Hart and Cooley TLC Installation Instructions Manual

Model TLC
Installation Instructions
All-Fuel Chimney - 5” to 8”
Factory-Built Type HT Insulated Chimney - Tested to UL103
Type of Appliances
Your Model TLC chimney is intended for venting gas, liquid, or solid fuel-fired, residential-type appliances and building heating appliances or as defined in NFPA 211, in which the maximum continuous flue gas temperatures do not exceed 1000°F. It has been tested and approved to withstand temperatures of up to 2100°F for three 10-minute intervals.
Pre-Installation Guidelines
If you choose to have your product installed by others, we recommend these products be installed by professionals who are certified by NFI (National Fireplace Institute) or equivalent.
Your Model TLC chimney and connecting stovepipe diameter should be sized in accordance with the appliance manufacturer’s recommendations.
Plan the installation of your appliance and chimney in such a way that both your chimney and your stovepipe run as short and straight as possible. By having too long and/or multiple-bend installations, you can reduce system draft that can affect the operation and/or performance
of your appliance and/or chimney system. The chimney should be located within the building in order to avoid cutting or altering load-bearing members, such as joists, rafters, studs, etc. If you have to cut or alter an existing load-bearing member, special reframing methods are required, which often include doubling of adjacent members. If such a case arises, contact your local Building Code Official regarding local regulations and proper installation methods.
Sections of the Model TLC chimney that pass through accessible areas of the building, such as through closets, storage areas, occupied spaces, or any place where the surface of the chimney could be contacted by persons or combustible materials, must be enclosed in a chase to avoid personal contact and damage to the chimney. The chase may be fabricated using standard building materials. Drywall mounted on 2” x 4” studs is typically used in this situation. The space between the outer wall of the chimney and the enclosure must be at least a minimum of 2 inches.
MAINTAIN A 2-INCH MINIMUM AIRSPACE
CLEARANCE BETWEEN INSULATED CHIMNEY
SECTIONS AND COMBUSTIBLE MATERIALS.
WARNING: A MAJOR CAUSE OF CHIMNEY-RELATED
FIRES IS FAILURE TO MAINTAIN REQUIRED CLEARANCES (AIRSPACES) TO COMBUSTIBLE MATERIALS. IT IS OF UTMOST IMPORTANCE THAT THIS CHIMNEY BE INSTALLED ONLY IN ACCORDANCE WITH THESE INSTRUCTIONS.
Please read all instructions before beginning your installation.
Failure to install this system in accordance with these instructions will
void the conditions of certification and the manufacturer’s warranty.
Keep these instructions in a safe place for future reference.
Hart & Cooley, Inc.
1
Model TLC All-Fuel Chimney - 5” to 8” Installation Instructions
WARNING: DO NOT PLACE ANY INSULATING MATERIALS
OR RUN ANY ELECTRICAL WIRING WITHIN THE REQUIRED AIR CLEARANCE SPACE SURROUNDING THE CHIMNEY.
Before beginning the installation, ensure that you obtain any necessary building permits, and that your installation will conform with all federal and municipal building code requirements.
CONTACT LOCAL BUILDING OR FIRE
OFFICIALS ABOUT RESTRICTIONS AND
INSTALLATION INSPECTION IN YOUR AREA.
The National Fire Protection Association Standard 211 states: Factory-built chimneys that pass through floors of buildings requiring the protection of vertical opening shall be enclosed with approved walls having a fire-resistance rating of not less than one hour where such chimneys are located in a building less than four stories in height, and not less than two hours where such chimneys are located in a building four or more stories in height.
WEAR SAFETY GLOVES WHEN HANDLING
SHEET METAL PARTS WITH SHARP EDGES.
The chimney must extend not less than 3 feet above the highest point where it passes through the roof of a building and not less than 2 feet above any portion of the building within 10 feet (Figure 1). See Chart 2 - Chimney Height Above the Roof on page 17 of these instructions. The use of Locking Bands at all chimney joints is
required for added safety, stability when exposed to high winds, and as a precaution against accidental unlocking of lengths when the system is inspected and swept.
The ideal location for your chimney system is within the building envelope. In cold climates, the use of external chimneys may result in operational problems, such as poor draft, excessive condensation of combustion products, and rapid accumulation of creosote. Under these circumstances, the installation of the chimney within the building is strongly recommended.
