Hearth and Home Technologies BIR50 User Manual

Page 1
O-T L
Tested and
Beaverton
Oregon USA
OMNI-Test Laboratories, Inc.
C
Hearth & Home Technologies
20802 Kensington Blvd.
Lakeville, MN 55044
Division, HON INDUSTRIES
www.heatnglo.com
NORTH STAR
EPA CERTIFIED
WOODBURNING FIREPLACE
INSTALLATION & OPERATING INSTRUCTIONS
SAVE THESE INSTRUCTIONS
Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage, bodily injury or even death. Please read entire manual before you install and use your replace.
4-03 1 480-1081
WARNING!
Page 2
North Star
EPA Certied Fireplace

TABLE OF CONTENTS

.......Installation and Draft Considerations ...................4
A. Listings and Code Approvals............................... 3
B. Description of the Fireplace System ................... 3
C. Fireplace Dimesions, Clearances & Outside Air . 5
D. Chimney Components......................................... 6
E. Pre-Installation Preparation................................. 9
F. Chimney Requirements..................................... 10
G. Installation of Fireplace ..................................... 13
H. Constructing a Chase........................................ 19
I. Operating Instructions ....................................... 21
J. Maintenance Instructions .................................. 27
Exploded View................................................... 32
Replacement Parts............................................ 33
Index ................................................................. 34
Warranty............................................................ 35
SAFETY PRECAUTIONS
1. Please read these installation instructions completely before
beginning installation procedures. Failure to follow them could cause a replace malfunction resulting in serious injury and/or property damage.
2. Contact local building or re ofcials or authorized authority about restrictions, installation inspection and permit require­ments in your area. The replace installation must comply with all local, regional, state and national codes and regulations.
3. An adequate supply of replacement combustion air from outside the house must be available to the re for the replace to operate properly.
In the event of negative pressure in the home when running
several appliances simultaneously caused by an unusually tightly sealed home, the combustion air kit supplied with your replace may not provide all the air required to support combustion. Hearth & Home Technologies is not responsible for any smoking or related problems that may result from the lack of adequate combustion air. It is the responsibility of the builder/contractor to ensure that adequate combustion air has been provided for the replace.
4. This fireplace must be installed with the HTI SL Series Chimney System.
The chimney system must always terminate outside the
building. Be sure to follow all chimney specications given in these installation instructions.
5. NEVER leave children unattended when there is a re burning in the replace.
6. This woodburning replace is built for solid wood fuel only. NEVER use gasoline, gasoline type lantern fuel, kerosene,
charcoal lighter uid, or similar liquids in this replace. Keep any flammable liquids a safe distance from the fireplace while it is in use.
7.
DO NOT use chimney cleaners or ame colorants in your replace.
8. While servicing this replace, always shut off any electricity
to the fireplace. This will prevent possible electric shock. Also, make sure the replace is completely cooled before
servicing.
9. To ensure a safe replace system and to prevent the build up of soot and creosote, inspect and clean the replace and chimney prior to use and periodically during the burning season. See page 27 for cleaning instructions.
10. DO NOT BURN GARBAGE OR FLAMMABLE FUIDS SUCH AS GASOLINE, NAPHTHA OR ENGINE OIL. Do not burn treated wood, or wood with salt (driftwood, etc.) Burning materials other than wood (including charcoal) under adverse conditions may generate carbon monoxide in the home, resulting inillness or possible death.
11. Do not connect this unit to a chimney ue already serving another appliance.
12. Comply with all minimum clearances to combustibles as shown in this manual for this appliance.
13. Build re on brick rebox oor. Do not use grates, andirons or other methods to support fuel.
14. For fur ther information refer to NFPA 211 (US) or
CAN/CSA-B365 (Canada).
WARNING!
HOT WHILE IN OPERATION AND WHEN COOLING DOWN, DO NOT TOUCH. SEVERE BURNS MAY RESULT. KEEP CHILDREN AWAY. KEEP COMBUSTI­BLE MATERIALS AND LIQUIDS HAVING FLAMMABLE VAPORS AWAY. A SAFETY BARRIER SHOULD BE INSTALLED IF CHILDREN ARE PRESENT.
WARNING!
D
o not operate without fully assembling all components.
WARNING!
Do not store wood within fireplace installation clearances or within the space required for re-fueling and ash removal.
WARNING!
Burning wet unseasoned wood can cause excessive creosote accumulation. When ignited it can cause a chimney re that may result in a serious house re.
CAUTION:
Do not expose the replace to the elements (i.e. rain, etc.) and keep the replace dry at all times. Wet insulation will produce an odor when the replace is used.
480-1081 2 4-03
Page 3
North Star
EPA Certied Fireplace

A. LISTINGS AND CODE APPROVALS

Th is fireplace system has been tested and listed in accordance with UL127 and ULC-S610-M87 standards, and has been listed by OMNI Test Laboratories, Inc., for installation and operation in the United States and Canada as described in this manual. The North Star Fireplace is approved for mobile home installations when not installed in a sleeping room and when an outside combustion air inlet is provided. The structural integrity of the mobile home oor, ceiling, and walls must be maintained. The replace must be properly grounded to the frame of the mobile home. Outside Air must be installed in a mobile home installation.
This replace has been tested and listed for use with the SL-300 Series chimney and replace components listed on page 7.
Check with your local building code agency before you begin your installation to ensure compliance with local codes, including the need for permits and follow-up inspections. Be sure local building codes do not supersede UL specications and always obtain a building permit so that insurance protection benets cannot be unexpectedly cancelled.
If you need assistance during installation, please contact your local dealer. For the number of your nearest Heat-N-Glo dealer, please call 1-888-427-3973.
B. DESCRIPTION OF THE FIREPLACE
SYSTEM
1. The replace system consists of the following:
a. Fireplace b. Firebrick c. Chimney Termination Cap d. Chimney System e. Hearth Extension f. Outside Air
2. Required Components Include:
a. Chimney Air Kit
3. Optional Components Include:
a. Fire Screen
b. Lintel Bar c. Heat Zone Kit
NOTE: Illustrations used throughout these instructions reect “typical installations” and are for design purposes only. Actual installation may vary slightly due to individual design preferences. However, minimum clearances must be maintained at all times.
The illustrations and diagrams used throughout these installation instructions are not drawn to scale.
Heat-N-Glo® is a registered trademark of Hearth & Home Technologies, Division of HON INDUSTRIES.
WARNING!
This replace and its components are designed to be installed and operated as a system. Any alteration to or substitution for items in this system, unless allowed by these installation instructions, will void the OMNI Test Laboratories, Inc., listing and may void the product warranty. It may also create a hazardous installation. Read through these instructions thoroughly before starting your installation and follow them carefully throughout your project.
Figure 3A - Typical Fireplace System
4-03 3 480-1081
Page 4
North Star
Recommended
Location
Marginal
Location
Location
Not
Recommended
Recommended
Location
Location NOT
Recommended
Cathedral Ceiling Construction
2nd Floor
Balcony
1st Floor
Multi-level Roofs
EPA Certied Fireplace
INSTALLATION AND DRAFT CONSIDERATIONS
The North Star Fireplace requires a minimum ue draft of -0.10 inches of water column on High, and -0.04 inches of water column on Low, as measured with a draft meter. Most dealers have draft meters available to measure your ue draft if you suspect a problem.
If the re is difcult to start, and smoke spills out of the door, or you nd it hard to establish and maintain a moderately high burn rate, then the ue draft is too low and corrective measures must be taken.
OUTSIDE AIR KIT INSTALLATION
The outside air kit is installed on the right hand side of the replace.
1.
Cut a 6” hole in outside wall to accommodate outside air piping.
2. Use 6” metal ex or rigid piping (not supplied) to directly connect outside air to fireplace intake. Secure with hose clamp.
3. Use the supplied termination cap with a rodent screen.
4. Seal between the wall and the pipe with silicone to prevent moisture penetration.
NOTE: A control knob allows you control of the outside air inlet. Use of outside air for combustion is required to conserve heated air within the structure and to provide make up air to keep the replace venting properly.
IMPORTANT!! OUTSIDE AIR MUST BE IN OPEN POSITION TO OPERATE FIREPLACE PROPERLY
480-1081 4 4-03
Page 5
North Star
23-1/8"
11-1/8"
9-11/16"
6-1/2"
5-7/8"
1"
Fan Electrical Access, (right side of fireplace)
See Page 10
NONCOMBUSTIBLE DECORATIVE MATERIAL
(2) HX4 MICORE FACTORY BUILT HEARTH EXTENSION (Each HX4 = 1/2" (13mm) thick)
HEARTH METAL STRIPS
GAP (SEAL WITH NONCOMBUSTIBLE SEALANT)
UP TO BOTTOM OF FASCIA
6" (152mm)
1" (51mm)
40-5/16"
31-1/8
"
37"
3-1/2"
40"
43-13/16"
EPA Certied Fireplace
FRONT VIEW
C. FIREPLACE DIMENSIONS
MINIMUM CLEARANCES TO COMBUSTIBLES
WITHIN ENCLOSURE AREA: Appliance to backwall 1” (25mm)
Appliance to sidewall 1” (25mm) Duct boots to framing 0” (0mm) Top standoffs to header 0” (0mm”)
EXPOSED SURFACES Faceplate to sidewall 16” (406mm)
Heat Zone air grills to ceiling 12”(305mm)
SIDE VIEW
TOP VIEW
MANTEL Mantel from base of replace 60” (1524mm)
Maximum mantel width 12” (305mm
CHIMNEY SECTIONS
Chimney sections at any level require a 2” (51mm) minimum air space clearance between the framing and chimney section.
1. Fireplace and Hearth Extension are ush on the oor:
Combustible ooring 20” (508mm) in front of and 8” (203mm) to either side of the fuel opening; must be insulated with non-combustible oor protection with a minimum thickness of 1” (25mm) and (“k” value = 0.43).
2. Fireplace is ush on the oor and Hearth Extension is raised to the bottom of the fascia:
Raised hearth must be constructed of non-combustible materials such as cement block or equivalent material Decorative combustible ooring on the raised hearth must be 20” (508mm) in front of and 8” (203mm) to either side of the fuel opening must be insulated with non-combustible floor protection with a minimum thickness of 1-1/2” (38mm) and (“k” value = 0.43).
3. Fireplace is recessed in the oor to the bottom of the fascia:
Combustible ooring 30” (762mm) in front of and 8” (203mm) to either side of the fuel opening ;must be insulated with non-combustible oor protection with a minimum thickness of 1” (25mm) and (“k” value = 0.43).
HEARTH EXTENSION / FLOOR PROTECTION
4-03 5 480-1081
Figure 5A - Factory Built Hearth Extension
Page 6
North Star
4"
42"
ID4
INSULATED DUCT
4
"
42"
UD4
UNINSULATED DUCT
EPA Certied Fireplace

