Please check whether the product is the exactly same as you ordered.
Before using the product, please read this instruction manual carefully.
Please keep this manual where you can view at any time
HEAD OFFICE
Safety information
Alerts declared in the manual are classified to Danger, Warning and Caution by their criticality
DANGER
WARNING
CAUTION
DANGER
Do not touch or contact the input/output terminals because they may cause
electric shock.
WARNING
• If the product is used with methods other than specified by the
manufacturer, then it may lead to injury or property damage.
• Please install an appropriate protective circuit on the outside if malfunction
or an incorrect operation may be a cause of leading to a serious accident.
• Since this product does not have the power switch or a fuse, please install
those separately on the outside. (Fuse rating: 250V 0.5A)
•
To prevent damage or failure of this product, please supply the rated power voltage.
• To prevent electric shock or equipment failure, please do not turn on the
power until completing wiring.
• Since this is not explosion-proof structure, please do not use in a place
where combustible or explosive gas is around.
• Never disassemble, modify, or repair the product. There is a possibility of
malfunction, electric shock, or a risk of fire.
• Please turn off the power when mounting/dismounting of the product. This
is a cause of electric shock, malfunction, or failure.
• Since there is a possibility of electric shock, please use the product as
mounted on a panel while the power is being supplied.
DANGER indicates an imminently hazardous situation
which, if not avoided, will result in death or serious injury
WARNING indicates a potentially hazardous situation
which, if not avoided, could result in death or serious injury
CAUTION indicates a potentially hazardous situation which,
if not avoided, may result in minor or moderate injury
HANYOUNGNUX CO.,LTD
1381-3, Juan-Dong, Nam-Gu Incheon, Korea.
TEL:(82-32)876-4697 FAX:(82-32)876-4696 http://www.hynux.net
PT. HANYOUNG ELECTRONIC INDONESIA
INDONESIA
FACTORY
Jl. cempaka blok F16, No.02 Delta Silicon II Cikarang Bekasi Indonesia
TEL : 62-21-8911-8120~4 FAX : 62-21-8911-8126
• It is effective against noise if making the power lines of the product the
twisted pair wiring.
•
Please make sure the operation of the product before using since the
product may not operate as it intends if the alarm function is not properly set.
• When replacing the sensor, please turn off the power.
• In case of the high frequent operation such as proportional operation,
please use an auxiliary relay since the life span of the output relay will be
shortened if it connects to the load without the rated margin. In this case,
SSR output is recommended.
⁕ Electromagnetic switch: proportion cycle: set 20 sec min.
⁕ SSR: proportion cycle: set min.1 sec
⁕ Contact output life expectancy:
Mechanical - 1 million times min. (without load)
Electrical – 100 thousand times min. (250 V a.c 3A: with rated load)
• Please do not connect anything to the unused terminals.
• Please connect wires properly after making sure the polarity of terminal.
• Please use a switch or breaker (IEC60947-1 or IEC60947-3 approved)
when the product is mounted on a panel.
• Please install a switch or break near the operator to facilitate its operation.
• If a switch or breaker is installed, please put a name plate that the power
is off when the switch or breaker is activated.
•
In order to use this product properly and safely, we recommend periodic maintenance.
•
Some parts of this product have limited expected life span and aged deterioration.
• The warranty of this product (including accessories) is 1 year only when it
is used for the purpose it was intended under normal condition.
• When the power is being supplied there should be a preparation time for
the contact output. Please use a delay relay together when it is used as a
signal on the outside of interlock circuit or others.
•
When the user replaces with a spare unit due to product failure or other reason,
please check the compatibility since the operation can be varied by the difference
of setting parameters even though the model name and code are the same.
• Before using a temperature controller, please check if there is a
temperature difference between PV of the temperature controller and the
actual temperature. If there is a temperature difference, please correct the
temperature difference with using the input correct parameter “SL-5”.
