Hearth and Home Technologies 299-900D User Manual

Heat-Zone-240V Air Duct Kit
INST ALLATION AND OPERATION INSTRUCTIONS
Hearth Technologies, Inc.
7571 215th Street West
Lakeville, MN 55044 USA
Approvals
The HEAT-ZONE-240V air duct kit is approved for use on Heat & Glo Models XLR-AU, 6000, 350 and 550 series gas heaters.
Introduction
The HEAT-ZONE-240V accessory kit conveys warm air from the heater through air duct(s) to remote locations in the same room or other rooms of the building. See Figures 1 and 2. One or two HEAT-ZONE-240V kits can be installed on the heater.
Possible Air Duct Runs/Locations
Preliminary Preparation
1. Contents of kit:
• 6 meters of 152 mm round duct
• Fan housing assembly
• Junction box
• Air register
• Register adapter frame
• Heater duct collar
• Duct adapter - (round to oval)
• Hardware
• 2166-191 IPI Plus auxiliary jumper
NOTICE! If any parts are missing or damaged, contact your dealer before starting installation. DO NOT install a damaged kit.
Figure 1
WALL REGISTER
CEILING REGISTER
TWO DUCT KITS
FLOOR REGISTER
WALL REGISTER
Hearth & Home Technologies • Heat-Zone-240V Air Duct Kit • 299-900D • 7/10 1
WALL REGISTER
WALL REGISTER
Possible Air Duct Runs/Locations
CEILING REGISTER
TWO DUCT KITS
FLOOR REGISTER
WALL REGISTER
Figure 2
2. The Heat-Zone 240V kit is tested and safe when installed in accordance with this installation manual. This kit is carefully engineered and must be installed only as speci­ ed. Modifying the kit or any of its components will void the warranty, and may possibly cause a fi re hazard.
3. CAUTION: Installation of this appliance should only be carried out by an authorized person. All relevant codes and regulations laid down by the gas piping authorities, municipal building regulations, electrical wiring regula­tions and the requirements of the AS5601 Gas Instal­lation code must be observed.
4. Plan the location of the heater and the warm air duct run(s).
MAXIMUM Duct Run = 6 M for useful heat output. MINIMUM Duct Run = NA - for runs out from the heater
to adjacent room OR down to the room below. MINIMUM Duct Run = 787 mm top of heater to room
above.
WALL REGISTER
6000 SERIES
DUCT
COLLAR
COVER
PLATE
Installation
1. Remove the cover plate from the side of the heater and discard it.
2. Center the duct collar around the exposed hole and attach it to the heater with 3 screws. NOTE: Do this BEFORE fi nal positioning of the heater. See Figure 3.
Hearth & Home Technologies • Heat-Zone-240V Air Duct Kit • 299-900D • 7/102
XLR-AU
Figure 3
Loading...
+ 2 hidden pages