Hartzell 34-24 Click Here for the Hartzell Spec Sheet

HARTZELL
Hartzell Fan, Inc., Piqua, Ohio 45356
www.hartzellfan.com
®
Ring & Panel Fans Belt & Direct Drive Series 01 Series 02 Series 08 Series 09 Series 10 Series 14
Bulletin A-109-AJ May 2009
Propeller Fans and Wall Ventilators
H
T
I
H
W
O
T
L
I
U
B
H
A
R
P
I
Q
U
N
O
R
C
N
I
,
Z
N
E
A
F
L
L
A
S
U
A
,
O
I
O
H
Propeller Fan Construction
and Selection . . . . . . . . . . . . . . . . . . . . . . . . Pages 2-3
Direct Drive Propeller Fans . . . . . . . . . . . . . . . . Pages 4-9
Belt Drive Propeller Fans . . . . . . . . . . . . . . . Pages 10-13
Reversible Fans . . . . . . . . . . . . . . . . . . . . . . . . . . Page 14
Low Speed High Volume Fans . . . . . . . . . . . . . . . Page 15
Filtered Wall Ventilators . . . . . . . . . . . . . . . . Pages 16-21
Accessory Mounting Configurations . . . . . . . Pages 22-23
Options and Accessories . . . . . . . . . . . . . . . . Pages 24-26
Other Propeller Fans . . . . . . . . . . . . . . . . . . . . . . . Page 27
How To Use Model Code Index:
Example: Assume a required performance of 10,000 CFM, at 0" SP standard air. Reading across the Series 02S Rating Table on
page 7, we find the 28" size with fan RPM of 1750 and brake horsepower of .71. This unit has a 2-blade, Type “NB” propeller. Motor horsepower is
3
4.
The model code can be constructed as follows: Type will be a production item (code A), product series for the Standard Flow Panel Fan is 02S, size of the wheel is 28", “G” (General Industrial) Duty construction, number of blades is 2, blade is NB, material of construction is steel (code ST), totally enclosed fan cooled (code FC), motor horsepower is
3
4 (code G), and motor RPM/phase is 1750
(code 3). This fan is also available in Hartzell HRS.
Note: All other informational fields must be filled with hyphens/dashes (–) if they are not applicable to the fan being considered.
A02SG–282NB ––– ST FC G3
Type
A – Production Item S – Stock Item
Q – Special Quote Product Series Duty (G or H) Size (nominal wheel diameter, inches) No. of Blades Wheel Code Blade Angle, no decimal (applies only to adjustable pitch fans) Material of Construction Motor Enclosure Motor Horsepower Motor RPM/ Phase
Motor RPM/ Phase 3 Phase 1 Phase
2 = 3450 B = 3450 3 = 1750 C = 1750 4 = 1140 D = 1140 5 = 870 E = 870 6 = 690 F = 690 7 = 575 G = 575
Index
Certified Ratings for Air Performance
Hartzell Fan, Inc. certifies that the Series 01S and 01R Direct Drive Ring Fan, Standard or Reverse Flow, and the Series 02S and 02R Direct Drive Panel Fan, Standard or Reverse Flow, shown on pages 4-9; Belted Ring Fan, Standard or Reverse Flow, Series 08S and 08R, and Series 09S and 09R, Belted Panel Fan, Standard or Reverse Flow, shown on pages 10-13 are licensed to bear the AMCA seal. The ratings are based on tests and procedures performed in accordance with AMCA Standard 211 and comply with the requirements of the AMCA Certified Ratings Program.
Propeller Fan Selection
The Hartzell Propeller Fan and Wall Ventilator performances on the following pages are based on standard air-conditions (sea level, 70°F, and 29.92 inches barometric pressure).
When placing your order, be sure to specify the Hartzell Model Code. The following example demonstrates our coding system. The illustrated Series Number specifies a Hartzell Series 02S Standard Flow Panel Fan (Direct Drive).
Be sure to include fan model, performance requirements, operating temperature, motor data (enclosure, voltage, mounting position, etc.) and a list of required accessory items. (See pages 24-26.)
Contact your local Hartzell Sales Representative for assistance.
Hartzell Model Code Explanation
Motor Horsepower
Horsepower
1
/41/31/23/4 111/2 23571/2 10 15 20 25 30
Code Letter D E F G H I J K L M N O P Q R
2
Bulletin A-1
09-AJ
www.hartzellfan.com
1 (800) 336-3267
®
This bulletin lists Hartzell’s line of Propeller Fans and Wall Ventilators and accessories. More than 70 Hartzell offices can provide specific performance and installation data to meet your requirements. Call your Hartzell representative for assistance. Visit our website
(www.hartzellfan.com) or call toll-free for the name of your Hartzell representative…
1-800-336-3267
Certificates of Design Assessment are issued by the American Bureau of Shipping. The assessment is a representation by the Bureau as to the degree of compliance the design exhibits with applicable sections of the Rules. The certificates, by itself, do not reflect that the products are Type Approved.
Blade Types
…Multiple Designs For Various Application
Construction Features
The Hartzell propeller type fan can be manufactured as a ring or panel type fan, standard or reverse flow, direct or belt driven and they are available in a wide range of sizes. The fan shall be packaged completely assembled and ready to install.
The fan propeller shall be an airfoil design, cast of 319 aluminum in compliance with Federal Specification QQ-A-601E and ASTM B26. Propellers shall be retained on the motor shaft
utilizing a split taper bushing or a clamp block arrangement. The propeller shall be mounted in a high efficiency air seal fan orifice with the smaller diameter of the ring overlapping the propeller tips.
“G” (General Industrial) Duty construction features an adjustable steel motor base and tubular steel frame, which are oversized to provide structurally rugged construction. “G” Duty is available as Series 02 and Series 09 in sizes 18" to 48" and will be limited by HP and RPM on certain sizes. Please reference the performance rating tables, the shaded models are those models offered as “G” duty.
“H” (Heavy Industrial) Duty construction features solid rolled rod supports, welded to the fan panel and motor mount to provide support for the motor. The steel motor base and solid steel support rods are oversized to
provide
structurally rugged construction.
“H” Duty is available in all sizes and mod­els.
Standard surface coating system shall be phosphatized surface preparation with an industrial grade air dry enamel paint. Motors shall be totally enclosed
air over type. Fans shall be designed for mounting in any position from horizontal to vertical.
The fan assembly shall be dynamically balanced at the Hartzell factory prior to shipping. Fans shall be balanced in accordance with AMCA Standard 204-96, fan application category BV-3 (comparable to Grade G6.3). Fans shall be manufactured in accordance with Hartzell’s standard quality assurance procedures.
Type N
Single-Propeller – Has unexcelled
efficiency when used in free air or against low pressures. Excellent for general exhaust, ventilation, drying and in roof ventilators. Sizes 12" to 60".
Type L
Lo-Noise – Airfoil blades operate
with full efficiency against low and moderate pressures at slow tip speeds without excessive noise. Reduces noise intensity up to 30%. 18" to 60".
Type W
Four-Blade – Four-bladed integral
cast propeller fans designed for high efficiency and low speed operation. Air delivery is excellent at or near free air. Ideal for general exhaust ventilation. 16" to 44".
Type O, P and Q
Multiblade – Carries its efficiency
farther along the pressure range than the single propeller. Excellent against moderate pressures. Sizes 12" to 44". Type O-4 blades; type P-6 blades, and type Q-8 blades.
Type C
High-Pressure – Modifications of
blade design increase efficiency at higher pressures. Operates successfully against pressures as high as 4" water gauge. 6 or 8 blades. 24" to 60".
Type AA
Multiblade – Outstanding line of
four and six bladed adjustable pitch propeller fans. Performance features low speeds and high efficiency from free air through moderate pressures. 48" to 72".
3
Bulletin A-1
09-AJ
www.hartzellfan.com
1 (800) 336-3267
®
Series 01S Ring Fan Direct Drive
Series 09S Panel
Fan Belt Drive
Type AL
Adjustable pitch Swept-back design includes features
to reduce noise levels. Excellent for low pressure applications to match performance more closely. Available in two, three, and four bladed configurations, sizes 18” thru 36”. See ESP for selection details.
Series 01S
Hartzell Fan, Inc. certifies that the 01S-Direct Drive Ring Fan, Standard Flow and 01R-Direct Drive Ring Fan, Reverse Flow, shown hereon is licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Standard 211 and comply with the requirements of the Certified Ratings Program.
Series 01S – Standard Flow and 01R – Reverse Flow Direct Drive Ring Fans.
Air Seal Fan Orifice.
Sizes 12" to 72".
STANDARD AIR FLOW – SERIES 01S
Standard Ring Fans (Direct Drive)
REVERSE AIR FLOW – SERIES 01R
CONFIGURATION 1 - RF
FAN ONLY
CONFIGURATION 1 - SF
FAN ONLY
Principal Dimensions
FAN
MAX. MAX.
MAX. MAX. MAX.
SIZE
AB C C1DF F1GK LM
MOTOR WT. # WT. # FRAME
ST L. FAN AL UM . FAN
12 12 143⁄4 141⁄8 163⁄8 131⁄2 155⁄8 141⁄4 23⁄16 15⁄813⁄165⁄16 145T 11 8
14 14 163⁄4 161⁄8 183⁄8 151⁄2 161⁄8 141⁄4 23⁄16 15⁄813⁄165⁄16 145T 12 8
16 16 183⁄4 181⁄8 203⁄8 171⁄2 161⁄8 141⁄2 23⁄16 15⁄813⁄165⁄16 145T 15 10
18 18 203⁄4 201⁄8 223⁄8 191⁄2 161⁄8 141⁄2 23⁄16 15⁄813⁄165⁄16 145T 18 12
20 20 223⁄4 221⁄8 243⁄8 211⁄2 161⁄8 145⁄8 23⁄16 15⁄83⁄165⁄16 145T 21 14
22 22 251⁄2 2411⁄16 275⁄8 24 165⁄8 147⁄8 31⁄4 35⁄8 13⁄167⁄16 145T 27 17
24 24 271⁄2 2611⁄16 295⁄8 26 181⁄8 17 31⁄4 35⁄8 13⁄167⁄16 184T 31 19
28 28 311⁄2 3011⁄16 335⁄8 30 181⁄8 17 31⁄4 35⁄8 13⁄167⁄16 184T 36 22
32 32 351⁄2 3411⁄16 375⁄8 34 231⁄8 223⁄8 31⁄4 35⁄8 13⁄167⁄16 256T 44 29
36 36 41 397⁄16 433⁄4 38 243⁄8 223⁄8 45⁄8 33⁄8 111⁄169⁄16 256T 71 46
40 40 45 437⁄16 473⁄4 42 255⁄8 223⁄8 45⁄8 33⁄8 111⁄169⁄16 256T 108 68
44 44 49 477⁄16 513⁄4 46 255⁄8 235⁄8 45⁄8 33⁄8 111⁄169⁄16 256T 124 73
48 48 54 527⁄16 58 50 32 303⁄4 515⁄16 429⁄16 365T 138 93
54 54 60 587⁄16 64 56 34 303⁄4 515⁄16 429⁄16 365T 183 115
60 60 66 647⁄16 70 62 351⁄2 31 515⁄16 429⁄16 365T 244 170
72 72 78 761⁄2 82 74 311⁄8 311⁄8 515⁄16 429⁄16 365T 260 176
WT. # LESS
MTR. & OPTIONS
NOTE: Dimensions and specifications are subject to change. Certified prints are available.
4
Bulletin A-1
09-AJ
www.hartzellfan.com
1 (800) 336-3267
®
ABS Certificate
of Design Assessment
Received
Series 02S
“G” Duty Shown
Series 02S
“H” Duty Shown with
AL Adjustable Pitch Prop
CONFIGURATION 1 - RF
FAN ONLY
CONFIGURATION 1 - SF
FAN ONLY
Standard Panel Fan (Direct Drive)
STANDARD AIR FLOW – SERIES 02S
REVERSE AIR FLOW – SERIES 02R
Series 02S – Standard Flow and 02R – Reverse Flow Direct Drive Panel Fans.
“G” (General Industrial) Duty and “H” (Heavy Industrial) Duty construction are available.
See page 3 and performance rating table.
Steel spun orifice panel.
Sizes 12" to 60".
Hartzell Fan, Inc. certifies that the 02S-Direct Drive Panel Fan, Standard Flow and 02R- Direct Drive Panel Fan, Reverse Flow, shown hereon is licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Standard 211 and comply with the requirements of the Certified Ratings Program.
Drawing for “G” (General Industrial) Duty construction shown, overall envelope dimensions of the “H” (Heavy Industrial) Duty construction will remain the same, except Fmax/F1max dimension, which is significantly larger for “H” Duty Construction.
MOTOR MAX MAX WT.
FAN
ABCD
FF
1
G
L
MNPRSTU
FRAME
MOTOR STEEL (LESS
SIZE
(MAX) (MAX)
STEEL
MIN. MAX.
HP
MOTOR WT.)
12 121⁄8 16 13⁄4 13⁄4 16 15 31⁄2 16 GA. 21⁄2 1 11.00 117⁄16 x 3⁄4 2
7
8 48 145T 2 15
14 143⁄16 18 2 13⁄4 161⁄4 15 33⁄4 16 GA. 21⁄2 1 13.00 137⁄16 x 3⁄4 2
7
8 48 145T 2 16
16 163⁄16 20 21⁄8 13⁄4 161⁄4 15 37⁄8 16 GA. 21⁄2 1 15.00 157⁄16 x 3⁄4 2
7
8 48 145T 2 17
18 181⁄8 22 21⁄2 13⁄4 133⁄8 145⁄16 41⁄4 16 GA. 21⁄2 1 17.00 177⁄16 x 3⁄4 2
7
8 48 56
3
4 51
20 203⁄16 25 21⁄2 13⁄4 143⁄4 145⁄16 41⁄4 16 GA. 21⁄2 2 10.00 207⁄16 x 3⁄4 3
7
8 48 143T 1 64
24 243⁄16 28 31⁄2 2143⁄4 145⁄16 51⁄2 14 GA. 21⁄2 2 11.50 237⁄16 x 3⁄4 3 1 48 145T 11⁄2 78
28 283⁄16 33 31⁄2 21⁄2 201⁄2 189⁄16 6 14 GA. 21⁄2 2 14.00 287⁄16 x 3⁄4 311⁄4 48 145T 2 102
32 323⁄16 36 31⁄2 23⁄4 201⁄2 183⁄4 61⁄4 14 GA. 21⁄2 2 15.50 317⁄16 x 3⁄4 313⁄8 48 184T 2 120
36 363⁄16 42 4 23⁄4 221⁄2 223⁄4 63⁄4 14 GA. 21⁄2 3 12.33 377⁄16 x 3⁄4 413⁄8 56 213T 3 147
40 403⁄16 46 43⁄8 23⁄4 223⁄4 223⁄4 71⁄8 14 GA. 21⁄2 3 13.66 417⁄16 x 3⁄4 413⁄8 56 215T 5 168
44 443⁄16 50 43⁄4 23⁄4 251⁄2 231⁄2 71⁄2 14 GA. 21⁄2 3 15.00 457⁄16 x 3⁄4 413⁄8 56 254T 5 183
48 483⁄16 54 43⁄4 23⁄4 251⁄2 231⁄2 71⁄2 14 GA. 21⁄2 3 16.33 497⁄16 x 3⁄4 413⁄8 56 254T 5 192
54 543⁄16 60 5 23⁄4 323⁄8 32 73⁄4 14 GA. 21⁄2 3 18.33 557⁄16 x 3⁄4 413⁄8 213T 365T 20 165
60 60
3
16 66 51⁄2 23⁄4 333⁄4 335⁄8 81⁄4 14 GA. 21⁄2 3 20.33 617⁄16 x 3⁄4 413⁄8 213T 365T 20 279
Principal Dimensions
NOTE: Dimensions and specifications are subject to change. Certified prints are available. Dimensions for fan sizes 12", 14", 16", 54" and 60" are "H" Duty construction.
