Installation and service must be performed by a qualified and knowledgeable individual who has been trained on the Harsco Industrial, Patterson-Kelley MODU-FIRE® Forced Draft boiler. The same
features which permit this boiler to achieve high-efficiency performance make it unlike most other boilers of this
general size, so it is important to understand how this boiler operates.
What to do if you smell gas:
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
If you cannot reach your gas supplier, call the fire department.
The MODU-FIRE® Forced Draft gas-fired boiler is a revolutionary advance. Harsco Industrial, Patterson-Kelley
now combines full-modulation burner control and forced draft advances with our time-tested modular hot water
boiler design. The result is afull-modulation boiler utilizing reduced vent sizing for installation and cost
efficiencies. This boiler combines the best of our earlier designs with a new generation of burner, control and
operating technology. You will achieve high part-load efficiencies – but without the complexity you might expect
in this type of high performance boiler. It is high performance made simple and dependable for years of troublefree operation.
®
This manual covers installation and operation of the MODU-FIRE
model numbers may include a prefix to indicate special features or different options. While details may differ
slightly, basic operation is the same for all models. Boilers are built to operate with natural gas or propane. Check
the rating label for the correct gas type and flow rate.
The boiler is only a part of the complete heating system. This boiler may be fully operational and yet, because of
poor circulation, controls, or other operating characteristics, not deliver heat to the desired location. Additional
equipment such as temperature sensors, pumps, flow switches, balancing valves and check valves will be
required for satisfactory operation of any system. Harsco Industrial, Patterson-Kelley cannot be responsible for
the design or operation of such systems and a qualified engineer or contractor must be consulted.
Forced Draft 2500 & 3000 MFD boiler. The
2 SAFETY
2.1 GENERALThe MODU-FIRE® Forced Draft gas-fired boiler must be:
Installed in accordance with designs prepared by qualified facility engineers including: structural,
mechanical, electrical, and other applicable disciplines.
Operated and serviced in accordance with a comprehensive safety program determined and established by
the customer. Do not attempt to operate or service the unit until such a program has been established.
Operated and serviced by qualified and knowledgeable personnel in accordance with all applicable codes,
laws, and regulations.
The use of the term “factory-trained personnel” throughout this manual indicates Harsco Industrial, Patterson-
Kelley trained on this specific piece of equipment.
2.2 T
It is essential to read, understand, and follow the recommendations of this manual before installing, operating, or
servicing this equipment. Failure to do so could result in serious injury, death, and/or property damage.
RAINING
Proper training is the best protection against accidents. Operating and service personnel must be thoroughly
familiar with the basic construction of the MODU-FIRE
the operation of the boiler, adjustment of its various mechanisms, and all applicable safety precautions. If any of
®
Forced Draft boiler, the use and locations of the controls,
5
the provisions of this manual are not fully and completely understood, contact the Harsco Industrial, PattersonKelley Technical Services Department at (877) 728-5351.
2.3 S
It is the responsibility of the customer to maintain the safety features of this machine, such as: guards, safety
labels, safety controls, interlocks, lockout devices.
2.4 S
The following words are used in this manual to denote the degree of seriousness of the individual hazards.
indicates an imminently hazardous situation which, if not avoided, will result
in death or serious injury. This signal word is to be limited to the most extreme situations.
indicates a potentially hazardous situation which, if not avoided, could re-
sult in death or serious injury.
indicates a potentially hazardous situation which, if not avoided, may result
in minor or moderate injury. It may also be used to alert against unsafe practices.
NOTICE/NOTE - NOTICE is the preferred signal word to address practices not related to personal
injury. The safety alert symbol is not used with this signal word.
The safety labels shown below are affixed to the boiler and dual language labels may also be affixed to the boiler.
Although the labels are of high quality, they may become dislodged or unreadable over time. Contact Harsco
Industrial, Patterson-Kelley for replacement labels.
2.5 S
Provide a suitable location for the boiler, away from normal personnel traffic, with adequate working space,
adequate clearances, proper ventilation and lighting, with a structure sufficiently strong and rigid to support the
weight of the boiler, all piping and accessories.
2.5.1 Electrical Hazards
AFETY PRECAUTIONS
Shock hazard! Properly lockout/tagout the electrical
service and all other energy sources before working on or
near the machine.
Shock hazard! Boiler is not rated for wash-down service.
Power down unit for at least 10 minutes before servicing
Make sure this union is
tight before closing cabinet
cover after servicing boiler.
c
1998 HCS, Inc. 800-748-0241
Reorder No. 8032-02NHAK
NOTE
When opening leak test valves,
always follow instructions in
operation and safety manual.
c
1998 HCS, Inc. 800-748-0241
Reorder No. 8032-01NHPK
c
1998 HCS, Inc. 800-748-0241
WARNING
Im p rop er use m a y
result in fire or injury.
Read instructions/safety
manual before installing,
operating or servicing boiler.
Re or de r No. 6020- V2 WH PK
Burn, fire, and explosion hazards! Installation must be in strict conformance to all applicable codes and
standards including NFPA 54/ANSI Z223.1 and/or CAN/CSA- B149.1.
Hazard from incorrect fuels! Possible fire, explosion, overheating, and damage. Do not use any fuels except
the design fuel for the unit.
Overfire hazards! High pressure in gas or propane supply could result in overfiring of other devices supplied
from the same source.
Fire and explosion hazards! Close the main gas shutoff before servicing boiler.
Fire and explosion hazards! Do not store or use gasoline or other flammable vapors or liquids in the vicinity
of this or any other gas fired appliance.
Burn hazard! Possible hot surfaces. Do not touch the stack during firing operations. Use only factory
recommended vent components.
Burn hazard! Hot fluids. Use caution. Allow boiler to cool before servicing or draining boiler.
Fire and explosion hazards! Use caution when servicing burner or heat exchanger. Unburned fuel may linger
in the combustion chamber, vent lines, or elsewhere.
Gas leak hazard! Make sure all connections to main burner are tight when reassembling the burner.
Gas leak hazard! All threaded gas connections must be made using a pipe compound that is resistant to
liquefied petroleum. Do not use Teflon tape on threaded gas piping.
Gas leak hazard! Check entire gas train for leaks after installation. If there is a smell of gas, shut down the
boiler, close all gas valves and obtain immediate assistance from factory-trained personnel and/or your local
fire department.
Overfire hazard! Possible fire and explosion from excess gas pressure. Make sure that gas inlet pressure
does not exceed 14 inches W.C. to the boiler main gas valve.
Overfire hazard! Possible fire and explosion. Possible malfunction of regulators and/or gas valves.
Maintain all gas train components in good condition. Do not alter wiring connections. Annual inspection by
factory-trained personnel for proper set-up and operation is recommended.
Overfire and underfire hazards! Possible fire, explosion, overheating, and component failure. Do not attempt
to adjust firing rate of the boiler. The firing rate must be adjusted only by factory-trained personnel.
7
2.5.3 Crush Hazards
Lifting hazards! Use properly rated lifting equipment to lift and position the boiler. The load is
unbalanced. Test balance before lifting more than 3 ft. above the floor. Do not allow
personnel beneath the lifted load. The approximate weight of the N2500 & N3000 MFD is
1200 lbs.
General Warning
Bump hazard from overhead piping. Install piping with adequate vertical clearance.
2.5.4 Chemical Hazards
Chemical hazards from cleaning products. Use caution when cleaning the system. The use
of professional assistance is recommended. Use safe procedures for the disposal of all
cleaning solutions.
General Warning
2.5.5 Pressure Hazards
Pressure hazard! Hot fluids. Install isolation valves on boiler water inlet and outlet. Make
sure isolation valves are closed before servicing boiler.
Pressure hazard! Hot fluids. Test safety relief valve every 30 days during the heating season
and after any prolonged period of inactivity. Do not operate boiler with faulty relief valve.
Tripping hazard! Do not install piping on floor surfaces. Maintain clear path around boiler.
Slip and fall hazard! Use drip pan to catch water while draining the boiler. Maintain dry floor
surfaces.
Slip and fall hazard! Through-the-wall vents shall not terminate over public walkways or over
an area where condensate or vapor could create a nuisance or hazard.
General Warning
Fall hazard! Do not stand on any part of the boiler.
Catch hazard! Do not wear rings, jewelry, long hair, loose clothing while working on the
boiler.
3 INSTALLATION
Installation and service must be performed by a qualified installer, service agency,
or gas supplier.
3.1 R
3.1.1 Initial Inspection
Upon receiving the boiler, inspect it for signs of shipping damage.
recommend unpacking the boiler, removing the top, front, and side covers and inspect the boiler. Verify that the
total number of pieces shown on the packing slip agrees with those actually received.
NOTICE! Note any damage, suspected potential damage, or shortage of materials on the freight bill
and immediately notify the carrier. File all claims for shortage or damage with the carrier. Claims for
hidden damages must be filed with your carrier within 7 days. The boiler carton is equipped with a
“Tip (N) Tell”. If "Tip (N) Tell” arrow point is blue, that indicates that the package has been on its
side or tipped over in transit.
3.1.2 Storage Prior to Installation
If the boiler is not installed immediately, it must be stored in a location adequately protected from the weather,
preferably indoors. If this is not possible, then it should remain in the shipping container and be covered by a
tarpaulin or other waterproof covering.
NOTICE! Controls and other equipment that are damaged or fail due to weather exposure are not covered by
warranty.
3.2 C
The MODU-FIRE® Forced Draft boiler with standard components and many options complies with American
National Standard/CSA Standard ANSI Z21.13/CSA 4.9, latest edition. The heat exchanger is constructed and
stamped in accordance with ASME Boiler and Pressure Vessel Code, Section IV for 160 psig maximum operating
pressure and 250º F maximum operating temperature. Other codes or approvals which apply will be labeled on
the boiler.
