Hearth and Home Technologies IDV6247ILT, IDV6247IT, IDV4833IH, IDV4833ILH, IDV6247ILH User Manual

...
Model(s):
IDV4833IT, IDV4833ILT,
IDV4833IH, IDV4833ILH,
IDV6247IT, IDV6247ILT,
Î
IDV6247IH, IDV6247ILH
Owner’s Manual
Installation and Operation
CAUTION
DO NOT DISCARD THIS MANUAL
• Important operating and maintenance instructions included.
Read, understand and follow these instructions for safe installation and operation.
WARNING
If the information in these instruc­tions is not followed exactly, a re may result causing property damage, personal injury, or death.
• Do not store or use gasoline or other fl am- mable vapors and liquids in the vicinity of this or any other appliance.
• What to do if you smell gas:
- Do not try to light any appliance.
- Do not touch any electrical switch. Do not use any phone in your building.
- Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
- If you cannot reach your gas supplier, call the fi re department.
• Installation and service must be performed by a qualifi ed installer, service agency, or
the gas supplier.
This appliance may be installed as an OEM installation in manufactured home (USA only) or mobile home and must be installed in accordance with the manufacturer’s instructions and the manufactured home construction and safety standard, Title 24 CFR, Part 3280 or Standard for
Installation in Mobile Homes, CAN/CSA Z240MH.
This appliance is only for use with the type(s) of gas indicated on the rating plate.
DO NOT
DISCARD
Leave this manual with party responsible for use and operation.
WARNING
HOT SURFACES!
Glass and other surfaces are hot during operation and cool down.
Hot glass will cause burns.
• Do not touch glass until it is cooled
• NEVER allow children to touch glass
• Keep children away
• CAREFULLY SUPERVISE children in same room as appliance.
• Alert children and adults to hazards of high temperatures.
High temperatures may ignite clothing or other ammable materials.
• Keep clothing, furniture, draperies and other combustibles away.
This appliance has been supplied with an integral barrier to prevent direct contact with the fi xed glass panel. Do NOT operate the appliance with the barrier removed.
Contact your dealer or Hearth & Home Technologies if the barrier is not present or help is needed to properly install one.
In the Commonwealth of Massachusetts installation must be performed by a licensed plumber or gas fi tter;
See Table of Contents for location of additional Commonwealth of Massachusetts requirements.
Installation and service of this appliance should be performed by qualifi ed personnel. Hearth & Home Technologies suggests NFI certifi ed or factory-trained professionals, or technicians supervised by an NFI certifi ed professional.
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/08 1
Read this manual before installing or operating this appliance.
Please retain this owner’s manual for future reference.
A. Congratulations
Congratulations on selecting a Heatilator gas fi replace, an elegant and clean alternative to wood burning fi replaces. The Heatilator gas fi replace you have selected is designed to provide the utmost in safety, reliability, and effi ciency.
As the owner of a new fi replace, you’ll want to read and carefully follow all of the instructions contained in this owner’s manual. Pay special attention to all cautions and warnings.
Homeowner Reference Information
This owner’s manual should be retained for future reference. We suggest that you keep it with your other important documents and product manuals.
The information contained in this owner’s manual, unless noted otherwise, applies to all models and gas control systems.
Your new Heatilator gas fi replace will give you years of durable use and trouble-free enjoyment. Welcome to the Heatilator family of fi replace products!
We recommend that you record the following pertinent information about your fi replace.
Model Name: ___________________________________________ Date purchased/installed: __________________
Serial Number: __________________________________________ Location on fi replace: _____________________
Dealership purchased from: _______________________________ Dealer Phone: __________________________
Notes: _______________________________________________________________________________________
_____________________________________________________________________________________________
Listing Label Information/Location
Hearth & Home Technologies Inc
1915 W. Saunders Street Mt. Pleasant, IA 52641
Model #
ANSI Standard
MODEL MFG. DATE MODÈLE DATE DE FAB.
GAS TYPE/TYPE DE GAZ NATURAL/NATUREL PROPANE ALTITUDE 0-2000 2000-4000 FT/PI 0-2000 2000-4000 FT/PI MAX INPUT/DÉBIT XX,XXX XX,XXX BTUH XX,XXX XX,XXX BTUH MIN INPUT/DÉBIT XX,XXX XX,XXX BTUH XX,XXX XX,XXX BTUH MANIFOLD PRESSURE/PRESSION TUBULAIRE MAX. XX IN. W.C./C. D'EAU XX IN. W.C./C. D'EAU MIN. XX IN. W.C./C. D'EAU XX IN. W.C./C. D'EAU MIN. INLET PRESS. XX IN. W.C./C. D'EAU 1XX IN. W.C./C. D'EAU FOR THE PURPOSE OF INPUT ADJUSTMENT PRESS. MIN. D'ALIMENTATION ORIFICE SIZE DIAM. DE L'INJECTEUR XX/XX DIA. in./mm XX/XX DIA. in./mm
LESS THAN/MOINS DE 3 AMPÈRES., 115V., 60 Hz
DO NOT REMOVE OR COVER THIS LABEL. VENTED GAS FIREPLACE - NOT FOR USE WITH SOLID FUEL. FOYER À GAZ À ÉVACUATION - NE DOIT PAS ÊTRE UTILISÉ AVEC UN COMBUSTIBLE SOLIDE.
XXXXXX
The model information regarding your specifi c fi replace can be found on the rating plate usually located in the control area of the fi replace.
Gas Type
SERIAL NO. DE SÉRIE
Serial #
XXXXXXXXX
XXXX
CERTIFIED
FOR CANADA
CERTIFIÉ POUR LE
CANADA
Orifice Size
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/082
Safety Alert Key:
• DANGER! Indicates a hazardous situation which, if not avoided will result in death or serious injury.
• WARNING! Indicates a hazardous situation which, if not avoided could result in death or serious injury.
• CAUTION! Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
• NOTICE: Used to address practices not related to personal injury.
Table of Contents
A. Congratulations 2 B. Warranty 5
1 Listing and Code Approvals
A. Appliance Certifi cation 7 B. Tempered Glass Specifi cations 7 C. BTU Specifi cations 7 D. High Altitude Installations 7 E. Non-Combustible Materials Specifi cation 7 F. Combustible Materials Specifi cation 7 G. Electrical Codes 7 H. Requirements for the Commonwealth of Massachusetts 8
User Guide
2 Operating Instructions
A. Gas Fireplace Safety 9 B. Your Fireplace 9 C. Clear Space 10 D. Decorative Doors and Fronts 10 E. Fixed Glass Assembly 10 F. Remote Controls, Wall Controls and Wall Switches 10 G. Before Lighting Fireplace 10 H. Lighting Instructions (IPI) 11 I. After Fireplace is Lit 12 J. Frequently Asked Questions 12
3 Maintenance and Service
A. Maintenance Tasks-Homeowner 13 B. Maintenance Tasks-Qualifi ed Service Technician 14
Installer Guide
4 Getting Started
A. Typical Appliance System 15 B. Design and Installation Considerations 16 C. Tools and Supplies Needed 16 D. Inspect Appliance and Components 16
5 Framing and Clearances
A. Select Appliance Location 17 B. Construct the Appliance Chase 18 C. Clearances 18 D. Mantel and Wall Projections 19
6 Termination Locations
A. Vent Termination Minimum Clearances 20
7 Vent Information and Diagrams
A. Approved Pipe 22 B. Vent Table Key 22 C. Use of Elbows 22 D. Measuring Standards 22 E. Vent Diagrams 23
8 Vent Clearances and Framing
A. Pipe Clearances to Combustibles 28 B. Wall Penetration Framing 28 C. Install the Ceiling Firestop 29 D. Install Attic Insulation Shield 30
9 Appliance Preparation
A. Secure and Level the Appliance 31
10 Install Vent Pipe
A. Assemble Vent Sections 32 B. Assemble Slip Sections 33 C. Secure the Vent Sections 33 D. Disassemble Vent Sections 34 E. Install Metal Roof Flashing 34 F. Assemble and Install Storm Collar 35 G. Install RF4-8 36 H. Install Vertical Termination Cap 37 I. Heat Shield Requirements for Horizontal Termination 37 J. Install Horizontal Termination Cap 38
11 Gas Information
A. Fuel Conversion 39 B. Gas Pressure 39 C. Gas Connection 39 D. High Altitude Installations 39
12 Electrical Information
A. Wiring Requirements 40 B. Intellifi re Ignition System Wiring 40 C. Optional Accessories Requirements 40 D. Electrical Service and Repair 40 E. Junction Box Installation 41
13 Finishing
A. Mantel and Wall Projections 42 B. Facing Material 42 C. Noncombustible Finishing Material 43
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/08 3
14 Appliance Setup
A. Remove Shipping Materials 44 B. Remove Fixed Glass Assembly 44 C. Remove Materials Shipped Inside Firebox 44 D. Clean the Appliance 44 E. Accessories 44 F. Heat-Zone-Gas 44 G. Refractory 44 H. Install the Logs 45 I. Place Lava Rock and Rockwool 46 J. Glass Panel Assembly 47 K. Decorative Firescreen, Refractory Shields and Lower
Decorative Front Face 48 L. Installing External Refractories 49 M. Air Shutter Setting 50
15 Troubleshooting
A. Intellifi re Ignition System 51
16 Reference Materials
A. Appliance Dimension Diagram 53 B. Vent Components Diagrams 54 C. Service Parts 59 D. Optional Components 63 E. Contact Information 64
Î = Contains updated information.
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/084
B. Warranty
Hearth & Home Technologies LIMITED WARRANTY
Hearth & Home Technologies (“HHT”) and its respective brands extends the following warranty for HHT gas, wood, pellet and electric appliances purchased from an authorized HHT dealer and installed in the United States of America or Canada. Warranty starts with date of purchase by the original owner (End User) except as noted for replacement parts.
Warranty Period HHT Manufactured Appliances and Venting
Parts Labor Gas Wood Pellet
1 Year XXXXXX
EPA
Wood
Electric Venting
Components Covered
All Parts and Material Except as
covered by Conditions, Exclu-
sion, and Limitations listed
XX
2 years
3 years X Firepots
5 years 3 years X X Castings & Baffl es
7 years 3 years X X X
10
years
Limited
Lifetime
1 year X Burners, Logs & Refractory
1 year X Firebox & Heat Exchanger
90 Days XXXXXX All Replacement Parts
XXXX Blowers
X Molded Refractory Panels
Igniters, Electronic Compo-
nents, and Glass
Firebox, HHT Chimney, Termi-
nation & Heat
Exchanger
See Conditions, Exclusions, and limitations. 9-01-08
CONDITIONS, EXCLUSIONS & LIMITATION OF LIABILITY
 This warranty applies to the original owner and is transferable up to two years from date of purchase to the new
homeowner, provided the purchase was made through an authorized dealer or distributor of HHT, and the appliance remains in its original place of installation.
 The maximum amount recoverable under this warranty is limited to the purchase price of the product.
 In no event shall HHT be liable for any incidental or consequential damages caused by defects in the product.
 Adjustments, regular maintenance, cleaning and temporary repairs, or the failure to duplicate the problem in the home
is not covered under this warranty.
4021-645A 09-01-08 Page 1 of 2
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/08 5
B. Limited Lifetime Warranty (continued)
This limited warranty does not extend to or include surface fi nish on the appliance or terminations, door gasketing, glass gasketing, glass discoloration, fi rebrick, pellet logs, kaowool or other ceramic insulating materials. Rust and/or corrosion on any of the metal surfaces, cast iron components, baffl es, fi repots, doors, or fi rebox area are not covered by this warranty.  Noise resulting from minor expansion, contraction, or movement of certain parts is normal and complaints related to
this noise are not covered by this warranty.
 HHT’s obligation under this warranty does not extend to damages resulting from: (1) installation, operation or
maintenance of the appliance not in accordance with the installation instructions; operating instructions and the listing agent identifi cation label furnished with the appliance; (2) installation which does not comply with local building codes; (3) shipping, improper handling, improper operation, abuse, misuse, accident or unworkmanlike repairs; (4) environmental conditions, inadequate ventilation or drafting caused by tight sealing construction of the structure or handling devices such as exhaust fans or forced air furnaces or other such causes; (5) use of fuels other than those specifi ed in the operating instructions; (6) installation or use of components not supplied with the appliance or any other components not expressly authorized and approved by HHT; and/or (7) modifi cation of the appliance not expressly authorized and approved by HHT in writing.
 This warranty does not apply to non-HHT venting components, hearth components or other accessories used in
conjunction with the installation of this product.
 This warranty is void if the appliance has been over- red or operated in atmospheres contaminated by chlorine,
uorine, or other damaging chemicals the appliance is subject to prolonged periods of dampness or condensation, or
there is any damage to the appliance or other components due to water or weather damage which is the result of, but not limited to, improper chimney or venting installation.
 HHT’s liability under this warranty is limited to the replacement and repair of defective components or workmanship
during the applicable period. HHT may fully discharge all of its obligations under such warranties by repairing the defective component(s) at HHT’s discretion. Shipping costs are not covered under this warranty.
 Some states do not allow exclusions or limitation of incidental or consequential damages, so those limitations may not
apply to you. This warranty gives you specifi c rights; you may also have other rights, which vary from state to state.
 EXCEPT TO THE EXTENT PROVIDED BY LAW, HHT MAKES NO EXPRESS WARRANTIES OTHER THAN THE
WARRANTY SPECIFIED HEREIN. THE DURATION OF ANY IMPLIED WARRANTY IS LIMITED TO DURATION OF THE WARRANTY SPECIFIED ABOVE.
This Limited Warranty is effective on all HHT appliances sold after September 01, 2008 and supersedes any and all warranties currently in existence.
If warranty service is needed, you should contact your installing dealer. If the installing dealer is unable to provide necessary parts or components, contact the nearest authorized HHT dealer or supplier.
4021-645A 09-01-08 Page 2 of 2
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/086
1
1
Listing and Code Approvals
A. Appliance Certifi cation
MODELS:
LABORATORY: Underwriters Laboratories, Inc. (UL)
TYPE: Vented Gas Fireplace Heaters
STANDARD: ANSI Z21.88-2002•CSA2.33-M2002•UL307B
This product is listed to ANSI standards for “Vented Gas Fireplace Heaters” and applicable sections of “Gas Burn­ing Heating Appliances for Manufactured Homes and Recreational Vehicles”, and “Gas Fired Appliances for Use at High Altitudes”.
NOTICE: This installation must conform with local codes. In the absence of local codes you must comply with the National Fuel Gas Code, ANSI Z223.1-latest edition in the U.S.A. and the CAN/CGA B149 Installation Codes in Canada.