CAUTION
•
The contents of the instruction manual are subjective to change without prior notice.
•
Please make sure that the specification is the same as what you have ordered.
• Please make sure that the product is not damaged during shipping.
• Please use this product in a place where the ambient operating
temperature is 0 ~ 50 ℃ (40 ℃ max, closely installed) and the ambient
operating humidity is 35 ~ 85 % R.H (without condensation).
• Please use this product in a place where corrosive gas (such as harmful
gas, ammonia, etc.) and flammable gas do not occur.
• Please use this product in a place where there is no direct vibration and a
large physical impact to the product.
• Please use this product in a place where there is no water, oil, chemicals,
steam, dust, salt, iron or others.
• Please do not wipe this product with organic solvents such as alcohol,
benzene and others. (Please use mild detergent)
• Please avoid places where excessive amounts of inductive interference
and electrostatic and magnetic noise occur.
• Please avoid places where heat accumulation occurs due to direct
sunlight or radiant heat.
• Please use this product in a place where the elevation is below 2,000 m.
• Please make sure to inspect the product if exposed to water since there is
a possibility of electric leakage or a risk of fire.
• For thermocouple (TC) input, please use a prescribed compensation lead
wire. (There is a temperature error if a general lead is used.)
• For resistance temperature detector (RTD) input, please use a small
resistance of lead wire and the 3 lead wires should have the same
resistance. (There is a temperature error if the 3 lead wires do not have
the same resistance.)
• Please put the input signal wire away from the power lines and load lines
to avoid the effect of inductive noise.
•
The input signal wires and output signal wires should be separated from each
other. If it is not possible, please use shielded wires for the input signal wires.
• For thermocouple (TC), please use ungrounded sensors. (There is a
possibility of malfunction of product by electric leakage if a grounded
sensor is used.)
•
If there is a lot of noise from the power line, installing an insulated transformer
or a noise filter is recommended. The noise filter should be grounded on the
panel and the lead wire between the output of the noise filter and the power
terminal of the instrument should be as short as possible.
Suffix code
ModelCode
☐ -☐☐☐☐☐☐
DX
2
3
Dimension
Input
Control
output
Alarm output
Option
4
7
9
K
J
R
D
P
V
C
F
M
C
S
S
W
A
N
Control operation ⁕1
Power supply
⁕
1 : The control operation can be changed in the parameter, SL9, and
※1 : Set-value (SV) is a control target, It is settable within the input range.
▒ Normal setting mode
※ Press the key continuously for 3 sec.
Process value
(PV) display unit
※1
※1
※2
※3
※ 1 ALH and ALL are initialized if SL3 is changed.
※ 2 or ※ 3 is an option.
(The parameters are not shown if retransmission output is unavailable)
(The retransmission output option is not available for DX4, DX7.)
▒
Initial set mode
(1) Press key and key simultaneously for 3 seconds to enter
the setting mode.
(2) Press key for 3 seconds to enter the PV / SV setting mode.
Caution
The value in the parameter SL1 (input selection) cannot be changed.
The SL1 is set according to the suffix code when ordering a product.
[ ] [ ] [ ] [ ]
Set-value (SV)
display unit
Set-value (SV)
NameDescription
High alarm (ALH)Displays high alarm set-value.
Low alarm(ALL)Displays low alarm set-value.
Proportional
band (P)
Anti-reset
windup (ARW)
Integral time
(I)
Derivative time
(D)
Control loop
break alarm
(LBA)
Proportioning cycle
(C)
Hysteresis
(HYS)
Full scale limit
Under scale
limit
Set data lock
(LOC)
Displays process-value. Set-value
(SV) can be set ※1
Set when proportional control is
performed. Control becomes ON/OFF
action with P set to “0” .
Prevents overshoot and/or undershoot
caused by integral action effect. It operates
automatically (AUTO) if ARW is set to “0”.
Eliminates offset occurring in proportional
control. Integral action is OFF with this
action set to “0”.