OMPLIANCE WITH CODES
Installation of the boiler must conform to all the requirements of all national, state and local codes established by
the authorities having jurisdiction or, in the absence of such requirements, in the U.S. to the National Fuel Gas
Code, NFPA 54/ANSI Z223.1., latest edition, and the specific instructions in this manual. In Canada, the
equipment shall be installed in accordance with the current Installation Code for Gas Burning Appliances and
Equipment, CAN/CSA-B149.1, and applicable Provincial Regulations for the class which should be carefully
followed in all cases. Authorities having jurisdiction should be consulted before installations are made.
Where required by local codes, the installation must conform to American Society of Mechanical Engineers Safety
Code for Controls and Safety Devices for Automatically Fired Boilers (ASME CSD-1).
In the Commonwealth of Massachusetts, see Massachusetts Installation & Owner’s Manual Supplement.
3.3 S
3.3.1 Foundation
Provide a firm, level foundation, preferably of concrete.
NOTICE! The boiler may be installed on a combustible floor; however, the boiler must never be installed on
carpeting.
NOTICE! This boiler is certified for indoor installation only.
3.3.2 Placement
The boiler must be level and upright to function properly. Use shims or other approved structural devices to
properly level boiler.
ETUP
9
3.3.3 Installation Clearances
If the boiler is to be installed near combustible surfaces, six (6”) inches minimum clearance to the combustible
surface must be maintained.
Failure to provide for the service access clearances, even with non-combustible surfaces, may cause future
problems servicing the boiler.
The boiler must be installed in a space large in comparison to the boiler as described in the National Fuel Gas
Code, NFPA 54/ANSI Z223.1, Latest Edition.
Clearances from Adjacent Walls, Ceiling,
and Obstructions Side Clearances for a Row of Boilers
Type of Surface Dimensions (inches)
CSA Minimum Clearances to
Combustibles
Recommended Service
Clearances
A B C† D
24 24* 24 24
30 24* 24 24**
boiler or row of boilers. Boilers may be installed immediately
adjacent to each other. However, Harsco Industrial,
Patterson-Kelley recommends this clearance between each boiler when there is insufficient access at the rear to allow
for service and adjustment.
3.4 E
All field wiring connections for power and controls are in the
junction box on the back of the boiler. The boiler wiring label
is attached to the inside front door of the boiler. An external
electrical disconnect (not supplied with the boiler) with
adequate overload protection is required. The boiler must be
grounded in accordance with local codes or in the absence of
such requirements, in the U.S. with National Electrical
Codes, ANSI/NFPA No. 70 latest edition and in Canada, wire
Electrical
according to the current Canadian Electrical Code.
LECTRICAL CONNECTIONS
Connections
† "C" dimension includes clearance to remove
the burner and installation of the air inlet duct.
Do not put pipes, other ducts, equipment, etc.
above the boiler.
* CSA minimum. Actual clearance depends upon
venting requirements.
** Service access need be only on one side of a
10
NOTICE! A dedicated earth ground (green wire) is required to avoid nuisance shutdowns. Do not ground
through the conduit. It is also important that proper polarity be maintained.
The junction box at the rear of the boiler contains terminal strips for all customer connections. A detailed
schematic of the connections is shown in 6.1.7. These connections are described as follows:
High Voltage (HV) Terminal Block
The boiler power circuit requires 208-240 volts, single phase, 60 hertz, with a dedicated neutral and ground for
the control circuit as labeled. The voltage from each line (L1, L2) to the neutral must be approximately 120V AC.
Electrical service must be rated for 17 amps minimum. Before starting the boiler, check to ensure that the proper
voltage and amperage are connected to the boiler and that the boiler is connected to a suitable fused disconnect
switch or circuit breaker. There must be less than 1.0V from Neutral (HV-3) to Ground (HV-10)
120VAC Switched Output- This contact closes when the boiler is switched on. This provides 120VAC 5Amp
service to HV12 and HV13. The neutral for this circuit is provided on HV4 and HV5. When the boiler is switched
off, these terminals are switched off as well.
3 Way Valve- This output is normally energized, keeping the three way valve providing heat to the building. The
Domestic Hot Water (DHW) call for heat de-energizes this circuit, causing the 3 way valve to self close, thereby
providing heat to the DHW loop. This output provides 120VAC 0.5Amp service to HV14. The neutral for this
circuit is provided on HV 6.
DHW Pump Relay w/Delay Off - This output is enabled when there is a call for DHW. When the call for heat is
removed, the output remains enabled for a period of time. This output provides 120VAC 0.5Amp service to HV15.
The neutral for this circuit is provided on HV 7.
Circ Pump Relay w/Delay Off - This output is enabled when there is a call for heat. When the call for heat is
removed, the output remains enabled for a period of time. This output provides 120VAC 0.5Amp service to HV16.
The neutral for this circuit is provided on HV 8.
Damper Relay - This output is enabled when the call for heat is enabled. This output provides 120VAC service
to HV17. The neutral for this circuit is provided on HV 9. This circuit is for pilot duty only.
Master Alarm Relay – This contact closes in the event of an alarm output from the boiler control, connecting
HV18 and HV19.
Flame Detected Relay – This contact closes whenever the boiler is firing, connecting HV20 and HV21.
Low Voltage (LV) Strip
Enable/Disable– Use for boiler enable. Closing this circuit allows the boiler to run. Opening this circuit prevents
the boiler from running, provided the remote/local enable switch is in the remote position. This circuit is energized
by the boiler. It has a 24VAC potential. Devices connected to these terminals must be rated for 24VAC
The remote/local switch bypasses the Enable/Disable (LV1 to LV2) when in the local
position. Do not connect safety devices into the Enable/Disable circuit.
Auxiliary Low Water Cutoff – These terminals are used for connection of a secondary low water cutoff used in
the system. This circuit is energized by the boiler. It has a 5V potential. Devices connected to these terminals
must be rated for 5V.
11
External Interlock - Use for attachment of an additional field safety device to the boiler control circuit. Closing
this circuit allows the boiler to run. Opening this circuit prevents the boiler from running. This circuit is energized
by the boiler with a 5V potential. Devices connected to these terminals must be rated for 5V.
Outdoor Temp Sensor – LV7 and LV8 are connected to the outdoor temperature sensor. The temperature
control must be programmed to run an outdoor air schedule. The outdoor air sensor and programming help are
available from the local Harsco Industrial, Patterson-Kelley Representative. This circuit is energized by the boiler
with a 5V potential. The temperature sensor must be a NTC having 12k@25°C.
DHW Stat/Sensor – LV9 and LV10 are connected to the DHW temperature sensor or thermostat. This circuit is
energized by the boiler with a 5V potential. The temperature sensor must be a NTC having 12k@25°C.
Header Temp Sensor – LV11 and LV12 are connected to the header temperature sensor. This circuit is
energized by the boiler with a 5V potential. The temperature sensor must be a NTC having 12k@25°C.
DHW Flow Switch – LV13 is energized by the boiler with a 5V potential. This circuit connects through a flow
switch on the domestic side of a domestic hot water system. The flow switch should close upon flow to provide a
closed circuit back to LV14.
Analog Input– Remote signal for controlling the boiler. The boiler can be operated in a remote setpoint or a
remote firing rate control mode. Input 0-10VDC signal only. The temperature control must be programmed to run
with the analog input.
– LV19 and LV20 are used for connecting a MODBUS® building management system. (See the ENVI®
Control Advanced Users Guide for more information)
Cascade – LV21 and LV22 are used to connect between boilers that are part of a Master/Member Network. Up to
24 boilers may be connected together. (See the ENVI
®
Control Advanced Users Guide for more information)
3.5 I
NLET AIR AND EXHAUST VENTING
3.5.1 Applicable Codes & Standards
CODES
United States:
NFPA 54/ANSI Z223.1 National Fuel Gas Code
NFPA/ANSI 211 Chimneys, Fireplaces, Vents and Solid Fuel Burning Appliances
Canada
CAN/CSA B149.1 Installation Codes for Gas Burning Equipment
STANDARDS
UL 1738 Venting Systems for Gas-Burning Appliances, Categories II, III, and IV
These codes and standards contain information for the venting of gas fired appliances, including, but not limited to
vent sizing, location, clearance to combustibles, and safe installation practices. The installation must comply with
both the above Federal Codes and with state, provincial and local codes.
Design and installation of venting systems should be done only by qualified and
knowledgeable venting systems personnel and in accordance with vent system manufacturer’s installation
instructions. Installing a boiler or vent system using improper installation methods or materials can result in
serious injury or death due to fire or asphyxiation.
12
Before connecting a boiler to a venting system, it must be determined whether the
boiler is to be installed in a conventional or Direct Vent configuration. In the US, provisions for combustion and
ventilation air must be in accordance with NFPA 54/ANSI Z223.1, National Fuel Gas Code, latest edition, or
applicable provisions of the local building codes. In Canada, combustion and ventilation air openings shall
comply with CAN/CSA B-149.1 Natural Gas and Propane Installation Code.
For correct installation of vent system, read all of these instructions and refer to vent
manufacturer’s instructions.
Failure to use a proper vent system (types and materials), as described in this manual will void the boiler warranty and may result in rapid deterioration of the venting system, creating a health or life safety hazard.
Faulty vent installation can allow toxic fumes to be released into living areas. This may cause property damage, serious bodily injury or death.
3.5.1.1 Gas Vent Categories
Several codes and standards have categorized appliances in accordance with the flue gas temperature and pressure produced by the appliance. Categories are defined as follows:
Category I An appliance that operates with a non-positive vent static pressure and with a vent tempera-
ture that avoids excessive condensate production in the vent.
Category II An appliance that operates with a non-positive vent static pressure and with a vent tempera-
ture that may cause excessive condensate production in the vent.
Category III An appliance that operates with a positive vent static pressure and with a vent temperature
that avoids excessive condensate production in the vent.
Category IV An appliance that operates with a positive vent static pressure and with a vent temperature
that may cause excessive condensate production in the vent.
Direct Vent An appliance that is constructed and installed so that all air for combustion is derived directly
from outdoors and all flue gases are discharged to the outdoors.
