Deep × width ×high165×802×262 Deep × width ×high165×802×262
Deep × width ×high260×760×540 All types
All types
Operation interface
Inner operation interface of Type HSAR
Inner operation interface of Type HSR
·Emergency operation button of indoor types:
Compulsory button
1) When the air-conditioner works with the absence of remote control, it
will stop working by pressing the compulsory button and it will resume
working by pressing the compulsory button once again.
2) When remote control is useless, you can adopt the compulsory
operation by which the air conditioner will go into automatic operation
mode.
·The operation interface of remote control:
Features of products
1. Fashionable appearance
2. Compact Design
3.7 Hours of Sleep Mode Operation
4. Economy Mode to Reduce Electrical Power Consumption
5.Clean breath efficient biological antibacterial filter gauze made
from green plant elite refined by using international leading
technology, with the function of filtering and suppressing bacteria,
and able to absorb and kill various pathogens and harmful gases
efficiently for a long period, prevent secondary pollution caused due
to microorganism spreading, and ensure the health of your family
6. R407c cold medium is applied, environment-friendly, and avoid
damages to ozonosphere
7. International famous-brand Toshiba Hitachi and Matsushita
compressors are applied
Chapter 2 Operating Principle
. Cooling
After the power supply is switched on, the machine is set to COOL
mode. With the compressor being operated, the low-temperature and
low-pressure refrigerant vapor is sucked into the compressor where it is
turned into high-temperature and high-pressure gas. Then it is cooled
down in the outdoor heat exchanger by the air and becomes liquid. After
being throttled by the capillary, the refrigerant liquid comes into the
indoor unit and then it evaporates in the indoor heat, exchanger,
absorbing heat and reducing the room temperature. The evaporated
refrigerant vapor returns to the outdoor unit and is again sucked into the
compressor, completing the cycle. With the refrigerant cycling being kept
on, the objective of lowering the room temperature is fulfilled.
. Heating
After the power supply is switched on, the machine is set to HEAT
mode and the coil of the electromagnetic four-way valve is energized.
After the compressor starts to operate, the high-temperature and
high-pressure refrigerant gas first comes into the heat exchanger of the
indoor unit, where it is cooled, releases heat and increases the room
temperature. The cooled high-pressure refrigerant is then throttle1d in the
outdoor unit and returns to the compressor after evaporation. With such
cycles being maintained, the objective of increasing the room temperature
is fulfilled.
Operation Hints
Chapter 3 operation details
1. Overall
1.1 Protection of compressor
Whatever operation modes the air- conditioner is under, there will
always be 3 minutes' time- delay protection unless it is on for the first
time. When the compressor is switched on, it can not be shut down
within 3 minutes (except under the modes of heating or defrosting)
unless it is powered off or its operation mode is changed.
1.2 The operation indicator will turn light when the air conditioner is
powered on.
1.3 The buzzer will sound immediately after the controlling device
receives a correct and effective signal sent by the remote control.
1.4 Timing function can be applicable to all operation modes while
sleep function can only be applicable to the modes of refrigeration
and heating.
2. Automatic operation mode
2.1 When the air conditioner works, it can detect the indoor temperature
automatically whereby its operation mode can be selected:
refrigeration, heating or dehumidification.
2.2 When the indoor temperature reaches more than 27, the air
conditioner will operate under the mode of refrigeration.
2.3 When the indoor temperature reaches between 20and 27the air
conditioner will work under the mode of dehumidification (always
mute).
2.4 When the indoor temperature reaches less than 20, the air
conditioner will work under the mode of heating.
2.5 Under this mode, the air conditioner will operate in the respect of
blowing rate as set and its pendulum leaves will work according to
the requirements of automatic ventilation door.
2.6 Once the operation mode is selected, it will not be able to be
changed. When the air conditioner is shut down and then restarted,
the operation mode will be selected once again based on the
variation of indoor temperature.
2.7 After the operation indicator has been flickering for 20 seconds, it
will turn light steadily (i.e. the determination of operation mode will
start in 20 seconds.)
2.8 This mode has timing function, does not have sleep function.
2.9 Under this operation mode, the temperature can be set and adjusted
by remote control.
3. Refrigeration mode
3.1 Under the refrigeration mode, the range of temperature set by
remote control is between 16and 32.
3.2 Shut-down of four-way valve;
3.3 The condition on which the compressor starts is that the indoor
temperature reaches more than the temperature set plus 1while the
condition on which the compressor shuts down is that the indoor
temperature reaches less than the temperature set minus 1.And
when the indoor temperature is equal to that set, the original
operation mode will be kept.
3.4 Under the mode of refrigeration, the function of preventing indoor
coiled pipe from being frozen will be effective.
3.5 The indoor wind speed will be as set. And the pendulum leaves will
work according to the instructions sent by remote control.
4. Dehumidification operation
4.1 The temperature range set and controlled is between 16and 32.
The temperature will be set by remote control.
4.2 The four-way valve is shut down.
4.3 The wind speed gear-changes to “mute". And the pendulum leaves
works according to the instructions sent by remote control;
4.4 The function of preventing indoor coiled pipe from being frozen is
effective.
4.5 When the indoor temperature reaches less than 16, the function of
dehumidification is out of use.
4.6 When the indoor temperature reaches more than 16 , the
compressor will be switched on and work intermittently. The time
when the compressor shuts down depends on T ring and T ring-T set.
When the compressor is shut down, the outdoor fan and indoor fan
will stop working.
When T ring≥23
T set <T ring-1, the compressor will be working for 8 minutes and then
stopping for 3 minutes in cycles.
T set≥T ring-1, the compressor will be working for 3 minutes and then
stopping for 6 minutes in cycles.
And when T ring <23
T set ≤T ring-1, the compressor will be working for 3 minutes and
then stopping for 4 minutes in cycles.
T set >T ring-1, the compressor will be working for 3 minutes and then
stopping for 6 minutes in cycles.
5. Function of ventilation control
5.1 Under the mode of ventilation, the outdoor fan assembly will
always be shut down.
5.2 The indoor fan will operate as set in the respect of air quantity
without the gear- change of “high power".
5.3 The pendulum leaves will work according to the instructions sent
by remote control.
6. Heating function
6.1 Under the mode of heating, the temperature range set is between 16
and 32. And the temperature will be set by remote control.
6.2 When the air conditioner is powered on, the outdoor fan, four- way
valve and compressor will start at the same time while when it is
shut down, the outdoor fan and compressor will be shut down at the
same time and so will the four- way valve after 2 minutes' delay.
6.3 Under the mode of heating, the compressor can not be shut down
within 3 minutes after it is powered on unless the operation mode is
changed or the air conditioner is turned off.
6.4 There is a 3 temperature compensating function. The temperature
measured at the in-blow vent minus 3 automatically can be
regarded as that compared with the temperature set (This function
does not exist under other circumstances).
6.5 According to the temperature set, the condition upon which the
compressor will be switched on is indoor temperature≤ temperature
set-1 While the condition upon which it will be switched off
is indoor temperature is indoor temperature≥ temperature + 1.
When the indoor temperature is equal to that set, the original
operation mode will be kept.
6.6 Indoor fan control:
6.6.1 Heating operation and prevention of cold wind
When the compressor works:
1. During the rising process of the temperature of coiled pipe,
the indoor fan will not start if the temperature of the coiled
pipes is less than 25.
2. When the temperature of coiled pipe reaches less than 35
But more than 25, The indoor fan will work under the
mode of “ mute". If the temperature of coiled pipe ascends
to 25and then descends, it will stop working only when
the temperature is lowered to 22.
3. When the temperature of coiled pipe reaches more than 35
, the indoor fan will operate as set in the respect of wind
speed. If the temperature of coiled pipe ascends to 35
And then descends, it will enter into the operation mode of
“ mute" only when the temperature is lowered to 30.
6.6.2 Afterheat-blowing function:
6.6.2.1 When the compressor stop working:
1. When the temperature of coiled pipe is more than 35, the indoor
fan will operate as set in respect of wind speed.
