Hanyoung NP100 Instruction Manual

NP100
Thank you for the purchase of HANYOUNG product. Please read this manual carefully.
NP100
Before you use, read safety precautions carefully, and use this product properly. The precautions described in this manual contains important contents related with safety; therefore, please follow the instructions accordingly. The precautions are composed of DANGER, WARNING and CAUTION.
Do not touch or contact the input/output terminals because they may cause electric shock.
1. If there is a possibility of an accident caused by errors or malfunctions of this product, install external protection circuit to prevent the accident.
2. This product does not contain an electric switch or fuse, so the user needs to install a separate electric switch or fuse externally. (Fuse rating : 250V 0.5A)
3. When setting, “Input type selection number” must be selected in the Group Input(G.In) and also “Output type selection number” must be selected in the Group Output(G.Out) before moving to other group. If not, data of other group will be changed to the initial stage.
4. To prevent defection or malfunction of this product, supply proper power voltage in accordance with the rating.
5. To prevent electric shock or devise malfunction of this product, do not supply the power until the wiring is completed.
6. Since this product is not designed with explosion-protective structure, do not use it at any place with flammable or explosive gas.
7. Do not decompose, modify, revise or repair this product. This may cause malfunction, electric shock or fire.
8. Reassemble this product while the power is off. Otherwise, it may cause malfunction or electric shock.
9. It you use the product with methods other than specified by the manufacturer, there may be bodily injuries or property damages.
10. Due to the danger of electric shock, use this product installed onto a panel while an electric current is applied.
1. The contents of this manual may be changed without prior notification.
2. Before using the product you have purchased, check to make sure that it is exactly what you ordered.
3. Check to make sure that there is no damage or abnormality of the product during delivery.
4. The ambient temperature do not exceed 0~50
& The ambient humidity do not exceed 35~85%RH
(no icing).
5. Do not use this product at any place with corrosive(especially noxious gas or ammonia) or flammable gas.
6. Do not use this product at any place with direct vibration or impact.
7. Do not use this product at any place with liquid, oil, medical substances, dust, salt or iron contents. (Use at the Pollution level 1 or 2)
8. Do not polish this product with substances such as alcohol or benzene.
9. Do not use this product at any place with excessive induction trouble, static electricity or magnetic noise.
10. Do not use this product at any place with possible thermal accumulation due to direct sunlight or heat radiation.
11. Install this product at place under 2,000m in altitude.
12. Attach the bractets(2pcs) on the fixed halls and tighten with a screwdriver. Fixing torque is about 14.7 N
cm (1.5 kg cm)
13. When the product gets wet, the inspection is essential because there is danger of an electric leakage or fire.
14. Use a compensating cable with thermocouple.
15. For R.T.D input use a cable which is a small lead wire resistance and without resistance difference to 3 wires.
16. To avoid inductive noise to input wires, seperate from the power and output wires.
17. Keep input wires away from output wires and use shielded wires to earth.
18. Use non-grounded sensor to R.T.D and thermocouple.
19. If there is excessive noise from the power supply, using insulating transformer and noise filter is rec­ommended. The noise filter must be attached to a panel grounded, and the wire between the filter output side and power supply terminal must be as short as possible.
20. It is effective to use a twisted cable for power supply against noise.
21. If alarm function is not set correctly, alarm output can not be operated at a trouble.
22. When replacing the sensor, please turn OFF the power supply.
23. Use an extra relay when the frequency of operation is rather high. In this case, SSR output type is recommended.
Electromagnetic switch : Proportional cycle time is Min. 20 sec SSR : Proportional cycle time is Min. 1 sec Contact output life : Mechanical : Min.10 million times (no load)
Eletrical : Min. 100 thousand times (rated load)
SSR drive pulse voltage, 4 ~ 20 mA DC are not insulated with internal circuit.