NOT INTENDED FOR USE AS A PRIMARY HEAT SOURCE.
This appliance is tested and approved as either supplemental room heat or as a decorative appliance. It should not be fac­tored as primary heat in residential heating calculations.
C. BTU Specifi cations
ICON DV-Mesh IDV4833 IDV6247
IPI
Max/Min Input Rate (NG) 48,000/33,500 59,000/40,000
Orifi ce Size (NG) 0.128 0.144
Max/Min Input Rate (LP) 48,000/35,500 56,000/41,500
Orifi ce Size (LP) 0.079 0.086
D. High Altitude Installations
NOTICE: If the heating value of the gas has been reduced, these rules do not apply. Check with your local gas utility or authorities having jurisdiction.
When installing above 2000 feet elevation:
• In the USA: Reduce input rate 4% for each 1000 feet above 2000 feet.
• In CANADA: Reduce input rate 10% for elevations between 2000 feet and 4500 feet. Above 4500 feet, consult local gas utility.
Check with your local gas utility to determine proper orifi ce size.
B. Tempered Glass Specifi cations
Hearth & Home Technologies appliances manufactured with tempered glass may be installed in hazardous locations such as bathtub enclosures as defi ned by the Consumer Product Safety Commission (CPSC). The tempered glass has been tested and certifi ed to the requirements of ANSI Z97.1 and CPSC 16 CFR 1202 (Safety Glazing Certifi cation Council SGCC# 1595 and
1597. Architectural Testing, Inc. Reports 02-31919.01 and 02-31917.01).
This statement is in compliance with CPSC 16 CFR Section 1201.5 “Certi cation and labeling requirements”
which refers to 15 U.S. Code (USC) 2063 stating “…Such certifi cate shall accompany the product or shall otherwise be furnished to any distributor or retailer to whom the product is delivered.”
Some local building codes require the use of tempered glass with permanent marking in such locations. Glass meeting this requirement is available from the factory. Please contact your dealer or distributor to order.
E. Non-Combustible Materials Specifi cation
Material which will not ignite and burn. Such materials are those consisting entirely of steel, iron, brick, tile, concrete, slate, glass or plasters, or any combination thereof.
Materials that are reported as passing ASTM E 136,
Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750 ºC and UL763 shall be
considered non-combustible materials.
F. Combustible Materials Specifi cation
Materials made of or surfaced with wood, compressed paper, plant fi bers, plastics, or other material that can ig- nite and burn, whether fl ame proofed or not, or plastered or unplastered shall be considered combustible materials.
G. Electrical Codes
NOTICE: This appliance must be electrically wired and grounded in accordance with local codes or, in the absence of local codes, with National Electric Code
ANSI/NFPA 70-latest edition or the Canadian Electric Code CSA C22.1.
• A 110-120 VAC circuit for this product must be protected with ground-fault circuit-interrupter protection, in compliance with the applicable electrical codes, when it is installed in locations such as in bathrooms or near sinks.
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/08 7
Note: The following requirements reference various Massachusetts and national codes not contained in this document.
H. Requirements for the Commonwealth of Massachusetts
For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above fi nished grade in the area of the venting, in- cluding but not limited to decks and porches, the following requirements shall be satisfi ed:
Installation of Carbon Monoxide Detectors
At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gas fi tter shall observe that a hard wired carbon mon- oxide detector with an alarm and battery back-up is installed on the fl oor level where the gas equipment is to be installed. In addition, the installing plumber or gas tter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or struc­ture served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualifi ed licensed profes- sionals for the installation of hard wired carbon monoxide detectors.
In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent oor level.
In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that dur­ing said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
Approved Carbon Monoxide Detectors
Each carbon monoxide detector as required in accor­dance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certifi ed.
Signage
A metal or plastic identifi cation plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) in. in size,
“GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
Inspection
The state or local gas inspector of the side wall horizon­tally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector ob­serves carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
Exemptions
The following equipment is exempt from 248 CMR
5.08(2)(a)1 through 4:
• The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and
• Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
MANUFACTURER REQUIREMENTS
Gas Equipment Venting System Provided
When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
• Detailed instructions for the installation of the venting system design or the venting system components; and
• A complete parts list for the venting system design or venting system.
Gas Equipment Venting System NOT Provided
When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the fl ue gases, but identi- es “special venting systems”, the following requirements shall be satisfi ed by the manufacturer:
• The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and
• The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.
A copy of all installation instructions for all Product Ap­proved side wall horizontally vented gas fueled equip­ment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
See Gas Connection section for additional Common­wealth of Massachusetts requirements.
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/088
2
User Guide
2
Operating Instructions
A. Gas Fireplace Safety
WARNING
HOT SURFACES!
Glass and other surfaces are hot during operation and cool down.
Hot glass will cause burns.
• Do not touch glass until it is cooled
• NEVER allow children to touch glass
• Keep children away
• CAREFULLY SUPERVISE children in
same room as appliance.
• Alert children and adults to hazards of high temperatures.
High temperatures may ignite clothing or other
ammable materials.
• Keep clothing, furniture, draperies and other combustibles away.
This appliance has been supplied with an integral barrier to prevent direct contact with the fi xed glass panel. Do NOT operate the appliance with the barrier removed.
Contact your dealer or Hearth & Home Technologies if the barrier is not present or help is needed to properly install one.
• Install a physical barrier such as:
- A decorative fi rescreen.
- Adjustable safety gate.
• Install a switch lock or a wall/remote control with child protection lockout feature.
• Keep remote controls out of reach of children.
• Never leave children alone near a hot fi replace, whether operating or cooling down.
• Teach children to NEVER touch the fi replace.
• Consider not using the fi replace when children will be present.
Contact your dealer for more information, or visit: www. hpba.org/staysafe.
To prevent unintended operation when not using your replace for an extended period of time (summer months, vacations, trips, etc):
• Remove batteries from remote controls.
• Turn off wall controls.
• Unplug 3 volt adapter plug and remove batteries on IPI models.
• Turn off gas controls valve on standing pilot models.
When lighting the pilot light on fi replaces with a standing pilot, remove the fi xed glass assembly so you can detect presence of residual gas build-up. See Standing Pilot Lighting instructions and Maintenance Tasks.
If you expect that small children or vulnerable adults may come into contact with this fi replace, the following precau- tions are recommended:
Decorative Doors
(not shown) Section 2.D.
Fixed Glass Assembly
(not shown) Section 2.E.
Grate (not shown) Section 2.B.
Clear Space Section 2.C.
Hearth
(not required)
Mantel
B. Your Fireplace
WARNING! DO NOT operate fi replace before reading and understanding operating instructions. Failure to operate
replace according to operating instructions could cause re or injury.
Figure 2.1 General Operating Parts
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/08 9
C. Clear Space
WARNING! DO NOT place combustible objects in front of the fi replace or block louvers. High temperatures may start a fi re. See Figure 2.2.
Avoid placing candles and other heat-sensitive objects on mantel or hearth. Heat may damage these objects.
Clear space 3 ft (914 mm) in front of appliance
Figure 2.2 Clear Space
E. Fixed Glass Assembly
See Section 14.J.
F. Remote Controls, Wall Controls and Wall Switches
Follow the instructions supplied with the control installed to operate your fi replace:
For safety:
• Install a switch lock or a wall/remote control with child protection lockout feature.
• Keep remote controls out of reach of children.
See your dealer if you have questions.
G. Before Lighting Fireplace
Before operating this replace for the rst time, have a qualifi ed service technician:
• Verify all shipping materials have been removed from inside and/or underneath the fi rebox.
• Review proper placement of logs, rockwool and/or other decorative materials.
• Check the wiring.
• Check the air shutter adjustment.
• Ensure that there are no gas leaks.
• Ensure that the glass is sealed and in the proper position and that the integral barrier is in place.
D. Decorative Doors and Fronts
WARNING! Risk of Fire! Install ONLY doors or fronts approved by Hearth & Home Technologies. Unapproved doors or fronts may cause fi replace to overheat.
This fi replace has been supplied with an integral barrier to prevent direct contact with the fi xed glass panel. DO NOT operate the fi replace with the barrier removed.
Contact your dealer or Hearth & Home Technologies if the barrier is not present or help is needed to properly install one.
For more information refer to the instructions supplied with your decorative door or front.
WARNING! Risk of Fire or Asphyxiation! DO NOT oper­ate fi replace with fi xed glass assembly removed.
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/0810
H. Lighting Instructions (IPI)
• For normal use, activate/deactivate your fi replace with the wall switch or remote control.
• The IPI system may be operated with two D-cell batteries. When using batteries, unplug the transformer. To prolong battery life, remove them when using the transformer.
• If your fi replace must be deactivated for service or an extended period of time, follow the instructions below.
This appliance needs fresh air for safe operation
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING: If you do not follow these instructions exactly, a fire
or explosion may result causing property damage, personal injury or loss of life.
A. This appliance is equipped with an ignition device which
automatically lights the pilot. Do not try to light the pilot by hand.
B. BEFORE LIGHTING smell all around the appliance area for
gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
C. Use only your hand to push in and move the gas control
valve or turn the gas control knob. Never use tools. If the lever or knob will not move by hand, don't try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been under water.
Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
LIGHTING INSTRUCTIONS
1. STOP! Read the safety information above on this label.
2. Turn wall switch to the "OFF" position or thermostat to the lowest setting.
3. Turn off all electric power to the appliance.
4. This appliance is equipped with an ignition device which automatically lights the pilot. Do NOT try to light the pilot by hand.
5. Wait five minutes to clear out any gas. If you then smell gas, STOP! Follow "B" in the safety information above on this label. If you don't smell gas, go to the next step.
6. To turn on the burner, turn on all electric power to this appliance and turn on the wall switch or set the thermostat to the desired setting.
7. If the appliance will not operate, follow the instructions "TO TURN OFF GAS TO APPLIANCE" and call your service technician or gas supplier.
and must be installed so there are provisions for adequate combustion and ventilation air.
This appliance must be installed in accordance with local codes, if any; if not, follow ANSI Z223.1 or, in Canada, current CAN/CGA-B149.
This appliance must be properly connected to a venting system in accordance with the manufacturer's installation instructions.
WARNING:
adjustment, alteration, service or maintenance can cause injury or property damage. Refer to the owner's information manual provided with the appliance. For assistance or additional information consult a qualified installer, service agency or the gas supplier.
CAUTION:
not touch. Keep children, clothing, furniture, gasoline and other liquids having flammable vapors away.
Improper installation,
Hot while in operation. Do
WARNING RISK OF FIRE
This appliance is intended to burn a specified gas fuel only. Do not attempt to use with solid wood fuel or another type of fuel. Do not attempt to modify or use any other type of gas burner system.
TO TURN OFF GAS TO APPLIANCE
1. Turn off wall switch or set thermostat to lowest setting.
2. Turn off all electric power to the appliance if service is to be performed.
Due to high surface temperatures, keep children, clothing and furniture away. Keep burner and control compartment clean. See installation and operating instructions accompanying the appliance.
3. Push the gas control lever in and move to the "OFF" position or push the gas control lever to the "OFF" position. Do not force.
4. Replace the control access panel.
WARNING: Disconnect the electric power
before servicing. If for any reason the original wire supplied with the appliance must be replaced, it must be replaced with 105° C or its equivalent.
For use with natural gas or propane. A conversion kit as supplied by the manufacturer shall be used to convert this appliance to the alternative fuel.
* Also certified for installation in a bedroom or a
bed-sitting room.
* For U.S. only!
NATURAL GAS
33631D
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/08 11
I. After Fireplace is Lit
Î
Initial Break-in Procedure
• The fireplace should be run three to four hours continuously on high.
• Turn the fi replace off and allow it to completely cool.
• Remove fi xed glass assembly. See Section 14.J.
• Clean fi xed glass assembly. See Section 3.
• Replace the fi xed glass assembly and run continuously on high an additional 12 hours.
This cures the materials used to manufacture the fi re- place.
NOTICE! Open windows for air circulation during fi replace break-in.
• Some people may be sensitive to smoke and
odors.
• Smoke detectors may activate.
J. Frequently Asked Questions
ISSUE SOLUTIONS
Condensation on the glass
Blue fl ames
Odor from appliance
This is a result of gas combustion and temperature variations. As the appliance warms, this condensation will disappear.
This is a result of normal operation and the fl ames will begin to yellow as the appliance is allowed to burn for 20 to 40 minutes.
When fi rst operated, this appliance may release an odor for the fi rst several hours. This is caused by the curing of materials from manufacturing. Odor may also be released from fi nishing materials and adhesives used near the appliance. These circumstances may require additional curing related to the installation environment.
Film on the glass
Metallic noise
Is it normal to see the pilot ame burn continually?
This is a normal result of the curing process of the paint and logs. Glass should be cleaned within 3 to 4 hours of initial burning. A non-abrasive cleaner such as gas appliance glass cleaner may be necessary. See your dealer.
Noise is caused by metal expanding and contracting as it heats up and cools down, similar to the sound produced by a furnace or heating duct. This noise does not affect the operation or longevity of the appliance.
In an Intellifi re ignition system it is normal to see the pilot fl ame, but it should turn off when ON/ OFF is turned to OFF. In a standing pilot system the pilot will always stay on.
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/0812
3
3
Maintenance and Service
Any safety screen or guard removed for servicing must be replaced prior to operating the fi replace.
When properly maintained, your fi replace will give you many years of trouble-free service. We recommend an­nual service by a qualifi ed service technician.
A. Maintenance Tasks-Homeowner
Installation and repair should be done by a qualifi ed service technician only. The fi replace should be inspect- ed before use and at least annually by a professional
service person. The following tasks may be performed annually by the homeowner. If you are uncomfortable performing any of the listed tasks, please call your dealer for a service ap­pointment.
More frequent cleaning may be required due to lint from carpeting or other factors. Control compartment, burner and circulating air passageway of the fi replace must be kept clean.
CAUTION! Risk of Burns! The fi replace should be turned off and cooled before servicing.
Glass Cleaning
Frequency: Seasonally By: Homeowner
Tools Needed: Protective gloves, glass cleaner, drop
cloth and a stable work surface.
CAUTION! Handle fi xed glass assembly with care.
Glass is breakable.
• Avoid striking, scratching or slamming glass
• Avoid abrasive cleaners
• DO NOT clean glass while it is hot
• Prepare a work area large enough to accommodate fi xed
glass assembly and door frame by placing a drop cloth on a fl at, stable surface.
Note: Fixed glass assembly and gasketing may have residue that can stain carpeting or fl oor surfaces.