3.5.1.2 Venting Materials for Flue/Exhaust Systems
®
MODU-FIRE
with a temperature that is likely to cause condensation in the vent. Therefore, any venting system used with the
MODU-FIRE
Forced Draft boilers are Category IV appliances, which vent with a positive exhaust pressure and
®
Forced Draft boiler must comply with the requirements for Category IV venting systems as speci-
fied in the latest edition of NFPA 54/ANSI Z223.1 in the US or the latest edition of CAN/CSA B-149.1 in Canada.
The venting materials listed below are intended for the venting of gas burning appliances only. Do not use these venting materials for venting liquid or solid fuel (such as oil, kerosene, wood or
coal) appliances.
Maintain clearances to combustibles as listed in the vent manufacturer’s installation instructions or as set forth
in the codes and standards listed in this section.
Do not use these vent pipes for incinerators of any sort.
3.5.2 Combustion Air
Combustion air must be free from dust, lint, etc. The presence of such materials in the air supplied to the burner
could cause nuisance "Low Air" shutdowns or premature burner failure. The boiler should not be operated during
construction while the possibility of drywall dust, demolition dust, etc. exists.
13
The combustion air supply must be completely free of chemical fumes which may be corrosive when burned in
the boiler. Common chemicals which must be avoided are fluorocarbons and other halogenated compounds,
most commonly present as refrigerants or solvents, such as freon, trichlorethylene, perchlorethylene, chlorine,
etc. These chemicals, when burned, form acids which quickly attack the boiler and the boiler stack. The result is
improper combustion and premature boiler failure.
Under no circumstances shall the boiler room ever be under a negative pressure.
Particular care should be taken when exhaust fans, compressors, air-handling units or other equipment may
rob air from the boiler. Note that this equipment might be in rooms other than the boiler room.
3.5.2.1 Air Inlet Requirements – United States (NFPA 54/ANSI Z223.1 & NFPA/ANSI 211)
When air is supplied from inside the building, the total required volume shall be the sum of the required volume for
all the appliances located in the mechanical room. Adjacent rooms furnished with fixed openings communicating
directly with the mechanical room are considered part of the required volume. The minimum volume is 50 ft
1000 Btu/hr (4.8 m
3
/kW) of installed appliance input capacity.
3
per
Openings used to connect indoor spaces to obtain the required minimum volume shall be sized as follows:
When rooms are on the same floor, each opening shall have an area equal to 1 square inch for each 1000
Btu/hr (2200 mm
2
/ kW) of installed appliance input capacity, but not less than 100 square inches. One opening should commence less than 12 inches above the floor and the other less than 12 inches below the ceiling.
The minimum dimension of air openings shall be 3 inches.
When rooms are on different floors, each opening shall have an area equal to 2 square inches for each 1000
Btu/hr (4400 mm
2
/ kW) of installed appliance input capacity.
When combustion air is supplied from outside the building, the boiler room shall be provided with one or two
openings to ensure adequate combustion air and proper ventilation.
When using one permanent opening, the opening shall commence within 12 inches of the ceiling and shall communicate directly with the outdoors or through a vertical or horizontal duct that communicates to the outdoors.
Minimum free area of the opening is 1 square inch for each 3000 Btu/hr (700 mm
2
/ kW) of installed appliance
input capacity, and
Not less than the sum of the areas of all vent connectors in the room.
When using two permanent openings, one opening shall commence within 12 inches above the floor and the other within 12 inches below the ceiling, preferably on opposite walls. The openings shall communicate directly, or
by way of ducts, with free outdoor air. The minimum net free area of the openings shall be calculated in accordance with the following:
When air is taken directly from outside the building, each opening (minimum of two, as outlined above), 1
square inch for each 4,000 Btu per hour (550 mm
When air is taken from the outdoors through a vertical duct into the mechanical room, 1 square inch per 4,000
Btu per hour (550 mm
When air is taken from the outdoors through a horizontal duct into the mechanical room, 1 square inch per
2,000 Btu per hour (1100 mm
2
/kW) of total boiler input is required.
2
/kW) of total boiler input is required.
2
/kW) of total boiler input is required.
14
NOTICE!
1. The required size of openings for combustion and ventilation air shall be based on the net free area of the
opening.
2. Screens shall be not smaller than ¼”
3. Motorized louvers shall be interlocked with the appliance so that they are proven open prior to main burner
ignition and operation.
Table of US Minimum area of ventilation openings per boiler (sq inches)
3.5.2.2 Air Inlet Requirements – Canada (CAN/CSA B149.1)
A. Ventilation of the space occupied by fuel burning appliance(s) or equipment shall be supplied by a ventilation
opening at the highest practicable point communicating with the outdoors. The total cross sectional area of
the ventilation opening must be either 10% of the net free area required for combustion air or 10 sq. in. (6500
2
), whichever is greater.
mm
B. Use the following opening calculation for MACH
®
condensing boilers or MODU-FIRE® Forced Draft boilers:
When combustion air is supplied for a forced draft burner by natural airflow from the outdoors and there is no
draft regulator or draft hood in the same space, there shall be a permanent opening with a cross sectional area not less than 1 sq. in/ 30,000 Btu/Hr (70 mm
2
/kW) of the total rated input to the burner(s). This opening
must not interfere with the ventilation air opening defined in paragraph A.
C. Use the following opening calculation for P-K THERMIFIC
®
boilers or other natural draft or fan-assist appli-
ances:
When combustion air is supplied for natural or fan-assisted burners by natural airflow from the outdoors, there
shall be a permanent opening with a cross sectional area not less than 1 sq. in/ 7000 Btu/Hr (321 mm
up to and including 1,000,000 Btu/Hr plus 1 sq. in. / 14,000 Btu/Hr (155 mm
2
/kW) in excess 1,000,000 Btu/Hr.
2
/kW)
This opening must be either located at or ducted to a point not more than 18 in. (450 mm) nor less than 6 in.
(150 mm) above floor level. This opening is in addition to the ventilation air opening defined in paragraph A.
D. When combustion air is supplied by natural airflow into a space containing both types of appliances described
in paragraphs B and C, the cross sectional area of the opening shall be not less than the sum of the cross
sectional areas for all appliances in the space as calculated by the applicable method . This opening is in addition to the ventilation air opening defined in paragraph A.
E. When a duct is used to meet the requirement for combustion air supply, as described in paragraphs A through
D, above, the opening of the duct shall be located so there is no possibility of cold air affecting steam or water
piping, electrical equipment or mechanical equipment.
F. When combustion air is supplied by mechanical means, an airflow-sensing device must be installed. It must
be wired into the pre-ignition limit string to prevent the burner from starting or to stop an operating burner in
case of air supply failure.
G. When all combustion air is supplied through a make-up air heater, and the appliance is interlocked to the
heater, the requirements of paragraphs A through F do not apply.
15
NOTICE!
1. The free area of a combustion air supply opening is calculated by deducting the blockage area of any fixed
louvers, grilles or screens from the total area of the opening.
2. Screens shall be not smaller than ¼”
3. Motorized louvers shall be interlocked with the appliance so that they are proven open prior to main burner
ignition and operation
Table of Canadian Minimum Area of Combustion and Ventilation Air Openings
MFD Required Combustion Air Opening Ventilation Air Opening
This boiler is not certified for use with Type "B" vent nor with any type of plastic venting.
This boiler is a Category IV appliance (condensing – positive pressure) as it is defined in ANSI Z21.13/CSA 4.9,
latest edition. The vent material must be as described in section 3.5.1.2. The exhaust vent can be run horizontally or vertically.
Vent installations shall be in accordance with NFPA54/ANSI Z223.1, the National Fuel Gas Code, or CAN/CSAB149.1, the Natural Gas and Propane Installation Code, or applicable provisions of the local building codes.
The vent must be sized in accordance with the ASHRAE Systems and Equipment handbook, Chapter 30 or according to the vent manufacturer’s recommendations. When using manufactured venting systems, consult your
vent supplier for correct sizing and structural support requirements.
Table of Vent Design Parameters
MFD Model
Frictional
Resistance
Stack
Temperature
CO
Natural Gas CO2 LP Gas
2
N2500/N3000 1.0” Max 300°F (gross) 8.5% 10.3%
The vent must be sized according to the vent manufacturer’s recommendations. Consult your vent supplier
for correct sizing and structural support requirements. Design calculations should be based on a positive
pressure at the flue collar, not to exceed 1.0 inch W.C. with a stack temperature of 300° F (gross) and a CO
2
level of 8.5% natural gas. The vent should be designed to provide positive pressure at the flue collar at all firing
rates.
NOTICE! Refer to example in section 3.5.5 regarding pressure drop across the boiler.
Do not use a barometric damper with this boiler. This is a positive pressure sys-
tem. Flue gases may leak into the room.
This equipment MUST NOT be used with a heat actuated automatic vent damper.
16
All boiler venting systems should be designed by a qualified venting professional experienced in venting system design. The information contained herein should be used as a guide only and is
not intended to be used in lieu of qualified technical expertise.
3.5.3.2 Required Clearances
Provide clearances between combustion air intake, exhaust vent, roof and wall surfaces, doors and window, and
snow line. Refer to Figure below: Termination Clearances – Forced Draft and Direct Vent Installations.
Do not locate intake or exhaust terminations directly above a walkway;
dripping of condensation can cause icing of the walking surface. Maintain a minimum clearance of 4
ft (1.22 m) horizontally from any electric or gas meter, regulator or relief equipment.
Conventional Vent Systems
The following termination clearance requirements are for conventional, non-direct vent installations.
The vent system shall terminate at least 3 ft above a forced air inlet that is within 10 feet horizontally.
The vent system shall terminate at least 4 ft below, 4 ft horizontally from or 1 ft above any door, operable win-
dow or gravity inlet into any building. The bottom of the vent terminal shall be at least 12 in. above grade or
highest expected snow line (if applicable).
Through the wall terminations shall not terminate over public walkways or over an area where condensate or
vapor could create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves or
other equipment.