24. The instrument has IP65. Use rubber packing when installing the instrument to panel.
25. Do not connect anything to the unused terminals.
26. After checking polarity of terminal, connect wires at the correct position.
27. When this product is connected to a panel, use a circuit breaker or switch approved with IEC847-1 or IEC947-3.
28. Install the circuit breaker or switch at near place for convenient use.
29. Write down on a label that the operation of circuit breaker or switch disconnects the power since the devise is installed.
30. For the continuous and safe use of this product, the periodical maintenance is recommended.
31. Some parts of this product have limited life span, and others are changed by their usage.
32. The warranty period for this product including parts is one year if this product is properly used.
33. The heater power supply and the instrument power supply should be connected using the same power supply when a heater break alarm.
34. When the power is on, the preparation period of contact output is required. In case of use for signals of external interlock circuit, use with a delay relay.
35. When changing a contorller to extra one, please check all parameters.
Function Description
RS 485 / 422
Time signal 2 points
Summary
Program temperature controller is consisted of three types of modes: operation indicator mode, engineering mode, and program mode. Operation indicator mode is displayed when the power is on and it indicates process value and set value, process value and output volume, and remaining time of the corresponding segment when in operation. Engineering mode sets up the basic functions of the instrument including types of input (sensor) and output, communication, retransmission, alarm, control output, PID, and auto tuning. Program mode sets up the control program. It establishes the number of program repetition, pattern number, segment number setup, program start condition, time signal, program ending mode, and each segment
s parameter.
Feature
Option
PV display
Digit number
Accuracy
Sampling time
Input type
Output type
Relay
Transistor
Standard
Speed
Max. Com. line
4 digits
0.1 %
250 ms
Universal input (selectable by parameter) refer to page 6
Universal output (selectable by parameter) refer to page 6
SSR / SCR
Relay
Current / SPS (power suppy for sensor)
(Use RET output terminal)
2 points
2 points
2 patterns & 20 segments (1 PT is max. 10 seg.)
RS485/422
600 ~ 9600 bps
31
Control
Output
Retransmission output
Alarm output
Time signal output
1 point
Measurement input
Contact input
SCR / SSR pulse
Retransmission output
Relay control output
Alarm output
Transistor output
Power supply
3 points (RUN,RESET,HOLD)
1 point (Current or SSR output)
1 point
1 point (C contact)
2 points (A contact)
2 points (Time signal)
100 - 240 V AC 50 - 60
Pattern & Segment number
Communication
Hard Ware
NP100
(Unit : mm)
Dimmension Panel cutout
NP100-
Model
Number
Function
1
0
1
2
3
Programmable Controller (96 X 96 mm)
None
Time signal 2 points
RS 485/422
Time signal 2 points +RS 485/422
Option
Caution Ground connection cable ( )
- Ground connection cable is a thick wire that is over 2 mm2in width. Wire with more than the third type ground connection (below 100
ground connection resistance).
- The length of the ground connection cable must be within 20m.
- Ground 1 point from the ground terminal.
- Do not spread cable between the ground terminals.
Caution Wiring
Main power must be off before wiring
Operate after disconnecting the main power and confirming the discontinuation of power to the cable connected to the main power by using a tester. There is danger of possible electric shock. Avoid any contact with the terminal when sending electricity.
Caution
Use panels with 2 ~ 10 mm tickness steel sheet.
Caution
Retransmission/SPS
-
ON OFF control* - -
Relay - -
Output 1 Output 2
Control type
SSR / SCR (Current)
RET / SPS
Display range : -5 % ~ +105 % of range 1 : below 0 : 0.2 % of F.S 1digit
2 : 0 ~ 400 : 5 % of F.S 2digit
Control output type
Input type and Measurement range
SSR -
SCR -
~ : Terminal number SPS: Power supply for exernal sensor
Thermocouple
(T.C)
R.T.D
Direct voltage
(V)
Direct voltage
(mV)
Scaling range
SL-L ~ SL-H = -1999 ~ 9999
**When using current input, use the
resistor 250
0.1% on input termi-
nal to use 4~20mA DC input.