5
Bulletin A-1
09-AJ
www.hartzellfan.com
1 (800) 336-3267
®
Hartzell Fan, Inc. certifies that the Panel Fan, Series 02, herein, are authorized to bear CE Marking in accordance with Machinery Safety Directive 98/37/EC of the European Union. Reference Technical File E.S. 13.2.2.
ABS Certificate
of Design Assessment
Received
AIRFLOW
-SLOT
-REQ'D PER SIDE
SQUARE OUTSIDE
SQUARE
OUTSIDE
I.D.
I.D.
-SPACE S
=
@
MAX.
REF.
AIRFLOW
-SLOT
-REQ'D PER SIDE
-SPACE S
=
@
MAX.
1
REF.
Peak CFM @ STATIC PRESSURE
Size Model Code
Motor
Fan
HP RPM BHP 0"
1
/8"
1
/4"
3
/8"
1
/2"5/8"
3
/4"
7
/8"1"11/4"11/2"
12
A_ _ _ _-126-P---STFCD2
1
4 3450 0.24 1,926 1,803 1,688 1,533 1,236 ,960 ,765 ,603
A_ _ _ _-124-O---STFCD3
1
4 1725 0.10 1,475 1,263
A_ _ _ _-142-N---STFCD2
1
4 3450 0.22 2,302 2,005 1,715 1,187 ,592
A_ _ _ _-146-P---STFCG2
3
4 3450 0.62 3,647 3,545 3,420 3,282 3,133 2,,950 2,680 2,160
14 A_ _ _ _-146-P---STFCD3
1
4 1725 0.08 1,798 1,540 ,746
A_ _ _ _-144-O---STFCD3
1
4 1725 0.16 2,263 1,975 ,765 ,493
A_ _ _ _-144-O---STFCD4
1
4 1140 0.05 1,478 ,428
A_ _ _ _-162NA---STFCD3
1
4 1725 0.09 2,124 1,552 ,400
A_ _ _ _-166-P---STFCD3
1
4 1725 0.18 2,657 2,,360 1,930 1,123 ,760 ,525
16 A_ _ _ _-164-W---STFCD3
1
4 1725 0.27 3,239 2,940 2,650 1,145 ,813
A_ _ _ _-162NB---STFCD4
1
4 1140 0.06 2,046
A_ _ _ _-164-W---STFCD4
1
4 1140 0.06 2,128 1,695 ,433
A_ _ _ _-184WA---STFCE3
1
3 1740 0.35 4,280 3,995 3,675 3,185 1,495 1,095 ,635
A_ _ _ _-182NA---STFCD3
1
4 1725 0.08 2,532 1,800 ,410
A_ _ _ _-188-Q---STFCD3
1
4 1725 0.28 3,346 3,100 2,660 1,985 1,530 1,160
18
A_ _ _ _-183-L---STFCE3
1
3 1750 0.34 3,530 3,170 2,760 2,260 1,395 ,710
A_ _ _ _-184WB---STFCE3
1
3 1725 0.37 4,081 3,735 3,390 2,975 1,335
A_ _ _ _-184WA---STFCD4
1
4 1185 0.12 2,915 2,465 ,960 ,310
A_ _ _ _-182NB---STFCD4
1
4 1140 0.08 2,589 1,720
A_ _ _ _-184WA---STFCF5
1
4 850 0.04 2,090 ,705
A_ _ _ _-208-Q---STFCH3 1 1750 0.98 6,082 5,805 5,515 5,125 2,850 2,350 2,000 1,755
A_ _ _ _-202NB---STFCD3
1
4 1725 0.12 3,199 2,363 ,945
A_ _ _ _-202NA---STFCD3
1
4 1725 0.24 4,168 3,495 2,525 ,785
A_ _ _ _-203-L---STFCF3
1
2 1725 0.52 4,905 4,510 4,100 3,665 2,015 1,135 ,925
A_ _ _ _-206-P---STFCF3
1
2 1725 0.50 4,985 4,600 4,175 3,520 2,190 1,445 1,305
20
A_ _ _ _-204-W---STFCG3
3
4 1725 0.78 6,305 5,900 5,525 5,130 4,565 1,970 1,560
A_ _ _ _-202NA---STFCD4
1
4 1140 0.07 2,728 ,945
A_ _ _ _-203-L---STFCD4
1
4 1140 0.14 3,238 2,620 ,875
A_ _ _ _-206-P---STFCD4
1
4 1140 0.15 3,316 2,690 1,170 ,760
A_ _ _ _-208-Q---STFCD4
1
4 1140 0.26 3,935 3,480 1,560 1,115
A_ _ _ _-204-W---STFCD4
1
4 1140 0.22 4,114 3,525 1,420 ,830
A_ _ _ _-208-Q---STFCD5
1
4 850 0.11 2,934 1,305 ,660
A_ _ _ _-226-P---STFCH3 1 1750 0.98 7,170 6,775 6,350 5,905 5,425 4,500 2,930 2,450
22
A_ _ _ _-222-N---STFCD3
1
4 1725 0.27 5,029 4,200 3,205 1,130
A_ _ _ _-226-P---STFCD4
1
4 1140 0.27 4,647 3,990 2,400 1,555 ,915
A_ _ _ _-226-P---STFCD5
1
4 850 0.11 3,465 2,400 ,860
Performance Data
Size 22" not available in Series 02S or 02R. Performance certified is for installation Type B: Free Inlet, Ducted Outlet. Speed (RPM) shown is nominal. Performance is based on actual speed of test. Performance ratings do not include the effects of appurtenances (accessories).
"G" (General Industrial) Duty construction available for models with shaded performance. "H" (Heavy Industrial) Duty construction available for all models.
Rating Table – Series 01S, 01R, 02S, 02R
6
Bulletin A-1
09-AJ
www.hartzellfan.com
1 (800) 336-3267
®
Performance certified is for installation Type B: Free Inlet, Ducted Outlet. Speed (RPM) shown is nominal. Performance is based on actual speed of test. Performance ratings do not include the effects of appurtenances (accessories).
"G" (General Industrial) Duty construction available for models with shaded performance. "H" (Heavy Industrial) Duty construction available for all models.
Rating Table – Series 01S, 01R, 02S, 02R
7
Bulletin A-1
09-AJ
www.hartzellfan.com
1 (800) 336-3267
®
Peak CFM @ STATIC PRESSURE
Size Model Code
Motor
Fan
HP RPM BHP 0"
1
/8"
1
/4"3/8"
1
/2"
5
/8"
3
/4"
7
/8"1"11/4"11/2"
A_ _ _ _-246-C---STFCK2 3 3450 3.40 10,679 10,435 10,190 9,945 9,680 9,420 9,140 8,860 8,540 7,900 7,270
A_ _ _ _-242NA---STFCD3
1
4 1725 0.29 5,529 4,450 2,970
A_ _ _ _-246-C---STFCE3
1
3 1725 0.45 5,324 4,820 4,245 3,605 2,955 2,205 1,450
A_ _ _ _-242NB---STFCF3
1
2 1725 0.56 7,170 6,300 5,350 3,750 1,750
A_ _ _ _-242NC---STFCG3
3
4 1725 0.80 7,936 7,225 6,460 5,490 2,800
A_ _ _ _-246PA---STFCH3 1 1750 1.10 8,436 8,075 7,610 7,100 6,605 6,020 5,060 3,825 3,020 2,090
A_ _ _ _-246PB---STFCI3 11⁄2 1750 1.50 9,529 9,140 8,740 8,310 7,800 7,085 6,070 4,160 3,500 2,590 1,860
A_ _ _ _-246PC---STFCJ3 2 1750 2.00 10,630 10,240 9,810 9,385 8,970 8,340 7,550 4,510 3,990 3,150 2,640
24 A_ _ _ _-244-W---STFCJ3 2 1750 2.10 11,067 10,610 10,090 9,705 9,225 8,670 7,880 4,100 3,330 2,560
A_ _ _ _-242NB---STFCD4
1
4 1140 0.16 4,766 3,350
A_ _ _ _-242NC---STFCD4
1
4 1140 0.23 5,245 4,155 1,560
A_ _ _ _-243-L---STFCE4
1
3 1140 0.34 5,655 4,985 4,230 1,820
A_ _ _ _-244-W---STFCF4
1
2 1140 0.57 7,221 6,540 5,770 2,640 1,790
A_ _ _ _-246PC---STFCF4
1
2 1140 0.52 6,929 6,300 5,550 2,920 2,200
A_ _ _ _-242NC---STFCD5
1
4 850 0.09 3,910 1,315
A_ _ _ _-243-L---STFCD5
1
4 850 0.15 4,209 3,235 1,015
A_ _ _ _-244-W---STFCD5
1
4 850 0.24 5,384 4,420 1,490
A_ _ _ _-282ND---STFCD3
1
4 1725 0.28 6,724 5,000 2,750
A_ _ _ _-282NA---STFCF3
1
2 1725 0.45 7,928 6,705 5,385 3,630 1,580
A_ _ _ _-282NB---STFCG3
3
4 1725 0.71 10,032 8,910 7,820 6,440 4,260
A_ _ _ _-282NC---STFCH3 1 1750 1.00 10,571 9,600 8,590 7,450 5,225 2,900
A_ _ _ _-286PB---STFCI3 11⁄2 1750 1.60 10,677 10,205 9,700 9,185 8,620 7,985 7,260 6,340 5,170 3,710 2,370
A_ _ _ _-286PA---STFCJ3 2 1750 2.30 12,643 12,120 11,600 11,080 10,500 9,870 9,180 8,330 6,730 4,650 3,340
A_ _ _ _-288-C---STFCK3 3 1750 3.00 14,283 13,790 13,330 12,925 12,430 11,710 10,840 9,800 8,500 4,560 3,590
A_ _ _ _-282NE---STFCD4
1
4 1140 0.17 5,823 3,530
28 A_ _ _ _-282NC---STFCD4
1
4 1140 0.27 6,860 5,320 2,230
A_ _ _ _-283-L---STFCG4
3
4 1140 0.77 8,739 8,035 7,245 6,250 3,700 2,190 1,510
A_ _ _ _-284-W---STFCH4 1 1160 1.10 10,991 10,240 9,470 8,630 7,600 3,310 2,600
A_ _ _ _-282NC---STFCD5
1
4 850 0.11 5,110 2,200
A_ _ _ _-286PB---STFCD5
1
4 850 0.18 5,166 4,105 2,185
A_ _ _ _-286PA---STFCD5
1
4 850 0.26 6,155 5,035 2,925 1,435
A_ _ _ _-283-L---STFCE5
1
3 850 0.31 6,470 5,450 3,790 1,400
A_ _ _ _-284-W---STFCF5
1
2 850 0.44 8,040 7,030 5,800 2,150
A_ _ _ _-284-W---STFCD6
1
4 690 0.23 6,526 5,225 1,825
A_ _ _ _-322NB---STFCH3 1 1750 1.00 12,627 11,320 9,915 8,200 5,130
A_ _ _ _-322NA---STFCJ3 2 1750 2.00 16,451 15,390 14,270 13,060 11,750 10,190 6,310
A_ _ _ _-326PB---STFCK3 3 1750 3.00 16,054 15,570 14,900 14,085 13,220 12,300 11,220 10,060 8,830 6,880 5,700
A_ _ _ _-326PA---STFCM3 71⁄2 1750 6.84 23,215 22,705 22,190 21,675 21,155 20,625 20,080 19,515 18,900 17,345
A_ _ _ _-322NB---STFCD4
1
4 1140 0.27 8,184 6,040
A_ _ _ _-322NA---STFCF4
1
2 1140 0.55 10,692 9,000 6,930 2,350
A_ _ _ _-326PB---STFCH4 1 1160 0.94 10,796 9,800 8,630 6,910 5,530 4,170 3,370 2,600 1,900
32
A_ _ _ _-323-L---STFCI4 1
1
2 1160 1.60 13,293 12,370 11,430 10,460 8,900 4,660 3,490
A_ _ _ _-324-W---STFCJ4 2 1160 2.30 16,010 15,190 14,280 13,410 12,500 6,375 5,300 4,600 3,850
A_ _ _ _-322NA---STFCD5
1
4 850 0.23 7,972 5,550
A_ _ _ _-323-L---STFCF5
1
2 850 0.63 9,741 8,470 7,000 2,930
A_ _ _ _-326PA---STFCG5
3
4 850 0.73 11,275 10,210 9,025 4,615 3,675
A_ _ _ _-324-W---STFCH5 1 870 0.94 12,007 10,870 9,700 4,780 3,400
A_ _ _ _-326PB---STFCD6
1
4 690 0.19 6,422 4,380 2,160
A_ _ _ _-323-L---STFCE6
1
3 690 0.34 7,907 6,300 2,350
A_ _ _ _-324-W---STFCF6
1
2 690 0.48 9,523 8,050 3,510 2,060
Rating Table – Series 01S, 01R, 02S, 02R
Performance certified is for installation Type B: Free Inlet, Ducted Outlet. Speed (RPM) shown is nominal. Performance is based on actual speed of test. Performance ratings do not include the effects of appurtenances (accessories).
"G" (General Industrial) Duty construction available for models with shaded performance. "H" (Heavy Industrial) Duty construction available for all models.