• Remove door or decorative front from fi replace and set
aside on work surface.
• See Section 14.J for instructions to remove fi xed glass
assembly.
• Clean glass with a non-abrasive commercially available
cleaner.
- Light deposits: Use a soft cloth with soap and water
- Heavy deposits: Use commercial fi replace glass cleaner (consult with your dealer)
• Carefully set fi xed glass assembly in place on fi replace. Hold glass in place with one hand and secure glass latches with the other hand.
• Reinstall door or decorative front.
Doors, Surrounds, Fronts
Frequency: Annually By: Homeowner Tools needed: Protective gloves, stable work surface
• Assess condition of screen and replace as necessary.
• Inspect for scratches, dents or other damage and repair as necessary.
• Check that louvers are not blocked.
• Vacuum and dust surfaces.
Remote Control
Frequency: Seasonally By: Homeowner Tools needed: Replacement batteries and remote control
instructions.
• Locate remote control transmitter and receiver.
• Verify operation of remote. Refer to remote control operation instructions for proper calibration and setup procedure.
• Place batteries as needed in remote transmitters and battery-powered receivers.
• Place remote control out of reach of children.
If not using your fi replace for an extended period of time (summer months, vacations/trips, etc), to prevent unin­tended operation:
• Remove batteries from remote controls.
• Unplug 3 volt adapter plug on IPI models.
Venting
Frequency: Seasonally By: Homeowner Tools needed: Protective gloves and safety glasses.
• Inspect venting and termination cap for blockage or obstruction such plants, bird nests, leaves, snow, debris, etc.
• Verify termination cap clearance to subsequent construction (building additions, decks, fences, or sheds). See Section 6.
• Inspect for corrosion or separation.
• Verify weather stripping, sealing and fl ashing remains intact.
• Inspect draft shield to verify it is not damaged or missing.
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/08 13
B. Maintenance Tasks-Qualifi ed Service Technician
The following tasks must be performed by a qualifi ed service technician.
Gasket Seal and Glass Assembly Inspection
Frequency: Annually By: Quali ed Service Technician Tools needed: Protective gloves, drop cloth and a stable
work surface.
• Inspect gasket seal and its condition.
• Inspect fi xed glass assembly for scratches and nicks that can lead to breakage when exposed to heat.
• Confi rm there is no damage to glass or glass frame. Replace as necessary.
• Verify that fi xed glass assembly is properly retained and attachment components are intact and not damaged. Replace as necessary.
Logs
Frequency: Annually By: Quali ed Service Technician Tools needed: Protective gloves.
• Inspect for damaged or missing logs. Replace as necessary. Refer to Section 14.H. for log placement instructions.
• Verify correct log placement and no fl ame impingement causing sooting. Correct as necessary.
Firebox
Frequency: Annually By: Quali ed Service Technician Tools needed: Protective gloves, sandpaper, steel wool,
cloths, mineral spirits, primer and touch-up paint.
• Inspect for paint condition, warped surfaces, corrosion or perforation. Sand and repaint as necessary.
• Replace fi replace if fi rebox has been perforated.
Burner Ignition and Operation
Frequency: Annually By: Quali ed Service Technician Tools needed: Protective gloves, vacuum cleaner, whisk
broom, fl ashlight, voltmeter, indexed drill bit set, and a manometer.
• Verify burner is properly secured and aligned with pilot or igniter.
• Clean off burner top, inspect for plugged ports, corrosion or deterioration. Replace burner if necessary.
• Replace rockwool with new dime-size pieces. DO NOT block ports or obstruct lighting paths. Refer to Section
14.I for proper rockwool placement.
• Verify batteries have been removed from battery back­up IPI systems to prevent premature battery failure or leaking.
• Check for smooth lighting and ignition carryover to all ports. Verify that there is no ignition delay.
• Inspect for lifting or other fl ame problems.
• Verify air shutter setting is correct. See Section 14.M. for required air shutter setting. Verify air shutter is clear of dust and debris.
• Inspect orifi ce for soot, dirt and corrosion. Verify orifi ce size is correct. See Service Parts List for proper orifi ce sizing.
• Verify manifold and inlet pressures. Adjust regulator as required.
• Inspect pilot fl ame pattern and strength. See Figure 3.1 for proper pilot fl ame pattern. Clean or replace orifi ce spud as necessary.
• Inspect thermocouple/thermopile or IPI fl ame sensing rod for soot, corrosion and deterioration. Clean with emery cloth or replace as required.
• Verify thermocouple/thermopile or IPI millivolt output. Replace as necessary.
Control Compartment and Firebox Top
Frequency: Annually By: Quali ed Service Technician Tools needed: Protective gloves, vacuum cleaner, dust
cloths
• Vacuum and wipe out dust, cobwebs, debris or pet hair. Use caution when cleaning these areas. Screw tips that have penetrated the sheet metal are sharp and should be avoided.
• Remove all foreign objects.
• Verify unobstructed air circulation.
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/0814
Figure 3.1 IPI Pilot Flame Patterns
4
Installer Guide
4
Getting Started
A. Typical Appliance System
NOTICE: Illustrations and photos refl ect typical installations and are for design purposes only. Illustrations/diagrams are not drawn to scale. Actual product may vary from pictures in manual
Vertical Termination Cap
(SECTION 10.H.)
Noncombustible roof flashing maintains minimum clearance around pipe (SECTION 10)
Vent Pipe (SECTIONS 7, 8, 10)
Storm Collar (SECTION 10.F.)
Vent pipe penetrates roof, preferably without affecting roof rafters (SECTION 8)
Attic insulation shield (not shown) must be used here to keep insulation away from vent pipe if attic is insulated. (SECTION 8.D.)
Ceiling Firestop on floor of attic (SECTION 8.C.)
Framing/Header (SECTION 5)
Framing Headed off in Ceiling Joists (SECTION 8)
Optional
Wall Switch
Mantel & Mantel Leg (SECTION 13.A.)
Surround
Hearth Extension (not required)
Gas Line (SECTION 11)
Figure 4.1 Typical System
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/08 15
B. Design and Installation Considerations
Heatilator direct vent gas appliances are designed to op­erate with all combustion air siphoned from outside of the building and all exhaust gases expelled to the outside. No additional outside air source is required.
Installation MUST comply with local, regional, state and national codes and regulations. Consult insurance carrier, local building inspector, fi re offi cials or authorities having jurisdiction over restrictions, installation inspection and permits.
Before installing, determine the following:
• Where the appliance is to be installed.
• The vent system confi guration to be used.
• Gas supply piping.
• Electrical wiring requirements.
• Framing and fi nishing details.
• Whether optional accessories—devices such as a fan,
wall switch, or remote control—are desired.
Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. For assistance or additional information, consult a qualifi ed service technician, service agency or your dealer.
C. Tools and Supplies Needed
Before beginning the installation be sure that the following tools and building supplies are available.
Tape measure Framing material Pliers High temperature caulking
material Hammer Phillips screwdriver Gloves Framing square Voltmeter Electric drill and bits (1/4 in.) Plumb line Safety glasses Level Reciprocating saw Manometer Flat blade screwdriver Non-corrosive leak check solution 1/2 - 3/4 in. length, #6 or #8 Self-drilling screws One 1/4 in. female connection (for optional fan).
D. Inspect Appliance and Components
• Carefully remove the appliance and components from the packaging. Refer to Section 14.A.
• The vent system components and decorative doors and fronts may be shipped in separate packages.
• If packaged separately, the log set and appliance grate must be installed.
• Report to your dealer any parts damaged in shipment, particularly the condition of the glass.
• Read all of the instructions before starting the installation. Follow these instructions carefully during the installation to ensure maximum safety and benefi t.
WARNING! Risk of Fire or Explosion! Damaged parts could impair safe operation. DO NOT install damaged, in­complete or substitute components. Keep appliance dry.
Hearth & Home Technologies disclaims any responsibility for, and the warranty will be voided by, the following actions:
• Installation and use of any damaged appliance or vent system component.
• Modifi cation of the appliance or vent system.
• Installation other than as instructed by Hearth & Home Technologies.
• Improper positioning of the gas logs or the glass door.
• Installation and/or use of any component part not approved by Hearth & Home Technologies.
Any such action may cause a fi re hazard.
WARNING! Risk of Fire, Explosion or Electric Shock! DO NOT use this appliance if any part has been under wa-
ter. Call a qualifi ed service technician to inspect the appli- ance and to replace any part of the control system and/or gas control which has been under water.
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/0816
5
5
Framing and Clearances
A. Select Appliance Location
When selecting a location for the appliance it is important to consider the required clearances to walls (see Figure
5.1).
WARNING! Risk of Fire or Burns! Provide adequate clearance around air openings and for service access. Due
to high temperatures, the appliance should be located out of traffi c and away from furniture and draperies.
1-1/2 in. (38 mm)
min.
appliance
to combustibles
B
B
E
A
Top Vent
One 90° Elbow
Horiz Term
NOTICE: Illustrations refl ect typical installations and are FOR DESIGN PURPOSES ONLY. Illustrations/diagrams are not drawn to scale. Actual installation may vary due to individual design preference.
A
D
Alcove
Installation
Drywall
F
Top Vent
One 90° Elbow
Horiz Term
A
Model # A B C D E F
IDV4833I
IDV6247I
in. 47-1/2 64-1/4 30-1/2 48-1/2 90-7/8 48
mm 1207 1632 775 1232 2309 1219
in. 61-1/2 74-1/8 30-1/2 62-1/2 104-7/8 48
mm 1562 1883 775 1588 2665 1219
C
Figure 5.1 Appliance Locations
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/08 17
B. Construct the Appliance Chase
A chase is a vertical box-like structure built to enclose the gas appliance and/or its vent system. In cooler climates the vent should enclosed inside the chase.
NOTICE:
restops and construction of the chase may vary with the type of building. These instructions are not substitutes for the requirements of local building codes. Therefore, you MUST check local building codes to determine the requirements to these steps.
Chases should be constructed in the manner of all out­side walls of the home to prevent cold air drafting prob­lems. The chase should not break the outside building envelope in any manner.
Walls, ceiling, base plate and cantilever fl oor of the chase should be insulated. Vapor and air infi ltration barriers should be installed in the chase as per regional codes for the rest of the home. Additionally, in regions where cold air infi ltration may be an issue, the inside surfaces may be sheetrocked and taped for maximum air tightness.
Treatment of ceiling fi restops and wall shield
1-1/2 in.(38 mm)
To further prevent drafts, the wall shield and ceiling fi re- stops should be caulked with high temperature caulk to seal gaps. Gas line holes and other openings should be caulked with high temp caulk or stuffed with unfaced insu­lation. If the appliance is being installed on a cement slab, a layer of plywood may be placed underneath to prevent conducting cold up into the room.
C. Clearances
NOTICE: Install appliance on hard metal or wood surfaces extending full width and depth. DO NOT install directly on carpeting, vinyl, tile or any combustible material other than wood.
WARNING! Risk of Fire! Maintain specifi ed air space clearances to appliance and vent pipe:
• Insulation and other materials must be secured to prevent accidental contact.
• The chase must be properly blocked to prevent blown insulation or other combustibles from entering and making contact with fi replace or chimney.
• Failure to maintain airspace may cause overheating and a fi re.
D
Combustible flooring may be installed next to the front of the appliance.
30 in. (762 mm) to ceiling
36 in.
(914 mm)
1-1/2 in. (38 mm)
0 in. TO LEVEL
OF STANDOFFS
1/2 in. (13 mm)
Drywall
0 in.
Model #
IDV4833I
IDV6247I
Rough
Opening
(Width)
in. 47-1/2 45-1/2 30-1/2 10
mm 1207 1156 775 254
in. 61-1/2 50 30-1/2 10
mm 1562 1270 775 254
B
C
A
A
B
Rough
Opening
(Height)
C
Rough
Opening
(Depth)
D
Rough
Opening
(vent pipe)
Adjust framing dimensions for interior sheathing (such as sheetrock)
Combustible Object
Figure 5.2 Clearances to Combustibles
O in.
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/0818
Note: Wiring for and the installation of the heat zone must be done before framed enclosure is completed.
D. Mantel and Wall Projections
WARNING! Risk of Fire! Comply with all minimum clear­ances to combustibles as specifi ed. Framing or fi nishing material closer than the minimums listed must be construct­ed entirely of noncombustible materials (i.e., steel studs, concrete board, etc).
Mantels
7
6
5
13
13-3/4
14-1/2
10
1
2
10-3/4
3
11- 1/2
4
12-1/4
8
15-1/4
9
16
10
16-3/4
11
17-1/2
12
18-1/4
30 in. minimum
to ceiling
18
17
16
15
14
20-1/2
21-1/4
13
19-3/4
19
22-3/4
22
Measured from top of fireplace opening (in inches)
Figure 5.3 Minimum Vertical and Maximum Horizontal Dimensions
Mantel Legs or Wall Projections
Top o f Appliance
A
B
Drywall
A
B
Mantel Leg or
Perpendicular Wall
1 in. (25 mm) min. to perpendicular wall
7.75 in. (159 mm) min. from fireplace opening to perpendicular wall
Figure 5.4 Mantel Leg or Wall Projections (Acceptable on both sides of opening)
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/08 19
6
6
Termination Locations
A. Vent Termination Minimum Clearances
24 in. min.
(610 mm)
Termination
Cap
Storm Collar
Roof
Flashing
WARNING
Fire Risk. Maintain vent clearance to combustibles as
specifi ed.
DO NOT pack air space with insulation or other materials.
Failure to keep insulation or other materials away from vent pipe may cause overheating and fi re.
Horizontal overhang
20 in.
(508 mm)
Lowest
Discharge
Opening
12
H (min.) - Minimum height from roof to lowest discharge opening.
Vertical wall
X
Roof Pitch is X / 12
AB
6in.(minimum)upto20in.
152 mm/508 mm
20 in. and over 0 in. minimum
18 in. minimum
457 mm
Gas, Wood or Fuel Oil
Termination Cap
B
Minimum
DV = 20 in.
A *
(508 mm)
BV = 8 ft
(2.44 m)
Gas
Termination
Cap **
If using decorative cap cover(s), this distance may need to be
*
increased. Refer to the installation instructions supplied with the decorative cap cover.
In a staggered installation with both gas and wood terminations, the
**
wood termination cap must be higher than the gas termination cap.
Perpendicular Wall
Roof Pitch H (Min.) Ft. Roof Pitch H (Min.) Ft.