D. CHIMNEY COMPONENTS

The following pictures show the SL-300 Series chimney and replace components which may be safely used with this replace.
Catalog No. Description
CAK4A Chimney Air Kit ID4 Insulated Duct/Outside Air UD4 Uninsulated Duct/Outside Air SL306 Chimney Section - 6” long SL312 Chimney Section - 12” long SL318 Chimney Section - 18” long SL324 Chimney Section - 24” long SL336 Chimney Seciton - 36” long SL348 Chimney Section - 48” long SL3 Chimney Stabilizer SL315 Chimney Offset/Return - 15° SL330 Chimney Offset/Return - 30° FS338 Firestop - Straight FS339 Firestop - 15° FS340 Firestop - 30° AS8 Straight Attic Insulation Shield JB877 Chimney Joint Band CB876 Chimney Bracket RF370 Roof Flashing - Flat to 6/12 Pitch RF371 Roof Flashing - 6/12 to 12/12 Pitch TR344 Round Termination Cap TR342 Round Telescoping Termination Cap ST375 Square Termination Cap TS345 Square Termination Cap CT35 Chase Top MH842 Mobile Home Thimble MH841 Mobile Home Thimble Extension, 20” HX4 MICORE Hearth Extension, 20” wide Mesh-HHT Fire Screen HHT-Template Metal Face Template HeatZone-Wood Heat Zone Kit LintelBar-HHT Lintel Bar
480-1081 6 4-03
Page 7
Chimney Sections
24"
A
8" 101/2"
Inside
Diameter
8"
Outside
Diameter
10"
A
B
14-1/2"
10-1/2"
2"
10-1/2"
12"
24-5/8"
27-3/8"
12"
31"
24-5/8"
Inside
Diameter
8"
Outside
Diameter
10"
20-3/4"
Catalog No. A B
SL306 6” 4-3/4” SL312 12” 10-3/4” SL318 18” 16-3/4” SL324 24” 22-3/4” SL336 36” 34-3/4” SL348 48” 46-3/4”
A = Actual Length B = Effective length (length of
chimney part after it has been snapped to another)
SL3 - Chimney Stabilizer
North Star
EPA Certied Fireplace
SL315-330 - Offset/Return
Firestop Spacer
Catalog No. A B
FS338 14-1/2” FS339 15° 18-3/8” FS340 30° 16-3/4”
4-03 7 480-1081
Chimney Bracket
CB876
RF370 - Roof Flashing
Flat to 6/12 Pitch
JB877
Joint Band
RF371 - Roof Flashing
6/12 to 12/12 Pitch
AS8
Straight Attic
Insulation Shield
Page 8
North Star
10-1/2"
12"
12"
5-1/4"
4"
TR342
TERMINATION CAP
TOP OF
UPPERMOST
CHIMNEY
SECTION
14-1/2"
MAX.
DISTANCE
CHASE TOP
23"
14-3/4"
17-3/4"
(8" Flue)
(10-1/2" Outer)
16-1/2"
13-1/4"
22-1/4"
23-1/2"
72" 36"
2"
10-7/8"
24-5/8"
16-5/8"
16-5/8"29"
EPA Certied Fireplace
TS345/TS345P
Square Termination Cap
ST375
Square Termination Cap
MH841
Mobile Home Thimble
Extension 20”
MH842
Mobile Home Thimble
TR344
Round Termination Cap
TR342
Round Telescoping
Termination Cap
Chase Top
480-1081 8 4-03
CT35
CAK4A
Chimney Air Kit
Page 9
North Star
88-7/8"
44-7/16"
23-5/8"
62-13/16"
42"
51"
23-1/2"
10"
As a room
divider
A
long a wall
In an exterior chase or
projecting into a garage
Across a corner
EPA Certied Fireplace

E. PRE-INSTALLATION PREPARATION

1. Fireplace Locations and Space Requirements
Several options are available to you when choosing a location for your replace. This replace may be used as a room divider, installed along a wall, across a corner or used in an exterior chase. See Figure 9A.
Locating the replace in a basement, near frequently opened doors, central heat outlets or returns, or other locations of considerable air movement can affect the performance and cause intermittent smoke spillage from the front of the replace when no outside air is used. Outside air is required for combustion. (see page 21). The North Star Fireplace comes equipped with an outside air inlet to feed combustion air from outside the home, along with an outside air termination cap. Consideration should be given to these factors before deciding on a location.
CLEARANCES!
A minimum 1” air clearance must be maintained at the back and sides of the replace assembly.
Chimney sections at any level require a 2” minimum air space clearance between the framing and chimney section.
Figure 9A - Fireplace Locations
Figures 9B and 9C show two typical installations for the outside air kit. Allowances must be made for 90° bends. Less space is required when ducting goes directly outside without forming elbows.
These are
rough
framing
dimensions
only.
Figure 9B
Installation Along a Wall or an Exterior Chase
Figure 9C
Corner Installation
WARNING! Do not draw outside air from garage spaces. Exhaust products of gasoline engines are hazardous.
Do not install outside air ducts such that the air may be drawn from attic spaces, basements or above the roong where other heating appliances or fans and chimneys exhaust or utilize air. These precautions will reduce the possibility of replace smoking or air ow reversal. The outside air inlet must remain clear of leaves, debris ice and/or snow. It must be unrestricted while unit is in use to prevent room air starvation which can cause smoke spillage and an inability to maintain a re. Smoke spillage can also set off smoke alarms.
WARNING! To prevent contact with sagging or loose insulation, the replace must not be installed against vapor barriers
or exposed insulation. Localized overheating could occur and a re could result.
4-03 9 480-1081
Page 10
North Star
43-7/8"
42"
2"
24"
14-2 w/ground
Standard wall mount with Junction Box
14-3 w/ground
WIRE NUT
WHITE
GREEN
BLACK
BLACK
RED
WHITE
Match colors to wire harness (red to red, white to white, etc) and secure with a wire nut
EPA Certied Fireplace
2. Framing the Fireplace
The North Star Fireplace will t the framed opening width of 43-7/8” tall. The nished cavity depth must be no less than 24”. Framing must extend straight up all the way to the ceiling.
Figure 10A shows a typical framing (using 2 x 4 lumber) of the replace, assuming combustible materials are used. All required clearances to combustibles around the replace must be adhered to. Any framing across the top of the replace must be above the level of the top standoffs.
CLEARANCES!
A minimum 1” air clearance must be maintained at the back and sides of the replace assembly.
Chimney sections at any level requ ire a 2” minimum air spac e clearance between the framing and chimney section.
WARNING!
Do not apply combustible nishing materials over any part of the front of this replace or a structure re may result. The metal replace face may only be covered with noncombustible materials such as ceramic tile, brick, or stone. Do not cover or block any cooling air slots.
Position mantel 60” from base of the replace
Figure 10A- Framing the Fireplace
3. Electrical Access and Wiring Diagram
NOTE: The manual override switch, rheostat speed control and cover plate are supplied. You will need to supply: 14-3 wire with ground; 14-2 wire with ground; standard wall mount junction box; wire nuts.
1. Remove outside air cover plate on the bottom
2. Thread the 14-3 with ground wire through the
3. Match colors to wire harness, (red to red, white
NOTE: Wiring for blowers must be done before framed enclosure is completed. If using a Heat Zone kit, it also must be installed before enclosure is complete.
When planning your fireplace location, the chimney construction and necessary clearances must be considered. The fireplace system and chimney components have been tested to provide exibility in construction. The following gures are the minimum distances from the base of the replace.
1. Min overall straight height 13 ft.
2. Min height with offset/return 14.5 ft.
3. Max height 50 ft.
4. Max chimney length between
480-1081 10 4-03
right side of the replace.
opening with the strain relief on the cover plate.
to white, etc) and secure with wire nuts.
an offset and return

