Harris RF Communications Division RF-7800B-DU024, RF-7800B-VU104 User Manual

RF-7800B
R
NOTE
SCHEDULED MAINTENANCE
CHAPTER 5
SCHEDULED MAINTENANCE
5.1 PREVENTIVE MAINTENANCE
Table 5-1 contains the checks and services that should either be performed on a daily basis when the equipment is
in use or on a weekly basis when the equipment is in a standby condition. Tab le 5-2 contains the checks and services that should be performed on a weekly basis.
Table 5-1. Daily Preventive Maintenance Checks and Services
Check No. Item to be Inspected Procedure
1 Completeness Check to see that the equipment is complete.
2 Exterior Surfaces Remove dust, dirt, and moisture from all surfaces. Only use a soft
damp cloth to clean the Broadband Global Area Network (BGAN) Terminal.
3 Operation Verify connection to BGAN terminal web interface.
4 Installation Check hardware for looseness. Make sure unit is secure.
5 RF-7800B-VU104 drain
holes
There are four separate drain holes on the bottom of the RF-7800B­VU104 that will allow condensation and moisture out of the antenna to prevent any corrosion. Turn the screws clockwise to Open and counterclockwise to Close.
Table 5-2. Weekly Preventive Maintenance Checks and Services
Check No. Item to be Inspected Procedure
1 Connectors Check all connectors for debris, damage, or corrosion. Elevate to
a higher level of maintenance, if required.
2 Antenna Check for breaks or strains; repair or replace as required.
3 Cables Check for cracks or cuts; repair or replace as required.
To avoid impaired BGAN terminal performance, make sure the antenna is not damaged or the surface is not covered with foreign material like paint of labeling.
5.2 CORRECTIVE MAINTENANCE
Shortcomings and defects which are revealed when the BGAN terminal is in service must be attended to by means of corrective maintenance. The type of work required determines if the corrective maintenance procedure can be performed by the operator, or if it must be performed at a maintenance facility.
5-1
RF-7800B
R
SCHEDULED MAINTENANCE
The following procedures assume that the operator has determined that the BGAN terminal is faulty. This could be determined in three ways:
The self-test has been run and a fault code has been identified by the BGAN terminal.
A run-time fault message is displayed by the Antenna Status page.
The observed degraded operation suggests that the BGAN terminal is faulty.
Whenever it is believed that the BGAN terminal may be faulty, the troubleshooting procedures in this chapter should be followed to determine the recommended corrective action. If the symptom observed is not covered, report the problem to a Level II or III maintainer (Direct Support, Intermediate Maintenance, or Factory Warranty Support). Faults can be detected by the Built-In Test (BIT) or visual observation.
5.2.1 Troubleshooting Procedures
Self test faults are displayed on the Antenna Status page. The following paragraphs identify probable failure causes, and suggested corrective actions.
5.2.1.1 Power-on BIT Faults
BIT faults are saved following an power-on BIT and are displayed on Antenna Status page.
5.2.1.2 Operator-Initiated BIT Faults
BIT faults are displayed following an operator-initiated BIT. For information on running BIT, refer to
Paragraph 4.3.7. When a fault message is displayed, record all fault code information and report the fault to a Level
II or Level III maintainer.
5.2.1.3 Run-Time Faults
Run-Time faults mostly occur due to programming errors and are listed in Table 5-3. Sometimes hardware failures can cause run-time failures. Send the radio to a level II or III repair facility for hardware failures.
Table 5-3. Run-Time BIT Faults, Descriptions, and Corrective Action
Text Message Description/Corrective Action
Hot, Very Hot, Very Very Hot, Too Hot Temperature warnings. Hot = warning, Very Hot = reducing
functionality, Very Very Hot = shutting down calls, Too Hot = imminent shutdown.
Personal Identification Number (PIN) Required Enter a 4-8 digit PIN to enable non-emergency functions.
Personal Unblocking Key (PUK) Required Enter a 4-8 digit PUK to revert Subscriber Identity Module
(SIM) to the original unlocked state.
5.2.1.4 Non-BIT Faults
Non-BIT faults are operator-observed failures, or cases of degraded operation. Locate the observation in the first column of Tabl e 5-4 and follow the recommended action. If the recommended action is unsuccessful, report the fault to a Level III maintainer.
5-2
SCHEDULED MAINTENANCE
R
Table 5-4. Non-BIT Troubleshooting
Observation Action
BGAN terminal does not power on. Check batteries and/or power source.
Check cable connections.
RF-7800B
Battery Box not supplying power. Applies to the RF-7800B-DU024 only.
Integrated Services Digital Network (ISDN) calls are not accepted.
Check Fuse F1, F2 (Automotive Blade, 5 A 32 V). Check Batteries.
The Mobile Subscriber Number (MSN) programmed into the ISDN device does not match the MSN programmed into the terminal.
ISDN calls are not being made. The ISDN interface is turned off (the interface turns
off automatically when the terminal is operating from battery power, or if no ISDN device is detected within five minutes from power on).
BGAN terminal is connected to the BGAN network, but cannot obtain the requested Quality of Service.
Terminal does not obtain a Global Positioning System (GPS) fix.