Direct Vent (Sealed Combustion) Systems
The vent terminal shall be located at least 12 in. from any air opening into a building. The bottom of the vent
terminal shall be at least 12 in. above grade. Both the vent and air intake terminals must be at least 12 in.
above the highest expected snow line.
17
Through the wall terminations shall not terminate over public walkways or over an area where condensate or
vapor could create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves or
other equipment.
When multiple direct vent appliances are adjacent, the exhaust must terminate at least 10 feet horizontally or
three feet vertically from the air intake of another appliance.
Interior Component Installation Clearances
All vent system components shall be installed so as to maintain the following required minimum clearances:
Vent Type and Clearance Type Combustible Surface Non-Combustible Surface
UL 1738 listed Category IV vent Per manufacturer’s listing Per manufacturer’s listing
3.5.3.3 Flue Connection
The boiler vent should not be connected into any portion of another mechanical
draft system without consulting the vent manufacturer. This boiler operates under a positive vent pressure.
The boiler shall not be connected to any part of a vent system serving a Category I or II appliance, nor shall a
Category I or II appliance be connected to any part of the vent system serving this appliance. Improper interconnection of venting systems may result in leakage of flue gases into occupied spaces.
NOTICE! Make sure that the weight of the vent is not supported by the boiler vent collar. The collar is not
designed to support the weight of the vent. The vent system shall be supported in accordance with the
manufacturer’s instructions. Horizontal vent sections shall be supported in a manner to prevent sags or low
spots where condensate can collect. Structural supports must be connected to building elements of sufficient
strength to withstand the weight of the vent system and any bending forces imposed by the venting system.
This boiler has 10” OD connections for the vent. If venting design permits, this connection may be reduced to 8”
diameter. The connection from the boiler to the vent should be made using an adapter that is designed to fit the
OD of the boiler outlet. The vent manufacturer’s adapter must be sealed to the boiler outlet with sealant listed for
use with the vent material. The connection from the boiler to the vent should be as direct as possible and the
upward slope of any horizontal breaching should be at least ¼ inch per linear foot. Provisions must be made for
supports to prevent contact of the vent with combustible surfaces.
The complete exhaust with drain system is shown in the figures below. The appliance connector should
incorporate provisions to drain condensate formed in the vent system. The first turn from horizontal to vertical
should be made with either a standard tee with condensate drain cap or an elbow with an “inline” drain installed
immediately above the elbow. The condensate drain line from the boiler must be connected to the stack drain
upstream of the stack trap using a material that will withstand condensate corrosion and a maximum temperature
of 400°F. The stack trap shall have a minimum height of 4 inches. The condensate must be routed to a suitable
drain that complies with all local codes.
The boiler condensate drain line can get as hot as the stack. This may be up to
400ºF. This line should be insulated to prevent thermal injury or burns.
Do NOT use copper or plastic for the boiler condensate line, as these may fail and
allow exhaust gas to leak into the room.
18
Building
Sidewall
Pitch Towards Boiler
¼” per foot min
Boiler Outlet
10” OD
Boiler Condensate Drain
(stainless steel or silicone tubing)
The vent shall extend at least three (3) feet above the roof, or at least two (2) feet above the highest part of any
structure within ten (10) feet of the vent. This is illustrated in the following diagram. Additionally the boiler vent
shall terminate at least 3 ft above a forced air inlet located within 10 ft.
19
Reference: NFPA 54/ANSI Z223.1 National Fuel Gas Code
To prevent the possible re-circulation of flue gases, the vent designer must take into consideration such things as
prevailing winds, eddy zones, building configurations, etc. Harsco Industrial, Patterson-Kelley cannot be
responsible for the effects such adverse conditions may have on the operation of the boilers. Dimensions listed
above are minimums and may not be sufficient for conditions at a specific job site. It is important to locate the
exhaust duct in such a way that it does not become blocked due to snow, ice, and/or other natural or man-made
obstructions.
VERTICAL VENTING
Harsco Industrial, Patterson-Kelley does not recommend the use
of a vent cap. A screen termination is not recommended due to
the possibility of ice formation on the screen. Rain is actually
beneficial to the vent internals.
SIDEWALL VENTING – N2500 & N3000 MFD
Harsco Industrial, Patterson-Kelley requires a “T” or 90
degree elbow to be used on the termination end of
sidewall venting on these models. The venting connection
for this “T” or 90 degree elbow should extend a minimum
of 12” from the wall, in addition to other venting
The venting instructions in this manual apply to a single
boiler.
Venting systems for multiple boilers must be designed by experienced and knowledgeable professionals.
The venting system must prevent backflow of exhaust gas through idle boilers.
3.5.5 Sealed Combustion/Direct Vent Systems
The MODU-FIRE
ized venting system. Such a system employs a sealed combustion air intake duct leading from outdoors and a
sealed exhaust vent terminating outdoors. Air flow through the system is maintained by the combustion air fan.
Intake Duct Materials and Sizes
The air intake duct can be fabricated from PVC, CPVC, single wall galvanized steel, or other suitable materials.
The duct must be rigid enough to maintain the full required cross sectional area under all operating conditions.
Proper sealing of the intake ductwork is necessary to prevent infiltration of air from conditioned space. Joints in
PVC or CPVC must be cemented. For galvanized duct, wrap each joint and seam with adhesive aluminum tape
or other sealant. Connect the air supply duct to the inlet air collar on the boiler. Fasten the duct to the collar with
sheet metal screws and seal with aluminum tape or sealant. The installation of a birdscreen on the intake termination is recommended. Ensure that the screen does not become blocked with snow, ice, insects etc.
The combined pressure drop of the air supply duct and exhaust
vent must not exceed 1.0” w.c. This combined pressure drop can
be distributed over the intake or exhaust as needed provided that the
air inlet pressure loss does not exceed -0.5” w.c.
®
Forced Draft boilers are also certified for operation with a sealed combustion air and pressur-
Air Requirements – SCFM
MFD MODEL Required SCFM
N2500 583
20
N3000 700
3.5.6 Removing an Existing Boiler
When an existing boiler is removed from a common venting system, the common venting system is likely to be
too large for proper venting of the appliances remaining connected to it.
At the time of removal of an existing boiler, while the other appliances remaining connected to the common
venting system are not in operation, the following steps should be followed with each appliance remaining
connected to the common venting system placed in operation:
1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch and determine that there is no
blockage or restriction, leakage, corrosion or other deficiency which could cause an unsafe condition.
3. Insofar as is practical, close all building doors and windows and all doors between the space in which the
appliances remaining connected to the common venting system are located and other spaces of the building.
Turn on clothes dryers and any appliances not connected to the common venting system. Turn on any
exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not
operate a summer exhaust fan. Close fireplace dampers.
4. Place the appliance being inspected in operation. Follow the lighting instructions. Adjust the thermostat so
that the appliance will operate continuously.
5. Test for spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a
match or candle or smoke from a cigarette, cigar or pipe.
6. After it has been determined that each appliance remaining connected to the common venting system
properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and
any other gas-burning appliance to their previous conditions of use.
Any improper operation of the common venting system should be corrected so the installation conforms with the
National Fuel Gas Code, NFPA 54/ANSI Z223.1 and CAN/CSA B149.1 Installation Code. When resizing any
portion of the common venting system, the common vent system should be resized to approach the minimum size
as determined using the appropriate tables.
3.6 G
Before making the gas hook-up, make sure the boiler is being supplied with the type of fuel shown on the boiler
nameplate. The boiler must be installed such that the gas system components are protected from water
(dripping, spraying, rain, etc.) during appliance operation and service (circulator replacement, control
replacement, etc.)
The boiler is factory fire-tested and adjusted for proper combustion with a natural gas supply pressure of 8 inches
W.C. Typical supply gas pressure is 8 inches W.C. for natural gas. The gas train components are certified to
handle a maximum inlet pressure of 14 inches W.C. (1/2 psig.). If the available gas pressure exceeds 14 inches
W.C., a suitable additional intermediate gas pressure regulator of the “lock up” type must be provided to reduce
the pressure to less than 14 inches W.C.
resistant to the action of liquefied petroleum gases. Do not use Teflon tape on gas line threads.
NOTICE! Piping must be installed such that no piping stresses are transmitted to the boiler. The boiler shall
not be used as a pipe anchor.
AS PIPING
All threaded connections must be made using a pipe compound that is certified
The boiler and all gas piping connections should be pressure-tested and must be checked for leaks before being
placed into service. Test with compressed air or inert gas if possible.
21
The boiler must be disconnected at the boiler manual shutoff valve (located at the end of the supplied gas train)
from the gas supply piping system during any pressure testing of the system at pressures in excess of 1/2 psig
(14” W.C.).
During any pressure testing of the gas supply piping system at pressures equal to or less than 1/2 psig (14"
W.C.), the boiler should be isolated from the gas supply piping system by closing the manual shut-off.
Some leak test solutions, including soap and water, may cause corrosion. These solutions should be rinsed off
with water after testing.
Install a sediment trap (drip leg) and a union connection should be installed upstream of the primary manual
shutoff valve on the boiler. Gas piping should be installed in accordance with National Fuel Gas Code, NFPA
54/ANSI Z223.1, latest edition, and any other local codes which may apply. In Canada, please refer to CAN/CSAB149.1
Pipe Capacity for Natural Gas
NOTICE! See Pipe Capacity for Natural Gas chart for required pipe size, based on overall length of pipe from
meter plus equivalent length of all fittings. Approximate sizing may be based on 1 cubic foot of natural gas per
1,000 Btu per hour input, i.e., 3,000,000 Btu per hour requires about 3,000 cubic feet per hour.
Nominal
Iron Pipe
Size
(Inches)
Internal
Diameter
(Inches)
Equivalent Pipe
Length
90º Ell
(Feet)
Tee
(Feet)
Maximum Capacity in Cubic Feet of Natural Gas per Hour
Pressure Drop of 0.5 inch Water Column/Equivalent Length of
Forced Draft boiler would consist of a 20º F temperature differential across
the heat exchanger at high fire. Insufficient flow may result in excessive short cycling of the boiler and eventual
damage or premature failure of the equipment.
