3.66 m) min.
60 ft (18.29 m) max.
Maximum horizontal
run is 100% of
vertical, but cannot
exceed 26 ft (7.92 m)
Note: Subtract 3 ft (914 mm) from the total horizontal
measurement for each 90° elbow installed horizontally.
Subtract 1-1/2 ft (457 mm) from the total horizontal
measurement for each 45° elbow installed horizontally.
0 min.
6 ft (1.83 m) max.
Figure 7.15
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0831
Maximum horizontal run is
100% of vertical, but cannot exceed 26 ft (7.92 m).
0 min.
6 ft (1.83 m) max.
Figure 7.16
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0832
Page 33
8
8
Vent Clearances and Framing
A. Pipe Clearances to Combustibles
WARNING! Risk of Fire! Maintain air space clearance to
vent. DO NOT pack insulation or other combustibles:
• Between ceiling fi restops
• Between wall shield fi restops
• Around vent system
Failure to keep insulation or other material away from
vent pipe may cause over heating and fi re.
Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm).
• DVP heat shield - designed to be used on a wall 4 in. to 7-1/4 in. (102 mm to
184 mm) thick.
• If wall thickness is less than 4 in. the existing heat shields must be field trimmed.
If wall thickness is greater than 7-1/4 in. a DVP-HSM-B will be required.
• SLP heat shield - designed to be used on a wall 4-3/8 in. to 7-5/8 in. (111 mm
to 194 mm thick).
• If wall thickness is less than 4-3/8 the existing heat shields must be field
trimmed. If wall thickness is greater than 7-5/8 in. a DVP-HSM-B will be
required.
(DVP-SLP Pipe Shown)
3 in. (76 mm)
top clearance
1 in. (25 mm)
clearance around
vertical sections
Heat
Shield
Heat
Shield
Wall
Shield
Firestop
WALL
3 in. (76 mm)
top clearance *
Heat
Shield
1 in. (25 mm)
clearance
bottom & sides
3 in. (76 mm)
top clearance *
Heat
Shield
B. Wall Penetration Framing
Combustible Wall Penetration
Frame a hole in a combustible wall for an interior wall shield
fi restop, (Figure 8.2) whenever a wall is penetrated.
The opening must be framed on all four sides using the same
size framing materials as those used in the wall construction.
The wall shield fi restop maintains minimum clearances and
prevents cold air infi ltration.
Non-Combustible Wall Penetration
If the hole being penetrated is surrounded by noncombustible materials such as concrete, a hole with diameter 1 in.
greater than the pipe is acceptable.
Whenever a non-combustible wall is penetrated, the wall
shield fi restop is only required on one side and no heat
shield is necessary.
If your local inspector requires the wall shield fi restop on
both sides, then both wall shield fi restops must have a heat
shield attached to them.
10 in.
12 in.
The center of the
framing hole is
1 in. (25mm) above
the center of the
horizontal vent pipe.
Framing should be
constructed of 2 X 4
lumber or heavier.
Vent framing hole.
DO NOT PACK WITH
INSULATION OR
OTHER MATERIAL.
A*
B*
Wall
Shield
Firestop
* When using SLP pipe, minimum clearances from the vent pipe to combus-
tible materials at inside wall firestops are: Top: 2-1/2 in. (64 mm)
Bottom: 1/2 in. (13 mm)
Sides: 1 in. (25 mm)
Figure 8.1 Pipe Clearances
1 in. (25 mm)
clearance
bottom & sides
WALL
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0833
* To center of pipe.
A
Model
NDV3630
NDV3933
NDV4236
NDV4842
Figure 8.2 Wall Penetration DVP only
Top VentBRear Vent
in.39-1/223-1/2
mm1003597
Page 34
C. Install the Ceiling Firestop
A ceiling fi restop MUST be used between
fl oors and attics.
• DVP Pipe only - Frame an opening 10 in.
Î
by 10 in. (254 mm by 254 mm) whenever
the vent penetrates a ceiling/fl oor (see
Figure 8.3).
Î
• SLP Pipe only - Frame an opening 9 in.
by 9 in. (229 mm x 229 mm) whenever the
vent penetrates a ceiling/fl oor (see Figure
8.3).
• Frame the area with the same sized lumber
as used in ceiling/fl oor joist.
• The ceiling fi restop may be installed above
or below the ceiling joists when installed
with a attic insulation shield. It must be
under joists between fl oors that are not
insulated. Refer to Figure 8.4.
• Secure with three fasteners on each side.
WARNING! Risk of Fire. DO NOT pack insulation around the vent. Insulation must be kept
back from the pipe to prevent overheating.
PIPE
DVP
SLP
ATTIC ABOVE
A
A
A
10 in. (254 mm)
9 in. (229 mm)
Figure 8.3 Installing Ceiling Firestop
Î
BEFORE OR AFTER INSTALLATION OF VENT SYSTEM
CEILING FIRESTOP
INSTALLED BELOW CEILING
Figure 8.4 Installing the Attic Shield
INSTALL ATTIC INSULATION SHIELDS
3 FASTENERS
PER SIDE
INSTALLED ABOVE CEILING
CEILING FIRESTOP
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0834
Page 35
D. Install Attic Insulation Shield
WARNING! Fire Risk. DO NOT allow loose materials or
insulation to touch vent. Hearth & Home Technologies Inc.
requires the use of an attic shield.
The National Fuel Gas Code ANSI Z223.1 requires an attic shield constructed of 26 gauge minimum metal that extends at least 2 in. (51 mm) above insulation.
Attic shields must meet specifi ed clearance and be se-
cured in place.
Flat Ceiling Installation
• Remove one shield from box.
Note: Cut previously installed batt insulation to make room
for the attic insulation shield.
• Wrap shield around pipe if pipe is already installed in
area to be insulated.
• Match the three holes in each side and fasten with three
screws to form a tube.
• Bend three tabs on the bottom of the shield outward to
allow attachment to the ceiling fi restop.
• Bend the remaining tabs inward 90° to maintain the air
space between the pipe and the shield. Set the shield
on the ceiling fi restop and attach to the fi restop.
• Bend all tabs inward 90° around the top of the shield.
These tabs must be used to prevent blown insulation
from getting between the shield and vent pipe, and to
maintain air space clearance.
Bend all tabs inward 90°
to maintain clearance and
prevent insulation from
falling inside.
Insert 3
screws
Figure 8.5 Attic Insulation Shield
Laser-etched
cut lines
Bend 3 tabs
outward to fasten
to ceiling firestop bend remaining
tabs inward 90° to
maintain clearance
Vaulted Ceiling Installation
• The attic insulation shield has been laser-etched with cut
lines and ceiling pitches to make fi eld trimming easier.
• Remove one shield from box.
NOTICE: Cut previously installed batt insulation to make
room for the attic insulation shield.
• Cut the attic insulation shield (if application is for vaulted
Î
ceiling) using a laser-etched cut line, to fi t your ceiling
pitch. Snip cut edge to create 1 in. bend tabs.
• Wrap shield around pipe if pipe is already installed in
area to be insulated.
• Match the three holes in each side and fasten with three
screws to form a tube.
• Bend three tabs on the bottom of the shield outward to
allow attachment to the ceiling fi restop.
• Bend the remaining tabs inward 90° to maintain the air
space between the pipe and the shield. Set the shield
on the ceiling fi restop and attach to the fi restop.
• Bend all tabs inward 90° around the top of the shield.
These tabs must be used to prevent blown insulation
from getting between the shield and vent pipe, and to
maintain air space clearance.