F. CHIMNEY REQUIREMENTS

12 ft.
Figure 10B- Fan Wiring Diagram
5. Maximum distance between chimney stabilizers 35 ft.
6. Double offset/return minimum height 20 ft.
7.
Maximum unsupported chimney length between the offset and return
8.
Maximum straight unsupported chimney height above the replace
6 ft.
35 ft.
Page 11
North Star
A
B
1-1/4" OVERLAP
EPA Certied Fireplace
1. Using Offsets and Returns
a. To bypass any overhead obstructions, the chimney may be offset using a 15° or a 30° offset/return. Perform the following steps
to determine the correct chimney component combination for your particular installation.
b. An offset and return may be attached together or a chimney section(s) may be used between an offset and return.
1) Measure how far the chimney needs to be shifted to enable it to avoid the overhead obstacle. See Figure 11A, dimension
“A” to determine chimney sections required to achieve the needed shift.
2) After determining the offset dimension, refer to Table 1 and nd the “A” dimension closest to but not less than the distance of shift needed for your installation.
3) The “B” dimension that coincides with the “A” dimension represents the required vertical clearance that is needed to complete the offset and return.
4) Read across the chart and nd the number of chimney sections required and the model number of those particular chimney parts.
5) Whenever the chimney penetrates a oor/ceiling, a restop spacer must be installed.
6) The effective height of the replace assembly is measured from the base of replace to top of starter collar.
WARNING!
Do not combine offsets to create an offset greater than 30° from vertical. This may create a re hazard since the natural draft may be restricted.
Table 1 Offset Chart*
15° 30°
A B A B
1-5/8” 13-3/8” 3-7/8” 14-1/2” - - - - - --
2-7/8” 17-3/4” 6-1/4” 18-5/8” 1 - - - - --
- - 8-5/8” 22-3/4” 2 - - - - --
4-1/2” 23-5/8” 9-1/4” 23-3/4” - 1 - - - --
- - 11-5/8” 27-7/8” 1 1 - - - --
6” 29-3/8” 12-1/4” 29” - - 1 - - --
7-1/4” 34” 14-5/8” 33” - 2 - - - --
- - 15-1/4” 34-1/8” - - 2 1 - --
- - 17-5/8” 38-1/4” 1 - - 1 - -
- - 20-5/8” 43-1/2” - - - - - --
10-5/8” 46-3/4” 21-1/4” 44-5/8” - - - - 1 -
11-7/8” 51-3/8” 23-5/8” 48-3/8” 1 - - - 1 -
- - 26-5/8” 53-7/8” - - - 2 - -
13-3/4” 58-3/8” 27-1/4” 55-3/4” - - - - - -
15” 63” 29-5/8” 59” 1 - - - - 1
16-1/2” 68-3/4” 32-5/8” 64-1/4” - 1 - - - 1
18” 74-5/8” 35-5/8” 69-1/2” - - 1 - - 1
- - 38-5/8” 74-5/8” - - - 1 - 1
- - 41” 78-3/4” 1 - - 1 - 1
22-3/4” 91-7/8” 44-5/8” 85” - - - - 1 1
24” 96-1/2” 47” 89-1/8” 1 - - - 1 1
25” 103-1/2” 50-5/8” 95-1/2” - - - - - 2
SL306 SL312 SL318 SL324 SL336 SL348
Figure 11A - Chimney Offset/
Return
Example: Your “A” dimension
from Figure 11A is 14-1/2”. Using Table 1 the dimension closest to, but not less than 14-1/2” is 14-5//8” using a 30° offset/return. It is then deter­mined from the table that you would need 33” (Dimension “B”) between the offset and return. The c himney com­pone nts that bes t fit your application are two SL312s.
*Proper assembly of air cooled chimney parts result in an overlap at
chimney joints of 1-1/4”. Effective length is built into this chart.
4-03 11 480-1081
Page 12
North Star
THEN
BUT
MUST BE AT
LEAST 2 FEET
NEVER LESS THAN 3 FEET
I
F 10
FEET OR
LESS
EPA Certied Fireplace
2. Chimney Height Requirements (above roof line)
a. Major building codes specify a minimum chimney
height above the roof top. These specications are summarized in what is known as the Ten Foot Rule. This rule states:
If the horizontal distance from the side of the
chimney to the peak of the roof is 10 feet or less, the top of the chimney must be at least 2 feet above the peak of the roof, but never less than 3 feet in overall height above the highest point where it passes through the roof.
If the horizontal distance from the side of the
chimney to the peak of the roof is more than 10 feet, a chimney height reference point is established on the surface of the roof a distance of 10 feet from the side of the chimney in a horizontal plane. The top of the chimney must be at least 2 feet above this reference point, but never less than 3 feet in height above the highest point where it passes through the roof. See Figure 12A.
b. These chimney heights are necessary in the interest
of safety but do not ensure smoke-free operation. Trees, buildings, adjoining roof lines, adverse wind conditions, etc. may create a need for a taller chimney should smoking occur.
Figure 12A- Chimney Height
3. Number of Sections Required
To determine the chimney components needed to complete your particular installation, follow the steps below:
a. Determine the total vertical height of the replace
installation. This dimension is measured from the base of the replace assembly to the point where the smoke exits the termination cap.
b. Subtract the effective height of the replace assembly
from the overall height of the replace installation (measured from the base of the replace to the bottom of the termination cap).
c. Refer to Table 2 to determine what components must
be selected to complete the replace installation.
d. Determine the number of restop spacers, stabiliz-
ers, roof ashing, etc. required to complete the replace installation.
Table 2
HEIGHT OF CHIMNEY COMPONENTS
Chimney Stabilizer SL3 4-3/4” Firestop Spacers
FS338 0” FS339 0” FS340 0”
Offsets/Returns
SL315 13-3/8” SL330 14-1/2”
Roof Flashing
RF370 0 RF371 0
Chimney Sections*
SL306 4-3/4” SL312 10-3/4” SL318 16-3/4” SL324 22-3/4” SL336 34-3/4” SL348 46-3/4”
*Dimensions reect effective height.
480-1081 12 4-03
Page 13
North Star
1" OVERLAP
Metal strips 2" under edge of Fireplace and Hearth Extension and 2" on both side of fireplace opening
EPA Certied Fireplace