If the chimney must be installed on an exterior wall, it is recommended that the chimney be enclosed below the roof line to protect the chimney from cold outdoor temperatures; this may help reduce condensation, creosote formation, and enhance draft. Provide an access door by the tee cap for chimney inspection and cleaning. The exterior enclosure may be insulated, maintaining the required minimum airspace clearance of 2 inches to any part of the chimney. Consult local building codes for cold-climate application.
Do not install the chimney directly at the outlet of the appliance. Interconnecting stovepipe is required, unless the appliance is specifically approved for that type of installation.
Use only with an appliance listed by a recognized testing authority, such as Underwriters Laboratories, Inc. or Intertek Testing Services.
2
The flue diameter of gas or oil-fired appliance should comply with the appropriate NFPA or ANSI Installation Codes, NFPA 54, ANSIZ223.1, and NFPA31.
YOUR CHIMNEY HAS BEEN TESTED AND LISTED,
USING ALL OF THE SUPPORTS, SHIELDS, ETC.,
DESCRIBED HEREIN. DELETION OR MODIFI-
CATION OF ANY OF THE REQUIRED PARTS OR
MATERIALS MAY SERIOUSLY IMPAIR THE SAFETY
OF YOUR INSTALLATION AND VOID THE CERTIFI-
CATION AND/OR WARRANTY OF THIS CHIMNEY.
Hart & Cooley, Inc.
Installation Instructions Model TLC All-Fuel Chimney
Installation Instructions Model TLC All-Fuel Chimney
Tools
Your Model TLC chimney system is designed for installation using standard building materials and procedures. The following tools/equipment may be required, as well as some others, depending on the location and structure in which the chimney is to be installed.
Safety Gloves
Screwdriver and Pliers
Safety Goggles
Plumb Line and Level
Hammer and Nails
Square
Tin Snips
Keyhole Saw or Power Jigsaw
Tape Measure
Caulking Gun
Framing Details
Plan your installation carefully. If possible, position the stove so that the flue outlet is between joists or rafters. Drop a plumb line to the center of the flue outlet, and mark this center point on the ceiling. Lay out and frame in all openings, ensuring the specified 2-inch clearance to combustibles is maintained. Refer to Table 1 for framing dimensions, and mark the appropriate cutting lines around the center point. All openings should be square (all four sides), plumb, and in perfect alignment with each other (Figure 2).
For sloping roofs, ensure that the framing dimension is measured in the horizontal plane (Figure 3).
Installation Procedures
Ceiling Support Installation
To complete a proper ceiling support installation, the following parts will or may be required.
Ceiling Support: Required when supporting a chimney through a flat level ceiling. Also acts as a firestop.
Attic Insulation Shield: Required where a chimney passes from a lower living space into an unoccupied attic space.
Firestop Radiation Shield: Required where a chimney passes from a lower living space into an upper living space or occupied attic space.
Roof Flashing Assembly (including Storm Collar): Required when the chimney penetrates a roof.
Rafter Radiation Shield: Required when the chimney is enclosed immediately below the roof.
Suitable Lengths of Chimney: The chimney diameter (ID) should be sized to suit the appliance.
Elbow Kit: To avoid cutting of joists and clear other obstructions. Kit includes 2 elbows, 1 offset support, and 4 locking bands.
Rain Cap: Deluxe model.
The Model TLC ceiling support will support up to 50 feet of chimney sections, all of which must be installed above the support. Figures 4 and 6 show the two most common types of ceiling support installation. Frame (all four sides) a level square opening to the dimensions specified in the
Framing Dimensions (Table 1).
Table 1
Chimney
Diameter
Support*
Wall
Thimble*
All
Framing
Tools
Your Model TLC chimney system is designed for installation using standard building materials and procedures. The following tools/equipment may be required, as well as some others, depending on the location and structure in which the chimney is to be installed.
