98 2420341380 E 02.12 USA
Summit Series
D
- Equipment Maintenance
129OPEN
CIRCUIT FS
EXT (FWS
C25)
A load of less than 70
mA was detected when
FS Ext (FWS C25)
circuit was energized
Disconnect a wire from
FS Ext (FWS C25) coil
This is a latched error.
Power must be cycled
to clear error.
Checked only at power
up
Machines with 4WS
option only
130SHORTE
D CIRCUIT
FS RET (FWS
C25)
Excessive load was
detected when FS Ext
(FWS C25) circuit was
energized
Use a piece of wire to
short the FS Ext (FWS
C25) coil
This is a latched error.
Power must be cycled
to clear error.
Checked only at power
up
Machines with 4WS
option only
131OPEN
CIRCUIT DC
D FWD (FWS
C26)
A load of less than 70
mA was detected when
DC D Fwd (FWS C26)
circuit was energized
Disconnect a wire from
DC D Fwd (FWS C26)
coil
This is a latched error.
Power must be cycled
to clear error.
Checked only at power
up
Machines with 4WS
option only
132SHORTE
D CIRCUIT
DC D FWD
(FWS C26)
Excessive load was
detected when DC D
Fwd (FWS C26) circuit
was energized
Use a piece of wire to
short the DC D Fwd
(FWS C26) coil
This is a latched error.
Power must be cycled
to clear error.
Checked only at power
up
Machines with 4WS
option only
133OPEN
CIRCUIT DC
D REV (FWS
C27)
A load of less than 70
mA was detected when
DC D Rev (FWS C27)
circuit was energized
Disconnect a wire from
DC D Rev (FWS C27)
coil
This is a latched error.
Power must be cycled
to clear error.
Checked only at power
up
Machines with 4WS
option only
134SHORTE
D CIRCUIT
DC D REV
(FWS C27)
Excessive load was
detected when DC D
Rev (FWS C27) circuit
was energized
Use a piece of wire to
short the DC D Rev
(FWS C27) coil
This is a latched error.
Power must be cycled
to clear error.
Checked only at power
up
Machines with 4WS
option only
135OPEN
CIRCUIT DC
D (FWS C28)
A load of less than 70
mA was detected when
DC D (FWS C28)
circuit was energized
Disconnect a wire from
DC D (FWS C28) coil
This is a latched error.
Power must be cycled
to clear error.
Checked only at power
up
Machines with 4WS
option only
136SHORTE
D CIRCUIT
DC D (FWS
C28)
Excessive load was
detected when DC D
(FWS C28) circuit was
energized
Use a piece of wire to
short the DC D (FWS
C28) coil
This is a latched error.
Power must be cycled
to clear error.
Checked only at power
up
Machines with 4WS
option only
137OPEN
CIRCUIT DC
D (FWS C29)
A load of less than 70
mA was detected when
DC D (FWS C29)
circuit was energized
Disconnect a wire from
DC D (FWS C29) coil
This is a latched error.
Power must be cycled
to clear error.
Checked only at power
up
Machines with 4WS
option only
138SHORTE
D CIRCUIT
DC D (FWS
C29)
Excessive load was
detected when DC D
(FWS C29) circuit was
energized
Use a piece of wire to
short the DC D (FWS
C29) coil
This is a latched error.
Power must be cycled
to clear error.
Checked only at power
up
Machines with 4WS
option only
139OPEN
CIRCUIT DC
D (FWS C30)
A load of less than 70
mA was detected when
DC D (FWS C30)
circuit was energized
Disconnect a wire from
DC D (FWS C30) coil
This is a latched error.
Power must be cycled
to clear error.
Checked only at power
up
Machines with 4WS
option only
140SHORTE
D CIRCUIT
DC D (FWS
C30)
Excessive load was
detected when DC D
(FWS C30) circuit was
energized
Use a piece of wire to
short the DC D (FWS
C30) coil
This is a latched error.
Power must be cycled
to clear error.
Checked only at power
up
Machines with 4WS
option only
141OPEN
CIRCUIT DC
D (FWS C31)
A load of less than 70
mA was detected when
DC D (FWS C31)
circuit was energized
Disconnect a wire from
DC D (FWS C31) coil
This is a latched error.
Power must be cycled
to clear error.
Checked only at power
up
Machines with 4WS
option only