G. INSTALLATION OF FIREPLACE

WARNING!
Before starting, do the following:
1. Wear gloves and safety glasses for protection.
2. Keep hand tools in good condition. Sharpen cutting edges and make sure tool handles are secure.
3. Always maintain the minimum air space required to the enclosure to prevent re.
1. Positioning the Fireplace
This fireplace may be placed on either a combustible or noncombustible continuous at surface, depending on the type of installation. Follow the instructions for framing on pages 9-10 and Hearth Extension/Floor Protection Requirements under Minimum Clearances to Combustibles on page 5. Slide the fireplace into position. Be sure to provide the
minimum 1” air clearance at the sides and back of the replace assembly.
2. Placing the Protective Metal Hearth Strips
Included with your replace you will nd two metal hearth strips measuring approximately 23” x 4”. These strips are used to provide added protection where the replace and the hearth extension meet.
Slide each metal strip 2” under the front edge of the replace. The individual pieces must overlap each other by 1” minimum in the middle of the replace to provide continuous coverage of the oor. See Figure 13A. These metal strips should extend from the front and sides of the replace opening by 2”.
3. Leveling the Fireplace
L
evel the replace side-to-side and front-to-back. Shim with noncombustible material, such as sheet metal, as necessary. Secure the replace (using the pallet mounting brackets located on either side of the replace) to the oor.
Figure 13A - Positioning the Metal Strips
4. Assembling Chimney Sections
Attach either a straight chimney section or an offset to the top of the replace (depending on your installation requirement). Chimney sections are locked together by pushing downward until the top section meets the stop bead on the lower section.
The inner ue is placed to the inside of the ue section below it. The outer casing is placed outside the outer casing of the chimney section below it. See Figure 13B.
NOTE: Chimney Air Kit, Part CAK4A is required. Follow instructions supplied with the kit.
WARNING!
Carefully follow the instructions for assembly of the pipe and other parts needed to install this fireplace system. Failure to do so may result in a re, especially if combustibles are too close to the replace or chimney and air spaces are blocked, preventing the free movement of cooling air.
4-03 13 480-1081
Figure 13B-Assembling Chimney Sections
CAUTION:
Inner ue and outer liner sections cannot be disassembled once locked together. Plan ahead to ensure the proper installation height is achieved with the selected chimney components.
Page 14
North Star
ROOM ABOVE
A
TTIC ABOVE
24"
AS8 ATTIC INSULATION SHIELD
FS338 FIRESTOP SPACER
CHIMNEY
IN
SULATION
10-1/2"
14-1/2"
EPA Certied Fireplace
5. Installing Firestop Spacers
Mark and cut out an opening in the ceiling for the restop spacer being utilized (14-1/2” x 14-1/2” for an FS338, 14-1/2” x 18-3/8” for an FS339 and 14-1/2” x 23” for an FS340). Frame the opening with the same dimension lumber used in the ceiling joists.
Install the restop spacer.
These restop spacers are designed to provide the minimum 2” air space required around the chimney. In all situations, the restop spacers are to be nailed to the ceiling joists from the bottom or replace side, EXCEPT when the space above is an insulated ceiling or attic space. In this situation, the restop spacer must be nailed from the top side to prevent loose insulation from falling into the required 2” air space around the chimney. See Figure 14A.
6. Attic Insulation Shield
An insulation shield should be installed when there is a possibility of insulation coming into contact with the factory built chimney system. The insulation shield is installed by positioning it over the vertical chimney section where it penetrates a restop spacer. The restop spacer will support the insulation shield. See Figure 14B.
7. Double-checking the Chimney Assembly
Continue assembling the chimney sections up through the restop spacers as needed. While doing so, be aware of the height and unsupported chimney length limitations that are given on page 10 under “Chimney Requirements”.
Check each section by pulling up slightly from the top to ensure proper engagement before installing the succeeding sections. If they have been connected correctly, they will not disengage when tested.
CAUTION:
Firestop spacers must be used whenever the chimney penetrates a ceiling/oor area.
Figure 14A
Installing the Firestop Spacer
Figure 14B
Installing an Attic Insulation Shield
480-1081 14 4-03
NOTE: Wiring for blowers must be done before framed enclosure is completed. If using a Heat Zone kit, it also must be installed before enclosure is complete.
Page 15
North Star
CHIMNEY
FLASHING PLATE
JOISTS
NAIL
THIMBLE
FLASHING
FLASHING
CHIMNEY
FLASHING PLATE
NAIL
THIMBLE
SCREW
THIMBLE EXTENSION
EPA Certied Fireplace
8. Mobile home installation
You must use the outside air termnination cap supplied with your North Star Fireplace for installation in a mobile home. If you use an alternative material it must be designed to prevent material from dropping into the area beneath the mobile home, and to prevent rodents from enterting from the outside.
1. An outside air inlet must be provided for combustion and must remain clear of leaves, debris, ice and/or snow. It must be unrestricted while unit is in use to prevent room air starvation which can cause smoke spillage and an inability to maintain a re. Smoke spillage can also set off smoke alarms.
2. The replace is to be secured to the mobile home structure.
Use same holes that attached the replace to the pallet to secure it to the oor use 1/4” x 2” lag bolts or equivalent.
3. Unit must be grounded with #8 solid copper grounding wire or
equivalent and terminated at each end with N.E.C. approved grounding device.
4.
Refer to Minimum Clearances to Combustibles on page 5 and chimney components on pages 6-8.
5. Floor protections requirements on page 17 must be followed
precisely.
6. Use silicone to create an effective vapor barrier at the location
where the chimney or other component penetrates to the exterior of the structure.
7.
Follow the chimney and chimney connector manufacturer’s instructions when installing the ue system for use in a mobile home.
9. SL-300 Series MH842 Celing/Roof Thimble
1. Locate the point where the chimney will exit the roof by plumbing down to the center of the chimney. Lay out, cut and frame a 14-1/2” square opening (measured on the horizontal) through the ceiling and roof structure. See Chapter 25 of the
Uniform Building Code for Framing Details.
2. The thimble must extend completely through the roof structure shielding combustible materials. Five location holes have been provided to allow for a variety of ceiling/roof thicknesses. The MH841 Thimble Extension is required when the ceiling/roof thickness exceeds 12-1/2”. The extension should overlap the thimble one inch.
3. To attach the extension to the thimble, drill 1/8” holes through the outer shield of the thimble using the predrilled holes in the extension as guides. Attach the extension to the thimble using the screws provided with the extension.
4. Install the thimble assembly and nail it securely to the framing members.
5. Center the ashing over the chimney and nail it to the roof using the Stormguard nails provided. Keep gaps between the ashing plate and the roof to a minimum.
6. Caulk the flashing plate and roof junction as well as the vertical seam on the ashing. All nail heads must be caulked with a roong sealant.
7. Finish assembling the chimney storm collar and termination cap following the installation instructions provided with them.
NOTE: Top sections of chimney must be removable to allow
maximum clearance of 13.5’ (411cm) from ground level for transportation purposes.
8. Burn wood only. Other types of fuels may generate poisonous gases (e.g., carbon monoxide).
WARNING!
NEVER DRAW COMBUSTION AIR FROM A WALL, FLOOR OR CEILING CAVITY OR FROM ANY ENCLOSED SPACE SUCH AS AN ATTIC OR GARAGE.
WARNING!
DO NOT INSTALL IN SLEEPING ROOM.
CAUTION:
The structural integrity of the mobile home oor, wall and ceiling/roof must be maintaned. (i.e., Do not cut through oor joist, wall stud, ceiling truss, etc.)
Figure 15A - Installing an MH842, Conguration 1
Figure 15A - Installing an MH842, Conguration 2
4-03 15 480-1081
Page 16
North Star
FIRESTOP
JOINT BAND (OPTIONAL)
STRAPS
OPTIONAL ADDITIONAL SUPPORT
NAIL
FLASHING PLATE
CHIMNEY
THIMBLE EXTENSION
SCREW
FLASHING
THIMBLE
A
DJUSTABLE EXTENSION HOLES
EPA Certied Fireplace
9. SL-300 MH842 Celing/Roof Thimble (Cont’d)
Figure 16A - Installing an MH842 Conguration 3
10 Securing the Chimney System
When offsets and returns are joined to straight pipe sections, they must be locked into position with the screws provided (outer only), using the predrilled holes. To prevent gravity from pulling the chimney sections apart, the returns and the chimney stabilizers have straps for securing these parts to joists or rafters. See Figure 16B.
11.Marking the Exit Point of the Roof
Locate the point where the chimney will exit the roof by plumbing down to the center of the chimney. Drive a nail up through the roof to mark the center. See Figure 16C.
12.Cutting out the Hole in the Roof
Measur e to either side of the nail 7-1/4” a nd mark the 14-1/2” x 14-1/2” opening required. This is measured on the horizontal; actual length may be larger depending on the pitch of the roof. Cut out and frame the opening. See Chapter 25 of the Uniform Building Code for Roof Framing Details.
Be sure to maintain a 2” minimum air space between the chimney section and the roof.
13.Assembling the Chimney Sections Through the Roof
Continue to add chimney sections through the roof opening, maintaining at least a 2” air space.
NOTE: You must provide support for the pipe during construction and check to be sure inadvertent loading has not dislodged the chimney section from the replace or at any chimney joint.
Figure 16B - Offset/Return with Stabilizer
Maintain a minimum of 2” air clearance to all parts of the chimney system at all times! Failure to maintain this 2” air
clearance will cause a structure re.
WARNING!
Figure 16C - Ceiling/Attic Construction
WARNING!
When chimney sections exceeding six feet in length are installed between an offset and return, structural support must be provided to reduce off-center loading and prevent chimney sections from separating at the chimney joints.
480-1081 16 4-03
Page 17
North Star
NONCOMBUSTIBLE DECORATIVE MATERIAL
(2) HX4 MICORE FACTORY BUILT HEARTH EXTENSION (Each HX4 = 1/2" (13mm) thick)
HEARTH METAL STRIPS
GAP (SEAL WITH NONCOMBUSTIBLE SEALANT)
UP TO BOTTOM OF FASCIA
6" (152mm)
1" (51mm)
20"
8" from each side of fuel loading door
41"
EPA Certied Fireplace
14.Installing the Roof Flashing
If a roof ashing is to be used, install the roof ashing
appropriate to the roof pitch and install a round termination
A minimum 1” air clearance must be maintained at the back and sides of the replace assembly.
CLEARANCES!
cap following the instructions shipped with the cap.
For chase installations you can use a round termination cap (TR344), a round telescoping termination cap (TR342) or a square termination cap (ST375). A chase installation
Chimney sections at any level require a 2” minimum air space clearance between the framing and chimney section.
must use a chase top. Chase tops are available from your dealer. See page 19 for building a chase.
NOTE: Use only a noncombustible material to nish the face of the replace below the level of the front standoffs.
15.Completion of the Enclosure
Complete the fireplace enclosure, allowing space for outside air ducts. Electrical wiring should not come in
A noncombustible material such as USG MICORE CV230 Mineral Fiber Board, or USG DUROCK Cement Board is recommended for this purpose.
contact with the replace. A minimum clearance of 1”
must be maintained between the replace sides and back and the enclosure. See pages 9-10 for framing
details.
16.Hearth Extension
A hearth extension must be installed with all replaces to protect the combustible oor in front of the replace from both radiant heat and sparks.
The construction of, and materials used for a hearth extension are shown in Figures 17A and 17B. A hearth extension of this construction may be covered with any noncombustible decorative material and may have a maximum thickness as per the illustration. Seal gaps between the hearth extension and the front of the replace with a bead of noncombustible sealant.
Figure 17A-Field Construction Hearth Extensions
1. Hearth Extension & Floor Protection ush on the oor.
Combustible ooring 20” in front of and 8” to either side of the fuel opening; must be insulated with non-combustible oor protection with a minimum thickness of 1” (“k” value = 0.43). Use Alternate Material Worksheet on page 18 to determine the “k” value of the alternative material..
2. Fireplace is ush on the oor and Hearth Extension is raised to the bottom of the fascia:
Raised hearth must be constructed of non-combustible materials such as cement block or equivalent material Decorative combustible ooring on the raised hearth must be 20” (508mm) in front of and 8” (203mm) to either side of the fuel opening must be insulated with non-combustible oor protection with a minimum thickness of 1-1/2” (38mm) and (“k” value = 0.43).
3. Fireplace is recessed in the oor to the bottom of the fascia:
Combustible ooring 30” (762mm) in front of and 8” (203mm) to either side of the fuel opening; must be insulated with non-combustible oor protection with a minimum thickness of 1” (25mm) and (“k” value = 0.43).
4-03 17 480-1081
Figure 17B - Factory Built Hearth Extension
Page 18
North Star
Seal with non­combustible sealant
=
1
.84
R =
x T
1 k
x 0.75 = 0.893
R
brick
= 0.2 x 4 = 0.431
4" brick of r = 0.2, therefore:
1/8" mineral board of k = 0.29, therefore:
R
mineral board
=
1
0.29
x 0.125 = 0.431
R
total
= R
brick
+ R
mineral board
= 0.8 + 0.431 = 1.231
1
k
Btu(in)
ft2(hr)(oF)
= K x 12
(ft2)(hr)(oF)
Btu
k =
K =
r =
(ft2)(hr)(oF)
(Btu)(in)
=
Btu(ft)
ft2(hr)(oF)
R =
x T
1 k
R =
x T
1
K x 12
EPA Certied Fireplace
17. Alternate materials worksheet
How to determine if alternate oor protection materials are acceptable:
All oor protection must be non-combustible (i.e., metals, brick, stone, mineral ber boards, etc.). Any organic materials (i.e., plastics, wood paper products, etc.) are combustible and must not be used. The oor protection specied includes some form of thermal designation such as R-value (thermal resistance) or k-factor (thermal conductivity).
PROCEDURE:
1. Convert specication to R-value:
R-value given - no conversion needed.
k-factor is given with a required thickness (T) in inches:
2. Determine the R-value of the proposed alternate oor protector.
i. Use the formula in step (1) to convert values not expressed as “R”.
ii. For multiple layers, add R-values of each layer to determine overall R-value.
3. If the overall R-value of the system is greater than the R-value of the specied oor protector, the alternate is acceptable.
EXAMPLE: The specied oor protector should be 3/4 inch thick material with a k-factor of 0.84. The proposed alternate is 4” brick with an r-factor
Step (a): Use formula above to convert specication to R-value.
Step (b): Calculate R of proposed system.
Step (c): Compare proposed system R
is acceptable.
DEFINITIONS
of 0.2 over 1/8” mineral board with a k-factor of 0.29.
of 1.231 to specified R of 0.893. Since proposed system R
total
K-factor is given with a required thickness (T) in inches:
r-factor is given with a required thickness (T) in inches: R = r x T
is greater than required, the system
total
18. Position the Hearth Extension
Position and secure the hearth extension over the protective metal strips that have been placed partially under the fireplace front. These stri ps should be protruding approximately 2” from under the replace front and 2” on both sides of the replace opening. See Figure 13A on page 13. Seal the crack between
the hearth extension and replace with a bead of noncombustible sealant. See Figure 18A. Apply a
noncombustible nishing material of your choice to the hearth extension.
NOTE: BUSTILES, HEARTH EXTENSIONS / FLOOR PROTEC­TION” FOR CLEARANCES REQUIRED FOR DIFFER­ENT HEARTH EXTENSION INSTALLATIONS. THE CLEARANCES MUST BE STRICTLY ADHERED TO.
SEE PAGE 5 “CL EARA NCES TO COM-
Hearth extensions are to be installed only as illustrated to prevent high temperatures from occurring on concealed combustible materials. Hearth sealing strips prevent burning or hot particles from inadvertently falling directly on combustible surfaces in the event the building should settle and disturb the original construction.
480-1081 18 4-03
WARNING!
Figure 18A - Position the Hearth Extension
Page 19
North Star
1 2 3
EPA Certied Fireplace
19. Finishing Material
Do not install combustible materials over the front of the replace! This poses a safety hazard and may start a re. You may only use noncombustible material
over the front of the replace.
a. Combustible Material
Material which is made of or surfaced with wood,
compressed paper, plant bers, plastics, or any material capable of igniting and burning, whether ame proofed or not, plastered or unplastered.
b. Noncombustible Material
Material whic h wil l not ignite and burn . Such
materials are those consisting entirely of steel, iron, brick, tile, concrete, slate, glass or plasters, or any combination thereof.
c. Noncombustible Sealant Material
Sealants which will not ignite and burn; General
Electric RTV103 Black (or equivalent), Rutland, Inc. Fireplace Mortar #63 (or equivalent).
After completing the framing and applying the facing
material (dry wall) over the framing, a 1/2” wide (maximum) bead of noncombustible sealant must be used to close off any gaps at the top and sides between the replace and facing to prevent cold air leaks.
Only noncombustible materials may be used to
cover the metal replace front.
d. Cardboard OR Metal Template
A cardboard template of the front is printed on the
outside of the shipping box. It measures 1/8” bigger all the way around than the actual front. Cut out the template for use in your installation.
A metal template is also available for more durable
co nti nue d use remaining accurat e over tim e. The part number for this metal template is HHT­Template.
21. Mantel
A combustible mantel may be positioned no lower than 60” from base of the replace. The combustible mantel may have a maximum depth of 12”. Combustible trim pieces that project no more than 1-1/2” from the face of the replace can be placed no closer than 6” from the side of the replace decorative front. Combustible trim must not cover the metal surfaces of the replace. This mantel clearance is in accordance with Section 7-3.3.3
of ANSI/NFPA211.