Flat to 6/12 1.0* Over 11/12 to 12/12 4.0 Over 6/12 to 7/12 1.25* Over 12/12 to 14/12 5.0 Over 7/12 to 8/12 1.5* Over 14/12 to 16/12 6.0 Over 8/12 to 9/12 2.0* Over 16/12 to 18/12 7.0 Over 9/12 to 10/12 2.5 Over 18/12 to 20/12 7.5 Over 10/12 to 11/12 3.25 Over 20/12 to 21/12 8.0
* 3 ft. minimum in snow regions
Figure 6.1 Minimum Height From Roof To Lowest Discharge Opening
Figure 6.2 Multiple Termination Caps
Î
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/0820
H
D
E
V
L
B
C
Fixed
V
Closed
V
F
B
V
Openable
B
V TERMINATION CAP
V
Fixed
Closed
J
A
B
X
Measure vertical clearances
from this surface
T
Measure horizontal clearances
from this surface.
Covered Alcove
Applications
Dimension Descriptions A Clearance above the ground, a veranda, porch, deck or balcony - 12 in.
(30 cm) minimum. *
B Clearance to window or door that may be opened – 10,000 BTUs or less,
6 in. (15 cm) minimum; 10,000-50,000 BTUs, 9 in. (23 cm) minimum; over 50,000 BTUs, 12 in. (30 cm) minimum. *
C Clearance to permanently closed window – 12 in. (30 cm) minimum -
recommended to prevent condensation on window.
D Vertical clearance to ventilated soffi t located above the termination within
a horizontal distance of 2 ft (60 cm) from the centerline of the termination
– 18 in. (46 cm) minimum. ** E Vertical clearance to unventilated soffi t - 12 in. (30 cm) minimum. ** F Clearance to outside corner - 6 in. (15 cm) minimum. G Clearance to inside corner - 6 in. (15 cm) minimum. H Not to be installed above a meter/regulator assembly within 3 ft (90 cm)
horizontally* from the center line of the regulator (Canada only) I Clearance to service regulator vent outlet – 3 ft (.91 m) U.S. minimum and
3 ft (.91 m) Canada minimum. * J Clearance to non-mechanical air supply inlet into building or the combustion
air inlet to any other appliance – 9” (23 cm) U.S. minimum and 12 in. (30
cm) Canada minimum. * K Clearance to mechanical air supply inlet - 3 ft (.91 m) U.S. minimum and
6 ft (1.8 m) Canada minimum. * L Clearance above a paved sidewalk or paved driveway located on public
property - 7 ft (2.1 m) minimum. A vent may not terminate directly above a sidewalk or paved driveway
which is located between two single family dwellings and serves both
dwellings. M Clearance under veranda, porch, deck or balcony - 12 in. (30 cm) minimum.
* Recommended 30 in. (76 cm) for vinyl or plastic. Only permitted if veranda, porch, deck or balcony is fully open on a
minimum of 2 sides beneath the fl oor. * N Vertical clearance between two horizontal termination caps – 12 in. (30
cm) minimum. O Horizontal clearance between two horizontal termination caps – 12 in. (30
cm) minimum.
Figure 6.3 Minimum Clearances for Termination
O
R
N
V
V
B
X
GAS METER
AIR SUPPLY INLET
Q
P
V
S
M
I
RESTRICTION ZONE (TERMINATION NOT ALLOWED)
V
V
KX
U
G
V
A
V
W
lectrical
Service
D*
V
V
U
V
Clearances to Electrical Service
P 6” - Non-vinyl sidewalls 12” – Vinyl sidewalls Q 18” – Non-vinyl soffi t and overhang 42” – Vinyl soffi t and overhang R 8 ft.
S
min
T
max
1 cap 3 ft 2 x S actual 2 caps 6 ft 1 x S actual 3 caps 9 ft 2/3 x S actual 4 caps 12 ft 1/2 x S actual
S
= # term caps x 3 T
min
= (2/# term caps) x S (actual)
max
U 6” min. – Clearance from sides of electrical service. W 12” min. – Clearance above electrical service. * As specifi ed in CGA B149 Installation Codes Note: Local codes or regulations may require different clearances. ** Clearance required to vinyl soffi t material – 30 in. (76 cm) minimum. Note: Location of the vent termination must not interfere with access to
the electrical service.
WARNING! In the U.S.: Vent system termination is NOT permitted in screened porches.
You must follow side wall, overhang and ground clearances as stated in the instructions.
In Canada: Vent system termination is NOT permitted in screened porches.
Vent system termination is permitted in porch areas with two or more sides open. You must follow all side wall, overhang and ground clearances as stated in the instructions.
Hearth & Home Technologies assumes no responsibility for the improper
performance of the appliance when the venting system does not meet these requirements.
CAUTION: IF EXTERIOR WALLS ARE FINISHED WITH VINYL SIDING, IT IS SUGGESTED THAT A VINYL PROTECTOR KIT BE INSTALLED.
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/08 21
7
7
Vent Information and Diagrams
A. Approved Pipe
This appliance is approved for use with Hearth & Home Technologies DVP venting systems. Refer to Section
16.B. for vent component information. DO NOT mix pipe, fi ttings or joining methods from differ-
ent manufacturers. The pipe is tested to be run inside an enclosed wall.
There is no requirement for inspection openings at each joint within the wall.
WARNING! Risk of Fire or Asphyxiation. This appliance requires a separate vent. DO NOT vent to a pipe serving a separate solid fuel burning appliance.
B. Vent Table Key
The abbreviations listed in this vent table key are used in the vent diagrams.
Symbol Description
First section (closest to appliance) of vertical length
V
1
Second section of vertical length
V
2
H
H
First section (closest to appliance) of horizontal length
1
Subsequent sections of horizontal length
2
C. Use of Elbows
Diagonal runs have both vertical and horizontal vent aspects when calculating the effects. Use the rise for the vertical aspect and the run for the horizontal aspect (see Figure
7.1). Two 45º elbows may be used in place of one 90º elbow.
On 45º runs, one foot of diagonal is equal to 8-1/2 in. (216 mm) horizontal run and 8-1/2 in. (216 mm) vertical run. A length of straight pipe is allowed between two 45º elbows (see Figure 7.1).
Vertical
12 in.
8-1/2 in.
Horizontal
On 45° runs, 1 ft (.3 m) of diagonal is equal to 8-1/2 in. (216 mm) horizontal run and 8-1/2 in. (216 mm) vertical run.
Figure 7.1 Using Two 45° Elbows
Effective Height/Length
Pipe
DVP4 4 102
Effective
Height/Length
DVP Pipe
(see chart)
Figure 7.2 Pipe Effective Length
DVP6 6 152 DVP12 12 305 DVP24 24 610 DVP36 36 914 DVP48 48 1219
DVP6A 3 - 6 76 - 152
DVP12A 3 - 12 76 - 305
8-1/2 in.
inches
mm
D. Measuring Standards
Vertical and horizontal measurements listed in the vent diagrams were made using the following standards.
• Pipe measurements are shown using the effective length of pipe (see Figure 7.2).
• Horizontal terminations are measured to the outside mounting surface (fl ange of termination cap) (see Figure 6.1).
• Vertical terminations are measured to bottom of termination cap.
• Horizontal pipe installed level with no rise.
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/0822
E. Vent Diagrams
To replace the fi rst starter elbow with two 45° elbows, refer to Figure 7.4. All other 90° elbows can be replaced with two 45° elbows.
General Rules:
• SUBTRACT 3 ft. from the total H measurement for each 90° elbow installed horizontally.
• SUBTRACT 1-1/2 ft. from the total H measurement for each 45° elbow installed horizontally.
• A maximum of three 90° elbows (or six 45° elbows) may be used in any vent confi guration. Some elbows may be installed horizontally. See Figure 7.9.
NOTICE: ICON direct vent appliances require the use of a vinyl soffi t shield (ICONDV-VSS) whenever the unit is terminated horizontally in a home with vinyl siding.
• Elbows may be placed back to back anywhere in the system as long as the fi rst 90° elbow is a starter elbow except as shown in Figure 7.4.
• When penetrating a combustible wall, a wall shield restop must be installed.
• When penetrating a combustible ceiling, a ceiling fi restop must be installed.
• Horizontal runs of vent do not require vertical rise; horizontal runs may be level.
1. Top Vent - Horizontal Termination
One Elbow
H
1
Figure 7.3
V
V1 min. V1 max. H1 max.
ft m ft m ft m 1 0.30 - - 25 in. 635 mm
1.5 0.46 - - 18 5.49 2 0.61 - - 25 7.62
- - 25 7.62 25 7.62
1
Î
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/08 23
1. Top Vent - Horizontal Termination - (continued)
Two 45° Elbows replacing One 90° Elbow
25 ft max.
(7.62 m)
Figure 7.4
4 ft min. (1.22 m)
Two Elbows
H
V1 min. V1 max. H1+H2 max. H1+H2+H3 max.
Note: For corner installations: A
6 in. (152 mm) section of straight pipe may need to be attached to the appliance before a 90º elbow, to allow the vent pipe to clear the top standoffs.
ft mftmftmftm
1.5 0.46 - - 18 5.49 18 5.49 2 0.61 - - 25 7.62 25 7.62
- - 25 7.62 25 7.62 25 7.62
Installed
Vertically
H
3
Installed
Horizontally
V
H
1
H
2
2
1
Figure 7.5
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/0824
1. Top Vent - Horizontal Termination - (continued)
Three Elbows
H
V1 min. V1 + V2 max. H1+H2 max.
ft m ft m ft m 1 0.30 24 7.32 19 5.79
Installed
Vertically
2
V
2
V
1
H
1
Figure 7.6
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/08 25
2. Top Vent - Vertical Termination
NOTICE: If installing a vertical vent/termination off the top of the appliance, the fl ue restrictor should be used.
No Elbow
12 ft (3.66 m) min.
60 ft (18.29 m) max.
Figure 7.7
Figure 7.7a 12 ft to 30 ft Vertical Run
Figure 7.7b 31 ft to 60 ft Vertical Run
Install Flue Restrictor
• Remove screws from fl ue (fi rebox top).
• Using the screws removed, install flue restrictor according to your installation requirements. Figures 7.7a and 7.7b.
See
Two Elbows
12 ft (3.66 m) min. 60 ft (18.29 m) max.
Maximum horizontal run is 100% of vertical, but cannot exceed 26 ft (7.92 m)
Figure 7.8
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/0826
2. Top Vent - Vertical Termination - (continued)
Three Elbows
Maximum horizontal run is 100% of vertical, but cannot exceed 26 ft (7.92 m)
Figure 7.9
12 ft (3.66 m) min. 60 ft (18.29 m) max.
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/08 27
8
8
Vent Clearances and Framing
A. Pipe Clearances to Combustibles
WARNING! Risk of Fire! Maintain air space clearance to vent. DO NOT pack insulation or other combustibles:
• Between ceiling fi restops
• Between wall shield fi restops
• Around vent system Failure to keep insulation or other material away from
vent pipe may cause over heating and fi re.
3 in.
(76 mm)
Sheetrock
2 x 4 or 2 x 6 header
Air space clearance to bottom and sides of horizontal pipe must be at least 1 in. (25 mm)
No combustible framing to be located within shaded area.
1-1/2 in. (38 mm)
WALL
B. Wall Penetration Framing
Combustible Wall Penetration
Whenever a combustible wall is penetrated, you must frame a hole for the wall shield fi restop(s). The wall shield restop maintains minimum clearances and prevents cold air infi ltration.
• The opening must be framed on all four sides using the same size framing materials as those used in the wall construction.
• SLP pipe - A wall shield fi restop must be placed on each side of an interior wall. A minimum 1 1/2 in. (38 mm) overlap of attached heat shields must be maintained.
• DVP pipe - A wall shield fi restop is required on one side only on interior walls. If your local inspector requires a wall shield fi restop on both sides, then both wall shield restops must have a heat shield attached to them.
• See Section 10.I. & 10.J. for information for regarding the installation of a horizontal termination cap.
Non-Combustible Wall Penetration
If the hole being penetrated is surrounded by noncombus­tible materials such as concrete, a hole with diameter one inch greater than the pipe is acceptable.
Whenever a non-combustible wall is penetrated, the wall shield fi restop is only required on one side and no heat shield is necessary.
Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm). The heat shield is designed to be used on a wall 4 in. to 7-1/4 in. (102 mm to 184 mm) thick. If wall thickness is less than 4 in. (102 mm) the existing heat
shields must be field trimmed. If wall thickness is greater than 7-1/4 in. (184 mm) a DVP-HSM-B will be required.
3 in. (76 mm) top clearance
1 in. (25 mm) clearance around vertical sections
Figure 8.1 Vent Pipe and Horizontal Venting Clearances To Com­bustible Materials
1 in. (25 mm)clearance
bottom & sides
Heat Shield
Wall
Shield
Firestop
WALL
3 in. (76 mm) top clearance
Heat Shield
1 in. (25 mm) clearance bottom & sides
12 in.
The center of the framing hole is 1 in. (25mm) above the center of the horizontal vent pipe.
Framing should be constructed of 2 X 4 lumber or heavier.
Appliance A
IDV4833 64-1/8 in./1629 mm IDV6247 68-5/8 in./1743 mm
Figure 8.2 Wall Penetration
10 in.
DO NOT PACK WITH
OTHER MATERIAL.
A*
* To center of pipe.
Vent framing hole.
INSULATION OR
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/0828
C. Install the Ceiling Firestop
A ceiling fi restop MUST be used between fl oors and at- tics.
• Frame an opening 10 in. by 10 in. (254 mm by 254 mm) whenever the vent penetrates a ceiling/fl oor (see Figure 8.3).
• Frame the area with the same sized lumber as used in ceiling/fl oor joist.
• The ceiling fi restop may be installed above or below the ceiling joists when installed with a attic insulation shield. It must be under joists between fl oors that are not insulated. Refer to Figure 8.4.
• Secure with three fasteners on each side.
WARNING! Risk of Fire! DO NOT pack insulation around the vent. Insulation must be kept back from the pipe to pre­vent overheating.
Attic Above
10 in. (254 mm)
10 in.
(254 mm)
Hole should measure
10 in. x 10 in.
(254 mm x 254 mm)
inside to inside
Figure 8.3 Installing Ceiling Firestop
Install attic insula­tion shields before or after installation of vent system.
3 fasteners
per side
Ceiling firestop
installed below ceiling.
Figure 8.4 Installing the Attic Shield
Ceiling firestop
installed above ceiling.
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/08 29
D. Install Attic Insulation Shield
WARNING! Fire Risk. DO NOT allow loose materials or insulation to touch vent. Hearth & Home Technologies Inc. requires the use of an attic shield.