2. When the temperature of coiled pipe is more than 25, but less
than 35, The indoor fan will operate under the mode of “ mute"
3. When the temperature of coiled pipe is less than 25, the indoor
fan will stop working.
6.6.2.2 The afterheat-blowing function when the air conditioner is just
shut down: If the temperature of indoor coiled pipe reaches more
than 30, The indoor fan will operate under the mode of “ mute"; If
it lowers to less than 30, the indoor fan will be shut down; And the
time when the afterheat blows will last less than 40 seconds after
the indoor fan is turned off.
6.7 Defrosting operation:
6.7.1The conditions upon which the outdoor sensor goes into operation are
as below:
1. Under the circumstance of heating, if T external coiled pipe is at the
temperature of less than -6 which lasts 2 minutes and the
accumulated working time of compressor reaches more than 50
minutes (if there is any power cut-off or shut-down by remote
control, the accumulated working time of compressor shall be
re-calculated), the defrosting interval will be more than 50 minutes
and the compressor will be working 5 minutes continually.
2. If there is any damage to the external coiled pipe, the accumulated
working time of compressor will reach 50 minutes (if there is any
power cut-off, shut-down by remote control or defrosting, the
accumulated working time of compressor shall be re-calculated)
and the defrosting operation will last 10 minutes.
6.7.2 Once one of the following conditions is satisfied, the defrosting will
end:
1. The temperature of T external coiled pipe is more than 12.
2. Defrosting duration is more than 12 minutes.
6.7.3 The requirements of defrosting operation:
1. Sleep indicator flickers at the speed of 1 time per second
2. When defrosting operation starts, the compressor and indoor fan
will stop working while outdoor fan and four-way valve will
continue to work.
3. The four-way valve and outdoor fan will stop operating in 30
seconds.
4. 15 seconds after that, the compressor starts and goes into
defrosting operation.
5. After the defrosting ends, the compressor stops working. And
the four-way valve and outdoor fan begins to work in 20
seconds.
6. 20 seconds after that, the compressor starts and goes into heating
operation. And the indoor fan enters into the prevention mode of
cold wind.
6.8 Auxiliary electric heating function
6.8.1 Only if the following conditions are satisfied under the
heating operation, can the auxiliary electric heating go into
operation automatically.
a. The compressor works for 4 minutes by heating pump
b. Indoor temperature is less than 22;
c. The temperature set-indoor temperature is more than 3;
d. Indoor fan goes into operation;
e. Indoor coiled pipe temperature is less than 48
6.8.2 Once one of the following conditions is satisfied, auxiliary
electric heating operation will end:
a. Indoor temperature is more than 22.
b. The temperature set –indoor temperature is less than 2.
c. When Indoor coiled pipe temperature is more than 52, the
electric heating operation will end.
d. Indoor temperature sensor becomes abnormal.
6.8.3 If compressor or indoor fan stops working, the electric
heating will stop operating as well.
6.8.4 During the operation of compressor, if the auxiliary electric
heating stops working, it can be restarted only in 1 minute.
7. Sleep operation
7.1 When the air conditioner enters into the mode of sleep, the indoor
wind speed will turn into the air quantity of “mute”.
7.2 When the sleep operation goes under the mode of refrigeration,
the temperature set rises by 1 automatically every one hour. And
the air conditioner will be powered off after sleep mode has
worked for 7 hours.
7.3 When the sleep operation goes under the mode of heating, the
temperature set drops by 2 automatically every one hour. And the air
conditioner will be powered off after sleep mode has worked for 7
hours.
7.4 When the button of mode selection is pressed down, the function
of sleep will be cancelled.
7.5 Sleep operation is effective under the modes of refrigeration and
heating. When sleep button is pressed down, the sleep operation
can begin or end.
7.6 Sleep function does not exist under the automatic mode, the
situation of dehumidification or the circumstance of ventilation.
8. Timing operation
8.1 When timing is set, timing indicator will turn light.
8.2 The time set by timing is 12 hours at most. The timing unit is 1
hour. Even if the operation mode is changed, the timing function
will still work.
8.3 Power-off at a fixed time
The power-off at a fixed time can be set only if the air conditioner
is on. And it continues to work though the power-off at a fixed
time has been already set. When it comes to the fixed time, the
indoor and outdoor fans will be shut down.
8.4 Power-on at a fixed time
The power-on at a fixed time can be set only if the air conditioner
is on. And it continues to be off though the power-on at a fixed
time has been already set. When it comes to the fixed time, the
indoor and outdoor fans will start to operate.
9. Emergency switch
When the soft-touch switch is pressed, the air conditioner will be
powered on and the operation indicator will flicker (1 time per
second). And it goes into the mode of automatic operation in 20
seconds. When the soft-touch is pressed once again, it will be
powered off. When the air conditioner goes under the mode of
automatic operation, the air door will assume the appearance of
automatic air door. Under the mode of heating or refrigeration,
the temperature set will be 24 and the wind speed will turn that
under the “high power” mode. Under the dehumidification
operation, the temperature set will be T ring-2 and the air
conditioner can work upon the instructions sent by remote
control.
10. Overload control and various protection functions:
10.1 Temperature control (overheat protection).
10.1.1 This function can only be applied to the mode of heating, not
others.
10.1.2 When the temperature of indoor coiled pipe reaches more than
57, outdoor fan will stop working.
10.1.3 When the temperature of indoor coiled pipe drops to less than
52, outdoor fan will resume to operate normally.
10.2 Temperature cut-off control function (overheat protection)
10.2.1 This function can only be applied to the mode of heating, not
others.
10.2.2 When the temperature of indoor coiled pipe reaches more than
64which lasts more than 10 seconds, the compressor and
outdoor fan will all stop working.
10.2.3 After 3 minutes’ shut-down, the compressor will resume to
operate if the temperature of indoor coiled pipe drops to less than
52.
10.3 Function of preventing indoor coiled pipe from being frozen
(supercooling protection).
10.3.1 This function can only be applied to the operation mode of
refrigeration or dehumidification, not others.
10.3.2 When the temperature of indoor coiled pipe drops to -2
which lasts more than 2 minutes, the compressor will stop
operating and the indoor fan will go by air quantity set.
10.3.3 When the compressor stops working, it can only be restarted
only if the temperature of indoor coiled pipe rises to more than 7
or the power-off of the compressor lasts more than 6 minutes.
10.4 Protection function of short or open circuit of temperature senor
10.4.1 Powered on, when it is detected that the T ring signal sent by
indoor environment temperature senor is abnormal, the air
conditioner will work under the mode of heating and will not be
powered off if the signal received from remote control is
“heating” or it will work under the mode of refrigeration and will
not be powered off if the signal received from remote control is
“refrigeration” or it will work for 8 minutes and then stop for 3
minutes with the wind speed of “mute cycle dehumidification” if
the signal received from remote control is “dehumidification”.
Besides, the signal of automatic mode sent by remote control
will not be effective, nor will the signal of automatic button
power-on and the related breakdown can be indicated at the
same time.
10.4.2 When it is detected that the T internal coiled pipe signal sent
by indoor coiled pipe temperature sensor is abnormal, the
freezing-proof, cold-wind-proof and overheat-proof functions
will be screened. Under the mode of heating, when the
compressor is powered on, indoor fan will be started after 30
seconds’ delay with the wind speed as set while when
compressor is powered off, indoor fan will be turned off after 30
seconds’ delay and the related breakdown can be indicated at the
same time.
10.4.3 When it is detected that the T external coiled pipe signal sent
by outdoor coiled pipe temperature sensor is abnormal, the air
conditioner will work for 50 minutes, defrost for 10 minutes and
heat in cycles if the signal received from remote control is
“heating” and the related breakdown can be indicated at the
same time while the air conditioner will not be powered off and
will operate normally if the signal received from remote control
is heating or defrosting or ventilation and the related breakdown
can be indicated at the same time.