H. CONSTRUCTING A CHASE

A chase is a vertical boxlike enclosure built around the chimney and replace. A chase may be constructed for the replace and chimney or for the chimney only. It is most commonly constructed on an outside wall.
In cold climates, it is recommended that the chase oor be insulated using batt type insulation between the oor joists.
Three examples of chase applications are shown in Figure 19A.
1. Fireplace and chimney enclosed in an exterior chase.
2. Chimney offset through exterior wall and enclosed in chase.
3. Chase constructed on roof.
Figure 19A - Chase Constructions
1. Materials
a. The chase is constructed using framing materials
much the same as the walls in your home. A variety of siding materials may be used including brick, stone, veneer brick, or standard siding materials.
b. In constructing the chase, several factors must
be considered:
1) Maintain a 2” air space around the chimney.
2) The chase top must be constructed of noncom-
bustible material.
3) In cold climates, a restop spacer should be installed in an insulated false ceiling at the 8’ level above the replace assembly. This reduces heat loss through the chase.
4) In cold climates, the walls of the chase should be insulated to the level of the false ceiling as shown in Figure 20A on page 20. This will help reduce heat loss from the home around the replace.
4-03 19 480-1081
Page 20
North Star
Storm Collar
Chase Flashing
6" min
2" min
2" min
Storm Collar
Chase Flashing
2" min
14-1/2" max
Top of uppermost chimney section
Cap standoff
Top of pipe
2" min from chase top to top of chase flashing
4-1/2" max
Chase flashing
Chase flashing
Top of pipe
2" min from chase top to top of chase flashing
3" max
FIRESTOP
SPACER
METAL CHASE TOP
ROUND TERMINATION CAP
(TR342/TR344)
FALSE
CEILING
EPA Certied Fireplace
2. Chase Top
Construct a chase of desired materials main­taining a minimum 2” air space around the chimney.
3. Termination Cap
a. Install the chimney sections up through
the chase enclosure. When using a TR344 round termination cap, the uppermost top section of pipe must extend 6” above the top of the chase collar to allow installation of the storm collar and termination cap. See Figure 20B.
b. For installations utilizing a TR342 telescop-
ing round termination cap, the uppermost chimney section must be below the top of the chase top, but not more than 14-1/2” below the top of the chase top flashing collar. See Figure 20C.
c. For installations utilizing an ST375 square
termination cap the last chimney section must not be more than 4-1/2” below the chase top. See Figure 20D.
d. For installation utilizing a TS345/TS345P
Square Termination Cap, the uppermost chimney section must not be more than 3” below the chase top. See Figure 20E.
e. Attach the chase top (CT35) to the top of
the chase.
f. Install the termination cap, following the
instructions provided with it.
NEED NEW DRAWING
Figure 20B - Installing a
TR344 Round Termination
Cap
Figure 20D - Installing an
ST375 Square Termination
Cap
Figure 20C - Installing a
TR342 Round Telescoping
Termination Cap
Figure 20E - Installing
a TS345/TS345P Square
Termination Cap
480-1081 20 4-03
Figure 20A - Chase Assembly
WARNING!
Never install a single wall slip section or smoke­pipe in a chase structure. The higher temperature of this single wall pipe may radiate sufcient heat to combustible chase materials to cause a re.
WARNING!
Detailed instructions for installation of the chase top, storm collar and termination cap are packaged with these parts. To avoid danger of re, all instructions must be strictly followed, including the provision of air space clearance between chimney system and enclosure. To protect against the effects of corrosion on those parts exposed to the weather, we recommend that the chase top be painted with a rust-resistant paint.
Page 21
North Star
EPA Certied Fireplace