0.10 % of F.S
1digit
0.15 % of F.S
1digit
0.1 % of F.S 1digit
0.2 % of F.S 1digit
0.1 % of F.S 1digit
Input type Code
Range ( )
Accuracy
K
K
J
E
T
R
B
S
L
N
U
W
Platinel
JPT100
PT100
1~5V**
0~10V
-10~20 mV
0~100 mV
-200 - 1370
-199.9 - 999.9
-199.9 - 999.9
-199.9 - 999.9
-199.9 - 400.0
0 - 1700
0 - 1800
0 - 1700
-199.9 - 900.0
-200 - 1300
-199.9 - 400.0
0 - 2300
0 - 1390
-199.9 - 500.0
-199.9 - 640.0
*1
*1
*1
*1
*1
*2
*1
*1
Caution Measurement Input Wiring
- When wiring the input line, cut off the controller and the external power.
- Be careful with polarity and wire the input signal at some interval from power circuit and ground connection circuit.
- Use shielded input cable when wiring and earth the shield 1 point.
Caution Control output wiring
- In case of wiring or eliminating the control output, cut off the controller and the external power.
- Use a shielded line for SSR pulse or Current output when wiring.
Relay
NP100
6-1. The function of individual LED
Function description
display lamp
display lamp
display lamp
PT1 display lamp
PT2 display lamp
RUN display lamp
WAIT display lamp
HOLD display lamp
MAN display lamp
AL1 display lamp
AL2 display lamp
TS1 display lamp
TS2 display lamp
OUT display lamp
AT display lamp
SEG1~10 display lamp
PV display lamp
SV display lamp
Lights during the ascending section of the segment.
Lights during the soak section of the segment.
Lights during the descending section of the segment.
Lights during the pattern 1.
Lights during the pattern 2.
Lights during the program run.
Lights when WAIT operation during the program run.
Lights when HOLD operation during the program run.
Lights during the manual control.
Lights during the Alarm 1 operation.
Lights during the Alarm 2 operation.
Lights during the time signal 1 operation.
Lights during the time signal 2 operation.
Lights when the control output is ON.
Lights during the auto tuning.
Display present segment during the program run.
Display process value.
Display set value.
Function
LED display
Operate the current pattern number.
Input the parameter setup value Use when moving the parameter Press 2.5 seconds or longer to alternate the operation indicator mode and the engineering mode.
Exit running program and convert to stop. Exit runing MAN operation and convert to reset mode. Use to finish program setup mode.
Press to move to other digit.
Use to change the parameter value. Use to move to other group.
Use to change the parameter value. Use to move to other group.
When the program is running, press to hold the running segment. Press again to release the holding
Exit the running segment while operating program and operate the next segment.
Use to change the pattern nember. Press key to alternate P1 and P2
AUTO:Use to change MAN control to program mode. MAN:Use to change program mode to MAN control. Press key to alternate AUTO and MAN.
6-2. Function of control key
- press the key firmly with your finger
- Do not press the key with any sharpened thing. It could cause key malfunction
Caution
Automatic/Manual Operation Selection Method Press the AUTO/MAN key on the front panel to choose automatic and manual operation. On manual mode, the MAN LED will be turned on and MAN LED will be turned off for automatic mode. The control output value continuously changes with the operation of ascent and descent keys.
Caution
NP100
When it becomes “9” in any digit besides the 4th digit (4D), it will be rounded up to the next digit when the button is pressed continuously.
6-3. Function of 4 digits LED
1. Digital Formation
4D 3D 2D 1Digit
2. Possible range of maximum indication using the or button.
3. Rounding Up & Off of Digits
4. Maximum & Minimum Indication
Rounding Up
When the 4th digit indicates “9”, there will be no changes despite the continuously pressing of
1. Represented data is “+”.
--> When it becomes “0” in any digit besides the 4th digit, it will be rounded off to the next digit when the button is pressed continuously.
2. Represented data is “-”,
--> When “9” is indicated, it will be rounded off from the next digit when the button is pressed continuously.