10.5 disposal of indoor PG electric motor abnormity
When indoor PG electric motor is loaded with voltage, the indoor
fan will operate under the mode of “weak wind” automatically if
the pulse signal feed backed by the indoor electric motor is not
detected within 12 seconds. If the feedback signal detected is
normal, the indoor fan will resume the turning speed set and the
related breakdown indication will be disappear.
10.6 Function of charatron display
When the controller is normal, there will be no charatron display
under the circumstance of power-off. When air conditioner is
powered on, the charatron will display room temperature under the
normal situation. If the temperature set is changed, the charatron
will show the temperature set which sparkles at the rate of 1 time
per second. Then it will display room temperature once again in 5
seconds. The display range of room temperature is 0~79.
11. Function of breakdown indication
HS, HSA series (charatron); HV (VFD display)
Breakdown cause Display way Display priority
class
PG feedback abnormity
T ring abnormity
T internal coiled pipe
abnormity
T external coiled pipe
abnormity
E4 1
E1 2
E3 3
E2 4
12. Adjustment function of air door direction by pendulum
leaves
12.1 When the air conditioner is powered on for the first time, the
pendulum leaves will move to the direction of full-opening and then
to the direction of full-closing wherever they are placed.
12.2 When the air conditioner is powered off, the pendulum leaves will
move up to “close” position immediately wherever they are placed
after the fan comes to an end.
12.3 Under the mode of refrigeration, the pendulum leaves will first move
to the full-opening position and then move to the horizontal position
and at last move under the mode set while under the mode of heating,
they will first move to the full-opening position and then backswing by
5 and at last work under the mode set (for details, please see the
following diagram).
12.4 Pendulum wind: automatic air door and manual air door will be
controlled by one button.
12.5 When the pendulum leaves move from full-opening position to
full-closing position at the time of power-on or from starting position
to full-closing position at the time of power-off, the speed will be 20
per second while the speed under the instruction situation will be 5
per second.
Swing angle under the mode of refrigeration: BD is 35±2
Swing angle under the mode of heating: FC is 40±2
Backswing angle under the mode of heating: EF is 5
13.Self-checking function of controller
After the automatic button is pressed, the air conditioner will be
powered on and enter into the process of self-checking:
Buzzer sounds two times→ operation indicator turns on → timing
(2) Press the TEMP/TIME button, set the time. When “ON” stops
intermittently, the “Timer ON” can be set.
Set the “Timer OFF” (it operates only when the air-conditioner is
running.)
(1) Press the TIMER button, select the “Timer OFF”, the remote control
display “00 HOUR OFF”; “OFF” displays intermittently at the same
time.
(2) Press the TEMP/TIME button, set the time. When “OFF” stops
intermittently, the “Timer OFF” can be set.
Remark: The remote control can only be set within 12 hour intervals.
Sleeping operation mode
(1) Press the SLEEP button, the sleeping indicator light of indoor unit
flashes.
(2) After the setting of sleeping mode, the cooling operation enables the
set temperature to increase 1
o
C after 1 hour and another 1 oC
automatically after another hour.
(3) After the setting of sleeping mode, the cooling operation enables the
set temperature to increase 2
after 1 hour and another 2
automatically after another hour.
(4) The air-conditioner runs in sleeping mode for 7 hours and stop
automatically.
Remark: 1. in sleeping mode the fan speed changes automatically to
“Mute”.
2. Press the MODE button, WIND button or ON/OFF button, the
remote control clears sleeping mode away.
Attention:
Aimed the remote control at the receiver on the air-conditioner.
The remote control should be within 8 meters away from the
receiver.
No obstacles between the remote control and receiver.
Don’t drop or throw the remote control.
Don’t put the remote control under the strong sunrays or heating
facilities and other heating sources.
Use two AAA batteries, don’t use rechargeable batteries.
Take the batteries out of remote control before stop using for long.
When the noise of transmitting signal can’t be heard from indoor
unit or the transmission symbol on the display screen doesn’t
flare, batteries need be replaced.
If reset phenomenon occurs on pressing the button of the remote
control, power of the batteries is deficient and need to be
replaced.
NOTE: 1.Specifications are standard values calculated based on rated
operation conditions, they will vary in different working condition
2. Our company has quick technical improvement. There will be no
prior notice for any change of technical data. Please read the
nameplate on the air conditioner
Chapter 6 Dismantling Procedure
Indoor Unit
Operating step Photo
1. To remove the panel and connecting wire
cover.
· Take off the screws of the connecting wire
cover and remove the cover.
· Then remove the panel.
2. To remove the air filter.
3. To remove the inter frame assembly
Take off three screws of inter frame
assembly
Then take off the inter frame assembly
4. To remove the electric control box
Take off one screw
Loose one obverse clip
Remove the electric control box
5. To remove the water-collecting plate
assembly
Loose three obverse clips
Take off the electric control box
6. To remove the evaporator assembly
Take off one screws of right locating
cover and two screws of left locating
cover
Remove the pipe strap
Remove the evaporator assembly
7. To remove the through-flow fan
Take off the screws of though-flow fan
Remove the though-flow fan
8. To remove the motor
Take off three screws of right locating
cover
Remove the motor
Outdoor Unit
Operating step Photo
1. To remove the top cover assembly
Take off six screws of top cover
2. To remove the panel assembly
Loose screws of panel assembly
Take off panel
3. To remove the right plate assembly
Loose nine screws of left plate
assembly
Take off right plate
4.To remove the axial-flow fan and fan
motor
5.To remove the electric assembly
Chapter 7 Brief introduction of installation
The installation of air-conditioner shoul d meet with the “Installation Instruction”.
The machine must be installed correctly by professional technicians according to the “Installation
Instruction”.
Guide to customer
zThe customer should provide a suitable power supply source, its voltage should be in the
range of 90-110% of its rated voltage.
zThe power supply circuit should have MCB leakage protection. The capacity should be more
than 1.5 times of the maximum current.
zMust use independent circuit and suitable grounding socket matching with the plug of
air-conditioner.
zThe wiring must be installed by qualified electrician according to the electrical safety
requirements.
zThe air-conditioner must be well grounded, the switch of the main power of air-conditioner
must be reliably grounded.
zThe power supply wire, must be changed by qualified electrician.
Installation Instruction
Installation order:
Selection of the installation position Installing the air-conditioner
Expelling the air in the pipes and the indoor unit Connecting the pipes and wires
Testing
Selection of the installation position
Indoor Unit
zThere is no heating and steaming source
nearby.
zNo obstacles for installation position
from nearby.
z Keep good air circulation.
z Convenient to adopt measures to reduce
noises.
zDon’t install them near the
doorway.
zMake sure to have the distance
specified in the picture between the ceiling,
wall, furniture and other obstacles.
z2 meters high above the floor.
Outdoor Unit
zIn case that you put up a canopy to protect it from rains and sunrays, pay attention not to
cause any obstacles for the heating dispersion for the condenser.
zDon’t keep animals or plants near the installa tion location for the hot air from the out door unit
will affect them.
zMake sure to have the distance specified in the picture between ceiling, wall, furniture and
other obstacles.
z Stay away from heating source and inflammable air.
z The installation base and supporting frame should be strong and secure. The machine should
be at a level surface.
Installation of the Outdoor Unit
zThe outdoor unit must be firmly fixed to
avoid falling in strong wind.
zInstall on the cement base as in the
drawing.
zIf it is installed at seaside or at a place high
above the ground and with strong wind, the AC should be in stalled agai n st the wal l to ensu re
the normal operation of the fan and the blocking plate should be used.
zIf it is an overhanging installation , the str ucture of th e mounting wall should b e made of s olid,
cement or materials with equivalent strength, and of sufficient support capacity. Otherwise,
measures such as reinforcement, support or vibration damping should be adopted.
Installation of the Indoor Unit
zFirst make changes to wall and make sure th at is hard and secure. Using four “+” type screws
to fasten the installation board onto the wall. Keep it level in horizontal direction and
perpendicular in vertical dire cti on. Otherwise it might cause w at er drips when air-co nd iti oner
is running in cooling operation.
zDrill 70mm diameter pipe hole at the left lower or right lower side of the installation board.