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0835
Page 36
9
9
Appliance Preparation
A. Top Vent
CAUTION! Risk of Cuts/Abrasions/Flying Debris. Wear
protective gloves and safety glasses during installation.
Sheet metal edges are sharp.
NOTICE: Once appliance is set up for top or rear venting,
it CANNOT be changed at a later time.
Figure 9.1
• Remove the cover plate by removing the four screws
holding it to the top of the appliance. Remove and discard
the cover plate.
Figure 9.4
• Fold the center parts of the retaining band up and use
to remove the vent cap.
Figure 9.2
• Remove the center insulation plug.
Figure 9.3
• Cut the metal retaining band and fold the sides out.
Figure 9.5
• Discard the vent cap, remove and discard the insulation
basket. Note: Once the vent cap has been removed it
cannot be reattached.
Figure 9.6
• Attach the fi rst vent section. It will snap into place.
Proceed to Section 10. C.
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0836
Page 37
B. Rear Vent
NOTICE: Once appliance is set up for top or rear venting,
it CANNOT be changed at a later time.
Figure 9.7
• Fold the tabs toward the center of the fi re plug (90º) and
remove the insulation gasket.
NOTICE: Once the vent cap has been removed it CANNOT
be reattached.
Figure 9.10
• Discard the vent cap, remove and discard the insulation
basket.
Figure 9.8
• Cut the metal retaining band and fold the sides out.
Figure 9.9
• Fold the center parts of the retaining band out and use
to remove the vent cap.
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0837
Figure 9.11
• Attach the fi rst vent section (it will snap into place). Slide
the insulation gasket onto the vent section, up against
the appliance and over the tabs.
Page 38
C. Secure and Level the Appliance
WARNING! Risk of Fire! Prevent contact with:
• Sagging or loose insulation
• Insulation backing or plastic
• Framing and other combustible materials
Block openings into the chase to prevent entry of blown-
in insulation. Make sure insulation and other materials
are secured.
DO NOT notch the framing around the appliance
standoffs.
Failure to maintain air space clearance may cause
overheating and fi re.
The diagram shows how to properly position, level, and secure the appliance (see Figure 9.12). Nailing tabs are provided to secure the appliance to the framing members.
• Bend out nailing tabs on each side.
• Place the appliance into position.
• Keep nailing tabs fl ush with the framing.
• Level the appliance from side to side and front to
back.
• Shim the appliance as necessary. It is acceptable to
use wood shims underneath the appliance.
• Secure the appliance to the framing by using nails or
screws through the nailing tabs.
• Secure the appliance to the fl oor by inserting two screws
through the pilot holes at the bottom of the appliance.
Nailing Flanges
(both sides)
Figure 9.12 Proper Positioning, Leveling And Securing of an Appliance
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0838
Page 39
10
10
A. Assemble Vent Sections (DVP only)
Î
Attach Vent to the Firebox Assembly
Note: The end of the pipe sections with the lanced tabs will face
toward the appliance.
Attach the fi rst pipe section to the starting collar:
• Lanced pipe end of the starting collar
• Inner pipe over inner collar
• Push the pipe section until all lanced tabs snap in place
• Lightly tug on pipe to confi rm it has locked.
Commercial, Multi-family (Multi-level exceeding two
stories), or High-Rise Applications
All outer pipe joints must be sealed with high temperature
silicone, including the slip section that connects directly to
the horizontal termination cap.
• Apply a bead of silicone sealant inside the female outer
pipe joint prior to joining sections. See Figure 10.1
• Only outer pipes must be sealed. All unit collar, pipe,
slip section, elbow and cap outer fl ues shall be sealed
in this manner, unless otherwise stated.
Installing Vent Pipe
Figure 10.1 High Temperature Silicone Sealant
A
A
WARNING! Risk of Fire/Explosion! DO NOT break
silicone seals on slip sections. Use care when removing
termination cap from slip pipe. If slip section seals are
broken during removal of the termination cap, vent will
leak and a fi re or explosion could occur.
Assemble Pipe Sections
• See Figure 10.2.
• Start the inner pipe on the lanced end of section A into
the fl ared end of section B.
• Start the outer pipe of section A over the outer pipe of
section B.
• Once both vents sections are started, push fi rmly until
all lanced tabs lock into place.
• Lightly tug on the pipe to confi rm the tabs have locked.
It is acceptable to use screws no longer than 1/2 in. (13 mm)
to hold outer pipe sections together. If predrilling holes, DO NOT penetrate inner pipe.
For 90° and 45° elbows that are changing the vent direction
from horizontal to vertical, one screw minimum should be
put in the outer fl ue at the horizontal elbow joint to prevent
the elbow from rotating. Use screws no longer than 1/2 in.
(13 mm). If predrilling screw holes, DO NOT penetrate inner pipe.
B
Figure 10.2
Note: Make sure that the seams are not aligned to prevent
unintentional disconnection.
CORRECT
Figure 10.3
B
Figure 10.4 Seams
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0839
INCORRECT
Page 40
B. Assemble Vent Sections (SLP Pipe Only)
ÎÎ
To attach the fi rst vent component to the starting collars of
the appliance
• Attach an SLP-DVP24 adapter to the starting collar of
the appliance.
• Lock the vent components into place by sliding the pipe
section onto the collar.
• Align the seam of the pipe and seam of collar to allow
engagement. Rotate the vent component to lock into
place. Use this procedure for all vent components. See
Figure 10.5.
• Slide the gasket over the fi rst vent section and place it fl ush to the appliance. This will prevent cold air infi ltration.
C. Assemble MI Sections (DVP only)
WARNING! Risk of Fire or Asphyxiation! Overlap pipe
sections at least 1 1/2 in. (38 mm). Secure MI sections
with three screws which must not exceed 1/2 in. (13 mm)
in length. Pipe could separate if not properly joined.
MI (Minimum Installation) sections are non-unitized so
that they can be cut to a specifi c length.
• Cut sections to length from the non-expanded end (see
Figure 10.6). Maintain 1-1/2 in. (38 mm) overlap.
• Connect the expanded end of the MI inner fl ue with the
inner fl ue of the adjacent pipe section and secure with
three screws.
High temperature caulk may be used to hold the part in
place.
• Continue adding vent components, locking each
succeeding component into place.
• Ensure that each succeeding vent component is securely
fi tted and locked into the preceding component.
Commercial, Multi-family (Multi-level exceeding
two stories), or High-Rise Applications
For Installation into a commercial, multi-family (multi-level
exceeding two stories) or high-rise applications: All outer
pipe joints must be sealed with high temperature silicone,
including the slip section that connects directly to the hori-
CAUTION! Risk of Fire! The expanded portion of the MI
inner fl ue must overlap completely with the unexpanded
end of the adjacent pipe section.
• Connect the cut end of the MI outer flue with the
expanded end of the outer fl ue of the adjacent pipe
section and secure with three screws.
• It is acceptable to use screws no longer than 1/2 in. (13
mm) to hold outer pipe sections together. If predrilling
holes, DO NOT penetrate inner pipe.
• Continue adding pipe sections as necessary following
instructions in “Assemble Pipe Sections.”
zontal termination cap.
• Apply a bead of silicone sealant inside the female outer
pipe joint prior to joining sections. See Figure 10.1
Cut from this end
• Only outer pipes need to be sealed. All unit collar, pipe,
slip section, elbow and cap outer fl ues shall be sealed
in this manner, unless otherwise stated.
(outer)
WARNING! Risk of Fire or Explosion! DO NOT break
silicone seals on slip sections. Use care when removing
termination cap from slip pipe. If slip section seals are broken during removal of the termination cap, vent may leak.