The National Fuel Gas Code ANSI Z223.1 and NFPA 54 requires an attic shield constructed of 26 gauge minimum metal that extends at least 2 in. (51 mm) above insulation.
Attic shields must meet specifi ed clearance and be se- cured in place.
Flat Ceiling Installation
• Remove one shield from box.
NOTICE: Cut previously installed batt insulation to make room for the attic insulation shield.
• Wrap shield around pipe if pipe is already installed in area to be insulated.
• Match the three holes in each side and fasten with three screws to form a tube.
• Bend three tabs on the bottom of the shield outward to allow attachment to the ceiling fi restop.
• Bend the remaining bottom tabs inward 90° to maintain the air space between the pipe and the shield. Set the shield on the ceiling fi restop and attach to the fi restop.
• Bend all tabs inward 90° around the top of the shield. These tabs must be used to prevent blown insulation from getting between the shield and vent pipe, and to maintain air space clearance.
Bend all tabs inward 90° to maintain clearance and prevent insulation from falling inside
Figure 8.5 Attic Insulation Shield
Î
Insert 3 screws
Bend 4 tabs inward 90° to maintain clearance
Î
Vaulted Ceiling Installation
• Remove one shield from box.
NOTICE: Cut previously installed batt insulation to make room for the attic insulation shield.
• Cut the attic insulation shield (if application is for vaulted
Î
ceiling), to fi t your ceiling pitch. Snip cut edge to recreate 1 in. bend tabs all the way around the bottom.
• Wrap shield around pipe if pipe is already installed in area to be insulated.
• Match the three holes in each side and fasten with three screws to form a tube.
• Bend three tabs on the bottom of the shield outward to allow attachment to the ceiling fi restop.
• Bend the remaining bottom tabs inward 90° to maintain the air space between the pipe and the shield. Set the shield on the ceiling fi restop and attach to the restop.
• Bend all tabs inward 90° around the top of the shield. These tabs must be used to prevent blown insulation from getting between the shield and vent pipe, and to maintain air space clearance.
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/0830
9
9
Appliance Preparation
A. Secure and Level the Appliance
WARNING! Risk of Fire! Prevent contact with:
• Sagging or loose insulation
• Insulation backing or plastic
• Framing and other combustible materials Block openings into the chase to prevent entry of
blown-in insulation. Make sure insulation and other materials are secured.
DO NOT notch the framing around the appliance standoffs.
Failure to maintain air space clearance may cause overheating and fi re.
The diagram shows how to properly position and secure the appliance (see Figure 9.1). Nailing tabs are provided to secure the appliance to the framing members.
• Bend out nailing tabs on each side.
• Place the appliance into position.
• Keep nailing tabs fl ush with the framing.
• Level the appliance from side to side and front to back.
• Shim the appliance as necessary. It is acceptable to use wood shims underneath the appliance.
• Secure the appliance to the framing by using nails or screws through the nailing tabs.
• Secure the appliance to the fl oor by inserting two screws through the pilot holes at the bottom of the appliance.
Nailing Tabs
(both sides)
Figure 9.1 Proper Positioning and Securing of an Appliance
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/08 31
10
10
Install Vent Pipe
A. Assemble Vent Sections
Attach Pipe to the Firebox Assembly
Note: The end of the pipe sections with the lanced tabs will
face towards the appliance. Attach the fi rst pipe section to the starting collar:
• Lanced pipe end to the starting collar
• Inner pipe over inner collar
• Push the pipe section until all lanced tabs snap in place
• Lightly tug on pipe to confi rm it has locked.
Commercial, Multi-family (Multi-level exceeding
two stories), or High-Rise Applications
All outer pipe joints must be sealed with high temperature silicone, including the slip section that connects directly to the horizontal termination cap.
• Apply a bead of silicone sealant inside the female outer
pipe joint prior to joining sections. See Figure 10.1
• Only outer pipes need to be sealed. All unit collar, pipe,
slip section, elbow and cap outer fl ues shall be sealed in this manner, unless otherwise stated.
Figure 10.1 High Temperature Silicone Sealant
A
Lances
WARNING! Risk of Fire or Explosion! DO NOT break silicone seals on slip sections. Use care when removing termination cap from slip pipe. If slip section seals are bro­ken during removal of the termination cap, vent may leak.
Assemble Pipe Sections
Per Figure 10.2:
• Start the inner pipe on the lanced end of section A into the fl ared end of section B.
• Start the outer pipe of section A over the outer pipe of section B.
• Once both vents sections are started, push fi rmly until all lanced tabs lock into place.
• Lightly tug on the pipe to confirm the tabs have locked.
It is acceptable to use screws no longer than 1/2 in. (13 mm) to hold outer pipe sections together. If predrilling holes, DO NOT penetrate inner pipe.
For 90° and 45° elbows that are changing the vent direction from horizontal to vertical, one screw minimum should be put in the outer fl ue at the horizontal elbow joint to prevent the elbow from rotating. Use screws no longer than 1/2 in. (13 mm). If predrilling screw holes, DO NOT penetrate inner pipe.
B
Figure 10.2
Note: Make sure that the seams are not aligned to prevent
unintentional disconnection.
CORRECT
Figure 10.3
INCORRECT
Figure 10.4 Seams
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/0832
B. Assemble Slip Sections
WARNING! Risk of Fire or Asphyxiation! Overlap pipe sections at least 1 1/2 in. (38 mm). Secure slip sections with two screws which must not exceed 1/2 in. (13 mm) in length. Use the pilot holes. Pipe could separate if not properly joined.
• Slide the inner fl ue of the slip section into the inner fl ue of the pipe section and the outer fl ue of the slip section over the outer fl ue of the pipe section. See Figure 10.5.
• Slide together to the desired length.
Figure 10.5 Slip Section Pilot Holes
• Maintain a 1-1/2 in. (38 mm) overlap between the slip section and the pipe section.
• Secure the pipe and slip section with two screws no longer than 1/2 in. (13 mm), using the pilot holes in the slip section. See Figure 10.6.
C. Secure the Vent Sections
• Vertical runs of DVP pipe must be supported every 8 ft. (2.44 m) after the 25 ft. (7.62 m) maximum unsupported rise.
• Horizontal sections of vent must be supported every 5 ft. (1.52 m) with a vent support or plumber’s strap.
• Wall shield fi restops may be used to provide horizontal support.
• Vent support or plumber’s strap (spaced 120° apart) may be used for support. See Figures 10.7 and 10.8.
WARNING! Risk of Fire, Explosion or Asphyxi-
ation! Improper support may allow vent to sag and separate. Use vent run supports and connect vent sections per installation instructions. DO NOT allow vent to sag below connection point to appliance.
Figure 10.6 Screws into Slip Section
• Continue adding pipe as necessary following instructions in “Assemble Pipe Sections.”
NOTICE: If slip section is too long, the inner and outer fl ues of the slip section can be cut to the desired length.
NOTICE: When installing a vent system with an HRC termination cap, all pipe system joints shall be sealed using a high temperature silicone sealant.
Apply a bead of silicone sealant inside the female outer
pipe joint prior to joining sections.
Only outer pipes are sealed, sealing the inner fl ue is not
required.
All unit collar, pipe, slip section, elbow and cap outer fl ues
shall be sealed.
Figure 10.7 Securing Vertical Pipe Sections
Figure 10.8 Securing Horizontal Pipe Sections
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/08 33
D. Disassemble Vent Sections
• Rotate either section (see Figure 10.9) so the seams on both pipe sections are aligned as shown in Figure
10.10.
• Pull carefully to separate the pieces of pipe.
24 in. min.
(610 mm)
Termination
Cap
20 in.
(508 mm)
Lowest
Discharge
Opening
Horizontal overhang
Vertical wall
Figure 10.9 Rotate Seams for Disassembly
Figure 10.10 Align and Disassemble Vent Sections
Storm Collar
Roof
Flashing
H (min.) - Minimum height from roof to lowest discharge opening.
Roof Pitch H (Min.) Ft. Roof Pitch H (Min.) Ft.
Flat to 6/12 1.0* Over 11/12 to 12/12 4.0 Over 6/12 to 7/12 1.25* Over 12/12 to 14/12 5.0 Over 7/12 to 8/12 1.5* Over 14/12 to 16/12 6.0 Over 8/12 to 9/12 2.0* Over 16/12 to 18/12 7.0 Over 9/12 to 10/12 2.5 Over 18/12 to 20/12 7.5 Over 10/12 to 11/12 3.25 Over 20/12 to 21/12 8.0
* 3 ft. minimum in snow regions
Figure 10.11 Minimum Height From Roof To Lowest Discharge Opening
X
12
Roof Pitch is X / 12
E. Install Metal Roof Flashing
Note: Skip to Section 10.G. if using the RF4-8.
• See minimum vent heights for various pitched roofs (Figure 10.11) to determine the length of pipe to extend through the roof.
• Slide the roof fl ashing over the pipe sections extending through the roof as shown in Figure 10.12.
NOTICE: Failure to properly caulk the roof fl ashing could cause water entry.
• Caulk the gap between the roof fl ashing and the outside diameter of the pipe.
• Caulk the perimeter of the fl ashing where it contacts the roof surface. See Figure 10.12.
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/0834
Pipe
Caulk
Flashing
Figure 10.12 Install Metal Roof Flashing
F. Assemble and Install Storm Collar
CAUTION! Risk of Cuts, Abrasions or Flying Debris.
Wear protective gloves and safety glasses during installa­tion. Sheet metal edges are sharp.
• Connect both halves of the storm collar with two screws (see Figures 10.13-10.14).
• Wrap the storm collar around the exposed pipe section closest to the roof and align brackets. Insert a bolt (provided) through the brackets and tighten the nut to complete the storm collar assembly. Make sure the collar is tight against the pipe section.
• Slide the assembled storm collar down the pipe section until it rests on the roof fl ashing.
• Caulk around the top of the storm collar (see Figure
10.20).
Figure 10.13 Assembling the Storm Collar
Figure 10.14 Assembling the Storm Collar Around the Pipe
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/08 35
G. Install RF4-8
The RF4-8 may be used in place of the roof fl ashing and storm collar.
Pipe must be supported within 12 in. (305 mm) of the roofl ine using plumbers strapping or an SLP-FS when us- ing the RF4-8 Flashing. Refer to Sect. 10.C. Secure the Vent Sections.
Secure with 4 screws no longer than 1/2 in./13 mm
SLP-FS
Figure 10.15 Secure Pipe with SLP-FS
• Trim the rubber boot (using scissors or a utility knife), cutting along the marked measurement lines. See Figure
10.16. Use the 210 mm line for DVP pipe.
• Lubricate pipe or fl ue with water and slide the fl ashing down. It may be necessary to trim the top shingles around the base of the rubber boot to ensure a good t.
• Draw around fl ashing, remove.
• Apply silicone sealant to roof inside the lines (Figure 10.17)
• Lubricate pipe or fl ue with water and slide fl ashing down. Seat fi rmly in sealant. Nail roof fl ashing to the roof.
• Apply silicone sealant on the top outside of the base plate on the sides and on top edge. See Figure 10.18. Install shingles, Apply sealant at the top edge of the rubber boot. See Figure 10.19.
• We recommend that you top coat with conventional acrylic house paint to improve the appearance of your galvanized base fl ashing.
The SLP-FS shown in this photo will not be used with DVP pipe.
SLP-FS
Figure 10.17 Apply Sealant
Apply Sealant
Top & Partial Sides
Figure 10.18 Slide Flashing Down, Secure & Apply Sealant
Silicone Sealant (top of boot)
Figure 10.16 Trim Rubber Boot
Shingles Trimmed
Flashing over Shingles
Figure 10.19 Installation Complete
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/0836
Shingles over Flashing
H. Install Vertical Termination Cap
• Attach the vertical termination cap by sliding the inner collar of the cap into the inner fl ue of the pipe section while placing the outer collar of the cap over the outer ue of the pipe section.
• Secure the cap by driving three self-tapping screws (supplied) through the pilot holes in the outer collar of the cap into the outer fl ue of the pipe).
Termination Cap
Brackets/
(1 of three)
Bolts
Storm Collar
Screws
Caulk
Figure 10.20
I. Heat Shield Requirements for Horizontal Termination
WARNING! Risk of Fire! To prevent overheating and fi re, heat shields must extend through the entire wall thick­ness.
DO NOT remove the heat shields attached to the wall shield fi restop and the horizontal termination cap (shown in Figure 10.26).
• Heat shields must overlap 1-1/2 in. (38 mm) mini­mum.
There are two sections of the heat shield. One section is factory-attached to the wall shield fi restop. The other section is factory-attached to the cap. See Figure 10.26.
If the wall thickness does not allow the required 1-1/2 in. (38 mm) heat shield overlap when installed, an extended heat shield must be used.
• If the wall thickness is less than 4 in./102 mm, the heat
shields on the cap and wall shield fi restop must to be trimmed. A minimum 1-1/2 in. (38 mm) overlap MUST be maintained.
• Use an extended heat shield if the fi nished wall thickness
is greater than 7-1/4 in. (184 mm).
• The extended heat shield may need to be cut to length
maintaining suffi cient length for a 1-1/2 in. (38 mm) overlap between heat shields.
• Attach the extended heat shield to either of the existing
heat shields using the screws supplied with the extended heat shield. Refer to “Vent Components Diagrams” in the back of this manual.
• Rest the small leg on the extended heat shield on top
of the pipe section to properly space it from the pipe section.
Important Notice: Heat shields may not be fi eld constructed.
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/08 37
J. Install Horizontal Termination Cap
WARNING! Risk of Fire! The telescoping fl ue section of the termination cap MUST be used when connecting vent.
• 1-1/2 (38 mm) minimum overlap of fl ue telescoping section is required.
Failure to maintain overlap may cause overheating and re.
• Vent termination must not be recessed in the wall. Siding may be brought to the edge of the cap base.
• Flash and seal as appropriate for siding material at outside edges of cap.
• When installing a horizontal termination cap, follow the cap location guidelines as prescribed by current ANSI Z223.1 and CAN/CGA-B149 installation codes and refer to Section 6 of this manual.
CAUTION! Risk of Burns! Local codes may require installation of a cap shield to prevent anything or anyone from touching the hot cap.
NOTICE: For certain exposures which require superior resistance to wind-driven rain penetration, a fl ashing kit and HRC caps are available. When penetrating a brick wall, a brick extension kit is available for framing the brick.
Note: When using termination caps with factory-supplied heat shield attached, no additional wall shield fi restop is required on the exterior side of a combustible wall.