NOTICE! The closing of the flow switch does not prove that flow is adequate. It only indicates that some flow
is present. The proper water flow rate for the N2500 & N3000 MFD is 165-325 gpm.
Minimum Return Water
Temperature should be
20
18
greater than 130º F to avoid
problems of condensation
on the outside of the heat
16
14
12
10
8
exchanger or in the flue
passages.
Proper flow rates and
return water temperature
may be achieved through a
combination of primary and
6
Pressure Drop (ft of hea
4
2
0
150175200225250275300325
Flow (GPM)
secondary flow loops.
Multiple zones and pumps
may result in different flow
rates at different times.
Consideration must be
given to all possible
conditions and their
consequences.
3.7.1.2 Piping with Refrigeration Machines
When used with a refrigeration system, the boiler shall be installed so that chilled medium is piped in parallel with
the boiler. Valves should be installed to prevent chilled water from entering the boiler when the system is
operated in the cooling mode.
3.7.1.3 Piping with Air Handling Units
The boiler piping system of a hot water heating boiler connected to heating coils located in air handling units,
where they may be exposed to refrigerated air circulation, must be equipped with flow control valves or other
automatic means to prevent gravity circulation of the boiler water during the cooling cycle.
Schematic showing rear of boiler (for a more detailed view, see section 4.0)
Make water connections as the application warrants or, at a minimum, as shown, but always in compliance with
the local requirements.
Both boiler water connections are 3” pipe, class 150#, ANSI B16.5 flanges. These require a mating flange, bolts,
and a gasket (all field supplied).
NOTICE! Isolating valves must be installed in both water connections for ease of service.
As you are facing the rear of the boiler, the right side connection (with the relief valve on it) is the boiler OUTLET
and must be connected as the hot water supply to the system. The left connection is the boiler INLET
be used for the cold water return from the system.
Piping must be installed such that no piping stresses are transmitted to the boiler. The boiler shall not
as a pipe anchor.
3.7.3 Boiler Water Piping by Installer
3.7.3.1 Strainer
To avoid possible contamination of the boiler with dirt, rust or sediment from the system, a strainer near the boiler
inlet is strongly recommended. Even new systems may contain sufficient foreign material to eventually reduce
the performance of the heat exchanger. Adequate circulation of good clean wateris essential to maximum
efficiency and long life of the boiler.
Drain
and must
be used
24
3.7.3.2 Relief Valve and Piping
Each boiler is supplied with a pressure-relief valve sized in accordance with ASME requirements. The relief valve
must be piped to a suitable drain prior to placing the boiler into service and in a manner that prevents water spray
from contacting any person. Reducing couplings or other restrictions are not permitted in the discharge line.
Do not plug or obstruct the discharge of the relief valve.
3.7.3.3 Low Water Cut-off
The boiler is furnished with a flow-switch-type low water cut-off as required by the ASME BPV Code, Section IV.
No field piping is required. If the flow switch does not sense water flow, the boiler will shut down and a red
indicator will be illuminated on the control panel.
Installation of an external low water cutoff or manual reset low-water switch may be required by certain codes or
in certain installations. Consult your local code for details.
Never install a valve that can isolate the low water cut-off from the boiler.
3.7.3.4 Drain Valve and Piping
The boiler is provided with external drain connections. A drain valve is installed in the bottom of the boiler. Prior
to draining the boiler for maintenance or testing, electrical power and gas supply must be turned off to the boiler.
The boiler must then be isolated from the system at the supply and return connections prior to draining water from
the boiler.
NOTICE! This drain valve is installed for draining of the boiler water only, not the entire system. Draining of the
system through the boiler will result in depositing sediment from the system in the boiler which will result in poor
heat transfer characteristics of the boiler and early boiler failure.
Before filling the boiler, flush the system to remove the debris. Clean and flush old piping thoroughly before
installing the boiler as recommended by your water conditioning or chemical treatment supplier.
Under no circumstances should the hydronic system be flushed while the boiler is attached to the system since
the debris or corrosion products could accumulate in the boiler and plug the boiler heat exchanger.
If the piping system attached to this unit will be chemically cleaned, the boiler must be disconnected from the
system and a bypass installed so that the chemical cleaning solution does not circulate through the boiler.
3.7.4.2 Filling
To insure that no air is trapped during the filling process, open the pressure-relief valve located at the rear of the
boiler prior to filling the boiler. While filling, leave the relief valve open until a steady flow of water is observed.
Close the valve and finish filling the system.
3.7.5 Water Quality
The boiler is designed to operate in a closed-loop system using water or water/glycol only. As such, the system
should be tight and not require make-up water. A high percentage of untreated make-up water can cause
premature failure due to build up of scale. Such failure is not covered by warranty.
Scale can also reduce efficiency. For example, a scale thickness of 1/16 inch will result in a 12.5% loss of
efficiency.
25
Consult your water conditioning or chemical treatment supplier for analysis and recommendations. Employing a
conscientious and competently administered program with emphasis on good maintenance practices as outlined
by your water treatment specialist is recommended.
If water/glycol is to be used in the system, the customer should perform a hazard analysis to determine proper
use and disposal.
Inspect the burner to be sure nothing was damaged or knocked loose during shipment. Inspect the main gas train
and ignition assembly to be sure they were not damaged during shipment or installation. Inspect the ignition wire
and igniter to be sure they were not damaged nor cracked.
Check all gas unions for tightness.
3.9 P
RE-START CHECK LIST
Before attempting to start the boiler, make sure the following items have been completed.
1. Flue gas from the boiler is properly vented. (See section 3.5)
2. Gas connection has been made, pressure tested for leakage, and the line purged of air. (See section 3.6)
3. Water connections are complete, and the boiler and system have been filled and purged of air. (See section
3.7)
4. The boiler must be connected to a 240 volt / 60 Hz / 1 Ph power source with proper polarity, a dedicated
machinery ground, and provided with a disconnect having adequate overload protection. (See section 3.4)
5. Combustion air openings are not obstructed in any way and have adequate capacity. (See section 3.5)
6. The boiler is located with the proper clearances as shown in this manual. (See Section 3.3.3)
7. Relief valves have been properly piped to floor drains. (See section 3.7)
8. There are no flammable liquids, materials or hazardous fumes present in the environment.
9. Remove/account for all tools and parts.
10. All panels and parts should be properly installed.
3.10 S
AFETY CHECKS
The following checks of safety systems must be made before putting the boiler into normal operation.
Before firing the boiler refer to Sections 4.1 and 4.2 for information on the use of the controls, lighting, and shutdown procedures.
Never attempt to operate a boiler that has failed to pass all the safety checks
described below.
26
After checking controls by manual adjustment, make sure they are always reset to
their proper settings. Verify proper operation after servicing.
3.10.1 Test of Ignition Safety System
Test the ignition system safety shutoff as follows:
1. Remove the black plug/connector from the main gas valve (it is held on with a central screw).
2. With the main gas cock (inlet manual gas valve) open, the burner should be cycled on. After all the safety
limits such as gas pressure, water flow and temperature are satisfied, the blower will run and pre-purge the
boiler.
3. Once the purge is complete (30 seconds), the ignition transformer will be energized. There will be a 4 second
trial for ignition period. During this period the boiler is attempting to light.
4.
The main gas valve will not open because there is no power to the valve due to the disconnected wires.
Hence, no flame will be established and the flame safeguard will not receive a flame signal from the UV
scanner.
5. After 4 seconds, the flame safeguard programmer will recognize a “Flame Failure” condition and go to a
“lockout” mode. Lockout will require manual reset of the flame safeguard.
After completing this test, turn off the boiler and reconnect the wires to the main gas valve.
The boiler is furnished with a flow-switch-type low water cut-off in the outlet nozzle. Test as follows:
1. Turn boiler and then system pump off.
2. Turn boiler back on.
3. The red “Low Water” light should illuminate and the boiler should not start.
Perform appropriate tests on any external probe-type low water cut-off.
3.10.3 Test of Limit Controls
Fire the boiler and test the high limit control as follows:
With the main burner operating, turn down the temperature setting on the "high-limit" thermostat (located in the
control panel below the digital operating control) until the main burner shuts off. The high-limit switch must be
manually reset by pushing the small green lever. A similar check should also be made for the digital operating
temperature control (see Section 3.11 for instructions on setting this control). After completion of these tests, readjust the operating thermostat to the desired operating temperature and set high-limit temperature, typically 20º
F above operating temperature.
27
3.10.4 Test of Low Gas Pressure Switch
Manual Reset
Gas Pressure Switch
The boiler is furnished with a low gas pressure switch. This switch must be set at 5” w.c. The operation of this
switch must be checked by slowly closing the main gas cock while the burner is operating. The switch should
shut down the main burner.
3.10.5 Test of High Gas Pressure Switch
The boiler is furnished with a high gas pressure switch. The operation of this switch must be checked by closing
the downstream main gas cock, and starting the boiler. Once the trial for ignition period is reached, the main gas
valve will open, pressurizing the line. This will trip the high gas pressure switch.
The high gas pressure switch must be manually reset after it trips.
The MODU-FIRE® Forced Draft boiler is equipped with a combination combustion and temperature control. This
control monitors combustion and lighting of the boiler,
as well as maintaining temperature of the supply
water. The temperature control portion modulates the
boiler to maintain the desired outlet temperature
based on the selected operating configuration.
3.11.1 Initial Adjustments
®
The ENVI
control uses a Liquid Crystal Display
(LCD) as a method of supplying information. The
LCD is used to setup and monitor system operation
by means of six push buttons RESET, MENU, BACK,
ENTER, UP & DOWN (Scroll, ▲,▼). Scroll advances
the display, while ▲,▼are used in the adjust menu.