2 - Rotate
1 - Align Seams
Figure 10.5 Adding Venting Components
Cut from this end
(inner)
Figure 10.6 MI Sections
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0840
Page 41
D. Assemble Slip Sections
Î
WARNING! Risk of Fire or Asphyxiation! Overlap pipe
sections at least 1 1/2 in. (38 mm). Secure slip sections
with two screws which must not exceed 1/2 in. (13 mm)
in length. Use the pilot holes. Pipe could separate if not
properly joined.
• Slide the inner fl ue of the slip section into the inner fl ue of
the pipe section and the outer fl ue of the slip section over
the outer fl ue of the pipe section. See Figure 11.7.
• Slide together to the desired length.
Figure 10.7 Slip Section Pilot Holes
• Maintain a 1-1/2 in. (38 mm) overlap between the slip
section and the pipe section.
• Secure the pipe and slip section with two screws no
longer than 1/2 in. (13 mm), using the pilot holes in the
slip section. See Figure 10.8.
Figure 10.8 Screws into Slip Section
• Continue adding pipe as necessary following instructions
in “Assembling Pipe Sections.”
NOTICE: If slip section is too long, the inner and outer fl ues
of the slip section can be cut to the desired length.
NOTICE: When installing a vent system with an HRC
termination cap, all pipe system joints shall be sealed using
a high temperature silicone sealant.
• Apply a bead of silicone sealant inside the female outer
pipe joint prior to joining sections.
• Only outer pipes are sealed, sealing the inner fl ue is not
required.
• All unit collar, pipe, slip section, elbow and cap outer fl ues
shall be sealed.
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0841
Page 42
Î
E. Secure the Vent Sections
• Vertical runs of DVP pipe must be supported every 8 ft.
(2.44 m) after the 25 ft. (7.62 m) maximum unsupported
rise.
• Vertical runs of SLP pipe must be supported every 8 ft.
(2.44 m).
• Horizontal sections of vent must be supported every 5
ft. (1.52 m) with a vent support or plumber’s strap.
• Wall shield fi restops may be used to provide horizontal
support.
• Vent support or plumber’s strap (spaced 120° apart) may
be used for support. See Figures 10.9 and 10.10.
• SLP ceiling fi restops have tabs that may be used to
provide vertical support.
WARNING! Risk of Fire, Explosion or Asphyxi-
ation! Improper support may allow vent to sag and
separate. Use vent run supports and connect vent
sections per installation instructions. DO NOT allow
vent to sag below connection point to appliance.
F. Disassemble Vent Sections
Î
• Rotate either section (see Figure 10.11) so the seams
on both pipe sections are aligned as shown in Figure
10.12.
• Pull carefully to separate the pieces of pipe.
Figure 10.11 Rotate Seams for Disassembly
Figure 10.9 Securing Vertical Pipe Sections
Figure 10.10 Securing Horizontal Pipe Sections
Figure 10.12 Align and Disassemble Vent Sections
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0842
Page 43
G. Install Decorative Ceiling Components
Î
(SLP only)
A black painted decorative ceiling thimble can be installed
on a fl at ceiling through which the vent passes. The ceil-
ing thimble is used to cover the fi restop, which is installed
according to section 8.C.
• Seal the gap between the vent pipe and firestop
using high temperature silicone to prevent cold air
infi ltration.
• Install the decorative ceiling thimble by sliding it up to
the ceiling and attaching it using the provided screws.
A decorative black cathedral ceiling support box can be
used where vertical vent runs pass through a cathedral
ceiling.
• Use a plumb-bob to mark the center line of the venting
system on the ceiling and drill a small hole through the
ceiling and roof at this point. Locate the hole and mark
the outline of the cathedral ceiling support box on the
outside roof.
• Remove shingles or other roof covering as necessary
to cut the rectangular hole for the support box. Cut the
hole 1/8 in. (3 mm) larger than the support box outline.
• Lower the support box through the hole in the roof until its
bottom is at least 2 in. (51 mm) below the ceiling (Figure
10.13).
• Level the support box both vertically and horizontally
and temporarily tack it in place through the inside walls
into the roof sheathing.
• Use tin snips to cut the support box from the top corners
down to the roof line and fold the resulting fl aps to the
roof. See Figure 10.14.
• Nail the fl aps to the roof AFTER running a bead of non
hardening sealant between the fl aps and the roof.
Level
Cathedral ceiling
support box
2 in. (51 mm)
minimum below
finished ceiling
Cut hole 1/8 in. (3 mm) greater
in size than pattern of support
box as it is projected onto
roofline.
Figure 10.13
WARNING! Risk of Fire! Clean out ALL materials from
inside the support box and complete the vertical vent run
and termination.
Figure 10.14
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0843
Page 44
H. Install Metal Roof Flashing
Î
Note: Skip this section if using the RF4-8.
• See minimum vent heights for various pitched roofs
(Figure 10.15) to determine the length of pipe to extend
through the roof.
• Slide the roof fl ashing over the pipe sections extending
through the roof as shown in Figure 10.16.
Horizontal
overhang
24 in. min.
(610 mm)
Termination
Cap
20 in.
(508 mm)
Lowest
Discharge
Opening
Vertical
wall
NOTICE: Failure to properly caulk the roof fl ashing could
cause water entry.
• Caulk the gap between the roof fl ashing and the outside
diameter of the pipe.
• Caulk the perimeter of the fl ashing where it contacts
the roof surface. See Figure 10.16.
Pipe
Caulk
Storm Collar
Roof
Flashing
H (min.) - Minimum height
from roof to lowest
discharge opening.
Roof Pitch H (Min.) Ft. Roof Pitch H (Min.) Ft.
Flat to 6/12 1.0* Over 11/12 to 12/12 4.0
Over 6/12 to 7/12 1.25* Over 12/12 to 14/12 5.0
Over 7/12 to 8/12 1.5* Over 14/12 to 16/12 6.0
Over 8/12 to 9/12 2.0* Over 16/12 to 18/12 7.0
Over 9/12 to 10/12 2.5 Over 18/12 to 20/12 7.5
Over 10/12 to 11/12 3.25 Over 20/12 to 21/12 8.0
* 3 ft. minimum in snow regions
Figure 10.15 Minimum Height From Roof To Lowest Discharge
Opening
X
12
Roof Pitch
is X / 12
Flashing
Figure 10.16
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0844
Page 45
I. Install RF4-8
Î
The RF4-8 may be used in place of the roof fl ashing and
storm collar (Sections 10.F. and 10.I.)
Pipe must be supported within 12 in. (305 mm) of the
roofl ine using plumbers strapping or an SLP-FS when us-
ing the RF4-8 Flashing. Refer to Sect. 8.C. Securing Vent
Sections.
Secure with 4
screws no longer
than 1/2 in./13 mm
SLP-FS
Figure 10.17 Secure Pipe with SLP-FS
• Trim the rubber boot (using scissors or a utility knife),
cutting along the marked measurement lines. See Figure
10.18. Use the 150 mm line for SLP, 210 mm for DVP.
• Lubricate pipe or fl ue with water and slide the fl ashing
down. It may be necessary to trim the top shingles around
the base of the rubber boot to ensure a good fi t.
• Draw around fl ashing, remove.
• Apply silicone sealant to roof inside the lines (Figure 10.19)
• Lubricate pipe or fl ue with water and slide fl ashing down.
Seat fi rmly in sealant. Nail roof fl ashing to the roof.
• Apply silicone sealant on the top outside of the base plate
on the sides and on top edge. See Figure 10.20. Install
shingles, Apply sealant at the top edge of the rubber
boot. See Figure 10.21.
• We recommend that you top coat with conventional
acrylic house paint to improve the appearance of your
galvanized base fl ashing.