Heat Shield or
Extended
Wall Shield
Firestop
Inner Vent
Outer Vent
Vent depth from back of appliance to
outside surface of exterior wall
(see chart below)
Figure 10.21 Venting through the wall
Heat Shield
Slip Section
can be extended
INTERIOR
Heat Shield
1-1/2 in. (38 mm) min.
overlap
SHEATHING
Cap Specifi cation Chart (depth without using additional pipe sections)
DVP-TRAPK1
Top Vent Depth
3-1/2 to 5-3/8 in. NA 5-7/8 to 9-7/8 in. NA
IDV Series
DVP-HPC1
Top Vent Depth
3-1/2 to 5-5/8 in. NA 5-5/8 to 9-3/4 in. NA
DVP-TRAP1
Rear Vent Depth
DVP-HPC1
Rear Vent Depth
DVP-TRAPK2
Top Vent Depth
DVP-HPC2
Top Vent Depth
EXTERIOR
DVP-TRAP2
Rear Vent Depth
DVP-HPC2
Rear Vent Depth
DVP-TRAP1 can adjust 1-7/8 in. (4-3/16 to 6-1/16)
DVP-TRAP2 can adjust 4 in. (6-9/16 to 10-9/16)
DVP-HPC1 can adjust 2-1/8 in. (4-1/4 to 6-3/8)
DVP-HPC2 can adjust 4-1/8 in. (6-3/8 to 10-1/2)
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/0838
11
11
Gas Information
A. Fuel Conversion
• Make sure the appliance is compatible with available gas types.
• Conversions must be made by a qualified service technician using Hearth & Home Technologies specifi ed and approved parts.
B. Gas Pressure
• Optimum appliance performance requires proper input pressures.
• Gas line sizing requirements will be determined in ANSI Z221.3 National Fuel Gas Code in the USA and CAN/ CGA B149 in Canada.
• Pressure requirements are:
Gas Pressure Natural Gas Propane
Minimum inlet pressure 5.0 in. w.c. 11.0 in. w.c. Maximum inlet pressure 7.0 in. w.c. 14.0 in. w.c. Manifold pressure 3.5 in. w.c. 10.0 in. w.c.
WARNING! Risk of Fire or Explosion! High pressure will damage valve. Low pressure may cause explosion.
• Verify inlet pressures. Verify minimum pressures when other household gas appliances are operating.
• Install regulator upstream of valve if line pressure is greater than 1/2 psig.
C. Gas Connection
• Refer to Reference Section 16 for location of gas line access in appliance.
• Gas line may be run through knockout(s) provided.
• The gap between supply piping and gas access hole may be caulked with high temperature caulk or stuffed with non-combustible, unfaced insulation to prevent cold air infi ltration.
• Ensure that gas line does not come in contact with outer wrap of the appliance. Follow local codes.
• Pipe incoming gas line into valve compartment.
• Connect incoming gas line to the 1/2 in. (13 mm) connection on manual shutoff valve.
WARNING! Risk of Fire or Explosion! Support control when attaching pipe to prevent bending gas line.
• A small amount of air will be in the gas supply lines.
WARNING! Risk of Fire or Explosion! Gas build-up dur­ing line purge could ignite.
• Purge should be performed by qualified service technician.
• Ensure adequate ventilation.
• Ensure there are no ignition sources such as sparks or open fl ames.
Light the appliance. It will take a short time for air to purge from lines. When purging is complete the appliance will light and operate normally.
WARNING
Fire Risk. Explosion Hazard. High pressure will damage valve.
• Disconnect gas supply piping BEFORE pressure testing gas line at test pressures above 1/2 psig.
• Close the manual shutoff valve BEFORE pressure testing gas line at test pressures equal to or less than 1/2 psig.
Note: Have the gas supply line installed in accordance with local codes, if any. If not, follow ANSI 223.1. Installation should be done by a qualifi ed installer approved and/or licensed as required by the locality. (In the Commonwealth of Massachusetts installation must be performed by a licensed plumber or gas fi tter).
Note: A listed (and Commonwealth of Massachusetts approved) 1/2 in. (13 mm) T-handle manual shut-off valve and fl exible gas connector are connected to the 1/2 in. (13 mm) control valve inlet.
• If substituting for these components, please consult local codes for compliance.
WARNING! Risk of Fire, Explosion or Asphyxiation!
Check all fi ttings and connections with a non-corrosive commercially available leak-check solution. DO NOT use open fl ame. Fittings and connections could have loos- ened during shipping and handling.
WARNING! Risk of Fire! DO NOT change valve settings. This valve has been preset at the factory.
D. High Altitude Installations
NOTICE: If the heating value of the gas has been reduced, these rules do not apply. Check with your local gas utility or authorities having jurisdiction.
When installing above 2000 feet elevation:
• In the USA: Reduce burner orifi ce 4% for each 1000 feet above 2000 feet.
• In CANADA: Reduce burner orifi ce 10% for elevations between 2000 feet and 4500 feet. Above 4500 feet, consult local gas utility.
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/08 39
12
12
Electrical Information
A. Wiring Requirements
NOTICE: This appliance must be electrically wired and grounded in accordance with local codes or, in the absence of local codes, with National Electric Code
ANSI/NFPA 70-latest edition or the Canadian Electric Code CSA C22.1.
• Wire the appliance junction box to 110-120 VAC. This is required for use of optional accessories (standing pilot ignition) or proper operation of the appliance (Intellifi re ignition).
• A 110-120 VAC circuit for this product must be protected with ground-fault circuit-interrupter protection, in compliance with the applicable electrical codes, when it is installed in locations such as in bathrooms or near sinks.
• Low voltage and 110 VAC voltage cannot be shared within the same wall box.
WARNING! Risk of Shock or Explosion! DO NOT wire 110V to the valve or to the appliance wall switch. Incorrect wiring will damage controls.
B. Intellifi re Ignition System Wiring
• Wire the appliance junction box to 110 VAC for proper operation of the appliance.
WARNING! Risk of Shock or Explosion! DO NOT wire IPI controlled appliance junction box to a switched circuit. Incorrect wiring will override IPI safety lockout.
• Refer to Figure 12.1, Intellifi re Pilot Ignition (IPI) Wiring Diagram.
• This appliance is equipped with an Intellifi re control valve which operates on a 3 volt system.
• Plug the 3-volt AC transformer into the appliance junction box to supply power to the unit OR install two D cell batteries (not included) into the battery pack before use.
NOTICE: Batteries should not be placed in the battery pack while using the transformer. Remove batteries before using the transformer, and unplug the transformer before installing the batteries. Battery polarity must be correct or module damage will occur.
C. Optional Accessories Requirements
• This appliance may be used with a wall switch, wall mounted thermostat and/or a remote control.
Wiring for optional Hearth & Home Technologies ap­proved accessories should be done now to avoid re­construction. Follow instructions that come with those accessories.
D. Electrical Service and Repair
WARNING! Risk of Shock! Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
WARNING! Risk of Shock! Replace damaged wire with type 105° C rated wire. Wire must have high temperature insulation.
Optional
SPST Wall Switch
or
Optional Remote
RED
WHT
GRN*
WHT
GRN wire only for
*
use with optional wall switch WSK-MLT
Figure 12.1 Intellifi re Pilot Ignition (IPI) Wiring Diagram
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/0840
RED
Battery
Pack
+
-
-
+
Adapter
3V
BLK
RED
To
Junction
Box
BRN
Valve
Control
Box
BLK
ORG
GRN
Ignitor
ORG
Flame
Sensor
Pilot Assembly
WHT
E. Junction Box Installation
If the junction box is being wired from OUTSIDE of the appliance (preferred method):
• Remove two screws that attach junction box and bracket to appliance. See Figure 12.2.
• Feed an appropriate length of romex through plastic romex connector.
• Make necessary electrical connections.
• Attach outlet and cover plate to junction box.
• Reattach junction box and bracket to appliance with two screws.
If the junction box is being wired from the INSIDE of the appliance:
• Remove one screw that attaches access panel to column. See Figure 12.3.
• Remove two screws that attach junction box to junction box bracket. See Figure 12.4.
• Feed an appropriate length of romex through plastic romex connector.
• Reattach junction box to junction box bracket with two screws.
• Make necessary electrical connections.
• Attach outlet and cover plate to junction box.
• Reattach cover plate to column with one screw.
Figure 12.2 Remove Two Screws From Bracket
NOTICE: DO NOT wire 110 VAC to wall switch.
Figure 12.3 Remove Access Panel Screw
Figure 12.4 Remove Two Screws Holding Junction Box
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/08 41
13
13
Finishing
A. Mantel and Wall Projections
WARNING! Risk of Fire! Comply with all minimum clear­ances to combustibles as specifi ed. Framing or fi nishing material closer than the minimums listed must be construct­ed entirely of noncombustible materials (i.e., steel studs, concrete board, etc).
Mantels
30 in. minimum
to ceiling
18
17
16
21-1/4
22-3/4
22
15
14
13
12
11
10
18-1/4
9
17-1/2
8
16-3/4
7
6
5
4
13-3/4
3
11- 1/2
12-1/4
13
2
1
10-3/4
10
16
15-1/4
14-1/2
Measured from top of fireplace opening (in inches)
20-1/2
19-3/4
19
B. Facing Material
• Metal front faces may be covered with non-combustible materials only.
• Facing and/or fi nishing materials must not interfere with air fl ow through louvers, operation of louvers or doors, or access for service.
• Facing and/or fi nishing materials must never overhang into the glass opening.
• Observe all clearances when applying combustible materials.
• Seal joints between the fi nished wall and appliance top and sides using a 300 °F minimum sealant. Refer to Figure 13.3.
WARNING! Risk of Fire! DO NOT apply combustible ma­terials beyond the minimum clearances. Comply with all minimum clearances to combustibles as specifi ed in this manual. Overlapping materials could ignite and will inter­fere with proper operation of doors and louvers.
Finish wall material may be combustible - Top and Sides
B
0 in.
Figure 13.1 Minimum Vertical and Maximum Horizontal Dimen­sions
Mantel Legs or Wall Projections
Top o f Appliance
A
B
Perpendicular Wall
1 in. (25 mm) min.
A
to perpendicular wall
7.75 in. (159 mm) min.
B
from fireplace opening to perpendicular wall
Mantel Leg or
Drywall
A
0 in.
High Temperature Sealant (300° F/149° C min.)
Top and Side Seal Joint
Model A B
IDV4833 inches 44 3/8 46 1/2
mm 1127 1181
IDV6247 inches 48 7/8 60 1/2
mm 1241 1537
Figure 13.3 Noncombustible Facing Diagram
Shaded area ­noncombustible materials only
0 in.
Figure 13.2 Mantel Leg or Wall Projections (Acceptable on both sides of opening)
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/0842
C. Noncombustible Finishing Material
Finishing Material Finishing Material
X
(Finished Opening Width)
Z
Model X Y
IDV4833 inches 33 34 1/2
mm 838 876
IDV6247 inches 47 39
mm 1194 991
(Finished
Opening
Height)
(Finished Opening Width)
Figure 13.4 Finished Fireplace Opening
X
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/08 43
14
14
Appliance Setup
A. Remove Shipping Materials
Remove shipping materials from inside or underneath the rebox.
• Front refractory (three pieces) package shipped in front of glass.
• Lower decorative front face, left and right refractory shields shipped on top of front refractory box.
• Remove ember material package shipped inside the column.
B. Remove Fixed Glass Assembly
• See Section 14.J.
C. Remove Materials Shipped Inside Firebox
• Three top logs are shipped inside the fi rebox.
D. Clean the Appliance
• Clean/vacuum any sawdust that may have accumulated inside the fi rebox or underneath in the control cavity.
E. Accessories
Install approved accessories per instructions included with accessories. Contact your dealer for a list of ap-
proved accessories.
F. Heat-Zone-Gas
Install the Heat-Zone-Gas Kit before enclosing the appli­ance.
• Remove one of two square cover plates for each kit from the top of the appliance. Set the screws aside, discard the cover plate.
• Replace the cover plate with the heat zone collar from the kit. Use the three screws removed from the cover plate.
• Return to Heat-Zone-Gas instructions.
Cover Plates
G. Refractory
All refractory internal to the fi rebox comes pre-installed. See Section 14.L. for installation of bottom front and side refractories.
WARNING! Risk of Fire and Electric Shock! Use ONLY Hearth & Home Technologies-approved optional acces­sories with this appliance. Using non-listed accessories could result in a safety hazard and will void the warranty.
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/0844
H. Install the Logs
• Base logs are pre-installed.
• Place three top logs: Place slot in bottom of top log over pin in top of base log.
Align opposite end of log with white notched area in top of base log. Repeat for each top log. See Figures 12.1 through 12.6.
Figure 12.1 Placing First Top Log - IDV4833
Figure 12.4 Placing First Top Log - IDV6247
Figure 12.2 Placing Second Top Log - IDV4833
Figure 12.3 Placing Third Top Log IDV4833
Figure 12.5 Placing Second Top Log - IDV6247
Figure 12.6 Placing Third Top Log - IDV6247
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/08 45
I. Place Lava Rock and Rockwool
WARNING! Risk of Explosion! Follow rockwool placement instructions. DO NOT place rockwool directly over burner ports. Replace rockwool material annually. Improperly placed rockwool interferes with proper burner operation.
Rockwool and lava rock are shipped with this gas appli­ance
• Place rockwool on burner in front of front base log.
• Place lava rock on hearth refractory (not burner) as desired.
• See Figure 12.7.
Rockwool Lava Rock
Figure 12.7 Placement of Rockwool and Lava Rock
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/0846
J. Glass Panel Assembly
Removing/Replacing Glass Assembly
WARNING! Risk of Asphyxiation! Handle fi xed glass assembly with care. Inspect the gasket to ensure it is undamaged and inspect the glass for cracks, chips or scratches.
DO NOT strike, slam or scratch glass.
DO NOT operate replace with glass removed, cracked, broken or scratched.
Replace as a complete assembly.
• Remove three outer refractory pieces as per instructions in Section 12.L.
• Remove the lower decorative front face by removing the four screws attaching the face. See Figure 12.16.
• Remove the left and right refractory shields by removing the three screws holding each shield. See Figure
12.15.
• Remove the decorative fi rescreen mesh. Release the screen rod from the center screen support. Remove the right side of the screen rod from the horseshoe-shaped cradle. Rotate the screen rod down on the right side until there is enough clearance to remove the screen completely. See Figures 12.11-12.14.
• Release glass latches (six in IDV4833, ten in IDV6247). Lift glass frame assembly forward past the glass latches. See Figure 12.9. Slide the glass to the right (into the cavity on the right).