The lighted window in the center is a four line LCD
that shows boiler operating information on various
screens. These screens are shown below with an introduction to the control operating features. For additional
information, the ENVI
®
control manuals may be obtained from the Harsco Industrial, Patterson-Kelley factory.
3.11.1.1 Operation of the control
The home page is the default screen that is shown upon startup. This screen shows the date, time, boiler status,
supply temperature and setpoint temperature.
The buttons across the bottom are used to navigate through the various screens. Pushing the MENU button
displays a menu of options.
28
Menu
Menu
Standby
Standby
Information
Information
Errors
Errors
3.11.1.2 Configuring the Control
First push the MENU button and then select PROGRAM PARAMETERS from the menu. A screen opens that
allows the user to view and change various operating parameters.
Parameters
Parameters
CH settings
CH settings
DHW settings
DHW settings
Boiler settings
Boiler settings
CH settings
CH settings
CH set ti ngs
Setpoint 180°F
Setpoint 180°F
Setpoin t 180°F
BLR OP 1
BLR OP 1
BLR OP 1
CH mode0
CH mode0
CH mode 0
The menu includes access to the STANDBY, INFORMATION,
ERRORS, PROGRAM PARAMETERS, CONFIGURATION,
CASCADE, and SERVICE menus. The UP and DOWN buttons
are used to position the arrow next to the desired option and the
ENTER button is pushed to access that option.
Select the CH SETTINGS to adjust parameters related to the
boilers Comfort Heat function.
For example, selecting the SETPOINT parameter opens up a
screen that allows the setpoint to be changed.
Other parameters are available and may be changed by contacting the factory for assistance. The ENVI
Getting Started Guide contains additional information regarding the operation of this control.
NOTICE! Changing parameters requires an understanding of the parameters and the functionality of the boiler.
The boiler may not function properly if parameters are changed from the factory values.
3.12 C
There is no required start-up or field adjustments for air flow control. The air flow is set at the factory.
3.12.1 Fuel/Air Ratio Adjustment
The fuel/air ratio is controlled by the automatic air gas ratio valve. This valve is adjusted at the factory to give 5.8-
6.5 % O2 at high fire and 7.0-7.5% O2 at low fire in the exhaust gas. However, the fuel/air ratio should be
OMBUSTION ADJUSTMENT
The UP or DOWN buttons are used to adjust the CH setpoint up
or down as desired.
®
Control
29
checked using a combustion analyzer at start-up to verify that the combustion is proper. Remove the exhaust
vent plug and place the analyzer probe in the exhaust as shown. Be sure to replace the plug after combustion
has been set.
Start the boiler. Using the control panel, access the SERVICE menu. The service menu allows the operator to
manually set the boiler to HI or LOW operation for setup and/or troubleshooting. Pressing the SVC shortcut key
(DOWN button when the default screen is present) accesses the SERVICE menu. Users can also access the
SERVICE menu by pressing the MENU button and using the UP and DOWN buttons until the cursor is next to
SERVICE. Press ENTER.
The first test mode allows the service technician to hold the boiler in high or low fire during operation so that the
combustion adjustment can be performed. Press the UP or DOWN button to select BURNER ON or BURNER
OFF, press ENTER. Then press the UP button followed by ENTER to select HIGH or DOWN followed by ENTER
to select LOW operation.
The second test mode checks the fan rate with the burner off at high speed or at low speed.
These test modes will automatically terminate after 15 minutes of inactivity or can be terminated from the
control/display panel by pressing the cancel/reset button
If the % O
hi fire, turn the bottom screw “V” counterclockwise to reduce the % O
Once high fire is adjusted, place the boiler in low fire using the control panel and adjust the % O
turning the top screw “N” counterclockwise to reduce the % O
NOTICE! For High altitude adjustments contact Harsco Industrial, Patterson-Kelley Technical service for
Service Bulletin No. 05-08.
is not within the range above at high fire, the gas valve should be adjusted. To adjust the gas valve on
part has been under water. Immediately call factory-trained personnel to inspect the boiler and replace any part
of the control system and any gas control which has been exposed to water.
Pop-Latch (2)
On/Off Switch
The front of the control panel shows Operating
Instructions and the control interface for the boiler. The
boiler operating controls are accessed by turning the
pop-latches ¼ turn, and opening the front cover.
4.1.1 Normal Operation
Under normal operating circumstances, this boiler
functions as a fully automatic appliance. The automatic
control senses the water outlet temperature and fires
the boiler when heat is needed by the system.
Additionally this boiler may function as part of an
integrated building management system.
4.2 L
IGHTING AND SHUT-DOWN PROCEDURES
Do not use this boiler if any
4.2.1 Initial Lighting Procedures
1. Utilities: Turn on electrical supply to the boiler. The blower will purge
briefly as the system controls get power. Open the manual gas supply
valves. Make sure the system is filled with water and turn on the
circulation pump.
2. Reset Switches: Press the reset button on both the high gas and low gas
pressure switches if the gas supply had previously been turned off. Press
the control reset button after a safety lockout.
3. Turn on the power switch. The blower will purge briefly as the electronic
controls energize. If the boiler control shows a warning or lockout
annunciation, see Section 5.6 of this manual to troubleshoot the problem
and take the necessary corrective action before proceeding.
4. Set the desired high temperature limit and operating temperature.
5. The lighting and operation of this boiler is fully automatic.
4.2.2 Normal Shut Off Procedures
1. Place the on/off switch in the off position.
2. Close all manual gas valves.
3. Turn off electrical power.
4.2.3 Emergency Shut Off Procedures
The main gas cock should be closed immediately. If overheating occurs or the
gas supply fails to shut off, do not turn off or disconnect the electrical supply to
the pump. Instead, shut off the gas supply at a location external to the boiler.
All weekly, monthly and annual maintenance checks should be performed by experienced and
knowledgeable personnel.
Installation and service must be performed by an experienced and knowledgeable
individual, such as a Harsco Industrial, Patterson-Kelley representative, qualified installer, service agency or
gas supplier.
Proper lockout /tagout procedures must be employed when servicing this unit.
A hazard analysis should be performed by the end user to insure the safety of their employees and/or service
technicians.
5.1 M
cause improper and dangerous operation.
Verify proper operation after servicing.
AINTENANC E AND INSPECTION SCHEDULE
Label all wires prior to disconnection when servicing controls. Wiring errors can
5.1.1 Daily
Observe operating temperature and general conditions. Make sure that the flow of combustion and ventilating air
to the boiler is not obstructed. Determine the cause of any illuminated red indicators, unusual noises or operating
conditions and make the necessary corrections.
Check daily to be sure that the boiler area is free and clear of any combustible
materials, including flammable vapors and liquids.
5.1.2 Weekly
Observe the conditions of the main flame. A normal high fire flame shows an orange screen with a blue halo. In
Low fire the burner should display a reddish orange glow. However, do not attempt to adjust the flame “by eye”.
Correct air adjustment is essential for the efficient operation of this boiler. If an adjustment to the combustion is
necessary, the flue gas composition should be checked with a carbon dioxide (CO
set conditions. Refer to Section 3.12.
5.1.3 Monthly
1. Using the control panel, enter the information mode and scroll down to view the flame signal. When the boiler
is firing, the signal will be “yes” and when the boiler is not firing, the signal will be “no”.
2. Test high-limit control by reducing setting below the operating temperature. Burner should shut off. After
readjusting the thermostat, press the button to reset the switch.
3. Test operating temperature control by reducing temperature setting as necessary to check burner operation.
4. Check flue gas temperature at outlet. If there is a temperature increase over previous readings, the probable
cause is soot or water-scale build- up on the tubes.
) or oxygen (O2) analyzer to
2
33
5. Test the water flow switch by trying to restart boiler with the system pump off. The boiler should not operate
and the control should display LOW FLOW/ILK.
6. Test low gas pressure switch and high gas pressure switch utilizing the procedure in sections 3.11.4 & 3.11.5.
The boiler should fail to start and the control should display LOW GAS or HIGH GAS.
7. Inspect and clean the inlet screen of any accumulated dust or lint.
8. The relief valve should be tested as per manufacturer’s instructions or every two months by lifting the lever for
5 seconds and allowing the valve to snap shut. Please see the manufacturer’s recommendations on the relief
valve tag.
5.1.4 Annually
In addition to the recommended monthly service:
1. Check burner and wash off (do not scrub or use wire brush) any soot or foreign material that may have
accumulated. See Section 5.2 on "Cleaning the Burner." Check the burner and its parts. If there is evidence
of deterioration or corrosion, replace immediately.
2. Inspect combustion chamber. To access the heat exchanger, remove the front door and the front inner
wrapper. Note any signs of deterioration. Examine the gasket and replace if necessary, using a Harsco
Industrial, Patterson-Kelley gasket kit only.
3. Inspect and clean heat exchanger. Wash the copper tubes with water and non corrosive soap. Green scale
on the tubes indicates that the boiler is condensing which is detrimental to boiler life. Perform corrective action
as necessary.
a. Check all joints and pipe connections for tightness.
b. Check vent for corrosion or deterioration. If any venting needs replacing, do so immediately.
5. Inspect heating system for other problems.
6. Perform combustion analysis and adjust if necessary (See 3.14.1).
7. Leak test gas valves. Leak Test must be performed only by qualified Harsco Industrial, Patterson-Kelley
certified personnel, who have been trained in this procedure. This procedure is available on request from the
Harsco Industrial, Patterson-Kelley Factory.
8. Perform a safety relief valve test.
34
5.2 CLEANING THE BURNER
Blower
Follow proper lockout / tagout procedures for the electrical, gas, and water
connections. Use caution when lifting heavy parts.
2. Remove the U-bolt on the gas valve, the back panel
flange over the gas pipe, and the 4 screws from the top
gas valve flange.
3. Disconnect the two wire plugs on the blower, the UV
scanner, ignition wire, ground wire and the wires to the
back pressure switch.
4. Disconnect the air gas mixer sensing tubes. NOTICE!
These tubes are color coded and must be correctly
reinstalled.