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0845
Shingles over
Flashing
Page 46
J. Install Vertical Termination Cap
• Attach the vertical termination cap by sliding the inner
collar of the cap into the inner fl ue of the pipe section
while placing the outer collar of the cap over the outer
fl ue of the pipe section.
• Secure the cap by driving three self-tapping screws
(supplied) through the pilot holes in the outer collar of the
cap into the outer fl ue of the pipe (see Figure 10.22).
K. Assemble and Install Storm Collar
CAUTION! Risk of Cuts/Abrasions/Flying Debris. Wear
protective gloves and safety glasses during installation.
Sheet metal edges are sharp.
• Connect both halves of the storm collar with two screws
(see Figure 10.23).
• Wrap the storm collar around the exposed pipe section
closest to the roof and align brackets. Insert a bolt
(provided) through the brackets and tighten the nut to
complete the storm collar assembly. Make sure the collar
is tight against the pipe section.
• Slide the assembled storm collar down the pipe section
until it rests on the roof fl ashing (see Figure 10.24).
• Caulk around the top of the storm collar (see Figure
10.22).
Figure 10.22
Figure 10.23 Assembling the Storm Collar
Figure 10.24 Assembling the Storm Collar Around the Pipe
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0846
Page 47
Î
L. Install Heat Shields and Horizontal Termination Cap
Note: For installations using black pipe, slide the decorative wall
thimble over the last vent pipe before connecting the termination
cap to the pipe.
the wall thimble up to the interior wall surface and attach
with screws provided. See fi gure 10.25
Figure 10.25 Wall Thimble
Heat Shield Requirements for Horizontal Termi-
nation
For all horizontally vented appliances, a heat shield
MUST be placed one in. above the top of the vent between the wall shield fi restop and the base of the termina-
tion cap.
There are two sections of the heat shield. One section
is factory-attached to the wall shield fi restop. The other
section is factory-attached to the cap. See Figure 10.26.
If the wall thickness does not allow the required 1-1/2 in.
(38 mm) heat shield overlap when installed, an extended
heat shield must be used.
When this connection has been made, slide
• Use an extended heat shield if the fi nished wall thickness
is greater than 7-1/4 in. (184 mm).
• The extended heat shield may need to be cut to length
maintaining suffi cient length for a 1-1/2 in. (38 mm)
overlap between heat shields.
• Attach the extended heat shield to either of the existing
heat shields using the screws supplied with the extended
heat shield.
• Rest the small leg on the extended heat shield on top
of the pipe section to properly space it from the pipe
section.
Important Notice: Heat shields may not be fi eld constructed.
WARNING! Risk of Fire! To prevent overheating and
fi re, heat shields must extend through the entire wall
thickness. Heat shields must overlap 1-1/2 in. (38 mm)
minimum.
• DO NOT remove the heat shields attached to the wall
shield fi restop and the horizontal termination cap (shown
in Figure 10.26).
• If the wall thickness is less than 4 in./102 mm (DVP)
or 4-3/8 in./ 111 mm (SLP), the heat shields on the cap
and wall shield fi restop must to be trimmed. A minimum
1-1/2 in. (38 mm) overlap MUST be maintained.
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0847
Page 48
Install Horizontal Termination Cap
WARNING! Risk of Fire! The telescoping fl ue section of
the termination cap MUST be used when connecting vent.
• 1-1/2 (38 mm) minimum overlap of fl ue telescoping
section is required.
Failure to maintain overlap may cause overheating and
fi re.
• Vent termination must not be recessed in the wall. Siding
may be brought to the edge of the cap base.
• Flash and seal as appropriate for siding material at
outside edges of cap.
Note: When using termination caps with factory-supplied heat shield
attached, no additional wall shield fi restop is required on the exterior side
of a combustible wall.
• When installing a horizontal termination cap, follow
the cap location guidelines as prescribed by current
ANSI Z223.1 and CAN/CGA-B149 installation codes
and refer to Section 6 of this manual.
CAUTION! Risk of Burns! Local codes may require
installation of a cap shield to prevent anything or anyone
from touching the hot cap.
NOTICE: For certain exposures which require superior
resistance to wind-driven rain penetration, a fl ashing kit and
HRC caps are available. When penetrating a brick wall, a
brick extension kit is available for framing the brick.
Î
NDV Series
Heat Shield or
Wall Shield
Firestop
Inner Vent
Outer Vent
Vent depth from back of appliance to
outside surface of exterior wall
(see chart below)
Figure 10.26 Venting through the wall
Heat Shield
Extended
Slip Section
can be extended
INTERIOR
Heat Shield
1-1/2 in. (38 mm) min.
overlap
SHEATHING
EXTERIOR
Cap Specifi cation Chart (depth without using additional pipe sections)
DVP-TRAPK1
Top Vent Depth
4 1/2 to 6 3/8 in.3 to 4 7/8 in.6 7/8 to 10 7/8 in.5 3/8 to 9 3/8 in.2 to 3 7/8 in.
DVP-HPC1
Top Vent Depth
4 1/2 to 6 5/8 in.3 to 5 1/8 in.6 5/8 to 10 3/4 in.5 1/8 to 9 1/4 in.4 3/8 to 8 3/8 in.
DVP-TRAP1
Rear Vent Depth
DVP-HPC1
Rear Vent Depth
DVP-TRAPK2
Top Vent Depth
DVP-HPC2
Top Vent Depth
DVP-TRAP2
Rear Vent Depth
DVP-HPC2
Rear Vent Depth
SLP-TRAP1
Top Vent Depth
SLP-TRAP2
Top Vent Depth
DVP-TRAP1 can adjust 1 1/2 in. (3 1/8 to 4 5/8)
DVP-TRAP2 can adjust 4 in. (5 3/8 to 9 3/8)
SLP-TRAP1 can adjust 1 5/8 in. (3 1/8 to 4 3/4)
SLP-TRAP2 can adjust 4 in. (5 1/4 to 9 1/4))
DVP-HPC1 can adjust 2 1/8 in. (4 1/4 to 6 3/8)
DVP-HPC2 can adjust 4 1/8 in. (6 3/8 to 10 1/2)
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0848
Page 49
11
11
Gas Information
A. Fuel Conversion
• Make sure the appliance is compatible with available gas
types.
• Conversions must be made by a qualifi ed technician
using Hearth & Home Technologies specified and
approved parts.
• Gas line sizing requirements will be determined in ANSI
Z221.3 National Fuel Gas Code in the USA and CAN/
CGA B149 in Canada.
• Pressure requirements are:
Gas PressureNatural GasPropane
Minimum inlet pressure5.0 in. w.c.11.0 in. w.c.
Maximum inlet pressure14.0 in. w.c.14.0 in. w.c.
Manifold pressure3.5 in. w.c.10.0 in. w.c.
WARNING! Risk of Fire/Explosion! High pressure will
damage valve. Low pressure may cause explosion.
• Verify inlet pressures. Verify minimum pressures when
other household gas appliances are operating.
• Install regulator upstream of valve if line pressure is
greater than 1/2 psig.
WARNING
Fire Risk.
Explosion Hazard.
High pressure will damage valve.
• Disconnect gas supply piping BEFORE
pressure testing gas line at test pressures
above 1/2 psig.
• Close the manual shutoff valve BEFORE
pressure testing gas line at test pressures
equal to or less than 1/2 psig.
Note: Have the gas supply line installed in accordance with
local codes, if any. If not, follow ANSI 223.1. Installation
should be done by a qualifi ed installer approved and/or
licensed as required by the locality. (In the Commonwealth of
Massachusetts installation must be performed by a licensed
plumber or gas fi tter).