• Completely remove the left side of the glass from the opening before sliding the entire glass panel from the unit. See Figure 12.10.
• Reverse steps above to replace the glass assembly.
Figure 12.9 Lift Glass Frame Assembly Forward
Left
Refractory
Panel
Left
Refractory
Shield
Decorative
Screen Front
Figure 12.8 Glass Panel Assembly Removal/Replacement
Glass Frame
Assembly
Front Hearth
Refractory
Refractory
Shield
Screen
Rod
Right
Refractory
Panel
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/08 47
Latches
Right
Glass
Figure 12.10 Remove Left Side of Glass Frame First
K. Decorative Firescreen, Refractory Shields and Lower Decorative Front Face
• Install the decorative fi rescreen by fi rst inserting the left side of the screen rod into the horseshoe-shaped cradle (see Figure 12.11)
• Rotate the right side of the rod up and into the cradle on the right (see Figure 12.12).
Note: Make sure the outside screen eyelets are placed behind the left and right screen rod supports to ensure the screen is locked closed. See Figure 12.13.
• Place the center of the screen rod into the center screen rod support (see Figure 12.14).
• Install the left and right refractory shields using the three screws (see Figure 12.15).
• Install lower decorative front face (see Figure 12.16).
Figure 12.14 Place Center of Screen Rod
Figure 12.11 Place Left End of Screen Rod
Figure 12.12 Place Right End of Screen Rod
Rod Support
Figure 12.15 Install Refractory Shields
Eyelet
Figure 12.16 Install Lower Decorative Front Face
Figure 12.13 Ensure Eyelets are Outside the Rod Support
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/0848
L. Installing External Refractories
Open Refractory Package (Figure 12.17)
• 1 - LH side refractory panel
• 1 - RH side refractory panel
• 1 - Front hearth refractory panel
Notches indicate top of refractory
Right
Left
Front Hearth
Figure 12.17 Refractory Pieces
Install Side Refractories
• Locate right side refractory panel. See Figure 12.17.
• Install rod in hole in glass frame top. See Figure
12.18.
Bottom Front Hearth Refractory
• The fi rescreen must be pulled up to install the hearth refractory (Figure 12.21). Slide hearth refractory under side refractories until tight against glass. See Figure 12.22.
Figure 12.21 Move Firescreen
Insert Pin
Notch
Figure 12.18 Insert Pin into Top Frame
• Install rod with swedge (Figure 12.19) in hole in glass frame bottom. See Figure 12.20.
• Repeat for the left side refractory panel.
Swedge
Figure 12.19 Swedge
Figure 12.22 Placing Bottom Front Hearth Refractory
Insert Pin
Figure 12.20 Insert Pin into Bottom Frame
Figure 12.23 Finished Refractory Installation
Swedge
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/08 49
M. Air Shutter Setting
Air shutter settings should be adjusted by a qualifi ed installer at the time of installation. The air shutter is set at the factory for minimum vertical vent run. Adjust air shut­ter for longer vertical runs. See Figure 12.24.
• Pull the air shutter knob up to close.
• Push the air shutter knob down to open.
NOTICE: If sooting occurs, provide more air by opening the air shutter.
Closed
Open
Figure 12.24 Air Shutter Adjustment
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/0850
15
15
Troubleshooting
With proper installation, operation, and maintenance your gas appliance will provide years of trouble-free service. If you do experience a problem, this troubleshooting guide will assist a qualifi ed service technician in the diagnosis of a problem and the corrective action to be taken. This troubleshooting guide can only be used by a qualifi ed service technician. Con- tact your dealer to arrange a service call by a qualifi ed service technician.
A. Intellifi re Ignition System
Symptom Possible Cause Corrective Action
1. Pilot won’t light. The ignitor/module makes noise, but no spark.
A. Incorrect wiring. Verify “S” wire (white) for sensor and “I” wire (orange) for ignitor are
connected to correct terminals on module and pilot assembly.
B. Loose connections or electrical
shorts in the wiring.
C. Ignitor gap is too large. Verify gap of igniter to right side of pilot hood. The gap should be
D. Module. Turn ON/OFF rocker switch or wall switch to OFF position. Remove
Verify no loose connections or electrical shorts in wiring from module to pilot assembly. Verify connections underneath pilot assembly are tight; also verify connections are not grounding out to metal chassis, pilot burner, pilot enclosure, mesh screen if present, or any other metal object.
approximately .17 inch or 1/8 in. (3 mm).
ignitor wire “I” from module. Place a grounded wire about 3/16 in. (5 mm) away from “I” terminal on module. Place ON/OFF rocker switch or wall switch in ON position. If there is no spark at “I” terminal module must be replaced. If there is a spark at “I” terminal, module is fi ne. Inspect pilot assembly for shorted sparker wire or cracked insulator around electrode. Replace pilot if necessary.
2. Pilot won’t light, there is no noise or spark.
3. Pilot sparks, but Pilot will not light.
A. No power or transformer
installed incorrectly.
B. A shorted or loose connection
in wiring confi guration or wiring harness.
C. Improper wall switch wiring. Verify that 110/VAC power is “ON” to junction box.
D. Module not grounded. Verify black ground wire from module wire harness is grounded to
E. Module. Turn ON/OFF rocker switch or wall switch to OFF position. Remove
A. Gas supply. Verify that incoming gas line ball valve is “open”. Verify that inlet
B. Ignitor gap is incorrect. Verify that spark gap from ignitor to pilot hood is .17 in. or 1/8 in (3
C. Module is not grounded. Verify module is securely grounded to metal chassis of appliance.
Verify that transformer is installed and plugged into module. Check voltage of transformer under load at spade connection on module with ON/OFF switch in ON position. Acceptable readings of a good transformer are between 3.2 and 2.8 volts AC.
Remove and reinstall the wiring harness that plugs into module. Verify there is a tight fi t. Verify pilot assembly wiring to module. Remove and verify continuity of each wire in wiring harness. Replace any damaged components.
metal chassis of appliance.
ignitor wire “I” from module. Place ON/OFF rocker switch or wall switch in ON position. If there is no spark at “I” terminal module must be replaced. If there is a spark at “I” terminal, module is fi ne. Inspect pilot assembly for shorted sparker wire or cracked insulator around electrode.
pressure reading is within acceptable limits, inlet pressure must not exceed 14 in. W.C.
mm).
D. Module voltage output / Valve/
Pilot solenoid ohms readings.
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/08 51
Verify battery voltage is at least 2.7 volts. Replace batteries if voltage is below 2.7.
Intellifi re Ignition System - (continued)
Symptom Possible Cause Corrective Action
4. Pilot lights but continues to spark, and main burner will not ignite. (If the pilot continues to spark after the pilot fl ame has been lit, ame rectifi cation has not occurred.)
A. A shorted or loose connection
in fl ame sensing rod.
B. Poor fl ame rectifi cation or
contaminated fl ame sensing rod.
C. Module is not grounded. Verify module is securely grounded to metal chassis of appliance.
Verify all connections to wiring diagram in manual. Verify connections underneath pilot assembly are tight. Verify connections are not grounding out to metal chassis, pilot burner, pilot enclosure or screen if present, or any other metal object.
With fi xed glass assembly in place, verify that fl ame is engulfi ng ame sensing rod on left side of pilot hood. Flame sensing rod should glow shortly after ignition. Verify correct pilot orifi ce is installed and gas inlet is set to pressure specifi cations.
Verify that wire harness is fi rmly connected to the module.
D. Damaged pilot assembly or
contaminated fl ame sensing rod.
E. Module. Turn ON/OFF rocker switch or wall switch to OFF position. Remove
Verify that ceramic insulator around the fl ame sensing rod is not cracked, damaged, or loose. Verify connection from fl ame sensing rod to white sensor wire. Clean fl ame sensing rod with emery cloth to remove any contaminants that may have accumulated on fl ame sensing rod. Verify continuity with a multimeter with ohms set at lowest range. Replace pilot if any damage is detected.
ignitor wire “I” from module. Place ON/OFF rocker switch or wall switch in ON position. If there is no spark at “I” terminal module must be replaced. If there is a spark at “I” terminal, module is fi ne.
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/0852
16
16
Reference Materials
A. Appliance Dimension Diagram
Dimensions are actual appliance dimensions. Use for reference only. For framing dimensions and clearances refer to Section 5.
C
29-1/2 in.
749 mm
21-1/2 in.
546 mm
A
B
Electric Line
2-1/4 in. 57 mm
D
1 in.
25 mm
Gas Line
9-7/8 in. 251 mm
2 in. 51 mm
E
F
13-3/8 in. 340 mm
IDV4833I
IDV6247I
Figure 16.1 Appliance Dimensions
Î
Model # A B C D E F
in. 46-1/2 33 27-5/8 34-1/2 45-1/4 44-3/8
mm 1181 838 702 876 1149 1127
in. 60-1/2 47 41-5/8 39 49-3/4 48-7/8
mm 1537 1194 1057 991 1264 1241
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/08 53
B. Vent Components Diagrams
Effective
Height/Length
DVP Pipe
(see chart)
Assembled
Height: 24 in./610 mm
Diameter: 10 in./254 mm
DVP-AS2
Î
Effective Height/Length
Pipe
DVP4 4 102
DVP6 6 152 DVP12 12 305 DVP24 24 610 DVP36 36 914 DVP48 48 1219
DVP6A 3 - 6 76 - 152
DVP12A 3 - 12 76 - 305
inches
mm
10 in.
(254 mm)
DVP-FS
Ceiling Firestop
1 in.
(25 mm)
10-1/2 in.
(267 mm)
13-1/4 in.
(337 mm)
4-7/8 in.
(124 mm)
9-1/4 in.
(235 mm)
DVP90ST
90° Elbow
10-7/8 in. (276 mm)
DVP45
45° Elbow
11-3/8 in.
(289 mm)
7-3/8 in.
(187 mm)
1/2 in.
(13 mm) TYP
45°
1-1/4 in. (32 mm)
10 in.
(254 mm)
UP
5 in.
(127 mm)
DVP-HVS
Vent Support
Figure 16.2 DVP Vent Components
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/0854
1-1/2 in. (38 mm)
12 in.
(305 mm)
14 in.
(356 mm)
12 in.
(305 mm)
6 in.
(152 mm)
DVP-WS
Wall Shield Firestop
1 in.
(25 mm)
8 in.
(203 mm)
B. Vent Components Diagrams (continued)
31 in.
(787 mm)
13-3/4 in. (349 mm)
13-1/4 in.
(367 mm)
24-5/8 in.
(625 mm)
27-1/2 in. (698 mm)
RF6M
Roof Flashing Multi-pak
13-3/4 in. (349 mm)
BEK
Trap Cap Brick Extension
5 in.
(127 mm)
24-5/8 in.
(625 mm)
13-7/8 in. (352 mm)
13-1/4 in. (367 mm)
Roof Flashing Multi-pak
DVP-HPC Cap Brick Extension
RF12M
11-7/8 in.
(302 mm)
DVP-BEK2
(127 mm)
5 in.
DVP-TRAPFL
Flashing
26 in.
(660 mm)
DVP-HSM-B
Extended Heat Shield
7-1/8 in.
(181 mm)
(356 mm)
14 in.
11-5/8 in.
(295 mm)
5-3/4 in.
(146 mm)
13-7/8 in.
(352 mm)
12-1/8 in. (308 mm)
COOL-ADD
Cap Shield
9-1/2 in.
(241 mm)
DRC-RADIUS
Cap Shield
Figure 16.3 DVP Vent Components
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/08 55
B. Vent Components Diagrams (continued)
7-3/8 in.
(187 mm)
1-1/2 in. (38 mm)
12 in.
(305 mm)
DVP-TB1
Basement Vent Cap
7-1/4 in.
(184 mm)
5-1/4 in.
(133 mm)
Vertical Termination Cap
14 in.
(356 mm)
DVP-TVHW
12-1/2 in. (318 mm)
(High wind)
17-3/4 in. (451 mm)
(For use with IPI and DSI appliances only)
Vertical Termination Cap
PVK-80
3-7/8 in. (98 mm)
10-1/2 in. (267 mm)
DVP-TV
7-1/4 in.
1 in.
(184 mm)
(25 mm)
16-7/8 in. (429 mm)
12 in.
(305 mm)
12-1/8 in. (314 mm)
1-5/8 in. (41 mm)
High Performance Cap
Figure 16.4 DVP Vent Components
7-1/8 in.
(181 mm)
DVP-HPC
14 in.
(356 mm)
14 in.
(356 mm)
3/8 in. (10 mm)
1 in. (25 mm)
7-3/4 to 10-3/8 in.
(197 to 264 mm)
DVP-FBHT
Fire Brick Termination Cap
8-3/4 in.
(222 mm)
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/0856
B. Vent Components Diagrams (continued)
Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm). The heat shield is designed to be used on a wall 4 in. to 7-1/4 in. (102 mm to 184 mm) thick. If wall thickness is less than 4 in. (102 mm) the
existing heat shields must be field trimmed. If wall thickness is greater than 7-1/4 in. (184 mm) a DVP-HSM-B will be required.
15-1/8 in. (384 mm)
12 in.
(305 mm)
8 in.
(203 mm)
Heat
Shield
Max
Effective
Length
DVP-TRAP
Horizontal Termination Cap
Term Cap
Trap1
Trap2
Minimum
Effective Length
3-1/8 in. 4-5/8 in.
79 mm 117 mm
5-3/8 in. 9-3/8 in.
137 mm 238 mm
Effective Length
Maximum
DVP-TRAP1
DVP-TRAP2
DVP-HPC1
Figure 16.5 DVP Vent Components
DVP-TRAPK1
DVP-TRAPK2
DVP-HPC2
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/08 57
B. Vent Components Diagrams (continued)
Fillers
DVP-TRAP to DVP-HPC Side Filler Kit
15 in.
(381 mm)
Effective Length
5-3/4 to 8-3/8 in.
146 to 213 mm
5-1/2 in. 140 mm
87°
8-1/8 in.
(206 mm)
DVP-HRC-SS
8-3/8 in. 213 mm
13 in.
(330 mm)
Figure 16.6 DVP Vent Components
10-1/2 in.
267 mm
10-7/8 in.
276 mm
DVP-HRC-ZC-SS
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/0858
Î
C. Service Parts
Stocked
11/ 08
at Depot
ITEM DESCRIPTION COMMENTS PART NUMBER
in this manual may be ordered from an authorized dealer.
SRV4042-069 Y
Front Log 4042-351
Logs & Tray Assembly - For Complete Log Assembly
order both #1 items.
