• Important operating
and maintenance
instructions included.
WARNING: If the information in these
instructions is not followed exactly, a fi re
or explosion may result causing property
damage, personal injury, or death.
• DO NOT store or use gasoline or other fl am-
mable vapors and liquids in the vicinity of this
or any other appliance.
• What to do if you smell gas
- DO NOT try to light any appliance.
- DO NOT touch any electrical switch. DO
NOT use any phone in your building.
- Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions.
- If you cannot reach your gas supplier, call
the fi re department.
• Installation and service must be performed
by a qualifi ed installer, service agency , or the
gas supplier.
This appliance may be installed as an OEM installation in
manufactured home (USA only) or mobile home and must be
installed in accordance with the manufacturer’s instructions
and the manufactured home construction and safety standard,
Title 24 CFR, Part 3280 or Standard for Installation in Mobile
Homes, CAN/CSA Z240MH, in Canada.
This appliance is only for use with the type(s) of gas indicated
on the rating plate.
• Read, understand and follow
these instructions for safe
installation and operation.
DO NOT
DISCARD
• Leave this manual with
party responsible for use
and operation.
WARNING
HOT SURFACES!
Glass and other surfaces are hot during
operation AND cool down.
Hot glass will cause burns.
• DO NOT touch glass until it is cooled
• NEVER allow children to touch glass
• Keep children away
• CAREFULLY SUPERVISE children in same room as
fi replace.
• Alert children and adults to hazards of high temperatures.
High temperatures may ignite clothing or other fl ammable
materials.
• Keep clothing, furniture, draperies and other fl ammable
materials away.
This appliance has been supplied with an integral barrier
to prevent direct contact with the fi xed glass panel. DO
NOT operate the appliance with the barrier removed.
Contact your dealer or Hearth & Home Technologies if the
barrier is not present or help is needed to properly install one.
In the Commonwealth of Massachusetts installation must be
performed by a licensed plumber or gas fi tter.
See Table of Contents for location of additional Commonwealth
of Massachusetts requirements.
Installation and service of this appliance should be
performed by qualifi ed personnel. Hearth & Home
Technologies suggests NFI certifi ed or factory trained
professionals, or technicians supervised by an NFI
certifi ed professional.
Read this manual before installing or operating this appliance.
Please retain this owner’s manual for future reference.
A. Congratulations
Congratulations on selecting a Heat & Glo gas fi replace, an
elegant and clean alternative to wood burning fi replaces.
The Heat & Glo gas fi replace you have selected is designed
to provide the utmost in safety, reliability, and effi ciency.
As the owner of a new fi replace, you’ll want to read and
carefully follow all of the instructions contained in this
owner’s manual. Pay special attention to all cautions and
warnings.
Homeowner Reference Information
This owner’s manual should be retained for future
reference. We suggest that you keep it with your other
important documents and product manuals.
The information contained in this owner’s manual, unless
noted otherwise, applies to all models and gas control
systems.
Your new Heat & Glo gas fi replace will give you years of
durable use and trouble-free enjoyment. Welcome to the
Heat & Glo family of fi replace products!
We recommend that you record the following pertinent
information about your fi replace.
Model Name: ___________________________________________ Date purchased/installed: __________________
Serial Number: __________________________________________ Location on fi replace: _____________________
Dealership purchased from: _______________________________ Dealer Phone: __________________________
Notes: _______________________________________________________________________________________
_____________________________________________________________________________________________
Listing Label Information/Location
This product may be covered by one or more of the following patents: (Nos produits sont couverts par un ou plusieurs des brevets suivants): (United States)
4593510,4686807, 4766876, 4793322, 4811534, 5000162, 5016609, 5076254, 5113843, 5191877, 5218953, 5263471, 5328356, 5341794, 5347983, 5429495,
5452708,5542407, 5601073, 5613487, 5647340, 5688568, 5762062, 5775408, 5890485, 5931661, 5941237,5947112,5996575, 6006743, 6019099, 6048195,
6053165, 6145502, 6170481, 6237588, 6296474, 6374822, 6413079, 6439226, 6484712, 6543698, 6550687, 6601579, 6672860, 6688302B2, 6715724B2,
6729551, 6736133, 6748940, 6748942, D320652, D445174, D462436; (Canada)1297749, 2195264, 2225408; or other U.S. and foreign patents pending (ou
autresbrevetsamericainsetetrangers en attente).
Type of Gas
NotNot for for use use withwith solid solid fuel.fuel.
((NeNe doitdoit pas pas entre entre utilise utilise avecavec un un combustible combustible solide).solide).
Type Type ofof Gas Gas (Sorte(Sorte DeDe Gaz)Gaz)::
NNAATURALTURAL GASGAS
Gas and Electric
Information
Minimum Minimum Permissible Permissible Gas Gas SupplySupplyfor for Purpose sPurposes ofof Input Input Adjustment.Adjustment.
ApprovedApproved Minimum Minimum (De (De Gaz)Gaz)AcceptableAcceptable 0.00.0inin w.c.w.c.(Po.(Po.Col.Col. d’eau)d’eau)
Maximum Maximum PressurePressure(Pression)(Pression)0.00.0inin w.c.w.c.(Po.(Po.Col.Col. d’eau)d’eau)
Maximum Maximum ManifoldManifoldPressurePressure (Pression)(Pression) 0.00.0 inin w.c.w.c.(Po.(Po.Col.Col.d’eau)d’eau)
Minimum Minimum ManifoldManifold PressurePressure(Pression)(Pression) 0.00.0 inin w.c.w.c.(Po.(Po.Col.Col. d’eau)d’eau)
Total Total ElectricalElectrical Requirements: Requirements: 000Vac, 000Vac, 00Hz.,00Hz.,lesslessthanthan0000 AmperesAmperes
The model information regarding your specifi c fi replace can be found on
the rating plate usually located in the control area of the fi replace.
Heat & Glo, a brand of Hearth & Home Technologies, Inc.
7571 215th Street West, Lakeville, MN 55044
ThisThisappliance appliance mustmust bebeinstalled installed inin accordanceaccordance withwith local local codes,codes, ifif any;any; ifif not,not, follow follow ANSIANSIZ223.1Z223.1
ininthe the USA USA ororCAN/CGA CAN/CGA B149 B149 installation installation codes.codes.(Installer (Installer l’appareill’appareilselon selon leslescodes codes ouou reglementsreglements
locauxlocaux ou,ou, enen l’absencel’absence dede telstels reglements, reglements, selon selon les les codescodes d’installationd’installation CAN/CGA-B149.)CAN/CGA-B149.)
B. Limited Lifetime Warranty
Hearth & Home Technologies LIMITED WARRANTY
Hearth & Home Technologies (“HHT”) and its respective brands extends the following warranty for HHT gas, wood, pellet
and electric appliances purchased from an authorized HHT dealer and installed in the United States of America or Canada.
Warranty starts with date of purchase by the original owner (End User) except as noted for replacement parts.
Warranty PeriodHHT Manufactured Appliances and Venting
PartsLaborGasWoodPellet
1 YearXXXXXX
EPA
Wood
ElectricVenting
Components Covered
All Parts and Material Except as
covered by Conditions, Exclusion,
and Limitations listed
XX
2 years
3 yearsXFirepots
5 years3 yearsXXCastings & Baffl es
7 years3 yearsXXX
10 years1 yearXBurners, Logs & Refractory
Limited
Lifetime
1 yearXFirebox & Heat Exchanger
90 DaysXXXXXX All Replacement Parts
XXXXBlowers
XMolded Refractory Panels
Igniters, Electronic Components,
and Glass
Firebox, HHT Chimney,
Termination & Heat
Exchanger
See Conditions, Exclusions, and limitations. 9-01-08
CONDITIONS, EXCLUSIONS & LIMITATION OF LIABILITY
• This warranty applies to the original owner and is transferable up to two years from date of purchase to the new homeowner,
provided the purchase was made through an authorized dealer or distributor of HHT, and the appliance remains in its
original place of installation.
• The maximum amount recoverable under this warranty is limited to the purchase price of the product.
• In no event shall HHT be liable for any incidental or consequential damages caused by defects in the product.
• Adjustments, regular maintenance, cleaning and temporary repairs, or the failure to duplicate the problem in the home is
not covered under this warranty.
• This limited warranty does not extend to or include surface fi nish on the appliance or terminations, door gasketing, glass
gasketing, glass discoloration, fi rebrick, pellet logs, kaowool or other ceramic insulating materials. Rust and/or corrosion
on any of the metal surfaces, cast iron components, baffl es, fi repots, doors, or fi rebox area are not covered by this
warranty.
• Noise resulting from minor expansion, contraction, or movement of certain parts is normal and complaints related to this
noise are not covered by this warranty.
• HHT’s obligation under this warranty does not extend to damages resulting from: (1) installation, operation or maintenance
of the appliance not in accordance with the installation instructions; operating instructions and the listing agent identifi cation
label furnished with the appliance; (2) installation which does not comply with local building codes; (3) shipping, improper
handling, improper operation, abuse, misuse, accident or unworkmanlike repairs; (4) environmental conditions, inadequate
ventilation or drafting caused by tight sealing construction of the structure or handling devices such as exhaust fans or forced
air furnaces or other such causes; (5) use of fuels other than those specifi ed in the operating instructions; (6) installation
or use of components not supplied with the appliance or any other components not expressly authorized and approved
by HHT; and/or (7) modifi cation of the appliance not expressly authorized and approved by HHT in writing.
• This warranty does not apply to non-HHT venting components, hearth components or other accessories used in conjunction
with the installation of this product.
• This warranty is void if the appliance has been over-fi red or operated in atmospheres contaminated by chlorine, fl uorine,
or other damaging chemicals the appliance is subject to prolonged periods of dampness or condensation, or there is any
damage to the appliance or other components due to water or weather damage which is the result of, but not limited to,
improper chimney or venting installation.
• HHT’s liability under this warranty is limited to the replacement and repair of defective components or workmanship during
the applicable period. HHT may fully discharge all of its obligations under such warranties by repairing the defective
component(s) at HHT’s discretion. Shipping costs are not covered under this warranty.
• Some states do not allow exclusions or limitation of incidental or consequential damages, so those limitations may not
apply to you. This warranty gives you specifi c rights; you may also have other rights, which vary from state to state.
• EXCEPT TO THE EXTENT PROVIDED BY LAW, HHT MAKES NO EXPRESS WARRANTIES OTHER THAN THE
WARRANTY SPECIFIED HEREIN. THE DURATION OF ANY IMPLIED WARRANTY IS LIMITED TO DURATION OF
THE WARRANTY SPECIFIED ABOVE.
This Limited Warranty is effective on all HHT appliances sold after September 01, 2008 and supersedes any and all
warranties currently in existence.
If warranty service is needed, you should contact your installing dealer. If the installing dealer is unable to provide necessary
parts or components, contact the nearest authorized HHT dealer or supplier.
MODELS: 6000G, 6000G-IPI
LABORATORY: Underwriters Laboratories, Inc. (UL)
TYPE: Direct Vent Gas Appliance Heater
STANDARD: ANSI Z21.88-2000 • CSA2.33-M98 • UL307B
This product is listed to ANSI standards for “Vented Gas
Appliance Heaters” and applicable sections of “Gas Burning Heating Appliances for Manufactured Homes and
Recreational Vehicles”, and “Gas Fired Appliances for
Use at High Altitudes”.
NOTICE: This installation must conform with local codes.
In the absence of local codes you must comply with the
National Fuel Gas Code, ANSI Z223.1-latest edition in
the U.S.A. and the CAN/CGA B149 Installation Codes in
Canada.
NOT INTENDED FOR USE AS A PRIMAR Y HEAT SOURCE.
This appliance is tested and approved as either supplemental room heat or as a decorative appliance. It should not be
factored as primary heat in residential heating calculations.
B. Tempered Glass Specifi cations
Hearth & Home Technologies appliances manufactured
with tempered glass may be installed in hazardous locations such as bathtub enclosures as defi ned by the Con-
sumer Product Safety Commission (CPSC). The tempered
glass has been tested and certifi ed to the requirements
of ANSI Z97.1 and CPSC 16 CFR 1202 (Safety Glazing
Certifi cation Council SGCC# 1595 and 1597. Architectur-
al Testing, Inc. Reports 02-31919.01 and 02-31917.01).
This statement is in compliance with CPSC 16 CFR Sec-tion 1201.5 “Certifi cation and labeling requirements”
which refers to 15 U.S. Code (USC) 2063 stating “…Such
certifi cate shall accompany the product or shall otherwise
be furnished to any distributor or retailer to whom the
product is delivered.”
Some local building codes require the use of tempered
glass with permanent marking in such locations. Glass
meeting this requirement is available from the factory.
Please contact your dealer or distributor to order.
C. BTU Specifi cations
Models
(U.S. or Canada)
6000G (NG)
6000G-IPI (NG)
6000G-LP
6000GIPILP
US
(0-2000 FT)
CANADA
(2000-4500 FT)
US
(0-2000 FT)
CANADA
(2000-4500 FT)
Maximum
Input
BTU/h
30,00018,20037
27,00016,38038
30,00018,20052
27,00016,38053
Minimum
Input
BTU/h
Orifi ce
Size
(DMS)
D. High Altitude Installations
NOTICE: If the heating value of the gas has been reduced,
these rules do not apply. Check with your local gas utility
or authorities having jurisdiction.