• Safety Gloves
• Safety Goggles
• Hammer and Nails • Square
• Tin Snips
• Tape Measure
Framing Details
Screwdriver and Pliers
Plumb Line and Level
Keyhole Saw or Power Jigsaw
Caulking Gun
Plan your installation carefully. If possible, position the stove so that the flue outlet is between joists or rafters. Drop a plumb line to the center of the flue outlet, and mark this center point on the ceiling. Lay out and frame in all openings, ensuring the specified 2-inch clearance to combustibles is maintained. Refer to Table 1 for framing dimensions, and mark the appropriate cutting lines around the center point. All openings should be square (all four sides), plumb, and in perfect alignment with each other (Figure 2).
For sloping roofs, ensure that the framing dimension is measured in the horizontal plane (Figure 3).
Installation Procedures
Ceiling Support Installation
To complete a proper ceiling support installation, the following parts will or may be required.
Ceiling Support: Required when supporting a chimney through a flat level ceiling. Also acts as a firestop.
Attic Insulation Shield: Required where a chimney passes from a lower living space into an unoccupied attic space.
Firestop Radiation Shield: Required where a chimney passes from a lower living space into an upper living space or occupied attic space.
Roof Flashing Assembly (including Storm Collar): Required when the chimney penetrates a roof.
Rafter Radiation Shield: Required when the chimney is enclosed immediately below the roof.
Suitable Lengths of Chimney: The chimney diameter (ID) should be sized to suit the appliance.
Elbow Kit: To avoid cutting of joists and clear other obstructions. Kit includes 2 elbows, 1 offset support, and 4 locking bands.
Rain Cap: Deluxe model.
The Model TLC ceiling support will support up to 50 feet of chimney sections, all of which must be installed above the support. Figures 4 and 6 show the two most common types of ceiling support installation. Frame (all four sides) a level square opening to the dimensions specified in the Framing Dimensions (Table 1).
Framing Dimensions (in inches)
Flue
5" 123/8 x 123/
6" 123/8 x 123/
7" 133/8 x 133/
8" 143/8 x 143/
* When cutting the inside "finished" surface of your wall or ceiling, cut a "round hole" to the framing dimension.
Ceiling
(Support)
14 x 14 11 x 11
8
14 x 14 12 x 12
8
14 x 14 13 x 13
8
14 x 14 14 x 14
8
Othe r
3
Model TLC All-Fuel Chimney - 5” to 8” Installation Instructions
Table 2
Framing Dimensions
for Attic Insulation Shield
Chimney Flue
Diameter
Slide the trim ring onto the ceiling support, and slide the assembly into the framed opening from below. Ensure that the finishing ring is flush with the underside of the ceiling and the assembly is level and plumb. Secure the ceiling support in place, using at least three 8-penny (2½”) nails through each of the four straps or through the twelve prepunched holes in the support. You may substitute, in lieu of nails, twelve #8 x 2” wood screws.
Stovepipe Adapter Installation
The stovepipe adapter is installed by twisting-locking it to the bottom end of the chimney section that enters the ceiling support. Lower the assembly down into the ceiling support so that the stovepipe adapter sleeve is protruding through the support and into the living space.
Attic Insulation Shield Installation
An attic insulation shield must be installed where the chimney enters an attic space. (It also acts as a firestop when properly framed.) An attic insulation shield should keep insulation from coming into contact with the chimney and will allow a depth of insulation of 10 inches plus the depth of the ceiling joist. Where height restrictions will not permit the use of the attic insulation shield, an enclosure from the attic joist to the roof joist will be sufficient. All chimney enclosures must maintain the required minimum airspace clearance of 2 inches to the chimney. When enclosing the chimney below the roof line, a rafter radiation shield at the roof level and a firestop radiation shield at the ceiling level must be installed.
inches
The crimped end (stub) of the stovepipe adapter is intended to fit inside the flue pipe from a solid-fuel appliance, thus preventing condensate drips at the chimney connection. Install interconnecting flue pipe by following the appliance manufacturer’s installation instructions and appropriate building code requirements, keeping in mind that the flue pipe run should be as short and straight as practical. Generally, for a wood-burning appliance installation, an 18-inch minimum clearance to combustibles must be maintained for a single-wall flue pipe.
5" 11 x 11
6" 12 x 12
7" 13 x 13
8" 14 x 14
Install additional chimney sections and lock together by turning clockwise until the two sections lock together tightly. Install required locking bands. Continue adding chimney lengths until a height of about 2 feet below the next ceiling level is achieved.
4
Hart & Cooley, Inc.