Prevents ripples by predicting output change
thereby improving control stability. Derivative
action is OFF with this action set to “0”.
Indicates control loop break alarm setting.
LBA is off if "0" is set.
Displays control output cycle (sec.).
Displays hysteresis of set-value for main
output. (ON/OFF control)
This limits the maximum of retransmission
output.
This limits the minimum of retransmission
output.
Turns the set data lock ON/OFF
Description
PV display unit
SV display unit
Input type selection (Fixed)
SetDescription
00001 - 5 V d.c or 4 - 20
0001K (CA)
0010KPt100 Ω
0011DIN Pt100 Ω
0100R (PR)
0101J (IC)
11110 - 10 V d.c
㎃
[ ] [ ] [ ] [ ]
PV display unit
SV display unit
Indicator / Controller
SetDescription
0Indicator
1Controller
℃
SetDescription
1℃
Decimal point selectable
SetDescription
0Decimal point
1None
Output (Fixed)
SetDescription
0Current output
1Relay or voltage pulse output
PV display
unit
※ For DCV input, if SL12 and SL13 are changed, the parameters related to temperature are initialized.
Description
Decimal point
position
selection
Input
correction
Hysteresis of
high alarm
(ALH)
Max. value of
temperature
setting range
Min. value of
temperature
setting range
Control
operation
direction
Hysteresis of
low alarm (ALL)
Input lter
Max. input
scale setting
Min. input
scale setting
Delay time of
high alarm
(ALH)
Delay time of
low alarm
(ALL)
SV display unit
(Setting range)
0 ~ 4
-100 ~ 100 % of FS
0 ~ 10 % of FS
Within input
range
Within input
range
0, 1
0 ~ 10 % of FS
0 ~ 100 second
9999Only for voltage input
-1999Only for voltage input
0 ~ 100 second
0 ~ 100 second
Remark
If you want 000.0, set
0002 on SV display unit.
Refer to input type
Refer to input type
0 : Reverse operation
1 : Direct operation
table
table
PV display unit
[ ] [ ] [ ] [ ]
SV display unit
Deviation alarm/Process alarm
SetDescription
0Deviation alarm
1Process alarm
Alarm mode selectable
SetDescription
0Band alarm
1High and Low alarm
Retransmission Output (Option)
SetDescription
0With retransmission output
1None
Hold function of alarm selectable
SetDescription
0With hold function
1Without hold function
※ ALH & ALL will be initialized if you change the deviation alarm or
process alarm at the SL3
Main functions
▒ Control loop break alarm (LBA) function
●Setting procedure
Usually set the set-value of the LBA to a value of twice the integral time (I).
The LBA can also be set by the auto-tuning (AT) function. In this case,
the set-value is automatically set to a value of twice the integral time (I).
●Description of operation
LBA function starts to measure the time from the moment when the
control output becomes 0% or 100%, and it detects the variation of the
process value in LBA setting time and then it determines that LBA is
ON or OFF by the variation.
• The LBA is ON if the process value is not increasing more than 2 ℃
within the LBA set-vale when the control output is 100%.
(In direct operation, the LBA is ON if the process value is not
decreasing more than 2 ℃.)
• The LBA is ON if the process value is not decreasing more than 2 ℃
within the LBA set-vale when the control output is 0%.
(In direct operation, the LBA is ON if the process value is not
increasing more than 2 ℃.)
●Causes of action
The LBA is activated under the following conditions.
•Controlled object trouble : Heater break, no power supply, incorrect
•Sensor trouble : Sensor disconnected, shorted, etc.
※ If causes of the above trouble cannot be identified, check the control
system.
●Cautions for control loop break alarm (LBA) function
•The LBA function is activated only when the control output is 0 % or
100 %. Therefore, the time from trouble occurrenece till the activation
of the LBA function equals the time of when the control output
becomes 0 % or 100 % plus the LBA setting time.