Note: A listed (and Commonwealth of Massachusetts approved) 1/2 inch (13 mm) T-handle manual shut-off valve
and fl exible gas connector are connected to the 1/2 inch (13
mm) control valve inlet.
• If substituting for these components, please consult
local codes for compliance.
C. Gas Connection
• Refer to Reference Section 16 for location of gas line
access in appliance.
• Gas line may be run through knockout(s) provided.
• The gap between supply piping and gas access hole may
be caulked with high temperature caulk or stuffed with
non-combustible, unfaced insulation to prevent cold air
infi ltration.
• Ensure that gas line does not come in contact with outer
wrap of the appliance. Follow local codes.
• Pipe incoming gas line into valve compartment.
• Connect incoming gas line to the 1/2 in. (13 mm)
connection on manual shutoff valve.
WARNING! Risk of Fire/Explosion! Support control
when attaching pipe to prevent bending gas line.
• A small amount of air will be in the gas supply lines.
WARNING! Risk of Fire/Explosion! Gas build-up during
line purge could ignite.
• Purge should be performed by a qualifi ed technician.
• Ensure adequate ventilation.
• Ensure there are no ignition sources such as sparks or
open fl ames.
Light the appliance. It will take a short time for air to purge
from lines. When purging is complete the appliance will
light and operate normally.
WARNING! Risk of Fire, Explosion or Asphyxiation!
Check all fi ttings and connections with a non-corrosive
commercially available leak-check solution. DO NOT use
open fl ame. Fittings and connections could have loosened
during shipping and handling.
WARNING! Risk of Fire! DO NOT change valve settings.
This valve has been preset at the factory.
D. High Altitude Installations
NOTICE: If the heating value of the gas has been reduced,
these rules do not apply. Check with your local gas utility or
authorities having jurisdiction.
When installing above 2000 feet elevation:
• In the USA: Reduce burner orifi ce 4% for each 1000 feet
above 2000 feet.
• In the CANADA: Reduce burner orifi ce 10% for elevations
between 2000 feet and 4500 feet. Above 4500 feet,
consult local gas utility.
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0849
Page 50
12
12
Electrical Information
A. Wiring Requirements
NOTICE: This appliance must be electrically wired and
grounded in accordance with local codes or, in the absence
of local codes, with National Electric Code ANSI/NFPA
70-latest edition or the Canadian Electric Code
CSA C22.1.
• Wire the appliance junction box to 110-120 VAC. This is
required for use of optional accessories (standing pilot
ignition) or proper operation of the appliance (Intellifi re
ignition).
• Low voltage and 110 VAC voltage cannot be shared
within the same wall box.
WARNING! Risk of Shock or Explosion! DO NOT wire
110V to the valve or to the appliance wall switch. Incorrect
wiring will damage controls.
• Determine if the appliance uses an Intellifi re ignition
system or standing pilot ignition system.
• Open the control access panel.
• A red or black ignitor button (as shown in Figure 12.1)
indicates this appliance is standing pilot ignition.
B. Standing Pilot Ignition System Wiring
• The standing pilot ignition system wiring does not require
a 110 VAC supply to operate.
• A 110 VAC junction box MUST be installed for use with
a fan or remote control. See Figure 12.3 for junction box
wiring. Keep wire lengths short as possible.
NOTICE: DO NOT wire 110 VAC to the millivolt valve! This
will damage the valve.
• If using a thermostat use one compatible with a millivolt
gas valve system:
- Install the thermostat in the location as indicated in the
thermostat instructions to ensure proper operation of
appliance.
- Use low resistance thermostat wire for wiring from
ignition system to the wall switch and thermostat.
- Keep wire lengths short as possible.
C. Intellifi re Ignition System Wiring
• Wire the appliance junction box to 110 VAC for proper
operation of the appliance.
Red or Black
Button
Figure 12.1 Ignitor Button
WARNING! Risk of Shock or Explosion! DO NOT wire
IPI controlled appliance junction box to a switched circuit.
Incorrect wiring will override IPI safety lockout.
• Refer to Figure 12.2, Intellifi re Pilot Ignition (IPI) Wiring
Diagram.
• This appliance is equipped with an Intellifi re control valve
which operates on a 3 volt system.
• Plug the 3-volt AC transformer into the appliance junction
box to supply power to the unit OR install two D cell
batteries (not included) into the battery pack before use.
NOTICE: Batteries should not be placed in the battery pack
while using the transformer. Remove batteries before using
the transformer, and unplug the transformer before installing
the batteries. Battery polarity must be correct or module
damage will occur.
D. Optional Accessories Requirements
• This appliance may be used with a wall switch, wall
mounted thermostat and/or a remote control.
Wiring for optional Hearth & Home Technologies approved
accessories should be done now to avoid reconstruction.
Follow instructions that come with those accessories.
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0850
Page 51
Flame
Sensor
Ignitor
*
GRN wire only used
with optional wall switch
Battery
Pack
WSK-MLT-HTL
-
Wall Switch
GRN*
Figure 12.2 Intellifi re Pilot Ignition (IPI) Wiring Diagram
RED
WHT
+
+
-
3V
Adapter
BLK
RED
To
Junction
Box
BRN
Valve
Control
Box
BLK
ORG
GRN
WHT
ORG
Pilot Assembly
E. Electrical Service and Repair
WARNING! Risk of Shock! Label all wires prior to
disconnection when servicing controls. Wiring errors can
cause improper and dangerous operation. Verify proper
operation after servicing.
Ignitor
Thermocouple
Copper
Tubing
ORG
Push
Button
Ignitor
Gas Inlet
Pilot
TO
PILOT
Pilot
Adjustment
Cap
Thermopile
TH
TP
TH/TP
Inlet Tap
WARNING! Risk of Shock! Replace damaged wire with
type 105° C rated wire. Wire must have high temperature
insulation.
Wall Switch (or
thermostat if
heater-listed)
RED
SILVER
RED
WHT
BRN
To Burner
Manifold Pressure
Adjustment Fitting
Manifold
(outlet)
Pressure Tap
WHT
GRN*
GRN wire only
*
for use with
optional wall switch
WSK-MLT-HTL
Figure 12.3 Standing Pilot Ignition Wiring Diagram
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0851
Page 52
F. Junction Box Installation
If the box is being wired from the OUTSIDE of the appliance:
• Remove the cover plate located on the outer shell - right
side (see Figure 12.4).
• Install the supplied Romex™ connector in the cover
plate.
If the box is being wired from the INSIDE of the appliance:
• Remove the screw attaching the junction box/receptacle
to the outer shell, rotate the junction box inward to
disengage it from the outer shell (see Figure 12.4).
• Pull the electrical wires from outside the appliance through
this opening into the valve compartment. See Figure
12.4.
WHT
BLK
WHT
BLK
GRN wire
inside box
Figure 12.4 Junction Box Detail
Romex
Connector
14/2WG
Cover Plate
outside firebox
Copper
ground attached
to GRN screw with
GRN wire
NOTICE: DO NOT wire
110 VAC to wall switch.
G. Wall Switch Installation for Fan (Optional)
If the box is being wired to a wall mounted switch for use
with a fan (See Figure 12.5):
• The power supply for the appliance must be brought into
a switch box.
• The power can then be supplied from the switch box
to the appliance using a minimum of 14-3 with ground
wire.
• At the switch box connect the black (hot) wire and red
(switch leg) wire to the wall switch as shown.
• At the appliance connect the black (hot), white (neutral)
and green (ground) wires to the junction box as shown.
