Harrington Signal T8000 Install Manual

DOCUMENT REV CN
780-0867
Installation Manual
FireSpy® Tracker T1000, T2000, T8000, T2000E
Fire Alarm Systems
C
1012
HSI #780-0867 FireSpy Tracker Installation Manual
Contents
1 Preliminary Information .........................................................1
Contents
1.1 Safety messages – Please read before proceeding..................................................................1
1.2 Warranty ........................................................................................................................................2
1.3 Support..........................................................................................................................................2
2 Overview..................................................................................3
2.1 General ..........................................................................................................................................3
2.2 System layout ...............................................................................................................................4
2.2.1 Standalone panel ....................................................................................................................4
2.2.2 Multiple panel network.............................................................................................................4
2.3 System components.....................................................................................................................5
2.3.1 Main circuit board assembly (T1-MB, T8000-MBC, T2000-MBCLC)......................................5
2.3.2 Display board (T-PDC)............................................................................................................8
2.3.3 Network Communications adapter (T8000-NCA)....................................................................8
2.3.4 LCD annunciator (T8000-RAN / -ANN)...................................................................................9
2.3.5 Graphic annunciator................................................................................................................9
2.3.6 Addressable Signaling Line Circuit (SLC) module (T8000-LCU)............................................9
2.3.7 Conventional zone module (T8000-CM) ...............................................................................10
2.3.8 Relay module (T8000-RC) ....................................................................................................11
2.3.9 Serial relay module (T8000-SRM).........................................................................................11
2.3.10 DACT communicator module (T-UDACT).............................................................................11
2.3.11 Audio evacuation modules ....................................................................................................12
2.3.12 City tie/reverse polarity communicator (UCT) .......................................................................12
2.3.13 Enclosures.............................................................................................................................13
2.4 Service use..................................................................................................................................14
2.5 Listings and approvals ..............................................................................................................14
1
2
3
A
B
C
3 Installation and Wiring.........................................................17
3.1 System planning.........................................................................................................................17
3.1.1 Battery calculation.................................................................................................................17
3.2 Control panel installation ..........................................................................................................17
3.2.1 Preparation............................................................................................................................17
3.2.2 Panel location........................................................................................................................17
3.2.3 Installation .............................................................................................................................18
3.3 Configuration and programming ..............................................................................................19
3.4 Check system operation ............................................................................................................19
Appendix A. Ordering and Parts Information.........................29
A.1 Component matrix......................................................................................................................29
A.1.1. Available panel configurations (factory pre-wired) ................................................................29
A.1.2. Board modules ......................................................................................................................29
A.1.3. Enclosures.............................................................................................................................30
A.1.4. Accessories...........................................................................................................................30
Appendix B. Compatible Devices............................................31
B.1 Startup delay for devices with alarm verification....................................................................31
i
D
HSI #780-0867 FireSpy Tracker Installation Manual
B.2 Addressable SLC devices (for use with T8000-LCU, T2000-MBCLC, and T1-MB)...............31
B.2.1. System Sensor......................................................................................................................31
B.2.2. Harrington Signal...................................................................................................................32
B.2.3. Apollo.....................................................................................................................................34
B.2.4. Air Products...........................................................................................................................34
B.3 Conventional two-wire smoke detectors (for use with T8000-CM)........................................35
B.3.1. Harrington Signal...................................................................................................................35
Contents
B.3.2. Apollo.....................................................................................................................................35
B.3.3. ESL/Sentrol ...........................................................................................................................37
B.3.4. System Sensor......................................................................................................................37
B.4 Releasing devices (for use with a NAC on MB / MBC / MBCLC) ...........................................37
Appendix C. Wire Selection .....................................................39
C.1 General wiring guidelines..........................................................................................................39
C.2 Wire length calculations ............................................................................................................39
C.3 Wire selection tables..................................................................................................................40
Appendix D. Battery Capacity Calculation .............................45
ii
HSI #780-0867 FireSpy Tracker Installation Manual
1 Preliminary Information
1.1 Safety messages – Please read before proceeding
People’s lives depend on your safe installation of our products. It is important to read, understand and follow all instructions shipped with this product. The equipment described herein is listed by the NRTL only when installed and configured in the manner described herein
It is possible to install equipment incorrectly or arrange system components and installation wiring in such a manner that life safety functions are not properly performed and, as a result, lives may be lost. To minimize this possibility, become familiar with the system layout and operation of the entire Fire­Protective Signaling System. Do not alter any mechanical or electrical features of the equipment supplied. Become familiar with the Building Code and Fire Prevention Code or other authority having jurisdiction requirements in the area of the installation.