Rounding Off
It indicates the greatest or the least of the selected item when it gets out of the range of the selected item (parameter).
If WTM = 0.00~99.59
--> If user selects over 99.60, it sets up 99.59, which is the maximum value. Moreover, it sets up the minimum value of WTM 0.00 if less below -0.01 is selected.
Ex.)
5. Operation of Button
4D 3D 2D 1Digit
It blinks in its change operation position.
6. Operation of button
7. Position of “ - (minus)” It is always indicated in the 4th digit.
Use , , buttons to change to the desired value. Then move to the next setup item (parameter) after registering with the button. However, this setup value must be within the range of each setup item (parameter). button leads to the next setup item without pressing any other buttons besides the button.
NP100
Process value
Set value
Power
(ON)
AT.M
AT
1.P
P4Gr
1.I
1.D
1.MR
2.P
2.I
2.D
2.MR
3.P
3.I
3.D
3.MR
4.P
4.I
4.D
4.MR
AR
PID
FUZY
TMU
WTH
PWR.S
When control setup group recovers from a power failure, it resets if selected COOL from the
control mode but keeps operating the program just before the power failure if
HOT is selected. When power turns on from its off mode in manual operation condition, it operates in the output of the manual operation condition if “HOT” is selected from the motion mode at the time of power recovery of the control setup group.
Press for
2.5 seconds
P1Gr
P2Gr
P3Gr
Process value
Output value
Display remain
time of segment
WZ
Displayed in running condition
PID OFF
PID=OFF
or
Remain time of segment is indicated in running
Caution Operation when power is on.
Caution
Preparation must be carried out in engineering mode when operating the controller. There are setup mode for input and output functions and setup mode for control function in engineering mode but must start with the setup of the input and output functions.
Caution Mode Setup
Mode setup is recommended after completing the Program operation since the set value varies in accordance with the setup of the specific parameter. Each parameter may not be indicated in accordance with the selection of form, addendums, control type and varieties of the control system.
: It is indicated when option is
ordered.
A1TY
A1DB
AL-1
A2TY
A2DB
AL-2
HYS
PR-S
BPS
PRI STP DLN ADR
RP.T
OUT
O.ACT
CT
PO OL-H OL-L
FR-L
INP
FR-H
DP-P
SL-H SL-L
RJC FILT
BIAS
B.OUT
P.E1 P.E2
RET RET.H RET.L
* : It is not indicated in ON/OFF control. #: It is indicated in running.
Process value
Set value
G.RPT
SEG.N=0
Power
(ON)
Program mode
RPT
G.PT
PT.NO
SEG.N
n.SSP
n.STC
n.T10
n.JC
n.T2F
n.T20
n.T1F
n.PI 1
n.TM1
n.SP1
n.PI 2
n.TM2
n.SP2
n.PI A
n.TMA
n.SPA
SEG.N=1 SEG.N=2
SEG.N=10
NP100
Process value
Output value
Display remain
time of segment
Press for
2.5 seconds
Operation indicator mode
PT.NO=n
PT.NO=0
: It is indicated when option is ordered.
Program mode is recommended after completing the engineering mode since the set value changes and initializes in accordance with the changes in specific engineering mode. Some modes are not represented in accordance with the forms, choices, and control type of the controller.
Caution
Operation indicator mode is displayed when the power is ON and it indicates process value and set value, process value and volume of output, and remaining time of the corresponding segment when in operation.
Model NP 100 program temperature controller is divided into operation indicator mode and
program mode and this program mode is further divided into engineering group and program group.
Operation
Indicator Mode
Engineering
Group
Program Group
Engineering mode sets up the basic functions of the instrument including types of input and output, communication, retransmission, alarm, controlling movement, PID, and auto tuning.
Program mode sets up the control program. It establishes the number of program repetition, pattern number, segment number setup, program start condition, time sig­nal, program ending mode, and each segment
s parameter.
