This Operating Manual describes only those functions which differ from the
MP60. The features of the MP60DP correspond to those of the MP60.
The MP60DP carrier−frequency measurement module has been expanded to
include a Profibus interface. The features on the CAN−interface remain the
same; the object directory is expanded to include some parameters for the
Profibus connection.
The Profibus connection is made using a 9−pin sub−D connector (conforming
to standard) on the front panel next to the transducer port.
DP protocol is used on the Profibus.
The following are communicated:
− the measured values (gross, net, peak values)
− the status of the limit switches
− control bits for taring, zeroing, peak value store control and changing the
parameter set, and
− optionally, the limit values
HBMA0623-6.1 en/de/fr
PME−MP60DP
2How to connect to a PLC
The steps in successfully connecting to the Profibus:
1. Physically connect the device to the Profibus (see page 8 and page 9)
2. Configure the device parameters, see page 12 (can also be carried out
using HBM‘s “PME-Assitent“ software).
3. Configure the Profibus message and set up its parameters with the aid of a
configuration tool (such as Step7) and GSE files, or manually as shown in
chapter 6.2.
A GSE file describes the properties of a Profibus node in standardized form.
The configuration tool uses it to define which data held on individual bus
nodes will be exchanged on the Profibus.
5
A default GSE file for PME modules is supplied with the device (on system
CD: hbmxxx.gsd = German version; hbmxxxgse = English version).
Profibus
configurator
System configuration
PLC
Electronic device data sheets (GSE files)
GSE
PROFIBUS−DP
Fig. 2.1:Configuration with the aid of GSE files
HBMA0623-6.1 en/de/fr
6
PME−MP60DP
2.1Configuring and assigning parameters
•Start your configuration program (e.g. Step7; if you have no configuration
program, proceed to chapter 6.2)
•Load the HBM GSD file (PME system CD incl. GSD/GSE files for PME)
•Add an HBM device (Hardware catalog)
•From the hardware catalog choose the configuration you want on the
Profibus.
Fig. 2.2:Hardware configuration
HBMA0623-6.1 en/de/fr
PME−MP60DP
•Double-click on the configured entries to open the properties window and
select the required parameters.
7
Fig. 2.3:Setting parameters
Notes for users of the Simatic S7 PLC:
•To download consistent data of 3 bytes or over 4 bytes, use special
function modules SFC14 to read and SFC15 to write.
•In the case of the S7 3xx a maximum of 32 bytes of consistent data can be
downloaded.
To find out the meaning of the status bits and control word bits please refer to
the tables in chapter 6.3.
HBMA0623-6.1 en/de/fr
8
PME−MP60DP
3Installation
•Connect the MP60DP module to a 24 V supply voltage.
•Connect the Profibus cable to the MP60DP module. Ensure that a
terminating resistance is connected to the first and last Profibus unit (the
housing of the Profibus connector usually contains a sliding switch for this
purpose).
Example:
PLC
Profibus
connector
First device in
the bus line
sliding switch of Profibus connector to
”Resistance ON” .
Fig. 3.1:Profibus operation
Profibus
connector
Last device in
the bus line
sliding switch of Profibus
connector to ”Resistance ON”
HBMA0623-6.1 en/de/fr
PME−MP60DP
4Connections
Warning
Please note the safety instructions before commissioning the device.
4.1Pin assignment
For the pin assignment of the MP60DP module please refer to the Operating
Manual “PME industrial measurement electronics with MP60/MP07 module
field bus link”. On the front panel of the MP60DP is an additional 9−pin D-sub
connection socket for the Profibus connection.
9
6
0
9
RS485-A
Vcc (5V)
6
Fig. 4.1:Profibus connection in accordance with standard
Profibus
connection
socket
GND
5
RS485-RTS
1
RS485-B
HBMA0623-6.1 en/de/fr
10
PME−MP60DP
5Operation via the keyboard
−
During measurement you can press
the display (e.g. mV; V; Out,In; error messages).
Next to the status message “ERROR” the display shows the status of the
Profibus DP connection. One of the following status messages is displayed in
each case:
BD_SEAR (baud rate search)
WT_PARM (waiting for parameter)
WT_CONF (waiting for configuration)
DATA_EX (cyclical data communication)
ERROR (bus error)
+
− to view the status messages in
The LED shows the operating status (ready to take measurements, overflow
etc.) of the MP60DP. Instead of the CAN status (as with the MP60), however,
the Profibus status is displayed.
Operating status:
LED
colour
GreenSteady lightDATA_EX status
YellowSteady lightBD_SEAR, WT_PARM, WT_CONF status
RedSteady lightERROR status
StatusMeaning
Profibus status
The representation of the other operating statuses is the same as that of the
MP60.