The Facilities Engineer and the Safety Engineer should make selection of mounting location for this equipment and routing of wiring. Listed below are some other important safety instructions and precautions you should follow:
This unit must be installed by a qualified electrician in accordance with NFPA 72, and national and local electrical and fire codes, under the direction of the authority having jurisdiction.
Only authorized and competent personnel must be allowed access to panel controls or panel power source, to limit the possibility of malfunction or failure.
Do not connect this unit to system wiring when circuits are energized. Check field wiring lines to ensure that voltages are not present. Warranty is void if the equipment is damaged by improperly connected untested wiring or if fused improperly.
The equipment must be connected to a dedicated source of reliable AC power adequate for the rating of the system as configured. The source must be secure and properly labeled "Fire Alarm Circuit Control".
A suitable battery set must be used to assure required operation in case of primary power loss. The battery set must be replaced after 4 years, or earlier if capacity is excessively reduced. The batteries should be checked at least twice per year, or more often if required by local codes.
Wiring used in the system must be adequate for the service and installed in accordance with applicable codes.
Devices used in the system and connected to the control panel must be verified compatible with the panel.
All effective warning speakers produce loud sounds which, in certain circumstances, may cause permanent hearing loss. Take appropriate precautions such as wearing hearing protection. Recommendations in OSHA Sound Level Standard (29 CFR 1910) should not be exceeded.
After installation and completion of initial system test, provide a copy of this instruction sheet to all personnel responsible for operation, periodic testing and maintenance of this equipment.
After installation, ensure that all bolts and threaded joints are tightened.
After installation and completion of initial system test, a program for periodic testing of this device
must be established. Proper periodic maintenance is required to assure operation through the life of the system, and to determine that point at which useful life of the system or of any of its components has been reached. Any malfunctioning units must be repaired or replaced immediately by competent, authorized personnel. Refer to NFPA 72, local Fire Codes and the authority having jurisdiction.
Instructions for proper response by building occupants must be developed and distributed in accordance with the Building Code and Fire Prevention Code or other authority having jurisdiction.
Unauthorized repair or servicing of equipment may result in degradation of performance and/or property damage, serious injury, or death to you or others. If a malfunctioning unit is encountered, do not attempt any field repair/retrofit of parts.
Failure to follow all safety precautions and instructions may result in property damage, serious injury, or death to you and others.
1
2
3
A
B
C
D
1
1
HSI #780-0867 FireSpy Tracker Installation Manual
The programming technician is ultimately responsible for conformance to the applicable codes and purchase order.
This manual cannot cover all details or contingencies which could exist in a system application. Refer to the authorized distributor if additional information is required.
Specifications are subject to change without notice.
Contents
1.2 Warranty
Harrington Signal products are covered by a limited warranty. See Harrington’s warranty statement for more details (document #780-0762)
1.3 Support
If you have any questions or concerns about installation, operation, or programming of our equipment, please contact us at:
Harrington Signal Inc. 2519 – 4th Ave Moline, IL 61265
Toll Free: (800) 577-5758 Tel: (309) 762-0731 Fax: (309) 762-8215 Email: techservices@harringtonsignal.com Web: www.harringtonfire.com
FireSpy is a registered trademark of Harrington Signal Inc. This document is copyright © 2009 Harrington Signal Inc.. All rights reserved.