The hole shall slant outward slightly.
z Hang the indoor unit to the board and make sure the
machine is in the middle of the
board.
z Push the machine towards
the left lower and right lower
side of the installation board
until the hangers enter tightly
into the grooves (it produces
“click” sound)
Check the water discharge
1. Take off the frame from the unit
cover.
Take off the front frame for
maintenance according to the
following steps:
z As shown in the picture on the right, take off two covers from the front frame and then
unfasten two fixture screws.
z Pull the front frame towards yourself and take it off.
To put the front frame back, reverse the steps.
You should check whether the front frame is firmly fixed into the fixture groove on the top.
2. Check the water discharge
z Pour a cup of water into groove.
z Check whether the water flow through the water discharge hole.
Pipe Connection
zConnect the pipe to the unit: point to the center of
pipe and fasten the connectio n screw at first by
hand and then by wrench until it is tightly
fastened. The fastening direction is shown in
the picture.
zPointing towards the center of pipe, fasten the screw
with strength.
zWrench the screw in the end until you hear th e
“click” sound.
The fixing of pipe
zWrap up all pipe, water discharge and
connection wire from top to below.
zCover the connection parts with
insulation material and fix them with two
plastic rings.
zWrap up the pipes with tape alongside the wall
and fix them to the wall with clips. These
steps are usually adopted when outdoor unit is installed below the indoor unit.
zIn case that you want to have additional water discharge pipe, the end of pipe should be
within certain distance from the floor (to prevent water from draini ng back into the pipe). Fix
it onto the wall so it won’t be swayed by wind.
zWrap the pipes and connection wire well from
below to top.
zWrap up the pipes that are rounded up in the
way shown in the picture so it can prevent
water from entering the room.
zUse clips or other fixture to fasten the pipes
to the walls.
Expelling the air in the pipes and the indoor unit
Expelling the air: humid air in the refrigerating system might cause trouble of compressor.
zTake off the cover from the stop valve
and T -branch valve.
zTake off the auxiliary cover from the
T-branch valve.
zTurn the stop valve rod anti-clock wise to
an angle of 90 degree, keep it open for 8
seconds and close the valve.
zCheck whether there is air leakage at all
connection parts of pipes.
zPush the top rod of T-branch valve by
hexagon wrench to expel air.
z Repeat the third and fifth steps.
z Open the stop and T-branch valve with a hexagon wrench to make the unit operate.
z No leakage is allowed, please check all the piping connecti on parts. You must test the leakage,
generally, it can be tested by soap water.
Electrical connection
z Unscrew the screw, take off the control panel cover from the unit.
z Cooling type: connect the wire to the relate d connection point on the panel and conne ct the
signal connection plug.
Remarks: yellow and green cord should be connected to connection point with mark.
z Fasten the fixture of wire to control panel.
z Screw up the control panel cover to its original place.
Test running
z Make sure that the pipes and wires are connected.
z Make sure that both the liquid valve and gas valve on the side are completely open.
1. The connection of power source
¾ Connect the wire to independent power source socket.
¾ Preparation of remote control.
¾ Run the air-conditioner in cooling operation mode for 30 minutes or longer.
2. Performance evaluation
¾ Test the out and in air temperature.
¾ Make sure that the temperature difference between the out and in air is grea ter than 8
o
C.
Items of attention
z Fix the machine firmly, otherwise it will produce noise and vibration.
z Install the outdoor unit where it will not disturb your neighbor.
Electrical connection diagram:
COOL SERIES HEAT PUMP
Indoor unit electric connection diagram
COOL SERIES HEAT PUMP
Outdoor unit electric connection diagram
Chapter 8 Fault Analysis of the Product Available and
Typical Examples
1 Procedure of deciding the faults
Before maintaining the air conditioner, firstly you should know the
phenomena of the faults, decide the location of the faults, analyze the
reason the faults occur, and then search for ways to solve the faults. The
detailed procedures are: Look, Listen, Touch, Measure, Analyze
Look: Observe air conditioner’s running. I.e., vibration;
condensation on evaporator; leakage; electrical and mechanical
connection, etc.
Listen: Listen to kinds of sounds of the running air conditioner.
Identify the abnormal noise from the sounds.
Touch: Touch the key position and position faulty. Touch the temp
of air circulation to decide the heating or cooling effect; as far to
abnormal sound, besides adopt “listen”, you should touch the frame, the
pipe of the air conditioner to feel the vibration. Touch the easily heated
parts, i.e. compressor, motor, touch them to feel the temp.(Wa rning: High
temp).
Measure: Measure the parameters of the air conditioner and
relevant parts by some instruments. Usually used instruments:
amperemeter, voltmeter multimeter thermometer, etc, i.e., Use
multimeter to test whether the capacitor is open, the insulation of the wire
and the parameters of other electrical parts; use the thermometer to
measure temp of airflow.
Analyze: Analyze the above results, decide the reason and location
of faults, and seek the solutions.
2 Types of Normal Faults
The type of faults is various. The normal faults can come down to six
types: leaks, block, open circuit, burnt, lock, scrape.
LeakMainly is leakage of R407C from cooling pipe system and
parts; leakage of condensation water from indoor units; electrical leakage
from electrical system and wires.
BlockMainly is block of the pipe system, block of capillary, block
of strainer or valve.
Open CircuitMainly is open circuit of electrical circuit, include:
fuse blowing out, connectors broke.
BurntMainly is burnout of fan motor, of compressor, of capacitor,
of transformer.
LockMainly is lock of compressor, four-way valve.
ScrapeMainly is scrape of indoor/outdoor fan and nearby parts,
and sound abnormally.
3 Examples
3.1 Leakage and seepage of indoor unit
Reason Check to be made Proposed remedy
Improper installation.
