HANYOUNG NUX MA4N-A, MA4N-B, MA4N, MA4N-C Instruction Manual

INSTRUCTION MANUAL
Analog Multi Timer
MA4N
We appreciate you for purchasing HanYoung NUX Co.,Ltd product. Before using the product you have purchased, check to make sure that it is exactly what you ordered. Then, please use it following the instructions below.
- DIGITAL : Temperature Controller, Counter, Timer,Speedmeter, Tachometer, Panel Meter, Recorder
- SENSOR : Proximity Sensor/Photo Electric Sensor, Rotary Encoder, Optical Fiber Sensor, Pressure Sensor
- ANALOG : Timer, Temperature Controller
HEAD OFFICE
1381-3, Juan-Dong, Nam-Gu Incheon, Korea
TEL: (82-32)876-4697 FAX :(82-32)876-4696
Safety information
Before you use, read safety precautions carefully, and use this product properly. The precautions described in this manual contain important contents related with safety; therefore, please follow the instructions accordingly. The precautions are composed of DANGER, WARNING and CAUTION.
There is a danger of occurring electric shock in the input/output terminals so please never let your body or conductive substance is touched.
1. This product does not contain an electric switch or fuse, so the user needs to install a separate electric switch or fuse externally. (Fuse rating: 250V 0.5A)
2. To prevent defection or malfunction of this product, supply proper power voltage in accordance with the rating.
3. To prevent electric shock or malfunction of product, do not supply the power until the wiring is completed.
4. Since this product is not designed with explosion-protective structure, do not use it any place with flammable or explosive gas.
5. Do not decompose, modify, revise or repair this product. This may be a cause of malfunction, electric shock or fire.
6. Reassemble this product while the power is OFF. Otherwise, it may be a cause of malfunction or electric shock.
7. If you use the product with methods other than specified by the manufacturer, there may be bodily injuries or property damages.
8. Due to the danger of electric shock, use this product installed onto a panel while an electric current is applied.
1. The contents of this manual may be changed without prior notification.
2. Before using the product you purchased, make sure that it is exactly what you ordered.
3. Make sure that there is no damage or abnormality of the product during delivery.
4. Do not use this product at any place with corrosive (especially noxious gas or ammonia) or flammable gas.
5. Do not use this product at any place with direct vibration or impact.
6. Do not use this product at any place with liquid, oil, medical substances, dust, salt or iron contents. (Use at Pollution level 1 or 2)
7. Do not polish this product with substances such as alcohol or benzene.
8. Do not use this product at any place with a large inductive difficulty or occurring static electricity or magnetic noise.
9. Do not use this product at any place with possible thermal accumulation due to direct sunlight or heat radiation.
10. Install this product at place under 2,000m in altitude.
11. When the product gets wet, the inspection is essential because there is a danger of electric leakage or fire.
12. If there is excessive noise from the power supply, using insulating transformer or noise filter is recommended. The noise filter must be attached to a panel which is already connected to a ground and the wire between the filter output and power supply terminal must be as short as possible.
13.If puttig power cables closely together then It is effective against noise.
14.Do not connect anything to the unused terminals.
15.After checking the polarity of terminal, connect wires at the correct position.
16.When this product is connected to a panel, use a circuit breaker or switch
approved with IEC947-1 or IEC947-3.
17.Install the circuit breaker or switch at near place for convenient use.
18.Write down on a label that if the circuit breaker or switch is operating then the
power will be disconnected since the circuit breaker or switch is installed.
19.For the continuous and safe use of this product, the periodical maintenance is
recommended.
20.Some parts of this product have limited life span, and others are changed by
their usage.
21.The warranty period for this product including parts is one year if this product is
properly used.
DANGER
WARNING
CAUTION
Names and functions of respective parts
Selection of operation mode
Please select operation mode by turning of operation mode switch in front of panel. User can select 6 types of operation modes Operation mode is displayed as like A, B. C. D. E. F or A1, B1, C1, D1, E1, F1.
Selection of Time unit
Please select time by turning of Time range switch Use can select 16 types of time ranges and it is displayed as like sec, min, hrs, 10h
Time range
Dimensions
Panel cutout
Connections
Specifications
sec
min
hrs
10h
1. 2
3
12
30
0.12 ~ 1.2
0.3 ~ 3
1.2 ~ 12
3 ~ 30
1.2 ~ 12
3 ~ 30
12 ~ 120
30 ~ 300
Setting range
Max. time
Time unit
Time Limit contact 1c Instautaneouscontact 1c
Time Limit contact 2c
Time Limit 2c Time Limit 1c
Instautaneous 1c
24 - 240 V a.c/d.c 50 - 60 Hz
10% from supply voltage
4.4 V A (240 V a.c), 2.1 W (240 V d.c)
Max. 0.1 sec
Min. 20ms
Max.
5 % 0.05 sec
N.O: 10 A 125 V a.c, 5 A 250 V a.c, 5 A 30 V d.c
N.C: 3 A 125 V a.c, 2 A 250 V a.c, 1A 30 V d.c
Max. 0.3 %
Max. 2 %
Min. 100 M(Base on 500 V d.c)
2000 V a.c 50/60 Hz for 1 min.
2000 V Max.
10-55Hz double amplitude0.75mm
10-55Hz double amplitude0.5mm
300
Approx. 30G)
100 Approx. 10G)
Over 10 million operations (Open & Short frequency : 180/min)
Over 100,000 (250V a.c 3A load resistance)
Socket type 11 Pin
Socket type 8 Pin
-10 ~ 55 No condensation)
-20 ~ 65
No condensation)
35 ~ 85 %RH
About 100g (Including fixing bracket)
Non voltage input Impedance in a short circui t: Max. 2 M Residual voltage in a short circuit: Max. 0.7 V d.c Impedance in open: Min. 100 M
MA4N-A MA4N-B
MA4N-C
MinSignal
length
Input
condition
Vibration
Shock
Life
expectancy
START Input
START Input
INHIBIT Input
INHIBIT Input
RESET Input
RESET Input
Output
Mechanical
durability
Malfunction
durability
Mechanical
durability
Malfunction
durability
Mechanical
Electrical
M o d e
Supply voltage
Voltage regulation
Power consumption
Resetting time
Setting error
Repeat error
Temperature error
Insulation resistance
Dielectric strength
Impulse voltage
Terminal type
Operation ambient
temperature
Conservation temperature
Operation ambient humidity
Weight
(unit : mm)
(unit : mm)
MA4N-A : 2 relay work as Time limit. MA4N-B : The relay connected , ,
work as Instantaneous and othrealys work astime limit. Please refer to Timing charts for
working of relays
Two relays in Mode A1 and D1 work as Time limit. The relays in Mode B1, C1, E1, F1
connected , , work as Instantaneous. And other realys work as time limit. MA4N-C : According to timing charts,
relays works as Time limit or Instantaneous.
Please refer to Timing charts for working of relays.