HBMA0623-6.1 en/de/fr
PME−MP60DP
5.1Expanded menus
New “Profibus” group in set-up mode:
−
SET
+
11
Groups
SET
+
Up
−
Down
DIALOGUE...PEAK STOREIN/OUTCAN-BUSPROFIBUS
PasswordOperatn.Output1Baud rateAddressAmplType
PassStatInputMinModeOut1AddressMAINGRPPrgVers
Language
I.DataSClearPkVModeOut2Output
I.Displ.
I.TransdMAINGRPModeOut3PDO-FrmtSNo
I.MeasOutput4
I.ConditModeOut4MAINGRP
I.AnalogZeroing
I.LimValTare
I.PStorePkMomMax
I.I/OPkHldMax
I.CANPkMomMin
I.AddFncPkHldMin
MAINGRPParaCo1
InputMax
kN/s
1)
Output2Profile>0<Rf kNm
Output3OutR. msKeyboard
MAINGRP
ADDITION
FUNCTION
HW synchr
HW vers.
1)
ParaCo2
Overview of parameters
InpFunc
MAINGRP
Groups
In/Out
CAN-bus
SET
+
PROFIBUS
−
SET
Address
Fig. 5.1:Setting up the Profibus address
SET
↑
↓
3 − 123
ADDITIONFUNCTION
SET
+/−
HBMA0623-6.1 en/de/fr
12
PME−MP60DP
6Setup for Profibus
6.1Parameter assignment
The amplifier parameters are set via the keyboard or CAN−interface, as on
the MP60. The Profibus DP parameter assignment telegram defines some
parameters for the DP communication. If you use Profibus parameter
assignment tools which are able to evaluate the GSD files of GSD revision 1,
the following parameters are available for selection:
Parameter nameAvailable
values
Diagnosisdisabled
released
Data formatinteger 16 bits
integer 32 bits
floating point
Zeroing control bitdisabled
released
Taring control bitdisabled
released
Clear maximum
control bit
Clear minimum
control bit
Hold maximum
control bit
Hold minimum
control bit
disabled
released
disabled
released
disabled
released
disabled
released
DefaultMeaning
releasedrelease of external diagnosis
integer 16 bitsdefines the coding format for
measured values
disabledreleases function for control of
output control word
disabledreleases function for control of
output control word
disabledreleases function for control of
output control word
disabledreleases function for control of
output control word
disabledreleases function for control of
output control word
disabledreleases function for control of
output control word
Parameter set
control bit
disabled
released
disabledreleases function for control of
output control word
Tab 6.1:Meaning of the parameters
The data format set applies to all the measured values exchanged in the
cyclical data communication. The definition of the decimal places for the
formats integer 16 bits and integer 32 bits is adopted from the module setting
(display, CAN−bus) (e.g. when 3 decimal places is specified, 2.0 mm is
communicated as integer value 2000). The choice of data format also affects
the length of the input data (integer 16 bits = 1 word per analogue value,
integer 32 bits and floating = 2 words per analogue value).
HBMA0623-6.1 en/de/fr
PME−MP60DP
13
The targeted operation of the required control bits in the control word allows
you to secure all the functions not required against accidental operation in the
event of an error; otherwise, for example, the zero point set could be lost.
If you are using older parameter assignment tools the parameter values will
have to be converted to decimal or hexadecimal values:
Tab 6.2:Contents of the parameter assignment message
1)
changed by your parameter assignment tool in certain circumstances
control of output
control word
control of output
control word
HBMA0623-6.1 en/de/fr
14
PME−MP60DP
6.2Configuration
The configuration defines which data content is exchanged in the cyclical data
communication. The following data is available for selection:
Input values:
NameMeaningLength
Grossgross measured value1 or 2
words
Netnet measured value (gross minus tare value)1 or 2
words
Maxcontents of the maximum store1 or 2
words
Mincontents of the minimum store1 or 2
words
Pk−Pkpeak−to−peak, difference between max and min1 or 2
words
Status1status word with status of the limit switches and gen. error
bits
Status2double status word with differentiated error flagging2 words
1 word
Output values:
NameMeaningLength
Control wordcontrol word for triggering taring, zeroing, clearing the peak
value store, parameter set selection, etc.
