3860 Calle Fortunada, San Diego, CA 92123-1825
Telephone: 1-800-821-5831 FAX: (858) 278-6700
Web Address: http://www.hardyinstruments.com
Hardy Instruments Part Number: 0596-0318-01 REV A
Copyright February 2010, Dynamic Instruments, All Rights Reserved.
Printed in the U.S.A.
Local Field Service
Hardy has over 200 field technicians in the U.S., and more positioned throughout the world to assist you in
your support needs. We also have factory engineers who will travel to your facility anywhere in the world
to help you solve challenging applications. We're ready to support you with:
Installation and start-up
Routine maintenance and certification
Plant audits and performance measurement
Emergency troubleshooting and repair
To request Emergency Service and Troubleshooting, Start-up, Installation, Calibration, Verifica¬tion or to
discuss a Maintenance Agreement please call 800-821-5831 Ext. 1757 or Emergency Service after hours
(Standard Hours 6:00 AM to 6:00 PM Pacific Standard Time) and weekends Ext. 1111.
Outside the U.S
Hardy Instruments has built a network of support throughout the globe. For specific field service options
available in your area please contact your local sales agent or our U.S. factory at +1 858-292-2710, Ext.
About Hardy Manuals .................................................................................................................................1
HI 1756 FC Overview....................................................................................................................................1
Features and Capabilities.............................................................................................................................2
Installing the HI 1756-FC.............................................................................................................................7
Allen-Bradley ControlLogix Pro cesso r o r R emote Rack............................................................................7
A ControlLogix Chassis..............................................................................................................................7
Removing the Module from the Chassis .....................................................................................................8
Installing the Module I/O Connector...........................................................................................................8
Power Check................................................................................................................................................11
C2 Calibration Using Ladder Logic ..........................................................................................................30
Hard Calibration.........................................................................................................................................31
Hard Calibration Ladder Logic Example ..................................................................................................31
Disassembly and Reassembly Notes, Warnings and Cautions ................................................................32
Weight and Voltage Testing .......................................................................................................................32
IT Test.......................................................................................................................................................33
General Troubleshooting Flow Chart Index.............................................................................................33
A1 - Guidelines for Instabilities on Formerly Operating System..............................................................34
B - Guidelines for Instabilities on Formerly Operating Systems (Cont’d)................................................35
B1 - Guidelines for Instabilities on Formerly Operating Systems (Cont’d)..............................................36
B1 - Guidelines for Instabilities on Formerly Operating Systems (Cont’d)..............................................37
F - Verify Individual Load Cell Millivolt Readings..................................................................................38
Testing an individual load cell signal output requires an IT Summing Junction box or millivolt meter...38
Use the load cell certificate to verify the millivolt per volt (mV/V) rating:..............................................38
G - Calibration Failed................................................................................................................................39
H - Mechanical Inspection ........................................................................................................................40
For Further Information Contact ...............................................................................................................47
INDEX ................................................................................................................ 48
iii
●
●
Contents
●
●
●
Chapter 1 Overview
●●●●●
This manual provides users and service personnel wi t h speci fi cat i ons an d p rocedures for
installing, configuring, operating, maintaining, and troub leshooting the Hardy
Instruments HI 1756 FC Rate Controller with WAVERSAVER.®
NOTE WAVERSAVER is a registered trademark of Hardy Instruments, Inc.
To ensure good performance and maximum service life, follow all guidelines described
in this manual. Be sure you understand all cautions, warnings, and safety procedures. If
you find that the information in this manual does not provide the help you need, contact
the HI Customer Service Department at:
Phone: (858) 278-2900
FAX: (858) 278-6700
Web Site: www.hardyinst.com
Support e-mail address: support@hardyinst.com
About Hardy Manuals
An overview of each chapter’s contents is listed below:
Chapter One - Provides an overview of HI 1756 FC capabilities and features
Chapter Two - Provides a overview of HI 1756 FC specific a t i ons
Chapter Three - Describes the steps for installing both the standard and optional HI
1756 FC equipment and the HI 215IT series junction box
Chapter Four - Explains how to configure the HI 1756 FC
Chapter Five - Provides calibration instructions
Chapter Six –Provides troubleshooting procedures for repair of the HI 1756 FC
HI 1756 FC Overview
The HI 1756-FC module is a self-contained, microprocessor-based ControlLogix I/O
module. Its control inputs and outputs will easily plug into the backplane of an AllenBradley ControlLogix programmable controller and/or remote rack. The remote rack
module is connected to the local chassis via a ControlNet link.
The analog-to-digital converter in the weigh module controller updates 100 times per
second and is capable of 8,388,608 counts of resolution. This allows the instrument to
tolerate large “dead” loads, over sizing of load cells/sensors, and still have sufficient
resolution to provide accurate weight measurement and control.
The module supports both C2 electronic calibration and hard calibration (i.e., traditional
calibration with weights).
The HI 1756 FC is a loss-in-weight controller that measures the flow rate from a feeding
device located on a process weighing scale. The user enters the flow parameters, and an
HI 1756 FC algorithm automatically calculates and adjusts the tuning parameters needed
to maintain the desired rate. After comparing the desired flow rate to the actual flow rate
(measured by calculating the loss of weight over short intervals), it computes the
adjustments needed to achieve the desired rate and transmits signals to adjust the speed of
the feeding device.
●
●
1
Chapter 1
●
●
●
NOTE
While the system rate calibration can fine tune the flow-rate parameters automatically,
you can also make manual adjustments.
Typical Applications
Closed-loop rate control can be used in a variety of material-flow applications, such as
auger, belt, and vibration-based feeders, converting them from volumetric to gravimetric.
The Feeder Controller controls a single-ingredient, si n gle -feeder. It can be operated in
batch, automatic, or manual mode.
Features and Capabilities
C2® Calibration
Traditional calibration uses certified test weights. C2® Electronic Calibration allows a
scale to be calibrated without the need for test weights. A C2® weighing system consists
of up to eight load cell sensors, a junction box, interconnect cable, and an instrument with
C2® capabilities (e.g., the HI 1756 FC). Each Hardy Instruments C2-certified load sensor
outputs digital information used for calculating the calibration. When the HI 1756 FC
reads the signals from the load sensors, it calibrates the scale based on the load sensor’s
output plus a user-supplied reference point value (from 0 to any known weight on the
scale).
NOTE C2® is registered trademarks of Hardy Instruments Inc.
WAVERSAVER®
n measuring small weight changes, the affects of mechanical vibration and noise
Whe
from the feeders and plant environment can introduce substantial interference.
WAVERSAVER factors out vibration, noise, and other interference-related si gnals fr o m
the load cell so the rate controller can better decipher the actual weight data.
While WAVERSAVER can factor out noise with frequencies as low as 0.25 Hz, five cutoff frequencies can be selected, with higher fre que nci e s pr oviding a faster response time.
The default factory setting is 1 Hz vibration frequency immunity.
Alarms
o HI 1756 FC alarms flag deviations from your specified flow rate.
Tw
The Rate Tolerance Alarm can alert you concerning flow-rate changes. It can be set to
trigger an alarm bit which, if sent to a PLC, can be used to respond (e.g., sound an alarm)
when the flow rate is above or below the tolerance range you select for a time that
exceeds a limit you set.
The Rate Exception Control (REC) Alarm is triggered by an out-of-tolerance flow rate
a guard band tolerance in conjunction with the Rate Tolerance Alarm. The REC sets
using
statusword bits that can flag a low or high rate. These signals can be used to either send
an alarm or shut down the feeder system. During an REC alarm state that has not resulted
in shutdown, the controller will continue to maintain the flow rate while monitoring the
loss in weight until the rate is within tolerance.
Integrated Technician™
e HI 1756 FC Integrated Technician™ (IT®), which requires an HI 215IT series
Th
junction box, provides built-in system diagnostics that makes it possible to diagnose
weighing system problems. IT allows the reading of individual load sensor voltages and
weights and isolates individual system components for quick and easy troubleshooting.
Digital Volt Meter (DVM) - Option
DVM re
quires the HI 215IT Series Junction Box to monitor mV/V readings for each load
sensor and the total system. When the operator detects a problem, the DVM readings help
●
●
2
Chapter 1
●
●
●
to isolate the faulty component. Further, the DVM readings can be used to level a system
and to make corner adjustments to platform scales. Accuracy is +/- 2% or better of full
scale.
NOTE If you do not have the HI 215IT Junction Box connected to the module, the mV/V reading
is the total for all load cells on the system.
Weighing System Tests - Optional
is test is used to diagnose drifting or unstable weight reading problems. It requires the
Th
HI 215IT Series Junction Box for full utilization. The ability to read the weight seen by
the individual load sensors allows you to use this test for making cornering, lev eling and
load sharing adjustments to the weighing system.
The Weighing System Test provides the following problem detection support:
1. Disconnects the controller and engages an internal reference signal to see if the
problem is inside of the instrument.
2. Disconnects the load sensors and engages an internal (in the junction box)
reference signal to see if the cable between the instrument and the Junction Box
is causing the problem.
3. Reads the weight of each load sensor to see if the load sensor might be causing
the problem.
Automatic or Manual Co ntrol Modes
omatic mode corrects for variations in desired flow rates automatically.
Aut
Continuous or Batch Modes
ser selectable operating modes provide support for continu ous or batch processing.
U
Automatic or Manual Refill
tomatic refill uses user-selectable refill points to start and stop the refill process
Au
without interrupting the feed process. HI and LO alarms are used to detect a refill failure.
The Manual Refill option only allows for manual refill at any time.
Two and Five-Point Automatic Rate Calibration
e 5-point auto rate calibration creates a high feed accuracy for a wide range of feed
Th
rates. It either provides the user with automatically calculated parameters, or it lets users
manually enter their own derived values.
●
●
3
Chapter 1
●
●
●
Chapter 2 Specifications
●●●●●
Chapter 2 provides specifications for the HI 1756 FC feeder controller and other
equipment that may come with the package. The specifications listed are designed to
assist in the installation, operation and troubleshooting of the in strument. All service
personnel should be familiar with this section before installing or repairing the
instrument.