Installation Instructions Model TLC All-Fuel Chimney
For proper installation, the attic opening must be fully framed at 2 inches of clearance to the chimney pipe with framing material of the same dimension as the ceiling joists, per Table 2 (Framing Dimensions for Attic Insulation Shield). The tabs on the plate of the attic insulation shield are inserted in the framed opening around the chimney. Nail the attic insulation shield base to the framing dimensions with at least two per side, using 2d 1” spiral nails or 1” x #8 wood screws.
When an attic insulation shield is required above the ceiling support into an attic as shown in Figure 4, ensure that the base of the shield is flush with the top of the joist framing, and nail in place. The telescoping portion of the attic insulation shield will eliminate the need to trim the bottom, when installed immediately above the ceiling support. When fully extended, the attic insulation shield will provide joist shielding when installed in a two-story main floor application (Figure 6).
If insulation is blown in and adheres to the chimney pipe, it must be brushed off to eliminate any possible contact of this material with the chimney surface.
Firestop Radiation Shield Installation
A firestop radiation shield must be installed where the chimney passes from one living space to another living space, as shown in Figure 7. It is designed to provide proper firestopping between floors and to keep direct radiation from the chimney away from the joist framing.
Install the firestop radiation shield from below the joist framing, and nail in place using 1” spiral nails. Ensure no insulation is within the 2-inch airspace clearance around the chimney. This includes the airspaces between the firestop radiation shield and the joist framing.
When the chimney is enclosed in the attic area, a firestop radiation shield must be installed at the ceiling level. If the base of the firestop radiation shield does not fit flush with the ceiling frame, measure the distance that the base is sitting below the framing, and trim that amount off the top of the firestop radiation shield before securing into place.
Elbow Installation
Two elbows may be used in an interior installation to provide an offset, in order to avoid cutting of joists and to clear other obstructions. Each elbow support will support 15 feet of chimney, and the maximum length of chimney allowed between elbows is 6 feet. Forty-five-
degree (45°) elbows may be used only with oil or gas appliances. See Chart 1 - Offset Chimney Installation
on page 16 of these instructions for details.
The female end of the elbows are not embossed; this ensures that proper alignment of the chimney system is maintained. Locking bands must be installed at all chimney joints, forming an offset.
Hart & Cooley, Inc.
Install the insulated offset elbow on the vertical chimney length, and position the elbow in the required direction. Fasten the elbow to the chimney length with the supplied locking band.
5
Model TLC All-Fuel Chimney - 5” to 8” Installation Instructions
Place the required offset chimney length(s) as per the Offset Chimney Installation chart for appropriate length(s). Turn it clockwise to lock it in place and fasten in place with the supplied locking band.
Install the remaining offset elbow to turn the chimney back to the vertical position and fasten in place with the supplied locking band.
During installation, provide supplementary support for the offset section to avoid undue stress on connected elbows.
Install an elbow support just above the highest elbow. Attach the support band to the chimney with four of the nuts and bolts, and then install the four stainless steel sheet metal screws through the prepunched holes. Attach the support straps to the support band assembly, and nail the support straps to the framing using 6d 2” nails or #8 x 1½” wood screws. See Figure 8.
Never install an elbow in a joist area. Chimney sections must pass vertically through framed joist areas.
To complete a proper wall support installation, the following parts will or may be required.
Wall Support: Intended for a through-the-wall installation where the chimney has a horizontal connection.
Stovepipe Adapter: Transition from chimney to flue pipe.
Insulated Tee with Insulated Tee Cap: Allowing a horizontal connection to the chimney.
Roof Flashing Assembly: Required when the chimney penetrates a roof or a roof overhang.
Rafter Radiation Shield: Required when the chimney is enclosed immediately below the roof.
Wall Band: Required to provide lateral support to chimney.
Suitable Lengths of Chimney: The chimney diameter should be sized to suit the appliance.
Chimney Length: Appropriate length for connection to tee branch.
Wall Thimble: Required to pass though a combustible wall. It also acts as a firestop.
Rain Cap: Deluxe model.
Note: Never offset an exterior chimney.
Note: Never offset an exterior chimney.
Adjustable Wall Support Installation
As previously mentioned, the ideal location for your chimney system is within the building envelope. A wall support installation is required when the above-mentioned location is not possible.