I. OPERATING INSTRUCTIONS

IMPORTANT! PLEASE READ BEFORE USING FIREPLACE
NOTE: Save and pass this instruction manual to subsequent home owners. The information provided is intended
to notify and warn them about making unsafe future modifications such as the addition of shelves or the use of unauthorized parts and repairs.
1. General Information
In recent years there has been an increasing concern about air quality. Much of the blame for poor air quality has been placed on the burning of wood for home heating. These replaces, like any other appliances, must be properly operated in order to ensure that they perform the way they are designed to perform.
Fireplaces, as well as other woodburning appliances, have been used safely for many years. It has been our experience that most problems are caused by improper installation and operation of the replace. Make certain that installation and operation of the replace system is in accordance with these instructions.
It is reco mmended that an annual insp ection be performed on the replace system to determine if the ue system needs to be cleaned, or as in the case of any appliance, if minor repairs are required to maintain the system in top operating condition before the heating season begins.
This factory-built replace is intended for use with solid fuel (rewood).
2. Outside Air
A source of air (oxygen) is required in order for combus­tion to take place. Whatever air is consumed by the re must be replaced through cracks around windows, under doors, etc. Most newly constructed houses or existing homes tted with tightly sealed doors and windows are relatively air tight. The Nor th Star Fireplace comes equipped with an outside air intake to feed combustion air from outside the home, along with an outside air termination cap. The 6” solid/ex pipe is not supplied.
Outside air is required to minimize the effects of negative pressure within the structure. It is recommended to utilize the shortest duct run to optimize the performance of the Outside Air Kit. The outside air inlet thimble should be positioned above the ground level, and must remain clear of leaves, debris, ice and/or snow. If you live in an area that experiences deep snow levels, this must be taken into consideration when determining the height placement above ground level. It must be unrestricted while unit is in use to prevent room air starvation which can cause smoke spillage and an inability to maintain a re. Smoke spillage can also set off smoke alarms.
This replace will operate correctly only if adequate
WARNING!
THIS FIREPLACE HAS NOT BEEN TESTED WITH ANY VENTED OR UNVENTED GAS LOT SET. TO REDUCE RISK OF FIRE OR INJURY, DO NOT INSTALL A VENTED OR UNVENTED GAS LOG SET INTO FIREPLACE.
WARNING!
ALWAYS OPERATE THIS APPLIANCE WITH THE DOOR CLOSED AND LATCHED EXCEPT DURING START-UP AND RE-FUELING OR WHEN USING THE FIRESCREEN.
ventilation is provided to allow proper draft to the replace system. Hearth & Home Technologies assumes no responsibility for the improper performance of the replace system caused by inadequate draft due to environmental conditions, down drafts, tight sealing construction of the structure, or mechanical exhausting devices which create a negative air pressure within the structure where the replace is located.
IMPORTANT!
WARNING!
DO NOT LEAVE THE FIRE UNATTENDED WHEN THE DOOR IS UNLATCHED OR WHEN USING THE FIRESCREEN. UNSTABLE FIREWOOD COULD FALL OUT OF THE FIRE­BOX CREATING A FIRE HAZARD TO YOUR HOME.
4-03 21 480-1081
OUTSIDE AIR MUST BE IN OPEN
POSITION TO OPERATE FIREPLACE
PROPERLY.
Page 22
North Star
Slide Air Control
Left-Close Right-Open
CLOSE
OPEN
Outside Air Knob
Low
Position
Meet
Resistance
ACC Fully
Engaged
EPA Certied Fireplace
3. Burning Process
Fire requires three things to burn: fuel, air and heat. So, if heat is robbed from the replace during the drying stage, the new load of wood has reduced the chances for a good clean burn. For this reason, it is always best to burn dry, seasoned rewood. We do not advise bur ning unseasoned wood, however if it happens, you must open the Slide Air Control and burn the fireplace at a high burn setting for a longer time to start it burning.
Kindling or 1st stage:
It helps to know a little about the actual process of burning in order to understand what goes on inside a replace. The rst stage of burning is called the kindling stage. In this stage, the wood is heated to a temperature high enough to evaporate the moisture which is present in all wood. The wood will reach the boiling point of water (212°F) and will not get any hotter until the water is evaporated. This process takes heat from the coals and tends to cool the replace.
2nd stage:
The next stage of burning, the secondary stage, is the period when the wood gives off ammable gases which burn above the fuel with bright flames. During this stage of burning it is very important that the ames be maintained and not allowed to go out. This will ensure the cleanest possible re. If you are adjusting your replace for a low burn rate, you should close down the air to the point where you can still maintain some ame. If the ames tend to go out, the replace is set too low for your burning conditions.
CAUTION:
Fireplace operation does require air. Do not take air from other fuel burning appliances which can result in improper venting (smoking) or air dilution. Always provide adequate makeup air.
4. Air Control
The air enters at the upper front of the rebox, near the top of the glass door. This preheated air supplies the necessary fresh oxygen to mix with the unburned gases. This air is regulated by the Slide Air Control. For more air - slide the control to the right, for less air
- slide the control to the left.
5. Automatic Combustion Control
Typically, when you build a fire, you need to open
the controls to give the re more air so the wood will get going. You then have to go back to the unit and shut it down so it doesn’t overre and burn up your wood too quickly.
With the Automatic Combustion Control system, you can set the replace to high (all the way to the right), start your re, and then move the Slide Air Control to their desired burn level. The replace will automatically go to that level after the re is fully established. This allows for less interaction with the re by the homeowner and more efcient use of fuel while maintaining the desired heat output.
IMPORTANT! As you move the control rod to the
right, about three-four ths of the way you will feel some resistance. You must move past that resistance approximately 3/4” to fully engage the Autom atic Combustion Control (ACC) sytstem
Final stage:
The nal stage of burning is the charcoal stage. This occurs when the ammable gases have been mostly burned and only charcoal remains. This is a naturally clean por tion of the burn. The coals burn with hot blue ames.
It is very important to reload your replace while enough lively hot coals remain in order to provide the amount of heat needed to dry and rekindle the next load of wood. It is best to open the air control for a short while before reloading. This livens up the coalbed. Open door slowly so that ash or smoke does not exit replace through opening. You should also break up any large chunks and distribute the coals so that the new wood is laid evenly on hot coals.
480-1081 22 4-03
Page 23
North Star
EPA Certied Fireplace
6. Burning Guidelines
For maximum operating efciency with the lowest emissions, follow these operating procedures:
1. Regardless of desired heat output, when loading the replace, burn your replace with the Slide Air Control wide open (fully to the right) for a minimum of 5 to 15 minutes.
2. Regulate burn rate (heat output) by using the Slide Air Control. See page 22.
3. Heat output settings: Following 5 to 15 minutes of burning with the control wide open (see #1
above):
BTU / Hr
Below 10,000 10,000 - 15,000 15,000 - 30,000 Maximum Heat
*These are approximate settings, and will vary with
type of wood or chimney draft.
NOTE: BURN DRY, WELL-SEASONED WOOD.
*Slide Control
Slide LEFT to Stop Stop to 1/8” -1/2” open 1/2” - 1-1/2” open Fully open
7. Fan Operating Instructions
Instructions with override switch in manual position.
8. Heat Zone Operating Instructions
The Heat-Zone accessory kit conveys warm air from the replace through air duct(s) to remote locations in the same room or other rooms of the building. One or two Heat-Zone kits can be installed on the replace. Follow the instructions that is supplied with the kit. Installation of this kit MUST be performed by a qualied service technician. If any parts are missing or damaged, contact your local Dealer before starting installation. DO NOT install a damaged kit.
The Heat-Zone kit is carefully engineered and must be installed only as specied. If you modify it or any of its components, you will void the warranty and you may possibly cause a re hazard. Installation must be done according to applicable local, state, provincial, and/or national codes.
9. Operation of Fireplace with Optional Fire Screen Instructions
CAUTION:
THE FIRESCREEN MAY BECOME EXTREMELY HOT WHILE IN USE. ALWAYS WEAR GLOVES TO PREVENT INJURY.
1. Initial (cold) startup: Leave fan off until your re­place is hot and a good coal bed is established, approximately 30 minutes after fuel is lit.
2. High Burn Setting: The fan may be left on through-
out the burn.
3. Medium or Medium High Burn Setting: The fan
should be left off until a good burn is established, then turned on a medium or high rate.
4. Low Burn Setting: The fan tends to cool the re-
place. Leave fan off until the burn is well estab­lished; then, if you wish, turn the fan on at a low rate.
NOTE: The Fan is equipped with a snap disc that will turn the blower on and off depending on the tempera­ture of the replace. If the fan is not coming on at the desired time, ip the override switch to manual and operate the fan as described above.
The override switch and the fan speed control are hard wired at time of installation and installed in a standard wall mount with junction box on the wall.
Alway wear gloves when installing or removing the screen as the screen may become extremely hot while in use. Use both hands to stablize the screen. Ensure that the screen is fully attached. Be careful not to stack wood close to the front or too high that logs could roll out the front. Start with a small re and adjust your heat to desired setting. If smoke spillage occurs, put on gloves and then remove the screen and close the doors. Refer to Flue Draft Troubleshooting on page 4.
CAUTION:
NEVER LEAVE THE FIRE UNATTENDED WHILE USING THE FIRESCREEN. NEVER LEAVE CHILDREN UNATTENDED WHEN THERE IS A FIRE BURNING IN THE FIREPLACE.
CAUTION:
ALL wiring should be done by a qualied electrician and shall be in compliance with local codes and with the National Electric Code ANSI/NF No. 70-current (in the United States), or with the current CSC22.1 Canadian Electric Code (inCanada).
4-03 23 480-1081
Page 24
North Star
EPA Certied Fireplace
10. Starting A Fire
Before lighting your first fire in the fireplace, make certain that the bafe and ceramic blanket are correctly positioned. It should be resting against the rear channel. Also refer to care and cleaning of gold
plated surfaces on page 28 before lighting your rst re.
There are many ways to build a re. The basic principle is to light easily-ignitable tinder or paper, which ignites the fast burning kindling, which in turn ignites the slow-burning rewood. Here is one method that works well:
1. Place several wads of crushed paper on the rebox floor. Hea ting the flue with slightl y crumpl ed newspaper before adding kindling keeps smoke to a minimum.
2. Lay small dry sticks of kindling on top of the paper.
3. Fully open the Slide Air Control by moving it completely to the right.
4. Make sure that no matches or other combustibles are in the immediate area of the fireplace. Be sure the room is adequately ventilated and the ue unobstructed.
5. Light the paper in the replace. NEVER light or
rekindle replace with kerosene, gasoline, or charcoal lighter uid; the results can be fatal.
6. Once the kindling is burning quickly, add several full-length logs 3” or 4” in diameter. Be careful not to smother the re. Stack the pieces of wood carefully: near enough to keep each other hot, but far enough away from each other to allow adequate air ow between them.
7. When ready to reload the replace, add more logs. Large logs burn slowly, holding a re longer. Small logs burn fast and hot, giving quick heat.
8. Adjust the Slide Air Control; the more you close down the Control, (sliding left) the lower and slower the re will burn. The more you open the Air Control, (sliding right) the more heat will be produced and teh faster the wood will burn..
As long as there are hot coals, repeating steps 7 and 8 will maintain a continuous re throughout the season.
NOTE: The special high temperature paint that your replace is nished with will cure as your replace heats. You will notice an odor and perhaps see some vapor rise from the replace surface; this is normal. We recommend that you open a window until the odor dissipates and paint is cured.
NOTE: Fireplace should be run full open for a minimum of 15 minutes a day to keep air passages clean.
11. Burn Rates
HIGH: Open (slide right) Slide Air Control fully. It
is important to do this when reloading the replace. Failure to do this could result in excessive emissions (smoke).
MEDIUM HIGH BURN RATE: After a wood load has been burning on high for 5 to 15 minutes, close the Slide Air Control to 1/2” - 1-1/2” distance open. (Move the handle to left to stop and then to right for the proper setting).
MEDIUM: After a wood load has been burning on high for 5 to 15 minutes (longer for very large pieces or wet wood), slide Slide Air Control left to 1/8”- 1/2” distance open. (Move the handle to left to stop and then to right for the proper setting).
LOW: After a wood load has been burning on high for 5 to 15 minutes (longer for very large pieces or wet wood), gradually slide the Air Control left to close down the air, making sure to maintain ames in the replace. It is very important to maintain ames in your replace during the rst few hours of a low burn, to avoid excessive air pollution.
12. Opacity
T
his is the measure of how cleanly your fireplace is burning. Opacity is measured in percent; 100% opacity is when an object is totally obscured by the smoke column from a chimney, and 0% opacity means that no smoke column can be seen. As you become familiar with your replace, you should periodically check the opacity. This will allow you to know how to burn your replace as nearly smoke-free as possible (goal of 0% opacity).
CAUTION:
Never use gasoline, gasoline-type lantern fuel, kerosene, charcoal lighter uid, or similar liquids to start or “freshen up” a re in this replace. Keep all such liquids well away from the replace.
WARNING!
Do not store fuel within the clearances to combustibles, or in the space required for refueling and ash removal. See maintenance instructions, “Clear Space Near the Fireplace”.
WARNING!
Burning wet, unseasoned wood can cause excessive creosote accumulation. When ignited it can cause a chimney re that may result in a serious house re.
480-1081 24 4-03
Page 25
North Star
EPA Certied Fireplace
13. Wood Fuel
Hardwood vs. Softwood
Your replace’s performance depends a great deal on the quality of the rewood you use. Contrary to popular belief, one species of wood varies very little to the other in terms of energy content. All seasoned wood, regardless of species, contains about 8,000 BTU’s per pound. The important factor is that hardwoods have a greater density than softwoods. therefore, a piece of hardwood will contain about 60% more BTU’s than an equal size piece of so ftwood. Since firewood is commonly sold by the cord (128 cu. ft) a volume measurement, a cord of seasoned oak (hardwood) would contain about 60% more potential energy than a cord of seasoned pine (softwood).
There are many denitions of hardwood and softwood. Although not true in every case, one of the most reliable is to classify them as coniferous or deciduous. Softwoods are considered coniferous. These are trees with needle­like leaves that stay green all year and carry their seeds exposed in a cone. Examples of softwood trees are Douglas r, pine, spruce and cedar. Softwoods, being more porous, require less time to dry, burn faster and are easier to ignite than hardwoods. Deciduous trees are broadleaf trees that lose their leaves in the fall. Their seeds are usually found within a protective pod or enclosure. Hardwoods fall into this category. Some examples of deciduous trees are oak, maple, apple, and birch. However, it should be noted that there are some deciduous trees that are denitely not considered hardwoods such as poplar, aspen and alder. Hardwoods require more time to season, burn slower and are usually harder to ignite than softwoods. Obviously, you will use the type of wood that is most readily available in your area. However, if at all possible the best arrangement is to have a mix of softwood and hardwood. This way you can use the softwood for star ting the re giving off quick heat to bring the appliance up to operating temperature. Then add the hardwood for slow, even heat
and longer burn time.
Fill it with a gallon of water, put it in the rebox and try to burn it. This sounds ridiculous but that is exactly what you are doing if you burn unseasoned wood. Dead wood lying on the forest oor should be considered wet, and requires full seasoning time. Standing dead wood can be considered to be about two-thirds seasoned.
The problems with burning wet, unseasoned wood are two fold. First, you will receive less heat output from wet wood because it requires energy in the form of heat to evaporate the water trapped inside. This is wasted energy that should be used for heating your home. Secondly, this moisture evaporates in the form of steam which has a cooling effect in your rebox and chimney system. When combined with tar and other organic vapors from burning wood it will form creosote which condenses in the relatively cool rebox and chimney. See the maintenance section of this manual for more information regarding creosote formation and need for removal.
Even dry wood contains at least 15% moisture by weight, and should be burned hot enough to keep the chimney hot for as long as it takes to dry the wood out
- about one hour. To tell if wood is dry enough to burn, check the ends of the logs. If there are cracks radiating in all directions from the center, it is dry. If your wood sizzles in the re, even though the surface is dry, it may not be fully cured.
Seasoning
Seasoned rewood is nothing more than wood that is cut to size, split and air dried to a moisture content of around 20%. The time it takes to season wood varies from around nine months for soft woods to as long as eighteen months for hardwoods. The key to seasoning wood is to be sure it has been split, exposing the wet interior and increasing the surface area of each piece. A tree that was cut down a year ago and not split is likely to have almost as high a moisture content now as it did when it was cut.
Moisture content
Regardless of which species of wood you burn, the single most important factor that affects the way your fireplace operates is the amount of moisture in the wood. The majority of the problems replace owners experience are caused by trying to burn wet, unseasoned wood. Freshly cut wood can be as much water as it is wood, having a moisture content of around 50%. Imagine a wooden bucket that weighs about 8 pounds.
4-03 25 480-1081
Page 26
North Star
EPA Certied Fireplace
Storing Wood
Splitting wood before it is stored reduces drying time. The following guideline will ensure properly seasoned wood:
a. Stack the wood to allow air to circulate freely around
and through the woodpile.
b. Elevate the woodpile off the ground to allow air
circulation underneath.
c. The smaller th e pie ces, the faster the dr y ing
process. Any piece over six inches in diameter should be split.
c. Wood should be stacked so that both ends of each
piece are exposed to air, since more drying occurs through the cut ends than the sides. This is true even with wood that has been split.
d. Store wood under cover, such as in a shed, or
covered with a tarp, plastic, tar paper, sheets of scrap plywood, etc., as uncovered wood can absorb water from rain or snow, delaying the seasoning pr oce ss. Avoid cover ing the sides and ends completely. Doing so may trap moisture from the ground and impede air circulation.
14. Draft Problems
NOTE: When rst lighting your replace, it may be
necessary to pre-warm the ue to establish a draft. This is done by holding a rolled up piece of burning newspaper under the ue for a few moments. This will help reduce smoke spillage during start-up.
This replace will operate correctly only if adequate ventilation is provided to allow proper draft to the replace system. Hearth & Home Technologies assumes no responsibility for the improper performance of the replace system caused by inadequate draft due to environmental conditions, windy conditions, down drafts, tight sealing construction of the structure, or mechanical exhausting devices which will create a negative air pressure within the structure where the fireplace is located.
Flue draft is measured as negative pressure in the chimney. The amount of negative pressure determines how strong the draft is. The draft is important because it draws the combustion air into the replace and pulls the smoke out of the chimney.
There are three basic criteria essential in establishing and maintaining ue draft:
• Availability of combustion air.
• Heat generated from the re.
• Diameter and height of the ue system.
These three factors work together as a system to create the ue draft. Increasing or decreasing any one of them will affect the other two and thus change the amount of draft in the entire system.
If the re is hard to start and smoke spills out of the replace, or you nd it difcult to establish and maintain a moderately high burn rate, then the ue draft is too low and corrective measures must be taken.
Be sure you have air available for combustion and that your firewood is dry and well seasoned. Build your res properly and according to the instructions given in operating instructions, “Starting a Fire”. Be sure your ue system is installed correctly and that it is the proper diameter and height. Check for the following:
• All chimney sections are properly installed.
• The chimney is clean and free of creosote or soot
buildup.
• Make sure overhanging trees and branches are cut
back within ten feet of the top of the chimney.
• Ensure the chimney cap is clean and free of any
buildup of soot or creosote.
If you still suspect you have a low draft problem it may be necessary to increase the volume of air in your ue system. Since the diameter of your ue system is matched with the size of the ue collar and should not be changed, then the height of the system must be increased. Add chimney sections a little at a time until the draft improves.
In some cases, regardless of what you do, it can still be difcult to establish the proper ue draft. This is especially evident when using an exterior factory-built chimney or exterior masonry chimney. Try placing several sheets of crumpled paper on top of your kindling as close to the ue outlet of the replace as possible. Light this paper rst then the paper under the kindling. The heat generated from the rapidly burning paper on top of the kindling should help get the draft established.
Still other factors can affect how well your ue system performs. Neighboring structures, high winds, tall trees, even hillsides can affect air currents around the chimney. Well designed chimney caps are available that can help. Your replace dealer is the local expert in your area. He can usually make suggestions or discover problems that can be easily corrected allowing your replace to operate correctly as it has been designed, providing safe and economical heat for your home.
480-1081 26 4-03
Page 27

