Harrington Signal T8000 Operation Manual

DOCUMENT
REV CN
Operation Manual
FireSpy® Tracker
T1000, T2000, T8000
Fire Alarm Systems
780-0923
C
1208
This page left intentionally blank for duplex printing.
Contents
HSI #780-0923 FireSpy Tracker Operation Manual
Contents
1 Preliminary Information ......................................................... 1
1.1 Safety messages – Please read before proceeding .................................................................. 1
1.2 Settings not allowed by regulations ........................................................................................... 2
1.3 Warranty ........................................................................................................................................ 2
1.4 Support .......................................................................................................................................... 2
2 Operation ................................................................................. 3
2.1 Standalone vs. networked panel(reserved) ............................................................................... 3
2.2 Inputs, outputs, and groups ........................................................................................................ 3
2.3 Types of inputs ............................................................................................................................. 3
2.3.1 Alarm ....................................................................................................................................... 3
2.3.2 Pullstation ................................................................................................................................ 3
2.3.3 Waterflow ................................................................................................................................. 3
2.3.4 Supervisory .............................................................................................................................. 3
2.3.5 Non-reporting........................................................................................................................... 3
2.3.6 FACP Reset ............................................................................................................................. 3
2.3.7 Releasing: Release ................................................................................................................. 3
2.3.8 Releasing: Fast Release ......................................................................................................... 4
2.3.9 Releasing: Halt ........................................................................................................................ 4
2.3.10 Releasing: Abort ...................................................................................................................... 4
2.4 User control interface................................................................................................................... 4
2.4.1 Resets ..................................................................................................................................... 4
2.5 System conditions and annunciation ......................................................................................... 6
2.5.1 Normal standby condition ........................................................................................................ 6
2.5.2 Non-normal condition (event counter) ..................................................................................... 6
2.5.3 Non-normal condition (browsing event list) ............................................................................. 7
2.5.4 Alarm condition ........................................................................................................................ 7
2.5.5 Supervisory alarm condition .................................................................................................... 7
2.5.6 Trouble condition ..................................................................................................................... 7
2.5.7 Pre-alarm condition ................................................................................................................. 7
2.5.8 Programming mode ................................................................................................................. 8
2.5.9 Other conditions ...................................................................................................................... 8
2.6 Features ......................................................................................................................................... 8
2.6.1 Alarm Verification .................................................................................................................... 8
2.6.2 Drift Compensation .................................................................................................................. 8
2.6.3 Releasing ................................................................................................................................. 8
2.6.4 Smoke Control ......................................................................................................................... 8
1
2
3
4
5
A
B
3 Test and maintenance .......................................................... 11
3.1 System test .................................................................................................................................. 11
3.1.1 Initial acceptance testing ....................................................................................................... 11
3.1.2 Walk test ................................................................................................................................ 11
3.2 System maintenance .................................................................................................................. 11
3.2.1 Fuse replacement .................................................................................................................. 12
4 Using the menu system ....................................................... 13
4.1 Accessing the menu system ..................................................................................................... 13
4.2 Exiting the menu system ........................................................................................................... 13
i
Contents
HSI #780-0923 FireSpy Tracker Operation Manual
4.3 About the numbering used ........................................................................................................ 13
4.4 Menu navigation ......................................................................................................................... 13
4.5 Assign a setting .......................................................................................................................... 13
4.6 Text and number entry ............................................................................................................... 14
5 Maintenance menu ............................................................... 15
5.1 Level 1 main menu...................................................................................................................... 15
5.2 Menu 1: Real time clock ............................................................................................................. 15
5.3 Menu 2: Test ................................................................................................................................ 15
5.4 Menu 2.1: Normal Walk Test ...................................................................................................... 15
5.5 Menu 2.2: Silent Walk Test ........................................................................................................ 16
5.6 Menu 2.3: Test NACs .................................................................................................................. 16
5.7 Menu 2.4: Test Relays ................................................................................................................ 16
5.8 Menu 2.5: Test LCD Display ...................................................................................................... 16
5.9 Menu 2.5: Drill Test ..................................................................................................................... 16
Appendix A. Glossary ............................................................... 17
Appendix B. Operating instructions ........................................ 21
HSI #780-0923 FireSpy Tracker Operation Manual
1 Preliminary Information
1.1 Safety messages – Please read before proceeding
People’s lives depend on your safe installation of our products. It is important to read, understand and follow all instructions shipped with this product. The equipment described herein is listed by the NRTL only when installed and configured in the manner described herein
It is possible to install equipment incorrectly or arrange system components and installation wiring in such a manner that life safety functions are not properly performed and, as a result, lives may be lost. To minimize this possibility, become familiar with the system layout and operation of the entire Fire­Protective Signaling System. Do not alter any mechanical or electrical features of the equipment supplied. Become familiar with the Building Code and Fire Prevention Code or other authority having jurisdiction requirements in the area of the installation.