Basic Specifications
General
Resolution
Internal:1:8,388,608
Input
Up to
eight 350-ohm Full Wheatstone Bridge, Strain Gauge Load Sensor/Cells (5 volt
excitation) on one vessel.
Non-Linearity
0.0015%
of Full Scale
Common-Mode Rejection
11
0dB at or below 60 Hz
Common-Mode Voltage Range
2.
5VDC maximum (with respect to earth ground)
Backplane Input Voltage/ Power Load
5 VDC
Backplane Current Load
<1
0.0125 Amps at 24 VDC (with 4-350 Ohm Load Cells)
Backplane Power Load
< 5W at
< .3W at 24 VDC with 4-350 Ohm Load Cells
C2 Calibration Input
Isol
Cable lengths
1
250 feet maximum of C2 authorized cable (Maximum of 4 load sensors) with IT Junction
Chapter 3 covers unpacking, cabling, interconnecting, configuring, and installing the
Weigh Scale Module. User and service personnel should r ead this chapter before
installing or operating the Weigh Scale module.
Unpacking
Step 1. Before signing the packing slip, inspect the packing and contents for damage of
any kind. Report any damage to the carrier company immediately.
Step 2. Verify that everything in the package matches the bill of lading.
Step 3. Write down the Model and Serial number of the module. Store this information
in a convenient location for reference when contacting The Custo mer Support
Department for parts or service.
Step 4. Be sure to complete the warranty registration on the Hardy web site.
Installing the HI 1756-FC
Allen-Bradley ControlLogix Processor or Remote Rack
WARNING Electrostatic discharge may damage semiconductor components in the module. DO NOT
TOUCH THE CONNECTOR PINS, and obse rve the foll owing handling precautions:
Wear an approved wrist-strap grounding device when handling the module.
Touch a grounded object or surface to rid yourself of any electrostatic
discharged prior to handling the module.
Handle the module from the bezel in front away from the connector. Do not
touch the connector pins.
Do not install the module right next to an AC or high voltage DC module.
Route all the load voltage cables away from high voltage cables.
A ControlLogix Chassis
Step 1. Make sure that the module is
oriented correctly for
installation.
Step 2. Gently slide the module into the
Chassis.
Step 3. Slide the digital board between
the PCB Guides on the top plate
and bottom plate of the chassis
to line up the module connector
with the backplane connector
Inserting the module
●
●
7
Chapter 3
●
●
●
Step 4. W
hen the module connector is touching the backplane connector, firmly but
carefully push toward the chassis until the pins are plugged in and the top and
bottom module releases are snapped into place.
Module release(s)
Module installed in chassis
Removing the Module from the Chassis
Step 1. Press down on the top and bottom module releases simultaneously until the
module can be pulled away from the chassis. (See Figure above.)
Step 2. Pull the module out of the chassis.
Step 3. Store in a safe, secure location in an anti-static bag or the original enclosure.
Installing the Module I/O Connector
The I/O connector at the front of the module
connects the module to the Remote Terminal
Assembly (-RTA), a load sensor, or the HI
215IT Series Junction Box, depending on
how many load sensors are installed in the
weighing system. (See the pin-out diagram
below.) A pin-out diagram is also located on
the inside of the module door.
Step 1. Open the module door to access to
the I/O connector.
Step 2. Install the cable and connector so it
allows the module door to be shut.
Step 3. With the plug oriented correctly
(See the pin-out diagram below),
plug the I/O male connector into the
I/O connector at the front of the
module.
Note When the door is open, the button you see on the top right has no function.
HI 1756 FC with door open
Check to be sure that the connector is completely
Single Channel
Pin 1 Exc+
●
●
8
Chapter 3
●
●
●
plugged in before operating the module.
NOTE Most module-related problems are due to loose
connections. Be sure to check the I/O connection first
in the event you have a problem receiving information
from the load cells or if the relays do not operate
correctly.
Load Cell Wiring Diagrams
The diagrams below show how Hardy Load Sensor with C2 wiring differs from standard
Load Cell wiring.
The Remote Terminal Assembly (RTA)
provides connection points between the cable
assembly from the HI 1756 FC module and
the individual wires from the junction
box(es) or load sensor(s). The RTA comes
with a standard 35 mm Din Rail Mounting
and requires at least a 5” inch long DIN rail
for mounting.
Remote terminal assembly
●
●
9
Chapter 3
●
●
●
You must have sense jumpers or sense
lines installed to properly reference the
excitation voltage. To properly reference
a C2 calibration, run sense lines and
remove the sense jumper.
NOTE When using load cells that do not have
sense lines, you will need to jumper the
Sense (-) to the Excitation (-) and the
Sense (+) to the Excitation (+) for one or
both channels.
RTA Cable Assembly and Jumpers
x-foot cable connects to the HI 1756 FC module.
A si
RTA cable assembly - HI 1756WS
Hardy HI 215IT Junction Box
1756 FC
Load
Cell
Connector
J1
Jumpers
RTA with jumpers for load cells without
sense lines
RTA cable schematic
Hardy HI 215IT Junction Box Wiring Diagram
NOTE When connecting the Hardy HI 215IT Junction Box, you must remove the two fa ctory
installed jumpers 1&2 and 5&6 on the module and install sense lines.
●
●
10
Chapter 3
●
●
●
Chapter 4 Configuration
●●●●●
Chapter 4 covers the settings used to prepare the controller for calibration and operation.
The Setup procedures require Allen-Bradl ey’s RS Logix 5000, Allen-Bradley RSLi nx ™
or RSLinx™ Lite.
Power Check
To make or change settings, there
must be power to both the PLC and
the module. Verify that the LEDs
are lit for normal operation.
Module LEDs
LEDS
Scale Data LEDs
Flashing Green
Steady Green Running (Normal)
Steady Red Error Read Failure or Error eeprom write. Contact HI
Flashing Red Read Convert Error.
LED is Off Channel is Inactive
OK Module Status LED
Brief Steady During power up the LED lights Red for about one second.
Flashing Green In Program mode. (Normal)
Steady Green In Run Mode. (Normal)
Steady Red Config. Fault The eeprom checksum failed - bad serial
(Backplane Available) data or blank serial eeprom. Contact HI Customer Support.
Steady Red Internal Hardware watchdog timer fault (e.g. bad Hardware
Flashing Red Communication Error.
Feeder is on
Customer Support
eeprom
or Firmware). ASIC is non-operational.
11
●
●
Chapter 4
●
●
●
Setting Up Communications
Linking the PLC with the HI 1756 FC Feeder Control Module
To set parameters for the weigh scale module, you must establish communications with a
ControlLogix PLC. Follow the steps below to set up the communication link. You will
need a new or open RS Logix® 5000 project. For instructions, see your RS LOGIX 5000
manual.
Step 1. Look for a list of folders on the left side of the screen. Scroll to and select the
I/O Config folder, which will open a menu.
Step 2. Select New Module to display a list of modules.
Step 3. Select the Generic 1756 module to open the
Module Properties form.
Step 4. Enter the following connection parameters in
the appropriate fields:
Name of Module
Description of Module (Optional)
Slot ID
Input Assembly Instance:101 Size = 32
Output Assembly Instance: 100 Size = 32
Configuration Assembly Instance: 102
Size = 200
Step 5. Select DATA INT from the Comm Format
pull-down list.
Module Properties Dialog Showing General tab
Step 6. Open the Connection Tab.
Step 7. Set the RPI to 20 milliseconds or greater. Do not set this parameter lower than
20 milliseconds.
12
●
●
Chapter 4
●
●
●
Step 8. Click Finish.
Configuration Output Table Overview
To configure the module, you send commands via the PLC output table.
The 1756 module uses 32 16-bit INT words in and out. Only 5 words of the output table
are normally used. (Command 0X5E uses ten and 0X5F uses seven)
Word Command structure write
0 Command number
1 Format word (see Format Word below)
2 Value (LSW)
3 Value (MSW)
4 Parameter ID
Param
eters can be read (READPARAM) or written (WRITEPARAM) one at a time:
To read a parameter, put the readparam command number in word 0, the format
word in word 1, and the parameter’s number in word 2 of the output table.
To write a parameter, put the writeparam command number in word 0, the
format word in word 1, and the parameter’s value in words 3 and 4 of the output
table.
First Word - 0: Command Number
The first word in the output table is a command. The possible commands are:
Command # Hex Description
13
●
●
Chapter 4
●
●
●
NOCMD
STARTCMD
STOPCMD
REFILLCMD
WRITENONVOLATILE
MANUALCMD
ABORTCMD
RELOADNONVOLATILE
RATE_CAL_5_POINTS_
DEFINED
RATE_CAL_2_POINTS_
DEFINED
0
1
2
3
4
5
6
0x10
0x5E
0x5F
No command
START
STOP
REFILL
Saves all parameters (including calibration
constants) to the non-volatile memory. Error Return
Values: None
Enters manual mode
Stop, go straight to IDLE mode
Causes the weigh module to re-read the values
stored in its non-volatile memory. Parameters
changed since the last write non-volatile command
are overwritten. Can be used to abort a calibration
or parameter entry session. No error return values.
Runs the 5-point rate calibration at percentage
outputs defined at words 2-6. The percentages have
0 decimal places. They must be > 0, < 100, and in
ascending order, with a minimum of 10 between
them.
Runs the 2-point rate calibration at percentage
outputs defined at words 2-3. The percentages have
0 decimal places, and must be > 0, < 100, and in
ascending order, with a minimum of 10 between
them. This calibration operates at points 2 and 4 of
int rate calibration. The other points are filled
a 5-po
with data based on these 2 points.
RATE_CAL_5POINT_CMD
0x60
Runs the 5-point rate calibration at whatever points
have previously been defined.
RATE_CAL_2POINT_CMD
0x61
Runs the 2-point rate calibration at whatever points
have previously been defined.
CALLOWCMD
0x64
Sets the “calLowCount” parameter to the current
A/D average counts when doing a hard calibration.
Calls an Integrated Technician function during low
calibration.