• Add a 1/4 in. insulated female connector to the red (switch
leg) wire, route it through the knockout in the face of the
junction box, and connect to the top fan switch connector
(1/4 in. male) as shown.
Minimum 14-3 AWG
with Ground
Junction Box
Red
Figure 12.5 Junction Box Wired to Wall Switch or BC10
Red
Black
White
Red
Black
Green
White
Green
Black
Switch Box
Knockout
White
Green
Switch
Power
Supply
Wires
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0852
Page 53
13
13
Finishing
A. Mantel and Wall Projections
WARNING! Risk of Fire! Comply with all minimum clearances to combustibles as specifi ed. Framing closer than the mini-
mums listed must be constructed entirely of noncombustible materials (i.e., steel studs, concrete board, etc.) Failure to comply
could cause fi re.
Mantels
30 in. minimum
to ceiling
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
6-1/4
5-1/2
5
7-3/4
7
9-1/4
8-1/2
10-3/4
10
12-1/4
11-1/2
14-1/2
13-3/4
13
16
15-1/4
Measured from top of hood (in inches)
Figure 13.1 Clearances To Mantels Or Other Combustibles Above Appliance
Mantel Legs or Wall Projections
Top of
Appliance
Drywall
A
B
Mantel Leg or
Perpendicular Wall
1 in. (25 mm) min.
A
to perpendicular wall
3-1/2 in. (89 mm) min.
B
from fireplace opening
to perpendicular wall
Figure 13.2 Mantel Leg or Wall Projections (Acceptable on both
sides of opening)
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0853
Page 54
B. Facing Material
• Cover the metal front faces with non-combustible materials only.
• Facing and/or fi nishing materials must not interfere with
air fl ow through louvers, operation of louvers or doors,
or access for service.
• Facing and/or fi nishing materials must never overhang
into the glass opening.
• Observe all clearances when applying combustible
materials.
• Seal joints between the fi nished wall and appliance top
and sides using a 300 °F minimum sealant. Refer to
Figure 13.3.
WARNING! Risk of Fire! DO NOT apply combustible
materials beyond the minimum clearances. Comply with
all minimum clearances to combustibles as specifi ed in
this manual. Overlapping materials could ignite and will
interfere with proper operation of doors and louvers.
Finish wall material may be
combustible - Top and Sides
0 in.
High Temperature Sealant (300° F/149° C min.)
Top and Side Seal Joint
Figure 13.3 Noncombustible Facing Diagram
0 in.
0 in.
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0854
Page 55
14
14
Appliance Setup
A. Remove the Packaging
Remove the shrink fi lm, corrugated top cap, bottom cap
and column protectors from the appliance. The appliance
should look as shown in Figure 14.1.
Figure 14.1 Appliance Unwrapped
Figure 14.2 Open Access Flap
B. Open Front Screen Assembly
• Open the fl ap in the upper left hand corner of the screen
protector (Figure 14.2)
• Pick up on the screen to release the screen from the
shoulder screws in the fi replace columns. See Figure
14.3.
• Rotate the screen open as shown in Figure 14.4.
C. Remove the Shipping Materials
Remove the shipping materials from inside or underneath
the fi rebox.
D. Remove Fixed Glass Assembly
See Section 14.K.
E. Clean the Appliance
Clean/vacuum any sawdust that may have accumulated
inside the fi rebox or underneath in the control cavity.
F. Accessories
Install approved accessories per instructions included with
the accessories. Refer to Section 16.
Figure 14.3 Lift up on Screen
WARNING! Rick of Fire and Electric Shock! Use ONLY
Hearth & Home Technologies-approved optional accessories with this appliance. Using non-listed accessories
could result in a safety hazad and will void the warranty.
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0855
Figure 14.4 Rotate Screen Open
Page 56
G. Place the Rockwool
WARNING! Risk of Explosion! Follow rockwool placement instructions. DO NOT place rockwool directly over
burner ports. Replace rockwool material annually. Improperly placed rockwool interferes with proper burner operation.
• Rockwool is shipped with this gas appliance.
• Place a small amount of 1/2 in. diameter pieces (dimesize) rockwool on the burner pan so that the rockwool
touches, but does not cover, the holes in the burner
pan (refer to Figure 14.5). This will provide the “glowing
embers” look.
• It is not necessary to use the entire bag. Save the
remaining rockwool for future use.
H. Place the Lava Rock
See Figure 14.5.
J. Remove Screen Protector
• Tear the corrugated as shown in Figure 14.6. The
corrugated must be separated along the entire top edge
of the protector.
• Slide the screen protector off the screen as shown in
Figure 14.7.
Figure 14.6 Tear the Corrugated
Rockwool
Lava Rock &
Vermiculite
Figure 14.5 Placement of Rockwool, Lava Rock and Vermiculite
I. Place the Vermiculite
Sprinkle on top of lava rock.
Slide off
Figure 14.7 Remove Screen Protector
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0856
Page 57
K. Unpackage the Hood & Floor Cover
Remove the hood, fl oor cover and protective cardboard
from the back side of the screen as shown in Figure 14.8.
Figure 14.8 Removing Parts Package
L. Install Hood
• Locate the four screws just inside the upper section of
the appliance.
• Slide the hood into position uncer the screw heads.
• Tighten the four screws. See Figure 14.9.
Figure 14.9 Intalling Hood
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0857
Page 58
M. Install Floor Cover
Install the fl oor cover as shown in Figure 14.10.
Figure 14.10 Installing Floor Cover
Note: The fl oor cover in the bottom front of the fi replace may
be covering the UL labels.
It is loose and can be removed/
replaced.
N. Fixed Glass Assembly
Removing Fixed Glass Assembly
WARNING! Risk of Asphyxiation! Handle fi xed glass
assembly with care. Inspect the gasket to ensure it is
undamaged and inspect the glass for cracks, chips or
scratches.
Replacing Fixed Glass Assembly
• Set the glass panel on the lower two or four glass
assembly latches, ensuring the glass panel is centered
in the opening.
• Replace screen.
O. Close the Screen Assembly
Rotate the screen closed. See Figures 14.12 and 14.13.
Figure 14.12 Closing Screen
DO NOT:
• Strike, slam or scratch glass
• Operate fi replace with glass removed, cracked,
broken or scratched.
Replace fi xed glass assembly as a complete assembly.
• Remove screen.
• Pull the four (30/33/36 in. appliances) or seven (42 in.
appliance) glass assembly latches out of the groove on
the glass frame. Refer to Figure 14.11.
• Remove the glass assembly from the appliance.
Latches
(both bottom
and top)
Glass
Assembly
Figure 14.13 Closing Screen
Figure 14.11 Glass Assembly
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0858
Page 59
P. Air Shutter Setting
Air shutter setting should be adjusted by a qualifi ed in-
staller at the time of installation.
• The air shutter is set at the factory for minimum vertical
vent run.
• Adjust air shutter for longer vertical runs. See
Figure 14.14.
• Turn the thumbscrew to open and close.
OpenClose
Figure 14.14 Adjusting Air Shutter
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0859
Page 60
15
15
Troubleshooting
With proper installation, operation, and maintenance your gas appliance will provide years of trouble-free service. If you
do experience a problem, this troubleshooting guide will assist a qualifi ed technician in the diagnosis of a problem and the
corrective action to be taken. This troubleshooting guide can only be used by a qualifi ed technician. Contact your dealer to
arrange a service call by a qualifi ed technician.
A. Standing Pilot Ignition System
SymptomPossible CausesCorrective Action
1. After repeated triggering
of the red or black piezo
ignitor button, the spark
ignitor will not light the
pilot. Check for spark.