J. MAINTENANCE INSTRUCTIONS

SCREW
REMOVE (4) SCREWS AND LIFT TOP PAN OFF.
CAP
SLIP SECTION
TR342, TR344
ROUND TERMINATION CAPS
ST375
SQUARE
TERMINATION CAP
LIFT UP TO REMOVE.
SCREW
CHASE
CAP
1. REMOVE THE 4 SCREWS.
2. REMOVE SCREEN.
3. REMOVE BAFFLE.
TS345
SQUARE
TERMINATION CAP
North Star
EPA Certied Fireplace
1. Creosote and Soot
a. Formation and need for removal: When wood
is burned slowly, it produces tar and other organic vapors which combine with expelled moisture to form creosote. The creosote vapors condense in the relatively cool chimney ue of a newly-started or a slow-burning re. As a result, creosote residue accumulates on the ue lining. When ignited, this creosote creates an extremely hot re which may damage the chimney or even destroy the home. The chimney connector and chimney should be inspected once every two months during the heating season to determine if a creosote or soot buildup has occurred. If creosote or soot has accumulated, it should be removed to reduce the risk of a chimney re.
b. Inspection: Inspect the system at the replace
connection and at the chimney top. Cooler surfaces tend to build creosote deposits quicker, so it is important to check the chimney from the top as well as from the bottom.
c. Removal: The creosote or soot should be removed
with a brush specically designed for the type of chimney in use. A chimney sweep can perform this service. It is also recommended that before each heating season the entire system be professionally inspected, and cleaned and repaired if necessary.
3. Disposal of Ashes
Ashes should be placed in a metal container with a tight-tting lid. The closed container of ashes should be placed on a noncombustible oor or on the ground, well away from all combustible materials, pending nal disposal. If the ashes are disposed of by burial in soil or otherwise locally dispersed, they should be retained in the closed container until all embers have thoroughly cooled.
4. Clear Space Near the Fireplace
Combustible materials must not be stored on the hearth extension. Room furnishings such as drapes, curtains, chairs, or other combustibles must be at least four feet from the open front of the replace.
5. Overring:
Do not overre. Using ammable liquids or too much
wood, burning trash in the stove, or allowing too much air into the replace, may result in overring. If the replace glows red or even worse, white, the replace is overred. This condition may ignite creosote in the chimney, which can be dangerous, possibly causing a house re. If you overre, immediately close the air controls and door, if open, to reduce the air supply to the re. Overring will void the replace warranty.
2. Chimney Cleaning
If you do detect a buildup of creosote, contact a qualied chimney sweep or clean it yourself. To do this, perform the following steps:
a. Remove the rst manifold tube and bafe. If you
do not remove the bafe, residue can pile up on top of the bafe, and the replace will not work properly.
b. Keep doors shut to prevent dirt and soot from
entering the room.
c. Remove the termination cap or housing top.
d. Clean with a stiff nylon brush attached to a pole OR
tie a small burlap bag lled with straw and several small stones or sand. Work up and down the ue until the ue is clean.
e. Replace the termination cap or housing top.
f. Reinstall bafe and manifold tube after cleaning.
4-03 27 480-1081
Figure 27A
Chimney & Termination Cap Cleaning
WARNING!
A chimney re can permanently damage your chimney system. This damage can only be repaired by replacing the damaged component parts. Chimney res are not covered by the Limited Lifetime Warranty.
Page 28
North Star
EPA Certied Fireplace
6. Care and Cleaning of Glass
Your replace is equipped with ceramic super heat­resistant glass, which can only be broken by impact or misuse. Do not slam doors or impact the glass. When closing doors, make sure that logs do not protrude against the glass. Clean glass with a nonabrasive glass cleaner, such as Windex. Abrasive cleaners may scratch and cause glass to crack. Inspect glass regularly. If you nd a crack or break, immediately put the re out and return the door to your dealer for replacement of glass before further use.
IMPORTANT! REMOVE ALL LABELS FROM GLASS BEFORE LIGHTING THE FIRST FIRE IN YOUR FIREPLACE.
IMPORTANT!
Replace with 5mm ceramic glass only
8. Glass Replacement
1. Ensure that the re is out and the appliance is cool to the touch.
2. Protect a table or counter top with padding or towels.
3. Remove door with broken glass from the appliance by lifting door up and off of the hinges.
4. Lay door face down on a table or counter making sure handle and handle attachment knob hang over the edge of the table top so door lays at, on a soft surface.
5. Remove the screws from each glass tab (5 on each door) using a #2 Phillips Head screwdriver.
HINT: Soak screws in penetrating oil for easy
removal.
6. Remove the glass.
7. Use only 5mm ceramic Glass, Part GLA-480.
7. Care and Cleaning of Plated Surfaces
Clean 24 karat gold-plated surfaces with vinegar or a glass cleaner before lighting your rst re.
CAUTION:
Do not use polishes with abrasives as it will scratch
the surface.
WARNING!
When the appliance is equipped with a 24 karat gold-plated door, you must clean all the ngerprints and oils from the gold surface before ring the appliance for the rst time. Use a glass cleaner or vinegar and towel to remove the oils. If not cleaned properly before lighting your first re, the oils can cause permanent markings on the gold plating. After the gold plating iis cured, the oils will not affect the nish and little maintenance is required: just wipe clean as needed.
8. Position the glass with edges evenly overlapping the opening in the front door.
9. Replace the glass tabs. Be careful not to cross thread the screws.
10. Tighten each tab just a few turns until each is secured. Then continue to tighten each tab alternately, a few turns at a time, until the glass panel is tightened snugly, but not over tightened.
11. Replace the door on the appliance.
12. After the rst burn, recheck the tighness of the screws.
480-1081 28 4-03
Page 29
9. Firebrick Replacement
3
2
3
3
3
3
3
3
3
2
1
4
1
1 1
1
4
3
3
3
3
3
3
1
1
1
1
1
3
3
4 4
2
2
The rebox of your replace is lined with high quality rebrick, which has exceptional insulating properties. There is no need to use a grate; simply build a re on the rebox oor. Do not operate the replace without rebrick.
IMPORTANT: The bricks are very similar in size. Be certain you have the proper brick in the correct location. Measue the brick size for accuracy.
After the coals are completely cooled, remove all old brick and ash from unit and vacuum out rebox.
1. Remove new brick set from box and lay out to diagram as shown in Figure 29B.
2. Lay bottom bricks in unit.
3. Install rear bricks on the top of the bottom bricks. Slide top of bricks under clip on back of rebox wall and push bottom of brick back.
4. Install side bricks. Slide top of brick under clips on side of rebox and push the bottom of the brick until it is ush with the side of the unit.
North Star
EPA Certied Fireplace
Figure 29A-Brick Pattern
Use Part SRV28111 when ordering individual brick. Provide brick dimension or copy this page, mark the desired brick and take it to your authroized dealer.
4-03 29 480-1081
Figure 29B-Brick Pattern
Nbr
Brick Size
1 13-1/2” x 4-1/2” x 1-1/4” 5
2 13-1/2” x 4-1/2” x 1-1/4” w/ 1-1/2” chamfer 2
3 12 x 4-1/2” x 1-1/4” 8
4 12-1/2” x 4-1/2” x 1-1/4” 2
Qty in Set
Page 30
North Star
Screwdrive
r
Slot
S
c
r
e
w
s
Rem
o
v
e
2 sc
re
w
s
a
n
d
p
ull
p
a
n
e
l
fo
rw
ar
d
(B
e
fore
fire
p
la
c
e
in
s
ta
l
la
ti
o
n)
After
fireplace
installation
Unplug wire harness before
removing fan
EPA Certied Fireplace
10. Fan Replacement
Fan Cord Location
The North Star Fireplace comes standard equipped with two fans, installed at the factory with electric access on the right side of replace (as you face it).
Fan Replacement Instructions
Power must be OFF prior to servicing!
The fan assembly may be accessed before or after the replace has been installed.
Before Fireplace Installation:
1. Remove the 2 screws located at the outside edge of the bottom panel as show in Figure 30A.
2. Pull panel forward and remove from replace.
After Fireplace Installation:
1. Remove the rebrick from the bottom of the replace.
2. Remove the 2 screws from the access panel in the rebox oor.
3. Pry up the access panel using the screwdrive slot and completely remove the panel.
Removing the Fan Assembly
1. Unplug the wire harness.
2. Lift fan off of studs and remove. Repeat for second fan if necessary. See Figure 30B.
3. Inspect the gasket and ensure it is in good condition.
4. Replace with new fan.
5. Reinstall bottom panel or rebox access
panel in reverse order as descibed above.
Figure 30-A Accessing Fan Motor
480-1081 30 4-03
Figure 30B-Fan Motor
Page 31
North Star
Locknut
Door Cross Section (example)
Latch Cam
Spacing Washers
Square Key
Handle
Teflon Washer
DO NOT REMOVE
EPA Certied Fireplace
11. Bafe Removal & Installation
NOTE: The bafe in the North Star Fireplace is 2700° Fiber Board. Removing hardware exposed to combustion processes
can be frustrating. If your reason for removing the bafe is simply to clean the chimney, you have alternatives which will save time and effort. Call a qualied chimney sweep or an authorized Heat-n-Glo dealer for details.
1. Remove all ash from rebox, and extinguish all hot embers before disposal into a metal container.
2. Remove ceramic blanket from above the bafe.
3. With a 3/16” Allen wrench, remove the front manifold tube retainer bolt on the air channel under the end of the front tube. NOTE: Soak the bolt with penetrating oil for at least 15 minutes before trying to remove it. See Figure 31A below.
4. To remove manifold tube, slide the tube to one side until one end is out of its hole. Then, while lifting that end of the ber board bafe, pull tube up over the air channel and out of hole at the other end. It is necessary to remove the rst tube in order to remove the bafe.
5. Slide ber board bafe forward to front of replace and straight out through door. See Figure 31B below.
6. To install the ber board bafe, repeat steps 2 through 4 in reverse. Be sure the ber board bafe and ceramic blanket are pushed back fully and blanket is down and at.
Figure 31A-Removing Manifold Tube
Figure 31B-Removing Bafe
shown without ceramic blanket
12. Door & Door Gasket
Periodically check the door gasket for proper seal. As the gasket compresses or “seats” during use, it may become necessary to adjust or tighten the door latch.
To Adjust or Tighten Door Latch Remove spacing washers shown in Figure 31C. At least one spacing washer must be left in place. OR Replace the gasket material. Wear or damage to the gasket material can cause air leakage into the rebox resulting in overring and loss of efciency.
A replacement gasket, Part 834-1460 is available from your dealer.
4-03 31 480-1081
Figure 31C-Door Handle Assembly
Page 32
1.0"
27-1/2"
27-3/8"
24"
2.0"
Ceramic Blanket
Service Parts
EXPLODED VIEW
North Star
EPA Certied Fireplace
Beginning Manufacturing Date: 02-17-03 Ending Manufacturing Date: __________
Door Assembly
Fascia Assembly
Part number list on following page.
480-1081 32 4-03
Page 33
Service Parts List
North Star
EPA Certied Fireplace
IMPORTANT: THIS IS DATED INFORMATION. The most current information is located on your dealers
VIP site. When ordering, supply serial and model numbers to ensure correct service parts.
ITEM DESCRIPTION SERIAL # PART NUMBER
Brick, Individual SRV28111 Gasketing , Glass 834-1460 Gasketing, Door (door requires 8 feet) 834-4170 Manual-Bag Assembly, (includes Owner’s Manual,
(2) Spring Handles-1/2”, (1) Spring Handle-1/4”, SRV480-1140 Paint, Fan Switches & Cover Plate, Warranty Card)
Snap Disc, F300-40 SRV480-0980 Speed Control SRV480-1250 Spring Handle, 1/4” 832-0630 Washers, 1/4” FW SAE (one under each door hinge pin) 28758 1 8” Starter Section SL1 2 Bafe, Fiberboard SRV480-0510 3 Brick, Set BRICK-480 4 Ceramic Blanket, 1”, cut to t (see drawing on page 32) 832-3400
Door Handle Assembly, (includes 2 door handles,
5
securing bracket, lock nut, latch cam key and cam latch)
6 Fan Replacement 812-4900 7 Fascia FASCIA-NS 8 Glass Assembly for Doors, 2 piece, w/gasketing GLA-480 9 Knob, Black,Outside Air 844-2640 10 Louver, Bottom, Cast, Black SRV480-7090 10 Louver, Bottom, Cast, Gold SRV480-7070 11 Louver, Top, Cast, Black SRV480-7100 11 Louver, Top, Cast, Gold SRV480-7080 12 Manifold Tube, Set of 3 TUBES-480 13 Spring Handle, 1/2” for Doors 832-0620 14 Timer SRV480-0790 15 Wiring Harness SRV480-0990
HANDLES-480
4-03 33 480-1081
Page 34
North Star
EPA Certied Fireplace
A
Accessories 6 Air Clearance 10, 17 Air Kit Knob Location 5 Ashes, Disposal of 27 Attic Insulation Shield 14 Air Controls 22-23 Automatic Combustion Control 23
B
Bafe 24, 31 Building Codes 2, 3 Burning
Guidelines 23 Process 22 Rates 24
C
Ceramic Blanket 24, 32 Chase 19 Chase Top 8, 20 Chimney
Assembling Sections Through the
Roof 16 Checking the Assembly 14 Cleaning 27 Creosote 27 Exit Point Through the Roof 16 Height Requirements 12 Inspection 2 Requirements 12 Securing the System 16
Chimney Air Kit 8 Chimney Bracket 7 Chimney Components 6-8 Chimney Requirements 10 Chimney Sections
Clearances 5 Assembling 13 Number Required 12
Chimney Stabilizer 6, 16 Clearances
Combustible Material 5
Combustion Air 2, 21 Construction 13-17 Creosote 13, 27
D
Description of the Fireplace System 3 Dimensions 5 Door & Door Gasket 31 Draft 4, 26