When installing above 2000 feet elevation:
• In the USA: Reduce input rate 4% for each 1000 feet
above 2000 feet.
• In CANADA: Reduce input rate 10% for elevations
between 2000 feet and 4500 feet. Above 4500 feet,
consult local gas utility.
Check with your local gas utility to determine proper
orifi ce size.
E. Non-Combustible Materials Specifi cation
Material which will not ignite and burn. Such materials are
those consisting entirely of steel, iron, brick, tile, concrete,
slate, glass or plasters, or any combination thereof.
Materials that are reported as passing ASTM E 136,
Standard Test Method for Behavior of Materials in a
Vertical Tube Furnace at 750 ºC and UL763 shall be
considered non-combustible materials.
F. Combustible Materials Specifi cation
Materials made of or surfaced with wood, compressed paper, plant fi bers, plastics, or other material that can ignite
and burn, whether fl ame proofed or not, or plastered or
unplastered shall be considered combustible materials.
G. Electrical Codes
NOTICE: This appliance must be electrically wired and
grounded in accordance with local codes or, in the absence
of local codes, with National Electric Code ANSI/NFPA
70-latest edition or the Canadian Electric Code CSA
C22.1.
• A 110-120 VAC circuit for this product must be protected
with ground-fault circuit-interrupter protection, in compliance
with the applicable electrical codes, when it is installed in
locations such as in bathrooms or near sinks.
Note: The following requirements reference various
Massachuset ts and national codes not contained in this
document.
H. Requirements for the Commonwealth of
Massachusetts
For all side wall horizontally vented gas fueled equipment
installed in every dwelling, building or structure used in
whole or in part for residential purposes, including those
owned or operated by the Commonwealth and where the
side wall exhaust vent termination is less than seven (7)
feet above fi nished grade in the area of the venting, in-
cluding but not limited to decks and porches, the following
requirements shall be satisfi ed:
Installation of Carbon Monoxide Detectors
At the time of installation of the side wall horizontal vented
gas fueled equipment, the installing plumber or gas fi tter
shall observe that a hard wired carbon monoxide detector
with an alarm and battery back-up is installed on the fl oor
level where the gas equipment is to be installed. In addition, the installing plumber or gas fi tter shall observe that
a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of
the dwelling, building or structure served by the side wall
horizontal vented gas fueled equipment. It shall be the
responsibility of the property owner to secure the services
of qualifi ed licensed professionals for the installation of
hard wired carbon monoxide detectors.
In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic,
the hard wired carbon monoxide detector with alarm and
battery back-up may be installed on the next adjacent
fl oor level.
In the event that the requirements of this subdivision can
not be met at the time of completion of installation, the
owner shall have a period of thirty (30) days to comply
with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon
monoxide detector with an alarm shall be installed.
Inspection
The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the
installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed
in accordance with the provisions of 248 CMR 5.08(2)(a)1
through 4.
Exemptions
The following equipment is exempt from 248 CMR
5.08(2)(a)1 through 4:
• The equipment listed in Chapter 10 entitled “Equipment
Not Required To Be Vented” in the most current edition
of NFPA 54 as adopted by the Board; and
• Product Approved side wall horizontally vented gas fu-
eled equipment installed in a room or structure separate
from the dwelling, building or structure used in whole or
in part for residential purposes.
MANUFACTURER REQUIREMENTS
Gas Equipment Venting System Provided
When the manufacturer of Product Approved side wall
horizontally vented gas equipment provides a venting
system design or venting system components with the
equipment, the instructions provided by the manufacturer
for installation of the equipment and the venting system
shall include:
• Detailed instructions for the installation of the venting
system design or the venting system components; and
• A complete parts list for the venting system design or
venting system.
Gas Equipment Venting System NOT Provided
When the manufacturer of a Product Approved side wall
horizontally vented gas fueled equipment does not provide the parts for venting the fl ue gases, but identifi es
“special venting systems”, the following requirements
shall be satisfi ed by the manufacturer:
Approved Carbon Monoxide Detectors
Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA
720 and be ANSI/UL 2034 listed and IAS certifi ed.
Signage
A metal or plastic identifi cation plate shall be permanent-
ly mounted to the exterior of the building at a minimum
height of eight (8) feet above grade directly in line with the
exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read,
in print size no less than one-half (1/2) in. in size, “GAS
VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
• The referenced “special venting system” instructions
shall be included with the appliance or equipment installation instructions; and
• The “special venting systems” shall be Product Ap-
proved by the Board, and the instructions for that system shall include a parts list and detailed installation
instructions.
A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting
instructions, and/or all venting design instructions shall
remain with the appliance or equipment at the completion
of the installation.
See Gas Connection section for additional Commonwealth of Massachusetts requirements.
Page 9
2
2
Operating Instructions
User Guide
A. Gas Fireplace Safety
WARNING
HOT SURFACES!
Glass and other surfaces are hot during
operation AND cool down.
Hot glass will cause burns.
• DO NOT touch glass until it is cooled
• NEVER allow children to touch glass
• Keep children away
• CAREFULLY SUPERVISE children in same room as
fi replace.
• Alert children and adults to hazards of high temperatures.
High temperatures may ignite clothing or other
fl ammable materials.
• Keep clothing, furniture, draperies and other fl ammable
materials away.
This appliance has been supplied with an integral barrier
to prevent direct contact with the fi xed glass panel. DO
NOT operate the appliance with the barrier removed.
Contact your dealer or Hearth & Home Technologies if the
barrier is not present or help is needed to properly install one.
If you expect that small children or vulnerable adults may
come into contact with this fi replace, the following precau-
tions are recommended:
• Install a physical barrier such as:
- A decorative fi rescreen.
- Adjustable safety gate.
• Install a switch lock or a wall/remote control with child
protection lockout feature.
• Keep remote controls out of reach of children.
• Never leave children alone near a hot fi replace, whether
operating or cooling down.
• Teach children to NEVER touch the fi replace.
• Consider not using the fi replace when children will be
present.
Contact your dealer for more information, or visit: www.
hpba.org/staysafe.
T o prevent unintended operation when not using your fi re-
place for an extended period of time (summer months,
vacations, trips, etc):
• Remove batteries from remote controls.
• Turn off wall controls.
• Unplug 3 volt adapter plug and remove batteries on IPI
models.
• Turn off gas controls valve on standing pilot models.
When lighting the pilot light on fi replaces with a standing
pilot, remove the fi xed glass assembly so you can de-
tect presence of residual gas build-up. See Standing Pilot
Lighting instructions and Maintenance Tasks.
B. Your Fireplace
WARNING! DO NOT operate fi replace before read-
ing and understanding operating instructions. Failure
to operate fi replace according to operating instructions
could cause fi re or injury.
If desired, a fan kit may be added. Contact your dealer to
order the correct fan kit.
D. Clear Space
WARNING! DO NOT place combustible objects in front
of the fi replace or block louvers. High temperatures may
start a fi re. See Figure 2.2.
A void placing candles and other heat-sensitive objects on
mantel or hearth. Heat may damage these objects.
3 FT. IN FRONT OF FIREPLACE
CLE
AR SPACE
Figure 2.2 Clear Space
E. Decorative Doors and Fronts
WARNING! Risk of Fire! Install ONLY doors or fronts
approved by Hearth & Home Technologies. Unapproved
doors or fronts may cause fi replace to overheat.
This fireplace has been supplied with an integral
barrier to prevent direct contact with the fi xed glass
panel. DO NOT operate the fi replace with the barrier
removed.
Contact your dealer or Hearth & Home Technologies if
the barrier is not present or help is needed to properly
install one.
F. Fixed Glass Assembly
See Section 14.G.
G. Remote Controls, Wall Controls and Wall
Switches
Follow the instructions supplied with the control installed
to operate your fi replace:
For safety:
• Install a switch lock or a wall/remote control with child
protection lockout feature.
• Keep remote controls out of reach of children.
See your dealer if you have questions.
H. Before Lighting Fireplace
Before operating this fi replace for the fi rst time, have a
qualifi ed service technician:
• Verify all shipping materials have been removed from
inside and/or underneath the fi rebox.
• Review proper placement of logs, ember material and/or
other decorative materials.
• Check the wiring.
• Check the air shutter adjustment.
• Ensure that there are no gas leaks.
• Ensure that the glass is sealed and in the proper position
and that the integral barrier is in place.
WARNING! Risk of Fire or Asphyxiation! DO NOT operate fi replace with fi xed glass assembly removed.
Determine if this fi replace has a standing pilot or an
Intellifi re ignition system. Ask your dealer or open control
access panel, look at gas valve assembly.
• A standing pilot ignition will have a red or black ignitor
button (refer to Figure 2.3).
• An Intellifi re ignition system will not have a button.
RED OR
BLACK
BUTTON
For more information refer to the instructions supplied with
your decorative door or front.
The IPI system may be operated with two D-cell batteries. When using batteries, unplug the transformer. To prolong battery
life, remove them when using the transformer.
FOR YOUR SAFETY
READ BEFORE LIGHTING
WARNING: If you do not follow these instructions exactly, a fi re or explosion
may result causing property damage, personal injury or loss of life.
A. This appliance is equipped with an
intermittent pilot ignition (IPI) device
which automatically lights the burner. DO NOT try to light the burner by
hand.
B.BEFORE LIGHTING, smell all around
the appliance area for gas. Be sure to
smell next to the fl oor because some
gas is heavier than air and will settle
on the fl oor.
WHA T TO DO IF YOU SMELL GAS
• DO NOT try to light any appliance.
• DO NOT touch any electric switch; do
not use any phone in your building.
WARNING:
DO NOT CONNECT 110 VAC TO
THE CONTROL VALVE.
Improper installation, adjustment, alteration, service or maintenance can
cause injury or property damage. Refer to the owner’s information manual
provided with this appliance.
This appliance needs fresh air for
safe operation and must be installed
so there are provisions for adequate
combustion and ventilation air.
If not installed, operated, and maintained in accordance with the manufacturer’s instructions, this product
could expose you to substances in fuel
or fuel combustion which are known to
the State of California to cause cancer, birth defects, or other reproductive
harm.
Keep burner and control compartment
clean. See installation and operating
instructions accompanying appliance.
• Immediately call your gas supplier
from a neighbor’s phone. Follow the
gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fi re department.
C. DO NOT use this appliance if any
part has been under water. Immediately call a qualifi ed service tech-
nician to inspect the appliance and
to replace any part of the control
system and any gas control which
has been under water.
CAUTION:
Hot while in operation. DO NOT touch.
Keep children, clothing, furniture, gasoline and other liquids having fl ammable
vapors away.
DO NOT operate the appliance with
fi xed glass assembly removed, cracked
or broken. Replacement of the fi xed
glass assembly should be done by a
licensed or qualifi ed service person.
NOT FOR USE
WITH SOLID FUEL
For use with natural gas and propane.
A conversion kit, as supplied by the
manufacturer, shall be used to convert
this appliance to the alternate fuel.
Also Certifi ed for Installation in a
Bedroom or a Bedsitting Room.
For assistance or additional information, consult a qualifi ed installer, ser-
vice agency or the gas supplier.
LIGHTING
INSTRUCTIONS
(IPI)
1. Turn off all electric power to the appliance.
2. This appliance is equipped with an ignition
device which automatically lights the burner.
DO NOT try to light the burner by hand.
GAS
VALVE
3. Wait fi ve (5) minutes to clear out any gas.
Then smell for gas, including near the fl oor. If
you smell gas, STOP! Follow “B” in the Safety
Information located on the left side of this label. If you do not smell gas, go to next step.
4. Turn on all electric power to the appliance.
5. To light the burner, fl ip the ON/OFF switch to
the “ON” position. (The ON/OFF switch may
include a wall switch if so equipped).
6. If the appliance will not operate, follow the instructions “To Turn Off Gas to Appliance” and
call your service technician or gas supplier.
TO TURN OFF
GAS TO APPLIANCE
1. Turn wall control or ON/OFF switch to “OFF”.
2. Turn off all electric power to the appliance if
service is to be performed.
593-913F
Hearth & Home Technologies fi replace, please refer to www.fi replaces.com.
WARNING: If you do not follow these instructions exactly, a fi re or explosion
may result causing property damage, personal injury or loss of life.
A. This appliance has a pilot which
must be lighted by hand. When
lighting the pilot, follow these instructions exactly.
B.BEFORE LIGHTING, smell all around
the appliance area for gas. Be sure to
smell next to the fl oor because some
gas is heavier than air and will settle
on the fl oor.
WHA T TO DO IF YOU SMELL GAS
• DO NOT try to light any appliance.
• DO NOT touch any electric switch; do
not use any phone in your building.
• Immediately call your gas supplier
from a neighbor’s phone. Follow the
gas supplier’s instructions.
WARNING:
DO NOT CONNECT 110 VAC TO
THE CONTROL VALVE.