A. No gas or low gas pressure.Check the remote shut-off valves from the appliance. Usually, there
is a valve near the gas main. There can be more than one valve
between the appliance and the main.
B. No lp in tank.Check the LP (propane) tank. You may be out of fuel.
C. Ignitor.Check the spark at the electrode and pilot. If no spark and electrode
wire is properly connected, replace the ignitor. Verify that there is
no short in electrode wire.
D. Pilot or misaligned electrode
(spark at electrode).
Using match, light the pilot. If the pilot lights, turn off the pilot and
trigger the piezo ignitor button again. If the pilot lights, an improper
gas/air mixture caused the bad lighting and a longer purge period
is recommended. If the pilot will not light, ensure the gap at the
electrode and pilot is one-eighth inch to have a strong spark. If the
gap is OK, replace the pilot.
2. The pilot will not stay lit
after carefully following the
lighting instructions.
3. The pilot is burning, there
is no burner fl ame, the
valve knob is in the ON
position, and the ON/
OFF switch is in the ON
position.
A. Thermocouple.Check that the pilot fl ame impinges on the thermocouple. Adjust the
pilot for proper fl ame impingement.
Ensure that the thermocouple connection at the gas valve is fully
inserted and tight (hand tighten plus 1/4 turn).
Verify proper voltage output from the thermocouple to the valve.
Place one millivolt meter lead wire on the thermocouple copper
lead. Place the second lead wire on the solder button on the back
of the valve (blue wire). Start the pilot and hold the valve knob in.
The millivolt reading should read 8-16 millivolts. If millivolt reading
is less than 8 millivolts, replace thermocouple.
B. Improper gas inlet pressure.Natural gas should be 5-14 in. w.c. LP should be 10-14 in. w.c.
Verify pressure with manometer.
C. Control valve.If the thermocouple is producing 8-16 millivolts, replace control
valve.
A. On/off switch or wires
defective.
B. Thermopile may not be
generating suffi cient
millivoltage.
Check the ON/OFF switch and wires for proper connections. Place
the jumper wires across the terminals at the switch. If the burner
comes on, replace the defective switch. If the switch is OK, place
the jumper wires across the switch wires at the gas valve. If the
burner comes on, the wires are faulty or connections are bad.
Check that the pilot fl ame impinges thermopile properly.
Be sure the wire connections from the thermopile at the gas valve
terminals are tight and that the thermopile is fully inserted into the
pilot bracket.
Check the thermopile with a millivolt meter. Take the reading at
TH-TP&TP terminals of the gas valve. The meter should read 350
millivolts minimum, while holding the valve knob depressed in the
pilot position, with the pilot lit, and the ON/OFF switch in the OFF
position. Replace the thermopile if the reading is below the specifi ed
minimum.
With the pilot in the ON position, disconnect the thermopile leads
from the valve. Take a reading at the thermopile leads. The reading
should be 350 millivolts minimum. Replace the thermopile if the
reading is below the minimum.
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0860
Page 61
Troubleshooting (continued)
SymptomPossible CauseCorrective Action
3. (Continued)C. Failed valve.Turn the valve knob to the ON position. Place the ON/OFF switch
in the ON position. Check the millivolt meter a the thermopile
terminals. The millivolt meter should read greater than 125mV. If the
reading is acceptable, and if the burner does not come on, replace
the gas valve.
D. Plugged burner orifi ce.Check the burner orifi ce for stoppage. Remove stoppage.
E. Wall switch or wires.Follow the corrective action in Symptom and Possible Cause 1.a
above. Check the switch and wiring.
4. Frequent pilot outage
problem.
5. The pilot and main
burner extinguish while in
operation.
A. Pilot fl ame may be too high or
too low, or blowing out (high
pressure), causing pilot safety
to drop out.
A. No LP in tank.Check the LP (propane) tank. Refi ll the fuel tank.
B. Improper gas inlet pressure.Verify with manometer. NG should read 5-14 inches w.c. LP should
C. Inner vent pipe leaking exhaust
gases back into the system.
Clean thermocouple and adjust the pilot fl ame for proper fl ame
impingement. Follow lighting instructions carefully.
read 10-14 inches w.c.
Check venting system for damage. Replace/repair improperly
assembled pipe sections.
D. Glass installed improperly.Check to ensure glass is installed properly. Replace glass panel
assembly.
E. Failed thermopile or
thermocouple.
F. Improper vent cap installation. Check for proper installation and freedom from debris or blockage.
6. Glass soots.A. Flame impingement.Adjust the log set so that the fl ame does not excessively impinge on
B. Improper air shutter setting.Refer to manual for shutter set points. Ensure that set point is
C. Debris around air shutter.Inspect the opening at the base of the burner. NO MATERIAL
7. Flame burns blue and lifts
off burner.
A. Insuffi cient oxygen being
supplied.
Replace pilot if necessary.
it. Refer to log instructions.
correct for appliance/gas type. If unit has adjustable shutter, it may
be necessary to increase shutter opening.
SHOULD BE PLACED IN THIS OPENING.
Ensure that the vent cap is installed properly and free of debris.
Ensure that the vent system joints are tight and have no leaks.
Ensure that no debris has been placed at the base of, or in the area
of the air holes in the center of the base pan beneath the burner.
Ensure that the glass is tightened properly on the unit, particularly
on top corners.
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0861
Page 62
B. Intellifi re Ignition System
SymptomPossible CauseCorrective Action
1. Pilot won’t light. The
ignitor/module makes
noise, but no spark.
A. Incorrect wiring.Verify “S” wire (white) for sensor and “I” wire (orange) for ignitor are
B. Loose connections or electrical
shorts in the wiring.
C. Ignitor gap is too large.Verify gap of igniter to right side of pilot hood. The gap should be
D. Module.Turn ON/OFF rocker switch or wall switch to OFF position. Remove
connected to correct terminals on module and pilot assembly.
Verify no loose connections or electrical shorts in wiring from
module to pilot assembly. Verify connections underneath pilot
assembly are tight; also verify connections are not grounding out to
metal chassis, pilot burner, pilot enclosure, mesh screen if present,
or any other metal object.
approximately .17 inch or 1/8 in. (3 mm).
ignitor wire “I” from module. Place a grounded wire about 3/16 in. (5
mm) away from “I” terminal on module. Place ON/OFF rocker switch
or wall switch in ON position. If there is no spark at “I” terminal
module must be replaced. If there is a spark at “I” terminal, module
is fi ne. Inspect pilot assembly for shorted sparker wire or cracked
insulator around electrode. Replace pilot if necessary.
2. Pilot won’t light, there is no
noise or spark.
3. Pilot sparks, but Pilot will
not light.
A. No power or transformer
installed incorrectly.
B. A shorted or loose connection
in wiring confi guration or wiring
harness.
C. Improper wall switch wiring.Verify that 110/VAC power is “ON” to junction box.
D. Module not grounded.Verify black ground wire from module wire harness is grounded to
E. Module.Turn ON/OFF rocker switch or wall switch to OFF position. Remove
A. Gas supply.Verify that incoming gas line ball valve is “open”. Verify that inlet
B. Ignitor gap is incorrect.Verify that spark gap from ignitor to pilot hood is .17 in. or 1/8 in (3
C. Module is not grounded.Verify module is securely grounded to metal chassis of appliance.
Verify that transformer is installed and plugged into module. Check
voltage of transformer under load at spade connection on module
with ON/OFF switch in ON position. Acceptable readings of a good
transformer are between 3.2 and 2.8 volts AC.
Remove and reinstall the wiring harness that plugs into module.
Verify there is a tight fi t. Verify pilot assembly wiring to module.
Remove and verify continuity of each wire in wiring harness.