5. Remove the air/gas mixer assembly (green) and the
gasket from the blower while leaving the piping attached.
Lift the assembled air/gas mixer and piping out of the
boiler and place it on the rear boiler water piping. Do not
disconnect the wires to the gas pressure switch.
6. Remove the blower and gasket from the boiler. Clean
the blower vanes. Do not disassemble the blower motor
or aluminum housing.
7. CAREFULLY remove the ignition assembly from the
boiler. Check the gap between the electrode and the
ground rod. It should be 1/8” (+1/16, -0). The electrode
should angle in towards the burner. Check for cracking
of the electrode. Do NOT over-tighten the electrode
High Exhaust
Back Pressure Switch
UV
Detector
Ignition
Electrode
Spark Gap
=1/8”
0” , +1/16”
8. Leaving the burner hood attached to the mounting plate,
CAREFULLY remove the burner assembly using the six
large hold down nuts. This assembly is top heavy.
Ignition Assembly
35
9. Check the gray grafoil gaskets around the burner flange for cracking. Replace if necessary. Replace the
red silicone gasket on the heat exchanger head.
10. Clean the burner to remove any soot or foreign material that may have accumulated. Blow the burner with
compressed air or wash off (do not scrub or use wire brush).
11. Use a soft, clean cloth to remove accumulated contaminants from the UV detector/scanner glass
envelope.
12. Before re-installing the burner, check the cleanliness of the heat exchanger and the condition of the
combustion chamber. If corrosion or leaks are noticed, please call for service.
13. Re-install components in the reverse order of removal. Be sure to reinstall all gaskets, O-rings and
electrical connections. Be sure the gas valve flange and O-ring is assembled correctly to prevent gas
leaks.
14. Reinstall all covers.
15. Fire Test the boiler and use a combustion analyzer to ensure that the fuel/air ratio is set correctly. If
Heat Exchanger is heavy and may cause injury if improperly handled. Removal of the
heat exchanger should be performed only by knowledgeable and experienced personnel.
5.4 A
FTER ALL REPAIRS OR MAINTENANCE
1. Follow "Pre-Start Check List" (Section 3.10) and all "Safety Checks" (Section 3.11) and verify proper
operation.
2. Fire the Boiler and perform combustion check.
3. Adjust gas flow if necessary. (See "Gas Pressure Adjustment", Section 3.14.1)
5.5 S
EQUENCE OF OPERATION
1. In order for the boiler to start, the following limits must be satisfied:
a) Water flow switch
b) High & low gas pressure switches
c) High temperature limit
d) High back pressure switch
e) High stack temperature switch
2. When the Boiler On/Off switch is turned on, power is provided through a circuit breaker to the boiler control
and the combustion blower.
3. If the high gas, low gas or low water level control is open, the boiler control locks out and displays an error.
4. When the water temperature is below the boiler control setpoint minus the hysteresis (On Differential), a heat
request is generated.
5. Provided all limits are made, the boiler will attempt to start.
36
6. The controller checks that the air pressure switch is open indicating no airflow. The blower is driven towards
the prestart fan speed. When the air pressure switch closes, the 25 second pre-purge time is started. After
the pre-purge, the blower is driven to the ignition speed.
7. A trial for ignition begins. The sequence of events is illustrated graphically below.
8. After ignition, the fan may be driven to low fire before the boiler is released to modulation.
9. The control modulates the firing rate between low and high fire to maintain the desired outlet water
temperature.
10. The burner will continue firing until the outlet water temperature reaches set point plus hysteresis (Off
Differential). At this temperature the fuel supply is shut off and the combustion air fan continues to run for a
30 second post-purge.
11. When the water temperature is reduced by the load on the system, a heat request is generated. The
operating sequence will recycle to step 4.
NOTICE! Once the boiler begins the ignition sequence, the firing sequence will continue until main flame is
reached regardless of heat request. The sequence can be interrupted by turning the power switch off.
5.6 T
correcting the cause. (Manual Reset Limits include: Flame safeguard, high or low gas pressure, high
temperature limit, stack temperature.)
5.6.1 Loss of Power
In the event of loss of power, the entire boiler system is de-energized, closing all automatic valves and halting all
boiler operations. When power is restored the sequence of operation will resume at Step 3, provided that all the
limits are satisfied.
5.6.2 Loss of Water Flow
When there is insufficient water flow to close the flow switch, the burner operation is interrupted and the control
displays LOW FLOW / ILK. When water flow is re-established, the sequence returns to Step 3, provided that the
other limits are satisfied. This error also indicates that the interlock jumper is removed or the interlock is wired to
an open device.
ROUBLESHOOTING
If any “Manual Reset” limit device trips, DO NOT RESET without determining and
*
*
Flame Detection
Flame Detection
Flame must be detected at T = 6 seconds
Flame must be detected at T = 6 seconds
*
*
37
5.6.3 Low Gas Pressure
The low gas pressure switch opens when there is insufficient gas pressure available for proper operation of the
boiler. LOW GAS PRESSURE is displayed, and burner operation is interrupted. If a gas-supply shut-off valve is
closed for any reason, a low gas condition will result. When gas pressure is restored, LOW GAS PRESSURE will
remain on the display panel. A manual reset is required to restart the boiler, provided that all other limits are
satisfied.
5.6.4 High Gas Pressure
The high gas pressure switch opens when there is excessive manifold gas pressure for the proper operation of
the boiler. HIGH GAS PRESSURE is displayed and the burner operation is interrupted. When proper gas
manifold pressure is restored, HIGH GAS PRESSURE remains on the display panel. A manual reset is required
to restart the boiler, provided that all other limits are satisfied.
5.6.5 High Water Temperature
When the boiler water has exceeded both the operating and high-limit temperature the high limit switch opens,
and HIGH LIMIT is shown on the display. When the water temperature falls below the high-limit temperature, the
boiler will remain locked out until the water high limit switch is manually reset and the front panel reset button is
pressed. Once the switch and the control are reset, the sequence returns to Step 3 to await heat demand
provided that the other limits are satisfied.
5.6.6 Low Air
The air switch has been factory set and should not be adjusted in the field.
If the display panel indicates AIR SWITCH NOT OPEN or AIR SWITCH NOT CLOSE this indicates improper airflow through the boiler. Check the hoses leading to the air switches. Verify proper blower operation. An air switch
error does not necessarily mean that the air switch is defective.
When AIR SWITCH NOT OPEN is shown on the display, check that the air switch is open when the fan is off.
Check that there is no air flow through the boiler when the fan is off.
When AIR SWITCH NOT CLOSE is shown on the display, check that the air switch is closed when the fan is
running. If the air switch does not close within 5 minutes during purge, the boiler locks out. Check that the burner
is clean and that there are no obstructions to airflow in the intake or exhaust ducts.
5.6.7 Vent Pressure
BLOCKED FLUE indicates that the high exhaust back pressure switch has tripped. This may be caused by a
blocked stack, a blocked air inlet, or a blocked condensate system. When the blockage is removed, the boiler will
automatically restart.
5.6.8 Ignition Failure
In the event the flame is not detected by the UV scanner during the 4 second trial-for-ignition period (Step 9), the
gas valve and spark ignition are de-energized. At this time a safety lockout occurs. A manual reset of the
programmer (located inside the control panel) is required.
5.6.9 Flame Failure
In the event of a flame failure, the main fuel valves are de-energized and a manual reset lockout occurs. IGNITION ERROR or FLAME ERROR is shown on the display. The cause of flame failure must be diagnosed and repaired before the control is reset.
When IGNITION ERROR is shown on the display, the boiler has not lit during a trial for ignition. Check that the
spark, electrode, ignition wire, and gas valve are functioning properly.
When FLAME ERROR is shown on the display, the boiler has lost the flame during run. Check that the combustion is setup properly, the gas pressure is correct, as well as other combustion parameters.
38
5.6.10 Flame Error
LATE FLAME
EARLY FLAME
FALSE FLAME
These errors signify flame error. This may be caused by a failed or leaky gas valve or a flame detector malfunction. If gas valve leakage is suspected, the unit must be isolated by turning off the main gas supply line. Qualified
and knowledgeable service personnel must be called to evaluate and repair/replace the failed parts.
A comprehensive listing of the locking and blocking error codes is provided below.
NOTICE! When an Internal Software Error occurs, the failure is internal to the ENVI
placement of the ENVI® control is required. A qualified service technician must replace the ENVI® control.