6
Hart & Cooley, Inc.
Installation Instructions Model TLC All-Fuel Chimney
Installation Instructions Model TLC All-Fuel Chimney
The maximum chimney height above a wall support is indicated in Table 3 and illustrated in Figure 10, all of which must be above the support.
The wall support will allow for an adjustment of 2" to 6" from a vertical wall. Threaded studs are factory-installed on both side brackets and the support plate for fast and easy assembly. See Figure 11.
Table 3
D (inches)
Wall to Chimney
H (feet)
Height
The maximum chimney height above a wall support is indicated in Table 3 and illustrated in Figure 10, all of which must be above the support.
Wall Support Chimney Height Chart
5" ID
Chimney
Distance from
2 74 63 56 49
2.5 73 62 55 48 3 71 60 53 47
3.5 69 59 51 46 4 66 56 49 44
4.5 62 53 46 42 5 58 50 43 39
5.5 52 45 38 35 6 45 39 34 30
D - Distanc e from wall to the chimney H - Height of chimney in feet See Figure 10 also
6" ID
Chimney
Maximum
7" ID
Chimney
8" ID
Chimney
The wall support will allow for an adjustment of 2” to 6” from a vertical wall. Threaded studs are factory-installed on both side brackets and the support plate for fast and easy assembly. See Figure 11.
Ensure that the wall support brackets are bolted securely to the wall.
The following steps will assist you in the installation of the wall thimble and of the wall support. Figure 10 shows a typical wall support installation through a combustible wall.
1. Determine the centerline of the horizontal connection (chimney length through the wall), and frame an opening to the dimensions for the wall thimble in a combustible wall. See Table 4 Section A and Figure 12(A).
- Use a stud finder to roughly locate the wall studs.
Mark the outline of the hole and drill a pilot hole in its center.
- Break out part of the wall covering within the
outline to confirm that the hole will be centered between studs and that no electrical wires could be cut by the saw.
2. For a noncombustible wall (concrete block or poured foundation), cut a hole 3/16” greater in diameter than the outside diameter of the chimney as per Table 4.
See Table 3 for maximum chimney heights based on
chimney diameter and distance from wall.
Hart & Cooley, Inc.
7
Model TLC All-Fuel Chimney - 5” to 8” Installation Instructions
Model TLC All-Fuel Chimney - 5" to 8" Installation Instructions
5" 6" 7" 8"
Wall Thimble
for Combustible Wall
Support Brackets
for Bracing
Table 4
Chimney SizeFraming Dimensions
Wall Thimble & Support Brackets
Section
A
B
Minimum Round Hole Diameter for Noncombustible Wall
Minimum Framed Opening
Minimum Framed Opening
3
7
14" x 14" 14" x 14" 14" x 14" 14" x 14"
91/4"9
3. After framing in your opening to the dimensions specified to the Framing Tables 1 or 3, install the outer half (with the unfinished square plate) of the wall thimble into the outside wall opening. Secure in place using appropriate fasteners through the prepunched holes.
/16"83/16"93/16" 103/16"
1
/4" 101/4" 111/4"
threaded studs into the oblong slots. See Figures 11 and 14. Install the supplied nuts on the threaded studs until snug. Do not tighten at this time, as adjustments may be required. Set aside and prepare the support bracing to secure the side brackets as per Framing Dimensions Table 4 Section B and Figure 12(B).
Two options are described hereafter for the installation of the wall support and the insulated tee assembly. Follow Method A if inserting an assembled insulated chimney length and insulated tee into the wall thimble prior to the wall support. Follow Method B if securing of the wall support to the wall prior to the insulated tee and the insulated chimney length.
4. Install the inner half (with round plate) of the wall thimble into the inside wall opening, ensuring that the shield slides over the shield of the outer half. Once in place and flush against the wall, install the black finishing trim plate onto the wall surface and fasten in place with appropriate fasteners through the four prepunched holes.
Note: To stop cold air infiltration into the dwelling,
you can install the optional universal shielding insulation into the wall thimble. See separate installation instructions packaged with the universal shield insulation.
5. Assemble the two side brackets (point of triangle facing down) to the support plate (flange up and threaded stud toward the wall) by inserting the
8
Hart & Cooley, Inc.
Loading...
+ 16 hidden pages