2
HSI #780-0867 FireSpy Tracker Installation Manual
290-0103
NETWORK WIRING (RS485) LOW CAPACITANCE TWISTED PAIR OR FIBER DAISY-CHAIN ONLY, DO NOT T-TAP STYLE 4 (CLASS B): SOLID LINE STYLE 7 (CLASS A): SOLID AND DOTTED LINES
MASTER PANEL T8000*
MASTER PANEL LOCAL PANEL LOCAL PANEL
NCA
RS485
NCA
RS485
NCA
RS485
NCA
RS485
REPORTING EQUIPMENT (OPTIONAL)
REPORTING EQUIPMENT (OPTIONAL)
MB, MBC, or MBCLC
MB, MBC, or MBCLC
MB, MBC, or MBCLC
MBC
* AT LEAST ONE T8000 MASTER PANEL IS REQUIRED. TOTAL COMBINATION OF MASTER AND LOCAL PANELS NOT TO EXCEED 254 PANELS.
2 Overview
2.1 General
The FireSpy Tracker series panels are sophisticated microprocessor-based fire alarm control systems suited to the various needs of commercial, industrial and institutional applications. The Tracker panel can connect to a Tracker network, a peer-to-peer network of up to 250 Tracker panels. Up to 254 points on each Signal Line Circuit (SLC) and up to 60 conventional fire detector zones can be configured. The distributed system architecture reduces the length of wiring needed because addressable SLC, conventional IDC, and other modules can be located closer to where devices are installed.
The Tracker panel functions in accordance with the National Fire Protection Association (NFPA) Standard 72 Fire Alarm Code. Activation of a compatible detector or normally open fire alarm initiating device will sound audible appliances, notify a remote station, annunciate a fire or alarm condition, and energize supplementary relays.
Automatic learning features can be used to quickly configure a system. Additional system configuration can be done through the annunciator or with a PC.
The Tracker 8000 allows up to eight SLCs for a total of 2032 addressable points. The SLCs are provided by the use of modular SLC boards, which may be mounted in the main enclosure or remotely.
The Tracker 2000 main board (MBCLC) has two SLCs for a total of 508 addressable points. The Tracker 1000 main board (MB) has one SLC for a total of 254 addressable points. The Tracker T2000E combines the Tracker 2000 fire alarm control panel and the HAVE audio voice
evacuation systems into one convenient package. In addition to the features of the T2000, it also provides conventional audio with up to 8 Class B speaker circuits (or up to 4 Class A) with amplification for 25, 50 or 100 watts. Within this manual, references to the T2000 also apply to the fire alarm portion of the T2000E (the MBCLC main board).
2
3
A
B
C
D
Figure 2-1: Peer-to-peer network layout
3
1
T1000
SYSTEM
(TO NETWORK)
TO PC
290-0158
* MAY BE INDIVIDUALLY CONFIGURED AS NAC, AUX POWER, OR INPUT ** MAY BE CONFIGURED AS NAC (FOR CONNECTION TO NAC BOOSTER OR VOICE MODULE) OR INPUT A SYSTEM MUST USE AT LEAST ONE INITIATING DEVICE
MAIN BOARD ASS'Y MB
RS485
(3) NACs*
(1) SLC
RELAY CONTACTS
(8) PER SRM
PHONE LINES
TO CENTRAL
OR REMOTE
STATION
RELAY
CONTACTS
(2) PER RC
RELAY CONTACTS (2) PER RC
ANN (7) MAX
IDC
(5) CLASS A OR
(10) CLASS B
PER CM
RC
(5) MAX
PER CM
CM (6) MAX
SRM (6) MAX
250 OUTPUTS
PER LDV
(250 TOTAL
CONFIGURABLE)
LDV (4) MAX
RC
(5) MAX
USB
RELAY CONTACTS: (1) SYSTEM ALARM (1) SYSTEM SUPV ALARM (1) SYSTEM TROUBLE
NCA
ANNUNCIATOR (MOUNTED ON MAIN CABINET DOOR)
(1) AUX I/O**
1
2
3
4
5
6
7
8
9
10
SILENCE
POWER
ALARM
TROUBLE
SUPERVISORY
1
2
3
4
5
6
7
8
9
10
SILENCE
POWER
ALARM
TROUBLE
SUPERVISORY
2
HSI #780-0867 FireSpy Tracker Installation Manual
2.2 System layout
2.2.1 Standalone panel
A Tracker panel consists of the main board (MB for T1000, MBC for T8000 or MBCLC for T2000) in the main enclosure and various devices that connect to the main board (see Figure 2-2). System programming can be done from a PC or laptop through the serial port of the panel’s communications
Contents
adapter.
