Electrical Connection
The sensor must be wired with a 4-cord cable with an M12 connection plug. Colour codes in the diagram below are related
to the cables delivered by HB. The supply voltage is limited to 24V AC/DC.
LED Indication
LED indication:
1) Green LED indicates 24 V AC/DC power supply
2) Red LED indicates ALARM at 100 %
Alarm to be activated at 100% level. The liquid level has to drop
below hysteresis
Further Information
Extended and detailed manuals are available on our homepage www.hbproducts.dk.
Quick Installation Guide for: HBLT-WIRE
Mechanical Installation
The sensor is installed in the standpipe or directly in the
tank. The sensor length is determined by standpipe length
or tank height. Please leave 50 mm space between the let
and the bottom of the pipe. Steel wire and Teflon hose
most be cut to desired length with wire cutters or a bolt
cutter, in the end where the let must be installed. Teflon
hose must be mounted outside on the wire.
Standpipe must be insulated to avoid boiling in the stand
pipe.
To install the HBLT-wire, you must use a 2.5 mm Allen
key, shifting spanner, wire cutter and liquid gasket.
Loosen the electronic part from mechanical part.
Define the sensor length from the standpipe height.
Shorten the wire and Teflon hose to required length.
Teflon hose must be 20 mm shorter than the wire.
Make sure that wire is in bottom of the hole.
Tighten the 2 setscrews to fix the wire.
When sealing the conical thread, you must use liquid
conductive sealant, which creates a ground connection
between the standpipe/tank and the sensor, since the
sensor uses the standpipe/tank as reference. If Teflon is
used, it must only be used on part of the thread so that the
ground connection is established. If you are in doubt
regarding the ground connection, measuring the resistance
between the tank and sensor is recommended. This should
be approx. 0 ohms. For cylindrical thread, an alu sealing
ring is included.
L = Programmable sensor length
L= Wire length + 86 mm
Teflon hose most be 20 mm shorter than wire length.
Insert wire in let part and tighten the 2 setscrews. Turn the
top cover plastic part on the metal part (right-hand
thread).
Supply 24 V AC/DC
1 = Brown +
2 = White 3 = Blue – DO, Alarm, PNP/NPN, 1A
4 = Black – AO, Control output, 4-20 mA
5 = Grey – Data communication

HBLT-Wire Quick guide - configuration (009-UK) HB Products A/S – Boegekildevej 21 – 8361 Hasselager – tlf. : 004587476200 – E-mail: info@hbproducts.dk
Configuration with PC and HB-TOOL
The HBLT-Wire sensor should be configured to the actual application. The software program can be downloaded at
www.hbproducts.dk. Programming cable has been included. The actual sensor settings can be displayed by pressing the
“Show current figuration” button.
DN25, DN32, DN40, DN50, DN65, DN80, DN100
The above shows the factory settings and configuration possibilities in an HBLT-Wire sensor. *
Configuration from sensor front
In case a PC is not available, the sensor configuration can be carried out by the sensor push bottom of the front.
To enter the configuration parameters please press the “R” button for 10 seconds and then follow the steps in the table.
The yellow LED will flash in 5 seconds and after this it will be off. When it is ON again the programming can start. No
change in 15 sec will interrupt the configuration. In that case please press the “R” button for 10 seconds again.
Enterring the configuration mode
Enterring length configuration mode
1 push to change the length
in cm.
To roll digit 3 from 1-9.
1-9
1 = 100 cm,
2 = 200 cm,
3 = 300 cm
1 push to change the length
in cm.
To roll digit 2 from 1-9.
1-9
1 = 110 cm,
2 = 120 cm,
3 = 130 cm
1 push to change the length
in cm.
To roll digit 1 from 1-9.
1-9
1 = 111 cm,
2 = 112 cm,
3 = 113 cm
To switch to refrigeration mode
1 push to change
refrigeration/liquid type
Change of refrigeration/liquid type
R717= 717
OIL= OIL
R134= 134
R507= 507
R404 = 404
R407= 407
R410= 410
R22 = 022
R123ZE = 123
To swtich to selection of standpipe
Size of standpipe to select
DN25 = 025
DN32 = 032
DN40 = 040
DN50 = 050
DN65 = 065
DN80 = 080
DN100 = 100
Saving all data and leaving
calibration mode.
The sensor configuration is saved when leaving the calibration mode. The “BYE” signal is a confirmation on this.
To view the configuration parameters please press the “R” button for 10 seconds and then press 5 seconds. It will start to
show programmed parameter, with a jump each 3 seconds. It will repeat the selected parameters once and then return to
the actual value in %.
-F- / xxx (type of refrigerant)
-O- / xxx (stand pipe dimension)
Select the refrigerant type here
Save by clicking “Save to sensor”
Sensor length (L) should be input here
Standpipe size shall be selected here
H-offset: Input offset value here. The measureent span –
programmable sensor length = Offset [mm]. E.g. if 100 %
should be at 1400 mm and the sensor length is 1600 mm, the
offset length should be 200 mm.
L-offset: Input offset value here. If measurement
should start 100 mm from end of sensor and not
at the end, then input offset should be 100 mm.