8-1. Engineering Group Setup
Power
ON
(Press 2.5
second.)
Must start with the setup of the input and output.
Engineering group
Caution
Program group
(1.Input setup group) (refer to page 14)
8-1-1
8-1-2
8-1-3
8-1-4
8-1-5
8-1-6
8-1-7
8-1-8
(2.Output setup group) (refer to page 15)
(3.Communication setup group) (refer to page 16)
(4.Retransmission setup group) (refer to page 17)
(5.Alarm setup group) (refer to page 18)
(6.Control setup group) (refer to page 19)
(7.PID setup group) (refer to page 20)
(8.Auto tuning setup group) (refer to page 21)
Press button to enter the engineering mode from each setup group
- Preparation must be carried out in engineering mode when operating the controller.
- There are set up mode for input and output functions and set up mode for control function in engineering mode but must start with the setup of the input and output functions.
Caution
8-1-1. Input Setup group
Refer to Input type and
measurement range
Setup range
Display
condition
Initial value
Input group
Input type
selection
Max. limit selection
Min. limit selection
Decimal point
position
Max. scale setup
Min. scale setup
Te mperature
compensation
PV filter
PV bias
Burn-out
Refer to Input type and
measurement range
(FR-H > FR-L)
0~3
-1999~9999
(SL-H > SL-L)
ON , OFF
OFF , 1~120
-100~100 %(EUS)
OFF , UP ,DOWN
Always
Always
In Voltage
input
In Voltage
input
TC
Always
Always
1370
-200
1
100.0
K(1)
0.0
ON
OFF
0 %
UP
Item
NP100
1) Selection of Input Type: NP100 Program Temperature Controller supports universal input and can be conveniently used by selecting and setting up the input signal symbol of the
Input Type Range List. This list includes the application input sensor and input types in accordance with voltage among the total of 18 types of input such as 12 types of thermocouple input (13 types of range), 2 types of R. T. D input, and 4 types of direct current voltage input.
2) Selection of Maximum and Minimum Range: Select the maximum and minimum value of the range within the maximum range for the setup item in changing the range.
3) Setup of Decimal Point Position: When selecting voltage input (V, mV) for the input type, decimal point can be indicated by selecting the position of first through third in order to indicate process value in dec­imals. (Select
1 to indicate one decimal place 000.0 .)
4) Selection of Maximum and Minimum Scale: Select the maximum and minimum scale when selected voltage input (V, mV) for the input type.
5) Selection of Temperature Compensation: As for the thermocouple input, select
ON for the selection of temperature compensation to compensate voltage for the terminal temperature. Otherwise, it will show declination as much as the terminal temperature (surrounding temperature).
6) Selection of Process Value Filter: When instability of the measurement value for the digital instrument is severe due to the external noise, reduce the instability of the process value by selecting the filter value.
7) Selection of Process Value Bias: Select correction value when it is necessary to correct the process value due to the error in input sensor.
8) Selection of Burn-Out Operation: As the safety mode of output in OFF condition by ordering the maxi­mum or minimum value and comparing with the set value when input (sensor) is disconnected, maxi­mum process value is indicated if UP is selected and minimum is indicated when DOWN is selected, thus output remains in OFF condition.
Setup below items.
Always
Signal
Signal
ON / OFF,
SSR, SCR,
Relay
Setup range
Display
condition
Initial value
Output group
Heating / Cooling
control selection
Heating cycle time
1~1000 sec.
0~100 %(EUS)
-5.0~105.0 %
OL-L+1Digit~105.0 %
-5.0~OL-H -1Digit %
Always
Heating
30 sec.
0.5 %(EUS)
0.0
Relay
100.0 %
Output type
selection
Hysteresis
Preset output volume
Max. output value
Min. output value
REV : heating
DIR : cooling
SSR
Relay
ON/OFF
Always
PID
control
0.0 %
Item
8-1-2.
1)Selection of Output Type : Control output can be selected from the relay on-off output, relay PID control output, SSR Driving
Pulse output, and voltage output by choosing “Output Type Selection Symbol” from the Control Output Type List.