8
Bulletin A-1
09-AJ
www.hartzellfan.com
1 (800) 336-3267
®
Peak CFM @ STATIC PRESSURE
Size Model Code
Motor
Fan
HP RPM BHP 0"
1
/8"
1
/4"
3
/8"
1
/2"5/8"
3
/4"
7
/8"1"11/4"11/2"
A_ _ _ _-362ND---STFCH3 1 1750 1.10 15,418 13,500 11,290 8,110 5,210
A_ _ _ _-362NC---STFCJ3 2 1750 2.00 18,886 17,420 15,840 14,150 12,070 9,210 6,520
A_ _ _ _-362NB---STFCK3 3 1750 2.80 21,922 20,680 19,270 17,830 16,600 15,000 13,100 10,200 5,770
A_ _ _ _-368CB---STFCK3 3 1750 3.00 15,666 15,020 14,300 13,600 12,980 12,330 11,700 11,060 10,430 9,150 7,850
A_ _ _ _-366PC---STFCK3 3 1750 3.00 18,685 18,060 17,300 16,560 15,730 14,770 13,630 12,400 11,290 9,270 6,450
A_ _ _ _-366PA---STFCL3 5 1750 5.00 24,112 23,350 22,600 21,780 20,930 20,000 18,800 17,600 16,000 13,200 11,000
A_ _ _ _-368CC---STFCL3 5 1750 4.80 18,575 18,100 17,600 17,020 16,400 15,800 15,200 14,530 14,120 13,280 12,250
A_ _ _ _-368CD---STFCM3 71⁄2 1750 7.20 22,636 22,080 21,570 21,000 20,400 19,830 19,250 18,610 18,000 16,780 15,430
A_ _ _ _-368CA---STFCN3 10 1780 9.80 27,800 27,250 26,800 26,300 25,800 25,300 24,700 24,200 23,500 22,100 20,500
A_ _ _ _-362ND---STFCD4
1
4 1140 0.29 9,952 6,600
36
A_ _ _ _-362NC---STFCF4
1
2 1140 0.54 12,212 9,900 6,380
A_ _ _ _-362NA---STFCH4 1 1160 1.10 16,178 14,450 12,600 10,240 5,670
A_ _ _ _-366PA---STFCI4 11⁄2 1160 1.50 15,902 14,720 13,360 11,730 9,730 7,640 5,770 4,580 3,720
A_ _ _ _-366PB---STFCK4 3 1160 2.40 20,003 18,850 17,970 16,500 14,970 12,340 8,400 6,660 5,400
A_ _ _ _-364-W---STFCL4 5 1160 4.20 23,851 22,850 21,870 20,880 19,820 18,540 16,800 8,180 7,470 6,030 4,900
A_ _ _ _-362NC---STFCD5
1
4 850 0.22 9,105 5,410
A_ _ _ _-362NA---STFCF5
1
2 850 0.43 11,784 9,315 4,700
A_ _ _ _-363-L---STFCH5 1 870 1.00 14,170 12,970 11,610 9,970 5,600
A_ _ _ _-364-W---STFCI5 11⁄2 870 1.60 17,889 16,660 15,210 13,480 6,300 5,040
A_ _ _ _-362NA---STFCD6
1
4 690 0.23 9,566 6,300
A_ _ _ _-363-L---STFCF6
1
2 690 0.53 11,239 9,550 7,570 3,130
A_ _ _ _-364-W---STFCG6
3
4 690 0.88 14,188 12,530 10,300 4,180 3,130
A_ _ _ _-402NC---STFCJ3 2 1750 2.10 21,648 19,650 17,930 16,030 13,800 11,000 8,000 5,370
A_ _ _ _-402NB---STFCK3 3 1750 3.00 24,600 22,820 21,200 19,370 17,200 14,450 10,600 7,200 4,550
A_ _ _ _-402ND---STFCH4 1 1160 0.94 17,457 14,880 12,000 7,000
A_ _ _ _-402NA---STFCJ4 2 1160 2.20 22,750 20,730 18,750 16,600 13,080 7,400 4,300
A_ _ _ _-406PA---STFCK4 3 1160 3.00 23,707 22,500 21,070 19,500 17,700 15,300 12,600 10,200 8,030 6,100
A_ _ _ _-406PB---STFCL4 5 1160 4.90 27,454 26,470 25,530 24,560 23,400 22,070 20,200 16,660 12,400 10,030 8,450
40
A_ _ _ _-404-W---STFCM4 71⁄2 1160 8.00 33,300 32,220 31,130 30,000 28,800 27,550 26,160 24,730
A_ _ _ _-402NA---STFCH5 1 870 0.94 17,077 14,400 11,370 4,670
A_ _ _ _-406PA---STFCI5 11⁄2 870 1.30 17,792 16,020 13,880 10,700 7,270 5,410 3,940
A_ _ _ _-403-L---STFCJ5 2 870 2.20 20,400 19,080 17,630 16,050 14,030 8,650 6,000 4,800
A_ _ _ _-404-W---STFCK5 3 870 3.50 25,200 23,800 22,420 20,780 18,800 9,270 7,990 7,050
A_ _ _ _-406PA---STFCG6
3
4 690 0.63 14,111 11,730 8,000 4,530
A_ _ _ _-403-L---STFCH6 1 690 1.00 16,250 14,400 12,400 9,300 4,350
A_ _ _ _-404-W---STFCI6 11⁄2 690 1.70 19,800 17,960 15,960 7,330 5,950
A_ _ _ _-442NC---STFCK3 3 1750 2.90 26,250 24,130 21,960 19,610 17,000 14,250 11,630 9,080 6,700
A_ _ _ _-442NE---STFCL3 5 1750 5.20 34,427 32,730 30,880 29,000 26,930 24,700 22,350 19,700 16,100 9,530
A_ _ _ _-442ND---STFCH4 1 1160 0.97 19,031 16,100 12,950 8,000
A_ _ _ _-442NB---STFCJ4 2 1160 2.20 25,400 22,800 20,100 16,970 11,400
A_ _ _ _-442NA---STFCK4 3 1160 3.50 30,103 27,550 25,300 23,000 20,540 16,600 9,200
A_ _ _ _-446PA---STFCL4 5 1160 5.50 31,323 30,200 28,800 27,630 26,170 24,700 23,050 21,000 17,000 13,300 10,800
44
A_ _ _ _-442NB---STFCH5 1 870 0.98 19,400 17,060 11,600 4,900
A_ _ _ _-442NA---STFCI5 11⁄2 870 1.50 22,733 19,500 16,550 11,600 5,700
A_ _ _ _-446-P---STFCJ5 2 870 2.30 23,223 21,570 19,770 17,700 14,150 11,080 8,950 7,210 5,500
A_ _ _ _-443-L---STFCK5 3 870 3.40 26,600 24,950 23,450 21,820 19,970 17,620 14,070 9,200 9,350
A_ _ _ _-444-W---STFCL5 5 870 5.50 33,230 31,700 30,150 28,400 26,400 24,270 12,400 11,170 10,050 7,450
A_ _ _ _-446-P---STFCH6 1 690 1.20 18,632 16,510 14,000 9,550 6,960
A_ _ _ _-443-L---STFCI6 11⁄2 690 1.60 20,570 18,730 16,670 14,060 7,730
A_ _ _ _-444-W---STFCK6 3 690 2.70 26,356 24,450 22,300 19,620 9,250 8,000 6,400
Rating Table – Series 01S, 01R, 02S, 02R
Performance certified is for installation Type B: Free Inlet, Ducted Outlet. Speed (RPM) shown is nominal. Performance is based on actual speed of test. Performance ratings do not include the effects of appurtenances (accessories).
"G" (General Industrial) Duty construction available for models with shaded performance. "H" (Heavy Industrial) Duty construction available for all models.
*48" AA prop data AMCA Certified for the Series 02S and 02R fans only.
9
Bulletin A-1
09-AJ
www.hartzellfan.com
1 (800) 336-3267
®
Peak CFM @ STATIC PRESSURE
Size Model Code
Blade
Motor
Fan
Angle
HP RPM BHP 0"
1
/8"
1
/4"3/8"
1
/2"
5
/8"
3
/4"
7
/8"1"11/4"11/2"
A_ _ _ _-482NC---STFCJ4 --- 2 1160 2.20 27,871 24,930 22,200 19,050 15,270 9,970
A_ _ _ _-482NB---STFCK4 --- 3 1160 3.10 31,426 28,900 26,200 23,200 19,530 13,500 8,430
A_ _ _ _-482NA---STFCL4 --- 5 1160 5.40 35,612 34,550 33,130 30,660 28,000 24,650 19,470 12,500 9,520
A_ _ _ _-486-C---STFCM4 --- 71⁄2 1160 7.40 37,700 36,500 35,170 33,680 32,050 30,330 28,530 26,580 24,350 18,050 13,300
A_ _ _ _-484AA170STFCM4 17° 71⁄2 1160 8.04 39,093 37,670 36,195 34,510 32,550 30,510 28,487 26,295 18,343 15,199 8,820
A_ _ _ _-482NC---STFCH5 --- 1 870 1.00 20,779 17,060 12,800 6,100
48*
A_ _ _ _-482NA---STFCJ5 --- 2 870 2.20 26,709 24,930 21,600 16,950 8,870
A_ _ _ _-486-C---STFCK5 --- 3 870 3.30 28,600 27,130 25,150 22,800 20,200 17,200 13,200 9,970 7,700
A_ _ _ _-486AA142STFCK5 14.2° 3 870 3.12 27,642 26,114 24,430 22,640 20,700 18,750 16,115 12,800 10,140 6,950
A_ _ _ _-483-L---STFCL5 --- 5 870 5.00 32,700 31,530 29,730 27,800 25,800 23,230 14,830 12,170 10,500 6,800
A_ _ _ _-482NA---STFCH6 --- 1 690 1.10 21,183 18,470 12,900
A_ _ _ _-484AA160STFCI6 16° 11⁄2 690 1.58 22,320 19,744 16,427 12,406 6,750 ,691
A_ _ _ _-484AA200STFCJ6 20° 2 690 2.01 25,518 22,999 19,646 15,932 10,602 1,490
A_ _ _ _-486AA230STFCK6 23° 3 690 3.19 30,013 27,314 24,860 22,542 19,806 15,791 9,864 2,099
A_ _ _ _-542NB---STFCK4 --- 3 1160 2.90 34,300 31,060 27,450 22,850 16,200 11,600 7,200
A_ _ _ _-542NA---STFCL4 --- 5 1160 5.10 43,200 40,750 37,500 34,300 30,800 26,950 19,500 13,500 9,500
A_ _ _ _-542NC---STFCM4 --- 71⁄2 1160 7.10 48,500 46,050 43,200 40,250 37,000 33,350 28,750 18,400 13,000
A_ _ _ _-544BA090STFCN4 10 1160 11.30 47,950 45,600 43,350 41,000 34,300 28,400 25,700 20,100
A_ _ _ _-542NA---STFCJ5 --- 2 870 2.10 32,700 28,800 24,330 18,550 10,000
A_ _ _ _-542NC---STFCK5 --- 3 870 3.20 36,500 32,950 28,900 24,000 13,200
54
A_ _ _ _-544BA110STFCL5 11° 5 870 5.50 38,800 35,850 32,650 24,500 18,000 12,050
A_ _ _ _-544BA165STFCM5 16.5° 71⁄2 870 8.20 46,930 44,200 41,470 38,530 28,600 19,000 14,150
A_ _ _ _-543-L---STFCM5 --- 71⁄2 870 8.40 48,785 47,000 45,000 43,000 40,900 38,750 36,000 32,150 20,450
A_ _ _ _-546BA175STFCN5 17.5° 10 870 11.00 51,770 49,550 47,250 44,550 40,570 28,480 21,950 17,900 16,200
A_ _ _ _-542NA---STFCH6 --- 1 690 1.00 25,700 20,500 12,500
A_ _ _ _-544BA080STFCJ6 2 690 2.20 27,500 22,970 14,800
A_ _ _ _-544BA140STFCK6 14° 3 690 3.30 34,150 30,600 25,800 13,700
A_ _ _ _-544BA175STFCL6 17.5° 5 690 5.50 41,070 38,300 34,830 24,650 16,130
A_ _ _ _-602NB---STFCL4 --- 5 1160 5.20 46,750 44,050 41,100 36,200 31,450 26,100 20,500 14,700
A_ _ _ _-602NC---STFCM4 --- 71⁄2 1160 7.20 54,200 51,370 48,200 44,300 40,350 34,600 27,400 21,100 14,000
A_ _ _ _-602NA---STFCN4 --- 10 1160 9.80 61,820 58,600 55,300 52,300 49,100 45,400 40,900 34,300 24,700 15,900
A_ _ _ _-608-C---STFCP4 --- 20 1160 17.60 54,590 53,050 51,550 50,000 48,500 47,000 45,450 44,000 42,650 40,000 37,500
A_ _ _ _-602NB---STFCJ5 --- 2 870 2.20 35,100 31,370 25,350 17,970 10,600
A_ _ _ _-602NC---STFCK5 --- 3 870 3.00 40,520 36,850 31,270 24,150 14,850
A_ _ _ _-602BA150STFCL5 15° 5 870 5.60 49,900 45,630 41,430 36,600 30,650 14,850
60
A_ _ _ _-604BA130STFCM5 13° 7
1
2 870 8.40 53,880 51,000 48,500 45,700 42,480 38,050 29,780 23,750
A_ _ _ _-608-C---STFCM5 --- 71⁄2 870 8.10 40,950 39,050 37,050 34,850 32,700 30,750 29,100 27,700 26,300 21,250 16,050
A_ _ _ _-604BA165STFCN5 16.5° 10 870 10.90 61,370 58,300 55,530 52,950 50,050 47,000 42,900 32,150 22,750
A_ _ _ _-603-L---STFCO5 --- 15 870 15.00 66,850 65,000 62,950 60,600 58,200 55,750 53,700 50,500 43,750 25,700 21,000
A_ _ _ _-606BA175STFCO5 17.5° 15 870 16.30 66,670 65,200 63,600 61,950 60,000 57,720 55,000 51,900 47,780 28,600
A_ _ _ _-604BA100STFCK6 10° 3 690 3.30 37,970 34,250 29,950 23,620 16,100
A_ _ _ _-604BA165STFCL6 16.5° 5 690 5.50 48,600 44,900 41,400 37,900 31,670 18,500 11,900
A_ _ _ _-603-L---STFCM6 --- 71⁄2 690 7.60 53,000 50,500 47,730 44,950 41,500 37,500 28,400 18,000 15,800
A_ _ _ _-606BA175STFCM6 17.5° 71⁄2 690 8.10 52,800 50,950 48,780 46,200 42,750 37,850 25,200
A_ _ _ _-724AA140STFCN5 14° 10 870 10.90 80,863 75,750 70,000 63,650 55,750 47,150 40,000 34,100 27,300
A_ _ _ _-724AA190STFCO5 19° 15 870 16.80 96,768 92,700 88,250 83,300 77,150 67,650 55,700 48,000 40,500 20,600
A_ _ _ _-724AA230STFCP5 23° 20 870 23.20
108,156 104,350 100,000
95,000 89,850 84,000 72,000 54,250 48,850 32,600
72
A_ _ _ _-724AA140STFCL6 14° 5 690 5.40 64,129 58,150 49,300 39,150 29,650 22,650
A_ _ _ _-724AA190STFCM6 19° 71⁄2 690 8.40 76,706 71,600 64,500 56,100 42,000 33,000 20,300
A_ _ _ _-724AA230STFCN6 23° 10 690 11.20 85,775 80,850 74,600 67,100 48,500 38,550 29,400
A_ _ _ _-724AA145STFCK7 14.5° 3 575 3.30 54,107 46,200 34,100 23,650 12,000
A_ _ _ _-724AA205STFCL7 20.5° 5 575 5.50 66,797 60,400 51,350 34,000. 22,350
The Hartzell Lo-Noise (slow tip speed) Fan is the result of years of experimentation and research in the Hartzell laboratories. Each unit is designed for quiet operation, low cost per foot of air moved and extra long, trouble-free life.
Series 08S – Standard Flow and 08R – Reverse Flow belted Lo-Noise Ring Fans.
Air seal fan orifice.
Sizes 24" to 72".
Long life V belts, pillow block ball bearings, ground and polished shaft.
Series 08 (ring)
Lo-Noise Ring Fan (Belted)
Hartzell Fan, Inc. certifies that the 08S-Belted Ring Fan, Standard Flow and 08R-Belted Ring Fan, Reverse Flow, shown hereon is licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures per­formed in accordance with AMCA Standard 211 and comply with the requirements of the Certified Ratings Program.