• No LBA function is activated while the auto-tuning (AT) function is
activated.
• The LBA function is influenced by disturbances (heat sources, etc)
and as a result may be activated even if there is no trouble in the
control system.
•If LBA setting time is too short or does not match the controlled
object, the LBA may be turned ON/OFF or not be turned ON. In such
case, set the setting time of LBA to be slightly longer.
wiring, etc.
not closed, etc.
open or closed, etc.
The process-value does not change even if input
changes, etc.
34
▒ Auto-tuning (AT) function
MODE
MODE
MODE
MODE
The Auto-tuning function automatically measures, computes and set
the optimum P. I. D and ARW constants, The Auto-tuning function is
activated any time from any process states after power-on, while
temperature is rising and or when control is stabilized.
● After finishing settings other than PID and ARW, perform the Auto-
tuning operation.
● Press the key and key at the same time then, A. T indication
lamp flashes to start the Auto-tuning function.
● If Auto-tuning function ends, the A. T indication lamp stops flashing
automatically. When checking the auto-tuned value, press the key .
● When changing the constants automatically set by the Auto-tuning,
changes each constant according to each parameter setting
● When you want Auto-tuning function to be suspended, press the
key and key simultaneously, then the A. T indication lamp
stops flashing to release Auto-tuning function. In this case P. I. D and
ARW values are not changed (Maintain the value before the Auto-
tuning started)
● When you want to changes the SV (set-value) during Auto-tuning,
suspend it and perform PID control using the values before Auto-
tuning started.
▒ Set data lock function
The set data lock function is used to prevent changing of each setvalue by the front key and the activation of the auto-tuning function, i.e.,
prevent misoperation after setting has ended.
For set data lock, display by pressing the key, then set the
following value in accordance with setting procedure thereby enabling
data lock ON or OFF.
0000 : No set data locked.
0001 : Only set-value (SV) can be changed with the set data locked.
Setting other than the above locks all set date and A.T function.
▒ Alarm function
※ Each alarm operation can be set as shown below.
(▲: Set-value (SV) △: Alarm set-value)
High & Low alarm
▒ Control operation direction
Set a control operation at the SL9.
① 0 : Reverse operation for heating control
② 1 : Direct operation for cooling control
▒ Input filter
Select the input filter calculation time in SL11. The input signal may
have noise that can be a cause of fluctuation of the process value. This
function eliminates the fluctuation by displaying the calculated value in
preset time. When 「0」 is set, the input filter is turned OFF.
▒ Input scale
Set a range of input voltage for DCV input.
For instance, SL1 = 0000 (1~5 V DCV) input, SL12 = 100.0, SL13 = 0.0
will be displayed as below.
Input Voltage1 V3 V5 V
Display0.050.0100.0
▒ Alarm delay time
Set high and low alarm delay time at SL14 and SL15 respectively. Even
when alarm condition is met, if delay is set at SL14 and SL15, the
alarm is triggered after those settings are exceeded. However, alarm
off is not related to the delay setting.
▒ Anti reset wind-up
Set the anti reset wind-up with “A” parameter.
① Control in case of A = Auto (0)
Temperature
Target value
Overshoot is relatively small.
Band alarm
Deviation alarmProcess alarm
This alarm setting is that the alarm is activated if a few ℃ is higher or low than setvalue. For example, if the set-value of the temperature is 200 ℃ and a system is
designed to have that the high alarm (ALH) is activated when the process value is 205
℃ and the low alarm is activated when the process value is 190 ℃ then set the high
alarm (ALH) 5 ℃, and set the low alarm (ALL) 10 ℃. If the set-value is changed to 300
℃, the high alarm is activated at 305 ℃ and the low alarm is activated at 290 ℃.
High & Low alarm
Band alarm
Note) Regardless of the set-value, the high or low alarm is activated at the alarm set- value.
※ For the band alarm, the relay of the low alarm (ALL) is not activated but the relay of the
high alarm (ALH) is activated.