2)Selection of Heating & Cooling control : Control method includes controlling by heating and cooling by freezing function. Choose REV (reverse
motion) for heating control and DIR (ordinary motion) for cooling control.
Setup below parameters.
Always
Reverse motion(REV)
Ordinary motion(DIR)
SV
SV
ON if PV
SV ON if PV SV
3) Heating Cycle Time : When selected relay or SSR output for the control output
: It is an item that selects the frequency of ON-OFF in proportion to output. Generally, set 30 seconds
for the relay output and 2 seconds for the SSR output in consideration of the life span.
4) Hysteresis
: This item sets the range between the ON temperature and OFF temperature
when relay ON-OFF control is selected from the control output.
5) Preset Output Volume
: This is useful when preheating condition must be maintained through continuous output volume previ-
ously set up by disconnecting the output from the PID calculation during the burn-out (disconnected sensor) A/D error.
6) Maximum & Minimum Value of Output : This item allows the setup of maximum and minimum percentage in which the output volume of the
control output would be operated by.
Hysteresis
SV
output
PV
ON
OFF
NP100
8-1-3. Communication Setup Group
Signal
Setup range
Display
condition
Initial value
Communication
setup group
1
2 bit
7 or 8
(except PC Link : 8)
1~99(max. 31 devices)
0~10
Option
Option
Option
Option
Option
Option
Option
NONE
1
8
1
PCL.0
0
Protocal
selection
Communication
rate
PARITY
STOP BIT
PCL.0: PC LINK
PCL.1: PC LINK SUM
Item
DATA LENGTH
ADDRESS
RESPONSE TIME
600 / 1200 / 2400 / 4800 / 9600 bps
NONE / EVEN / ODD
9600
Setup below items.
8-1-4. Retransmission Setup Group
Response time = (handling time + response time) 10 ms
Caution
Retransmission Output Wiring
- Must disconnect the controller and external power source when setting up/removing a receiver since there is danger of electric shock.
- Use same terminal for retransmission output and SPS output. Use of the terminal with what function of output is selected through parameter.
- 4/20m ADC is outputted for the retransmission output.
- When using the retransmission output, it is impossible to use the SPS function for sensor.
SPS Output Wiring for Sensor
- Must disconnect the controller and external power source when setting up/removing a sensor since there is danger of electric shock.
- Same terminal is used for the SPS output and the previous retransmission output. Using the terminal as an output of one side is selected by the parameter. (24 VDC 20mA DC MAX)
Caution! PC-LINK Communication / LADER Communication Wiring
- Must disconnect the controller and the external power source when connecting to the communication terminal due to the danger of electric shock.
- Connect the termination resistor (220
1/4W) at the end or master located at the both ends of the
communication equipment.
Signal
Setup range
Display
condition
Initial value
Retransmission
setup group
Always
PV
Retransmission output selection
Max.
Retransmission
output
Min.
Retransmission
output
PV, SV, MV(output volume), SPS
Setup below items.
Item
T.C, R.T.D : FR-H~FR-L
mV,V : SL-H~SL-L
(RET.H > RET.L)
T.C, R.T.D : FR-H~FR-L
mV,V : SL-H~SL-L
(RET.H > RET.L)
RET=PV
MV,SV
RET=PV
MV,SV
T.C,RTD : FR-H
mV, V : SL-H
T.C,RTD : FR-H
mV, V : SL-H
1) Selection of retransmission Output : Process value, output volume or setup value can range from 4~20 mADC as retransmission output
and when SPS is selected, power for external sensor will be outputted. (24 VDC 20 mA MAX)
2) Selection of Maximum & Minimum Retransmission Output : 4 ~ 20 mADC output can be selected within the range of value from the maximum range selection
(FR-H) and the minimum range selection (FR-L) in case of thermocouple or R. T. D input. As for the voltage output (V, mV), select the desired maximum and minimum range within the maximum scale (SL-H) and (SL-L).