Indoor drain position is
lower than outdoor or
slanting installation of
indoor unit
Water collecting plate is
blocked
Water collecting plate or
drain pipe is cracked
Loosen wrap belt,
heat-preservation layer is
bad or layer behind indoor
units is bad
High ambient relative
humidity, low temp/speed
of air flow
Observe if the
condensation water drain
out, if the indoor unit is
declining
Check if the plate is
blocked
Check the location, ensure
if it is cracked
Connecting pipe bleed the
water, condensation water
exists behind the indoor
unit, the wall is wet and
turn colors
Water is blow out from air
outlet, or water drips from
the outlet. Lower speed of
air flow
Level the indoor unit and
adjust the height
Remove the matters block
the plate
Replace the plate or pipe
Rewrap the connecting
pipe, add new
heat-preservation layer
Suggest set the units to
dehumidifying mode at
high speed of air flow, to
lower relative humidity;
if the high speed is still
felt lower, the fan motor
must be checked
3.2 Poor cooling or heating effect
Reason Check to be made Proposed remedy
The cooling/heating load of
the room is heavy or the
room is not closed perfectly
Calculate the area of the
Enlarge the capacity of
the units, improve the
room, check the close of the
leakproofness of the
room
room
Insufficient refrigerant
R407C
Measure the operating
current
Air intake temp is too low,
condensation water on air
Too much R407C
intake pipe is too much,
temp of discharge is too high
Effect of heat exchange is
too poor
Some of the windings of
motor fan is short-circuit,
so cause speed decline
Dust on outdoor condenser
and indoor filter is too much
Speed of indoor/outdoor fan
is too low, air circulation is
small
Check if the installation is
Running condition is too
proper; outdoor temp is too
bad
high when heating
No high-low pressure
Convexity exists in
compressor or valve or lock
of compressor
difference, no clear temp
difference in air intake inlet
or discharge outlet of
compressor
Openness of check valve is
too small or the system
partly or completely
Check the openness; partly
frost on outdoor pipe system
blocked
3.3 Big noise or abnormal sound
Reason Check to be made Proposed remedy
Foreign matters in wind
Check if they are Clear away
guide or impeller fan
Fan is distorted or in bad
Check them
balance
Open the unit or move the
Improper location of fan, so
fan manually, find the
fan touches the housing
location
Bearing of the fan is
Check the bearing Replace the bearing
sluggish or destroyed
Add R407C welding
the leaked point
Discharge a little
R407C
Cleanup filter and
condenser
Repair or replace motor
Improve the condition,
use auxiliary heating
Replace compressor or
valve
Open the valve; use
high pressure N
to
2
clean out the block
Replace indoor/outdoor
fan
Adjust the position
Connecting pipe vibrates
due to improper
installation, or touch the
lower frame
Outdoor pipes touches
Abrasion of the parts of
compressor
3.4 Frequently switch on/off of the compressor
Reason Check to be made Proposed remedy
Running voltage is too low Measure the voltage
Discharge temp is too high
caused by insufficient of
R407C, compressor is
protected by overheat
Temp sensor is too close to
evaporator or moved
Air inlet/outlet of heat
exchange is blocked or low
speed of fan motor; indoor
air filter is too dirty or
blocked
Too much R407C
Bad insulation of
compressor, high operating
current, overcurrent proof
Improper temp set
3.5 Promptly protected by halt after compressor starts
Reason Check to be made Proposed Remedy
Insufficient R407C
Mixed with air in the
system, vacuum is not good
Check the connecting pipe
Check the vibration of the
pipes, check if them touch
Check if the sound of
compressor is normal
Check condensation of air
intake pipe or measure if
operating current is lower
than rated current
Check the position of
sensor
Check indoor/outdoor heat
exchange, speed of motor,
air inlet/outlet
Too much condensation
water on air intake pipe,
high operating current
Check start or operating
current
Check actual ambient
temp
Little or no condensation
water on air intake pipe,
operating current is lower
than rated current
Power varies when
running
Tidy up the pipes,
eliminate the noise source
Tidy up the pipes
Replace the compressor
Add measures of voltage
stabilization
Check leakage point,
welding or add R407C
Adjust the position or
replace the sensor
Cleanup the filter, remove
the obstacle
Discharge a little R407C
Replace compressor
Reset
Add R407C
Vacuumize the system,
recharge R407C
Blocked caused by water or
impurity
Damaged compressor, high
start current
3.6 The units blow out cool air when in heating mode
Reason Check to be made Proposed Remedy
Operating current is lower
than rated current, part of
the unit frosts heavily
Check the windings and
insulation of compressor
and if it is locked
use high pressure N
to
2
clean out the block,
revacuumize and recharge
R407C
Replace the compressor
Four-way valve doesn’t
work
Listen to the units if there
is sounds of valve’s
working when heating or
cooling
Faults of control interrupter
Check the circuit Repair or replace the
or other relevant circuits of
the valve
Insufficient R407C causes
the insufficient heating
capacity
Little condensation water
on outdoor air intake pipe,
low operating current
Connexity of compressor Same temp of air intake
inlet and discharge outlet
of the compressor, no
condensation in air intake
inlet
3.7 The units doesn’t work
Reason Check to be made Proposed Remedy
Bad connection of the
power plugs, or no power
Check the socket Repair or replace
plug
Outdoor fuse or indoor fuse
Check if the fuse is good Replace the fuse
is burnt
Low voltage Measure the voltage
Measure actual indoor
temp, compare to the set
temp(in cooling set temp
Wrong indoor tem p set
should be lower than the
actual, in heating, is
higher)
Replace the valve
control board
Add R407C
Replace the compressor
Heighten the voltage of
the power supply system
Reset the temp
Wrong running mode of
indoor units set
3.8 Cannot receive the remote control signal
Reason Check to be made Proposed Remedy
Check if running mode of
two indoor units is the
same( it is not available if
one is heating and another
is cooling
Reset
Damaged remote control or
low battery
Short-circuit of connections
of main control board to
switch board
Running mode of two
indoor units is not the same
Indoor units are in test
mode
RemarksThe above mentioned “faults” are the faults possibly occur, we
will continue to collect the faults and analysis.
Check if the indication is
normal
Replace the remote
control or battery
Check the board Replace the components
Check if one is heating
Reset
and another is cooling
Open the air intake grill to
see the running mode
Adjust test mode to
remote control mode
CONTENTS
Chapter 1 photos and Features of products
Chapter 2 Operating Principle
Chapter 3
Chapter 4
Chapter 5
Chapter 6
Chapter 7
Chapter 8
operation details
Exploded Views of the Production
Main Technical Data
Dismantling Procedure
Brief introduction of installation
Fault Analysis of the Product Available
Chapter 1 photos and Features of products
Features of outlook and construction
ASW-H12A4/HSAR ASW-H12A4/HSR
ASW-12A4/HSAR ASW-12A4/HSR
Deep × width ×high176×890×296 Deep × width ×high176×890×296
Deep × width ×high260×760×540 All types
All types
Operation interface
Inner operation interface of Type HSAR
Inner operation interface of Type HSR
·Emergency operation button of indoor types:
Compulsory button
1) When the air-conditioner works with the
absence of remote control, it will stop
working by pressing the compulsory button and it will resume working
by pressing the compulsory button once again.
2) When remote control is useless, you can adopt the compulsory
operation by which the air conditioner will go into automatic operation
mode.
·The operation interface of remote control:
Features of products
1. Fashionable appearance
2. Compact Design
3.7 Hours of Sleep Mode Operation
4. Economy Mode to Reduce Electrical Power Consumption
5.Clean breath efficient biological antibacterial filter gauze made
from green plant elite refined by using international leading
technology, with the function of filtering and suppressing bacteria,
and able to absorb and kill various pathogens and harmful gases
efficiently for a long period, prevent secondary pollution caused due
to microorganism spreading, and ensure the health of your family
6. R407c cold medium is applied, environment-friendly, and avoid
damages to ozonosphere
7. International famous-brand Toshiba Hitachi and Matsushita
compressors are applied
Chapter 2 Operating Principle
. Cooling
After the power supply is switched on, the machine is set to COOL
mode. With the compressor being operated, the low-temperature and
low-pressure refrigerant vapor is sucked into the compressor where it is
turned into high-temperature and high-pressure gas. Then it is cooled
down in the outdoor heat exchanger by the air and becomes liquid. After
being throttled by the capillary, the refrigerant liquid comes into the
indoor unit and then it evaporates in the indoor heat, exchanger,
absorbing heat and reducing the room temperature. The evaporated
refrigerant vapor returns to the outdoor unit and is again sucked into the
compressor, completing the cycle. With the refrigerant cycling being kept
on, the objective of lowering the room temperature is fulfilled.
. Heating
After the power supply is switched on, the machine is set to HEAT
mode and the coil of the electromagnetic four-way valve is energized.
After the compressor starts to operate, the high-temperature and
high-pressure refrigerant gas first comes into the heat exchanger of the
indoor unit, where it is cooled, releases heat and increases the room
temperature. The cooled high-pressure refrigerant is then throttle1d in the
outdoor unit and returns to the compressor after evaporation. With such
cycles being maintained, the objective of increasing the room temperature
is fulfilled.
Operation Hints
Chapter 3 operation details
1. Overall
1.1 Protection of compressor
Whatever operation modes the air- conditioner is under, there will
always be 3 minutes' time- delay protection unless it is on for the first
time. When the compressor is switched on, it can not be shut down
within 3 minutes (except under the modes of heating or defrosting)
unless it is powered off or its operation mode is changed.
1.2 The operation indicator will turn light when the air conditioner is
powered on.
1.3 The buzzer will sound immediately after the controlling device
receives a correct and effective signal sent by the remote control.
1.4 Timing function can be applicable to all operation modes while
sleep function can only be applicable to the modes of refrigeration
and heating.
2. Automatic operation mode
2.1 When the air conditioner works, it can detect the indoor temperature
automatically whereby its operation mode can be selected:
refrigeration, heating or dehumidification.
2.2 When the indoor temperature reaches more than 27, the air
conditioner will operate under the mode of refrigeration.
2.3 When the indoor temperature reaches between 20and 27the air
conditioner will work under the mode of dehumidification (always
mute).
2.4 When the indoor temperature reaches less than 20, the air
conditioner will work under the mode of heating.