Improper installation, adjustment, alteration, service or maintenance can
cause injury or property damage. Refer to the owner’s information manual
provided with this appliance.
This appliance needs fresh air for
safe operation and must be installed
so there are provisions for adequate
combustion and ventilation air.
If not installed, operated, and maintained in accordance with the manufacturer’s instructions, this product
could expose you to substances in fuel
or fuel combustion which are known to
the State of California to cause cancer, birth defects, or other reproductive
harm.
Keep burner and control compartment
clean. See installation and operating
instructions accompanying appliance.
For additional information on operating your
Hearth & Home Technologies fi replace, please refer to www.fi replaces.com.
• If you cannot reach your gas supplier, call the fi re department.
C. Use only your hand to push in or
turn the gas control knob. Never use
tools. If the knob will not push in or
turn by hand, DO NOT try to repair
it, call a qualifi ed service technician.
Force or attempted repair may result in a fi re or explosion.
D.DO NOT use this appliance if any
part has been under water. Immediately call a qualifi ed service tech-
nician to inspect the appliance and
to replace any part of the control
system and any gas control which
has been under water.
CAUTION:
Hot while in operation. DO NOT touch.
Keep children, clothing, furniture, gasoline and other liquids having fl ammable
vapors away.
DO NOT operate the appliance with
fi xed glass assembly removed, cracked
or broken. Replacement of the fi xed
glass assembly should be done by a
licensed or qualifi ed service person.
NOT FOR USE
WITH SOLID FUEL
For use with natural gas and propane.
A conversion kit, as supplied by the
manufacturer, shall be used to convert
this appliance to the alternate fuel.
Also Certifi ed for Installation in a
Bedroom or a Bedsitting Room.
For assistance or additional information, consult a qualifi ed installer, ser-
vice agency or the gas supplier.
Final inspection by
1. Open control access panel.
2. Turn off all electric power to
3. Push in gas control knob
Note: Knob cannot be turned from “PILOT” to “OFF” unless knob is pushed in slightly. DO NOT force.
4. Open the fi xed glass assembly. You may need to
5. Wait fi ve (5) minutes to clear out any gas. Then
6. Find the pilot. The pilot is inside
7. Turn knob on gas control counterclockwise
8. Push in control knob all the way and hold in. Immedi-
12. To light burner, turn the wall control or on/off switch
1. Turn off all electric power to the appliance if ser-
2. Open control access panel.
3. Move switch to “OFF” position.
4. Push in gas control knob slightly and turn clock-
5. Close control access panel.
LIGHTING
INSTRUCTIONS
the appliance.
slightly and turn clockwise
to “OFF”.
remove the decorative front.
smell for gas, including near the fl oor. If you smell
gas, STOP! Follow “B” in the Safety
Information located on the left side
of this label. If you don’t smell gas,
go to next step.
combustion chamber next to the
main burner
to “PILOT”.
ately depress red or black piezo button. It may require
several depressions of the red or black piezo button
until PILOT lights. If PILOT light does not light after
10 seconds, return to step 3. Continue to hold the
control knob in for about one minute after the pilot is
lit. Release knob and it will pop back out. Pilot should
remain lit. If it goes out, repeat steps 3 through 6.
• If knob does not pop up when released, stop and
immediately call your service technician or gas
supplier.
• If the pilot will not stay lit after several tries, turn
the gas control knob to “OFF” and call your service technician or gas supplier.
• The fireplace should be run three to four hours
continuously on high.
• Turn the fi replace off and allow it to completely cool.
• Remove fi xed glass assembly. See Section 14.G.
• Clean fi xed glass assembly. See Section 3.
• Replace the fi xed glass assembly and run continuously
on high an additional 12 hours.
This cures the materials used to manufacture the fi re-
place.
NOTICE! Open windows for air circulation during fi re-
place break-in.
• Some people may be sensitive to smoke and odors.
• Smoke detectors may activate.
L. Frequently Asked Questions
ISSUESOLUTIONS
Condensation on the glass
Blue fl ames
Odor from appliance
Film on the glass
Metallic noise
Is it normal to see the pilot fl ame burn
continually?
This is a result of gas combustion and temperature variations. As the appliance warms, this
condensation will disappear.
This is a result of normal operation and the fl ames will begin to yellow as the appliance is al-
lowed to burn for 20 to 40 minutes.
When fi rst operated, this appliance may release an odor for the fi rst several hours. This is caused
by the curing of the paint and the burning off of any oils remaining from manufacturing. Odor may
also be released from fi nishing materials and adhesives used around the appliance.
This is a normal result of the curing process of the paint and logs. Glass should be cleaned
within 3 to 4 hours of initial burning to remove deposits left by oils from the manufacturing
process. A non-abrasive cleaner such as gas fi replace glass cleaner may be necessary. See
your dealer.
Noise is caused by metal expanding and contracting as it heats up and cools down, similar to
the sound produced by a furnace or heating duct. This noise does not affect the operation or
longevity of the appliance.
In an Intellifi re ignition system it is normal to see the pilot fl ame, but it should turn off when
ON/OFF is turned off. In a standing pilot system the pilot will always stay on.
Any safety screen or guard removed for servicing must be
replaced prior to operating the fi replace.
When properly maintained, your fi replace will give you
many years of trouble-free service. We recommend annual service by a qualifi ed service technician.
A. Maintenance Tasks-Homeowner
Installation and repair should be done by a qualifi ed service
technician only. The fi replace should be inspected before
use and at least annually by a professional service person.
The following tasks may be performed annually by the
homeowner. If you are uncomfortable performing any of
the listed tasks, please call your dealer for a service appointment.
More frequent cleaning may be required due to lint from
carpeting or other factors. Control compartment, burner
and circulating air passageway of the fi replace must be
kept clean.
CAUTION! Risk of Burns! The fi replace should be turned
off and cooled before servicing.
• Inspect venting and termination cap for blockage or
obstruction such plants, bird nests, leaves, snow, debris,
etc.
• Verify termination cap clearance to subsequent construction (building additions, decks, fences, or sheds). See
Section 6.
• Inspect for corrosion or separation.
• Verify weather stripping, sealing and fl ashing remains
intact.
• Inspect draft shield to verify it is not damaged or missing.
B. Maintenance Tasks-Qualifi ed Service
Technician
The following tasks must be performed by a qualifi ed ser-
vice technician.
Gasket Seal and Glass Assembly Inspection
Frequency: Annually
By: Qualifi ed Service Technician
T ools needed: Protective gloves, drop cloth and a stable
work surface.
• Inspect gasket seal and its condition.
• Inspect fi xed glass assembly for scratches and nicks that
can lead to breakage when exposed to heat.
• Confi rm there is no damage to glass or glass frame.
Replace as necessary.
• Verify that fi xed glass assembly is properly retained and
attachment components are intact and not damaged.
Replace as necessary.
Logs
Frequency: Annually
By: Qualifi ed Service Technician
Tools needed: Protective gloves.
• Inspect for damaged or missing logs. Replace as necessary . Refer to Section 14 for log placement instructions.
• Verify correct log placement and no fl ame impingement
causing sooting. Correct as necessary.
Firebox
Frequency: Annually
By: Qualifi ed Service Technician
Tools needed: Protective gloves, sandpaper, steel wool,
cloths, mineral spirits, primer and touch-up paint.
• Inspect for paint condition, warped surfaces, corrosion
or perforation. Sand and repaint as necessary.
• Replace fi replace if fi rebox has been perforated.
Control Compartment and Firebox Top
Frequency: Annually
By: Qualifi ed Service Technician
Tools needed: Protective gloves, vacuum cleaner, dust
cloths
• V acuum and wipe out dust, cobwebs, debris or pet hair.
Use caution when cleaning these areas. Screw tips that
have penetrated the sheet metal are sharp and should
be avoided.
• Remove all foreign objects.
• Verify unobstructed air circulation.
Burner Ignition and Operation
Frequency: Annually
By: Qualifi ed Service Technician
T ools needed: Protective gloves, vacuum cleaner, whisk
broom, fl ashlight, voltmeter, indexed drill bit set, and a
manometer.
• Verify burner is properly secured and aligned with pilot
or igniter.
• Clean off burner top, inspect for plugged ports, corrosion
or deterioration. Replace burner if necessary.
• Replace Glowing embers with new dime-size pieces.
DO NOT block ports or obstruct lighting paths. Refer to
Section 14 for proper ember placement.
• Verify batteries have been removed from battery backup IPI systems to prevent premature battery failure or
leaking.
• Check for smooth lighting and ignition carryover to all
ports. Verify that there is no ignition delay.
• Inspect for lifting or other fl ame problems.
• Verify air shutter setting is correct. See Section 14 for
required air shutter setting. Verify air shutter is clear of
dust and debris.
• Inspect orifi ce for soot, dirt and corrosion. Verify orifi ce
size is correct. See Service Parts List for proper orifi ce
sizing.
• Verify manifold and inlet pressures. Adjust regulator as
required.
• Inspect pilot fl ame pattern and strength. See Figures 3.1
and 3.2 for proper pilot fl ame pattern. Clean or replace
orifi ce spud as necessary.
• Inspect thermocouple/thermopile or IPI fl ame sensing rod
for soot, corrosion and deterioration. Clean with emery
cloth or replace as required.
• Verify thermocouple/thermopile millivolt output. Replace
pilot as necessary. (Standing pilot only)
• Verify that there is not a short in fl ame sense circuit
by checking continuity between pilot hood and fl ame
sensing rod. Replace pilot as necessary. (IPI only)
NOTICE: Illustrations and photos refl ect typical installations and are for design purposes only . Illustrations/diagrams are not
drawn to scale. Actual product may vary from pictures in manual
Getting Started
Note: Dual venting configurations
ARE NOT allowed. Appliance MUST
be vented EITHER vertically OR
horizontally.
VERTICAL TERMINATION CAP
(SECTION 10.J)
NON-COMBUSTIBLE ROOF FLASHING
MAINTAINS MINIMUM CLEARANCE
AROUND PIPE (SECTION 10.G)
Heat & Glo direct vent gas appliances are designed to
operate with all combustion air siphoned from outside of
the building and all exhaust gases expelled to the outside.
No additional outside air source is required.
Installation MUST comply with local, regional, state and
national codes and regulations. Consult insurance carrier,
local building inspector, fi re offi cials or authorities having
jurisdiction over restrictions, installation inspection and
permits.
Before installing, determine the following:
• Where the appliance is to be installed.
• The vent system confi guration to be used.
• Gas supply piping requirements.
• Electrical wiring requirements.
• Framing and fi nishing details.
• Whether optional accessories—devices such as a fan,
wall switch, or remote control—are desired.
Improper installation, adjustment, alteration, service or
maintenance can cause injury or property damage. For
assistance or additional information, consult a qualifi ed
service technician, service agency or your dealer.
C. Tools and Supplies Needed
Before beginning the installation be sure that the following
tools and building supplies are available.
Tape measure Framing material
Pliers High temperature caulking material
Hammer Phillips screwdriver
Gloves Framing square
Voltmeter Electric drill and bits (1/4 in.)
Plumb line Safety glasses
Level Reciprocating saw
Manometer Flat blade screwdriver
Non-corrosive leak check solution
1/2 - 3/4 in. length, #6 or #8 Self-drilling screws
One 1/4 in. female connection (for optional fan).
D. Inspect Appliance and Components
• Carefully remove the appliance and components from
the packaging.
• The vent system components and decorative doors and
fronts may be shipped in separate packages.
• If packaged separately, the log set and appliance grate
must be installed.
• Report to your dealer any parts damaged in shipment,
particularly the condition of the glass.
• Read all of the instructions before starting the instal-
lation. Follow these instructions carefully during the
installation to ensure maximum safety and benefi t.
WARNING! Risk of Fire or Explosion! Damaged parts
could impair safe operation. DO NOT install damaged, incomplete or substitute components. Keep appliance dry.
Hearth & Home T echnologies disclaims any responsibility for ,
and the warranty will be voided by, the following actions:
• Installation and use of any damaged appliance or vent
system component.
• Modifi cation of the appliance or vent system.
• Installation other than as instructed by Hearth & Home
Technologies.
• Improper positioning of the gas logs or the glass door.
• Installation and/or use of any component part not approved
by Hearth & Home Technologies.
Any such action may cause a fi re hazard.
WARNING! Risk of Fire, Explosion or Electric Shock!
DO NOT use this appliance if any part has been under
water. Call a qualifi ed service technician to inspect the
appliance and to replace any part of the control system
and/or gas control which has been under water.
When selecting a location for the appliance it is important to
consider the required clearances to walls (see Figure 5.1).
WARNING! Risk of Fire or Burns! Provide adequate
clearance around air openings and for service access.
Due to high temperatures, the appliance should be located out of traffi c and away from furniture and draperies.
A
1/2 IN.
G
A
B
C
TOP VENT
ONE 90º ELBOW
B
ALCOVE
INSTALLATION
NOTICE: Illustrations refl ect typical installations and are
FOR DESIGN PURPOSES ONLY. Illustrations/diagrams
are not drawn to scale. Actual installation may vary due to
individual design preference.