2.2.2 Multiple panel network
A Tracker network consists of multiple Tracker panels with each panel connected to the network through a communications adapter (see 2.3.3 Network Communications adapter (T8000-NCA)). Local network devices (annunciators, etc.) connect to the RS485 outputs of each panel, as they would in a standalone panel. Each panel provides the same capabilities as it would as a standalone panel, with the addition of the network connection. System programming can be done from a PC or laptop through the serial port of the panel’s communications adapter.
NOTE: A Tracker network must include at least one T8000 panel, set up as master.
Figure 2-2: System layout (T1000)
4
HSI #780-0867 FireSpy Tracker Installation Manual
T2000
,
T8000
SYSTEM
* MAY BE INDIVIDUALLY CONFIGURED AS NAC, AUX POWER, OR INPUT A SYSTEM MUST USE AT LEAST ONE INITIATING DEVICE
(TO NETWORK)
TO ONE OF:
- PRINTER (straight cable)
- MODEM (straight cable)
TO PC
290-0104
(2) SLCs T2000 ONLY
MAIN BOARD ASS'Y MBC (T8000) OR MBCLC (T2000)
RS485
(4) NACs*
RELAY CONTACTS
(8) PER SRM
PHONE LINES
TO CENTRAL
OR REMOTE
STATION
RELAY
CONTACTS
(2) PER RC
RELAY CONTACTS (2) PER RC
SLC
(2) PER LCU
ANN (15) MAX (T8000) (7) MAX (T2000)
IDC
(5) CLASS A OR
(10) CLASS B
PER CM
RC
(5) MAX
PER CM
CM (6) MAX
SRM (6) MAX
UDACT
250 OUTPUTS
PER LDV
(250 TOTAL
CONFIGURABLE)
LDV (4) MAX
RC
(5) MAX
LCU (4) MAX
RS232
USB
RELAY CONTACTS: (1) SYSTEM ALARM (1) SYSTEM SUPV ALARM (1) SYSTEM TROUBLE
NCA
T8000 ONLY
1
2
3
4
5
6
7
8
9
10
SILENCE
POWER
ALARM
TROUBLE
SUPERVISORY
1
2
3
4
5
6
7
8
9
10
SILENCE
POWER
ALARM
TROUBLE
SUPERVISORY
2.3 System components
The Tracker is a modular system. Each module may be purchased and installed separately. Some common system configurations are also available pre-assembled at the factory.
2.3.1 Main circuit board assembly (T1-MB, T8000-MBC, T2000-MBCLC)
The main circuit board assembly (T1-MB, T8000-MBC or T2000-MBCLC) is the core of the Tracker panel. It contains the main board and power supply mounted on a metal chassis. The MB / MBC / MBCLC mounts in the main panel enclosure.
The T1-MB, T8000-MBC and T2000-MBCLC are respectively referred to as MB, MBC and MBCLC in this manual.
2
3
A
Figure 2-3: System layout (T2000, T8000)
5
B
C
D
1
2
HSI #780-0867 FireSpy Tracker Installation Manual
Table 2-1: Power supply specifications (MBC/MBCLC).