▒ Overscale and underscale
● If a process value exceeds the maximum temperature range due to
upscale (input break) or etc., the process value (PV) display unit
flashes overscale display 「“”」
● If a process value reaches below the minimum temperature range,
the process value (PV) display unit flashes underscale display
「“”」
▒
Model information after power on
•Input display
ex.) C : K
•Model display
ex.) d9. : DX9
d9 : DX9
d7 : DX7
d4 : DX4
d3 : DX3
d2 : DX2
•Version display
ex.) V 0.1 : Version 0.1
C : K
D : KPT100
P : PT100
R : R
J : J
V : 1 - 5 V d,c
or 4 - 20 ㎃
F : 0 - 10 V d.c
•Output
display
ex.) C : Current
R : Relay
S : Voltage
pulse
C : Current
Rising time is slow.
Time
② In case of a set value for temperature on “A” parameter.
Temperature
Overshoot is relatively large.
Target value
Time
Rising time is fast.
※
If “A” is too small, large overshoot or undershoot occurs. Set the value
the same as the proportional value.
Input type
Classifi-
cation
Thermo-
couple
RTD
DCV
SL1Input type
0001K- 50 ~ 1300 ℃- 50.0 ~ 999.9 ℃
0101J- 50 ~ 600 ℃- 50.0 ~ 600.0 ℃
(T.C)
0100R0 ~ 1700 ℃0.0 ~ 999.9 ℃
0010KPt100- 199 ~ 500 ℃
0011Pt100- 199 ~ 640 ℃
0000
1 - 5 V, 4 - 20 ✽1
11110 - 10 V
※ Accuracy : ± 0.5 % of FS
✽1 : ± 1 % of FS
1℃ (SL2 : X1XX)
- 1999 ~ 9999
✽
- 1999 ~ 9999
1
Range
0.1℃ (SL2 : X0XX)
- 199.0 ~ 500.0 ℃
- 199.0 ~ 640.0 ℃
Decimal point is
set by SL4
Dimension & Panel cutout & Connections
DX2
●
DX3
●
Apearence
Apearence
●
●
Panel cutout
Panel cutout
●
Connection diagram
●
Connection diagram
Unit : mm
DX4
●
DX7
●
DX9
●
Apearence
Apearence
Apearence
●
Panel cutout
●
Panel cutout
●
Panel cutout
●
Connection diagram
●
Connection diagram
●
Connection diagram
※ Reference : CURRENT : 4 - 20 ㎃ d.c, SOLID STATE : 12 Vd.c Min.
※ There is no earth terminal for DX4 and DX7.
Be careful this matter when you use.
5
Bright color TFT LCD &
Touch panel system
FEATURES
▒
Bright color TFT LCD & Touch panel system
▒ Various input types
(T/C 12 kinds, R.T.D 2 kinds, DC voltage
3 kinds)
▒
Horizontal & Vertical trend, Text, Bar graph,
History view
▒ 6 or 12 channel analog inputs, 6 external
inputs (D/I), 6 or 12 relay outputs (D/O)
▒ 4 alarms per channel
Computing, Function, Conversion function
▒
▒ RS232, RS422/485, USB, ETHERNET
communication
(MODBUS-RTU, MODBUS on TCP)
▒ Support Large capacity SD memory card
(FAT 16 / 32)
Programmable
Temperature & Humidity Controller
TH500TD500
▒ High Accuracy Control
▒ History management
▒ 300 pattern setting
▒ Temperature & Humidity PID group
▒ Convenient communication data
management
▒ Various output type
Programmable Temperature Controller
▒ Touch screen color LCD screen
▒ 4 P.I.D zone
▒ Universal Input
▒ Time signal 8 points
▒ Alarm output 4 points
▒ Heating / Cooling control output
▒ Contact input (D.I) 8 points/ Contact
output (D.O) 16 points
▒ Communication function
6
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.