8-1-5. Alarm Setup Group
Caution!
Alarm Output Wiring
- In relay close contact output, use relay to operate ON/OFF when the close contact capacity exceeds
240VAC, resistance 1A, and 30VDC resistance load 1A.
- Connect the Bleeder resistance for the current to flow more than the opening and closing volume of the
relay when opening or closing of small amount of current.
- There is life span ([Resistance load] for over 100,000) for relay. Connect CR Filter (when using AC) or
diode in the direct current L load).
Signal
Setup range
Display
condition
Initial value
Alarm setup
group
0.0~100.0 %(EUS)
Setup below items.
Absolute value : 0.0~100.0 %(EU)
Deviation value : -100.0~100.0 %(EUS)
OFF,PUL,CONT
0.5 %
0.0
0.0
3
OFF
Alarm 1 selection
Alarm 2 selection
Dead band of
Alarm 1
Dead band of
Alarm 2
Alarm 1 set value
Alarm 2 set value
Patter 1 End
Patter 2 End
OFF
Item
4
NP100
1) Alarm - Select 1 or 2 Types : Select code number of the Alarm type from the “Alarm Type and Code” list.
2) Alarm - Set up Dead Band 1 or 2
: Set the ON-OFF width (dead band) when operating Alarm 1 and 2.
3) Alarm - Set Value of 1 or 2
: Set value for Alarm 1 & 2.
4) Pattern 1 ending signal : Since there is no separate output, pattern 1 ending signal setup item will be indicated when selected
number 21 from the Alarm 1 type selection. (However, pattern-1 ending signal will not activate when pattern - 2 is selected from the setup item at the completion of the program.)
5) Pattern 2 ending signal : Pattern-2 ending signal setup item is indicated when #21 is selected from the Alarm 2 type selection.
(Pattern ending signal setup item will not be indicated if #21 is not selected.) Here, if OFF is selected from the pattern ending signal setup item, it doesn
t activate, PUL allows output to be on for about 0.5 seconds and lastly if CONT. is ending, already setup alarm output will continue on. Press RST Key to remove the alarm.
EX) PUL selection
0.5 sec.
ON
ONOFF
Option
Option
code 21
selection
OFF,PUL,CONT
OFF / 1~22
Refer to “Alarm type and code”
(31, 32 page)
CONT selection
OFF/ON
HH.MM (00
00 )
MM.SS (00
00 )
OFF/0~max. range
OFF / 0.01~99.59
COOL / HOT
8-1-6. Control Setup Group
1) Selection of Fuzzy Function : Fuzzy function is an over shoot inhibitory function using the fuzzy reasoning. Fuzzy function can pro-
vide control effects in the following situations: Starting the control when there are variation between the desired set value and actual process value Wanting to reduce the operative preheating period Having severe load changes Having frequent changes to set value
2) Selection of Time Unit : Maximum of 99 hours 59 minutes or 99 minutes 59 seconds
can be selected in the setup item for the selection of time unit.
3) Setup of Wait Zone : Process value must agree in accord to the process of programmed set value in program temperature
controller but unpredicted events occur. Here, if the temperature variation set in the wait zone when moving segments, program can continue on to the next segment. However, if it is outside the variation range, it doesn
t move on from the current segment to the next segment but rather waits
until it enters the set range of wait zone.
4) Setup of Wait Time : When the process value doesn
t agree with the progress of the programmed set value in the program temperature controller, in other words, when the process value is not controlled within the range of set variation between the set value + the wait zone, program continues on when the wait time elapses.
5) Power Recovery Motion Mode : Can choose between COOL or HOT in the set up item. If COOL is selected, the system resets when
recovered from the power failure and if HOT is selected, it continues on from the segment operated just before the failure.
However, must start from the beginning of the segment even if the system recovers to the
segment just operated before the power failure.