Replace any damaged components.
metal chassis of appliance.
ignitor wire “I” from module. Place ON/OFF rocker switch or wall
switch in ON position. If there is no spark at “I” terminal module
must be replaced. If there is a spark at “I” terminal, module is fi ne.
Inspect pilot assembly for shorted sparker wire or cracked insulator
around electrode.
pressure reading is within acceptable limits, inlet pressure must not
exceed 14 in. W.C.
mm).
D. Module voltage output / Valve/
Pilot solenoid ohms readings.
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0862
Verify battery voltage is at least 2.7 volts. Replace batteries if
voltage is below 2.7.
Page 63
Intellifi re Ignition System - (continued)
SymptomPossible CauseCorrective Action
4. Pilot lights but continues
to spark, and main burner
will not ignite. (If the pilot
continues to spark after
the pilot fl ame has been lit, fl ame rectifi cation has not
occurred.)
A. A shorted or loose connection
in fl ame sensing rod.
B. Poor fl ame rectifi cation or
contaminated fl ame sensing
rod.
C. Module is not grounded.Verify module is securely grounded to metal chassis of appliance.
Verify all connections to wiring diagram in manual. Verify
connections underneath pilot assembly are tight. Verify connections
are not grounding out to metal chassis, pilot burner, pilot enclosure
or screen if present, or any other metal object.
With fi xed glass assembly in place, verify that fl ame is engulfi ng fl ame sensing rod on left side of pilot hood. Flame sensing rod
should glow shortly after ignition. Verify correct pilot orifi ce is
installed and gas inlet is set to pressure specifi cations.
Verify that wire harness is fi rmly connected to the module.
D. Damaged pilot assembly or
contaminated fl ame sensing
rod.
E. Module.Turn ON/OFF rocker switch or wall switch to OFF position. Remove
Verify that ceramic insulator around the fl ame sensing rod is not
cracked, damaged, or loose. Verify connection from fl ame sensing
rod to white sensor wire. Clean fl ame sensing rod with emery cloth
to remove any contaminants that may have accumulated on fl ame
sensing rod. Verify continuity with a multimeter with ohms set at
lowest range. Replace pilot if any damage is detected.
ignitor wire “I” from module. Place ON/OFF rocker switch or wall
switch in ON position. If there is no spark at “I” terminal module
must be replaced. If there is a spark at “I” terminal, module is fi ne.
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0863
Page 64
16
16
Reference Materials
A. Appliance Dimension Diagram
Dimensions are actual appliance dimensions. Use for reference only. For framing dimensions and clearances refer to Section 3.
C
19-1/8 in.
(486 mm)
Gas Line
Access
6-1/2 in.
(165 mm)
11-5/8in.
(295 mm)
3 in.
(76 mm)
23-1/2 in.
(597 mm)
A
Alternative
Gas Access
31-1/2 in.
(800 mm)
34 in.
(864 mm)
B
1-1/2 in.
(38 mm)
2-3/8 in.
(60 mm)
8 in.
(203 mm)
Electrical
Access
15-3/4 in.
(400 mm)
34-1/2 in.
(876 mm)
1-3/4 in.
(44 mm)
Figure 16.1 Appliance Dimensions
ModelABC
NDV3630in.35308 5/8
mm889762219
NDV3933in.383311 5/8
mm965838295
NDV4236in.413614 5/8
mm1041916371
NDV4842in.474220 5/8
mm11941067524
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0864
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0865
Page 66
B. Vent Components Diagrams (continued)
31 in.
(787 mm)
13-3/4 in.
(349 mm)
13-1/4 in.
(367 mm)
24-5/8 in.
(625 mm)
27-1/2 in.
(698 mm)
RF6M
Roof Flashing Multi-pak
13-3/4 in.
(349 mm)
BEK
Trap Cap Brick Extension
5 in.
(127 mm)
24-5/8 in.
(625 mm)
13-7/8 in.
(352 mm)
13-1/4 in.
(367 mm)
Roof Flashing Multi-pak
DVP-HPC Cap Brick Extension
RF12M
11-7/8 in.
(302 mm)
DVP-BEK2
(127 mm)
5 in.
DVP-TRAPFL
Flashing
26 in.
(660 mm)
DVP-HSM-B
Extended Heat Shield
7-1/8 in.
(181 mm)
(356 mm)
14 in.
11-5/8 in.
(295 mm)
5-3/4 in.
(146 mm)
13-7/8 in.
(352 mm)
12-1/8 in.
(308 mm)
COOL-ADD
Cap Shield
9-1/2 in.
(241 mm)
DRC-RADIUS
Cap Shield
Figure 16.3 DVP Vent Components
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0866
Page 67
B. Vent Components Diagrams (continued)
7-3/8 i
7-1/4 i
n.
(187 mm)
1-1/2 in.
(38 mm)
12 in.
(305 mm)
DVP-TB1
Basement Vent Cap
7-1/4 in.
(184 mm)
5-1/4 in.
(133 mm)
Vertical Termination Cap
14 in.
(356 mm)
DVP-TVHW
12-1/2 in.
(318 mm)
(High wind)
17-3/4 in.
(451 mm)
(For use with IPI and DSI appliances only.)
Vertical Termination Cap
PVK-80
3-7/8 in.
(98 mm)
10-1/2 in.
(267 mm)
DVP-TV
n.
1 in.
(184 mm)
(25 mm)
16-7/8 in.
(429 mm)
12 in.
(305 mm)
12-1/8 in.
(314 mm)
1-5/8 in.
(41 mm)
High Performance Cap
Figure 16.4 DVP Vent Components
7-1/8 in.
(181 mm)
DVP-HPC
14 in.
(356 mm)
14 in.
(356 mm)
3/8 in. (10 mm)
1 in. (25 mm)
7-3/4 to 10-3/8 in.
(197 to 264 mm)
DVP-FBHT
Fire Brick Termination Cap
8-3/4 in.
(222 mm)
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0867
Page 68
B. Vent Components Diagrams (continued)
Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm). The heat shield is designed to be
used on a wall 4 in. to 7-1/4 in. (102 mm to 184 mm) thick. If wall thickness is less than 4 in. (102 mm) the
existing heat shields must be field trimmed. If wall thickness is greater than 7-1/4 in. (184 mm) a DVP-HSM-B
will be required.
15-1/8 in.
(384 mm)
12 in.
(305 mm)
8 in.
(203 mm)
Heat
Shield
Max
Effective
Length
DVP-TRAP
Horizontal Termination Cap
Term Cap
Trap1
Trap2
Minimum
Effective Length
3-1/8 in. 4-5/8 in.
79 mm117 mm
5-3/8 in. 9-3/8 in.
137 mm238 mm
Effective Length
Maximum
DVP-TRAP1
DVP-TRAP2
DVP-HPC1
Figure 16.5 DVP Vent Components
DVP-TRAPK1
DVP-TRAPK2
DVP-HPC2
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0868
Page 69
B. Vent Components Diagrams (continued)
DVP-TRAP to DVP-HPC Side Filler Kit
Î
Fillers
15 in.
(381 mm)
Effective Length
5-3/4 to 8-3/8 in.
146 to 213 mm
8-1/8 in.
(206 mm)
DVP-HRC-SS
(Not approved for NDV4842)
5-1/2 in.
140 mm
87°
8-3/8 in.
213 mm
3°
13 in.
(330 mm)
Figure 16.6 DVP Vent Components
10-1/2 in.
267 mm
10-7/8 in.
276 mm
DVP-HRC-ZC-SS
(Not approved for NDV4842)
Heatilator • Novus NDV Series • 4055-187 Rev F • 06/0869