Harrington Signal FHEX-24SMR User Manual

Commercial Products Group
document rev
2519-4th Ave, Moline, IL61265
800.521.8219 : 800.225.4109
www.cpglifesafety.com
INSTRUCTION SHEET
FHEXFHEX
FHEX
FHEXFHEX
VIBRATONE® EXPLOSION-PROOF VIBRATORY HORNVIBRATONE® EXPLOSION-PROOF VIBRATORY HORN
VIBRATONE® EXPLOSION-PROOF VIBRATORY HORN
VIBRATONE® EXPLOSION-PROOF VIBRATORY HORNVIBRATONE® EXPLOSION-PROOF VIBRATORY HORN
256884 0209
A
SAFETY MESSAGE TO INSTALLERS
Selection of mounting location for this device, its controls and routing of wiring should be made by the Facilities Engineer and the Safety Engineer. Listed below are some other important safety instructions and precautions you should follow:
This unit must be installed by a qualified electrician in accordance with NFPA 72, and National and local Elec­trical and Fire Codes, under the direction of the authority having jurisdiction.
Do not connect this unit to system wiring when circuits are energized.
For optimum sound distribution do not install this device where objects would block any portion of front of speaker.
All effective warning horns produce loud sounds which, in certain circumstancs, may cause permanent hearing loss. Take appropriate precautions such as wearing hearing protection. Recommendations in OSHA Sound Level Standard (29 CFR 1910) should not be exceeded.
After installation, ensure that all bolts threaded joints are tightened.
After installation and completion of initial system test, a program for periodic testing of this device must be established. Refer to NFPA 72, local Fire Codes and the authity having jurisdiction for this information.
After installation and completion of initial system test provide a copy of this instruction sheet to all personnel responsible for operation, periodic testing and mainte­nance of this equipment.
Failure to follow all safety precautions and instructions may result
in property damage, serious injury, or death to you and others.
A. GENERAL.
The Vibratone Model FHEX is a hazardous location, intermittent duty, polarized, 24 Volt dc, indoor/outdoor rated, high output, vibratory horn for use with fire alarm systems. This model is suitable for use in hazardous locations NEC Class I, Groups C, & D; Class II, Groups E, F and G and has factory sealed leads.
B. SPECIFICATIONS.
Operating 24 Vdc Voltage
Current 0.96A - 1.44 A Duty cycle 5 min. on—5 min. off Weight (approx.) 10 lb. (4.536kg)
Size 12" (305mm) high, 6-7/8"
Construction Heavy corrosion resistant cast
Approval Agency Listings:
Underwriters Laboratories Inc.
File E190785(Guide UJPX) Listed as a HAZARDOUS LOCATION AUDIBLE
SIGNAL FOR FIRE ALARM SERVICE. California State Fire Marshal—(Listing is pending.) New York City—(Listing is pending.)
Audibility: 94 dBA, UL omni-directional sound pressure rating.
116 dBA, Sound Power measurement. 100 dBA on axis at 10' in Anechoic chamber.
C. INSTALLATION.
1.
Unpacking.
damage that may have occurred in transit. If equipment has been damaged, immediately file a claim with carrier stating extent of damage. Carefully check all shipping labels and tags for special instructions before removing or destroying them.
Conduit connection can be made to 3/4" threaded opening in splicing condulet attached to this device (see figure 1).
After unpacking the horn, examine it carefully for possible
Property damage, serious injury or death could occur if this product’s explosion-proof housing is damaged. The horn mechanism contains no user serviceable parts. Therefore, DO NOT loosen or remove clamp ring, which holds mecha­nism into housing, or any of the six screws on the front of the horn grille. Loosening or removing any of these six screws may disturb factory adjustment of horn mechanism and cause the horn to malfunction. Attempting to remove the horn mechanism from the horn housing may damage the horn mechanism.
2.
Mounting Arrangements (see figure 1).
Property damage, serious injury, or death could occur if an accumulation of water, snow, dust, etc. resides in the horn’s grille, severely reducing or preventing operation of this device. Mount the unit so the grille is pointed horizontally or slightly downward.
This device can be mounted on any relatively flat surface.
(175mm) wide, 6" (152mm) deep.
aluminum enclosure. Splicing condulet, tapped for 3/4" conduit. Stainless steel diaphragm. Exterior painted with red enamel. Leads factory sealed.