STANDARD AIR FLOW – SERIES 08S
REVERSE AIR FLOW – SERIES 08R
CONFIGURATION 1 - RF
FAN ONLY
CONFIGURATION 1 - SF
FAN ONLY
24 24 27
1
/2 2611/16 295/8 26 20 31/4 35/8 113/167/16 145T 41 29
28 28 31
1
/2 3011/16 335/8 30 21 31/4 35/8 113/167/16 145T 46 32
32 32 35
1
/2 3411/16 375/8 34 25 31/4 35/8 113/167/16 184T 54 39
36 36 41 39
7
/16 433/4 38 26 45/8 33/8 111/169/16 184T 81 56
40 40 45 43
7
/16 473/4 42 26 45/8 33/8 111/169/16 184T 123 83
44 44 49 47
7
/16 513/4 46 32 45/8 33/8 111/169/16 215T 143 92
48 48 54 52
7
/16 58 50 32 515/16 429/16 215T 183 126
54 54 60 58
7
/16 64 56 34 515/16 429/16 256T 233 153
60 60 66 64
7
/16 70 62 381/4 515/16 429/16 256T 299 219
72 72 78 76
1
/2 82 74 381/4 515/16 429/16 256T 319 227
WT. # LESS
MTR. & OPTIONS
MAXIMUM WEIGHT #
STL. FAN
B C
C
1
D FMAX G K L M
FAN SIZE
A
MAX. MOTOR FRAME
MAXIMUM WEIGHT #
ALUM. FAN
Principal Dimensions – Series 08
NOTE: Dimensions and specifications are subject to change. Certified prints are available.
10
Bulletin A-1
09-AJ
www.hartzellfan.com
1 (800) 336-3267
®
MOTOR MAX MAX WT.
FAN
ABCD
FF
1
G
L
MNPRSTU
FRAME
MOTOR STEEL (LESS
SIZE
(MAX) (MAX)
STEEL
MIN. MAX.
HP
MOTOR WT.)
24 243⁄16 28 31⁄2 2181⁄2 163⁄4 51⁄2 14 GA. 21⁄2 2 11.50 237⁄16 x 3⁄4 3 1 48 56
3
4 74
28 283⁄16 33 31⁄2 21⁄2 191⁄2 18 6 14 GA. 21⁄2 2 14.00 287⁄16 x 3⁄4 311⁄4 48 56
3
4 93
32 323⁄16 36 31⁄2 23⁄4 201⁄2 181⁄2 61⁄4 14 GA. 21⁄2 2 15.50 317⁄16 x 3⁄4 313⁄8 48 145T 2 111
36 363⁄16 42 4 23⁄4 213⁄4 183⁄4 63⁄4 14 GA. 21⁄2 3 12.33 377⁄16 x 3⁄4 413⁄8 48 145T 2 149
40 403⁄16 46 43⁄8 23⁄4 23 193⁄4 71⁄8 14 GA. 21⁄2 3 13.66 417⁄16 x 3⁄4 413⁄8 48 182T 3 164
44 443⁄16 50 43⁄4 23⁄4 23 203⁄4 71⁄2 14 GA. 21⁄2 3 15.00 457⁄16 x 3⁄4 413⁄8 48 184T 5 180
48 483⁄16 54 43⁄4 23⁄4 23 203⁄4 71⁄2 14 GA. 21⁄2 3 16.33 497⁄16 x 3⁄4 413⁄8 48 184T 5 201
54 543⁄16 60 5 23⁄4 34 34 73⁄4 14 GA. 21⁄2 3 18.33 557⁄16 x 3⁄4 413⁄8 56 256T 71⁄2 215
60 60
3
16 66 51⁄2 23⁄4 381⁄4 381⁄4 81⁄4 14 GA. 21⁄2 3 20.33 617⁄16 x 3⁄4 413⁄8 56 256T 15 334
Series 09 (panel)
“G” Duty Shown
Series 09 (panel)
“H” Duty Shown
Lo-Noise Panel Fan (Belted)
CONFIGURATION 1-SF
FAN ONLY
CONFIGURATION 1-RF
FAN ONLY
The Hartzell Series 09S – Standard Flow and Series 09R – Reverse Flow are Panel Fan versions of the Hartzell Lo-Noise, belted fan.The heavy duty, solid steel panel and frame are designed to be easily mounted, directly into roughed in wall opening or used with a wide variety of Hartzell mounting accessories.
Series 09S – Standard Flow and 09R – Reverse Flow.
“G” (General Industrial) Duty and “H” (Heavy Industrial) Duty construction are available.
See page 3 and performance rating table.
Steel spun orifice panel.
Sizes 24" to 60".
Long life V belts, pillow block ball bearings, ground and polished shaft.
STANDARD AIR FLOW – SERIES 09S
REVERSE AIR FLOW – SERIES 09R
Hartzell Fan, Inc. certifies that the 09S-Belted Panel Fan, Standard Flow and 09R-Belted Panel Fan, Reverse Flow, shown hereon is licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures per­formed in accordance with AMCA Standard 211 and comply with the requirements of the Certified Ratings Program.
Drawing for “G” (General Industrial) Duty construction shown, overall envelope dimensions of the “H” (Heavy Industrial) Duty construction will remain the same, except Fmax/F1max dimension, which is significantly larger for “H” Duty Construction.
Principal Dimensions
NOTE: Dimensions and specifications are subject to change. Certified prints are available. Dimensions for fan sizes 54" and 60" are "H" Duty construction.
11
Bulletin A-1
09-AJ
www.hartzellfan.com
1 (800) 336-3267
®
AIRFLOW
SQUARE OUTSIDE
I.D.
-SPACE S
=
@
-SLOT
-REQ'D PER SIDE
MAX.
AIRFLOW
-SLOT
-REQ'D PER SIDE
I.D.
SQUARE OUTSIDE
-SPACE S
=
@
MAX.
1
Ring Fan (Series 08S and 08R) Panel Fan (Series 09S and 09R)
Power rating (BHP) includes transmission losses. Performance certified is for Installation type B: Free Inlet, Ducted Outlet. Performance ratings do not include the effects of appurtenances (accessories).
"G" (General Industrial) Duty construction available for models with shaded performance. "H" (Heavy Industrial) Duty construction available for all models.
Rating Table (Lo-Noise Fan)
12
Bulletin A-1
09-AJ
www.hartzellfan.com
1 (800) 336-3267
®
Peak
Cubic Feet Per Minute vs. Static Pressure
Size Model Code
Blade
Motor
Fan
Fan
Angle
HP RPM BHP
RPM
0"1/8"1/4"3/8"1/2"5/8"3/4"7/8"1"11/8"11/4"13/8"11/2"
A_ _ _ _-243-L---STFCD3 ---1⁄4 1750 0.19 862 4,217 3,321 1,213
24
A_ _ _ _-243-L---STFCD3 ---1⁄4 1750 0.25 960 4,696 3,917 2,077
A_ _ _ _-243-L---STFCE3 ---1⁄3 1750 0.36 1071 5,239 4,558 3,706 1,568
A_ _ _ _-243-L---STFCF3 ---1⁄2 1750 0.53 1220 5,968 5,383 4,702 3,501 1,719
A_ _ _ _-283-L---STFCD3 ---1⁄4 1750 0.27 765 5,774 4,551 1,458
28
A_ _ _ _-283-L---STFCE3 ---1⁄3 1750 0.36 820 6,189 5,083 1,951 ,702
A_ _ _ _-283-L---STFCF3 ---1⁄2 1750 0.55 938 7,079 6,163 4,674 1,797 ,745
A_ _ _ _-283-L---STFCG3 ---3⁄4 1750 0.82 1082 8,166 7,401 6,437 3,121 2,063 1,085
A_ _ _ _-323-L---STFCF3 ---1⁄2 1750 0.55 825 9,146 7,919 6,420 2,642
A_ _ _ _-323-L---STFCG3 ---3⁄4 1750 0.84 945 10,477 9,435 8,227 5,189 2,963
32 A_ _ _ _-323-L---STFCH3 --- 1 1750 1.14 1045 11,585 10,660 9,600 8,456 4,862 3,186
A_ _ _ _-323-L---STFCI3 --- 11⁄2 1750 1.64 1190 13,193 12,395 11,498 10,529 9,497 5,972 4,061
A_ _ _ _-323-L---STFCJ3 --- 2 1750 2.23 1305 14,468 13,746 12,952 12,095 11,201 10,165 6,577 4,699 3,845
A_ _ _ _-363-L---STFCE3 ---1⁄3 1750 0.36 575 9,196 7,211 2,568
A_ _ _ _-363-L---STFCF3 ---1⁄2 1750 0.58 666 10,651 9,056 5,585 2,616
36
A_ _ _ _-363-L---STFCG3 ---3⁄4 1750 0.88 764 12,218 10,869 9,098 4,125 2,941
A_ _ _ _-363-L---STFCH3 --- 1 1750 1.07 837 13,386 12,160 10,703 8,099 3,947
A_ _ _ _-363-L---STFCI3 --- 11⁄2 1750 1.79 980 15,673 14,624 13,532 12,144 9,970 5,189 4,235
A_ _ _ _-363-L---STFCJ3 --- 2 1750 2.21 1050 16,792 15,813 14,824 13,627 12,137 8,633 5,237 4,459
A_ _ _ _-403-L---STFCH3 --- 1 1750 1.12 690 15,996 14,213 12,231 5,288
40 A_ _ _ _-403-L---STFCI3 --- 11⁄2 1750 1.64 780 18,083 16,534 14,851 12,705 5,701
A_ _ _ _-403-L---STFCK3 --- 3 1750 3.20 980 22,719 21,513 20,210 18,869 17,429 15,213 7,587
A_ _ _ _-443-L---STFCF3 ---1⁄2 1750 0.52 474 14,142 11,376 4,728
A_ _ _ _-443-L---STFCH3 --- 1 1750 1.07 580 17,304 15,302 12,282 5,768 3,572
44
A_ _ _ _-443-L---STFCI3 --- 11⁄2 1750 1.67 680 20,287 18,545 16,491 13,618 7,138 4,863
A_ _ _ _-443-L---STFCJ3 --- 2 1750 2.16 738 22,018 20,386 18,757 16,234 11,632 6,980 5,118
A_ _ _ _-443-L---STFCK3 --- 3 1750 3.33 853 25,449 24,004 22,718 21,016 18,781 15,885 9,801 7,453 5,935
A_ _ _ _-443-L---STFCL3 --- 5 1750 5.26 1010 30,133 28,895 27,764 26,683 25,250 23,325 21,510 18,852 12,974 10,235 8,540
A_ _ _ _-483-L---STFCH3 --- 1 1750 1.15 525 19,633 16,862 11,982 5,622
48
A_ _ _ _-483-L---STFCJ3 --- 2 1750 2.31 660 24,682 22,556 20,156 16,681 8,674 6,590
A_ _ _ _-483-L---STFCK3 --- 3 1750 3.33 740 27,674 25,801 23,739 21,379 16,421 9,790 7,859 6,009
A_ _ _ _-483-L---STFCL3 --- 5 1750 5.85 895 33,470 31,945 30,318 28,580 26,699 24,278 17,194 12,455 10,650 9,201 7,729
Rating Table (Lo-Noise Fan)
13
Bulletin A-1
09-AJ
www.hartzellfan.com
1 (800) 336-3267
®
Peak
CFM @ STATIC PRESSURE
Size Model Code
Blade
Motor
Fan
Fan
Angle
HP RPM BHP
RPM
0"1/8"1/4"3/8"1/2"5/8"3/4"7/8"1"11/8"11/4"13/8"11/2"
A_ _ _ _-543-L---STFCJ3 --- 2 1750 2.01 497 27,349 24,292 19,105 8,728
54
A_ _ _ _-543-L---STFCK3 --- 3 1750 3.09 573 31,531 28,944 25,820 14,739 10,029
A_ _ _ _-543-L---STFCL3 --- 5 1750 5.10 671 36,924 34,753 32,344 29,402 18,527 13,078 10,595
A_ _ _ _-543-L---STFCM3 --- 71⁄2 1750 8.13 786 43,252 41,423 39,464 37,310 34,772 30,235 18,198 14,952 12,850
A_ _ _ _-603-L---STFCJ3 --- 2 1750 2.11 437 32,457 28,400 22,816 10,199
A_ _ _ _-603-L---STFCK3 --- 3 1750 3.12 496 36,839 33,260 29,252 16,224 11,147
60
A_ _ _ _-603-L---STFCL3 --- 5 1750 5.46 595 44,191 41,171 38,212 34,586 28,502 15,625 12,798
A_ _ _ _-603-L---STFCM3 --- 71⁄2 1750 7.96 672 49,910 47,224 44,635 41,832 38,394 33,502 19,032 15,916 13,804
A_ _ _ _-603-L---STFCN3 --- 10 1750 10.97 747 55,481 53,058 50,711 48,356 45,675 42,473 38,242 23,106 19,288 16,936 15,153
A_ _ _ _-603-L---STFCO3 --- 15 1750 16.18 858 63,725 61,611 59,529 57,518 55,453 53,146 50,558 47,458 43,550 27,908 23,597 21,159 19,228
A_ _ _ _-724AA250STFCK3 25° 3 1750 3.27 432 55,031 45,611 23,310
A_ _ _ _-724AA250STFCL3 22° 5 1750 5.60 538 65,004 58,168 49,022 28,322
72 A_ _ _ _-724AA250STFCM3 25° 71⁄2 1750 8.31 588 74,903 68,592 60,894 37,542 29,090 19,087
A_ _ _ _-724AA250STFCN3 25° 10 1750 11.02 646 82,292 76,820 69,876 60,247 38,434 30,273 21,239
A_ _ _ _-724AA250STFCO3 25° 15 1750 16.54 740 94,266 89,771 83,752 77,715 67,122 45,631 39,025 30,761 23,481
Series 72" not available in Series 09S and 09R. Power rating (BHP) includes transmission losses. Performance certified is for Installation type B: Free Inlet, Ducted Outlet. Performance ratings do not include the effects of appurtenances (accessories).
"G" (General Industrial) Duty construction available for models with shaded performance. "H" (Heavy Industrial) Duty construction available for all models.
Motor Peak CFM CFM vs. S.P. (Wall Inst.)
Size Model Code Fan @
HP RPM BHP Free Air .10 .20 .30 .40 .50 .75 1.00
18 A14_--186RA---STFCD31⁄4 1725 0.263 3,350 3,140 2,910 2,620 2,190 1,780
24
A14_--246RB---STFCH3 1 1750 1.100 7,850 7,500 7,150 6,850 6,550 6,250 A14_--246RA---STFCI3 11⁄2 1750 1.550 8,850 8,550 8,300 8,000 7,650 7,300 A14_--284-R---STFCE4
1
3 1140 0.350 6,650 5,510 4,440 2,075
28 A14_--282-R---STFCF3
1
2 1725 0.650 8,500 7,300 6,050 4,810 2,640 A14_--284-R---STFCH3 1 1725 1.300 10,080 9,310 8,560 7,840 7,140 6,400 2,630 A14_--362-R---STFCF4
1
2 1140 0.680 11,890 9,600 7,210 3,250 A14_--364-R---STFCH4 1 1140 1.400 14,130 12,620 11,200 9,820 8,130 4,320
36 A14_--366RA---STFCJ4 2 1160 2.850 15,250 14,680 14,050 13,250 12,550 12,030 10,150 6,750
A14_--366RB---STFCK4 3 1160 3.200 16,050 15,800 15,020 14,400 13,800 13,200 11,200 6,800 A14_--362-R---STFCJ3 2 1725 2.530 18,000 16,480 14,900 13,250 11,780 10,240 3,550
42 A14_--426-R---STFCK5 3 870 3.400 23,300 22,300 21,300 20,300 19,350 18,450
A14_--446-R---STFCH6 1 675 1.320 17,000 15,140 13,160 10,770 6,350 3,630
44 A14_--446-R---STFCJ5 2 860 2.580 21,700 21,350 18,800 17,200 15,600 13,900 6,000
A14_--446-R---STFCL4 5 1150 6.000 28,900 28,000 26,950 25,850 24,700 23,550 20,600 13,700
48
A14_--482-R---STFCI5 11⁄2 860 1.500 21,800 18,640 15,190 6,920 A14_--482-R---STFCK4 3 1160 3.500 29,650 27,300 24,800 22,250 19,500 11,600
54 A14_--542-R---STFCK4 3 1160 3.400 32,150 30,000 27,600 25,120 22,300 18,800 6,900
A14_--602RB---STFCK5 3 860 2.800 30,400 27,000 23,300 19,200 13,850 7,500
60
A14_--602RA---STFCL5 5 860 4.400 33,800 32,400 30,700 26,850 21,100 13,700 A14_--602RB---STFCM4 71⁄2 1160 7.100 40,600 38,100 35,500 32,750 30,000 27,000 16,750 5,700 A14_--602RA---STFCN4 10 1160 10.700 45,580 44,700 43,600 42,250 39,700 37,100 30,000 14,600
Rating Table (Reversible Fan)
Reversible Ring Fan (Double Ring)
The Series 14, Direct Drive and 14B, Belt Drive Reversible Ring Fans are ideal for ventilating applications where varying conditions may call for intake during some periods and exhaust during others, or periodic reversal of airflow for drying purposes.