2.5 Under this mode, the air conditioner will operate in the respect of
blowing rate as set and its pendulum leaves will work according to
the requirements of automatic ventilation door.
2.6 Once the operation mode is selected, it will not be able to be
changed. When the air conditioner is shut down and then restarted,
the operation mode will be selected once again based on the
variation of indoor temperature.
2.7 After the operation indicator has been flickering for 20 seconds, it
will turn light steadily (i.e. the determination of operation mode will
start in 20 seconds.)
2.8 This mode has timing function, does not have sleep function.
2.9 Under this operation mode, the temperature can be set and adjusted
by remote control.
3. Refrigeration mode
3.1 Under the refrigeration mode, the range of temperature set by
remote control is between 16and 32.
3.2 Shut-down of four-way valve;
3.3 The condition on which the compressor starts is that the indoor
temperature reaches more than the temperature set plus 1while the
condition on which the compressor shuts down is that the indoor
temperature reaches less than the temperature set minus 1.And
when the indoor temperature is equal to that set, the original
operation mode will be kept.
3.4 Under the mode of refrigeration, the function of preventing indoor
coiled pipe from being frozen will be effective.
3.5 The indoor wind speed will be as set. And the pendulum leaves will
work according to the instructions sent by remote control.
4. Dehumidification operation
4.1 The temperature range set and controlled is between 16and 32.
The temperature will be set by remote control.
4.2 The four-way valve is shut down.
4.3 The wind speed gear-changes to “mute". And the pendulum leaves
works according to the instructions sent by remote control;
4.4 The function of preventing indoor coiled pipe from being frozen is
effective.
4.5 When the indoor temperature reaches less than 16, the function of
dehumidification is out of use.
4.6 When the indoor temperature reaches more than 16 , the
compressor will be switched on and work intermittently. The time
when the compressor shuts down depends on T ring and T ring-T set.
When the compressor is shut down, the outdoor fan and indoor fan
will stop working.
When T ring≥23
T set <T ring-1, the compressor will be working for 8 minutes and then
stopping for 3 minutes in cycles.
T set≥T ring-1, the compressor will be working for 3 minutes and then
stopping for 6 minutes in cycles.
And when T ring <23
T set ≤T ring-1, the compressor will be working for 3 minutes and
then stopping for 4 minutes in cycles.
T set >T ring-1, the compressor will be working for 3 minutes and then
stopping for 6 minutes in cycles.
5. Function of ventilation control
5.1 Under the mode of ventilation, the outdoor fan assembly will
always be shut down.
5.2 The indoor fan will operate as set in the respect of air quantity
without the gear- change of “high power".
5.3 The pendulum leaves will work according to the instructions sent
by remote control.
6. Heating function
6.1 Under the mode of heating, the temperature range set is between 16
and 32. And the temperature will be set by remote control.
6.2 When the air conditioner is powered on, the outdoor fan, four- way
valve and compressor will start at the same time while when it is
shut down, the outdoor fan and compressor will be shut down at the
same time and so will the four- way valve after 2 minutes' delay.
6.3 Under the mode of heating, the compressor can not be shut down
within 3 minutes after it is powered on unless the operation mode is
changed or the air conditioner is turned off.
6.4 There is a 3 temperature compensating function. The temperature
measured at the in-blow vent minus 3 automatically can be
regarded as that compared with the temperature set (This function
does not exist under other circumstances).
6.5 According to the temperature set, the condition upon which the
compressor will be switched on is indoor temperature≤ temperature
set-1 While the condition upon which it will be switched off
is indoor temperature is indoor temperature≥ temperature + 1.
When the indoor temperature is equal to that set, the original
operation mode will be kept.
6.6 Indoor fan control:
6.6.1 Heating operation and prevention of cold wind
When the compressor works:
1. During the rising process of the temperature of coiled pipe,
the indoor fan will not start if the temperature of the coiled
pipes is less than 25.
2. When the temperature of coiled pipe reaches less than 35
But more than 25, The indoor fan will work under the
mode of “ mute". If the temperature of coiled pipe ascends
to 25and then descends, it will stop working only when
the temperature is lowered to 22.
3. When the temperature of coiled pipe reaches more than 35
, the indoor fan will operate as set in the respect of wind
speed. If the temperature of coiled pipe ascends to 35
And then descends, it will enter into the operation mode of
“ mute" only when the temperature is lowered to 30.
6.6.2 Afterheat-blowing function:
6.6.2.1 When the compressor stop working:
1. When the temperature of coiled pipe is more than 35, the indoor
fan will operate as set in respect of wind speed.
2. When the temperature of coiled pipe is more than 25, but less
than 35, The indoor fan will operate under the mode of “ mute"
3. When the temperature of coiled pipe is less than 25, the indoor
fan will stop working.
6.6.2.2 The afterheat-blowing function when the air conditioner is just
shut down: If the temperature of indoor coiled pipe reaches more
than 30, The indoor fan will operate under the mode of “ mute"; If
it lowers to less than 30, the indoor fan will be shut down; And the
time when the afterheat blows will last less than 40 seconds after
the indoor fan is turned off.
6.7 Defrosting operation:
6.7.1The conditions upon which the outdoor sensor goes into operation are
as below:
1. Under the circumstance of heating, if T external coiled pipe is at the
temperature of less than -6 which lasts 2 minutes and the
accumulated working time of compressor reaches more than 50
minutes (if there is any power cut-off or shut-down by remote
control, the accumulated working time of compressor shall be
re-calculated), the defrosting interval will be more than 50 minutes
and the compressor will be working 5 minutes continually.
2. If there is any damage to the external coiled pipe, the accumulated
working time of compressor will reach 50 minutes (if there is any
power cut-off, shut-down by remote control or defrosting, the
accumulated working time of compressor shall be re-calculated)
and the defrosting operation will last 10 minutes.
6.7.2 Once one of the following conditions is satisfied, the defrosting will
end:
1. The temperature of T external coiled pipe is more than 12.
2. Defrosting duration is more than 12 minutes.
6.7.3 The requirements of defrosting operation:
1. Sleep indicator flickers at the speed of 1 time per second
2. When defrosting operation starts, the compressor and indoor fan
will stop working while outdoor fan and four-way valve will
continue to work.
3. The four-way valve and outdoor fan will stop operating in 30
seconds.
4. 15 seconds after that, the compressor starts and goes into
defrosting operation.
5. After the defrosting ends, the compressor stops working. And
the four-way valve and outdoor fan begins to work in 20
seconds.
6. 20 seconds after that, the compressor starts and goes into heating
operation. And the indoor fan enters into the prevention mode of
cold wind.
6.8 Auxiliary electric heating function
6.8.1 Only if the following conditions are satisfied under the
heating operation, can the auxiliary electric heating go into
operation automatically.
a. The compressor works for 4 minutes by heating pump
b. Indoor temperature is less than 22;
c. The temperature set-indoor temperature is more than 3;
d. Indoor fan goes into operation;
e. Indoor coiled pipe temperature is less than 48
6.8.2 Once one of the following conditions is satisfied, auxiliary
electric heating operation will end:
a. Indoor temperature is more than 22.
b. The temperature set –indoor temperature is less than 2.
c. When Indoor coiled pipe temperature is more than 52, the
electric heating operation will end.
d. Indoor temperature sensor becomes abnormal.
6.8.3 If compressor or indoor fan stops working, the electric
heating will stop operating as well.
6.8.4 During the operation of compressor, if the auxiliary electric
heating stops working, it can be restarted only in 1 minute.
7. Sleep operation
7.1 When the air conditioner enters into the mode of sleep, the indoor
wind speed will turn into the air quantity of “mute”.
7.2 When the sleep operation goes under the mode of refrigeration,
the temperature set rises by 1 automatically every one hour. And
the air conditioner will be powered off after sleep mode has
worked for 7 hours.
7.3 When the sleep operation goes under the mode of heating, the
temperature set drops by 2 automatically every one hour. And the air
conditioner will be powered off after sleep mode has worked for 7
hours.
