HBM GN610, GN611 Technical Note

Technical Note
English
HBM public
GEN series 1 kV Input Cards GN610 and GN611
Isolation and Type Testing
GN610, GN611 Isolation and type testing

1 International standards for test equipment safety

Measurement categories

l
The international standards for test equipment safety are the IEC 61010-1 and the IEC 61010-2-030.
l
IEC 61010-1 defines three overvoltage categories (CAT II, CAT III, and CAT IV) on the power supply side of an instrument.
l
IEC 61010-2-030 defines three measurement categories (CAT II, CAT III, and CAT IV) on the measurement input side of an instrument, for measurement inputs which can be directly connected to mains.
l All measurement inputs, which are not specified to be connected to mains,
have no CAT rating and are referred to as O (like
Categories according to IEC 61010-2-030:2010
Electrical equipment, specifically measurement tools can according to IEC 61010-2-030:2010 be assigned into 4 categories. These measurement categories are indicated with the terms O (previously CAT I), CAT II, CAT III and
CAT IV. Originally these categories are used to indicate the overvoltage or surge voltage that is likely to occur and can be sustained by the equipment. Actually the category indicates the amount of energy that can be released in the event of a short circuit. A higher category number indicates a higher energy level that can occur and can be sustained by the equipment.
O (Other) (previously referred to as CAT I): This category is for measurements not directly connected to mains. Think of measurement of: signal levels, regulated low voltage circuits or protected secondary circuits. For this category there are no standard over voltage or surge impulse levels defined.
Others).
CAT II: This category is for measurements directly connected to low-voltage mains. Think of measurement of: mains sockets in household applications or portable tools. This category is expecting to have a minimum of three levels of over current protection between the transformer and connection point of the measurement. (See Figure 1.1).
CAT III: This category is for measurements directly connected to the distribution part of a low-voltage mains installation. Think of measurement of: circuit breakers, wiring, junction boxes etc. This category is expecting to have a minimum of two levels of over current protection between the transformer and connection point of the measurement. (See Figure 1.1).
2 HBM public
GN610, GN611 Isolation and type testing
CAT IV:
a low-voltage mains installation. Think of measurement of: over current protection devices, ripple control units etc. This category is expecting to have a minimum of one level of over current protection between the transformer and connection point of the measurement circuit. (See Figure 1.1).
Figure 1.1: Category indication according to IEC 61010-2-030:2010
This category is for measurements directly connected to the source of
Example: voltage 1000 V DC.
Table 1.1: Insulation test voltages according to IEC 61010
Nominal Voltage (V RMS or V DC)
≤ 150
> 150 300
> 300 600
> 600 1 000
Using the above table one can deduct that this specification informs the user the device passed the insulation tests;
4.000 V. The maximum operating input voltage is 1000 V DC. This device is to be used to measure CAT II circuitry up to 600 V.
A measurement device is specified as 600 V CAT II, maximum input
-2-
030:2010
IEC 61010-2-030:2010
5 sec. AC test (V RMS) Impulse test (V)
CAT II CAT III CAT IV CAT II CAT III CAT IV
840 1.390 2.210 1.550 2.500 4.000
1.390 2.210 3.310 2.500 4.000 6.000
2.210 3.310 4.260 4.000 6.000 8.000
3.310 4.260 6.600 6.000 8.000 12.000
5 sec at 2.210 V RMS and impulse
HBM public 3
GN610, GN611 Isolation and type testing
WARNING
Measurement inputs of this instrument should not be used to measure high-energy signals of measurement categories CAT IV (IEC 61010-2-30:2010) (e.g. mains measurements) , unless specifically stated for the specific input.
CAT II, CAT III or
4 HBM public
GN610, GN611 Isolation and type testing

1.2 Basic versus reinforced insulation

For reference below one can find the basic insulation and supplementary insulation as well as the reinforced insulation test values for CATII.
Table 1.2: Test voltages for testing electric strength of solid insulation in measuring circuits of measurement category II (IEC 61010
-2-
30:2010)
Nominal voltage line to neutral a.c r.m.s. or d.c. of MAINS being measured. (V)
≤ 150
> 150 300
> 300 600
> 600 1000
To protect a user from hazardous voltages there are several means of protection possible. As one can see below basic insulation + supplementary insulation is a possibility but also reinforced isolation is a means of protection. The test voltages are different per means as can be found in the above table.
Test voltage
5 s a.c. test V a.c. r.m.s. Impulse test V peak
Basic insulation and supplementary insulation
840 1390 1550 2500
1390 2210 2500 4000
2210 3510 4000 6400
3310 5400 6000 9600
Reinforced insulation
Basic insulation and suplementary insulation
Reinforced insulation
HBM public 5
GN610, GN611 Isolation and type testing
Additional means of protection in case of single fault conditions
Accessible parts shall be prevented from becoming HAZARDOUS LIVE IN SINGLE FAULT CONDITION. The primary means of protection (see Figure 1.2) shall be supplemented by one of A, B, C or D. Alternatively one of the single means of protection E or F shall be used. See Figure 1.2
.
Figure 1.2: Acceptable
Example: A measurement device is specified as 600 V CAT II reinforced insulation, maximum input voltage 1000 V DC. Using the above information one can deduct that this specification informs the user that the measurement device is tested on input to chassis ground 5 s at
3.510 V RMS and impulse 6.400 V. The maximum operating input voltage is 1000 V DC. This device is to be used to measure CAT II circuitry up to 600 V.
6 HBM public
arrangement of protective means against electric shock
GN610, GN611 Isolation and type testing

2 GEN series 1 kV input cards GN610, GN611

Isolation and input of the GN610, GN611

An overview of the GN610, GN611 card isolation and input is given below (see Figure 2.1). The isolation of the channel to chassis is 1000 V RMS and is also qualified as 600 V CAT II (or 300 V CAT III). The common mode of the differential input channel (isolated GND) can be 1000 V RMS with respect to the chassis. If one channel has common mode at +1000 V and one at
-1000 V (with respect to chassis), the voltage between the two channels is 2000 V. The standards at which the card is certified is IEC61010-1:2010 and IEC61010-2-30:2010.
Isolation
Input signal to chassis 1000 V RMS, 600 V CAT II (REINFORCED)
Channel to chassis 1000 V RMS, 600 V CAT II (REINFORCED)
Channel to channel 2000 V RMS, (BASIC)
Figure 2.1: Isolation 1kV card overview
l The isolation between channel and chassis is classified as
REINFORCED. This can be seen as double isolation, which is necessary because the chassis might be accessible (conductive parts can be touched) to users (personal safety).
HBM public 7
GN610, GN611 Isolation and type testing
l Isolation between channels is BASIC, since a channel is not accessible
and there is therefore no direct risk for a user (product safety).
l REINFORCED or DOUBLE isolation has higher test values than BASIC
isolation.
8 HBM public
Loading...
+ 16 hidden pages