Error Return Values:
STATUSWORD - There was a conversion error or
A/D conversion failure.
HARDCALFAILCOUNTS - There are less than
1000 counts between the zero and the span weights.
CALHIGHCMD
0x65
Sets the Span Weight parameter to the current A/D
average counts when doing Hard CAL.
Error Return Values:
STATUSWORD - There was a conversion error or
A/D conversion failure.
HARDCALFAILCOUNTS - There are less than
1000 counts between the zero and the span weights.
C2CALCMD
0x66
Performs a C2 Calibration. Uses CalLowWeight as
the reference point.
Error Return Values:
STATUSWORD - There was a conversion error or
A/D conversion failure.
C2FAILNODEVS – Detected no C2 load cells.
C2FAILCAPEQ - Detected two load cells with
different capacities.
WRITEPARAM
0x67
Writes the parameters. See Parameter Table
below.
Return Data:
COMMAND STATUS - The status is 0 if the
command succeeded. If a range error was detected
in one of the parameters, a non-zero value is
returned indicating which parameter failed its range.
See Status Table below.
READPARAM
0x69
Reads the parameters. See Parameter Table
below.
Return Data:
COMMAND STATUS See Status Table below.
PARAMETERS
SETDEFAULTPARAMS
0x94
Loads the default settings into RAM, and nonvolatile RAM. Error Return Values: None
14
●
●
Chapter 4
●
●
●
Command Return or Error Codes
Commands always return the command word and command status. The command status
word may include the following codes:
Return Codes # Hex Description
SUCCESS 0 Pass
OUTOFTOLERANCE -3 Out of tolerance
INDEXOUTOFRANGE -4 Out of range
NOSUCHCMD -5 Command bad
C2FAILNODEVS -6 No C2 devices
C2FAILCAPEQ -7 Failure, C2 capacities not equal
HARDCALFAILCOUNTS -8 Fails, too few ADC counts between high - low
NOSUCHPARAM -9 Parameter ID incorrect
Second Word - 1: Format Word
Format Word Decimal Point Parameters
Word 1 is the format word. The decimal point parameters, which are set via the format
word, indicate the location of the decimal point within the values to follow (i.e., how
many decimal places the integer values in the input and output tables have). The higher
the number, the farther to the left the decimal point moves and the more precisely the rate
is displayed. However, setting the decimal point far to the left does not ensure that the
measuring device will be accurate enough to distinguish the requested level of precision
from interference factors.
While the decimal point values for total, weight, and rate are separate, each has four bits
in the format word. The maximum decimal place value is 7.
Formatword uses hex format 0000xxxxyyyyzzzz, where 0000 is not used at this time,
xxxx = total DP, yyyy = Weight DP, and zzzz = Rate DP. The DP values position the
decimal point within the number.
0x0123 means TOTAL decimal places is 1, WEIGHT decimal places is 2, RATE decimal
places is 3. For example, writing the value 0x0123 in the format word sets the total decimal place value, which is used for the TOTAL and BATCH TOTAL values to 1. It
sets the weight decimal place, which is used for the gross weight, to 2, and it sets the rate decimal place, which is used for the rate of change (ROC) values to 3.
Total Decimal Point (xxxx)
e Total Decimal Point parameter sets the location of the decimal point within the
Th
Totalizer value, which is based on the selected unit of measure.
Range: 0-7 (default 1) In most applications a decimal setting of 0 or 1 is recommended.
Weight Decimal Point (yyyy)
e Weight Decimal Point parameter to indicate the location of the decimal point
Set th
within the weight values, which are based on the selected unit of measure.
Range: 0-7 (default 2)
Rate Decimal Point (zzzz)
e Rate Decimal Point Parameter sets the location of the decimal point within the Flow
Th
Rate value.
15
●
●
Chapter 4
●
●
●
ange: 0-7 (no default)
R
Third / Fifth Words - 2, 3, 4: Parameter Number and Value
The third and fourth words in the output table, Parameter Value, are used by the
WRITEPARAM command. The fifth word is the parameter ID, used by the
WRITEPARAM and READPARAM commands. Parameter values are written with the
least significant word first and one 32-bit integer per parameter. For details see the
Parameter Table below. Expanded descriptions are listed below the table by hex number.
All parameters are DINT.
There are 14 spare parameters for possible future use.
Notes When set by a command, all parameters except the rate setpoint are saved to non-volatile
memory. Both rate and scale calibrations are saved automatically when completed
successfully. Totals are not saved automatically when changed, and will be lost if no
WRITENONVOLATILE command is executed before power down.
The section above “Format Word Decimal Point Parameters” explains Weight DP, Rate
DP, and Total DP, which appear in the chart below.
16
●
●
Chapter 4
●
●
●
Parameters
#hex
/sub#
Brief Description (Note: Expanded descriptions are listed
below the chart by hexadecimal number)
Chan Active 1 0-1 flag, determines if a channel is alive.
Metric 2 0-1. Report Weight In. Units of measure listed below
span weight 3 Calibration weight, high. Must be >0. Weight DP.
cal low weight 4 Calibration weight, low. Must be > or = 0. Weight DP.
ROC time base 5 In seconds, 0 decimal places. 1-1800 seconds.
ROC time units 6 0=sec,1=min,2=hr
NumAverages 7 Dint. 1-255. Default = 1
WAVERSAVER 8 0-5 See 8 below
PID_P 9 1 decimal places.
PID_I A 1 decimal places.
Batch amount B Weight DP. Must be > or = zero.
Preact C Weight DP. No limits.
Mode D 15 // 0=continuous or 1=batch.
Prime Time E seconds, 0 decimal places.
Pause Time F seconds, 0 decimal places.
feed time 10 seconds, 0 decimal places.
Initial Refill on 11 0 = no, 1 = yes
Auto Refill On 12 0=off, 1=on
Refill Start
Weight 13 Weight DP. No limits
Refill End
Weight 14 Weight DP. No limits
Refill Too High
Weight 15 Weight DP. No limits.
Refill Shut
Down Weight 16 Weight DP. No limits.
Op Adjust 17 0=off,1= learning, 2= fixed.
Op Adjust % 18 6 decimal places.
Wait Time 19 Seconds, 0 decimal places. Must be > or = 0
EC Level 1A 1 decimal place. Must be > or = 0.
R
REC Time 1B Seconds, 0 decimal places. Must be > or = 0
REC Shutdown 1C 0=no, 1=yes
Shutoff Percent 1D 0 decimal places. 0-100
Total 1E Total DP
Batch Total 1 F Total DP. Must be > or = 0
Low Alarm Shut
Down Rate 20 Rate DP. No limits
High Alarm Shut
Down Rate 21 Rate DP. No limits
Alarm Delay 22 Seconds, 0 decimal places. Must be > or = 0.
Rate Setpoint 23 Rate DP. Must be > or = 0, < MAX RATE.
Rate Calibration Parameters See Rate Calibration Parameters section below
REC_P_Limit 1 decimal place. Must be > 0 and < or = 100.0.
7 Rate Cal Rates (xx32) 7 rate calibration rates. All are R DP > or = 0.
0 rate 0032 0x0032 is the minimum rate
1st rate 1032 0x1032 is the next stepped rate
2nd rate 2032 0x2032 is the next stepped rate
3rd rate 3032 0x3032 is the next stepped rate
4th rate 4032 0x4032 is the next stepped rate
5th rate 5032 0x5032 is the next stepped rate
100 rate 6032 0x6032 is the MAX RATE
7 Rate Cal
Percentages
(xx33) // 7 rate calibration percents. Uses 2 decimal places. 0.00-100.00
0 Percent 0033 0x0033 is the minimum %
1st Percent 1033 0x1033 is the next stepped %
2nd Percent 2033 0x2033 is the next stepped %
3rd Percent 3033 0x3033 is the next stepped %
4th Percent 4033 0x4033 is the next stepped %
5th Percent 5033 0x5033 is the next stepped %
100 Percent 6033 0x6033 is the MAX %
End Rate Cal section
ADC Average 34 0x0034 // Read Only
STATE 35 0x0035 // read only – see mode list below
Bit 0 Idle Mode
Bit 1 Auto Mode
Bit 2 Manual Mode
Bit 3 Start Mode
Bit 4 Stop Mode
Bit 5 Shut Off Mode
Bit 6 Pause Mode
Bit 7 Rate Cal Mode
Bit 8 Refill Mode
Bit 9 Full Mode
Bit 10 Manual Hold Mode
Bit 11 Rate Cal Hold Mode
17
●
●
Chapter 4
●
●
●
Bit 12 Initial Refill Mode
Two decimal places. This it the output percent when in
MANUALOP 37
FAST_ROC 38
zerocount 0x0A00 AD counts at zero weight
calLowCount 0x0A01
mbers or letters in the titles below correspond to the values in Column 2, Hex#, above
e Unit parameter sets the scale and related displays to one of the following options:
Th
Pounds (lb) - Default
Ounces (oz)
Ton (ton) short ton
Kilograms (kg)
Grams (g)
Metric Tonnes (t) long ton
Range: LB, OZ, TON, KG, G, T (default LB)
Any weight value input to the module (e.g. CALLOWWEIGHT, SPANWEIGHT) are in
the currently selected unit. The unit of measure can be set at any time, not just at
calibration. Set the metric before calibrating to verify the unit of measure.
Note The weigh scale module does not need to be recalibrated after changing the metric value.
Parameter 3 Span Weight
The
Span Weight is a reference point derived from an actual measured weight. This
should not be confused with the Scale Capacity. If you have a 100 pound weight and you
place it on the scale, the Span Weight would be 100 pounds.
Parameter 4 Cal low weight
s reference weight is the weight of any product on the scale that is not removed during
Thi
calibration (derived from actual measured weight used at cal low or C2 cal). Normally,
you would remove all “live load” weight from the scale to obtain a CalLow Weight of
0.0. The location of the decimal point in this value is based on the Weight decimal point
parameter.
Range: Must be > or = 0.