Parameter Rating
Input voltage (AC supply) 120VAC @ 50/60Hz
Input current draw (AC supply) 1.8A @ 120VAC
Contents
24VDC power available (total system current) and max battery load 7A Battery charge voltage, max 27.6V Battery charge current, max 1.6A Battery capacity
Min Max
Use two UL864 listed 12V batteries connected in series.
Table 2-2: Power supply specifications (MB).
Parameter Rating
Input voltage (AC supply) 120VAC @ 50/60Hz
Input current draw (AC supply) 1.8A @ 120VAC
24VDC power available (total system current) and max battery load 4A Battery charge voltage, max 27.6V Battery charge current, max 1.6A Battery capacity
Min Max
Use two UL864 listed 12V batteries connected in series.
230VAC @ 50/60Hz
0.4A @ 230VAC
8Ah 40Ah
240VAC @ 50/60Hz
2.15A @ 240VAC
7Ah 40Ah
Table 2-3: Environmental specifications (MB / MBC / MBCLC).
Parameter Rating
Environment UL864 location Temperature range Maximum relative humidity
Indoor, dry 32 to 120° F 93%
Table 2-4: RS-485 specifications (MB / MBC / MBCLC).
Parameter Rating
Output voltage (MBC / MBCLC) 24VDC Max output current (MBC / MBCLC) 2.5A Max impedance, RS-485 wiring* 100 ohms Max capacitance, RS-485 wiring* .3uF Max impedance, power wiring, total (3V drop each wire @ 80mA)*
(MBC / MBCLC) * See Appendix C Wire Selection for suggested wiring distances.
75 ohms
6
HSI #780-0867 FireSpy Tracker Installation Manual
The main circuit board contains 4 circuits (3 for MB) that can be individually programmed to operate in the following modes:
NAC (steady, temporal coding, or march time coding, Gentex 1 synchronization for Commander 3 and 4, Gentex 2 synchronization for Commander 1)
Auxiliary power supply (resettable or continuous)
Auxiliary input
NOTE: UL864 requires audible alarm notification devices to be synchronized on a
circuit or a system basis. If using notification appliances other than Gentex Commander 1, 3, or 4, synchronization modules must be used.
Table 2-5: NAC specifications (output modes) (MB / MBC / MBCLC)
Parameter Rating
Output voltage 24VDC Output current, max
MBC / MBCLC MB
Wiring styles (NAC mode) Style Y (Class B)
End-of-line resistance (NAC mode, Class B) 10k ohm * See Appendix C Wire Selection for suggested wiring distances.
3A
1.8A
Style Z (Class A)
2
3
A
Table 2-6: NAC specifications (input mode) (MB / MBC / MBCLC)
Parameter Rating
Input voltage (input mode) 24VDC Input current draw, max (input mode), inherently power limited 5mA End of line resistance (input mode) 10k
The MB contains an auxiliary input/output circuit that can be used in a NAC mode or as an input. The NAC mode can be used to activate an external NAC-driven device, such as a NAC power supply or HAVE voice evacuation system. The AUX IO port provides alarm activation, silencing and resound operation.
Table 2-7: AUX IO specifications (output mode) (MB)
Parameter Rating
Output voltage 24VDC Output current, max 0.02A Wiring styles Style Y (Class B) End-of-line resistance 10k ohm
Table 2-8: AUX IO NAC specifications (input mode) (MB)
B
C
D
Parameter Rating
Input voltage (input mode) 24VDC Input current draw, max (input mode), inherently power limited 5mA End of line resistance (input mode) 10k
7
1
HSI #780-0867 FireSpy Tracker Installation Manual
The main board contains (1) common alarm relay output, (1) common supervisory alarm relay output, and (1) common trouble relay output, as well as a connection for up to (5) relay modules (T8000-RC).