The Facilities Engineer and the Safety Engineer should make selection of mounting location for this equipment and routing of wiring. Listed below are some other important safety instructions and precautions you should follow:
This unit must be installed by a qualified electrician in accordance with NFPA 72, and national and local electrical and fire codes, under the direction of the authority having jurisdiction.
Only authorized and competent personnel must be allowed access to panel controls or panel power source, to limit the possibility of malfunction or failure.
Do not connect this unit to system wiring when circuits are energized. Check field wiring lines to ensure that voltages are not present. Warranty is void if the equipment is damaged by improperly connected untested wiring or if fused improperly.
The equipment must be connected to a dedicated source of reliable AC power adequate for the rating of the system as configured. The source must be secure and properly labeled "Fire Alarm Circuit Control".
A suitable battery set must be used to assure required operation in case of primary power loss. The battery set must be replaced after 4 years, or earlier if capacity is excessively reduced. The batteries should be checked at least twice per year, or more often if required by local codes.
Wiring used in the system must be adequate for the service and installed in accordance with applicable codes.
Devices used in the system and connected to the control panel must be verified compatible with the panel.
All effective warning speakers produce loud sounds which, in certain circumstances, may cause permanent hearing loss. Take appropriate precautions such as wearing hearing protection. Recommendations in OSHA Sound Level Standard (29 CFR 1910) should not be exceeded.
After installation and completion of initial system test, provide a copy of this instruction sheet to all personnel responsible for operation, periodic testing and maintenance of this equipment.
After installation, ensure that all bolts and threaded joints are tightened.
After installation and completion of initial system test, a program for periodic testing of this device
must be established. Proper periodic maintenance is required to assure operation through the life of the system, and to determine that point at which useful life of the system or of any of its components has been reached. Any malfunctioning units must be repaired or replaced immediately by competent, authorized personnel. Refer to NFPA 72, local Fire Codes and the authority having jurisdiction.
Instructions for proper response by building occupants must be developed and distributed in accordance with the Building Code and Fire Prevention Code or other authority having jurisdiction.
Unauthorized repair or servicing of equipment may result in degradation of performance and/or property damage, serious injury, or death to you or others. If a malfunctioning unit is encountered, do not attempt any field repair/retrofit of parts.
Failure to follow all safety precautions and instructions may result in property damage, serious injury, or death to you and others.
1
2
3
4
5
A
B
1
Contents
HSI #780-0923 FireSpy Tracker Operation Manual
Feature or
Regulation*
Settings not allowed
Settings allowed
The programming technician is ultimately responsible for conformance to the applicable codes and purchase order.
This manual cannot cover all details or contingencies which could exist in a system application. Refer to the authorized distributor if additional information is required.
Specifications are subject to change without notice.
1.2 Settings not allowed by regulations
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES
1
This product incorporates field-programmable software. In order for the product to comply with regulations, certain programming features or options must be limited to specific values or not used at all as indicated below.
option
Alarm verification 36.5.3, 36.6.3 Alarm verification is not permitted on any
device that is used as part of the cross­zone or multiple detector initiating operation.
Abort switch 36.3.1 Abort switches shall not be used on
systems intended to perform pre-action or deluge water functions.
Time delay 36.1.7 An automatic delay provided prior to
release operation by a system shall be a maximum of 60 seconds.
* Sections cited are from the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864 ninth edition
Verify that alarm verification is not used on any device used in cross-zone or multiple detector initiation.
Do not assign the abort or halt function to modules used in the releasing operation.
Verify that the time delay is set to 60 seconds or less.
1.3 Warranty
Harrington Signal products are covered by a limited warranty. See Harrington’s warranty statement for more details (document #780-0762).CPG products are covered by a limited warranty. See CPG’s warranty statement for more details.