7.4 When the button of mode selection is pressed down, the function
of sleep will be cancelled.
7.5 Sleep operation is effective under the modes of refrigeration and
heating. When sleep button is pressed down, the sleep operation
can begin or end.
7.6 Sleep function does not exist under the automatic mode, the
situation of dehumidification or the circumstance of ventilation.
8. Timing operation
8.1 When timing is set, timing indicator will turn light.
8.2 The time set by timing is 12 hours at most. The timing unit is 1
hour. Even if the operation mode is changed, the timing function
will still work.
8.3 Power-off at a fixed time
The power-off at a fixed time can be set only if the air conditioner
is on. And it continues to work though the power-off at a fixed
time has been already set. When it comes to the fixed time, the
indoor and outdoor fans will be shut down.
8.4 Power-on at a fixed time
The power-on at a fixed time can be set only if the air conditioner
is on. And it continues to be off though the power-on at a fixed
time has been already set. When it comes to the fixed time, the
indoor and outdoor fans will start to operate.
9. Emergency switch
When the soft-touch switch is pressed, the air conditioner will be
powered on and the operation indicator will flicker (1 time per
second). And it goes into the mode of automatic operation in 20
seconds. When the soft-touch is pressed once again, it will be
powered off. When the air conditioner goes under the mode of
automatic operation, the air door will assume the appearance of
automatic air door. Under the mode of heating or refrigeration,
the temperature set will be 24 and the wind speed will turn that
under the “high power” mode. Under the dehumidification
operation, the temperature set will be T ring-2 and the air
conditioner can work upon the instructions sent by remote
control.
10. Overload control and various protection functions:
10.1 Temperature control (overheat protection).
10.1.1 This function can only be applied to the mode of heating, not
others.
10.1.2 When the temperature of indoor coiled pipe reaches more than
57, outdoor fan will stop working.
10.1.3 When the temperature of indoor coiled pipe drops to less than
52, outdoor fan will resume to operate normally.
10.2 Temperature cut-off control function (overheat protection)
10.2.1 This function can only be applied to the mode of heating, not
others.
10.2.2 When the temperature of indoor coiled pipe reaches more than
64which lasts more than 10 seconds, the compressor and
outdoor fan will all stop working.
10.2.3 After 3 minutes’ shut-down, the compressor will resume to
operate if the temperature of indoor coiled pipe drops to less than
52.
10.3 Function of preventing indoor coiled pipe from being frozen
(supercooling protection).
10.3.1 This function can only be applied to the operation mode of
refrigeration or dehumidification, not others.
10.3.2 When the temperature of indoor coiled pipe drops to -2
which lasts more than 2 minutes, the compressor will stop
operating and the indoor fan will go by air quantity set.
10.3.3 When the compressor stops working, it can only be restarted
only if the temperature of indoor coiled pipe rises to more than 7
or the power-off of the compressor lasts more than 6 minutes.
10.4 Protection function of short or open circuit of temperature senor
10.4.1 Powered on, when it is detected that the T ring signal sent by
indoor environment temperature senor is abnormal, the air
conditioner will work under the mode of heating and will not be
powered off if the signal received from remote control is
“heating” or it will work under the mode of refrigeration and will
not be powered off if the signal received from remote control is
“refrigeration” or it will work for 8 minutes and then stop for 3
minutes with the wind speed of “mute cycle dehumidification” if
the signal received from remote control is “dehumidification”.
Besides, the signal of automatic mode sent by remote control
will not be effective, nor will the signal of automatic button
power-on and the related breakdown can be indicated at the
same time.
10.4.2 When it is detected that the T internal coiled pipe signal sent
by indoor coiled pipe temperature sensor is abnormal, the
freezing-proof, cold-wind-proof and overheat-proof functions
will be screened. Under the mode of heating, when the
compressor is powered on, indoor fan will be started after 30
seconds’ delay with the wind speed as set while when
compressor is powered off, indoor fan will be turned off after 30
seconds’ delay and the related breakdown can be indicated at the
same time.
10.4.3 When it is detected that the T external coiled pipe signal sent
by outdoor coiled pipe temperature sensor is abnormal, the air
conditioner will work for 50 minutes, defrost for 10 minutes and
heat in cycles if the signal received from remote control is
“heating” and the related breakdown can be indicated at the
same time while the air conditioner will not be powered off and
will operate normally if the signal received from remote control
is heating or defrosting or ventilation and the related breakdown
can be indicated at the same time.
10.5 disposal of indoor PG electric motor abnormity
When indoor PG electric motor is loaded with voltage, the indoor
fan will operate under the mode of “weak wind” automatically if
the pulse signal feed backed by the indoor electric motor is not
detected within 12 seconds. If the feedback signal detected is
normal, the indoor fan will resume the turning speed set and the
related breakdown indication will be disappear.
10.6 Function of charatron display
When the controller is normal, there will be no charatron display
under the circumstance of power-off. When air conditioner is
powered on, the charatron will display room temperature under the
normal situation. If the temperature set is changed, the charatron
will show the temperature set which sparkles at the rate of 1 time
per second. Then it will display room temperature once again in 5
seconds. The display range of room temperature is 0~79.
11. Function of breakdown indication
HS, HSA series (charatron); HV (VFD display)
Breakdown cause Display way Display priority
class
PG feedback abnormity
T ring abnormity
T internal coiled pipe
abnormity
T external coiled pipe
abnormity
E4 1
E1 2
E3 3
E2 4
12. Adjustment function of air door direction by pendulum
leaves
12.1 When the air conditioner is powered on for the first time, the
pendulum leaves will move to the direction of full-opening and then
to the direction of full-closing wherever they are placed.
12.2 When the air conditioner is powered off, the pendulum leaves will
move up to “close” position immediately wherever they are placed
after the fan comes to an end.
12.3 Under the mode of refrigeration, the pendulum leaves will first move
to the full-opening position and then move to the horizontal position
and at last move under the mode set while under the mode of heating,
they will first move to the full-opening position and then backswing by
5 and at last work under the mode set (for details, please see the
following diagram).
12.4 Pendulum wind: automatic air door and manual air door will be
controlled by one button.
12.5 When the pendulum leaves move from full-opening position to
full-closing position at the time of power-on or from starting position
to full-closing position at the time of power-off, the speed will be 20
per second while the speed under the instruction situation will be 5
per second.
Swing angle under the mode of refrigeration: BD is 35±2
Swing angle under the mode of heating: FC is 40±2
Backswing angle under the mode of heating: EF is 5
13.Self-checking function of controller
After the automatic button is pressed, the air conditioner will be
powered on and enter into the process of self-checking:
Buzzer sounds two times→ operation indicator turns on → timing
(2) Press the TEMP/TIME button, set the time. When “ON” stops
intermittently, the “Timer ON” can be set.
Set the “Timer OFF” (it operates only when the air-conditioner is
running.)
(1) Press the TIMER button, select the “Timer OFF”, the remote control
display “00 HOUR OFF”; “OFF” displays intermittently at the same
time.
(2) Press the TEMP/TIME button, set the time. When “OFF” stops
intermittently, the “Timer OFF” can be set.
Remark: The remote control can only be set within 12 hour intervals.
Sleeping operation mode
(1) Press the SLEEP button, the sleeping indicator light of indoor unit
flashes.
(2) After the setting of sleeping mode, the cooling operation enables the
set temperature to increase 1
o
C after 1 hour and another 1 oC
automatically after another hour.
(3) After the setting of sleeping mode, the cooling operation enables the
set temperature to increase 2
after 1 hour and another 2
automatically after another hour.
(4) The air-conditioner runs in sleeping mode for 7 hours and stop
automatically.
Remark: 1. in sleeping mode the fan speed changes automatically to
“Mute”.
2. Press the MODE button, WIND button or ON/OFF button, the
remote control clears sleeping mode away.
Attention:
Aimed the remote control at the receiver on the air-conditioner.
The remote control should be within 8 meters away from the
receiver.
No obstacles between the remote control and receiver.
Don’t drop or throw the remote control.