A chase is a vertical box-like structure built to enclose the
gas appliance and/or its vent system. In cooler climates
the vent should be enclosed inside the chase.
NOTICE: Treatment of ceiling fi restops and wall shield
fi restops and construction of the chase may vary with the
type of building. These instructions are not substitutes
for the requirements of local building codes. Therefore,
you MUST check local building codes to determine the
requirements to these steps.
Chases should be constructed in the manner of all outside walls of the home to prevent cold air drafting problems. The chase should not break the outside building
envelope in any manner.
Walls, ceiling, base plate and cantilever fl oor of the chase
should be insulated. Vapor and air infi ltration barriers
should be installed in the chase as per regional codes for
the rest of the home. Additionally, in regions where cold
air infi ltration may be an issue, the inside surfaces may be
sheetrocked and taped for maximum air tightness.
To further prevent drafts, the wall shield and ceiling fi re-
stops should be caulked with high temperature caulk to
seal gaps. Gas line holes and other openings should be
caulked with high temperature caulk or stuffed with unfaced insulation. If the appliance is being installed on a
cement surface, a layer of plywood may be placed underneath to prevent conducting cold up into the room.
C. Clearances
NOTICE: Install appliance on hard metal or wood surfaces
extending full width and depth. DO NOT install directly
on carpeting, vinyl, tile or any combustible material other
than wood.
WARNING! Risk of Fire! Maintain specifi ed air space
clearances to appliance and vent pipe:
• Insulation and other materials must be secured to prevent
accidental contact.
• The chase must be properly blocked to prevent blown
insulation or other combustibles from entering and
making contact with fi replace or chimney.
• Failure to maintain airspace may cause overheating and
a fi re.
A
E
F
B
C
D
G
J
I
*MINIMUM FRAMING DIMENSIONS
ABC**DEFGHIJ
Rough
Opening
(Vent Pipe)
Inches1038-1/2224226-5/8001/21/236
Rough
Opening
(Height)
Rough
Opening
(Depth)
Rough
Opening
(Width)
Clearance
to Ceiling
Combustible
Floor
Combustible
Flooring
Behind
Appliance
Sides of
Appliance
Front of
Appliance
H
Millimeters25497855910676760013 13915
* Adjust framing dimensions for interior sheathing (such as sheetrock)
C** Add 12 inches for rear venting with one 90º elbow.
WARNING! Risk of Fire! Comply with all minimum clearances as specifi ed. Framing or fi nishing material closer than
the minimums listed must be constructed entirely of noncombustible materials (i.e., steel studs, concrete board, etc).
Combustible Mantel Legs or Wall Projections
INTERIOR WALL
Combustible Mantels
4
3
2-1/2
5
Note: All measurements in inches.
18
12
11
10
9
8
7
6
5
14
13
12
11
10
MEASUREMENTS FROM
TOP EDGE OF THE OPENING
17
16
15
TO CEILING
25
19
18
32
TOP VIEW
A
FIREPLACE OPENING
MANTEL LEG OR WALL PROJECTIONS
B
If A minimum is ____, then B maximum is_____.
Inches
A
B
2-7/16 3-7/16 4-7/16 5-7/16 6-7/16 7-7/16
Millimeters
Inches
Millimeters
6287113138164189
12345
255176102127
∞
∞
Figure 5.4 Clearances to Mantel Legs or Wall Projections
(Acceptable on both sides of opening.)
Note: Measurement is taken from top of the
opening, NOT the top of the fi replace.
Figure 5.3 Minimum Vertical and Maximum Horizontal
Dimensions of Combustibles
A = 12 inches.................clearances above grade, veranda,
(See Note 1)
porch, deck or balcony
B = 12 inches.................clearances to window or door
that may be opened, or to permanently closed window. (Glass)
C = 18 inches.................vertical clearance to unventilated
soffi t or to ventilated soffi t located
above the terminal
30 inches .................for vinyl clad soffi ts and below
electrical service
D = 9 inches...................clearance to outside corner
E = 6 inches...................clearance to inside corner
F = 3 ft. (Canada) ..........not to be installed above a gas
meter/regulator assembly within 3
feet (90 cm) horizontally from the
center-line of the regulator
G = 3 ft ...........................clearance to gas service regulator
vent outlet
H = 9 inches (U.S.A.)
12 inches (Canada) clearance to non-mechanical
(See Note 2)
air supply inlet to building or the
combustion air inlet to any other
appliance
i = 3 ft. (U.S.A.)
6 ft. (Canada) ...........clearance to a mechanical (pow-
(See Note 2)
** a vent shall not terminate directly above a sidewalk or paved driveway
which is located between two single family dwellings and serves both
dwellings.
*** only permitted if veranda, porch, deck or balcony is fully open on a
minimum of 2 sides beneath the fl oor, or meets Note 2.
Note 1: On private property where termination is less than 7 feet above a
sidewalk, driveway, deck, porch, veranda or balcony, use of a listed cap
shield is suggested. (See vents components page)
Note 2: Termination in a covered alcove space (spaces open only on one
side and with an overhang) are permitted with the dimensions specifi ed
for vinyl or non-vinyl siding and soffi ts. 1. There must be 3 feet minimum
between termination caps. 2. All mechanical air intakes within 10 feet
of a termination cap must be a minimum of 3 feet below the termination
cap. 3. All gravity air intakes within 3 feet of a termination cap must be a
minimum of 1 foot below the termination cap.
Figure 6.3 Minimum Clearances for Termination
ered) air supply inlet
= AREA WHERE TERMINAL IS NOT PERMITTED
J** = 7 ft. ......................... clearance above paved
(See Note 1)
sidewalk or a paved driveway
located on public property
K = 6 inches................. clearance from sides of electri-
(See Note 5)
cal service
L = 12 inches................ clearance above electrical
(See Note 5)
service
Covered Alcove Applications
M*** = 18 inches .............clearance under veranda, porch,
42 inches ......... vinyl
N = 6 inches ........... non-vinyl sidewalls
12 inches .........vinyl sidewalls
O = 18 inches ......... non-vinyl soffi t and overhang
42 inches .........vinyl soffi t and overhang
P = 8 ft.
1 cap3 feet 2 x Q
2 caps6 feet 1 x Q
3 caps9 feet2/3 x Q
4 caps12 feet1/2 x Q
Q
= # termination caps x 3 R
MIN
Note 3: Local codes or regulations may require different
clearances.
Note 4: Termination caps may be hot. Consider their proximity to
doors or other traffi c areas.Note 5: Location of the vent termination must not interfere with
access to the electrical service.
In the U.S and Canada: Vent system termination is NOT permitted
in screened porches.
Vent system termination is permitted in porch areas with two or more
sides open. You must follow all side walls, overhang and ground
clearances as stated in the instructions.
Heat & Glo assumes no responsibility for the improper performance
of the appliance when the venting system does not meet these
requirements.
deck, balcony or overhang
Q
MIN
= (2 / # termination caps) x Q
MAX
R
MAX
ACTUAL
ACTUAL
ACTUAL
ACTUAL
ACTUAL
CAUTION: IF EXTERIOR WALLS ARE FINISHED WITH VINYL SIDING, IT IS SUGGESTED THAT A VINYL PROTECTOR KIT BE INSTALLED.
This appliance is approved for use with Hearth & Home
T echnologies DVP or SLP venting systems. Refer to Section 16B for vent component information.
DO NOT mix pipe, fi ttings or joining methods from differ-
ent manufacturers.
The pipe is tested to be run inside an enclosed wall.
There is no requirement for inspection openings at each
joint within the wall.
WARNING! Risk of Fire or Asphyxiation. This appliance requires a separate vent. DO NOT vent to a pipe
serving a separate solid fuel burning appliance.
Vertical
12 in.
8-1/2 in.
8-1/2 in.
B. Vent Table Key
The abbreviations listed in this vent table key are used in
the vent diagrams.
SymbolDescription
First section (closest to appliance) of vertical length
V
1
Second section of vertical length
V
2
First section (closest to appliance) of horizontal length
H
1
Subsequent sections of horizontal length
H
2
C. Use of Elbows
Diagonal runs have both vertical and horizontal vent aspects when calculating the effects. Use the rise for the
vertical aspect and the run for the horizontal aspect (see
Figure 7.1).
Two 45º elbows may be used in place of one 90º elbow.
On 45º runs, one foot of diagonal is equal to 8-1/2 in. (216
mm) horizontal run and 8-1/2 in. (216 mm) vertical run. A
length of straight pipe is allowed between two 45º elbows
(see Figure 7.1).
Horizontal
Figure 7.1
D. Measuring Standards
Vertical and horizontal measurements listed in the vent
diagrams were made using the following standards.
• Pipe measurements are shown using the effective length
of pipe (see Figure 7.2).
• Horizontal terminations are measured to the outside
mounting surface (fl ange of termination cap) (see Figure
6.3).
• Vertical terminations are measured to bottom of
termination cap.
• Horizontal pipe installed level with no rise.
Effective Length
InchesMillimeters
Effective
Height/Length
Pipe
DVP44102
DVP66152
DVP1212305
DVP2424610
DVP3636914
DVP48481219
DVP6A3 to 676 to 152
DVP12A 3 to 12 76 to 305
DVP12MI 3 to 12 76 to 305
DVP24MI 3 to 24 76 to 610
E. Vent Diagrams
Top Vent - Horizontal Termination
Note: The 6000 series fi replaces can adapt to SLP series vent
pipe, if desired.
When venting off the top of the unit, use a DVP-2SL adapter and a
minimum 48 inch vertical section of SLP series vent pipe.
A DVP-SLP24 adapter may also be used with a 24 inch vertical
section of SLP series vent pipe.
After the 48 inch vertical section, the venting table rules must be
followed. The fi rst 48 inch vertical section is NOT counted as part
of the vertical components in the table. It is still counted as part of
the overall maximum run. All venting table rules for the vent run
must still be followed.
Example: DVP pipe 3 ft. min. vertical = 11 ft. max. horizontal
SLP pipe 7 ft. min. vertical = 11 ft. max. horizontal
Top Vent - Horizontal Termination
One Elbow
H
1
WARNING
Fire Risk. Explosion Risk.
Do NOT pack insulation or other combustibles
between ceiling fi restops.
• ALW A YS maintain specifi ed clearances around
venting and fi restop systems.
• Install wall shield and ceiling fi restops as speci-fi ed.
Failure to keep insulation or other material away
from vent pipe may cause fi re.
WARNING
Fire Risk.
• When using DVP-HRC-SS and DVP-HRC-ZCSS termination caps on top vented fi replaces, a
6 inch minimum vertical vent section is required
before installing fi rst elbow.
V1 MinimumH1 Maximum
Elbow only2 ft 610 mm
1 ft.305 mm3 ft. 914 mm
2 ft.610 mm6 ft. 1.8 m
3 ft.914 mm11 ft.3.4 m
V
1
4 ft. 1.2 m20 ft. 6.1 m
+ H1 = 40 ft. (12.2 m) Maximum
V
1
H
= 20 ft. (6.1 m) Maximum
1
Figure 7.3
Two Elbows
H
2
Figure 7.4
INSTALLED
HORIZONTALLY
Note: For corner installations: A 6 inch
(152 mm) section of straight pipe may
need to be attached to the appliance
before a 90º elbow, to allow the vent
pipe to clear the top standoffs.
V
H
1
Note: For corner installations: A 6 inch (152
mm) section of straight pipe may need to
be attached to the appliance before a 90º
elbow, to allow the vent pipe to clear the top
standoffs.
V1 MinimumH1 + H2 Maximum
Elbow only1 ft.305 mm
6 in. 152 mm2 ft.610 mm
1 ft.305 mm2 ft.610 mm
2 ft.610 mm4 ft. 1.2 m
3 ft.914 mm9 ft. 2.7 m
4 ft. 1.2 m18 ft. 5.5 m
5 ft.1.5 m20 ft. 6.1 m
WARNING! Risk of Fire! Maintain air space clearance to
vent. DO NOT pack insulation or other combustibles:
• Between ceiling fi restops
• Between wall shield fi restops
• Around vent system
Failure to keep insulation or other material away from
vent pipe may cause over heating and fi re.
Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm).
• DVP heat shield - designed to be used on a wall 4 in. to 7-1/4 in. (102 mm to 184
mm) thick.
• If wall thickness is less than 4 in. the existing heat shields must be field trimmed. If
wall thickness is greater than 7-1/4 in. a DVP-HSM-B will be required.
• SLP heat shield - designed to be used on a wall 4-3/8 in. to 7-5/8 in. (111 mm to
194 mm thick).
• If wall thickness is less than 4-3/8 the existing heat shields must be field trimmed.
If wall thickness is greater than 7-5/8 in. a DVP-HSM-B will be required.
(DVP-SLP Pipe Shown)
3 in. (76 mm)
top clearance
1 in. (25 mm)
clearance around
vertical sections
Heat
Shield
Wall
Shield
Firestop
3 in. (76 mm)
top clearance *
Heat
Shield
1 in. (25 mm)
clearance
bottom & sides
B. Wall Penetration Framing
Combustible Wall Penetration
Whenever a combustible wall is penetrated, you must
frame a hole for the wall shield fi restop(s). The wall shield fi restop maintains minimum clearances and prevents cold
air infi ltration.