Fully reversible welded construction – This design utilizes two curved orifices welded face-to-face to
provide efficient airflow in both directions. The streamlined arc-welded motor mount combines minimum resistance to airflow with exceptional strength and ability to withstand vibration.
Reversible airfoil propellers – Cast aluminum reversible airfoil blades. The leading edges and trailing
edges of the blades are identical in either direction of rotation ... 100% airflow in either direction.
Motors – Totally enclosed motors conservatively rated for continuous duty.
Direct Drive Model shown – Also available in belt drive, lo-noise type belted or extension shaft construction.
Manual or Automatic Reversal – The unit can be furnished with or without customer specified controls.
Series 14
(Direct Drive)
Direct Drive – Series 14
Belt Drive – Series 14B
Performance certified is for Installation Type B: Free Inlet, Ducted Outlet. Speed (RPM) shown is nominal. Performance is based on actual speed of test.
MAX. MOTOR FRAME
FAN
MAX. MAX.
DIRECT BELT
SIZE
ABC D E F F1JKL
DRIVE DRIVE
18 18 203⁄4 223⁄8 191⁄2 43⁄8 185⁄16 2615⁄16
5
16 15⁄8
13
16 145T 145T
24 24 271⁄2 295⁄8 26 61⁄2 213⁄8 24
7
16 35⁄8 113⁄16 184T 145T
28 28 311⁄2 335⁄8 30 61⁄2 213⁄8 24
7
16 35⁄8 113⁄16 184T 145T
36 36 41 433⁄4 38 91⁄4 29 261⁄8
9
16 33⁄8 111⁄16 256T 184T
42 42 47 493⁄4 44 91⁄4 301⁄4 273⁄8
9
16 33⁄8 111⁄16 256T 215T
44 44 49 513⁄4 46 91⁄4 301⁄4 273⁄8
9
16 33⁄8 111⁄16 256T 215T
48 48 54 58 50 117⁄8 3715⁄16 2711⁄16
9
16 4 2 365T 215T
54 54 60 64 56 117⁄8 3915⁄16 2911⁄16
9
16 4 2 365T 256T
60 60 66 70 62 117⁄8 417⁄16 3511⁄16
9
16 4 2 365T 256T
NOTE: Dimensions and specifications are subject to change. Certified prints are available.
14
Bulletin A-1
09-AJ
www.hartzellfan.com
1 (800) 336-3267
®
ABS Certificate
of Design Assessment
Received
Principal Dimensions
CFM at Various Static Pressures (Duct Installation)
Motor
Peak CFM
Size Model Code
Blade
Fan
Fan Free
Angle
HP RPM
BHP
RPM Delivery
1
/8"
1
/4"
3
/8"
1
/2"
5
/8"
A_ _ _ _-724-A172STFCL3 17.2° 5 1750 5.5 584 63,000 57,500 51,000 43,500 33,200
72 A_ _ _ _-724-A232STFCM3 23.2° 71⁄2 1750 8.1 584 74,000 69,400 63,600 56,500 45,000
A_ _ _ _-724-A284STFCN3 28.4° 10 1750 10.9 584 82,300 77,600 72,000 64,500 52,000 A_ _ _ _-854-A130STFCL3 13.0° 5 1750 5.5 495 74,800 66,000 56,500 45,200 28,000
85
A_ _ _ _-854-A180STFCM3 18.0° 71⁄2 1750 8.0 495 89,800 82,600 74,400 64,300 48,000 A_ _ _ _-854-A227STFCN3 22.7° 10 1750 11.0 495 102,000 95,200 87,200 77,500 61,500 A_ _ _ _-854-A234STFCO3 23.4° 15 1750 16.5 495 113,000 107,500 101,500 95,000 87,000 75,500 A_ _ _ _-964-A150STFCM3 15.0° 71⁄2 1750 8.2 438 103,000 93,000 82,000 68,000 48,000
96
A_ _ _ _-964-A189STFCN3 18.9° 10 1750 11.0 438 117,000 108,000 97,500 85,000 65,000 A_ _ _ _-964-A250STFCO3 25.0° 15 1750 16.5 438 137,500 129,000 119,000 106,000 87,000 A_ _ _ _-966-A241STFCP3 24.1° 20 1750 22.0 438 147,000 139,000 131,500 123,000 113,000 99,000 A_ _ _ _1034-A171STFCN3 17.1° 10 1750 11.0 408 128,000 116,000 104,000 88,500 66,000
103
A_ _ _ _1034-A230STFCO3 23.0° 15 1750 16.5 408 151,500 141,500 130,000 115,000 93,000 A_ _ _ _1034-A280STFCP3 28.0° 20 1750 22.0 408 168,000 158,000 146,000 131,000 106,000 A_ _ _ _1036-A220STFCQ3 22.0° 25 1750 26.6 445 174,000 167,000 159,000 151,000 140,000 128,000 A_ _ _ _1084-A227STFCO3 22.7° 15 1750 16.5 390 164,000 152,000 139,500 124,500 100,000
108
A_ _ _ _1084-A274STFCP3 27.4° 20 1750 22.0 390 183,000 172,000 159,000 144,000 118,000 A_ _ _ _1086-A247STFCQ3 24.7° 25 1750 27.5 390 187,000 178,000 169,000 160,000 148,000 128,000 A_ _ _ _1086-A278STFCR3 27.8° 30 1750 33.0 390 198,000 194,000 185,000 175,000 162,500 145,000 A_ _ _ _1204-A197STFCO3 19.7° 15 1750 16.5 350 186,000 172,000 156,000 138,000 106,000
120
A_ _ _ _1204-A242STFCP3 24.2° 20 1750 22.0 350 222,000 197,500 181,000 163,000 132,500 A_ _ _ _1204-A279STFCQ3 27.9° 25 1750 27.5 350 230,000 216,000 198,000 179,000 144,000
A_ _ _ _1206-A245STFCR3 24.5° 30 1750 33.0 350 229,000 218,000 206,000 194,000 180,000 158,000
A_ _ _ _1444-A171STFCP3 17.1° 20 1750 22.0 292 247,500 227,000 202,000 172,000 127,500
144
A_ _ _ _1444-A202STFCQ3 20.2° 25 1750 27.5 292 270,000 252,000 230,000 203,000 157,000 A_ _ _ _1444-A232STFCR3 23.2° 30 1750 33.0 292 294,000 275,000 252,000 223,000 178,000 A_ _ _ _1444-A280STFCS3 28.0° 40 1750 44.0 292 327,000 312,000 287,500 257,500 208,000
Rating Table (Belted, Lo-speed, High Volume Fans)
Lo-Speed, High Volume Fans (Belted)
Where you have a really big air moving job, Hartzell Lo-Speed, High Volume Fans can handle it with amazing economy. Often one of these big fans can be used in place of sev­eral small fans. Maintenance costs are practically zero because these heavy-duty units are designed and built specifically for long life and reliable operation in demanding industrial applications. Series 10S – Standard Flow and Series 10R – Reverse Flow.
Performance data shown is based on fan tip speed of 11,000 FPM. These fans can also be furnished to operate at tip speeds of 10,000 or 12,000 FPM.
Airfoil Blades – Aluminum alloy castings ground to a satin finish.
Hub – Cast aluminum threaded to accept the blades which are locked into position at the
desired blade angle setting by tension bolts.
Split Taper Bushing – Sizes 85" to 144", hub is furnished with split taper bushing.
Balance – Blades are statically balanced against a master blade. Hub is dynamically
balanced.
Belted Units shown – Also available in direct connected or pulley drive (less motor)
construction or in belt drive models with motor mounted completely out of the airstream.
Series 10S
Power rating (BHP) includes transmission losses. Performance certified is for Installation Type B: Free Inlet, Ducted Outlet. Speed (RPM) shown is nominal. Performance is based on actual speed of test.
Principal Dimensions
FAN
SIZE AB CD*E F*GHJ
72 73 79 77 41
1
/4 46 3 3
13
/16
85 86
1
/4 921/4 901/4 46
3
/8 51 3 3 11/16
96 97
3
/8 1033/8 1013/8 46
3
/8 51 3 3 11/16
103 104
1
/2 1101/2 1081/4 45
3
/8 51 3 3 11/16
108 110 116 114 45
3
/8 51 3 3 11/16
120 121
1
/2 1271/2 125 45
3
/8 51 3 3 11/16
144 146 154 150
1
/2 54
1
/2 60 4 4 11/16
*Maximum – varies with motor size. NOTE: Dimensions and specifications are subject to change. Certified prints are available.
15
Bulletin A-1
09-AJ
www.hartzellfan.com
1 (800) 336-3267
®
®
12 24 121/8 161/8 483/8 235/8 201/8 319/16 163/4 221/8 465/8 145T 155 70
16 24 163/16 201/8 451/4 201/4 201/8 319/16 203/4 183/4 431/8 145T 170 80
18 24 181/8 221/8 425/8 175/8 201/8 319/16 223/4 161/8 401/8 56 180 85
20 36 203/16 251/8 45 20 2815/16 447/16 253/4 181/2 421/2 143T 225 115
24 36 243/16 281/8 483/8 211/4 2815/16 447/16 283/4 193/4 447/8 145T 280 140
28 36 283/16 331/8 503/8 231/2 2815/16 447/16 333/4 22 467/8 145T 325 160
32 36 323/16 361/8 551/4 223/8 2815/16 447/16 363/4 207/8 513/4 184T 385 195
36 48 363/16 421/8 52 191/8 377/8 563/4 423/4 175/8 48 213T 385 195
40 48 403/16 461/8 511/8 18 377/8 563/4 463/4 161/2 463/4 215T 515 280
44 60 443/16 501/8 493/4 165/8 4611/16 691/8 503/4 151/8 45 254T 535 290
48 60 48
3
/16 541/8 625/8 221/4 4611/16 691/8 543/4 203/4 577/8 254T 670 380
A B C D E F G Y Z
FAN SIZE
NOMINAL
HOOD
SIZE
MAX. MOTOR FRAME
WT. # LESS
MTR. & OPTIONS
SIZE ALUM.
The Type LV (low-volume) filter box is available as an accessory with Hartzell Direct Drive Series 02S – Standard Flow panel fans. This short profile unit is available with disposable or permanent, washable type filters and is designed to maximize efficient utilization of space.
Compact unit – Draw-through design with fan frame mounted inside the filter box
efficiently utilizes available space and facilitates ease of installation. The perimeter mounting flange about the filter box is supplied as standard. Structural members to support the weight of the unit are supplied by others.
Sizes – 12" - 48".
Quick access to filters – A gasketed, hinged access door with quick release latches is
supplied to provide easy access to the filters for maintenance into the fan for inspection.
Use with other Hartzell accessories – This modular unit is designed to be completely
compatible with other Hartzell panel fan accessories such as hoods, shutters, and guards. See pages 24 -26.
Easy selection – The Hartzell Type LV filter box supplied with Hartzell Series 02S and
02R direct drive panel fan provides an economical intake filtered wall ventilator. The draw-through arrangement maximizes fan and filter efficiency. Panel fan performance including losses for filters is provided on the following page.
Principal Dimensions
Type LV Filter Box
Intake end of Series 02S Panel Fan
with Type LV filter box,
less shutter and weather hood.
16
Bulletin A-1
09-AJ
www.hartzellfan.com
1 (800) 336-3267
Air intake unit shown with flanged inlet for mounting inside building;
also available with flanged discharge for mounting outside building.
*Consult page 26 for intake hood sizing and pressure drop information.
Discharge end of Series 02S Panel
Fan with Type LV filter box.
®
®
Rating Table – Series 02S Panel Fans with Type “LV” Filter Boxes…Direct Drive
Performance certified is for installation Type B: Free Inlet, Ducted Outlet. Speed (RPM) shown is nominal. Performance is based on actual speed of test. Performance is based on clean filters.
"G" (General Industrial) Duty construction available for models with shaded performance. "H" (Heavy Industrial) Duty construction available for all models.