Don’t put the remote control under the strong sunrays or heating
facilities and other heating sources.
Use two AAA batteries, don’t use rechargeable batteries.
Take the batteries out of remote control before stop using for long.
When the noise of transmitting signal can’t be heard from indoor
unit or the transmission symbol on the display screen doesn’t
flare, batteries need be replaced.
If reset phenomenon occurs on pressing the button of the remote
control, power of the batteries is deficient and need to be
replaced.
NOTE: 1.Specifications are standard values calculated based on rated
operation conditions, they will vary in different working condition
2. Our company has quick technical improvement. There will be no
prior notice for any change of technical data. Please read the
nameplate on the air conditioner
Chapter 6 Dismantling Procedure
Indoor Unit
Operating step Photo
1. To remove the panel and connecting wire
cover.
· Take off the screws of the connecting wire
cover and remove the cover.
· Then remove the panel.
2. To remove the air filter.
3. To remove the inter frame assembly
Take off three screws of inter frame
assembly
Then take off the inter frame assembly
4. To remove the electric control box
Take off one screw
Loose one obverse clip
Remove the electric control box
5. To remove the water-collecting plate
assembly
Loose three obverse clips
Take off the electric control box
6. To remove the evaporator assembly
Take off one screws of right locating
cover and two screws of left locating
cover
Remove the pipe strap
Remove the evaporator assembly
7. To remove the through-flow fan
Take off the screws of though-flow fan
Remove the though-flow fan
8. To remove the motor
Take off three screws of right locating
cover
Remove the motor
Outdoor Unit
Operating step Photo
1. To remove the top cover assembly
Take off six screws of top cover
2. To remove the panel assembly
Loose screws of panel assembly
Take off panel
3. To remove the right plate assembly
Loose nine screws of left plate
assembly
Take off right plate
4.To remove the axial-flow fan and fan
motor
5.To remove the electric assembly
Chapter 7 Brief introduction of installation
The installation of air-conditioner shoul d meet with the “Installation Instruction”.
The machine must be installed correctly by professional technicians according to the “Installation
Instruction”.
Guide to customer
zThe customer should provide a suitable power supply source, its voltage should be in the
range of 90-110% of its rated voltage.
zThe power supply circuit should have MCB leakage protection. The capacity should be more
than 1.5 times of the maximum current.
zMust use independent circuit and suitable grounding socket matching with the plug of
air-conditioner.
zThe wiring must be installed by qualified electrician according to the electrical safety
requirements.
zThe air-conditioner must be well grounded, the switch of the main power of air-conditioner
must be reliably grounded.
zThe power supply wire, must be changed by qualified electrician.
Installation Instruction
Installation order:
Selection of the installation position Installing the air-conditioner
Expelling the air in the pipes and the indoor unit Connecting the pipes and wires
Testing
Selection of the installation position
Indoor Unit
zThere is no heating and steaming source
nearby.
zNo obstacles for installation position
from nearby.
z Keep good air circulation.
z Convenient to adopt measures to reduce
noises.
zDon’t install them near the
doorway.
zMake sure to have the distance
specified in the picture between the ceiling,
wall, furniture and other obstacles.
z2 meters high above the floor.
Outdoor Unit
zIn case that you put up a canopy to protect it from rains and sunrays, pay attention not to
cause any obstacles for the heating dispersion for the condenser.
zDon’t keep animals or plants near the installa tion location for the hot air from the out door unit
will affect them.
zMake sure to have the distance specified in the picture between ceiling, wall, furniture and
other obstacles.
z Stay away from heating source and inflammable air.
z The installation base and supporting frame should be strong and secure. The machine should
be at a level surface.
Installation of the Outdoor Unit
zThe outdoor unit must be firmly fixed to
avoid falling in strong wind.
zInstall on the cement base as in the
drawing.
zIf it is installed at seaside or at a place high
above the ground and with strong wind, the AC should be in stalled agai n st the wal l to ensu re
the normal operation of the fan and the blocking plate should be used.
zIf it is an overhanging installation , the str ucture of th e mounting wall should b e made of s olid,
cement or materials with equivalent strength, and of sufficient support capacity. Otherwise,
measures such as reinforcement, support or vibration damping should be adopted.
Installation of the Indoor Unit
zFirst make changes to wall and make sure th at is hard and secure. Using four “+” type screws
to fasten the installation board onto the wall. Keep it level in horizontal direction and
perpendicular in vertical dire cti on. Otherwise it might cause w at er drips when air-co nd iti oner
is running in cooling operation.
zDrill 70mm diameter pipe hole at the left lower or right lower side of the installation board.
The hole shall slant outward slightly.
z Hang the indoor unit to the board and make sure the
machine is in the middle of the
board.
z Push the machine towards
the left lower and right lower
side of the installation board
until the hangers enter tightly
into the grooves (it produces
“click” sound)
Check the water discharge
1. Take off the frame from the unit
cover.
Take off the front frame for
maintenance according to the
following steps:
zAs shown in the picture on the right, take off two covers from the front frame and then
unfasten two fixture screws.
zPull the front frame towards yourself and take it off.
To put the front frame back, reverse the steps.
You should check whether the front frame is firmly fixed into the fixture groove on the top.
2. Check the water discharge
z Pour a cup of water into groove.
z Check whether the water flow through the water discharge hole.
Pipe Connection
zConnect the pipe to the unit: point to the center of
pipe and fasten the connectio n screw at first by
hand and then by wrench until it is tightly
fastened. The fastening direction is shown in
the picture.
zPointing towards the center of pipe, fasten the screw
with strength.
zWrench the screw in the end until you hear th e
“click” sound.
The fixing of pipe
zWrap up all pipe, water discharge and
connection wire from top to below.
zCover the connection parts with
insulation material and fix them with two
plastic rings.
zWrap up the pipes with tape alongside the wall
and fix them to the wall with clips. These
steps are usually adopted when outdoor unit is installed below the indoor unit.
zIn case that you want to have additional water discharge pipe, the end of pipe should be
within certain distance from the floor (to prevent water from draini ng back into the pipe). Fix
it onto the wall so it won’t be swayed by wind.
zWrap the pipes and connection wire well from
below to top.
zWrap up the pipes that are rounded up in the
way shown in the picture so it can prevent
water from entering the room.
zUse clips or other fixture to fasten the pipes
to the walls.
Expelling the air in the pipes and the indoor unit
Expelling the air: humid air in the refrigerating system might cause trouble of compressor.
zTake off the cover from the stop valve
and T -branch valve.
zTake off the auxiliary cover from the
T-branch valve.
zTurn the stop valve rod anti-clock wise to
an angle of 90 degree, keep it open for 8
seconds and close the valve.
zCheck whether there is air leakage at all
connection parts of pipes.
zPush the top rod of T-branch valve by
hexagon wrench to expel air.
z Repeat the third and fifth steps.
z Open the stop and T-branch valve with a hexagon wrench to make the unit operate.
z No leakage is allowed, please check all the piping connecti on parts. You must test the leakage,
generally, it can be tested by soap water.
Electrical connection
z Unscrew the screw, take off the control panel cover from the unit.
z Cooling type: connect the wire to the relate d connection point on the panel and conne ct the
signal connection plug.
Remarks: yellow and green cord should be connected to connection point with mark.
z Fasten the fixture of wire to control panel.
z Screw up the control panel cover to its original place.
Test running
z Make sure that the pipes and wires are connected.
z Make sure that both the liquid valve and gas valve on the side are completely open.
1. The connection of power source
¾ Connect the wire to independent power source socket.
¾ Preparation of remote control.
¾ Run the air-conditioner in cooling operation mode for 30 minutes or longer.
2. Performance evaluation
¾ Test the out and in air temperature.
¾ Make sure that the temperature difference between the out and in air is grea ter than 8
o
C.
Items of attention
z Fix the machine firmly, otherwise it will produce noise and vibration.
z Install the outdoor unit where it will not disturb your neighbor.
Electrical connection diagram:
COOL SERIES HEAT PUMP
Indoor unit electric connection diagram
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.