Parameter 5 ROC time base
e Time Base is the length of time in seconds between two weight readings that are
Th
subtracted to determine the initial flow rate. By increasing the time base, you increase the
time between weight readings. This allows more material to be dispensed during the time
base period. Low flow rates require a longer time base than high flow rates. The
controller measures weight to about 1 part in 10,000. The formula below provides a
minimum. Auto rate calibration uses a minimum of 10 ROC Time p eriods to make the
rate calculation.
TIME BASE > (SCALE CAPACITY/5000)/LOW SETPOINT (units per sec.)
SCALE CAPACITY/5000 = determines minimum weight increment
18
●
●
Chapter 4
●
●
●
Example: (440/5000) = 0.088 lb
e lowest setpoint in units per second @ 3 lb per min is: 3 lb/60 sec = 0.05 lb/sec
Th
Thus:
TIM
E BASE = 0.088/0.05
TIME BASE = 1.76 (rounded to 2)
MINIMUM TIME BASE = 2 seconds
Range: In seconds, 0 decimal places. 1-1800 seconds.
Parameter 6 ROC time units
e units of time (seconds, minutes or hours) you want for the Rate of Change. The ROC
Th
display on the summary display will read in these units.
Range: 0=sec, 1=min, 2=hr (default Seconds)
Parameter 7 Averages
s is the number of samples to average when determining a value to reduce the affect
Thi
of material impact and/or vibration as material moves on and off the scale. The Rate
Controller takes 100 readings per second. If you average enough weight readings, the
weight loss or gain remains smooth and the displayed value shows little or no fluctuation,
although it is actually recalculated (by sliding average) with each reading. If a weight
reading fluctuates too much, increase the number of readings in the average, but for
applications that require a very quick weight reading, do not set this value too high.
The averaging parameter is most often set when using any device that outputs an erratic
signal (e.g. a flow meter). Using the averaging function comes at the expense of response
time. A setting of one average takes 10 milliseconds. A setting of 100 averages takes 1
second. The averaging function is a running average, where the input signals are totaled
and the total is divided by the averaging number. The instrument reads one new signal
plus the last number of averages signals and repeats the averaging process again.
19
●
●
Chapter 4
●
●
●
For example: With a setting of 20 averages, the instrument reads the 20 most current
input signals, totals the signals, divides by 20, drops the oldest one, reads one new signal
along with 19 old readings, totals the signals, di vi des by 2 0, d ro ps t he oldest one, etc.
Range: 1-255(default 1)
See also WAVERSAVER for information on filtering unstable weight readings.
Parameter 8 WAVERSAVER®
apter One provides a detailed description of WAVERSAVER’s function and purpose.
Ch
In short, WAVERSAVER helps to mitigate the effects of vibratory forces, allowing the
HI 1756 FC to distinguish between actual weight data and mechanical noise in the signals
the load cell sends. WAVERSAVER can be configured to ignore noise with frequencies
as low as 0.25 Hz. High values allow faster readings, while the lower values raise the
degree of filtration. 7.5 Hz provides the least vibration immunity with the fastest response
time. 0.25 Hz provides the most vibration immunity with the slowest response time. The
function is user selectable and can be turned off.
e P parameter for Rate Calibration. See Chapter 5 for additional instructions on
Th
running Rate Calibration. Rate calibration determines this parameter, so you may not
want to set it. It would be difficult to know what to enter.
P and I
values: Use Rate Calibration to calibrate the system starting flow rate. Rate
calibration establishes the feeder maximum rate, PI settings, and the starting OP% for a
given rate setpoint. From that starting point, the controller adjusts the OP% to maintain
an optimized setpoint. Environment and product conditions require monitoring and
adjustment to meet the requested setpoint target.
NOTE
You must calibrate the scale prior to rate calibration.
The PI controller calculates an output percenta ge base d o n the parameters P (proportional)
and I (integral). The rate calibration process can set the values for P and I automatically.
The output percent is determined by the formula:
P*((Setpoint - ActualRate)/MaxRate + I * (integral of the proportional term)).
P and I Must be > or = 0
Parameter A Rate Calibration Configuration PID I
The
I parameter for Rate Calibration. See explanation under Parameter 9 above.
Parameter B Batch amount
batch amount and preact parameters are used when operating in Batch mode. The
The
Batch Amount sets the amount of ingredient in weight units used per batch for the
selected ingredient.
Range: >
0.0 (default 0.0) It is not necessary to enter 0.00 for these parameters) The
decimal point is positioned based on the Weight Decimal parameter for batch amount.
Parameter C Preact
Preact is
used when operating in Batch mode. It is the amount to allow between the batch
amount signal and the time when the feeder actually stops feeding. Where the feeder
slows to a stop, set the preact value so the desired batch amount is dispensed when the
feeder stops completely. The decimal point is positioned based on the Weight Decimal
parameter for preact. No limits.
Range: >0.0 (default 0.0) No limits.
Parameter D Mode
u can operate either in continuous or batch mode depending on the process.
Yo
Range: 0=continuous or 1=bat c h.
Parameter E Prime Time
Th
e time in seconds it takes to get the system up to full flow for the first calibration point.
on the first test OP% run of the rate calibration, the feeder must prime the feeding system
and the feeding system must smoothly feed product at an OP % selected rate.
Range: 1-999 (default 5 sec) Must be > or = 0
Parameter F Pause Time
is is the time you want the feeder to wait between Auto Rate Calibration cycles. If
Th
necessary, more material may be added to the feeder. Note that this parameter should be
set long enough to allow the operator to trigger a "hold" in between feed runs.
We recommend that you make the Pause Time equal to or greater than the Timebase
value you entered for the ROC.
NOTE If a feeder is manually paused before a cycle starts or during a cycle, when the test is
restarted it will run from the beginning.
Parameter 10 Feed Time
Time is the test duration at each rate. Set this to a minimum of 10 X ROC time base.
Feed
Make sure that your feeder hopper holds enough product to complete the high percentage
rate test. You cannot pause or refill during a test phase.
20
●
●
Chapter 4
●
●
●
Must be > 0. Range: 1-999
Parameter 13-18 Refills
Automatic Refill uses user-selectable refill points to signal a start or stop of the refill
process without interrupting the feed process. HI and LO alarms can be used to flag a
refill failure.
Manual Refill allows for manual refill at any time. The Manual Refill stops at the Refill
High point.
Initial Refill
itial Refill ensures that the feeder contains enough material to safely begin operation. It
In
can help to decrease the number of refills d uring a run. Review how the Initial Refill
works before you make this selection.
After you select Initial Refill and start the feeder, the instrument checks to see if the
material in the hopper is below the refill end weight. If it is, the instrument goes into refill
mode until the refill end weight is reached.
Parameter 11 Initial Refill on
is value serves as an ON/OFF switch for the initial refill function.
Th
Range: 0 = no, 1 = yes (default NO)
Parameter 12 Auto Refill On
Th
is value serves as an ON/OFF switch for the auto refill function.
Range: 0=off, 1=on
NOTE If Initial Refill is on with Auto Refill off, the unit still goes into refill mode until the unit
high weight is reached. If you wish to prevent this, turn off Initial Refill when you turn off
Auto Refill.
Parameter 13/14 Refill Start Weight and End Weight
Th
e Start Weight, which is set in mass units (actual gross weight), triggers a signal to
begin the refill process. You need to determine when you want the refill to automatically
begin (or an alarm to trigger so an operator can refill the feeder). The Start Weight value
must be higher than the Lo Shutoff value. End Weight signals when the hopper is full.
The Refill Shutdown setting stops the process when there is insufficient or no material in
the hopper. This setting can be 0 weight indicating nothing in the hopper or a weight
setting somewhat above the 0 weight and below the Refill Start Weight value. The Refill
Shutdown value must be below the Refill Start Weight value.
The weight you enter for Refill Too High will trigger an alarm should the weight go
above this value while refilling.
Refill Shutdown Range >
0 (default 0) Refill Too High Range >0 (default 100,000)
Parameter 17 OP Adjust
There
are thee options:
OFF: (default) Turns off the function.
21
●
●
Chapter 4
●
●
●
ON-LEARN: (works only with Auto Refill) The HI 1756 FC saves the % output and
change in weight values from previous refills and continuously calculates the optimal
Output % based on these values. This allows the instrument to adjust as conditions and
the material or refill characteristics change over time.
XED: With Auto Refill, you can use ON-FIXED to either lock in an effective
ON-FI
learned value or enter a noted value that has worked well on previous applications.
Range: 0, 1 or 2
Parameter 18 OP Adjust %/wgt during refill
Refill OP Adjust %/wgt
This is the OP (Output Percentage) Adjust % per unit of wgt. Rate calibration determines
this parameter, so you may not want to set it. It would be difficult to know what to enter.
The weight of an ingredient in a hopper can affect the rate of feed. For example, a liquid
at the base of a full hopper is under greater pressure than a liquid at the base of a near
empty hopper. If no adjustment is made, the liquid flows out faster when the hopper is
full than when it is low. When the OP Adjust parameter is ON (i.e., not set to OFF), the
OP Adjust %/wgt value will adjust the refill rate to compensate for any change in weight
of the ingredient in the hopper. OP Adjust On Learn is used to calculate this value.
Range: -100 to +100 up to six decimal places (Default 0.0)
Parameter 19 Wait Time
me the controller waits for the material to settle before it calculates the batch total.
Ti
Seconds, 0 decimal places. Must be > or = 0
Parameter 20 Low Alarm
Shut Down Rate
If the actual flow rate is below the setpoint beyond the alarm delay time, the Lo Shutoff
alarm can be configured to signal an alarm condition that can either shut the process
down or lower the output to a set percentage (See Shutoff % Out below). The decimal
point is positioned based on the Rate DP parameter.
NOTE The Lo Shutoff alarm value must be equal to or less than the lowest set point value.
Range: No limits
Parameter 21 High Alarm Shut Down Rate
he actual flow rate is above the setpoint beyond the alarm delay time, the Hi Shutoff
If t
alarm can be configured to signal an alarm condition that can either shut the process
down or lower the output to a set percentage (See Shutoff % Out below). The decimal
point is positioned based on the Rate DP parameter.