1
Ending Manufacturing Date: Active
Beginning Manufacturing Date: Jan. 2007
IDV4833IT, IDV4833IH
Service Parts List
Service Parts
33 in. ICON Gas Appliance - DV
IMPORTANT: THIS IS DATED INFORMATION. When requesting service or replacement
parts for your appliance please provide model number and serial number. All parts listed
Middle Log 4042-352
Back Log 4042-353
4042-072 Y
Top Left Log 4042-354
Top Middle Log 4042-355
Log/Foam Assembly - For Complete Log Assembly order
both #1 items.
1
Top Y Log 4042-356
2 Standoff Qty. 5 Reg. 31779
3 Heat Zone Cover Plate Qty. 2 Reg. 31051
4 Drywall Lip 4042-149
5 Nailing Flange Qty. 4 Reg. 31190
6 Junction Box Bracket 4042-290
7 Junction Box 21878
4042-171 / 4042-0170
8 Junction Box Cover Plate 4042-293
9 Glass Clip Support Assembly Qty. 4 Reg. 33858 Y
11 Pilot Bracket /Pilot Base
10 Glass Latch Assembly Qty. 2 Reg. 4042-047
Pilot Assembly - NG 4042-333 Y
12 Pilot Gasket 4042-325
13
4042-575
4042-341
14333B
4021-295
Mineral Wool
Lava Rock
Pilot Assembly - LP 4042-334 Y
Burner Assembly - NG 4042-053 Y
14
Burner Assembly - LP 4042-052 Y
15 Hearth Support Qty. 2 Reg. 4042-640
16 Glass/Frame Assembly 4042-037 Y
17 Refractory Shield 4042-642
3V Adapter Plug 593-593A Y
Flue Baffl e 4045-203
Installation Instructions & Owner's Manual
Lava Rock Bag Assembly
Screen Rod 4042-581
Screen Assembly 4042-583
Wall Switch Wire Assembly 4018-018 Y
Additional service part numbers appear on following page.
11/ 08
2
3
Ending Manufacturing Date: Active
Beginning Manufacturing Date: Jan. 2007
IDV4833IT, IDV4833IH
4
Service Parts
33 in. ICON Gas Appliance - DV
Service Parts Diagram
1 Log Set Assembly
5
9
10
6
8
7
11
12
14
13
15
16
17
Part number list on following page.
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/08 59
C. Service Parts (continued)
Ending Manufacturing Date: Active
Beginning Manufacturing Date: Jan. 2007
IDV4833IT, IDV4833IH
33 in. ICON Gas Appliance - DV
Service Parts
Valve Assembly Diagram/ Parts List
1
Y
Y
Y
Stocked
17
16
15
14
13
12
11
10
9
3
4
2
5
6
8
7
at Depot
Val ve - NG 750-500YVal ve - LP 750-501
Y
Threaded Orifi ce (.079) - LP 4042-319
Threaded Orifi ce (.128) - NG 4042-317
11/ 08
IPI Valve Assembly
10
8 - Front
Refractory Kit
9
Ending Manufacturing Date: Active
Beginning Manufacturing Date: Jan. 2007
IDV4833IT, IDV4833IH
Refractory Diagram / Parts List
Service Parts
33 in. ICON Gas Appliance - DV
2
1
1 Push/Pull Shutter Control 4042-321
2 Bulkhead 4042-315Y3 Brass Elbow - 3/8 Flare to 3/8 NPT 4021-045
ITEM DESCRIPTION COMMENTS PART NUMBER
IMPORTANT: THIS IS DATED INFORMATION. When requesting service or replacement
parts for your appliance please provide model number and serial number. All parts listed
in this manual may be ordered from an authorized dealer.
Stocked
at Depot
11
7
6
5
3
4 Flex Gas Line 15696Y5 On/Off valve 15697Y6
7 Battery Pack 593-594AY8 Wire Assembly 593-590AY9 Control Module 593-592
10 Brass Elbow - 3/8 MIP to 1/2 Flare 4042-314
11 Valve Bracket 4042-211
13 Bulkhead Locking Bracket 4042-289
14 Cover Plate Gasket 4042-306
15 Cover Plate 4042-239
16 Orifi ce/Cable Bracket 4042-288
12
17 Air Shutter 4042-311
11/ 08
4
3 Left Hearth Refractory 4042-408 4042-732
4 Hearth Refractory 4042-412 4042-736
5 Back Refractory Panel 4042-418 4042-742
6 Right Hearth Refractory Panel 4042-419 4042-743
7 Right Side Refractory Panel 4042-405 4042-729
8 Front Refractory Kit 4042-454 4042-754
1 Left Side Refractory Panel 4042-404 4042-728
2 Refractory Retainer Bracket (qty 3 req.) 4042-291
IDV4833 Traditional Refractory Pre GA1732717 Post GA1732717
ITEM DESCRIPTION COMMENTS PART NUMBER
IMPORTANT: THIS IS DATED INFORMATION. When requesting service or replacement
parts for your appliance please provide model number and serial number. All parts listed
in this manual may be ordered from an authorized dealer.
9 Left Front Refractory 4042-454 4042-759
11 Front Hearth Refractory 4042-466 4042-766
10 Right Front Refractory 4042-454 4042-758
1 Left Side Refractory Panel 4042-406 4042-730
2 Refractory Retainer Bracket (qty 3 req.) 4042-291
IDV4833 Herringbone Refractory Pre April 2004 Post April 2004
3 Left Hearth Refractory 4042-410 4042-734
4 Hearth Refractory 4042-412 4042-736
5 Back Refractory Panel 4042-418 4042-742
6 Right Hearth Refractory Panel 4042-419 4042-743
7 Right Side Refractory Panel 4042-407 4042-731
8 Front Refractory Kit 4042-455 4042-755
9 Left Front Refractory 4042-455 4042-763
11 Front Hearth Refractory 4042-466 4042-766
10 Right Front Refractory 4042-455 4042-762
Additional service part numbers appear on following page.
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/0860
C. Service Parts (continued)
Stocked
at Depot
10/08
ITEM DESCRIPTION COMMENTS PART NUMBER
in this manual may be ordered from an authorized dealer.
SRV4042-069 Y
Front Left Log 4042-357
Logs & Tray Assembly - For Complete Log Assembly
order both #1 items.
1
Ending Manufacturing Date: Active
Beginning Manufacturing Date: Jan. 2007
IDV6247IT, IDV6247IH
Service Parts
47 in. ICON Gas Appliance - DV
Service Parts List
IMPORTANT: THIS IS DATED INFORMATION. When requesting service or replacement
parts for your appliance please provide model number and serial number. All parts listed
Front Right Log 4042-358
Middle Left Log 4042-359
Middle Right Log 4042-360
Back Log 4042-361
4042-073 Y
Top Middle Log 4042-355
Top Y Log 4042-356
Log/Foam Assembly - For Complete Log Assembly order
both #1 items.
1
Top Left Log 4042-362
2 Standoff Qty. 5 Reg. 31779
3 Heat Zone Cover Plate Qty. 2 Reg. 31051
4 Drywall Lip 4042-150
5 Nailing Flange Qty. 4 Reg. 31190
6 Junction Box Bracket 4042-290
7 Junction Box 21878
8 Junction Box Cover Plate 4042-293
9 Glass Clip Support Assembly Qty. 8 Reg. 33858 Y
10 Glass Latch Assembly Qty. 2 Reg. 4042-047
4042-171 / 4042-0170
Pilot Assembly - NG 4042-333 Y
Pilot Assembly - LP 4042-334 Y14Burner Assembly - NG 4042-054 Y
Burner Assembly - LP 4042-055 Y
11 Pilot Bracket /Pilot Base
12 Pilot Gasket 4042-307
13
15 Hearth Support Qty. 2 Reg. 4042-629
16 Glass/Frame Assembly 4042-038 Y
4042-575
4042-341
14333B
4021-295
Mineral Wool
Lava Rock
3V Adapter Plug 593-593A Y
Flue Baffl e 4045-203
Installation Instructions & Owner's Manual
Lava Rock Bag Assembly
17 Refractory Shield 4042-631
Screen Rod 4042-580
Screen Assembly 4042-582
Wall Switch Wire Assembly 4018-018 Y
Additional service part numbers appear on following page.
10/08
2
3
Ending Manufacturing Date: Active
Beginning Manufacturing Date: Jan. 2007
IDV6247IT, IDV6247IH
4
Service Parts
47 in. ICON Gas Appliance - DV
Service Parts Diagram
6
5
9
10
8
7
11
12
14
13
1 Log Set Assembly
15
16
17
Part number list on following page.
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/08 61
C. Service Parts (continued)
Ending Manufacturing Date: Active
Beginning Manufacturing Date: Jan. 2007
IDV6247IT, IDV6247IH
Service Parts
47 in. ICON Gas Appliance - DV
Valve Assembly Diagram/ Parts List
1
Y
Y
Y
Y
Stocked
at Depot
17
16
15
14
13
12
11
10
9
3
4
2
5
6
8
7
Val ve - NG 750-500YVal ve - LP 750-501
Threaded Orifi ce (.086) - LP 4042-318
Threaded Orifi ce (.144) - NG 4042-316
10/08
IPI Valve Assembly
10
8 - Front
Refractory Kit
9
Ending Manufacturing Date: Active
Beginning Manufacturing Date: Jan. 2007
IDV6247IT, IDV6247IH
Service Parts
47 in. ICON Gas Appliance - DV
Refractory Parts Diagram
2
1
1 Push/Pull Shutter Control 4042-321
2 Bulkhead 4042-315Y3 Brass Elbow - 3/8 Flare to 3/8 NPT 4021-045
ITEM DESCRIPTION COMMENTS PART NUMBER
IMPORTANT: THIS IS DATED INFORMATION. When requesting service or replacement
parts for your appliance please provide model number and serial number. All parts listed
in this manual may be ordered from an authorized dealer.
Stocked
at Depot
11
7
6
5
3
4 Flex Gas Line 15696Y5 On/Off valve 15697Y6
7 Battery Pack 593-594AY8 Wire Assembly 593-590AY9 Control Module 593-592
10 Brass Elbow - 3/8 MIP to 1/2 Flare 4042-314
11 Valve Bracket 4042-211
12
13 Bulkhead Locking Bracket 4042-289
14 Cover Plate Gasket 4042-306
15 Cover Plate 4042-239
16 Orifi ce/Cable Bracket 4042-288
17 Air Shutter 4042-311
10/08
4
1 Left Side Refractory Panel 4042-414 4042-738
2 Refractory Retainer Bracket (qty 3 req.) 4042-291
3 Left Hearth Refractory 4042-420 4042-744
4 Hearth Refractory 4042-413 4042-737
5 Back Refractory Panel 4042-409 4042-733
6 Right Hearth Refractory Panel 4042-421 4042-745
7 Right Side Refractory Panel 4042-415 4042-739
8 Front Refractory Kit 4042-456 4042-756
IDV6247 Traditional Refractory Pre GA1732717 Post GA1732717
ITEM DESCRIPTION COMMENTS PART NUMBER
IMPORTANT: THIS IS DATED INFORMATION. When requesting service or replacement
parts for your appliance please provide model number and serial number. All parts listed
in this manual may be ordered from an authorized dealer.
9 Left Front Refractory 4042-456 4042-761
11 Front Hearth Refractory 4042-467 4042-767
10 Right Front Refractory 4042-456 4042-760
1 Left Side Refractory Panel 4042-416 4042-740
2 Refractory Retainer Bracket (qty 3 req.) 4042-291
IDV6247 Herringbone Refractory Pre April 2004 Post April 2004
3 Left Hearth Refractory 4042-420 4042-744
4 Hearth Refractory 4042-413 4042-737
5 Back Refractory Panel 4042-411 4042-735
6 Right Hearth Refractory Panel 4042-421 4042-745
7 Right Side Refractory Panel 4042-417 4042-741
8 Front Refractory Kit 4042-457 4042-757
9 Left Front Refractory 4042-457 4042-765
11 Front Hearth Refractory 4042-467 4042-767
10 Right Front Refractory 4042-457 4042-764
Additional service part numbers appear on following page.
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/0862
D. Optional Components
Part # Description
DF-PORT33-BK Portfolio black decorative front
DF-PORT33-BZ Portfolio bronze decorative front
DF-PORT47-BK Portfolio black decorative front
DF-PORT47-BZ Portfolio bronze decorative front
DF-SAL33-BK Salem black decorative front DF-SAL33-BZ Salem bronze decorative front DF-SAL47-BK Salem black decorative front DF-SAL47-BZ Salem bronze decorative front
WSK-MLT-HTL Multi-function wall switch
SMART-BATT-HTL Remote control
SMART-STAT-HTL Multi-function remote: on/off, room temp, thermostat temp. timer
DCKVP-I60 LP gas conversion kit DCKVN-I60 NG gas conversion kit
DCKVP-I100 LP gas conversion kit
DCKVN-I100 NG gas conversion kit
ICONDV-VSS ICON vinyl soffi t shield (required for horizontal venting on home with vinyl siding
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/08 63
E. Contact Information
Please contact your Heatilator dealer with any questions or concerns.
For the location of your nearest Heatilator dealer,
please visit www.heatilator.com.
- NOTES -
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
NOTICE
DO NOT DISCARD THIS MANUAL
• Important operating and maintenance instructions included.
• Read, understand and follow these instructions for safe installation and operation.
• Leave this manual with party responsible for use and operation.
This product may be covered by one or more of the following patents: (United States) 4593510, 4686807, 4766876, 4793322, 4811534, 5000162, 5016609, 5076254, 5113843, 5191877, 5218953, 5263471, 5328356, 5341794, 5347983, 5429495, 5452708, 5542407, 5601073, 5613487, 5647340, 5688568, 5762062, 5775408, 5890485, 5931661, 5941237, 5947112, 5996575, 6006743, 6019099, 6048195, 6053165, 6145502, 6170481, 6237588, 6296474, 6374822, 6413079, 6439226, 6484712, 6543698, 6550687, 6601579, 6672860, 6688302B2, 6715724B2, 6729551, 6736133, 6748940, 6748942, 6769426, 6774802, 6796302, 6840261, 6848441, 6863064, 6866205, 6869278, 6875012, 6880275, 6908039, 6919884, D320652, D445174, D462436; (Canada) 1297749, 2195264, 2225408, 2313972; (Australia) 780250, 780403, 1418504 or other U.S. and foreign patents pending.
Printed in U.S.A. - Copyright 2008
Heatilator • ICON DV-IDV Series • 4042-575 • Rev K • 11/0864
Loading...