The MP85/MP85DP module and its connected transducers are to be used
exclusively for measurement tasks and directly related control tasks. Use for
any purpose other than the above shall be deemed to be not in accordance
with the regulations.
To ensure safe operation, the device may only be operated in accordance with
the information given in the Operating Manual. It is also essential to comply
with the legal and safety requirements for the application concerned during
use. The same applies to the use of accessories.
The device must not be connected directly to the mains supply. The
supply voltage may be 18 to 30 V.
General dangers of failing to follow the safety instructions
The MP85/MP85DP module corresponds to the state of the art and is
fail−safe. The device may give rise to further dangers if it is inappropriately
installed and operated by untrained personnel.
Any person instructed to carry out installation, commissioning, maintenance or
repair of the device must have read and understood the Operating Manual
and in particular the technical safety instructions.
Conditions on site
Protect the device from direct contact with water (IP20).
Maintenance and cleaning
The MP85/MP85DP module is maintenance-free. Please note the following
points when cleaning the housing:
− Before cleaning, disconnect the devices from the power supply.
− Clean the housing with a soft, slightly damp (not wet!) cloth. You should
never use solvent, since this could damage the labelling on the front panel
and the display.
− When cleaning, ensure that no liquid gets into the device or connections.
Remaining dangers
The scope of supply and list of components provided with the MP85/MP85DP
cover only part of the scope of measurement technology. In addition,
equipment planners, installers and operators should plan, implement and
respond to the safety engineering considerationsof measurement technology
in such a way as to minimize remaining dangers. Prevailing regulations must
be complied with at all times. There must be reference to the remaining
dangers connected with measurement technology.
A0897−3.4 enHBM
6
Any risk of residual dangers when working with the MP85/MP85DP is pointed
out in this introduction by means of the following symbols:
PME-MP85
Symbol:
Meaning:Dangerous situation
Warns of a potentially dangerous situation in which failure to comply with
safety requirements can result in death or serious physical injury.
Symbol:
Meaning:Potentially dangerous situation
Warns of a potentially dangerous situation in which failure to comply with
safety requirements could result in damage to property or some form of
physical injury.
Symbols indicating application notes and useful information:
Symbol:
WARNING
CAUTION
NOTE
Indicates that important information is given about the product or how to
handle it.
Symbol:
Meaning:CE mark
With the CE mark, the manufacturer guarantees that his product complies
with the requirements of the relevant EC guidelines (see Declaration of
conformity at the end of this operating manual).
Working safely
Error messages must only be acknowledged when the cause of the error has
been removed and no further danger exists.
The instrument complies with the safety requirements of DIN EN 61010, Part
1 (VDE 0411, Part 1) protection class I.
The device must be mounted on a supporting rail connected to the protective
earth potential. Make sure, that at this spot both the supporting rail and the
MP85/MP85DP module are free from dirt and other foreign material.
To guarantee adequate immunity from interference, the buses (CAN and in
the case of MP85DP, Profibus DP) should be run with shielded and twisted
2-wire lines. The transducer lines should also be run using shielded cables.
A0897−3.4 enHBM
PME-MP85
The shield of each transducer cable should be connected at the PME end by
as short a line as possible (t5 cm) and a blade connector (4.8 mm;
“Faston”).
The lines to connect the power supply and the digital control inputs and
outputs only need to be shielded if the cable length exceeds 30 m or if the
lines are installed outside closed buildings.
When connecting the lines (clip on and pull off clamps) and when replacing
the MMC, measures must be taken against electrostatic discharge to prevent
damage to the electronics.
The MP85/MP85DP module should be operated at a separated extra−low
voltage (SELV) (supply voltage 18 − 30 V DC) that usually supplies one or
more consumers within a control panel.
1)
If the device is operated on a direct voltage network
, additional precautions
must be taken to discharge excess voltages.
7
Conversions and modifications
The MP85/MP85DP module must not be modified from the design or safety
engineering point of view except with our express agreement. Any
modification shall exclude all liability on our part for any resulting damage.
In particular, any repair or soldering work on motherboards is prohibited.
When exchanging complete modules, use only original parts from HBM.
Qualified personnel
This instrument is only to be installed and used by qualified personnel strictly
in accordance with the technical data and with the safety rules and regulations
which follow. It is also essential to comply with the legal and safety
requirements for the application concerned during use. The same applies to
the use of accessories.
Qualified personnel means persons entrusted with the installation, assembly,
commissioning and operation of the product who possess the appropriate
qualifications for their function.