Range: No limits
Parameter 22 Alarm Delay
e number of seconds you want the instrument to delay before setting off either a HI
Th
shutoff or LO shutoff alarm after detecting a flow rate that is out of tolerance. This avoids
nuisance alarms and gives the system time to clear a problem.
If a product is easily liquefied, set a very short delay to prevent large spills. If a product
tends to plug or bridge set a longer delay.
Range: 0 decimal places. Must be > or = 0.
Parameter 23 Rate Setpoint
e Rate Setpoint is the ingredient target flow rate (Loss in Weight) you want to
Th
maintain for your process. The decimal point is positioned based on the Rate DP
parameter.
22
●
●
Chapter 4
●
●
●
Range: Must be > or = 0, < the maximum rate set for rate calibration.
REC Parameters
Parameter 1A REC Level %
The REC Level % (RECPERCENT or REC LEVEL% parameter) is a percentage of Max
Rate. It is the level of error above or below the Setpoint Rate that you can accept before
the instrument goes into REC mode. For example: If the rate calibration Max Rate is 5.0
lb/min, and the REC level % is 20%, the allowable deviation is 1.0 lb/min from the Rate
Setpoint before a Rate Exception error occurs.
Range: 0-100.0 (default 20%. This allows for a very larg e error. We recommend a setting
between 5% and 10% and allowing a RE+ or RE- indication about every five min.)
Parameter 1B REC Time
e time the unit must remain in the REC mode to get an alarm condition or if the
Th
Shutdown parameter is selected to shutdown the operation.
Range: 0-999 (default 10)
Parameter 1C REC Shutdown
EC Shutdown enables you to shutdown your operation if the system operates in
The R
REC mode beyond the time limit set in REC Time. If you select YES for REC Shutdown
and the RE error goes beyond the REC Time, the HI 1756 FC goes to shutoff mode. If
you select NO, once the deviation goes beyond the REC Time, the system only sends an
alarm bit.
Range: NO/YES (default NO)
Parameter 1D Shutoff Percent
hutdown signal can trigger a fixed OP % response if Shutoff Percent is greater than
A s
0.0%. This allows for processes that should not be halted completely, even if an error
occurs, to continue at a slower rate.
Range: 0 decimal places. 0-100
Parameter 1E Total
ontroller records the total amount dispensed. The Total number displays the amount
The c
of material that has been processed from the start of the process until the process
completes or is interrupted. You would probably not want to reset the Total value each
time you start the module, but for error correction, the Total parameter can be cleared (in
either continuous or batch modes). For example, if a power failure shuts the system down
during a process, before you resume operation you can re-enter the lost total from the
front panel.
CAUTION If you change the Total, stop the system.
Total Range 0 - >99,999.0 wt units (default 0.0)
Parameter 1F Batch Total
atch Total reads the total amount of material for the selected batch that has been
The B
processed from the start of a batch process until the batch process ends (by intent or other
reason). When the Batch is complete, the Batch Total resets to 0.0 for the next batch. The
Batch Total parameter can be changed should there be an error in the batch total amount
while processing.
CAUTION If you change the Batch Total, stop the system.
Batch Total Range 0 - >99,999.0 wt units (default 0.0)
●
●
23
Chapter 4
●
●
●
Rate Calibration Parameters
Three types of calibrations determine the flow rate per output percentage:
1. Two-point rate calibration: Used for Auto RateCal. If a two-point Auto Rate
Calibration is selected, two flow rate points (points two and four) are used for
calculating other rate point values. The unit will go to the high rate output percent
for a period of feed time plus prime time (See parameters E and 10 above). When
this period is complete, it saves the actual rate as the high cal rate, then pauses for
a period of pause time (See parameter F) before going to the low rate output
percent for a period of feed time. When this period is complete, it will save the
actual rate as the low cal rate. After doing the auto rate calibration at the low and
high rates, the unit will estimate the zero rate output percent and the Max rate cal
rate and will fill values for the first, third, and fifth five-point calibration rate pairs.
2. Five-point rate calibration: Five-point measurement used with Auto RateCal to
provide tighter flow rate control. The user enters the output percent values, and the
unit then runs at each of these output percents, starting with the highest one, for a
period of feed time or feed time plus prime time on the first run. It saves the actual
rates it observes into the cal rates and estimates the MaxRate and zero output rates.
3. User-setrate calibration: Used when you cannot do an Auto RateCal and you
know the flow rate for all seven output percentage selections. If user-set
calibration is selected, you must manually enter the PI settings and the output %
and rate for all calibration pairs. The entered flow rates can come from experience
with the material, often through trial and error. We recommend that you select
output percentage points where your expected control set point falls between point
two and point four.
Configuring Rate Calibration
OTES Make sure you have enough material to do a Rate Cal at the highest OP%. If, for
N
example, 30 seconds at 90% would empty the hopper, reduce the Rate Cal to a lower
rate.
RateCal Percents
RateCal Percen
ts sets the output percentage for the three cal types.
1. For the 2 pt Cal Type (%Lo & % Hi), make sure that the Hi % is higher than the
Lo % and that there is a separation of at least 10%. You enter Pt2 and Pt4.
2. For the 5 pt Cal Type (Pt1, Pt2, Pt3, Pt4, Pt5), each % should be >
10% different.
3. For the User-set cal Type, you need to know the flow rates for all output
percentage setpoints. You enter the output percentages and the known f low rates
and the correct PI setting.
Range: 0 -100
You can edit other parameters, including adjustable values in the OP% (and/or Cal Rate)
fields.
Example: A calibration pair Output percent of 25% and a cal rate 250 means that a rate of
250 weight units per unit time will be obtained when the output percent is 25 %.
Running Rate Cal
e user enters all OP percentages. The Auto Rate Cal will prime the system then run for
Th
the selected feed time based on the calibration type, pause time, and RateCal Percents
you selected.
24
●
●
Chapter 4
●
●
●
Input Table
r the 2 pt Cal Type (Pt2 and Pt4), the two flow rates for the percentages you
1. Fo
selected are the actual flow rates. The instrument calculates the remaining three
flow rates.
2. For the 5 pt Cal Type, you provide the five RateCal percents between the Low and
High output percentages.
3. For the User-set cal Type, you provide known flow rates for output percentage
setpoints (Pt2 and Pt4) and the output percentages. This only establishes the rate
lookup table for startup rates.
25
●
●
Chapter 4
●
●
●
.
The first 5 words of the input table echo the output table, except that the format word is
replaced with a command status that indicates whether a command succeeded or failed.
The next words are the OP% rate of change, the gross weight, rate setpoint, state, version,
and the module status word. There is also a counter which continuously increments.
Command # Offset Description
CMD 0 Command # echo the command from the input
CMD_STATUS 1 Status of command
PARAM_VALUE 2 Parameter value (LSW)
PARAM_VALUE 3 parameter value (MSW)
PARAM_NUMBER 4 Parameter number, in read and write commands
OP 5 Operating %. 2 decimal places 0.00 - 100.00
ROC 6 Uses 'rate decimal places' ROC value (LSW)
ROC 7 ROC value (MSW)
GROSS_WEIGHT 8 Uses 'weight decimal places' Gross wt. (LSW)
GROSS_WEIGHT 9 Gross wt. (MSW)
RATESETPOINT 10 Uses ‘rate decimal places' Total . (LSW)
RATESETPOINT 11 Total . (MSW)
STATE 12 State
SION 13 Firmware version
VER
STATUS 14 Statusword (See Statusword below)
COUNTER 15
Statusword
At word
14, the module returns a binary statusword where each bit indicates a state or
condition within the module. To interpret these states, note which bits are ON and use the
chart below to match each bit location to the state it represents.
For Example: If the statusword is 69 with a binary value of 0000 0000 0100 0101, bits 0,
2, and 6 are on. Bit 0 indicates an A/D conversion error, bit 2 indicates status is ON and
bit 6 indicates a shutdown error.
STATUSWORD bit positions refer to these variables:
Word# Definition
ERRORADCONVERT 0x0001/0
Millivolt return from the load cell
system is out of range for the unit.
ERRORADFAILURE 0x0002/1 Unit’s A/D converter not responding.
STATUS_ON 0x0004/2 System on or off
ERRORLOWALARM 0x0008/3 Low alarm
ERRORHIGHALARM 0x0010/4 High alarm
ERRORCONTROL_LOST 0x0020/5 Controller communication failure
ERROR_SHUTDOWN 0x0040/6 Shutdown
ERROR_RANGE 0x0080/7 Out of range value
ERROR_REC 0x0100/8 REC value over high limit
ERROR_RECMINUS 0x0200/9 REC valu e below low limit
ERROR_REFILL_OVER 0x0400/10 Exceed refill limit
STATUS_REFILL 0x0800/11 Refill process active
STATUS_BATCH_COMPLETE 0x1000/12 Batch process completed
ERROREEPROMWRITE 0x4000/14 EEPROM Hardware Error
STATUSCHANENABLED 0x8000/15 Set if channel is enabled
If there is NO IT JBOX, the instrument can still measure the sense voltage, the overall
load cell millivolts per volt, and the internal reference weight value. If the user has an IT
JBOX, th
attached to the IT JBOX.
To initiate an IT test, do a WRITEPARAM command, with parameter number 0x0036,
and a parameter value equal to the number of sensors, which should be 1-4 if you have an
IT JBOX. If you do not have an IT JBOX, the parameter value does not matter.
To read back the results, do a READPARAM command, with paramet er numbers
0x0036, 0x1036, 0xB036. The return values are listed below.