Table 2-9: Output relay specifications (MB / MBC / MBCLC)
Parameter Rating
Type Form C (SPDT)
Contents
Contact rating MBC / MBCLC resistive load, PF=1.0
inductive load, PF=0.4 MB resistive load, PF=1.0
* Limited to 50VDC due to spacing
10A @ 30VDC 10A @ 240VAC* 3A @ 240VAC*
2A @ 30VDC
2
Table 2-10: SLC specifications (MB / MBCLC)
Parameter Rating
Loop output voltage 32V @ 10kHz Max loop output current 400mA max Max loop capacitance 0.5uF Max loop impedance (total per loop) 40 ohms Environment
UL864 location Temperature range Maximum relative humidity
* See Appendix C Wire Selection for suggested wiring distances.
Indoor, dry 32 to 120° F 93%
2.3.2 Display board (T-PDC)
The display board may mount either inside the enclosure door so its buttons are accessible with the door closed or on the chassis assembly (MBC or MBCLC only) so it is accessible after unlocking and opening the enclosure. When the PDC is mounted on the door and connected to the keyswitch, the keyswitch must be activated to enable keypad access to the system’s security-sensitive control functions.
2.3.3 Network Communications adapter (T8000-NCA)
The network communications adapter is used with each panel in a networked system. It allows the connected panel to communicate with other panels on the panel network.
Table 2-11: Communications adapter (T8000-NCA) specifications.
Parameter Rating
Input voltage Regulated 24 DC Input current draw 60 mA Max impedance, RS485 communication wiring, total 40 ohms* Max capacitance, RS485 communication wiring 0.3 uF* Environment
UL864 location Temperature range Maximum relative humidity
* See Appendix C Wire Selection for suggested wiring distances.
Indoor, dry 32 to 120° F 93%
8
HSI #780-0867 FireSpy Tracker Installation Manual
2.3.4 LCD annunciator (T8000-RAN / -ANN)
The Tracker 8000 allows up to 15 remote display annunciators (Model T8000-ANN or T8000-RAN). The T2000 and T1000 allow up to 7 remote annunciators. The T8000-ANN remote annunciator is intended for surface or flush mounting and is comprised of the T8000-RAN module within the T8000-A-CAB cabinet.
Table 2-12: Remote annunciator (T8000-RAN/T8000-ANN) specifications.
Parameter Rating
Dimensions (backbox of T8000-ANN) 8.5H x 10W x 2D
Input voltage 24VDC Input current draw
Standby Alarm, without backlight Alarm, with backlight (10 seconds after key press)
Max impedance, power wiring, total (3V drop each wire @ 80mA)* 75 ohms Environment
UL864 location Temperature range Maximum relative humidity
* See Appendix C Wire Selection for suggested wiring distances.
(inches)
19mA 25mA 80mA
Indoor, dry 32 to 120° F 93%
2
3
A
2.3.5 Graphic annunciator
A graphic annunciator module (T8000-LDV) is for use in appropriately UL864 Listed custom enclosures to provide graphic annunciator capabilities. The module may be configured to use either LED or incandescent lamps; either type of output is supervised. Up to 4 lamp annunciator modules may be used for a total of 250 programmable outputs per Tracker panel. Additionally, each module has outputs for power on, common alarm and common trouble visual indicators and a sounder.
Table 2-13: Lamp annunciator module (T8000-LDV) specifications.
Parameter Rating
Input voltage 24VDC Input current draw
Standby (no devices) Alarm (full load)
Max impedance, RS-485 wiring* 100 ohms Max impedance, power wiring, total (3V drop each wire @ ?? mA)* ?? ohms Environment
UL864 location Temperature range Maximum relative humidity
* See Appendix C Wire Selection for suggested wiring distances.
TBD
Indoor, dry 32 to 120° F 93%
B
C
D
2.3.6 Addressable Signaling Line Circuit (SLC) module (T8000-LCU)
The Tracker panel monitors addressable fire detection devices that are connected to up to (4) loop modules (T8000-LCU).
Each loop module provides the following:
Two Signaling Line Circuits (SLCs).
Up to 254 addressable analog devices can be installed on any loop (limited by device protocol).
9
HSI #780-0867 FireSpy Tracker Installation Manual
Compatible with System Sensor, Apollo, Harrington and Air Productsdevices (see Appendix B for details).