Index

E
Exploded Views
Door Assembly 33
E
Fascia 33 Fireplace 32
Exhaust Products 9
F
Fan Replacement 30 Fan Wiring Diagram 10 Firebrick 29 Fireplace
Enclosure 16-17 Locations 9
Firestop Spacer 7
Installation 14 Firewood 25, 26 Floor Protection 5 Flue 26 Framing 9, 10 Fuel 2, 25, 26
G
General Information 21 Glass Cleaning 28 Glass Replacement 28 Gold Plated Surfaces 28
H
Hearth Extension 17
Positioning 19 Heat Zone Kit 14, 23
I
Installation
Fireplace 13 Installation Along a Wall 9 Installation, Corner 9 Insulation Shield 7, 14
J
Joint Band 7
L
Leveling the Fireplace 13 Locations 9
M
Maintenance 27 Mantel 5, 10 Material, Sealant 19 Metal Hearth Strips 13 Mobile Home Installation 15
Moisture Content of Wood 25, 26
N
Negative Air Pressure 27 Noncombustible Material 16-18 Noncombustible SealantMaterial 18
O
Offsets/Returns 6, 11, 16 Outside Air 5, 22 Opacity 24 Overhead Obstructions 12
P
Positioning 13 Pre-Installation Preparation 9
R
Replacement Parts 33 Roof Flashing 7, 14
S
Safety 2, 13 Seasoning the Wood 25 Sidewalls/Surrounds 9 Slide Air Controls 22 Smoke 24 Soot 27 Space Requirements 9 Starting a Fire 24
T
Ten Foot Rule 12 Termination Cap 8, 20 Typical Fireplace System 3
U
UL 127 Standards 3 Uniform Building Code for Roof Framing Details 16
V
Ventilation 4
W
Wet Insulation 2 Wiring Diagram for Fans 10 Wood
Moisture of 25 Seasoning of 25 Storing of 26
Wood Fuel 25, 26
480-1081 34 4-03
Page 35
LIMITED LIFETIME WARRANTY
The Hearth & Home Technologies limited Lifetime Warranty guarantees that the following components will work as designed for the lifetime of the stove or Hearth & Home Technologies will repair or replace them. These items include but are not limited to steel and cast iron components, all gas burners, gas logs, combustion chambers, heat exchanger systems, stainless steel firebox components, plating, doors, glass damaged by thermal breakage, steel baffle supports, steel and ceramic baffles and manifold tubes. Labor is for the first five years.
THREE YEAR WARRANTY
Our EZ Clean firepots are covered under Hearth & Home Technologies three-year warranty program. Labor is for 3 years.
TWO YEAR WARRANTY
A
ll electrical components such as but not limited to blowers, wiring, vacuum switches, speed controls, control boxes, thermodisc switches, pilot assembly, gas valves, thermostats and remotes are covered under Hearth & Home Technologies two-year warranty program.
ONE YEAR WARRANTY
Porcelain finishes are warranted against manufacturer defects for one year. Labor to repair or replace these parts is covered for one year, reimbursed per our warranty service fee schedule.
CONDITIONS
This warranty is non-transferable and is made to the original retail purchaser only provided that the purchase was made through an authorized dealer of Hearth & Home Technologies It must be installed and operated at all times in accordance with the Installation and Operating Instructions furnished with this product, as well as any applicable local and national codes. Any alteration, willful abuse, accident, or misuse of the product shall nullify this warranty.
Labor to repair or replace items covered under the limited Lifetime Warranty will be covered for the first five years per our warranty service fee reimbursement schedule. Parts covered under the limited Lifetime Warranty will be covered for the lifetime of the appliance up to a maximum of ten (10) years after Hearth & Home Technologies discontinues the model and two (2) years for optional accessories. Adjustments, regular maintenance, cleaning and temporary repairs do not qualify for a service call fee and will not be covered. The replacement of consumer replaceable items and installation of upgraded component parts do not quality for a service call fee, and will not be covered.
This limited Lifetime Warranty does not extend to or include surface finish on the appliance, door gasketing, glass gasketing, firebrick, kaowool or other ceramic insulating materials. It does not cover installation or operational-related problems such as overfiring, use of corrosive driftwood, downdrafts or spillage caused by environmental conditions, nearby trees, buildings, hilltops, mountains, inadequate venting or ventilation, excessive offsets, or negative air pressures caused by mechanical systems such as furnaces, fans, clothes dryers, etc.
A
ny installation, construction, transportation, or other related costs or expenses arising from defective part(s), repair, replacement, etc., will not be covered by this warranty, nor will Hearth & Home Technologies assume responsibility for them. Further, Hearth & Home Technologies will not be responsible for any incidental, indirect, or consequential damages, except as results in damage to the interior or exterior of the building in which this appliance is installed. This limited Lifetime Warranty does not apply to the venting components, hearth components or other accessories used in conjunction with the installation of this product not manufactured by Hearth & Home Technologies
This warranty is void if the stove has been overfired or operated in atmospheres contaminated by chlorine, fluorine, or other damaging chemicals, the stove is subjected to prolonged periods of dampness or condensation, or there is any damage to the stove or other components due to water or weather damage which is the result of, but not limited to, improper chimney or venting installation. Hearth & Home Technologies may, at its discretion, fully discharge all obligations with respect to this warranty by either repairing or replacing the unit, or refunding the wholesale price of the defective part(s).
This limited Lifetime Warranty is effective on all appliances sold after May 1, 2002 and supersedes any and all warranties currently in existence.
Policy 250-8620 Rev C
Lifetime Warranty
4-03 35 480-1081
Page 36
ATTENTION INSTALLER:
PLEASE RETURN THESE INSTRUCTIONS TO THE HOME OWNER
WHEN INSTALLATION
IS COMPLETE.
4-03 36 480-1081
Loading...