Integrated Technician Return Values Table
Return Value # Hex Description
PARAMID_ITECH 0x0036
INSTANCE_VSENSE 0036 Sense voltage, 2 decimal places
INSTANCE_DVM_COMBINED 1036 millivolts per volt, 4 decimal places
INSTANCE_IREF_WEIGHT 2036 internal reference weight, weight decimal point
INSTANCE_JBOX_MV/V1 3036 Load cell 1 millivolts per volt, 4 decimal places
INSTANCE_JBOX_MV/V2 4036 Load cell 2 millivolts per volt, 4 decimal places
INSTANCE_JBOX_MV/V3 5036 Load cell 3 millivolts per volt, 4 decimal places
INSTANCE_JBOX_MV/V4 7036 Load cell 4 millivolts per volt, 4 decimal places
INSTANCE_JBOX_REF_WEIGHT 7036 reference weight on IT JBOX, weight decimal pt
INSTANCE_JBOX_WEIGHT1 8036 Sensor 1 on JBOX, weight decimal point
INSTANCE_JBOX_WEIGHT2 9036 Sensor 2 on JBOX, weight decimal point
INSTANCE_JBOX_WEIGHT3 A036 Sensor 3 on JBOX, weight decimal point
INSTANCE_JBOX_WEIGHT4 B036 Sensor 4 on JBOX, weight decimal point
e instrument can also read the weights and voltages of the individual sensors
27
●
●
Chapter 4
●
●
●
CIP Messages
The weight and rate calibration values can be read and written by CIP messages.
Message Type: CIP generic
Service Code: 4C (hex)
Class Name: 4
Instance Name: 254
Object Attribute: none, leave this blank
It is possible and convenient to configure the MSG instruction to use the same tag for
both source and destination.
There are four read and write calibration commands, each consisting of 20 DINT values
(80 bytes) as follows:
Command (see the list of commands below)
Channel (0 or 1)
Rate Decimal points (0-7)
7 pairs of rate calibration values. Each pair has an operating percentage
(OP) with two decimal places, and an associated rate, shown with the
number of decimal places specified by the Rate Decimal points parameter.
CalZeroCounts
CalLowCounts
CalibK
1. Command 1: Read calibration values. Use this command to read the rate and
weight calibration values.
2. Command 0x81: Write rate calibration values. Use this command to set the 7
rate calibration pairs.
3. Command 0x82: Write weight calibration. Use this command to set the 3 weight
calibration values: zero counts, low counts, and CalibK (weight per A/D count).
4. Command 0x83: Write both weight and rate calibration values.
The two commands below read and write configuration data. Each returns 52 DINT
values, which are the command, the channel, and the format word, followed by 49
parameter values, which are listed in the order of the parameter IDs.
5. Command 0x0F: Read configuration data.
6. Command 0x8F: Write configurati o n dat a.
The format word is like the one in the configuration data table, but in the least significant
word of the DINT rather than in the most significant word.
Note The values written via these commands are NOT saved automatically to the non-volatile
memory and are lost on power down if no save to non-volatile command is given.
28
●
●
Chapter 4
●
●
●
Chapter 5 Calibration
●●●●●
The Feeder Controller Module should be calibrated before use. We also recommend that
you verify the calibration periodically or wh en not i n use f or exte nded periods of time.
Users and service personnel should be familiar with the procedures in this chapter before
installing or operating the Feeder Controller Module.
NOTE Do not perform a calibration while the application is in operation.
Pre-Calibration Procedures
Verify that the load cells have been properly installed.
Refer to your load cell I&M manual for proper installation instructions.
On some sensors and cells an arrow indicates the direction of the applied load. If
the arrow is pointing in the wrong direction, change the position of the load cell
so that it is mounted in the direction of the applied load.
Check for binding on the Load Cell or other parts of the weighing system.
CAUTION: Binding on a scale/vessel or load cell does not allow the load cell free vertical movement
and may prevent the instrument from returning to the original zero reference point.
A load cell must be mounted so that
100% of the load (Vessel w/Contents)
passes vertically through the load cell.
Verify that nothing is binding the load
cell. This means that nothing is draped
across the scale/vessel or the load cell,
such as a hose, electrical cord, tubes,
or other objects.
Verify that nothing is in contact with
the scale/vessel other than service
wires and piping that have been
properly mounted with flexible
connections.
Electrical Check Procedures
Load Cell/Point Input/Output Measurements
The Feeder Controller Module is designed to supply 5 VDC excitation to as many as four
350-Ohm load cells/points. The expected output from each load cell/point will depend on
the mV/V rating of the load cell/point and the weight.
Properly Installed Load Cell
29
●
●
Chapter 5
●
●
●
Fo
r example, a 2mV/V load cell/point will respond with a maximum of 10 mVDC at the
system’s full weight capacity, which includes the weight of the vessel and the weight of
the product as measured by the load cell/point. Thus, if the load cell/point weight
acity is rated at 1000 pounds, the load cell/point will be 10 mVDC at 1000 pounds,
cap
7.5 mVDC at 750 pounds, 5 mVDC at 500 pounds and so on.
A zero reference point will
vary from system to system
depending on the “Dead Load”
of the vessel. “Dead Load” is
the weight of the vessel and
appurtenances only, with no
product loaded. In our
example we will assume the
dead load to be 500 pounds.
The operating range for the
scale in this example is 5-10
mVDC with a 500 pound
weight range. Note that after
zeroing the instrument, the 0
reading refers to the zero
reference point and not
absolute 0 mVDC or absolute
0 weight.
Millivolts/Weight Scale
NOTE Load cell/point measurements are checked with a digital volt meter at the J1 connector
on the front of the module or by using INTEGRATED TECHNICIAN with the HI 215IT
Junction Box.
Load Check
Place a load (weight) on the scale or vessel, and check to see if the weight reading on the
input table changes in the proper direction.
For example: If the input table display reads 100 pounds and a 20-pound weight is placed
on the vessel or scale, the ladder logic display should read 120 or some value over 100.
With the input table display reading 100 pounds, if a 20-pound load is placed on the
vessel or scale and the reading is 80 pounds, the reading is going in the wr ong di rect i o n
and indicates some problem with the system.
If the input table reads improperly or shows no change, something is wrong with the
setup. If the input table changes weight in the proper direction, remove the weight and
proceed to calibrate the module.
C2 Calibration
C2 calibration requires C2 load sensors. (If you have no C2 load sensors, see Hard
Calibration below). The Weigh Module reads the performance characteristics of the
individual load cells and detects the quantity of load cell(s) in the system. C2 Calibration
can be performed via Allen Bradley RS LOGIX 5000 using either the output table or
ladder logic.
C2 Calibration Using Ladder Logic
Verify that the parameters have been setup for your weighing process in accordance with
the setup information provided in Chapter 4.
A Ladder Logic example on the Hardy Instruments Inc. Web Site explains how to run the
C2 Calibration. See http://www.hardyinst.com
Sample Programs. You will find the sample programs under the HI 1756 Heading.
. Click Support > Online Support >
30
●
●
Chapter 5
●
●
●
Hard Calibration
Hard Calibration is the traditional method of calibration using test weights. Hardy
recommends that the test weights total 80 to 100% of the load capacity.
Hard Calibration Ladder Logic Example
Verify that the parameters have been setup for your weighing process in accordance with
the setup information provided in Chapter 4.
A Ladder Logic example on the Hardy Instruments Inc. web site explains how to set the
weigh process parameters. Depending on your application, this Ladder Logic example
may or may not meet your requirements.
The Hard Calibration Ladder Logic Example is located at the Hardy Instruments Inc.
Web Site. See http://www.hardyinst.com
Programs. Select the product you are calibrating on the pull-down list; then click on the
Ladder Logic Example for the HI 1756 –WS or -FC Modules.
. Click Support > Online Support > Sample
31
●
●
Chapter 5
●
●
●
Chapter 6 Troubleshooting
●●●●●
Chapter 6 provides procedures for troubleshooting the electrical, mechanical and
firmware elements of the HI 1756 FC and for using Hardy’s Integrated Technician (IT®)
software utility to isolate problems. Flow charts provide troubleshooting s for the rate
controller, load cells, and cabling.
Disassembly and Reassembly Notes, Warnings and Cautions
WARNING EXPLOSION HAZARD - DO NOT DISCONNECT EQUIPMENT OR REPLACE
COMPONENTS UNLESS POWER HAS BEEN SWITCHED OFF OR AREA IS KNOWN
TO BE NON-HAZARDOUS.
Always replace broken or damaged module s or har dw are i mmediately.
Always check to be sure that no loose parts are sitting on printed circuit boards
or electrical connectors or wires when disassembling or reassembling.
Always protect printed circuit boards from electrostatic discharge (ESD).
Always use approved ESD wrist straps and anti-static pads.
Always follow proper safety procedures when wo r ki n g on or arou n d the R at e
C
ontroller.
This chapter describes several tests that can
problems require the use of two or more tests to determine the cause.
If a problem is isolated to a load cell, it may not mean the load cell is the damaged
ponent. Mechanical imbalances and system piping stress (lack of piping flexures,
com
cables draped over pipes etc.) can make a load cell seem to be the problem.
If you are in doubt as to how to resolve a problem
Hardy Instruments Web-tech at http://www.hardyinst.com. Web-tech is updated often
and is available 365 days a year 24/7. It contains several frequently asked questions to aid
you in troubleshooting, and it provides a form for requesting additional information and
answers to questions, with no waiting on hol d.
shorten the time for troubleshooting. Most
or if you need assistance, look for
Weight and Voltage Testing
This test section looks at the readings from ALL the load cells to test overall system
performance and signal voltage readings. This test works for all varieties of load cell
connection systems.
NOTE IT ®is a registered trademark of Hardy Instruments Inc.
Weight
s displays the amount of force seen by all load cells installed in the summing junction
Thi
box. Further investigation to isolate system problems will require the use of hand tools
and Multi-meters or the Integrated Summing Junction box and using the IT test section.
This force can show an imbalance or weight distribution problem. Review your system to
insure proper balance. Motors can account for this problem. Piping should not apply any
appreciable force on the scale.
32
●
●
Chapter 6
●
●
●
mV/V
DC voltage signals are between 0-15 millivolts. Overloads and negative millivolt
readings are not shown as actual readings but 15.3 for over voltage and 0.0 for negative
voltage. You will need to use a multimeter with a 200 or 300 mVDC range to view the
out-of-range voltages. Millivolt/volt equals the output from a load cell per each volt of
excitation. The HI 1756 FC reads the load cell output in mV/V, which provides higher
resolution (4 decimal places) than an mV reading. This provides more sensitivity to help
you troubleshoot the condition of the load cell under certain conditions. Load cells are
rated in millivolts/volts. To convert to mV, multiply the mV/V times the sense voltage.