Maintenance and repair work on an open device with the power on must only
be carried out by trained personnel who are aware of the danger involved.
1)
Distribution system for electrical power with greater spatial expansion (e.g. via several control panels) that
may possibly even supply consumers with high nominal (rated) currents.
D multimedia card (MMC), e.g. Sandisk (www.sandisk.com)
D standard ribbon cable, 10−pin, grid 1.27 mm
1.2General
The MP85/MP85DP module from the PME product line is a two−channel
measuring amplifier suitable for connecting the transducers of a great variety
of technologies. In the case of the MP85DP, there is also a Profibus interface
available for CAN-Interface.
Carrier-frequency
excitation voltage 4.8 kHz
Supply for active transducer
5V or 24V
A
D
Intelligent signal conditioning
and powerful algorithms for
A
press-fit monitoring
D
Voltage supply,
electrically isolated
µP
24 V
Control inputs and
control outputs
CANopen
interface
"10V
SSI
Keyboard &
display
MP85 / MP85DP
MMC memory
card
Fig. 1.1:Block diagram of the MP85/MP85DP module
Profibus DP
interface
(for MP85DP)
A0897−3.4 enHBM
PME-MP85
The PME Assistant provides a simple user interface under MS-Windows for
parameterizing the modules.
The PME Assistant is the sole means of parameterizing and setting up
the MP85/MP85DP module (described in the Online Help).
To do this you need an LPT → CAN or USB → CAN interface converter, that
has to be ordered separately (1−PMESETUP; 1−PMESETUP-USB).
The software allows you to set all the device parameters apart from the one
for the CAN-BUS interface used for setup.
The software also allows you to set up the other devices of the PME family.
1.3Valuable information about PME MP85 documentation
MP85 documentation comprises
9
•this Operating Manual,
which describes mainly the configuration of the hardware (transducer,
device and PC with the software).
•the Online Help of the PME Assistant
which describes how to use the software to set up the device
•a separate Operating Manual for the MP85DP with a CAN object index,
CAN interface description and Profibus communication
A0897−3.4 enHBM
10
PME-MP85
2Commissioning
To prepare the MP85 measurement system for a measurement task, the
following conditions must be met or the relevant steps taken:
•You need a PME module MP85 or MP85DP and the PME Assistant,
including software
•The hardware must be configured (transducer, device, PC with the
software) (from Page 16)
•The PME Assistant software must be installed (from Page 18)
•To connect the PME module to a PC, you need a CAN adapter (from Page
17)
− PCAN parallel interface LPT to CAN or
− PCAN USB to CAN or
− PCAN card (PCI or ISA) to CAN
•The PME module must be connected to the CAN adapter
•Once you have started the software, you can set up the PME module with
the PME Assistant (Online Help) (Page 19)
A0897−3.4 enHBM
PME-MP85
2.1Philosophy of operation
2.1.1 Settings on the device
The display of the MP85/85DP shows you the measured value and status
information.
The device is actually set up by means of the “PME Assistant” software
(described in Online Help).
Display in measuring mode:
11
−18.0024
status field
!
kg
x
Function of the keys:
SET
1. Switch from measuring mode to
input mode
2. Choose the first parameter within
the group.
3. Confirm your Input
4. Back to measuring mode (press for
2 secs.)
measured value
unit
+
Select
Parameters/Group
+
−
−
↑
↓
Flashes in the status field if the parameter value can be edited
−
Keys :
+
Keep key pressed − value runs continuously
Short press of the key − advance one value at a time
A0897−3.4 enHBM
12
−
During measurement you can press
1. Measured values
•MVxmeasured value channel x
•MVymeasured value channel y
2. Process status, “ProcStat”
•Alarmthe last process was finished via the alarm window
•OKthe last process was OK
•Not OKthe last process was not OK
•Starteda process has been started and not yet finished
+
− to view in the display:
PME-MP85
3. Status of the digital inputs and outputs
The MP85 has 5 inputs and 8 outputs.
The MP85DP has 1 input and 4 outputs.
•Input
set,not set
•Output
set,not set
4. Profibus status
BD_SEAR (baud rate search)
WT_PARM (waiting for parameterization)
WT_CONF (waiting for configuration)
DATA_EX (cyclical data traffic)
ERROR (bus error)
A0897−3.4 enHBM
PME-MP85
5. MMC-DisplayState (MMCState)
DisplayExplanation
notinuseNo data storage on MMC
with any other display: data storage on MMC
no MMCThere is no MMC in the device
Init...The MMC is initialized automatically after insertion
SET ³ STOPMMC ready for storing. Press SET to reset to Stop state.