• The opening must be framed on all four sides using the
same size framing materials as those used in the wall
construction.
• SLP pipe - A wall shield fi restop must be placed on each
side of an interior wall. A minimum 1-1/2 in. (38 mm)
overlap of attached heat shields must be maintained.
• DVP pipe - A wall shield fi restop is required on one side
only on interior walls. If your local inspector requires a
wall shield fi restop on both sides, then both wall shield fi restops must have a heat shield (refer to Section 16.B.)
attached to them.
• See Section 10.M. for information for regarding the installation of a horizontal termination cap.
Non-Combustible Wall Penetration
If the hole being penetrated is surrounded by noncombustible materials such as concrete, a hole with diameter
one inch greater than the pipe is acceptable.
Whenever a non-combustible wall is penetrated, the wall
shield fi restop is only required on one side and no heat
shield is necessary.
WALL
Heat
Shield
Wall
Shield
Firestop
WALL
* When using SLP or SL-D pipe, minimum clearances from the vent pipe to combus-
tible materials at inside wall firestops are: T op: 2-1/2 in. (64 mm)
Bottom: 1/2 in. (13 mm)
Sides: 1 in. (25 mm)
Figure 8.1 Horizontal Venting Clearances To Combustible
Materials
3 in. (76 mm)
top clearance *
Heat
Shield
1 in. (25 mm)
clearance
bottom & sides
10 in.
10 in.
A*
B*
Inches42-3/427-7/841-3/426-7/8
* Shows center of vent framing hole for top or rear venting. The center of the
hole is one (1) in. (25.4 mm) above the center of the horizontal vent pipe.
A ceiling fi restop MUST be used between
fl oors and attics.
• DVP pipe only - Frame an opening 10 in.
by 10 in. (254 mm by 254 mm) whenever
the vent penetrates a ceiling/fl oor (see
Figure 8.3).
• SLP pipe only - Frame opening 9 in. x 9
in. (229 mm x 229 mm) whenever the vent
penetrates a ceiling/fl oor (see Figure 8.3).
• Frame the area with the same sized lumber
as used in ceiling/fl oor joist.
• The ceiling fi restop may be installed above or
below the ceiling joists when installed with a
attic insulation shield. It must be under joists
between fl oors that are not insulated. Refer
to Figure 8.4.
• Secure with three fasteners on each side.
WARNING! Risk of Fire! DO NOT pack insu-
lation around the vent. Insulation must be kept
back from the pipe to prevent overheating.
WARNING! Fire Risk. DO NOT allow loose materials or
insulation to touch vent. Hearth & Home Technologies
Inc. requires the use of an attic shield.
The National Fuel Gas Code ANSI Z223.1 and NFPA 54
requires an attic shield constructed of 26 gauge minimum
metal that extends at least 2 in. (51 mm) above insulation.
Attic shields must meet specifi ed clearance and be se-
cured in place.
Flat Ceiling Installation
• Remove one shield from box.
NOTICE: Cut previously installed batt insulation to make
room for the attic insulation shield.
• Wrap shield around pipe if pipe is already installed in
area to be insulated.
• Match the three holes in each side and fasten with three
screws to form a tube.
• Bend three tabs on the bottom of the shield outward to
allow attachment to the ceiling fi restop.
• Bend the remaining bottom tabs inward 90º to maintain
the air space between the pipe and the shield. Set the
shield on the ceiling fi restop and attach to the fi restop.
• Bend all tabs inward 90º around the top of the shield.
These tabs must be used to prevent blown insulation
from getting between the shield and vent pipe, and to
maintain air space clearance.
Vaulted Ceiling Installation
• Remove one shield from box.
NOTICE: Cut previously installed batt insulation to make
room for the attic insulation shield.
• Cut the attic insulation shield (if application is for vaulted
ceiling) to fi t your ceiling pitch. Snip cut edge to recreate
1 in. bend tabs all the way around the bottom.
• Wrap shield around pipe if pipe is already installed in
area to be insulated.
• Match the three holes in each side and fasten with three
screws to form a tube.
• Bend three tabs on the bottom of the shield outward to
allow attachment to the ceiling fi restop.
• Bend the remaining bottom tabs inward 90º to maintain
the air space between the pipe and the shield. Set the
shield on the ceiling fi restop and attach to the fi restop.
• Bend all tabs inward 90º around the top of the shield.
These tabs must be used to prevent blown insulation
from getting between the shield and vent pipe, and to
maintain air space clearance.
BEND ALL TABS INWARD 90°
TO MAINTAIN CLEARANCE
AND PREVENT INSULATION
FROM FALLING INSIDE
BEND 3 TABS
OUTWARD TO
FASTEN TO CEILING
FIRESTOP-BEND
REMAINING TABS
INWARD 90 DEGREES
TO MAINTAIN
INSERT 3
SCREWS
Figure 8.5 Attic Insulation Shield
CLEARANCE
E. Installing the Optional Heat-Zone-Gas Kit
• Remove the knockout from the fi replace and discard it
(see Figure 8.6).
• Center the duct collar around the exposed hole and
attach it to the fi replace with 3 screws. Note: Do this
BEFORE fi nal positioning of fi replace.
• Determine the location for the air register/fan housing
assembly.
Reference the Heat-Zone-Gas kit instructions for the
remaining installation steps.
CAUTION! Risk of Cuts, Abrasions or Flying Debris.
Wear protective gloves and safety glasses during installation. Sheet metal edges are sharp.
NOTICE: Once appliance is set up for top or rear venting,
it CANNOT be changed at a later time.
Figure 7.1 For top vent, remove the two screws holding the
elbow heat shield in place. Use this heat shield over the
fi rst elbow if applicable. For rear vent skip this step.
Appliance Preparation
Figure 7.4 Fold the center parts of the retaining band up
and use to remove the vent cap.
Figure 7.2 Cut the seal cap strap across the rectangles
next to the disk.
Figure 7.3 Remove the white gasket material covering
the seal cap.
Figure 7.5 Discard the vent cap, remove and discard
the insulation basket. Note: Once the vent cap has been
removed it cannot be reattached.
Proceed to Section 10.
Page 38
B. Rear Vent
NOTICE: Once appliance is set up for top or rear venting,
it CANNOT be changed at a later time.
Figure 9.6 Fold the tabs toward the center of the seal
cap (90º) and remove the insulation gasket.
NOTICE: Once the seal cap has been removed it CANNOT
be reattached.
Figure 9.7 Cut the metal retaining band and fold the
sides out.
Figure 9.9 Discard the vent cap, remove and discard the
insulation basket.
Figure 9.10 Attach the fi rst vent section (it will snap into
place). Slide the insulation gasket onto the vent section,
up against the appliance and over the tabs.
Figure 9.8 Fold the center parts of the retaining band out
and use to remove the seal cap.
The factory supplied non-combustible board spans the
distance from the top of the fi replace to the center of
the framing header. This board must be used. See
figure 9.11.
HEADER
Figure 9.11 Non-combustible Board
D. Securing and Leveling the Appliance
WARNING! Risk of Fire! Prevent contact with:
• Sagging or loose insulation
• Insulation backing or plastic
• Framing and other combustible materials
Block openings into the chase to prevent entry of blown-
in insulation. Make sure insulation and other materials
are secured.
DO NOT notch the framing around the appliance
standoffs.
Failure to maintain air space clearance may cause
overheating and fi re.
The diagram shows how to properly position and secure
the appliance (see Figure 9.12). Nailing tabs are provided
to secure the appliance to the framing members.
• Bend out nailing tabs on each side.
• Place the appliance into position.
• Keep nailing tabs fl ush with the framing.
• Level the appliance from side to side and front to back.
• Shim the appliance as necessary. It is acceptable to use
wood shims underneath the appliance.
• Secure the appliance to the framing by using nails or
screws through the nailing tabs.
• Secure the appliance to the fl oor by inserting two screws
through the pilot holes at the bottom of the appliance.
NAILING TABS
(BOTH SIDES)
PILOT HOLES
Figure 9.12 Proper Positioning and Securing of an Appliance
Note: The end of the pipe sections with the lanced tabs will face
toward the appliance.
Attach the fi rst pipe section to the starting collar:
• Lanced pipe end to the starting collar
• Inner pipe over inner collar
• Push the pipe section until all lanced tabs snap in place
• Lightly tug on pipe to confi rm it has locked.
Commercial, Multi-family (Multi-level exceeding two stories), or High-Rise Applications
All outer pipe joints must be sealed with high temperature
silicone, including the slip section that connects directly to
the horizontal termination cap.
• Apply a bead of silicone sealant inside the female outer
pipe joint prior to joining sections. See Figure 10.1
• Only outer pipes need to be sealed. All unit collar, pipe,
slip section, elbow and cap outer fl ues shall be sealed
in this manner, unless otherwise stated.
Figure 10.1 High Temperature Silicone Sealant
A
Lances
WARNING! Risk of Fire or Explosion! DO NOT break
silicone seals on slip sections. Use care when removing termination cap from slip pipe. If slip section seals
are broken during removal of the termination cap, vent
may leak.
Assemble Pipe Sections
Per Figure 10.2:
• Start the inner pipe on the lanced end of section A into
the fl ared end of section B.
• Start the outer pipe of section A over the outer pipe of
section B.
• Once both vents sections are started, push fi rmly until
all lanced tabs lock into place.
• Lightly tug on the pipe to confi rm the tabs have locked.
It is acceptable to use screws no longer than 1/2 in. (13
mm) to hold outer pipe sections together. If predrilling holes,
DO NOT penetrate inner pipe.
For 90º and 45º elbows that are changing the vent direction
from horizontal to vertical, one screw minimum should be
put in the outer fl ue at the horizontal elbow joint to prevent
the elbow from rotating. Use screws no longer than 1/2
in. (13 mm). If predrilling screw holes, DO NOT penetrate
inner pipe.
B
Figure 10.2
Note: Make sure that the seams are not aligned to prevent
To attach the fi rst vent component to the starting collars
of the appliance:
• Attach a DVP-2SL or DVP-SLP24 adapter to the starting
collar of the appliance.
• Lock the vent components into place by sliding the pipe
section onto the collar.
• Align the seam of the pipe and seam of collar to allow
engagement. Rotate the vent component to lock into
place. Use this procedure for all vent components. See
Figure 10.5.
• Slide the gasket over the fi rst vent section and place it fl ush to the appliance. This will prevent cold air infi ltration.
High temperature caulk may be used to hold the part in
place.
• Continue adding vent components, locking each
succeeding component into place.
• Ensure that each succeeding vent component is securely
fi tted and locked into the preceding component.
Commercial, Multi-family (Multi-level exceeding two stories), or High-Rise Applications
For Installation into a commercial, multi-family (multi-level
exceeding two stories) or high-rise applications: All outer
pipe joints must be sealed with high temperature silicone,
including the slip section that connects directly to the horizontal termination cap.
• Apply a bead of silicone sealant inside the female outer
pipe joint prior to joining sections. See Figure 10.1.
• Only outer pipes need to be sealed. All unit collar, pipe,
slip section, elbow and cap outer fl ues shall be sealed
in this manner, unless otherwise stated.
C. Assemble Slip Sections
• Slide the inner fl ue of the slip section into the inner fl ue of
the pipe section and the outer fl ue of the slip section over
the outer fl ue of the pipe section. See Figure 10.6.
• Slide together to the desired length.
Pilot hole
Figure 10.6 Slip Section Pilot Holes
• Maintain a 1-1/2 in. (38 mm) overlap between the slip
section and the pipe section.
• Secure the pipe and slip section with two screws no
longer than 1/2 in. (13 mm), using the pilot holes in the
slip section. See Figure 10.7.
WARNING! Risk of Fire or Explosion! DO NOT break
silicone seals on slip sections. Use care when removing termination cap from slip pipe. If slip section seals
are broken during removal of the termination cap, vent
may leak.
Note: Align seams to engage pipe,
then rotate counterclockwise to lock
Figure 10.5 Adding Venting Components
Figure 10.7 Screws into Slip Section
• Continue adding pipe as necessary following instructions
in “Assembling Pipe Sections.”
NOTICE: If slip section is too long, the inner and outer fl ues
of the slip section can be cut to the desired length.
NOTICE: When installing a vent system with an HRC
termination cap, all pipe system joints shall be sealed using
a high temperature silicone sealant.
• Apply a bead of silicone sealant inside the female outer
pipe joint prior to joining sections.
• Only outer pipes are sealed, sealing the inner fl ue is not
required.
• All unit collar, pipe, slip section, elbow and cap outer
fl ues shall be sealed.
• Vertical runs of DVP pipe must be supported every 8 ft.
(2.44 m) after the 25 ft. (7.62 m) maximum unsupported
rise.
• Vertical runs of SLP pipe must be supported every 8 ft.
(2.44 m).
• Horizontal sections must be supported every 5 feet
(1.52 m).