1.4 Support
If you have any questions or concerns about installation, operation, or programming of our equipment, please contact us at:
Harrington Signal Inc. Commercial Products Group 2519 – 4th Ave Moline, IL 61265
Toll Free: (800) 577-5758 Phone: (309) 762-0731 Fax: (309) 762-8215 Email: techservices@harringtonsignal.com Web: Email: techservices@cpglifesafety.com Web: www. cpglifesafety.com FireSpy is a registered trademark of Harrington Signal Inc. This document is copyright © 2009-2011 Harrington Signal Inc. All rights reserved.
2
HSI #780-0923 FireSpy Tracker Operation Manual
2 Operation
This manual describes the operation of FireSpy Tracker 1000, 2000, and 8000 Fire Alarm Control Panels.
2.1 Standalone vs. networked panel(reserved)
A networked panel provides the same local operations and features as a standalone panel, plus the operations and features offered by the network connection. A panel performs building monitoring of its location regardless of whether it is standalone or networked.
2.2 Inputs, outputs, and groups
A panel responds to alarm and supervisory alarm events using inputs and outputs. Each input is placed in one or more groups and is programmed to detect a certain type of event. When an event activates an input, the system activates the outputs that are programmed in the same groups as the input.
Trouble conditions indicate that something on the system needs maintenance or servicing or is improperly configured.
2.3 Types of inputs
Each input device on a panel can be programmed as one of the types of inputs below.
2.3.1 Alarm
Alarm is the normal type of input for automatic smoke detectors, heat detectors, etc. They are required to activate building notification devices as well as the ALARM light on annunciators. They can optionally operate relays and output modules in the system.
2
3
4
2.3.2 Pullstation
Pullstation is the normal type of input for manual pullstations. They operate similar to alarm inputs.
2.3.3 Waterflow
Waterflow is for water flow detectors. They are required to activate building notification devices as well as the ALARM light on annunciators. They can optionally operate relays and output modules in the system. Waterflow inputs can be programmed so that the outputs they activate are silenceable or nonsilenceable.
2.3.4 Supervisory
Supervisory inputs are for items such as shut-off valves and pressure detectors for sprinkler systems. They cannot operate building notification devices, but can optionally operate relays and output modules in the system.
2.3.5 Non-reporting
Non-reporting inputs allow associated outputs to be triggered without affecting the condition of the panel or being reported by the DACT. The panel remains in its previous condition (normal standby, etc.) when a non-reporting event is active.
2.3.6 FACP Reset
The FACP Reset input performs a fast reset. This clears any events that qualify as resettable, i.e. the inputs that triggered the event have returned to normal.
2.3.7 Releasing: Release
Modules or detectors assigned to operate as a Release function initiate a sequence that will cause the associated releasing device to energize. The sequence includes the delay timer.
5
A
B
3
Contents
1
2
HSI #780-0923 FireSpy Tracker Operation Manual
2.3.8 Releasing: Fast Release
Modules or detectors assigned to operate as a Fast Release function energize the releasing device without performing the delay.
2.3.9 Releasing: Halt
Modules assigned to operate as a Halt function are able to interrupt the releasing delay timer, thus preventing energization of the releasing device. Restoring the halt input does not allow the delay timer to restart; the releasing sequence remains halted. The halt function has no effect if it is activated after the delay time has expired.. The halt can only be cleared by resetting the panel.
2.3.10 Releasing: Abort
Modules assigned to operate as an Abort function are able to stop the delay timer when it reaches 10 seconds, thus preventing energization of the releasing device. Restoring the abort input allows the delay timer to restart. Subsequent activation of the abort input will again stop the timer. The Abort function has no effect if the delay timer has timed out.
2.4 User control interface
System control and programming can be done through the LCD annunciator on the panel. The main status display is an LCD screen with 8 line by 20 character text capability. Five system LEDs indicate alarm (red), alarm silence (red), supervisory alarm (red), trouble (yellow), and AC power (green). Ten zones of programmable alarm and trouble LEDs are located on the right hand side of the annunciator. A piezoelectric sounder provides audible annunciation of off-normal indications. LCD remote annunciators are similar and provide the same functionality as the panel’s local LCD annunciator.
Security is provided by a locking door or requiring activation of a keyswitch for most annunciator commands. Maintenance and programming functions are further protected by passwords.
2.4.1 Resets
There are three types of resets available.
Fast reset
If all events qualify as resettable, i.e. the condition that triggered the event is no longer present, a fast
Figure 2-1. LCD annunciator
4
Loading...
+ 18 hidden pages