IGNIT ERROR
TOO MANY FLAME FAILURES
T MAX LOCK ERROR
GV RELAY ERROR
SAFTEY RELAY ERROR
RAM ERROR
FLAG BYTE INTEGRITY ERROR
AD HI CPL ERROR
AD LO CPL ERROR
REGISTER ERROR
E2PROM ERROR
WRONG EEPROM SIGNATURE
STATE ERROR
ROM ERROR
15MS XRL ERROR
20 MS XLR ERROR
STACK ERROR
FLAME OUT TOO LATE ERROR
FLAME ERROR I
HIGH GAS PRESSURE ERROR
LOW GAS PRESSURE ERROR
41MS ERROR
FAN ERROR
AIR PRESS SW NOT OPEN ERROR
AIR PRESS SW NOT CLOSED ER-
ROR
UV SENSOR BROKEN
MOD BACK DIFF ERROR
RAPID RISE ERROR LOCK RET
RAPID RISE ERROR LOCK FLOW
RAPID RISE ERROR LOCK HX
LOW WATER CUTOFF ERROR
1 Three unsuccessful ignition attempts in a row
24 Three times flame was lost during on demand
18 Overheat stat is open
5
6
9 Internal software error
27 Internal software error
28 Internal software error
29 Internal software error
33 Internal software error
12 No communication with E2prom
10 Contents of Eprom is not up-to-date
13 Internal software error
14 Internal software error
16 Internal software error
22 Internal software error
19 Internal software error
20 Flame still present 10 sec. after closing the gas valve
21 Flame detected just before gas valve opened
32 Gas pressure is to high
31 Gas pressure is to low
23 Internal software issue
8
25 Air pressure switch doesn’t open within 30 seconds
26 Air pressure switch doesn’t close within 30 seconds
11 UV scanner not functioning
4 Large difference between return and flow temperatures
15 Return temperature rise too rapidly
7 Flow temperature rise to rapidly
17 Heat exchanger rise to rapidly
30 Water pressure is to low
34
Problems with gas valve relay= internal hardware error
(pump not running)
Problems with gas valve relay = internal hardware error
(pump not running)
Fan deviation more than300 rpm longer than 1 minute
(when fan speed > 4200 rpm this error is ignored)
Ionization (flame rod)wire lost for more than 15 seconds
T FLOW OPEN
T RETURN OPEN
T FLUE OPEN
T DHW OPEN
T HX OPEN
HEADER SENSOR OPEN
T FLOW SHORTED
T RETURN SHORTED
T FLUE SHORTED
T DHW SHORTED
T HX SHORTED
HEADER SENSOR SHORTED
PHASE ERROR
E2PROM READ ERROR
FLAME ERROR 2
LOW FLOW/ILK
WD 50HZ ERROR
NET FREQ ERROR
FAULTY EARTH ERROR
FLUE GAS ERROR
RETURN TEMP ERROR
BLOCKED FLUE ERROR
REVERSE FLOW ERROR
WD COMMUNICATION ERROR
FLAME CKT FAULT
REFHI TOO LO ERROR
REFHI TOO HI ERROR
REFLO TOO LO ERROR
REFLO TOO HI ERROR
RAPID RISE HX ERROR BLOCK
RAPID RISE ERROR BLOCK
RESET BUTTON ERROR
APPLIANCE SELECTION ERROR
IF COMMUNICATION FAILURE
53 Flow sensor not connected
54 Return sensor not connected
59 Flue sensor not connected
57 DHW sensor not connected
58 Heat exchanger sensor not connected
70 Header sensor on IF board not connected
61 Flow sensor shorted
62 Return sensor shorted
67 Flue sensor shorted
65 DHW sensor shorted
66 Heat exchanger sensor shorted
71 Header sensor on IF board shorted
46 Phase and neutral of supply voltage mains are reversed
0 Problems from reading from or writing to E2prom
74 False flame detected
73 Low flow or interlock error
45 No earth ground connected or internal hardware error
47
48 Faulty earth ground to boiler
39 Flue gas sensor is above setpoint plus differential
42 Return temperature is above 90 degrees
41 Flue gas outlet is restricted or blocked
43 Supply and return temp are reversed
49 Internal hardware error
40 Ionization or flame rod wire is lost
35 Internal hardware error
36
37
38 Internal hardware error
51 Heat exchanger temperature rise to rapidly (blocking)
72 Flow temperature rise too rapidly (blocking)
68 Reset button pressed more than 7 times within 1 minute
50 Appliance and resistor do not match at start up
69 No communication with interface board
Description
Main supply voltage frequency differs more than 2%
from 60HZ
Spare parts and replacement parts can be ordered from your local representative or Harsco Industrial, PattersonKelley by calling (877) 728-5351. The fax number is (570) 476-7247. Refer to the parts list shown on the
assembly drawing provided with this manual. Factory direct replacement parts must be used to ensure that the
boiler operates correctly.
Use of Non-Factory-Authorized replacement parts are not recommended for this
equipment. All control components are engineered for safety and are designed to work in unison with each of
the other components. Use of non-factory-authorized replacement parts would jeopardize the functionality of
the safety features as well as the performance of the boiler.
Technical information is also available at the above number or at the Harsco Industrial, Patterson-Kelley website
www.harscopk.com
your boiler available.
6.1 S
Typical schem atic drawings are shown on the following pages. Drawings specific to your particular
boiler can be supplied by your local Harsco Industrial, Patterson-Kelley representative.
CHEMATIC DIAGRAMS
. When ordering replacement parts please have the model number and serial number of
42
6.1.1 High Voltage Terminal Block Assignments (HV)
Terminal
Number
9 DHW Stat or Sensor Domestic Hot Water Thermostat (contact closure) or
10
11 Header Temp Sensor
12
13 DHW Flow Switch
14
15 0-10V Analog Input 0-10VDC Remote Control Input
16 0V Analog Input 0VDC Remote Control Common
17 For Future Use
18 For Future Use
19 MODBUS® COM 1A
20 MODBUS® COM 1B
21 CASCADE A TO A
22 CASCADE B TO B
Subject to the terms and conditions herein, Harsco Industrial, Patterson-Kelley, Seller warrants to the original owner at the
original installation site that products manufactured by Seller will be free from defects in materials and workmanship for a period of one (1) years from date of start up (the "Warranty Period"), provided that startup is completed within six months from the
date of shipment. The heat exchanger and burner will be warranted for a period of five (5) years from the date of shipment
(the “Warranty Period”).
REMEDY
The sole remedy of this warranty is expressly limited to the repair or replacement of any part found to be defective under conditions of normal use within the Warranty Period. Installation is not included.
WARRANTY
The owner must notify the original installer of the Product and Seller (Attention: Harsco Industrial, Patterson-Kelley, 100
Burson Street, East Stroudsburg, PA 18301), in writing, within the Warranty Period, providing a detailed description of all
claimed defects. Transportation to the factory or other designated facility for repairs of any products or items alleged defective
shall, in all events, be the responsibility and at the cost of the owner.
EXCLUSIONS
Seller shall have no liability for and this warranty does not cover:
A. Incidental, special or consequential damages, such as loss of the use of products, facilities or production, inconvenience,
loss of time or labor expense involved in repairing or replacing the alleged defective Product.
B. The performance of any Product under conditions varying materially from those under which such Product is usually test-
ed under industry standards at of the time of shipment.
C. Any damage to the Product due to abrasion, erosion, corrosion, deterioration, abnormal temperatures or the influence of
foreign matter or energy.
D. The design or operation of owner's plant or equipment or of any facility or system of which any Product may be made a
part.
E. The suitability of any Product for any particular application.
F. Any failure resulting from misuse, modification not authorized by Seller in writing, improper installation or lack of or im-
proper maintenance.
G. Equipment furnished by the owner, either mounted or unmounted, or when contracted for by the owner to be installed or
handled.
H. Leakage or other malfunction caused by:
1. Defective installations in general and specifically, any installation which is made:
a. in violation of applicable state or local plumbing housing or building codes,
b. contrary to the written instructions furnished with the unit
2. Adverse local conditions in general and, specifically, sediment or lime precipitation in the tubes and/or headers or corrosive elements in the atmosphere.
3. Misuse in general and, specifically, operation and maintenance contrary to the written instructions furnished with the
unit, disconnection, alteration or addition of components or apparatus, not approved by Seller, operation with fuels or
settings other than those set forth on the rating plate or accidental or exterior damage.
I. Production of noise, odors, discoloration or rusty water.
J. Damage to surrounding area or property caused by leakage or malfunction.
K. Costs associated with the replacement and/or repair of the unit including: any freight, shipping or delivery charges, any
removal, installation or reinstallation charges, any material and/or permits required for installation, reinstallation or repair,
charges to return the boiler and or components. Seller's liability under this warranty shall not in any case exceed the
amount paid for the Product found to be defective.
THIRD PARTY WARRANTIES
For goods or components not manufactured by Seller, the warranty obligations of Seller shall, in all respects, conform and be
limited to one (1) year from the date of shipment.
SEVERABILITY
To the extent that any provision of this warranty would be void or prohibited under applicable law, such provisions shall be
limited in effect to the minimum extent necessary to render the remaining provisions hereof enforceable.
NO OTHER WARRANTIES
Seller makes no implied warranty of merchantability or fitness for a particular purpose or other warranties with respect to any
products or services except as expressly set forth in this limited warranty.
1. Factory Fire-Test: (copy from boiler label)2. Sealed Combustion:YES orNO
Inlet Gas "w.c."w.c.2b. Approximate Elevation:Ft.
Oxygen (O2)%%3. Water Inlet Temperature: ° F
Carbon Dioxide (CO2) %%4. Water Outlet Temperature:° F
Carbon Monoxide (CO) ppmppm
Stack Temperature ° F° F5a. Glycol ?YESo
Main Flame Signal Yes/No Yes/No 6. Operating Temperature Setpoint:° F
Inlet AirTemperature° F° F
Start-Up Field Test: DATE:9. Stack Pressure (measured where stack exits boiler):
"w.c."w.c."w.c. (Low)
Inlet Gas
Oxygen (O2)%%10. Electrical Supply Power: L1 to L2Volts
Carbon Dioxide (CO2) %% L1 to N Volts
Carbon Monoxide (CO) ppmppmLess than 1 volt between neutral and ground: YES or NO
Stack Temperature (net)° F° F11. Total Cycles:
Main Flame Signal Yes/No Yes/No 12. Total Hours:
Inlet Air Temperature
14. Condensate drain from boiler connected to stack drain with Stainless Steel or High-Temp (500
Performed by:
dditional Comments:
State: Zip:Phone:
HighLow2a. Combustion Air Temperature: ° F
HighLow"w.c. (High)
° F° F13. Any Faults? Describe with
®
FORCED DRAFT BOILER
START-UP REPORT
Type of Installation:
ddress:
Contact:
Date:
5. Water Flow:
(from internal OR external control)
7. Gas Valve a. Low Fire Setting (N)
8. Approximate Stack Lengths:
code, time and description:
o
F) Silicon piping or tubing, and then trapped: YES or NO
b. High Fire Setting (V)
Ft. Horizontal
Ft. Vertical
Flue Pipe Diamete
gpm
NO
Please return a copy to Harsco Industrial, Patterson-Kelley, ATTN: Boiler Technical Service
Harsco Industrial, Patterson-Kelley 100 Burson Street · E. Stroudsburg, PA 18301
Phone: (570) 476-7261 Fax: (570) 476-7247 www.harscopk.com