• Vent supports or plumbers strap (spaced 120º apart)
may be used to support vent sections. See Figures 10.8
and 10.9.
• Wall shield fi restops may be used to provide horizontal
support vent sections.
• SLP ceiling fi restops have tabs that may be used to
provide vertical support.
WARNING! Risk of Fire, Explosion or Asphyxiation!
Improper support may allow vent to sag and separate.
Use vent run supports and connect vent sections per installation instructions. DO NOT allow vent to sag below
connection point to appliance.
E. Disassemble Vent Sections
• Rotate either section (see Figure 10.10) so the seams
on both pipe sections are aligned as shown in Figure
A decorative ceiling thimble can be installed on a fl at ceil-
ing through which the vent passes. The decorative ceiling
thimble is used to cover the fi restop.
• Seal the gap between the vent pipe and fi restop using
high temperature silicone to prevent cold air infi ltration.
• Install the decorative ceiling thimble by sliding it up to
the ceiling and attaching it using the provided screws.
A decorative cathedral ceiling support box can be installed
on a cathedral ceiling through which the vent passes.
• Use a plumb-bob to mark the center line of the venting
system on the ceiling and drill a small hole through the
ceiling and roof at this point. Locate the hole and mark
the outline of the cathedral ceiling support box on the
outside roof.
• Remove shingles or other roof covering as necessary
to cut the rectangular hole for the support box. Cut the
hole 1/8 in. (3 mm) larger than the support box outline.
• Lower the support box through the hole in the roof until its
bottom is at least 2 in. (51 mm) below the ceiling (Figure
10.12).
• Level the support box both vertically and horizontally and
temporarily tack it in place through the inside walls into
the roof sheathing.
• Use tin snips to cut the support box from the top corners
down to the roof line and fold the resulting fl aps to the
roof. See Figure 10.13.
• Nail the fl aps to the roof AFTER running a bead of non
hardening sealant between the fl aps and the roof.
WARNING! Risk of Fire! Clean out ALL materials from
inside the support box and complete the vertical vent run
and termination.
LEVEL
CATHEDRAL CEILING
SUPPORT BOX
2 in. (51 mm) MIN. BELOW
FINISHED CEILING
CUT HOLE 1/8 in. (3 mm)
GREATER IN SIZE THAN
PATTERN OF SUPPORT
BOX AS IT IS PROJECTED
ONTO ROOF LINE
Figure 10.17 Assembling the Storm Collar Around the Pipe
Figure 10.15
Note: Skip this section if using the RF4-8.
• See minimum vent heights for various pitched roofs
(Figure 10.14) to determine the length of pipe to extend
through the roof.
• Slide the roof fl ashing over the pipe sections extending
through the roof as shown in Figure 10.15.
HORIZONTAL
OVERHANG
CAULK
2 FT.
MIN.
GAS DIRECT VENT
TERMINATION CAP
Roof Pitch H (Min.) Ft.
Flat to 6/12........................................1.0*
Over 6/12 to 7/12 ............................1.25*
Over 7/12 to 8/12 ..............................1.5*
Over 8/12 to 9/12 ..............................2.0*
Over 9/12 to 10/12 ............................. 2.5
Over 10/12 to 11/12 ......................... 3.25
Over 11/12 to 12/12 ........................... 4.0
Over 12/12 to 14/12 ........................... 5.0
Over 14/12 to 16/12 ........................... 6.0
Over 16/12 to 18/12 ........................... 7.0
Over 18/12 to 20/12 ........................... 7.5
Over 20/12 to 21/12 ........................... 8.0
20 INCHES MIN.
LOWEST
DISCHARGE
OPENING
X
12
ROOF PITCH
H (MIN.) - MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING
* 3 foot minimum in snow regions
VERTICAL
WALL
IS X/ 12
Figure 10.15
H. Assemble and Install Storm Collar
CAUTION! Risk of Cuts, Abrasions or Flying Debris.
Wear protective gloves and safety glasses during installation. Sheet metal edges are sharp.
• Connect both halves of the storm collar with two screws
(see Figure 10.16).
• Wrap the storm collar around the exposed pipe section
closest to the roof and align brackets. Insert a bolt
(provided) through the brackets and tighten the nut to
complete the storm collar assembly . Make sure the collar
is tight against the pipe section.
• Slide the assembled storm collar down the pipe section
until it rests on the roof fl ashing (see Figure 10.17).
• Caulk around the top of the storm collar (see Figure 10.23).
Figure 10.14 Minimum Height From Roof To Lowest Discharge
Opening
NOTICE: Failure to properly caulk the roof fl ashing could
cause water entry.
• Caulk the gap between the roof fl ashing and the outside
diameter of the pipe.
• Caulk the perimeter of the fl ashing where it contacts the
roof surface. See Figure 10.15.
Figure 10.17 Assembling the Storm Collar Around the Pipe
Page 45
I. Install RF4-8
The RF4-8 may be used in place of the roof fl ashing and
storm collar (Sections 10.G. and 10.H.)
Pipe must be supported within 12 inches of the roofline
using plumbers strapping or an SLP-FS when using
the RF4-8 Flashing. Refer to Section 10.D. Secure
Vent Sections.
SECURE WITH 4
SCREWS NO LONGER
THAN 1 IN. (25 MM)
SLP-FS
Figure 10.18 Secure Pipe with SLP-FS
Figure 10.20 Apply Sealant
• Trim the rubber boot (using scissors or a utility knife),
cutting along the marked measurement lines. See Figure
10.19. Use the 150 mm line for SLP, 210 mm for DVP.
• Lubricate pipe or fl ue with water and slide the fl ashing
down. It may be necessary to trim the top shingles around
the base of the rubber boot to ensure a good fi t.
• Draw a line around fl ashing. Remove fl ashing.
• Apply silicone sealant to roof inside the lines (Figure 10.20).
• Lubricate pipe or fl ue with water and slide fl ashing down.
Seat fi rmly in sealant. Nail roof fl ashing to the roof.
• Apply silicone sealant on the top and sides edges of the
fl ashing. See Figure 10.21. Install shingles. Apply sealant
at the top edge of the rubber boot. See Figure 10.22.
• We recommend that you top coat with conventional
acrylic house paint to improve the appearance of your
galvanized base fl ashing.
• Attach the vertical termination cap by sliding the inner
collar of the cap into the inner fl ue of the pipe section
while placing the outer collar of the cap over the outer
fl ue of the pipe section.
• Secure the cap by driving three self-tapping screws
(supplied) through the pilot holes in the outer collar of the
cap into the outer fl ue of the pipe (see Figure 10.23).
TERMINATION CAP
(1 of 3)
STORM
COLLAR
SCREWS
CAULK
Figure 10.23
K. Install Decorative Wall Components (SLP
only)
A decorative wall thimble can be installed on wall through
which the vent passes. The decorative wall thimble is used
to cover the wall shield fi restop.
• Slide the decorative wall thimble over the last section of
horizontal pipe before connecting the termination cap to
the pipe.
• Once the pipe section and the termination cap have been
connected, slide the wall thimble up to the interior wall
surface and attach with screws provided. See Figure
10.24.
L. Heat Shield Requirements for Horizontal
Termination
WARNING! Risk of Fire! To prevent overheating and fi re,
heat shields must extend through the entire wall thickness.
• DO NOT remove the heat shields attached to the
wall shield fi restop and the horizontal termination cap
(shown in Figure 10.25).
• Heat shields must overlap 1-1/2 in. (38 mm) minimum.
There are two sections of the heat shield. One section
is factory-attached to the wall shield fi restop. The other
section is factory-attached to the cap. See Figure 10.25.
If the wall thickness does not allow the required 1-1/2 in.
(38 mm) heat shield overlap when installed, an extended
heat shield must be used.
• If the wall thickness is less than 4 in./102 mm (DVP)
or 4-3/8 in./ 111 mm (SLP), the heat shields on the cap
and wall shield fi restop must be trimmed. A minimum
1-1/2 in. (38 mm) overlap MUST be maintained.
• Use an extended heat shield if the fi nished wall thickness
is greater than 7-1/4 in. (184 mm).
• The extended heat shield may need to be cut to length
maintaining suffi cient length for a 1-1/2 in. (38 mm)
overlap between heat shields.
• Attach the extended heat shield to either of the existing
heat shields using the screws supplied with the extended
heat shield. Refer to vent components diagrams in the
back of this manual.
• Rest the small leg on the extended heat shield on top
of the pipe section to properly space it from the pipe
section.
Important Notice: Heat shields may not be fi eld constructed.
WARNING! Risk of Fire! The telescoping fl ue section of
the termination cap MUST be used when connecting vent.
• 1-1/2 (38 mm) minimum overlap of fl ue telescoping
section is required.
Failure to maintain overlap may cause overheating and
fi re.
• Vent termination must not be recessed in the wall. Siding
may be brought to the edge of the cap base.
• Flash and seal as appropriate for siding material at
outside edges of cap.
• When installing a horizontal termination cap, follow
the cap location guidelines as prescribed by current
ANSI Z223.1 and CAN/CGA-B149 installation codes
and refer to Section 6 of this manual.
CAUTION! Risk of Burns! Local codes may require installation of a cap shield to prevent anything or anyone
from touching the hot cap.
NOTICE: For certain exposures which require superior
resistance to wind-driven rain penetration, a fl ashing kit and
HRC caps are available. When penetrating a brick wall, a
brick extension kit is available for framing the brick.
Note: When using termination caps with factory-supplied
heat shield attached, no additional wall shield fi restop is
required on the exterior side of a combustible wall.
HEAT SHIELD OR
EXTENDED
WALL SHIELD
FIRESTOP
INNER VENT
OUTER VENT
VENT DEPTH FROM BACK OF APPLIANCE TO
OUTSIDE SURFACE OF EXTERIOR WALL
Figure 10.25 Venting through the wall
HEAT SHIELD
SLIP SECTION
CAN BE EXTENDED
(SEE CHART BELOW)
INTERIOR
Cap Specifi cation Chart
(depth without using additional pipe sections)
DVP-TRAPK1
Top Vent
Depth
2-3/4 in. to
6000
Series
DVP-TRAP1 can adjust 1-1/2 in. (3-1/8 to 4-5/8 in.)
DVP-TRAP2 can adjust 4 in. (5-3/8 to 9-3/8)
DVP-HPC1 can adjust 2-1/8 in. (4-1/4 to 6-3/8)
DVP-HPC2 can adjust 4-1/8 in. (6-3/8 to 10-1/2)
• Gas line sizing requirements will be determined in ANSI
Z223.1 National Fuel Gas Code in the USA and CAN/
CGA B149 in Canada.
• Pressure requirements are:
Gas PressureNatural GasPropane
Minimum inlet pressure5.0 in. w.c.11.0 in. w.c.
Maximum inlet pressure14.0 in. w.c.14.0 in. w.c.
Manifold pressure3.5 in. w.c.10.0 in. w.c.
WARNING! Risk of Fire or Explosion! High pressure
will damage valve. Low pressure may cause explosion.
• Verify inlet pressures. Verify minimum pressures when
other household gas appliances are operating.
• Install regulator upstream of valve if line pressure is
greater than 1/2 psig.
WARNING
Fire Risk.
Explosion Hazard.
High pressure will damage valve.
• Disconnect gas supply piping BEFORE
pressure testing gas line at test pressures
above 1/2 psig.
• Close the manual shutoff valve BEFORE
pressure testing gas line at test pressures
equal to or less than 1/2 psig.
Note: Have the gas supply line installed in accordance with
local codes, if any. If not, follow ANSI 223.1. Installation
should be done by a qualifi ed installer approved and/or
licensed as required by the locality. (In the Commonwealth
of Massachusetts installation must be performed by a
licensed plumber or gas fi tter).
Note: A listed (and Commonwealth of Massachusetts approved) 1/2 in. (13 mm) T-handle manual shut-off valve
and fl exible gas connector are connected to the 1/2 in. (13
mm) control valve inlet.
• If substituting for these components, please consult
local codes for compliance.
C. Gas Connection
• Refer to Reference Section 16 for location of gas line
access in appliance.
• Gas line may be run through knockout(s) provided.
• The gap between supply piping and gas ac cess hole
may be caulked with high temperature caulk or stuf fe d
with non-combustible, unfaced insulation to prev ent cold
air infi ltration.
• Ensure that gas line does not come in contact with outer
wrap of the appliance. Follow local codes.
• Pipe incoming gas line into valve compartment.
• Connect incoming gas line to the 1/2 in. (13 mm)
connection on manual shutoff valve.
WARNING! Risk of Fire or Explosion! Support control
when attaching pipe to prevent bending gas line.
• A small amount of air will be in the gas supply lines.
WARNING! Risk of Fire or Explosion! Gas build-up dur ing line purge could ignite.
• Purge should be performed by qualified service
technician.
• Ensure adequate ventilation.
• Ensure there are no ignition sources such as sparks
or open fl ames.
Light the appliance. It will take a short time for air to purge
from lines. When purging is complete the appliance will
light and operate normally.
WARNING! Risk of Fire, Explosion or Asphyxiation!