Mounts in the main enclosure or remotely (see Table 2-20)
Table 2-14: Addressable SLC module (T8000-LCU) specifications.
1
2
Contents
Parameter Rating
Input voltage 24V Input current draw
Standby (no devices) Alarm (full load)
Max impedance on 24VDC input wiring (per side) 2 ohms Loop output voltage 25V Max loop output current 400mA max Max loop capacitance 0.5uF Max loop impedance (total per loop) 100 ohms Environment
UL864 location Temperature range Maximum relative humidity
* See Appendix C Wire Selection for suggested wiring distances.
2.3.7 Conventional zone module (T8000-CM)
The Tracker panel monitors conventional fire detection devices that are connected to conventional zone modules (T8000-CM). Each zone module provides 5 Class A zones or 10 Class B zones for FireSpy conventional devices. Zone modules may be mounted in the main enclosure or in remote enclosures.
107mA
Indoor, dry 32 to 120° F 93%
Table 2-15: Conventional IDC module (T8000-CM) specifications.
Parameter Rating
Input voltage 24V Input current draw
Standby (no detectors) Alarm, base module current Alarm, each additional zone in alarm*
Max impedance, power wiring, total (3V drop each wire) 6V divided by total
Max impedance, RS-485 wiring* 100 ohms Zone output voltage (normal standby) 26.5V Zone output current
Supervision Short circuit
Zone impedance (total per loop), max 100 ohms Zone end-of-line resistor 4.7k ohms Environment
UL864 location Temperature range Maximum relative humidity
* For total alarm current, add 14mA plus 40mA for each additional zone used ** See Appendix C Wire Selection for suggested wiring distances.
11mA 14mA 40mA
alarm current*
5mA 40mA
Indoor, dry 32 to 120° F 93%
10
HSI #780-0867 FireSpy Tracker Installation Manual
2.3.8 Relay module (T8000-RC)
The T8000-RC relay module has (2) form C (SPDT) relays, providing individually programmable dry contact outputs. Up to (5) relay modules may be daisy-chained, with the first one connected to a conventional zone module (T8000-CM) or the main board (MB, MBC, MBCLC) via the relay output connector. Relay modules may be mounted in the main enclosure or remotely (see Table 2-20).
Table 2-16: Relay module (T8000-RC) specifications.
Parameter Rating
Input current draw Standby Alarm
Relay type Form C (SPDT) Contact rating
resistive load, PF=1.0 inductive load, PF=0.4
UL864 location Indoor, dry Temperature range 32 to 120° F Maximum relative humidity 93%
2mA 25mA
10A @ 30VDC 10A @ 240VAC 3A @ 240VAC
2.3.9 Serial relay module (T8000-SRM)
The T8000-SRM module provides (8) programmable relays. It may be mounted in the main enclosure or remotely (see Table 2-20).
2
3
A
B
Table 2-17: Relay module (T8000-SRM) specifications.
Parameter Rating
Input current draw Standby Alarm
Max impedance, power wiring, total (3V drop each wire)* 26 ohms Max impedance, RS-485 wiring* 100 ohms Relay type Form C (SPDT) Contact rating
resistive load, PF=1.0 inductive load, PF=0.4
Environment UL864 location Temperature range Maximum relative humidity
30mA* 230mA*
10A @ 30VDC 10A @ 240VAC 3A @ 240VAC
Indoor, dry 32 to 120° F 93%
2.3.10 DACT communicator module (T-UDACT)
The T-UDACT is used for off-premises monitoring of the Tracker system. The T1000 has the DACT built­in. For the T2000 or T8000, the DACT mounts in the main cabinet or in a separate UL864 listed enclosure. Programming is done through the Tracker user interface or a PC with the Tracker PC Programmer software.
Signals are sent to a Digital Alarm Communicator Receiver (DACR) using either a primary or secondary telephone line. A test call is transmitted to the DACR every 24 hours.
C
D
11
Loading...
+ 33 hidden pages