Calibration:
0% or 100% calibration can be carried out independently of each other. HBLC level sensor is delivered precalibrated. For normal use, calibration is not necessary. If the signal changes over time, we recommend a
0% calibration with an empty overflow pipe or container.
Instruction for 0% calibration:
1) The sensors calibration function shall be connected via the HB tool. See instruction for PC
connection and configurations parameters in separate manuals.
2) Connect the power cable.
3) Empty container/overflow pipe
4) Activate "R" for 5 seconds to activate "calibration mode" = Yellow LED turns on (ON) during the 5
seconds activation, and goes off (OFF) when the calibration mode is activated.
5) Activate "R" once = Yellow LED blinks once. The green LED then blinks to confirm calibration.
6) Connect PC Tool again and disconnect the calibration function in tool.
7) Connect the power cable.
"Calibration mode" is complete and the sensor is then running normally.
Instruction for 100% calibration:
1) The sensors calibration function shall be connected via the HB tool. See instruction for PC
connection and configurations parameters in separate manuals.
2) Connect the power cable.
3) Full container/overflow pipe up to a 100% level.
4) Activate "R" for 5 seconds to activate "calibration mode" = Yellow LED turns on (ON) during the 5
seconds activation, and goes off (OFF) when the calibration mode is activated.
5) Activate "R" twice = Yellow LED blinks twice. The green LED then blinks to confirm calibration.
6) Connect PC Tool again and disconnect the calibration function in tool.
7) Connect the power cable.
"Calibration mode" is complete and the sensor is then running normally.
Installation of HB Configuration Tool
See separate manual.
PC Configuration
See separate manual.
Setup and Connection of Valve
See separate manual.