The BGAN terminal is not optimally pointed at the satellite. Re-point the terminal.
BGAN terminal location limits visibility of four or more GPS satellites. Move the terminal to a location where there are few obstructions.
BGAN terminal makes a continuous beep when an ISDN device is connected to the ISDN port.
The ISDN device is trying to draw too much power from the BGAN terminal's ISDN interface. Make sure it is an ISDN device that draws less than 70 mA of current at 40 V (equivalent power 2.8 W). It might be an Ethernet device.
The terminal will not register with the BGAN Network.
When viewing the terminal's Web interface, does the
terminal have a 3D GPS fix?
The BGAN terminal requires a GPS fix to determine the correct Rx and Tx radio frequencies to use.
The terminal will not register with the BGAN Network.
Does the terminal have a clear line of sight to the
satellite?
The terminal will not register with the BGAN Network.
Are you in a geographical location where two BGAN
satellites have coverage?
Using the BGAN terminal's Web interface, wait for the terminal to acquire a 3D fix. Attempt to move the terminal to a location with a more open view of the sky. Once the unit has acquired a GPS fix, it can be moved into a more sheltered location nearby.
Move the terminal to a more open location. In urban environments, buildings produce regions of signal reflection and fade that can result in strong signal readings, but which introduce sufficient noise to prevent communication. In such conditions, often moving the terminal only a couple meters can fix the problem.
The Land Mobile SATCOM-on-the-Move terminal will automatically search for the best satellite connection, but your position may be blocking the view to the nearer satellite. You can force the terminal to search for the other satellite by changing the 'Satellite Selection' setting on the Web interface Setup page from 'AUTO' to the desired satellite.
5-3
RF-7800B
R
SCHEDULED MAINTENANCE
Table 5-4. Non-BIT Troubleshooting (Continued)
Observation Action
The terminal will not register with the BGAN Network.
Is the 'Satellite Selection' configured with the
appropriate setting?
Using the Web interface on the Properties screen, the terminal shows the "Registration Status" as "Registered", but the "PS Attach" status as "Not Attached".
The Packet Data Protocol (PDP) context activation attempt fails because the requested static Internet Protocol (IP) address is in use or otherwise unavailable.
Are you requesting the correct static IP address?
The PDP context activation attempt fails because the requested static IP address is in use or otherwise unavailable.
Is the requested IP address permitted in your current
location?
The 'Satellite Selection' allows for specification of the satellite to use. This can be configured to use a specific satellite, or to automatically locate the most appropriate one.
If a specific satellite is selected, ensure that it is within your field of view. Alternatively, select 'AUTO' if the specific satellite is unknown.
Is your BGAN subscription valid?
The most common cause for a failure to PS Attach is that your BGAN service provider is denying you service. Contact your BGAN service provider to ensure the subscription is valid.
Confirm you are using the correct Access Point Name (APN), username, and password to obtain the desired IP address. These parameters may vary based on your geographical location. Check with your BGAN service provider.
The use of static IP addresses is specific to geographical regions. Your BGAN service provider will provide the details. Confirm that you are requesting the correct static IP address for your current geographical position.
The PDP context activation attempt fails because the requested static IP address is in use or otherwise unavailable.
Was the last context activation made to the requested
IP address properly deactivated?
The BGAN system is designed to allow for short outages in the connection link between the terminal and the satellite. For example, when the vehicle with a BGAN terminal drives behind a building, the BGAN system will allow the Background PDP connection to remain broken for one hour. During that one hour the IP address remains assigned to that context. (Note, if you remove DC power from the BGAN terminal without properly deactivating a context, the BGAN Network will keep the IP address for that context allocated to that BGAN terminal for one hour. Moving the Land Portable power switch to OFF will correctly deactivate the PDP context before shutting off power to the unit.) You can power the terminal back on, reactivate the context, and then properly deactivate it to release the IP address. Alternatively, wait one hour for BGAN to release the IP address, or use a different IP address.
5-4
SCHEDULED MAINTENANCE
R
Table 5-4. Non-BIT Troubleshooting (Continued)
Observation Action
RF-7800B
The PDP context activation attempt fails because the requested static IP address is in use or otherwise unavailable.
Is there network congestion in your specific spot
beam?
The terminal has power, but the Ethernet electrical link indication is not present.
The terminal has power, but the Ethernet electrical link indication is not present.
Check computer settings.
The terminal Ethernet electrical link is present, but IP traffic to the default IP address of the terminal gets no response.
Was the IP address of the terminal changed from the
default?
The terminal Ethernet electrical link is present, but IP traffic to the default IP address of the terminal gets no response.
Is the DHCP server feature enabled in the terminal?
It is possible during periods of heavy network usage that the network is too busy to grant a PDP context request.
Continuously retry activation attempts. As soon as the network is able to grant you a PDP context, it will. Additionally, your BGAN Service Provider can determine if the problem is due to network congestion.
Verify that the MIL Data Connector on the cable is fully connected to the MIL Data Connector on the BGAN terminal. The red outline on the BGAN terminal connector should not be seen when fully screwed in.