17
Bulletin A-1
09-AJ
www.hartzellfan.com
1 (800) 336-3267
Motor Peak CFM @ STATIC PRESSURE
Size Model Code Fan
HP RPM BHP 0"
1
/8"
1
/4"
3
/8"
1
/2"
3
/4"
12 A02S_-126-P---STFCD3
1
4 1725 0.03 ,725 ,430 ,142
16 A02S_-166-P---STFCD3
1
4 1725 0.17 1,675 1,360 1,090 ,860 ,640
18 A02S_-186-P---STFCD3
1
3 1725 0.36 2,050 1,680 1,310 1,020 ,840
A02S_-206-P---STFCD4
1
4 1140 0.15 2,420 1,580 ,920
A02S_-202NB---STFCD3
1
4 1725 0.14 2,240 1,480 ,710
20 A02S_-202NA---STFCD3
1
4 1725 0.24 2,935 2,130 1,290 ,680
A02S_-203-L---STFCF3
1
2 1725 0.55 3,820 3,500 2,840 2,075 1,375 ,875
A02S_-206-P---STFCF3
1
2 1725 0.50 3,800 3,300 2,590 2,150 1,650 1,230
A02S_-242NB---STFCD4
1
4 1140 0.25 3,655 2,225 1,280
A02S_-243-L---STFCE4
1
3 1140 0.37 4,405 3,760 2,460 1,590 1,050
24
A02S_-242NA---STFCD3
1
4 1725 0.28 3,900 3,060 1,765 ,780
A02S_-246-C---STFCE3
1
3 1725 0.44 4,400 3,930 3,480 2,985 2,470 1,320
A02S_-242NB---STFCF3
1
2 1725 0.56 5,090 4,430 3,220 2,370 1,390
A02S_-242NC---STFCG3
3
4 1725 0.80 5,790 5,150
A02S_-286PB---STFCD5
1
4 850 0.18 3,750 2,760 1,690 ,820
A02S_-286PA---STFCD5
1
4 850 0.27 4,250 3,060 2,090 1,160
A02S_-283-L---STFCE5
1
3 850 0.31 4,470 3,430 2,010 1,200
28 A02S_-282NC---STFCD4
1
4 1140 0.27 4,200 2,870 1,400
A02S_-283-L---STFCG4
3
4 1140 0.78 6,330 5,620 4,650 3,420 2,480 1,350
A02S_-282ND---STFCD3
1
4 1725 0.26 4,090 3,000 1,810
A02S_-282NA---STFCF3
1
2 1725 0.45 5,140 4,310 3,420 2,450 1,300
A02S_-322NA---STFCD5
1
4 850 0.22 4,360 2,500
A02S_-323-L---STFCF5
1
2 850 0.64 6,020 4,450 3,200 2,350
32 A02S_-326PA---STFCG5
3
4 850 0.76 7,030 5,150 4,275 3,660 2,900
A02S_-322NB---STFCD4
1
4 1140 0.25 4,600 3,050 1,350
A02S_-322NA---STFCF4
1
2 1140 0.62 6,130 4,600 3,130 1,630
A02S_-363-L---STFCF6
1
2 690 0.53 7,540 5,830 3,970 2,360
A02S_-362NA---STFCF5
1
2 850 0.42 6,800 4,870 2,900
36
A02S_-363-L---STFCH5 1 870 1.14 9,850 8,500 6,740 5,350 4,030 2,200 A02S_-362NC---STFCF4
1
2 1140 0.52 7,120 5,500 3,630 A02S_-362NA---STFCH4 1 1160 1.08 10,000 8,370 6,870 5,280 3,730 A02S_-362ND---STFCH3 1 1750 1.02 9,240 7,720 6,250 5,100 3,150 A02S_-406PA---STFCG6
3
4 690 0.64 8,350 6,730 4,850 3,700
40
A02S_-403-L---STFCH6 1 690 1.07 10,500 8,730 6,350 4,800 3,630 A02S_-402NA---STFCH5 1 870 0.88 9,320 7,150 5,150 3,100 A02S_-402ND---STFCH4 1 1160 0.87 9,850 7,940 6,100 4,170 2,000 A02S_-446-P---STFCH6 1 690 1.18 11,450 9,500 7,920 6,700 5,300
44
A02S_-442NB---STFCH5 1 870 0.93 10,050 7,850 5,600 3,500 A02S_-442NA---STFCI5 11⁄2 870 1.46 12,150 9,800 7,400 5,870 3,550 A02S_-442ND---STFCH4 1 1160 0.93 10,730 8,950 7,100 5,100 A02S_-482NA---STFCH6 1 690 1.10 12,700 9,600 6,430 3,600
48 A02S_-484AA---STFCI6 11⁄2 690 1.57 15,130 12,200 9,200 6,730
A02S_-482NC---STFCH5 1 870 1.00 12,730 10,450 7,400 4,350
®
24 36 24 331/8 641/8 261/4 2815/16 447/16 331/4 31/4 20 273/4 243/4 26 22 95/8 44 661/8 397/8 145T 28 42 28 361/8 651/8 211/2 333/8 525/8 361/4 31/4 21 313/4 20 30 23 12 44 671/8 497/8 145T
32 42 32 421/8 691/8 261/2 333/8 525/8 421/4 31/4 25 353/4 25 34 27 91/2 44 711/8 593/8 184T 36A 48 36 421/8 701/8 261/2 377/8 563/4 421/4 45/8 26 411/4 25 38 28 91/2 44 721/8 593/8 184T 36B 60 36 501/8 701/8 261/2 4611/16 691/8 501/4 45/8 26 411/4 25 38 28 91/2 44 721/8 593/8 184T
40 60 40 501/8 701/8 261/2 4611/16 691/8 501/4 45/8 26 451/4 25 42 28 91/2 44 721/8 593/8 184T
44 60 44 501/8 761/8 261/2 4611/16 691/8 501/4 45/8 32 491/4 25 46 34 91/2 44 781/8 593/8 215T
48 72 48 541/8 761/8 261/2 555/8 803/4 541/4 515/16 32 541/4 25 50 391/2 91/2 44 835/8 79 215T
54 72 54 601/8 821/8 261/2 555/8 803/4 601/4 515/16 34 601/4 25 56 4113/16 111/2 48 8915/16 79 256T
60 84 60 703/8 863/8 261/2 641/2 951/4 701/2 515/16 381/4 661/4 25 62 461/2 111/2 48 945/8 985/8 256T
72 84 72 84 98
3
/8 273/8 641/2 951/4 841/8 515/16 381/4 781/4 257/8 74 479/16 17 60 10711/16 1183/8 256T
FAN SIZE
NOMINAL
HOOD
SIZE
A B C D E F G S T U Y Z AA BB CC DD EE
MAX.
MOTOR
FRAME
WT. # LESS
MTR. & OPTIONS
STEEL ALUM.
400 185 495 225 620 280 635 300 720 325 755 350 760 350
960 450 1200 555 1570 750 2260 1035
The Type HV (high-volume) filter box is available as an accessory with Hartzell Series 01R (direct drive) and Series 08R (belted) ring fans. This accessory offers maximum utilization of available space to supply high volumes of filtered intake air to industrial applications. Hartzell high volume filter boxes are available with direct and belted fans and are mounted in a draw-through arrange­ment to provide maximum filter and fan efficiencies. This unit is available with disposable or permanent, washable type filters.
Draw-through design – standard Hartzell Series 01R or 08R ring fans are mounted externally to the high volume filter box.
This minimizes the overall length required for the filter box and accommodates easy access to the fan. The fan is bolted to a flat mounting panel. A perimeter mounting flange is supplied to the Type HV filter box as standard.
Sizes – 24" - 72".
Quick access to filters – a gasketed hinged access door is supplied with quick release latches for easy access and maintenance
to the filters for maintenance into the fan for inspection.
Use with other Hartzell accessories – the Hartzell Type HV high volume filter box is available with other Hartzell ring fan
accessories such as hoods, shutters, and guards.
Easy Selection – the Hartzell Type HV filter box provides an economical intake filtered wall ventilator. Ring fan performance
including losses for the filters is provided on the following two pages.
Principal Dimensions – Series 08R (Belted) Shown
NOTE: Dimensions and specifications are subject to change. Certified prints are available.
Type HV Filter Box
Air intake unit shown with flanged inlet for mounting inside building;
also available with flanged discharge for mounting outside building.
*Consult page 26 for intake hood sizing and pressure drop information.
18
Bulletin A-1
09-AJ
www.hartzellfan.com
1 (800) 336-3267
®
DD
C
10-GA.
HRS
.190 ALUM
S
T
14 GA. HRS. 1/8 ALUM.
MAX.
A
FAN ID
AA
O.D.
Z
(REF.)
(OPTIONAL) REAR BASKET GUARD
AIRFLOW
8 1/2
7 1/2
I.D.
(REF)
U
B
SQ.
INSIDE
E
(REF)
(OPTIONAL)
BIRDSCREEN
(REF.)
F
HOOD - (OPTIONAL) 14 GA. GALN 1/8 ALUM
SHUTTER MOTOR
(OPTIONAL)
G
SQUARE
ROUGH
OPENING
BB
SHUTTER (OPTIONAL)
CC
Y
DOOR OPENING
D
FILTER ACCESS DOOR
(ONE SIDE ONLY)
EE
MAX.
OUTSIDE
CASING
Motor Peak CFM @ STATIC PRESSURE
Size Model Code Fan
HP RPM BHP 0"
1
/8"
1
/4"
3
/8"
1
/2"
5
/8"1"
A01R_-243-L---STFCE4
1
3 1140 0.33 5,415 4,780 4,020
A01R_-246PC---STFCF4
1
2 1140 0.52 6,610 6,020 5,200
A01R_-244-W---STFCF4
1
2 1140 0.57 6,855 6,190 5,430
A01R_-242NB---STFCF3
1
2 1725 0.56 6,710 5,900 5,000 3,250
24 A01R_-242NC---STFCG3
3
4 1725 0.77 7,490 6,830 6,070 5,070 A01R_-246PA---STFCH3 1 1750 1.07 8,150 7,730 7,290 6,820 6,360 4,660 A01R_-246PB---STFCI3 11⁄2 1750 1.50 9,140 8,760 8,380 7,930 7,390 A01R_-246PC---STFCJ3 2 1750 1.86 10,130 9,780 9,370 8,960 8,470 A01R_-244-W---STFCJ3 2 1750 2.03 10,490 10,090 9,660 9,220 8,730 A01R_-283-L---STFCG4
3
4 1140 0.68 8,425 7,730 6,950 5,900 A01R_-284-W---STFCH4 1 1160 1.10 10,470 9,750 9,020 8,240
28 A01R_-286PB---STFCI3 11⁄2 1750 1.58 10,340 9,870 9,400 8,860 8,350 6,960
A01R_-286PA---STFCJ3 2 1750 2.11 12,150 11,670 11,200 10,650 10,100 8,770 6,300 A01R_-288-C---STFCK3 3 1750 2.80 13,700 13,300 12,900 12,400 11,780 10,100 7,850 A01R_-322NA---STFCF4
1
2 1140 0.55 10,140 8,550 6,500 A01R_-326PB---STFCH4 1 1160 0.91 10,490 9,480 8,300 6,630 5,350
32
A01R_-323-L---STFCI4 11⁄2 1160 1.51 12,860 11,970 11,060 10,060 8,100 A01R_-324-W---STFCJ4 2 1160 2.20 15,430 14,560 13,700 12,960 11,830 A01R_-322NA---STFCJ3 2 1750 2.01 16,060 15,020 13,930 12,750 11,450 A01R_-326PB---STFCK3 3 1750 3.00 15,710 15,130 14,370 13,600 12,770 10,800 8,400 A01R_-362NC---STFCF4
1
2 1140 0.54 11,350 9,150
36A*
A01R_-362NA---STFCH4 1 1160 1.12 15,020 13,450 11,900 9,000 A01R_-366PA---STFCI4 11⁄2 1160 1.40 15,170 14,050 12,600 11,000 8,950 A01R_-366PB---STFCJ4 2 1160 2.42 18,800 17,970 16,750 15,400 13,900 A01R_-366PB---STFCJ4 2 1160 2.42 19,400 18,430 17,360 15,970 14,530 A01R_-363-L---STFCK4 3 1160 2.40 18,370 17,470 16,500 15,520 14,420 10,500 A01R_-364-W---STFCL4 5 1160 3.86 23,070 22,150 21,200 20,200 19,200 15,800 A01R_-362NC---STFCJ3 2 1750 2.01 18,300 16,850 15,250 13,680 11,550
36B* A01R_-362NB---STFCK3 3 1750 2.82 21,200 19,930 18,600 17,270 16,070 12,570
A01R_-366PC---STFCK3 3 1750 2.97 18,400 17,750 17,000 16,400 15,380 13,300 11,100 A01R_-366PA---STFCL3 5 1750 4.83 23,500 22,730 22,000 21,200 20,400 18,220 15,500 A01R_-368CD---STFCM3 71⁄2 1750 6.25 21,930 21,400 20,870 20,350 19,800 18,700 17,600 A01R_-368CA---STFCN3 10 1750 9.00 27,530 27,000 26,550 26,100 25,700 24,800 23,800 A01R_-402NA---STFCH5 1 870 0.94 16,200 13,700 10,700 A01R_-406PA---STFCI5 11⁄2 870 1.25 17,160 15,370 13,270 10,100 A01R_-403-L---STFCJ5 2 870 1.90 19,750 18,450 17,030 15,450 13,300 A01R_-404-W---STFCK5 3 870 3.48 24,130 22,800 21,350 19,650 17,750
40 A01R_-402NA---STFCJ4 2 1160 2.25 21,550 19,700 17,900 15,800 11,800
A01R_-406PA---STFCK4 3 1160 2.88 22,830 21,580 20,200 18,650 16,900 12,150 A01R_-406PB---STFCL4 5 1160 4.87 26,550 25,600 24,700 23,800 22,500 18,650 12,000 A01R_-403-L---STFCL4 5 1160 4.50 26,350 25,300 24,300 23,200 22,100 19,600 14,800 A01R_-404-W---STFCM4 71⁄2 1160 7.95 31,900 29,850 28,750 27,600 25,000
Rating Table – Series 01R Propeller Fans with Type “HV” Filter Boxes…Direct Drive
19
Bulletin A-1
09-AJ
www.hartzellfan.com
1 (800) 336-3267
®
Performance certified is for installation Type B: Free Inlet, Ducted Outlet. Speed (RPM) shown is nominal. Performance is based on actual speed of test. Performance shown is based on permanent filters. *Within the 36" size, two different HV filter box designs are available. See Page 18. Non-shaded performance requires Type A HV filter box; shaded performance requires Type B HV filter box.
