Haws TWBS.SHE User Manual

)
INSTALLATION, OPERATION
&
MAINTENANCE INSTRUCTIONS
1455 Kleppe Lane Sparks, NV 89431-6467 (775) 359-4712 Fax (775) 359-7424
E-mail: haws@hawsco.com website: www.hawsco.com
No. 2080226(5
Model TWBS.SHE
Tempered Water Blending System
NOTE TO INSTALLER: Please leave this information with the Maintenance Department.
HAWS® warrants that this specific product is guaranteed against defective material or poor workmanship for a period of three years from date of shipment. HAWS liability under this warranty shall be discharged by furnishing without charge F.O.B. HAWS Factory any goods, or part thereof, which shall appear to the Company upon inspection to be of defective material or not of first class workmanship, provided that claim is made in writing to Haws within a reasonable period after receipt of the product. Where claims for defects are made, the defective part or parts shall be delivered to the Company, prepaid, for inspection. HAWS will not be liable for the cost of repairs, alterations or replacements, or for any expense connected therewith made by the owner or his agents, except upon written authority from HAWS, Sparks, Nevada. HAWS will not be liable for any damages caused by defective materials or poor workmanship, except for replacements, as provided above. Buyer agrees that Haws has made no other warranties either expressed or implied in addition to those above stated, except that of title with respect to any of the products or equipment sold hereunder and that HAWS shall not be liable for general, special, or consequential damages claimed to arise under the contract of sale.
The thermostatic mixing valve manufactured by HAWS is warranted to function if installation and maintenance instructions provided are adhered to. The units also must be used for the purpose, which they were intended. This product is intended to supplement first-aid treatment. Due to widely varying conditions HAWS cannot guarantee that the use of this emergency equipment will prevent serious injury or the aggravation of existing or prior injuries.
NO OTHER WARRANTIES EXPRESSED OR IMPLIED ARE AUTHORIZED, PROVIDE D OR GIVEN BY HAWS.
SHOULD YOU EXPERIENCE DIFFICULTY WITH THE INSTALLATION OF THIS MODEL, OR REQUIRE REPLACEMENT PARTS, PLEASE CALL:
TECHNICAL SUPPORT:
LIMITED WARRANTY
1-800-766-5612
FOR CUSTOMER SERVICE: 1-888-640-4297
01/14 TWBS.SHE Page 1 of 6
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
Valve operating principle:
The Haws Corporation TWBS.SHE Emergency Valve thermostatically mixes hot and cold water to provide a safe fluid supply for emergency showers and eyewash equipment. The TWBS.SHE valve contains a secondary high temperature limit valve to provide additional protection to the user in the event of main tempering valve malfunction. Additionally, to ensure a fail-safe water supply for emergency shower and eyewash stations, a series of cold water by-pass valves open in the event of hot water pressure loss, or main valve thermostat malfunction.
Valve features:
Paraffin filled thermostats with industry leading response time. ‐ Tempered water: Temperature is factory set to 85°F (29°C). ‐ Tempered water: High temperature limit is factory set to 85°F (29°C). ‐ The over temperature valve is calibrated to shut off the hot water inlet flow when the outlet
temperature exceeds 95°F (35°C).
Cold water by-pass valve opens if hot water fails. ‐ Actively suspends hot water flow when cold water supply is lost to protect against scalding. ‐ Cold water by-pass valves are closed during normal operation, regardless of flow rate.
Valve sizing:
The flow capacity table shown below contains discharge flow rates @ 85°F (29 °C) outlet temperature with the valve tested under the conditions described by ASSE 1071.
Flow Capacity
Model No. Min flow
TWBS.SHE
* Denotes minimum flow rate without re-circulation.
1.0* GPM
5 PSI 10 PSI 20 PSI 30 PSI 40 PSI 45 PSI By-pass @ 30 PSI
30
GPM
Pressure drop across valve Cold water
43
GPM
60
GPM
74
GPM
85
GPM
91
GPM
50
GPM
Valve specifications:
Maximum operating pressure: 125 PSI ‐ Minimum / Maximum hot water temperature: 120°F / 180°F (49°C / 82°C). ‐ Tempered water temperature adjustment range: 60°F – 85°F (15°C - 29°C) ‐ Compliance/Listings: ASSE 1071, NSF 61, California Lead Plumbing Law and applicable
sections of CSA B125.3.
IMPORTANT
To ensure the proper operation of the TWBS.SHE valve it is essential to:
Properly size the valve for each application. ‐ Keep the outlet temperature set between 60°F and 85°F (15°C - 29°C). ‐ Haws recommends a weekly testing and recording of the outlet water temperature.
Failure to comply with installation and/or maintenance instructions could result in valve failure.
01/14 Model TWBS.SHE Page 2 of 6