Cable 12043-0834 contains both a female ISDN and a male Ethernet connector. Ensure the correct connector is used.
Ensure that the Ethernet Device is properly configured on your computer. Refer to
Paragraph 2.6 Initial Turn-On / Check.
Retry the communication using the correct IP address for the terminal. If the address was changed and forgotten proceed to the actions below to recover the IP address of the terminal.
Configure the communicating device to use Dynamic Host Configuration Protocol (DHCP).
The terminal Ethernet electrical link is present, but IP traffic to the default IP address of the terminal gets no response.
Was the embedded DHCP server turned off?
Configure the communicating device to use DHCP.
If the BGAN terminal was changed to a static IP address, and that IP address was forgotten, remove the Universal Mobile Telecommunications System Subscriber Identification Module (USIM) card, then power the terminal up. With the USIM removed, the terminal will automatically enable the DHCP server feature. This will allow a directly connected computer to use DHCP to receive an address from the BGAN terminal, as well as allow the computer to reconfigure the BGAN terminal appropriately.
Ensure that the computer is configured to be in the same subnet as the terminal if the terminal is not configured for DHCP. If DHCP is enabled on the terminal, ensure that the computer got an IP Address from the BGAN terminal. Refer to
Paragraph 2.6 Initial Turn-On / Check.
5-5
RF-7800B
R
SCHEDULED MAINTENANCE
Table 5-4. Non-BIT Troubleshooting (Continued)
Observation Action
The PDP context is active, but data will not flow over the connection.
The PDP context is active, but data will not flow over the connection.
Does your Local Area Network (LAN) route packets
between the Local IP Address and the BGAN terminal?
I can't hear pointing tones on my RF-7800B-DU when the switch is in the audio position
On the 'PDP-Contexts' Web interface page, confirm that the Local IP address of the active context matches the IP address of the device attempting to send data.
Only packets sourced from the Local IP Address will be allowed to pass over the PDP context created.
If the addresses do not match, you must deactivate the context and create a new one with the correct Local IP Address. Note that when using DHCP from the computer, the computer IP address may change.
Confirm you network configuration is correctly routing packets between the Local IP Address of the active context to the BGAN terminal.
Check the 'Bypass Antenna Pointing' setting on the Web interface Setup page.
The 'Auto Power On' setting might be disabled on your terminal. Use the switch to power off the terminal and power it back on. Check the 'Auto Power On' feature setting via the Web interface.
When the 'Auto Power On' feature is enabled, the terminal will automatically power on when power is applied to the unit and the power switch is not in the OFF position. This feature allows for automatic reboot of the terminal following an unexpected power failure.
What frequency is my BGAN terminal transmitting on? Check the Web interface 'Antenna' page.
It varies slightly by location. Register and create a PDP context with the terminal. Then check the 'Antenna' page on the terminal's Web interface for your spot beam frequency. This is the frequency that user data is transmitted on.
5-6
SCHEDULED MAINTENANCE
R
Table 5-4. Non-BIT Troubleshooting (Continued)
Observation Action
RF-7800B
My RF-7800B-DU does not seem to turn on when power is applied.
The BGAN terminal was online, but has since been placed offline (Not Registered) without user intervention.
Has the view of the satellite become obstructed?
The BGAN terminal was online, but has since been placed offline (Not Registered) without user intervention.
Was there any data sent over the connection for 12
hours?
The BGAN terminal was online, but has since been placed offline (Not Registered) without user intervention.
Did you reach the data limit for your BGAN
subscription?
Check if the 'Auto Power On' feature is enabled on the Web interface 'Setup' page.
The 'Auto Power On' setting might be disabled on your terminal. Use the switch to power off the terminal and power it back on. Check the 'Auto Power On' feature setting via the Web interface.
When the 'Auto Power On' feature is enabled, the terminal will automatically power on when power is applied to the unit and the power switch is not in the OFF position. This feature allows for automatic reboot of the terminal following an unexpected power failure.
Restore a clear line of sight between the terminal and the satellite. The connection will automatically be restored if the interruption was less than one hour.
The BGAN system will automatically deactivate a context that has not sent any data for 12 hours. Manually reactivate the PDP Context.
If desired, enable the '24/7 PDP Context Keep Alive' feature on the 'Setup' page of the Web interface to keep unused connections active longer than 12 hours.
To limit BGAN expenses, USIM cards can be commissioned to have a daily/weekly/monthly traffic or monetary limit.
Contact your USIM administrator to obtain more air-time. Check with your BGAN Service Provider to determine if this was the cause.
5.3 BATTERIES
The BGAN Battery Box Kit 12091-4010-01 can use one of the following batteries:
BA-5590/U Lithium Sulfur Dioxide (Li-SO2) non-rechargeable
BA-5390/U Lithium Manganese Dioxide (Li-MnO2) non-rechargeable
BB-590/U Nickel-Cadmium (Ni-Cd) rechargeable
BB-390A/U Nickel-Metal Hydride (Ni-MH) rechargeable
BB-390B/U Ni-MH rechargeable
BB-490/U lead-acid rechargeable
BB-2590/U Lithium-Ion (Li-ION) rechargeable
5-7
Loading...
+ 15 hidden pages