Check all fi ttings and connections with a non-corrosive
commercially available leak-check solution. DO NOT use
open fl ame. Fittings and connections could have loos-
ened during shipping and handling.
WARNING! Risk of Fire! DO NOT change valve settings.
This valve has been preset at the factory.
D. High Altitude Installations
NOTICE: If the heating value of the gas has been reduced,
these rules do not apply. Check with your local gas utility
or authorities having jurisdiction.
When installing above 2000 feet elevation:
• In the USA: Reduce burner orifi ce 4% for each 1000 feet
above 2000 feet.
• In CANADA: Reduce burner orifi ce 10% for elevations
between 2000 feet and 4500 feet. Above 4500 feet,
consult local gas utility.
NOTICE: This appliance must be electrically wired
and grounded in accordance with local codes or, in the
absence of local codes, with National Electric Code
ANSI/NFPA 70-latest edition or the Canadian Electric
Code CSA C22.1.
• Wire the appliance junction box to 110-120 VAC. This is
required for use of optional accessories (standing pilot
ignition) or proper operation of the appliance (Intellifi re
ignition).
• A 1 10-120 V AC circuit for this product must be protected
with ground-fault circuit-interrupter protection, in
compliance with the applicable electrical codes, when
it is installed in locations such as in bathrooms or near
sinks.
• Low voltage and 110 VAC voltage cannot be shared
within the same wall box.
WARNING! Risk of Shock or Explosion! DO NOT wire
1 10V to the valve or to the appliance wall switch. Incorrect
wiring will damage controls.
Determine if the appliance uses an Intellifi re ignition sys-
tem or standing pilot ignition system:
• Open the control access panel or remove the decorative
front.
• A red or black ignitor button (as shown in Figure 12.1)
indicates this appliance is standing pilot ignition.
RED OR
BLACK
BUTTON
B. Intellifi re Ignition System Wiring
• Wire the appliance junction box to 110 VAC for proper
operation of the appliance.
WARNING! Risk of Shock or Explosion! DO NOT wire
IPI controlled appliance junction box to a switched circuit.
Incorrect wiring will override IPI safety lockout.
• Refer to Figure 12.2, Intellifi re Pilot Ignition (IPI) Wiring
Diagram.
• This appliance is equipped with an Intellifi re control valve
which operates on a 3 volt system.
• Plug the 3-volt AC transformer into the appliance junction
box to supply power to the unit OR install two D cell
batteries (not included) into the battery pack before use.
NOTICE: Batteries should not be placed in the battery
pack while using the transformer. Remove batteries before
using the transformer, and unplug the transformer before
installing the batteries. Battery polarity must be correct or
module damage will occur.
C. Standing Pilot Ignition System Wiring
• The standing pilot ignition system wiring does not require
a 110 VAC supply to operate. See Figure 12.3
• A 110 VAC junction box MUST be installed for use with
a fan or remote control. See Figure 12.4 for junction box
wiring. Keep wire lengths short as possible.
NOTICE: DO NOT wire 1 10 VAC to the millivolt valve! This
will damage the valve.
• If using a thermostat use one compatible with a millivolt
gas valve system:
- Install the thermostat in the location as indicated in the
thermostat instructions to ensure proper operation of
appliance.
- Use low resistance thermostat wire for wiring from
ignition system to the wall switch and thermostat.
- Keep wire lengths short as possible.
Figure 12.1 Ignitor Button
D. Optional Accessories Requirements
• This appliance may be used with a wall switch, wall
mounted thermostat and/or a remote control.
Wiring for optional Hearth & Home T echnologies approved
accessories should be done now to avoid reconstruction.
Follow instructions that come with those accessories.
Figure 12.2 Intellifi re Pilot Ignition (IPI) Wiring Diagram
E. Electrical Service and Repair
WARNING! Risk of Shock! Label all wires prior to disconnection when servicing controls. Wiring errors can
cause improper and dangerous operation. Verify proper
operation after servicing.
GROUND TO
FIREPLACE
CHASSIS*
BRN
REMOTE
ORG
WHT
ORG
GRN
THERMOSTAT
WIRE
VALVE
ASSEMBLY
WARNING! Risk of Shock! Replace damaged wire with
type 105º C rated wire. Wire must have high temperature
insulation.
STANDING
PILOT
BRN
RED
VALVE
WHT
RED
ON/OFF PIGGYBACK WIRE
Figure 12.3 Standing Pilot Ignition Wiring Diagram
If the box is being wired from the INSIDE of the appliance:
• Remove the screw attaching the junction box/receptacle to
the outer shell, rotate the junction box inward to disengage
it from the outer shell (see Figure 12.4).
• Pull the electrical wires from outside the appliance through
the opening into the valve compartment and secure wires
with a Romex connector. See Figure 12.4.
• Make all necessary wire connections to the junction box/
receptacle and reattach the junction box/receptacle to the
outer shell.
WHT
BLK
WHT
BLK
Figure 12.4 Junction Box Detail
Romex
Connector
Cover Plate
outside firebox
Copper
GRN wire
inside box
ground attached
to GRN screw with
GRN wire
NOTICE: DO NOT wire
110 VAC to wall switch.
14/2WG
G. Wall Switch Installation for Fan (Optional)
If the box is being wired to a wall mounted switch for use
with a fan (See Figure 12.5):
• The power supply for the appliance must be brought into
a switch box.
• The power can then be supplied from the switch box to the
appliance using a minimum of 14-3 with ground wire.
• At the switch box connect the black (hot) wire and red
(switch leg) wire to the wall switch as shown.
• At the appliance connect the black (hot), white (neutral)
and green (ground) wires to the junction box as shown.
• Add a 1/4 in. insulated female connector to the red (switch
leg) wire, route it through the knockout in the face of the
junction box, and connect to the top fan switch connector
(1/4 in. male) as shown.
Figure 12.5 Junction Box Wired to Wall Switch or BC10
Red
Black
White
Red
Black
Green
White
Green
Knockout
Switch Box
Black
White
Switch
Green
Power
Supply
Wires
Page 52
13
13
Finishing
A. Mantel and Wall Projections
WARNING! Risk of Fire! Comply with all minimum clearances as specifi ed. Framing closer than the minimums list-
ed must be constructed entirely of noncombustible materials (i.e., steel studs, concrete board, etc.) Failure to comply
could cause fi re.
Combustible Mantels
TO CEILING
Note: All
measurements
in inches.
2-1/2
9
8
7
6
5
4
3
13
12
11
10
5
18
12
11
10
17
16
15
14
32
25
19
18
B. Facing Material
• Metal front faces may be covered with non-combustible
materials only.
• Facing and/or fi nishing materials must not interfere with
air fl ow through louvers, operation of louvers or doors,
or access for service.
• Facing and/or fi nishing materials must never overhang
into the glass opening.
• Observe all clearances when applying combustible
materials.
• Seal joints between the fi nished wall and appliance top
and sides using a 300 ºF minimum sealant. Refer to
Figure 13.3.
WARNING! Risk of Fire! DO NOT apply combustible
materials beyond the minimum clearances. Comply with
all minimum clearances to combustibles as specifi ed in
this manual. Overlapping materials could ignite and will
interfere with proper operation of doors and louvers.
NON-COMBUSTIBLE ZONE (Shaded areas)
MEASUREMENTS FROM
TOP EDGE OF THE OPENING
Note: Measurement is taken from top of the opening,
NOT the top of the fi replace.
Figure 13.1 Minimum Vertical and Maximum Horizontal
Dimensions of Combustibles
Combustible Mantel Legs or Wall Projections
INTERIOR WALL
TOP VIEW
A
FIREPLACE OPENING
MANTEL LEG OR WALL PROJECTIONS
If A minimum is ____, then B maximum is_____.
Inches
A
B
2-7/16 3-7/16 4-7/16 5-7/16 6-7/16 7-7/16
Millimeters
Inches
Millimeters
6287113138164189
12345
255176102127
B
41 in.
39-3/8 in.
Figure 13.3 Noncombustible Facing Diagram
∞
∞
Figure 13.2 Combustible Mantel Leg or Wall Projections
(Acceptable on both sides of opening)
Only doors certifi ed for use with this appliance model may
be used. Contact your dealer for a list of doors that may
be used. Once you have determined what kind of door
and fi nishing material is going to be used on the fi replace,
you may use the table below which shows the door models and the fi nishing material thickness allowed. For an
inside fi t there is an available template to assist with siz-
ing the fi nishing material.
FINISH
DOORFIT
FolioInsideAny13.4
Arcadia
Halston
Chateau
Valencia
Galleria
MATERIAL
MAXIMUM
THICKNESS
Overlap1 inch13.5
InsideAny13.6
Overlap1 inch13.5
Inside1 inch - 3 inch13.7
Overlap1 inch13.5
InsideAny13.6
Overlap1 inch13.5
InsideAny13.6
Overlap1 inch13.5
Inside1 inch - 3 inch13.7
SEE
FIGURE
FINISHING
MATERIAL
DOOR
37-1/4 in.
(Includes 1/8 in. opening each side of door)
(Outside door width)
(Includes 1/8 in. opening each side of door)
Finishing materials over 1 inch thick.
Figure 13.6 Inside fi t door
ELBOW
HEAT
SHIELD
37 in.
(Outside door width)
33-3/4 in.
37 in.
37-1/4 in.
FINISHING
MATERIAL
34 in.
Stop fi nishing material fl ush with opening.
Figure 13.4 Folio Door
ELBOW
HEAT
SHIELD
1-2 IN. THICK
FINISHING
MATERIAL
*IF FINISHING MATERIAL IS THICKER THAN
2 IN., DOORS WILL ONLY OPEN
AS FAR AS PICTURED
DOORS
33 3/4 IN.
37 1/4 IN.
Finishing material between 1 and 3 inches thick.
Figure 13.7 Operable hinge door
1-2 IN. THICK
FINISHING
MATERIAL
34 IN.
Finishing materials 1 inch maximum thick.
Stop fi nishing material fl ush with opening.
Remove shipping materials from inside or underneath the
fi rebox.
C. Clean the Appliance
Clean/vacuum any sawdust that may have accumulated
inside the fi rebox or underneath in the control cavity.
D. Accessories
Install approved accessories per instructions included
with accessories. Contact your dealer for a list of approved accessories.
WARNING! Risk of Fire and Electric Shock! Use ONLY
Hearth & Home Technologies-approved optional accessories with this appliance. Using non-listed accessories
could result in a safety hazard and will void the warranty.
E. Ember Placement
WARNING! Risk of Explosion! Follow ember placement
instructions in manual. DO NOT place embers directly over
burner ports. Replace ember material annually . Improperly
placed embers interfere with proper burner operation.
Ember material is shipped with this gas appliance. T o place
the ember material:
• Embers CANNOT be placed directly over ports. Care
should be taken not to cover the lighting trail of ports
(from back to front).
• Place dime-size pieces of Glowing Embers® just in front
of the port trail, but not on or in between the ports (see
Figure 14.1). Care should be taken so that the ports are
not covered. Failure to follow this procedure will likely
cause lighting and sooting problems.
EMBER MATERIAL
Figure 14.1 Placement of Embers
• Place Mystic Embers on areas of base refractory away
from port holes. Use this material to give the appliance
a realistic ash bed.
• Save the remaining ember materials for use during
appliance servicing. The embers provided should be
enough for 3 to 5 applications.
If the gas logs have been factory installed they
should not need to be positioned. If the logs have
been packaged separately, refer to the following
instructions.
STEP 1.
CAUTION: Logs are fragile! Carefully remove
the logs, grate and supporting cardboard from
the inside of the fi replace See Figure 14.2.
STEP 2.
Place the metal grate on top of the burner.
Position the legs of the grate into the forward set
of indentations in the burner top. Make sure the
grate is all the way forward. See Figure 14.3.
Figure 14.2
Log Assembly: LOGS-6000G
1
3
4
2
5
STEP 3.
Log #1 (SRV2103-107):
Place the log on the burner so the cutout in the
log goes around the hump in the burner. The outer
legs of the log should self center on the sides of
the burner. The ramp shape in the bottom of the
log sits fully against the ramp shape molded into
the burner. Pull the log forward. The right side of
log will touch the smaller hump. There will be a
1/4 inch or so gap around the hump. See Figures
WARNING! Risk of Asphyxiation! Handle fi xed glass
assembly with care. Inspect the gasket to ensure it is
undamaged and inspect the glass for cracks, chips or
scratches.
• DO NOTstrike, slam or scratch glass.
• DO NOToperate fi replace with glass removed, cracked,
broken or scratched.
• Replace as a complete assembly.
Removing Fixed Glass Assembly
• Pull the four glass assembly latches out of the groove on
the glass frame. Remove glass door from the appliance
(see Figure 14.14).
Replacing Fixed Glass Assembly
• Replace the glass door on the appliance. Pull out and
latch the four glass assembly latches into the groove on
the glass frame.
I. Air Shutter Setting
Air shutter settings should be adjusted by a qualifi ed ser-
vice technician at the time of installation. The air shutter is
set at the factory for minimum vertical vent run. Adjust air
shutter for longer vertical runs. See Figure 14.15.
• Loosen the wing nut.