IT Test
If your system has an Integrated Technician Summing Junction box, the IT test can help
identify individual load cell problems up to a maximum of four load cell selections.
Sensor Number
I
ndicates which sensor is under test. Select the target sensor to be tested.
Warning Do not install your HI 215IT summing board in areas susceptible to high vibrations. The
relays on the board can chatter and affect your weight readings and the vibration can
crystallize the solder joints.
General Troubleshooting Flow Chart Index
Drifting or unstable weight readings
Electrical, Mechanical and
Configuration reviews
Verify individual load sensor operation
Trad. Cal - A/D Failure Error
Mechanical Inspection
Electrical Inspection
Load Sensor Installation
A
B
F
G
H
J
K
33
●
●
Chapter 6
●
●
●
A1 - Guidelines for Instabilities on Formerly Operating System
A1
UNSTABLE RATE CONTROLLER
Disconnect external signal cables and
shields, except AC Power
Monitor the reading
for stability
Yes
Reconnect signal
cables one at a
time
Monitor the
display for stability
If installing any cable causes
unstable readings
REVIEW TROUBLESHOOTING
SECTION B: B1.1-B1.7
STABLE?
No
Problem could be in
the instrument. Contact
Hardy Customer Support
PH: 800-821-5831
Go to
B
34
●
●
Chapter 6
●
●
●
B - Guidelines for Instabilities on Formerly Operating Systems
(Cont’d)
B
Check for
Electrical Stability
OK?
Yes
Check for
Mechanical Stability
OK?
Yes
Check Configuration
settings for
stability
No
No
B1
B2
35
●
●
Chapter 6
●
●
●
OK?
Yes
Go To
A
Stability
No
B3
B1 - Guidelines for Instabilities on Formerly Operating Systems
(Cont’d)
B1.1
B1.2
B1.3
B1.4
B1.5
B1
Physical Grounding All common equipment share a common ground point.
Keep the ground cable length to earth ground as short as possible.
Install a new ground rod if the cable length is excessive.
Cable Cuts or breaks in the load cell insulation allow moisture to wick into the
cable and load points. This can setup stray capacitance charges and allow
ground currents to exist. This could create a highly intermittent situation.
Vessel, Fill and discharge piping Ground all to a common point to eliminate electrical differences in potential
and static build-up.
Load Cells Ground straps must be installed to provide a direct discharge path to ground
around the load points.
Cable Routing Separate high voltage sources and cables form low voltage signal cables.
Stay a minimum of 14 inches from magnetic fields and VFD controls.
Avoid parallel high voltage and signal cable runs.
Electrical
36
●
●
Chapter 6
●
●
●
B1.6
B1.7
Cable Shielding Ground low voltage cable shields only at the controller end.
Grounding both cable ends produce ground currents.
Verify, with and ohm meter, the shield is only grounded at the weight controller.
Disconnect eh shield at the controller and check for an open circuit between ground
and shield. Reconnect the shield to ground and confirm a proper ground path from
the IT Junction box to the controller.
Verify the shield is not connected to ground at the IT Junction Box.
Load cell shields only pass thru the IT Junction boxes and are not connected
ground at that pont.
Weight Controller - Common AC ground and Chassis grounds.
Go to
B
B1 - Guidelines for Instabilities on Formerly Operating Systems
(Cont’d)
B1
B2
OK?
Yes
Vessel When inspecting a vessel, the Center of Gravity (COG) should be
low and centered equally over all the load cells. Insure the load is
directly over or under the load point to avoid side-loading and
No
that there isn’t any side loading from piping or external forces.
Install flexures on all piping to insure a free floating vessel.
Make sure the vessel and load cell mounts are mechanically stable
and fixed.
Large changes in individual load cells indicate a shift in the COG or
faulty load cells.
Piping and motors can effect the individual load cell readings.
Allow for a higher reading on load cells that support motors and
piping.
Insure pneumatic lines are not applying pressure to the vessel
when energized.
Use check (stay) rods to minimize vessel movement.
Make sure the check rods are loose and not interacting with
the vessel.
Power down all vibration, vacuum and pressurization equipment
during the test process.
B3
OK?
Yes
Return to
A
STABILITY
Configuration Settings
No
Incorrect WAVERSAVER settings can cause unstable weight readings.
Adjust to the lowest WS setting that gives you a stable reading.
Higher frequencies with low amplitude vibrations - Use WS settings 1
or 2 lower frequencies with high amplitude vibrations - Use WS setting
3 or higher incorrect number of decimal places. Reading weight
increments beyond the equipment applications level. (Sed Guideline
Calculations below)
Repeatability Divide the total load cell capacity, including decimal points by 10,000.
(Expected stable weight reading)
Resolution Divide the total load cell capacity, including decimals points by 30,000.
(The amount you can expect to see but not necessarily stable
C
37
●
●
Chapter 6
●
●
●
F - Verify Individual Load Cell Millivolt Readings
Testing an individual load cell signal output requires an IT Summing Junction box or
millivolt meter.
Use the load cell certificate to verify the millivolt per volt (mV/V) rating:
ple: 3mV/V load cells produce approximately 15mV at full load. That is 5 volts
Exam
excitation x 3 mV/V. At a scale capacity of 1,000 lbs. with 100 lbs. of deadload when
empty, the load point mV reading should measure 1.5mV.
F
Select
IT
TEST MV/V
Press ENTER
to check load
sensor
Record load
sensor mV/V output
level for
comparison
Repeat for all load
sensors
IT TEST Checks
individual load
sensor output
mV/V readings
No
MV/V
readings
acceptable?
Zero mV/V
reading
High mV/V
reading
High mV/V
reading
1) No dead load
Apply load and re-test.
2) Wiring error
Verify color code using the
load cell certificate
3) Open bridge circuit
Disconnect power and verify
load point bridge resistance
reading with an Ohmmeter
1) Stressed load cell, remove
all load and re-test.
2) Excessive loading
For additional
testing go to:
H
K
Defective load Cell
Replace and repeat
TEST F
38
●
●
Chapter 6
●
●
●
Yes
TEST COMPLETE
G - Calibration Failed: Not Enough Counts Between ZERO and
SPAN
This error only occurs at the SPAN parameter. You may ZERO out chains and temporary
calibration equipment to hold or hoist test weights. Zeroing the temporary weight does
not effect the calibration.
G
The difference between zero and span is less than
1000 counts
Using a millivolt meter, verify that:
• The signal millivolt reading is positive and within the
acceptable range of 0 to 15 mV.
• When weight is applied there is a positive increase
in the signal millivolt readings
• The compression load cell has not been installed
upside down. Refer to the load cell installation guide
for installation instructions.
• No mechanical binding is restricting the vessel
movement during the load
• The load cell wiring is correct
• Each load cell signal changes under load. A single
load cell installed upside down or wired backwards
can change the total signal output.
SPAN WEIGHT TOO SMALL
• 1000 counts out of 985,000 is very small
• A 100,000 lb scale would require a minimum of 101 lbs
Ye s
Contact Hardy
Instruments
Customer Service
(800) 321-5831
Ext. 1757
ERROR
No
PROCEED
WITH
CALIBRATION
39
●
●
Chapter 6
●
●
●
H - Mechanical Inspection
1) Keep flexures on the horizontal
2) Vertical flexures should be avoided
3) Do not use flexures to correct for misaligned piping
4) Do not use hose flexures to make right angle bends
5) Non-flexed piping should have an unsupported
horizontal run using a ratio of 36 times it’s diameter
6) Pipe flexure lengths should be a ratio of 6 times it’s diameter
7) Feed and discharge piping flexed
8) Are the flex joints on the correct side of the valve?
(a) You weigh the output valve, not the input valve
(b) Does the weight scale see all the product to be
weighed?
(c) If the product applies a force to a valve or pipe, that
pipe or valve must be included in the weight vessel.
(d) Proper position of the flexures are key
(e) Your vessel must seem to float.
H1
H
All pipes and conduits
flexible
H2
H3
H4
H5
H6
Verify Electrical
Mechanically isolated
from ladders and
connecting structures?
Are the load cells
properly mounted?
Are check rods
installed to dampen
vessel movement?
Are cables routed
properly?
Housekeeping
To
go to
J
1) Floors or structure does not interact
2) Local traffic does not interact
3) Protected from forklifts and adjacent processing
equipment.
1) Level, solid mounting base
2) The load cell is mounted right side up
3) All load cell bolts installed using anti-seize compounds
4) Mechanically aligned to compensate for expansion and
contraction
1) Protects the load cells from overload and impact forces
2) Limits the movement of the vessel
3) Rods must be loose and not interact with the vessel
1) Separate conduit for low and high voltage cables
2) Do not bundle low voltage with high voltage cables
3) Maintain at least 3 inches of separation
4) Maintain 14” separation from magnetic fields and 440 VAC
5) Cables are in conduit or tied up and protected from damage
1) Product, tools and production aids are off the vessel.
2) No workers are physically on the scale
3) Must protect equipment from environmental damage
4) Insure openings are sealed to keep water and environmental
contaminates from damaging
1) Verify the proper input power, AC or DC, is properly installed
2) Use a meter to verify neutral, ground and hot are correct
3)
Isolated from SCR and motor control circuits
4)
Use a Common earth ground.
(a) Keep ground cable runs as short as possible
(b) Excessive ground cable runs can act as an antenna
for AC noise
(c) Install grounding straps around load cells to direct
static away from the load cell and directly to ground
(d) Install ground straps on the input and discharge
piping and the vessel to a common earth ground
1) Verify the front LEDS illuminate
2) Completes the initialization process
3) Reads the weight. This weight value will not be
correct if a calibration procedure was not performed
1) Read the NET weight
2) Send a TARE command to ZERO the NET weight
3) Apply weight to the vessel
(a) Does the weight increase and decrease in the
correct direction with the weight?