Then the MMC can be removed.
StoringData is written to the MMC. Upon completion of data sto-
rage, the state changes to “Ready”; SET ³ STOP is displayed.
StoppedBefore removing the MMC from the device,
you must press the SET key to close all files
and write the FAT.
13
The message “MMC Disk Closed” or in case of an error
“MMC DiskClose Err” is displayed for a short time.
Then the MMC changes to the “Stopped” state and can be
removed from the device.
If there is no more free memory available on the MMC, the
status automatically changes to “Stopped”.
The only way to exit this state is to remove the MMC from
the device. Afterwards, there will be an automatic reinitialization.
5. Error types
During measurement, the character ! in the status field (whilst in measuring
mode) indicates a module error.
−
+
The errors are displayed one after the other (obtainable by using
).
•ERROR x (related to screw terminal SENSOR X)
•ERROR y (related to screw terminal SENSOR Y)
SENSOR X
SENSOR Y
Possible error messages are summarized in
Chapter 7 ”Error messages”,
Page 41.
A0897−3.4 enHBM
2.1.2Overview of all groups and parameters
+
SET
+
Up
−
Down
CAN-BUSPROFIBUSADDITIONAL FUNCTION
Baud rateAddressAmplType
Address
OutpR. msSrNo
MAINGRP
−
Overview of parameters
Groups
MAINGRP
Explanation of parameters:
Load MMC:
Allows you to load a parameter set that has already been
stored on the MMC using the PME Assistant.
PrgVers
HW vers
Load MMC
MAINGRP
We recommend to format the MMC from time to time
for optimizing MMC access times.
MAINGRP with
A0897−3.4 en HBM
SET
back to Group
14
2.1.3 Configuring parameters on the device
Measured
value
+
−
2sec
SET
Groups
10kB
20kB
50kB
100kB
+
−
+/-
+
PROFIBUS
SET
ADDITIONAL FUNCTION
AmplTyp
e
PrgVers
CAN bus
SETSETSET
Baud rate
SET
↑
↓
125kB
Address
OutpR. ms
SET
SET
250kB
500kB
1000kB
↑
1−127
↓
↑
↓
000
+/-
+/-
−
SETSET
Address
back
MAINGRP
SET
↑
3 − 123
↓
+/-
SrNo
+
−
HW vers
Load MMC
+
SET
−
Measured
value
↑
↓
MEAS MODE
Save ?
0 − 39
+/-
SET
Yes
↑
↓
No
+/-
SET
back
MAINGRP
A0897−3.4 en HBM
Parameter values
+
Select Parameters
−
↑
↓
Flashes if the parameter value can be edited
SET
Confirm your Input
+/-
=
+−
or
Back to measuring mode:
Print
SET
2sec
SET
back
MAINGRP
15
16
PME-MP85
2.2Configuring the hardware
2.2.1 Voltage supply / Transducer
•Connect the power supply cable and the transducer to the module
(Chapters 5.3 and 5.4).
CAUTION
Be sure to comply with the safety instructions!
•Activate the power supply.
•The device will run a self-test (approx. 10 secs) and will then, if working
properly, be in measuring mode. During the self-test, the control
outputs stay at 0V.
If ! appears in the display or the status LED shows red, please consult
Chapter 7 ”Error messages”.
•Connecting the bus system
To find out how to connect several devices to a CAN bus, refer to Chapter 5.5.
How to set up the CAN address and the baud rate is described in Chapter
2.1.3.
NOTE
A0897−3.4 enHBM
PME-MP85
17
2.2.2 Connecting the CAN adapter (LPT and USB)
To enable PME devices to communicate with the PC, you first have to link the
device to the PC.
1.Connecting LPT to CAN (parallel interface)
•Switch off the PC and attach the LPT to CAN adapter to the parallel
interface port of the PC.
Unfortunately it is not possible to operate a printer from this parallel
interface at the same time. You need a second parallel interface.
•Attach the cable on the adapter between the male connector of the PS2
mouse and the female connector of the PC. This cable is needed to supply
power for the adapter. Alternatively you can attach this power supply cable
between the keyboard connector and the relevant PC socket.
•Attach the CAN connector cable to the MP85 to the adapter.
•Activate the PC.
2.Connecting USB to CAN
First install the PME Assistant.
•Attach the USB to CAN adapter to a free USB interface on your PC.
•The PC will immediately detect the adapter (Plug and Play).
A floppy disk is supplied with the adapter. It includes the driver required for
installation.
A0897−3.4 enHBM