Limit1level at which limit switch 1 responds1 or 2
Limit2level at which limit switch 2 responds1 or 2
Limit3level at which limit switch 3 responds1 or 2
Limit4level at which limit switch 4 responds1 or 2
1 word
words
words
words
words
The formats of the cyclically communicated data content are specified in detail
in chapter 6.3. The measured values are offered optionally as a 16-bit integer,
32-bit integer or 32 bit float. The values are always scaled to physical size
with the number of decimal places of your choice. Information on whether the
16 bit format or a 32 bit format is used and on the number of decimal places is
defined in the parameter assignment message.
Typical combinations are predefined in the GSD file. If you require other
combinations you can expand the GSD file accordingly using the following
specifications.
HBMA0623-6.1 en/de/fr
PME−MP60DP
15
6.2.1 Defining your own configuration combinations
Only one configuration entry is available. The special identification format
(special format) must be used for this. The manufacturer−specific data
specifies the contents and thus also the length of the input data and is 2 bytes
in length.
CFG entry no.MeaningContents
0channel 1special format with inputs and outputs, maximum 9 words
output, maximum 13 words input, 2 bytes comment length
(data)
The following input and output data can be configured for the cyclical data
communication. The choice of which data is actually transferred is
communicated via the manufacturer−specific data of the special identification
format.
101Control word
111(2)Limit value level 1
121(2)Limit value level 2
131(2)Limit value level 3
Length of cyclical data
inputs
Length of cyclical data
outputs
Contents of cyclical
data
Input values:
Output values:
141(2)Limit value level 4
Tab 6.3:Selecting the data content via the manufacturer−specific data
The length of the input data is the sum of all the data lengths selected for the
communication in words. When selecting the 32 bit format and the float format
for measured values, the length values in brackets must be used.
HBMA0623-6.1 en/de/fr
16
p
(
PME−MP60DP
The configuration telegram thus has the following format:
CFG byteMeaningPermitted values for CFG (hex.)
1header0xC2 (inputs and outputs, 2 bytes manufacturer−specific
data)
2length of outputs0x40 − 0x48 (1 to 9 words of outputs) or
0xC0 − 0xC8 (1 to 9 words of outputs with consistency)
3length of inputs0xC0 − 0xCC or
0x40 − 0x7C (1 to 13 words of inputs with/without
consistency)
4
5
Tab 6.4:Contents of the configuration telegram
user−specific data
Input data
Output data
selection of the data content (see
Tab 6.3)
When using the 32 bit formats data consistency must always be set.
6.3Cyclical data exchange
Depending on the configuration, the following data content is exchanged:
6.3.1 Inputs (from MP55IBS to the PLC)
Measured values
Measured values can be communicated in various forms of representation.
The forms of representation available for selection are floating (2 words, 32
bit), 16 bit fixed point number (1 word, 16 bit integer in two’s complement,
decimal place must be known to the reader) or 32 bit fixed point number (2
words, 32 bit integer in two’s complement, decimal place must be known to
the reader). For conversion of the values to fixed point representation the
number of decimal places in the module parameter assignment (display,
CAN−bus) is used as a basis.
HBMA0623-6.1 en/de/fr
PME−MP60DP
Status 1
BitsNameMeaning
0Ovflmeasured values overflow
1AOutOvflanalogue output overflow
2ScalErrscaling defective
3EEPROMErrEEPROM (parameter set) defective
4Limit1status of limit switch 1
5Limit2status of limit switch 2
6Limit3status of limit switch 3
7Limit4status of limit switch 4
8PAR1active parameter set bit 1
9PAR2active parameter set bit 1
10..14resreserved
15MViOMeasured value in order 1) (if bit 0,2,3=0)
Tab 6.5:Contents of status 1
1)
Meaning of MViO:
NOR operation of: MesswOvfl, SkalErr, EEPROMErr.
MesswOvfl is the OR operation of ADCOvfl, HardwOvfl, GrossOvfl, NetOvfl
17
The parameter set number is coded in 2 bit binary:
Bit 8 Bit 9Parameter set no.
001
102
013
114
Status 2
Double status word 2 returns detailed error flagging.
BitsNameMeaning
0HardwOvflhardware overflow
1ADCOvflADC overflow
2GrossOvflgross signal overflow
3NetOvflnet signal overflow
4AOutOvflanalogue output overflow
5MaxOvflmaximum overflow
6MinOvflminimum overflow
7NegOvfloverflow in negative direction
8Limit1status of limit switch 1
9Limit2status of limit switch 2
10Limit3status of limit switch 3
11Limit4status of limit switch 4
12ScalInErrorscaling input invalid
13ScalOutErrorscaling output invalid
14GainErrornominal value exceeded
15InitErrorworks calibration defective
16TransducerErrortransducer error
17..31resreserved
Tab 6.6:Contents of status 2
HBMA0623-6.1 en/de/fr
Loading...
+ 39 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.