(b) Does the weight return to ZERO NET?
(c) The weight value will not be correct until a proper
calibration is complete
1) Use the load cell certificate, manuals or drawings to verify the
load cell color code. Input = Excitation, Output = Signal
J4
To Verify Proper Load Cell
Operations Go to
Cabling
K
2) Shielding
(a) Grounded only at the rate controller
(b) Continuous shield connection from the load cell cable
to the controller. Single point EMI/RFI drain
(c) Terminated but not grounded at the summing box
3) Sense lines installed?
(A) Jumpers or sense lines in the J1 connector?
(B) Sense lines must be installed for C2 or Softcal
calibration
4) Use IT TEST to verify readings
41
●
●
Chapter 6
●
●
●
K - Load Sharing and Load Sensor Checkout
42
●
●
Chapter 6
●
●
●
Erratic Weight or Rate Control
This section explains how to resolve problems relating to rate and Rate of Change (ROC)
calculation, Rate Exception Control (REC), motor speed control, and weight calibration.
Rate calculations
1. Rate calcu
scale calibration using test weights.
2. Follow the weight troubleshooting flow charts and correct any equipment
binding, rubbing, and piping problems.
3. After an initial rate calibration on a new system, verify the calibration several
times to ensure consistency, and verify the calibration using the posted weight
loss over time.
4. If the rate displayed does not match your test samples:
Re-calibrate the scale and then the rate.
Review the troubleshooting tips for mechanical influences relating to the
Look for leaks in the delivery system or refill gate.
5. If the system is slow to change rate (or weight) readings.
Adjust the number of averages setting lower.
Adjust the WAVERSAVER setting lower.
See REC +/- settings below.
6. Look for a systematic and consistent weight loss. Determine what a stable rate
should be. If the rate displayed on the monitor continuously falls and rises and
you never get a stable rate or symmetrical weight loss pattern:
The rate may be too slow for the load call capacity.
The material may be bridging or liquefying and basically inconsistent.
The feeder motor may be feeding too fast, mechanisms may be damaged, or
lations are no better than the scale’s calibration accuracy. Verify the
feeder mechanism
working conditions may not be right.
43
●
●
Chapter 6
●
●
●
ROC calculation
OC reading does not necessarily indicate a smooth weight loss. The amount of
The R
ROC control required depends on the material currently being fed.
1. Since ROC calculations are developed from the weight reading, the weight
reading must be correct.
2. The Loss In Weight (LIW) ratio is calculated from the total scale load cell
capacity. If an LIW rate error greatly exceeds the weighing error:
Add decimal points up to 1 part in 50,000 to help determine the ROC.
Balance the WAVERSAVER setting and averages.
Motor speed control output signal
he motor speed control output signal indicates a problem, but the voltage and current
If t
levels measured on the terminals is correct:
1. Adjust the OP% out in manual mode.
2. In the ON condition, verify that the output signal matches the percentage of full
range. For example: 50% of a 0-10V signal should read 5 VDC at the analog out
terminal.
3. Adjust the WAVERSAVER setting and averages.
he output is properly wired back to the motor speed controller, verify that the PLC
If t
analog card parameters for that analog out are set correctly and that the HI 1756 FC
analog signal is programmed for the corrected controller terminals.
NOTE Hardy Instruments Inc. does not provide motor speed control converters or analog out
PLC modules. Consult the motor speed controller manufacturer’s manual for
troubleshooting and settings.
REC +/- settings
e rate exception control indicates whether the controller is running within the
1. Th
requested range. If a status bit is out-of-range, the REC status bit is displayed to
indicate the direction. While this may indicate that the rate is too small for the
scale’s accuracy or resolution, the reading can be used to determine the effect of
parameter and mechanical adjustments on improving the material flow control.
2. During auto rate calibration the PI settings are adjusted to optimize the flow rate
for your feeder settings and material. The speed of oscillation can be used to
view the effect of correction or adjustments to the PI settings.
P = 0-100% correction factor. P determines the amount of action or reaction
that is made in response to an out-of-range rate indication
I = the speed of that action/reaction. This value normally requires only a
small adjustment. (0.2 increments) If the rate is always high, reduce the I. If
it is always low, increase I.
The feeder fails to stop in HOLD, STOP or IDLE
ermine whether the motor speed control OP% analog card module reacts properly and
Det
goes to the low setting.
1. Verify with a multimeter.
2. Follow the manufacturer’s troubleshooting guide(s) to determine the
malfunction.
3. Verify that the Analog out is returning to the low parameter setting as set in the
PLC menu for that analog out channel.
NOTE Send a Stop or Hold signal when a stop conditi on occu rs. D o not rel y on the analog
signal to stop the feeder.
System and Load Cell Tests
Overview of Typical Load Cell System
The typical load cell system consists of one or more load cells/points and an HI 1756 FC
Rate Controller. If you have more than one load point, an optional summing junction box
can read data for individual load cells.
Load Cell/Sensor/Point - is a strain gauge-based force transducer that generates an
electrical signal proportional to the load applied to the scale. Tension or compression type
load cells/points can be used to measure pressure, load, or torque.
44
●
●
Chapter 6
●
●
●
SS
UNIVERSAL JOINT
OR
HOSE
NON METALLIC EXPANSION
EMBLY OR HOSE
A
USE SYMMETRIC BEAM LOADED
THROUGH SHEAR CENTER TO
AVOID TWIST WITH LOAD
JUNCTION
BOX
INTERMEDIATE SUPPORT FRAME
FULLY CONSTRAINED
LATERALLY WITH STAY RODS
BI N ACT IVATOR
HI 4060
Rate Controller
The load cell/point takes as an input the 5 volts DC excitation voltage generated by the
HI 1756 FC. It generates a millivolt output proportional to the weight on the scale (010mV DC for 2mV/V load cells/points or 0-15mV DC for 3mV/V load cells/points).
Rate Controller - is the part of the HI 1756 FC instrument that, among other functions:
Powers the load cell(s)/point(s)
Reads the millivolt signal output from the load cell(s)/point(s)
Digitizes, interprets, communicates the results in terms of weight and rate
INTEGRATED TECHNICIAN (IT®)
INTEGRATED TECHNICIAN (IT®) is a diagnostics utility that enables the operator to
rapidly troubleshoot the individual load cells in a weighing system. An HI 215IT
Summing junction box is required to read data for individual load points. It provides
separate inputs for each load cell.
If you have more than one load cell without the IT junction box, there is no easy way to
isolate the load cell signals.
If you have more than one load cell with the IT junction box, the system can provide both
the average numerical values and values specific to each load cell. The number for a load
sensor is based on the connections in the IT junction box.
Check the installation sequence in the box to determine which load sensor is number 1, 2
and so on. Always install the first load cell in position 1.
If you do not have the optional IT junction box, some of the options described below will
not appear on either interface.
Warning Do not install your junction box in areas that are susceptible to high vibrations since the
relays on the summing board can “chatter” and af f ect your wei ght rea di n gs.
●
●
45
Chapter 6
●
●
●
determine if an instrument or cabling problem exists, verify the basic operation of the
To
system by performing the following system checks.
Weight and Voltage Test
The Weight and Voltage tests are used to diagnose a weighing system and, if certain
types of problems are indicated, determine their source. It provides the total scale input to
the instrument, such as mV/V and Weight in the units selected (i.e. lbs, kg, oz, g).
Running the IT test will show the weight and voltage results for each load sensor,
including the following values:
Weight: Weight value recorded on the sensor
mV/V: The mV/V reading is sufficient to balance the corners of your scale or vessel.
These readings allow you to determine if the problem is in the instrument (internal) or in
a load sensor(s) (external). The normal specification range for the Rate Controller is 0-15
mV. Readings outside this range (15.5 mV, 3.1 mV/V Maximum or any negative values),
indicate an external problem. (most likely improper wiring).
When you check the results, if all the load sensors read 0.00, something is probably
wrong between the HI 1756 FC and the HI 215IT junction box, e.g., the cable may be
disconnected. Something could also be causing the box to not transmit the readings to the
HI 1756 FC.
If you get no reading for one or possibly two or more load sensors (e.g., sensor 3 reads
0.00 or the reading is larger or smaller than it should be) and you know that the sensors
are connected to the junction box, either the load sensor is malfunctioning or its cable to
the junction box is loose or incorrectly wired.
General Policies and Information
Hardy Instruments provides world-wide support for its products. The following
paragraphs describe Hardy's customer support services and equipment warranty. When
returning a product, call the Technical Service Department listed below for a Return
Authorization Number. You will need to provide your company name, address, telephone
number, equipment model number, S/N, and a brief description of the problem.
NOTE For all non-warranty repairs a purchase order or credit card information is required.
You can also go to the Hardy web site and request a Return Authorization numb er. An
RA# will be e-mailed to you. http://www.hardyinst.com/service/repair.php
Warranty
A warranty problem may be handled by returning the product to the factory for repair or
replacement under warranty. In the event you experience a problem with this instrument
contact your local Hardy Representative or the Hardy Instruments Service Center to
determine if the problem is covered under warranty.
Web Address: http://www.hardyinst.com/Service/term.php
Ordering Replacement Parts
Contact the
boards. Have your equipment model number and serial number ready.
Note System Support (Requires Purchase Order or Credit Card)
Technical Service is provided as follows:
New system start-up: Ensure that the installation is checked and correct;
Service: Engineers are trained and qualified to provide on-site installation,
●
●
46
Chapter 6
●
●
●
Hardy Instruments Sales Department to order replacement parts and option
instruments are calibrated, and operators trained.
calibration, and maintenance.
On-site training: A Hardy Support Representative can be scheduled to train your
operations and maintenance personnel. This can be as simple as basic load cell
theory or as complete as troubleshooting techniques which allow you to service your
equipment.
For Further Information Contact
Technical Service Manager
Hardy Instruments, Inc.
3860 Calle Fortunada, San Diego, CA 92123-1825
Telephone: +1 (858) 278-2900
FAX: +1 (858) 278-6700
Web Site: http://www.hardyinstruments.com
E-Mail: hardysupport@hardyinst.com