CFM @ STATIC PRESSURE
Motor
Peak
Size Model Code Fan Fan
HP RPM RPM RPM 0"
1
/8"
1
/4"
3
/8"
1
/2"
3
/4"1"
A08R_-243-L---STFCD3
1
4 1750 0.25 960 4,575 3,800
A08R_-243-L---STFCE3
1
3 1750 0.36 1071 5,110 4,430 3,400
24 A08R_-243-L---STFCF3
1
2 1750 0.54 1220 5,810 5,640 5,225 3,100
A08R_-244-W---STFCF3
1
2 1750 0.55 1091 6,565 5,900 5,020
A08R_-244-W---STFCG3
3
4 1750 0.82 1249 7,500 6,940 6,290
A08R_-283-L---STFCD3
1
4 1750 0.24 806 5,890 4,770
28
A08R_-283-L---STFCE3
1
3 1750 0.36 883 6,440 5,450 3,400
A08R_-283-L---STFCF3
1
2 1750 0.55 1035 7,560 6,730 5,770 3,100
A08R_-283-L---STFCG3
3
4 1750 0.77 1165 8,500 7,815 7,040 6,050 3,270
A08R_-323-L---STFCF3
1
2 1750 0.52 825 8,925 7,700 6,000
32
A08R_-323-L---STFCG3
3
4 1750 0.75 945 10,240 9,190 8,000 A08R_-323-L---STFCH3 1 1750 1.03 1045 11,340 10,420 9,360 8,120 A08R_-323-L---STFCI3 11⁄2 1750 1.50 1190 12,910 12,100 11,200 10,250 9,000 A08R_-363-L---STFCF3
1
2 1750 0.52 666 10,250 8,700 A08R_-363-L---STFCG3
3
4 1750 0.80 764 11,770 10,420 8,650
36A* A08R_-363-L---STFCH3 1 1750 1.07 837 12,900 11,680 10,200
A08R_-363-L---STFCI3 11⁄2 1750 1.70 980 15,100 14,100 12,950 11,500 8,700 A08R_-363-L---STFCJ3 2 1750 2.08 1050 16,200 15,250 14,180 13,000 11,370 A08R_-363-L---STFCF3
1
2 1750 0.51 666 10,500 8,900 A08R_-363-L---STFCG3
3
4 1750 0.80 764 12,080 10,700 8,900
36B* A08R_-363-L---STFCH3 1 1750 1.10 837 13,240 12,000 10,500 7,800
A08R_-363-L---STFCI3 11⁄2 1750 1.70 980 15,500 14,450 13,280 11,870 9,300 A08R_-363-L---STFCJ3 2 1750 2.08 1050 16,600 15,640 14,570 13,370 11,850 A08R_-403-L---STFCH3 1 1750 1.17 690 15,720 14,000 11,950 A08R_-403-L---STFCI3 11⁄2 1750 1.67 780 17,790 16,230 14,560 12,230
40 A08R_-403-L---STFCJ3 2 1750 2.29 870 19,800 18,450 16,940 15,300 11,800
A08R_-403-L---STFCK3 3 1750 3.30 980 22,330 21,100 19,850 18,500 16,950 A08R_-403-L---STFCL3 5 1750 4.95 1160 26,350 25,300 24,300 23,200 22,100 19,600 14,800
CFM @ STATIC PRESSURE
Motor
Peak
Size Model Code
Blade
Fan
Angle
HP RPM RPM 0"
1
/8"
1
/4"
3
/8"
1
/2"
3
/4"1"
A01R_-442NB---STFCH5 --- 1 870 0.98 18,070 16,000 10,400 A01R_-442NA---STFCI5 --- 11⁄2 870 1.51 20,830 18,200 15,500 A01R_-446-P---STFCJ5 --- 2 870 2.24 22,200 20,600 18,870 16,920 13,500 8,600 A01R_-443-L---STFCK5 --- 3 870 3.24 25,200 23,850 22,400 20,800 18,900 12,500 A01R_-444-W---STFCL5 --- 5 870 5.10 31,200 29,900 28,300 26,550 24,900
44 A01R_-442ND---STFCH4 --- 1 1160 0.97 17,730 15,150 12,000
A01R_-442NB---STFCJ4 --- 2 1160 2.17 23,460 21,200 17,650 15,400 10,600 A01R_-442NA---STFCK4 --- 3 1160 3.50 27,600 25,600 23,650 21,500 19,300 A01R_-446-P---STFCL4 --- 5 1160 5.21 30,000 29,150 28,100 27,150 26,200 23,850 21,000 A01R_-443-L---STFCM4 --- 71⁄2 1160 6.9 33,150 32,700 32,150 31,550 31,050 29,900 28,750 A01R_-442NE---STFCL3 --- 5 1750 5.17 32,100 30,500 28,800 27,000 25,100 20,900 15,000 A01R_-482NA---STFCJ5 --- 2 870 2.18 26,150 23,700 20,350 15,600 A01R_-484AA190STFCK5 19° 3 870 3.26 30,920 28,700 26,400 23,550 19,500 A01R_-484AA220STFCL5 22° 5 870 4.85 35,750 33,550 31,200 28,750 24,800 A01R_-482NB---STFCK4 --- 3 1160 3.11 29,750 27,400 24,900 22,000 18,400
48 A01R_-482NA---STFCL4 --- 5 1160 5.36 35,250 33,550 31,300 29,050 26,400 18,000
A01R_-484AA145STFCL4 14.5° 5 1160 5.45 36,200 34,250 32,350 30,500 28,600 23,000 A01R_-484AA160STFCM4 16° 71⁄2 1160 8.11 41,750 38,500 34,800 30,000 21,200 A01R_-484AA160STFCM4 16° 71⁄2 1160 8.40 40,000 38,550 37,000 35,200 33,500 29,200 22,600 A01R_-484AA200STFCN4 20° 10 1160 10.80 44,600 43,100 41,570 39,850 38,350 34,800 28,800
Rating Table – Series 08R Propeller Fans with Type “HV” Filter Boxes…Belted
Performance certified is for installation Type B: Free Inlet, Ducted Outlet. Speed (RPM) shown is nominal. Performance is based on actual speed of test. *Within the 36" size, two different HV filter box designs are available. See Page 18. Non-shaded performance requires Type A HV filter box; shaded performance requires Type B HV filter box.
Rating Table – Series 01R Propeller Fans with Type “HV” Filter Boxes…Direct Drive
20
Bulletin A-1
09-AJ
www.hartzellfan.com
1 (800) 336-3267
®
CFM @ Static Pressures
Motor
Peak
Size Model Code
Blade
Fan Fan
Angle
HP RPM RPM RPM 0"
1
/8"
1
/4"
3
/8"
1
/2"
3
/4"1"
A08R_-443-L---STFCF3 ---
1
2 1750 0.50 474 13,650 11,000
A08R_-443-L---STFCH3 --- 1 1750 0.97 580 16,600 14,700 11,550
44
A08R_-443-L---STFCI3 --- 11⁄2 1750 1.53 680 19,600 18,000 15,730 12,250 A08R_-443-L---STFCJ3 --- 2 1750 1.99 738 21,300 19,850 17,900 15,500 10,500 A08R_-443-L---STFCK3 --- 3 1750 3.02 853 24,600 23,300 21,850 20,000 17,900 A08R_-443-L---STFCL3 --- 5 1750 5.06 1010 29,100 28,000 26,900 25,600 23,900 20,400 12,200 A08R_-483-L---STFCH3 --- 1 1750 1.07 525 19,250 16,600 12,000 A08R_-483-L---STFCI3 --- 11⁄2 1750 1.50 600 21,850 19,600 16,500 A08R_-483-L---STFCJ3 --- 2 1750 2.06 660 24,000 22,000 19,600 16,100 A08R_-483-L---STFCK3 --- 3 1750 3.00 740 26,950 25,100 23,000 20,500 16,100
48 A08R_-483-L---STFCL3 --- 5 1750 5.20 895 32,620 31,100 29,430 27,600 25,900 17,300
A08R_-483-L---STFCM3 --- 71⁄2 1750 7.68 1020 36,650 35,170 33,600 32,050 30,850 27,650 18,200 A08R_-486AA220STFCM3 22° 71⁄2 1750 7.51 870 39,350 37,550 35,600 33,600 31,200 17,600 A08R_-484AA160STFCM3 16° 71⁄2 1750 7.83 1160 39,930 38,200 36,350 34,650 32,800 28,200 18,700 A08R_-484AA250STFCN3 25° 10 1750 10.90 1160 44,900 43,650 42,050 40,300 38,450 34,330 26,900 A08R_-543-L---STFCI3 --- 11⁄2 1750 1.46 456 24,230 20,800 A08R_-543-L---STFCJ3 --- 2 1750 2.01 497 26,430 23,200 15,400 A08R_-543-L---STFCK3 --- 3 1750 3.00 573 30,450 27,900 24,600 14,200
54
A08R_-543-L---STFCL3 --- 5 1750 4.86 671 35,680 33,600 31,200 28,100 17,800 A08R_-543-L---STFCM3 --- 71⁄2 1750 7.79 736 41,800 39,950 38,000 35,900 33,300 17,500 A08R_-544AW190STFCL3 19° 5 1750 5.55 690 37,900 36,000 33,800 31,200 27,100 A08R_-544AW250STFCM3 25° 71⁄2 1750 8.00 690 45,850 43,700 41,600 38,800 35,700 A08R_-544AW280STFCN3 28° 10 1750 11.30 690 53,000 50,700 48,200 45,400 41,400 A08R_-603-L---STFCJ3 --- 2 1750 2.10 437 31,500 27,500 21,200 A08R_-603-L---STFCK3 --- 3 1750 3.00 496 35,750 32,100 28,200 A08R_-603-L---STFCL3 --- 5 1750 5.15 595 42,700 39,900 37,000 33,100 27,000 A08R_-603-L---STFCM3 --- 71⁄2 1750 7.50 672 48,250 45,700 43,100 40,000 36,500
60
A08R_-603-L---STFCN3 --- 10 1750 10.20 747 53,600 51,500 49,250 46,650 43,900 36,000 A08R_-604AW190STFCM3 19° 71⁄2 1750 8.45 690 49,700 47,700 45,350 42,700 39,500 25,600 A08R_-604AW190STFCN3 19° 10 1750 11.00 690 57,900 55,600 52,800 50,200 47,300 27,000 A08R_-604BA160STFCL3 16° 5 1750 5.71 690 45,050 41,400 37,400 35,000 27,100 A08R_-604BA220STFCM3 22° 71⁄2 1750 8.66 690 53,000 49,900 47,300 48,700 39,750 A08R_-604BA160STFCN3 16° 10 1750 11.40 870 57,000 54,400 52,000 49,400 46,650 36,500 A08R_-724AA190STFCL3 19° 5 1750 5.48 513 61,500 53,300 34,000
72
A08R_-724AA220STFCM3 22° 71⁄2 1750 8.26 588 70,900 64,300 56,400 36,000 A08R_-724AA220STFCN3 22° 10 1750 11.00 646 77,700 72,800 65,500 49,000 37,400 A08R_-724AA220STFCO3 22° 15 1750 16.50 740 89,050 84,000 78,500 72,500 52,000 38,000
Performance certified is for installation Type B: Free Inlet, Ducted Outlet. Power rating (BHP) includes transmission losses. Speed (RPM) shown is nominal. Performance is based on actual speed of test. *Within the 36" size, two different HV filter box designs are available. See Page 18. Non-shaded performance requires Type A HV filter box; shaded performance requires Type B HV filter box.
Rating Table – Series 08R Propeller Fans with Type “HV” Filter Boxes…Belted
21
Bulletin A-1
09-AJ
www.hartzellfan.com
1 (800) 336-3267
®
Accessory Mounting Configurations
Ring Fans (Direct Drive or Belted)
* Refer to page 24 for rough opening dimensions
CAUTION: When the periphery of the blades of a fan is less
than
seven (7) feet above the floor or working level, the blades
must be
guarded to comply with OSHA requirements.
REVERSE FAN
WITH HOOD AND PANEL
SHUTTER
Configuration 4 - RF
STANDARD FAN
WITH HOOD AND PANEL
SHUTTER
Configuration 4 - SF
REVERSE FAN
WITH BOOT, PANEL AND HOOD
SHUTTER
Configuration 5 - RFConfiguration 5 - SF
STANDARD FAN
WITH BOOT, PANEL AND HOOD
SHUTTER
Configuration 3 - RFConfiguration 3 - SF
Configuration 2 - RFConfiguration 2 - SF
NOTE: Birdscreen may be used in lieu of shutter.
Standard Flow
Reverse Flow
FAN
MTG.
PANEL
SHUTTER
FRONT GUARD
STANDARD
RING FAN
REAR
GUARD
FAN
MTG.
PANEL
SHUTTER
FRONT
GUARD
REVERSE
FAN
REAR
GUARD
SHUTTER
MTG. BOOT
AND PANEL
SHUTTER
STANDARD
RING FAN
REAR
GUARD
SHUTTER
MTG. BOOT
AND PANEL
SHUTTER
REVERSE
FAN
REAR
GUARD
22
Bulletin A-1
09-AJ
www.hartzellfan.com
1 (800) 336-3267
®
* Refer to page 24 for rough opening dimensions
CAUTION: When the periphery of the blades of a fan is less
than
seven (7) feet above the floor or working level, the blades
must be
guarded to comply with OSHA requirements.
Panel Fans (Direct Drive or Belted)
Standard Flow
Reverse Flow
FRONT
GUARD
STANDARD
PANEL FAN
REAR
GUARD
FRONT
GUARD
REVERSE
PANEL FAN
REAR
GUARD
Configuration 2 - RFConfiguration 2 - SF
SHUTTER
STANDARD PANEL FAN WITH MOUNTING BOOT
REAR
GUARD
SHUTTER
REVERSE PANEL FAN
WITH MOUNTING BOOT
REAR
GUARD
Configuration 3 - RFConfiguration 3 - SF
FRONT
GUARD
STANDARD PANEL FAN WITH
HOOD AND MOUNTING ADAPTER
FRONT
GUARD
REVERSE PANEL FAN WITH
HOOD AND MOUNTING ADAPTER
Configuration 4 - RFConfiguration 4 - SF
SHUTTER
STANDARD PANEL FAN WITH
MOUNTING BOOT, PANEL AND HOOD
SHUTTER
REVERSE PANEL FAN WITH
MOUNTING BOOT, PANEL AND HOOD
Configuration 5 - RFConfiguration 5 - SF
23
Bulletin A-1
09-AJ
www.hartzellfan.com
1 (800) 336-3267
®
Options and Accessories
Front Guard Ring Fan Rear Guard Panel Fan Rear Guard
Ring fan mounting panels are available to facilitate the
mounting of the ring fan (Series 01R, 01S, 08R, 08S, and 14B) to the wall opening. Panel fan mounting flanges are available if a vertical flange is required to mount a panel fan (Series 02R, 02S, 09R and 09S) to the wall opening. Shutter mounting boots are available to insure proper spacing between the fan
and optional shutters. For use with ring fans (Series 01R, 01S, 08R, 08S and 14B) ring fan mounting panels are required. For use with panel fans (Series 02R, 02S, 09R and 09S) the shutter mounting boot is furnished with an integral mounting flange. Please refer to the drawings and dimensions on the bottom of this page and page 25 for additional information
Mounting Dimensions – Ring Fans
Size 12 14 16 18 20 22 24 28 32 36 40 44 48 54 60 72
RO1 12
1
/2 141/2 161/2 181/2 201/2 221/2 241/2 281/2 321/2 361/2 401/2 441/2 481/2 541/2 601/2 721/2
RO2 17 19 21 23 26 27 29 34 37 43 47 51 55 61 67 79
S 17
1
/2 191/2 211/2 231/2 27 281/4 301/4 351/4 381/4 441/4 481/4 521/4 561/4 621/4 681/4 801/4
T 37/8 37/8 37/8 37/8 43/8 45/8 45/8 47/8 5415/16 51/16 551/32 51/32 51/32 421/32
U 8 8 8 8 12 12 12 12 12 16 16 16 16 16 16 16
V 11 13 15 17 10 10
1
/2 111/2 14 151/2 123/8 135/8 15 165/16 185/16 205/16 245/16
W 18
3
/4 203/4 223/4 243/4 283/4 301/4 321/4 373/4 41 47 51 55 59 65 71 821/4
X5/85/85/85/87/8 111
1
/4 1
3
/8 13/8 13/8 13/8 13/8 13/8 13/8 1
Guards
Mounting Accessories
Mounting Panel
Mounting Dimensions – Panel Fans
SAFETY ACCESSORIES, APPLICATION AND USE WARNING
The safe application and use of equipment supplied by Hartzell Fan, Inc. is the responsibility of the installer, the user, the owner, and the employer.Since the application and use of its equipment can vary greatly, Hartzell Fan, Inc. offers various product types, optional safety accessories, and sound performance data per laboratory tests. Hartzell Fan, Inc. sells its equipment with and without safety accessories, and accordingly, it can supply such safety accessories only upon receipt of an order. The need for safety accessories will frequently depend upon the type of system, fan location and operating procedures being employed. The proper protective safety accessories to meet company standards, local codes, and the requirements of the Occupational Safety and Health Act must be determined by the user since safety requirements vary depending on the location and use of the equipment. If applicable local conditions, standards, codes or OSHA rules require the addition of the safety accessories, the user should specify and obtain the required safety accessories from Hartzell Fan, Inc. and should not allow the operation of the equipment without them.
Owners, employers, users and installers should read “RECOMMENDED SAFETY PRACTICES FOR USERS AND INSTALLERS OF INDUSTRIAL AND COMMERCIAL FANS” published by the Air Movement and Control Association International, Inc., 30 West University Drive, Arlington Heights, Illinois 60004. A copy of this publication is enclosed with each fan shipped from Hartzell Fan, Inc., and is available upon request at Hartzell’s office in Piqua, Ohio 45356.
Please contact Hartzell Fan, Inc. or your local Hartzell representative for more information on product types, safety accessories, and sound performance estimates
Remember, the selection of safety accessories and the safe application and use of equipment supplied by Hartzell Fan, Inc. is your responsibility.
CAUTION: When the periphery of the blades of a fan is less than seven (7) feet above the floor or working level, the blades must be guarded to comply with OSHA requirements.
Front and rear safety guards for Hartzell propeller and panel fans are available as shown.