WARNING
WARNING
- 1 -
256884
FHEX Instruction Sheet
WARNING
Property damage, serious injury, or death could occur if any objects are in front of the horn’s grille, severely reducing optimum sound distribution. For maximum effectiveness, ensure that the front of the grille is clear of obstructions.
a. Select mounting location.
b. Using the horn as a template, scribe drill position marks on the mounting surface. See figure 1 for mounting hole locations and dimensions.
CAUTION
Before drilling holes in any surface, be sure both sides of surface are clear of anything that could be damaged.
c. Drill holes at the previously scribed drill position marks to accommodate 3/8" diameter bolts.
d. Secure the horn to the mounting surface with 3/8" diameter hex head bolts, lockwashers, and hex nuts.
Electrical Connection.
3.
DANGER
To avoid electrical shock, do not connect wires when circuits are energized.
MOUNTING HOLE CENTERS
13/32" DIA. MOUNTING HOLES (2)
3/4" I.P.S. OUTLET
6-1/2"
45°
6"
7/8"
1/2"
12"
CONNECTIONS
Figure 1. Model FHEX Mounting Dimensions.
3. Provide a copy of these instructions for the Safety Engineer,
system operator(s) and maintenance personnel.
SAFETY MESSAGE TO OPERATORS
Even if your warning system is operating properly, it may not be completely effective. People may not hear or heed your warning signal. You must recognize this fact and ensure that your warning signal achieves its intended effect through proper test/training sequences within your specific application(s).
6-7/8"
REMOVABLE
COVER FOR
WIRE
290A2627-22
adhered to in the installation of this device. All electrical wiring must be
National Electrical Code as well as local codes must be routed through conduit and fittings approved for explosion-proof instal-
lations.
WARNING
Property damage, serious injury, or death could occur if independent conductors are terminated together; both wires of the same polarity must be used as two separate connec­tions. NFPA 72 requires that the wires be terminated inde­pendently to provide electrical supervision of the connection.
a. Remove splicing condulet cover. See figure 2. Connect the device’s red (+) leads to the power source positive (+) lead. Connect the device’s black (-) leads to the power source negative (-) lead.
WARNING
Property damage, serious injury, or death could occur if the condulet cover is not closed properly. To reduce the possibility of explosion, splicing condulet cover must be kept tightly closed while circuits are energized.
b. Replace splicing condulet cover and tighten.
D. TESTING/OPERATING.
WARNING
Under certain conditions these devices are capable of pro­ducing sounds loud enough to cause hearing damage. Ad­equate hearing protection should be worn if standing within close proximity to device while testing. Recommendations in the OSHA Sound Level Standard (29 CFR 1910) should not be exceeded.
1. After installation is complete, be sure to test the system to
verify that each horn operates satisfactorily.
E. MAINTENANCE.
SAFETY MESSAGE
TO
MAINTENANCE PERSONNEL
Failure to follow all safety precautions and instructions may result in property damage, serious injury, or death to you or others. People’s lives depend on your safe maintenance of our products. Read and understand all warnings in paragraph C. INSTALLATION. In addition, listed below are some other safety messages and precautions you should follow:
Read and understand all instructions before performing maintenance on this unit.
Do not perform maintenance on this unit when circuits are energized.
Periodic checks should be made to ensure that effective­ness of this device has not been reduced because speaker has become clogged with a foreign substance or because objects have been placed in front of the speaker.
Any maintenance to this unit MUST be performed by a trained electrician in accordance with NEC guidelines and local codes.
Never alter this unit in any manner. Safetyin hazardous locations may be jeopardized if additional openings or alterations are made to this device.
The nameplates, which contain cautionary or other information of importance to maintenance personnel, should not be obscured if exterior of device is painted.
1. Periodically check this device to verify that there are no
foreign substances in, or in front of, the horn’s grille which will reduce its effectiveness.
2. After completion of initial system test, establish a program for periodic testing of this device. Refer to NFPA 72G, local Fire Codes and the authority having jurisdiction for this information.
2. Testing should be periodically performed. Refer to NFPA 72G, local Fire Codes and the authority having jurisdiction for informa­tion.
- 2 -
Loading...
+ 1 hidden pages