• Push the air handle in to close the air shutter.
• Pull the air handle out to open the air shutter.
• Tighten the wing nut.
NOTICE: If sooting occurs, provide more air by opening
the air shutter.
LATCHES
(BOTH BOTTOM
AND TOP)
GLASS
ASSEMBLY
Figure 14.14 Fixed Glass Assembly
H. Install Trim and/or Surround
• Install optional trim kits and/or surrounds using the
instructions included with the accessory.
• Use non-combustible materials to cover the gap between
the sheet rock and the appliance (when applicable to the
model).
With proper installation, operation, and maintenance your gas appliance will provide years of trouble-free service. If you do
experience a problem, this troubleshooting guide will assist a qualifi ed service technician in the diagnosis of a problem and
the corrective action to be taken. This troubleshooting guide can only be used by a qualifi ed service technician. Contact
your dealer to arrange a service call by a qualifi ed service technician.
A. Standing Pilot Ignition System
SymptomPossible CausesCorrective Action
1. After repeated triggering
of the red or black piezo
ignitor button, the spark
ignitor will not light the
pilot.
2. The pilot will not stay lit
after carefully following
the lighting instructions.
3. The pilot is burning,
there is no burner
fl ame, the valve knob is
in the ON position, and
the ON/OFF switch is in
the ON position.
A. No gas or low gas pressure.Check the remote shut-off valves from the appliance. Usually, there
is a valve near the gas main. There can be more than one valve be-
tween the appliance and the main.
B. No lp in tank.Check the LP (propane) tank. You may be out of fuel.
C. Ignitor.Check the spark at the electrode and pilot. If no spark and electrode
wire is properly connected, replace the ignitor. Verify that there is no
short in electrode wire.
D. Pilot or misaligned electrode
(spark at electrode).
A. Thermocouple.Check that the pilot fl ame impinges on the thermocouple. Adjust the
B. Improper gas inlet pressure.Natural gas should be 5-14 in. w.c. LP should be 10-14 in. w .c. V erify
C. Valve.If the thermocouple is producing 8-16 millivolts, replace control valve.
A. ON/OFF switch or wires.Check the ON/OFF switch and wires for proper connections. Place
B. Thermopile may not be gen-
erating suffi cient millivoltage.
Using match, light the pilot. If the pilot lights, turn off the pilot and
trigger the piezo ignitor button again. If the pilot lights, an improper
gas/air mixture caused the bad lighting and a longer purge period is
recommended. If the pilot will not light, ensure the gap at the elec-
trode and pilot is one-eighth in. to have a strong spark. If the gap is
OK, replace the pilot.
pilot for proper fl ame impingement.
Ensure that the thermocouple connection at the gas valve is fully in-
serted and tight (hand tighten plus 1/4 turn).
Verify proper voltage output from the thermocouple to the valve.
Place one millivolt meter lead wire on the thermocouple copper lead.
Place the second lead wire on the solder button on the back of the
valve (blue wire). Start the pilot and hold the valve knob in. The mil-
livolt reading should read 8-16 millivolts. If millivolt reading is less
than 8 millivolts, replace thermocouple.
pressure with manometer.
the jumper wires across the terminals at the ON/OFF switch. If the
burner comes on, replace the ON/OFF switch. If the ON/OFF switch
is OK, place the jumper wires across the ON/OFF switch wires at the
gas valve. If the burner comes on, the wires are faulty or connections
are bad.
Check that the pilot fl ame impinges thermopile properly.
Be sure the wire connections from the thermopile at the gas valve
terminals are tight and that the thermopile is fully inserted into the
pilot bracket.
Check the thermopile with a millivolt meter. Take the reading at TH-
TP&TP terminals of the gas valve. The meter should read 350 mil-
livolts minimum, while holding the valve knob depressed in the pilot
position, with the pilot lit, and the ON/OFF switch in the OFF position.
Replace the thermopile if the reading is below the specifi ed mini-
mum.
With the pilot in the ON position, disconnect the thermopile leads
from the valve. Take a reading at the thermopile leads. The reading
should be 350 millivolts minimum. Replace the thermopile if the read-
3. (Continued)C. Valve.Turn the valve knob to the ON position. Place the ON/
OFF switch in the ON position. Take a reading with a
millivolt meter at the thermopile terminals. The millivolt
meter should read greater than 125mV. If the reading
is acceptable, and if the burner does not come on, replace the gas valve.
D. Plugged burner orifi ce.Check the burner orifi ce for stoppage. Remove stop-
page.
E. Wall switch or wires.Check the wall switch and wires for proper connec-
tions. Place the jumper wires across the terminals at
the wall switch. If the burner comes on, replace the
wall switch. If the wall switch is OK, place the jumper
wires across the wall switch wires at the gas valve. If
the burner comes on, the wires are faulty or connections are bad.
4. Frequent pilot outage
problem.
5. The pilot and main
burner extinguish
while in operation.
6. Glass soots.A. Flame impingement.Adjust the log set so that the fl ame does not exces-
A. Pilot fl ame may be too high or too low, or blow-
ing out (high pressure), causing pilot safety to
drop out.
A. No LP in tank.Check the LP (propane) tank. Refi ll the fuel tank.
B. Improper gas inlet pressure.Natural gas should be 5-14 in. w.c. LP should be 10-
C. Inner vent pipe leaking exhaust gases back
into the system.
D. Glass installed improperly.Check to ensure glass is installed properly. Replace
E. Thermopile or thermocouple.Replace pilot if necessary.
F. Improper vent cap installation.Check for proper installation and freedom from debris
B. Improper air shutter setting.Refer to manual for shutter set points. Ensure that set
C. Debris around air shutter.Inspect the opening at the base of the burner. NO MA-
Clean thermocouple and adjust the pilot fl ame for
proper fl ame impingement. Follow lighting instructions
carefully.
14 in. w.c. Verify pressure with manometer.
Check venting system for damage. Replace/repair im-
properly assembled pipe sections.
fi xed glass panel assembly.
or blockage.
sively impinge on it. Refer to log instructions.
point is correct for appliance/gas type. If unit has adjustable shutter, it may be necessary to increase shutter opening.
TERIAL SHOULD BE PLACED IN THIS OPENING.
7. Flame burns blue
and lifts off burner.
A. Insuffi cient oxygen being supplied.Ensure that the vent cap is installed properly and free
of debris. Ensure that the vent system joints are tight
and have no leaks.
Ensure that no debris has been placed at the base of,
or in the area of the air holes in the center of the base
pan beneath the burner.
Ensure that the glass is tightened properly on the unit,
particularly on top corners.
1. Pilot won’t light.
The ignitor/module
makes noise, but no
spark.
2. Pilot won’t light,
there is no noise or
spark.
A. Incorrect wiring.Verify “S” wire (white) for sensor and “I” wire (orange) for ignitor are
connected to correct terminals on module and pilot assembly.
B. Loose connections or electrical
shorts in the wiring.
C. Ignitor gap is too large.Verify gap of igniter to right side of pilot hood. The gap should be
D. Module.Turn ON/OFF rocker switch or wall switch to OFF position. Remove
A. No power or transformer installed
incorrectly.
B. A shorted or loose connection in
wiring confi guration or wiring har-
ness.
Verify no loose connections or electrical shorts in wiring from module to pilot assembly. Verify connections underneath pilot assembly are tight; also verify connections are not grounding out to metal
chassis, pilot burner, pilot enclosure, mesh screen if present, or any
other metal object.
approximately .17 in. or 1/8 in. (3 mm).
ignitor wire “I” from module. Place a grounded wire about 3/16 in. (5
mm) away from “I” terminal on module. Place ON/OFF rocker switch
or wall switch in ON position. If there is no spark at “I” terminal module
must be replaced. If there is a spark at “I” terminal, module is fi ne.
Inspect pilot assembly for shorted sparker wire or cracked insulator
around electrode. Replace pilot if necessary .
Verify that transformer is installed and plugged into module. Check
voltage of transformer under load at spade connection on module
with ON/OFF switch in ON position. Acceptable readings of a good
transformer are between 3.2 and 2.8 volts AC.
Remove and reinstall the wiring harness that plugs into module.
Verify there is a tight fi t. Verify pilot assembly wiring to module. Re-
move and verify continuity of each wire in wiring harness. Replace
any damaged components.
3. Pilot sparks, but
Pilot will not light.
C. Improper wall switch wiring.Verify that 110/VAC power is “ON” to junction box.
D. Module not grounded.Verify black ground wire from module wire harness is grounded to
metal chassis of appliance.
E. Module.Turn ON/OFF rocker switch or wall switch to OFF position. Remove
ignitor wire “I” from module. Place ON/OFF rocker switch or wall
switch in ON position. If there is no spark at “I” terminal module
must be replaced. If there is a spark at “I” terminal, module is fi ne.
Inspect pilot assembly for shorted sparker wire or cracked insulator
around electrode.
A. Gas supply.Verify that incoming gas line ball valve is “open”. Verify that inlet
pressure reading is within acceptable limits, inlet pressure must not
exceed 14 in. W.C.
B. Ignitor gap is too large.Verify gap of igniter to right side of pilot hood. The gap should be
approximately .17 in. or 1/8 in. (3 mm).
C. Module is not grounded.Verify module is securely grounded to metal chassis of appliance.
D. Module voltage output / Valve/Pilot
solenoid ohms readings.
Verify battery voltage is at least 2.7 volts. Replace batteries if volt-
4. Pilot lights but continues to spark, and main
burner will not ignite.
(If the pilot continues
to spark after the
pilot fl ame has been lit, fl ame rectifi cation has
not occurred.)
A. A shorted or loose connection in fl ame
sensing rod.
B. Poor fl ame rectifi cation or contaminated
fl ame sensing rod.
C. Module is not grounded.Verify module is securely grounded to metal chassis of ap-
D. Damaged pilot assembly or contami-
nated fl ame sensing rod.
E. Module.Turn ON/OFF rocker switch or wall switch to OFF position.
Verify all connections to wiring diagram in manual. Verify
connections underneath pilot assembly are tight. Verify connections are not grounding out to metal chassis, pilot burner, pilot enclosure or screen if present, or any other metal
object.
With fi xed glass assembly in place, verify that fl ame is en-
gulfi ng fl ame sensing rod on left side of pilot hood. Flame
sensing rod
rect pilot orifi ce is installed and gas inlet is set to pressure
specifi cations. Clean fl ame sensing rod with emery cloth to
remove any contaminants that may have accumulated on
fl ame sensing rod.
pliance. Verify that wire harness is fi rmly connected to the
module.
Verify that ceramic insulator around the fl ame sensing rod
is not cracked, damaged, or loose. Verify connection from
fl ame sensing rod to white sensor wire. Clean fl ame sensing
rod with emery cloth to remove any contaminants that may
have accumulated on fl ame sensing rod. Verify continuity
with a multimeter with ohms set at lowest range. Replace
pilot if any damage is detected.
Remove ignitor wire “I” from module. Place ON/OFF rocker
switch or wall switch in ON position. If there is no spark at “I”
terminal module must be replaced. If there is a spark at “I”
terminal, module is fi ne.
DVP44102
DVP66152
DVP1212305
DVP2424610
DVP3636914
DVP48481219
DVP6A3 to 676 to 152
DVP12A 3 to 12 76 to 305
DVP12MI 3 to 12 76 to 305
DVP24MI 3 to 24 76 to 610
Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm). The heat shield is designed to be
used on a wall 4 in. to 7-1/4 in. (102 mm to 184 mm) thick. If wall thickness is less than 4 in. (102 mm) the
existing heat shields must be field trimmed. If wall thickness is greater than 7-1/4 in. (184 mm) a DVP-HSM-B
will be required.
• When using DVP-HRC-SS and DVP-HRC-ZCSS termination caps on top vented fi replaces, a
6 inch minimum vertical vent section is required
before installing fi rst elbow.
IMPORTANT: THIS IS DATED INFORMATION. When requesting service or replacement parts for your
appliance please provide model number and serial number. All parts listed in this manual may be ordered
from an authorized dealer.
Includes Vent, Seal Cap, Burner Neck, Shutter Bracket, Manifold
and Valve Plate gaskets
Glass Latch Assembly386-122AY
Mineral Wool050-721
Pilot TubeSRV485-301Y
Touch Up PaintTUP-GBK-12
Vermiculite EmbersMystic-Embers
IMPORTANT: THIS IS DATED INFORMATION. When requesting service or replacement parts for your
appliance please provide model number and serial number. All parts listed in this manual may be ordered
from an authorized dealer.
ITEMDESCRIPTIONCOMMENTSPART NUMBER
Orifi ce, NG (#37C)582-837Y
1
Orifi ce, LP (#52C)582-852Y
Pilot Assembly, NG2090-012Y
IMPORTANT: THIS IS DATED INFORMATION. When requesting service or replacement parts for your
appliance please provide model number and serial number. All parts listed in this manual may be ordered
from an authorized dealer.
ITEMDESCRIPTIONCOMMENTSPART NUMBER
Pilot Assembly, NG2103-010Y
1
Pilot Assembly, LP2103-011Y
Orifi ce NG (#37C)582-837Y