Heat-Zone-240V Air Duct Kit
INST ALLATION AND
OPERATION INSTRUCTIONS
Hearth Technologies, Inc.
7571 215th Street West
Lakeville, MN 55044 USA
Approvals
The HEAT-ZONE-240V air duct kit is approved for use on
Heat & Glo Models XLR-AU, 6000, 350 and 550 series
gas heaters.
Introduction
The HEAT-ZONE-240V accessory kit conveys warm air
from the heater through air duct(s) to remote locations
in the same room or other rooms of the building. See
Figures 1 and 2. One or two HEAT-ZONE-240V kits can
be installed on the heater.
Possible Air Duct Runs/Locations
Preliminary Preparation
1. Contents of kit:
• 6 meters of 152 mm round duct
• Fan housing assembly
• Junction box
• Air register
• Register adapter frame
• Heater duct collar
• Duct adapter - (round to oval)
• Hardware
• 2166-191 IPI Plus auxiliary jumper
NOTICE! If any parts are missing or damaged, contact your
dealer before starting installation. DO NOT install a damaged kit.
Figure 1
WALL REGISTER
CEILING REGISTER
TWO DUCT KITS
FLOOR REGISTER
WALL REGISTER
Hearth & Home Technologies • Heat-Zone-240V Air Duct Kit • 299-900D • 7/10 1
WALL REGISTER
WALL REGISTER
Possible Air Duct Runs/Locations
CEILING REGISTER
TWO DUCT KITS
FLOOR REGISTER
WALL REGISTER
Figure 2
2. The Heat-Zone 240V kit is tested and safe when installed
in accordance with this installation manual. This kit is
carefully engineered and must be installed only as specifi ed. Modifying the kit or any of its components will void
the warranty, and may possibly cause a fi re hazard.
3. CAUTION: Installation of this appliance should only be
carried out by an authorized person. All relevant codes
and regulations laid down by the gas piping authorities,
municipal building regulations, electrical wiring regulations and the requirements of the AS5601 Gas Installation code must be observed.
4. Plan the location of the heater and the warm air duct
run(s).
MAXIMUM Duct Run = 6 M for useful heat output.
MINIMUM Duct Run = NA - for runs out from the heater
to adjacent room OR down to the room below.
MINIMUM Duct Run = 787 mm top of heater to room
above.
WALL REGISTER
6000 SERIES
DUCT
COLLAR
COVER
PLATE
Installation
1. Remove the cover plate from the side of the heater and
discard it.
2. Center the duct collar around the exposed hole and
attach it to the heater with 3 screws. NOTE: Do this
BEFORE fi nal positioning of the heater. See Figure 3.
Hearth & Home Technologies • Heat-Zone-240V Air Duct Kit • 299-900D • 7/102
XLR-AU
Figure 3