Size 12 14 16 18 20 22 24 28 32 36 40 44 48 54 60
PO1
161/4
181/4
201/4
221/4
251/4
261/4
281/4
331/4
361/4
421/4
461/4
501/4
541/4
601/4
661/4
PO2
163/4
183/4
203/4
223/4
253/4
263/4
283/4
333/4
363/4
423/4
463/4
503/4
543/4
603/4
663/4
S 11/2
11/2
11/2
11/2
11/2
11/2
11/2
11/2
11/2
11/2
11/2
11/2
11/2
22
T 177/8
197/8
217/8
237/8
267/8
277/8
297/8
347/8
377/8
437/8
477/8
517/8
557/8
627/8
687/8
U 8 8 8 8 12 12 20 20 20 20 20 20 24 28 28
V 11 13 15 17 10 101/2
53/4
773/4
91/4
101/4
111/4
93/4
95/16
105/16
W
MAX
193/8
213/8
233/8
253/8
283/8
293/8
313/8
363/8
393/8
453/8
493/8
533/8
573/8
643/8
703/8
X
STL.
10 GA. 10 GA. 10 GA. 10 GA.3/163/163/163/163/163/163/163/163/161/41/4
ALUM.
.125 .125 .125 .1253/163/163/163/163/163/163/163/163/161/41/4
Mounting Panel
NOTE: Dimensions and specifications are subject to change. Certified prints are available.
NOTE: Dimensions and specifications are subject to change. Certified prints are available.
Detail – Mounting Holes Panel Shown
24
Bulletin A-1
09-AJ
www.hartzellfan.com
1 (800) 336-3267
®
Detail – Showing Mounting Hole
Location on Optional Mounting
Flange and on Mounting Boot
SIZE 12 14 16 18 20 22 24 28 32 36 40 44 48 54 60 72
A 12 14 16 18 20 22 24 28 32 36 40 44 48 54 60 72
B
15 17 19 21 23 25 27 31 35 39 43 47 51 57 63 75
Damper Resistance Curve
Shutters
NOTE: Specifications are subject to change. Certified prints are available.
Principal Dimensions
AA
Z
Y
W
X
N
MOUNTING PANEL
14-GA. HRS
1/8 ALUM
BOOT
SQ. I.D.
SQ.
SQ.
Shutter Mounting Boots
Ring Fan Boot
Panel Fan Boot
End Pivoted (Automatic)
Center Pivoted (Manual or Motor Operated)
12
7 GA
1
/4
18
3
/4
18
3
/4
12
1
/
2
16
1
/8
1
13
/16
20
14
7 GA
1
/4
20
3
/4
18
3
/4
14
1
/
2
18
1
/8
1
13
/16
NA
16
7 GA
1
/4
22
3
/4
18
3
/4
16
1
/
2
20
1
/8
1
13
/16
20
18
7 GA
1
/4
24
3
/4
18
3
/4
18
1
/
2
22
1
/8
1
13
/16
20
20
7 GA
1
/4
28
3
/4
18
1
/4
20
1
/
2
25
1
/8
2
5
/16
20
22
7 GA
1
/4
30
3
/4
18 22
1
/
2
26
1
/8
1
13
/16
NA
24
7 GA
1
/4
32
1
/4
18 24
1
/
2
28
1
/8
1
13
/16
20
28
7 GA
1
/4
37
3
/4
17
3
/4
28
1
/
2
33
1
/8
2
5
/16
20
32
7 GA
1
/4
41 17
5
/8
32
1
/
2
36
1
/8
1
13
/16
20
36
7 GA
1
/4
47 17
5
/8
36
1
/
2
42
1
/8
2
13
/16
20
40
7 GA
1
/4
51 17
5
/8
40
1
/
2
46
1
/8
2
13
/16
20
44
7 GA
1
/4
55 17
5
/8
44
1
/
2
50
1
/8
2
13
/16
20
48
7 GA
1
/4
59 17
5
/8
48
1
/
2
54
1
/8
2
13
/16
20
54
7 GA
1
/4
65 17
5
/8
54
1
/
2
60
1
/8
2
13
/16
20
60
7 GA
1
/4
71 17
5
/8
60
1
/
2
66
1
/8
2
13
/16
20
72
7 GA
1
/4
82
1
/4
18 72
1
/
2
78
1
/8
2
13
/16
NA
W X Y Z AA AB
FAN
SIZE
N
STL
ALUM
Automatic Shutter
Manual Shutter Motor Operated Shutter
Heavy-duty automatic shutters, opening with the air velocity from the fan and closing by gravity when the fan is not in operation, are available to prevent backdraft from all openings with either standard ring or panel fans.
Center-pivoted, motor operated, or manual shutters are also available. Sketches are shown below. Please refer to the Resistance Curve at the right which shows resistance to airflow in terms of static pressure for shutters mounted in the airstream.
25
Bulletin A-1
09-AJ
www.hartzellfan.com
1 (800) 336-3267
®
Z
14-GA. HRS
1/8 ALUM
AA
SQ.
SQ.
Y
I.D.
AB
HOOD
AB CDE FGR
0
1
R
0
2
STUVWXFFGG
AREA
FAN SIZES AVAILABLE PER HOOD FAN SIZES AVAILABLE PER HOOD
SIZE (FT2)
SERIES 01, 08 SERIES 02, 09
24 24 319/16 201/8 27 251/2 51/4 20 241/2 241/2 251/2 251/2 20 51/4 27 27 3 3 4 12, 14, 16, 18 12, 16
36 36 447/16 2829/32 39 371/2 81/4 20 361/2 361/2 371/2 371/2 20 81/4 39 39 3 3 9 20, 22, 24, 28, 30 18, 20, 24
42 42 525/8 3311/32 45 431/2 93/4 20 421/2 421/2 431/2 431/2 20 93/4 45 45 3 3 121/4 24, 28, 30, 32 24, 28, 30, 32
48 48 563/4 377/8 51 491/2 111/4 20 481/2 481/2 491/2 491/2 20 111/4 51 51 3 3 16 32, 36 32, 36
60 60 691/8 4611/16 63 611/2 91/2 28 601/2 601/2 611/2 611/2 28 91/2 63 63 3 3 25 36, 40, 42, 44, 4
8
36, 40, 42, 44, 4
8
72 72 8023/32 5519/32 75 731/2 111/2 28 721/2 721/2 731/2 731/2 28 111/2 75 75 3 3 36 48, 54, 60 48, 54, 60
84 84 959/32 641/2 87 851/2 101/8 36 841/2 841/2 851/2 851/2 36 101/8 87 87 3 3 49 54, 60, 72 54, 60
Wall Hood
Wall Hood
Panel Fan Adapter
Ring Fan Adapter Panel
Wall Hood Resistance Curves
Wall Hood Birdscreens Resistance Curve
Wall Hood Birdscreen
Wall Hoods are available to protect the fan and equipment as well as the building opening from the elements. Hartzell wall hoods are fabricated of heavy gauge galvannealed steel and are designed for minimum resistance to air flow. Lifting lugs are standard and bird screens are available as an option.The exterior is finished with an industrial grade enamel. Wall hoods are bolted together, shipping knocked down as standard (factory assembly is available). Wall hoods are also available with continuous weld assembly.
The wall hood is designed to either (a) mount directly to the wall or (b) interface directly with Hartzell fans and other accessories. When the wall hood interfaces with other Hartzell products, a panel fan adapter or ring fan adapter panel is required. Please refer to the drawing and dimensions below.
Note that the wall hoods may be used with a variety of different fan sizes. Information detailing which fans should be used with which hoods is included in the dimensional table below.
For intake air configurations, the fan should be selected based on air flow performance and total system static pressure (resistance associated with appurtenances and external static pressure). Once the flow is determined, the velocity should be calculated for a given hood. Divide CFM by square foot open area for the wall hood (see table below). To prevent
entrainment of water, intake velocities through the wall hood should not exceed 1,000 feet per minute.
Fan resistance associated with the use of the wall hood varies with air velocity and fan configuration (intake or exhaust). Please refer to the wall hood resistance curves at the bottom of this page to determine system static pressure associated with the application of a wall hood.
1. INTAKE AIR FLOW
2. EXHAUST AIR FLOW
1 1.5 2 2.5 3 4 5 6 7 8 9 10 15 20 25 30
AIR VELOCITY BASED ON HOOD OPENING AREA (FPM X 100)
1. INTAKE AIR FLOW
2. EXHAUST AIR FLOW
.200
.150
.100 .090 .080
.070
.060
.050
.040
.030
.025
.020
.015
.010
1 1.5 2 2.5 3 4 5 6 7 8 9 10 15 20 25 30
AIR VELOCITY BASED ON HOOD OPENING AREA (FPM X 100)
(1)
(2)
(1)
(2)
S.P. (IN. W.G.)
S.P. (IN. W.G.)
Painted steel wire mesh (1/2" by 1/2") easily installed and removable, with mounting hardware (included). Fan resistance is effected by velocity through the birdscreen and fan configuration (intake or exhaust). Please see resistance curve at the bottom of this page.
26
Bulletin A-1
09-AJ
www.hartzellfan.com
1 (800) 336-3267
®
.200
.150
.100 .090 .080
.070
.060
.050
.040
.030
.025
.020
.015
.010
LIFTING LUG
3
F
B
REF.
TYP.
PITCH
TYP.
D
W
3/4
3/4
V
FF
GG
A
SQ.
INSIDE
A
SQ.
INSIDE
BIRDSCREEN
OPTION
V
C
REF.
OPENING VARIES
WITH FAN SIZE
9/16 DIA
REQ'D
G
E
SQ.
OPENING VARIES
WITH FAN SIZE
9/16 - DIA.
U
REQ'D
S
X
3/4
Designed for operation from separate motor or line shaft. Two sets of self-aligning ball bearings, mechanically sealed, insure a smooth running shaft which will not bind.
Improved strong, vibration-absorbent welded truss-type shaft support. Extra-strength Hartzell propeller with extra efficiency against pressure. Curved orifice retains a 10% gain in air delivery when compared to non-venturi construction.
Performance data on propeller fans (pages 4 through 9) apply to pulley drive models. When ordering, use catalog numbers on those pages and specify “Pulley Drive Fan.” Furnished without motor or pulley.
This fan is designed for use where it is desirable to mount the motor outside of a duct because of flammable fumes, corrosive elements, excessive heat or abrasive dust in the airstream.
Simple, sturdy, trouble-free. Rigid construction and oversize shaft prevent any possibility of shaft whip. Mechanically sealed ball bearings with grease retainers.
This model is furnished without housing. Housing of any type can be furnished at extra cost. Pulley drive units also available.
Performance data on propeller fans (pages 4 through 9) apply to those fans in extension shaft models. When ordering, use catalog numbers on those pages and specify “Extension Shaft Fan.”
This fan is particularly desirable for use in paint spray booths and other locations where fire constitutes a hazard. Especially valuable where ordinances prohibit the use of a fan with motor located in the airstream even though it is explosion-proof.
The heavier, wider Hartzell propeller, which is extra-efficient against pressure, and the curved orifice Air Seal Ring are built into this fan. The curved orifice retains a 10% gain in air delivery when compared to non-venturi construction.
Simple, long lived construction. Belt easily adjusted or changed. Self-aligning, felt-sealed ball bearings. Complete with motor, pulley and belt.
Available with all propeller fans and sizes listed on pages 4 through 9. When ordering, use catalog numbers on those pages and specify “Belt Driven Fan.” Performance data available on request.
This fan is constructed of fiberglass and Ashland 693FR with other resins available. It is suitable for temperatures up to 180°F. (specially insulated motors are required for temperatures above 104°F.) The fiberglass wall ventilator is available in sizes ranging from 12" to 60" with performance from 1315 CFM to 55,500 CFM at free air.
Fiberglass Wall Ventilator
Belt Drive Fan
Pulley Drive Fan
Extension Shaft Fan
Other Propeller Fans
27
Bulletin A-1
09-AJ
www.hartzellfan.com
1 (800) 336-3267
®
Hartzell Warranty
Rev. Warranty 5/1/11
LIMITED WARRANTIES
Hartzell represents to Buyer that any goods to be delivered hereunder will be produced in compliance with the requirements of the Fair Labor Standards Act of 1938 as amended.
Hartzell also warrants to Buyer its goods to be free from defects in workmanship and material under normal use and service for one (1) year after tender of delivery by Hartzell, plus six months allowance for shipment to approved stocking dealers and distributors. No warranty extends to future performance of goods and any claims for breach of warranty or otherwise accrues upon tender of delivery.
The foregoing constitute Hartzell’s sole and exclusive warranties and are in lieu of all other warranties, whether written, oral, express, implied or statutory.
LIMITATION OF LIABILITY FOR BREACH OF WARRANTY
Hartzell’s obligation for any breach of warranty is limited to repairing or replacing, at its option, without cost to Buyer at its factory any goods which shall, within such a warranty period, be returned to it with transportation charges prepaid, and which its examination shall disclose to its satisfaction to have been defective. Any request for repair or replacement should be directed to Hartzell Fan, Inc., P.O. Box 919, Piqua, Ohio 45356. Hartzell will not pay for any repairs made outside its factory without its prior written consent. This does not apply to any such Hartzell goods which have failed as a result of faulty installation or abuse, or incorrect electrical connections or alterations, made by others, or use under abnormal operating conditions or misapplication of the goods.
LIMITATION OF LIABILITY
To the extent the above limitation of liability for breach of warranty is not applicable, the liability of Hartzell on any claim of any kind, including negligence, for any loss or damage arising out of or connected with, or resulting from the sale and purchase of the goods or services covered by these Terms and Conditions of Sale or from the performance or breach of any contract pertaining to such sale or purchase or from the design manufacture, sale, delivery, resale, installation, technical direction installation, inspection repair, operation or use of any goods or services covered by these Terms and Conditions shall, in no case exceed the price allocable to the goods or services which gave rise to the claim and shall terminate one year after tender of delivery of said goods or services, plus six months allowance for shipment to approved stocking dealers and distributors. In no event will Hartzell be responsible or liable for any labor or other incidental costs associated with the removal or replacement of defective products or materials.
In no event whether as a result of breach of contract, or warranty or alleged negligence, defects, incorrect advice or other causes, shall Hartzell be liable for special or consequential damages, including, but not limited to, loss of profits or revenue, loss of use of the equipment or any associated equipment, cost of substitute equipment, facilities or services, down time costs, or claims of customers of the Buyer for such damages. Hartzell neither assumes nor authorizes any person to assume for it any other liability in connection with the sale of its goods or services.
NO IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS
HARTZELL DOES NOT WARRANT THAT SAID GOODS ARE OF MERCHANTABLE QUALITY OR THAT THEY ARE FIT FOR ANY PARTICULAR PURPOSE. THERE IS NO IMPLIED WARRANTY OF MERCHANTABILITY AND THERE IS NO IMPLIED WARRANTY OF FITNESS.
www.hartzellfan.com
Propeller Fans
Vaneaxial Blowers
Heating Equipment –
Gas & Steam
Hartzell Fan, Inc., Piqua, Ohio 45356 • Plants in Piqua, Ohio and Portland, Indiana.
Cooling Tower &
Heat Exchanger Fans
Cool Blast & Utility Fans
Fiberglass
Axial Flow Fans
Duct Fans
Steel Centrifugal Blowers
Fiberglass Centrifugal
Blowers
Duct Axial Fans
Roof Ventilators – Steel & Fiberglass
Marine –
Mine Duty Blowers
Litho in U.S.A. A-109-AJ 5/09
Loading...