Signal
Setup range
Display
condition
Initial value
Control setup
group
Always
Always
Always
Always
OFF
HH.MM
OFF
OFF
COOL
Fuzzy function
selection
Time unit selection
Wait zone setup
Wait time setup
Power recovery
motion mode
Item
Setup below items.
Except
ON / OFF
PV
Target SV
Subsidiary target SV
PV
Start FUZZYreasoning
Time
Fuzzy Function
Signal
Setup range
Display
condition
Initial value
PID setup group
Auto / 50.0~200.0 %
OFF / P1Gr ~P4Gr
0.1~999.9 %
OFF / 1~6000 sec.
OFF / 1~6000 sec.
-5.0 ~ 105.0 %
Always
Integral
time OFF
Auto
0
5.0 %
240 sec.
60 sec.
50.0 %
Anti Reset wind up
PID indication group
n. Proportion
n. Integral
n. Differential
Manual reset
Item
1) Anti Reset Wind Up : Anti Reset Wind Up operation is carried out to prevent over-integral when the control output value
reached the limitation. Integral time is not
0 and integral time executes the ARW operation under the following conditions when AUTO is selected for the auto tuning execution from the auto tuning setup group.
DV 0 & output value maximum restriction DV<0 & output value maximum restriction
2) Selection of PID Indication Group Number : The PID control integer possesses 4 types and the operated PID integer can indicate and set up the
items when selecting manual operation. The operative integer of the PID group in agreement with the selected number from the auto tuning selection in the auto tuning setup group is applied to each pat­tern segment of 4 types due to the selection of pattern segment PID group number of segment #0 in memory program setup mode.
3) n. Proportion : If select PID 1 group (P1GR) from the setup item of PID indication group number selection, 1 group
proportion (1.p) with n. proportion is indicated. Here, the proportional value of the operated 1 group is indicated and can be changed and set up manually.
4) n. Integral Time : According to the PID indication group number selection, 1~4 group integral time will be indicated in
the setup item and will be automatically remembered and manually changed/set up due to the auto tuning.
5) n. Differential Time : According to the PID indication group number selection, 1~4 group differential time will be indicated in
the setup item and will be automatically remembered and manually changed/set up due to the auto tuning.
6) Manual Reset : If “0” is selected as the integral time, variation occurs in control due to proportionate movement. Such
variation can be eliminated through manual reset. (Parameter appears only when the integral time is set up “0”)
Setup below items.
8-1-7. PID Setup Group
NP100
P.I.D
control
Always
Always
P.I.D
control
Signal
Setup range
Display condition
Initial value
Auto tuning
setup group
OFF/1~4
STD:Standard AT
LOW:Low PV AT(*1)
Except
RUN& ON/OFF
STD
OFF
8-1-8. Auto Tuning Setup Group
Auto tuning type
AT operation
selection
Item
control outuput
ON ON ON
OFF
OFF
AT=ON
ON/OFF control
Time
SV -10% of SV scale
PID control
PV
SV
AT
point
AT operation
control outuput
ON
ON
ON
OFF
OFF
AT=ON
ON/OFF control
Time
AT end on The 3rd peak
PID control
PV
SV
AT operation
Standard AT
Low PV AT
Setup below items. Please select 1 at “ the AT operation selectin” to run.
Except
RUN& ON/OFF
Caution! Auto Tuning Operation/Stop
Do not use the auto tuning function in the following process.
- Control process with fast response system such as flow control and pressure control.
- Process that doesn
t allow ON and OFF of an output not even momentarily.
- Process that can
t handle huge loads in the operation.
- Process that is in danger of having negative influence on the product quality by exceeding the allowed range of changes in set value.
- If the desired set value is changed during AT, the changed goal will carry out AT and when AT is complet­ed, the desired set value will be changed to the new value.
- When burn out and A/D error occurs during AT, AT will be stopped and Preset output will be outputted.
(*1) When Low is selected from the auto tuning type selection, it is operated from the -10% of the set value.
The symbol for the auto tuning setup group is only indicated in operative period. The auto tuning output is not indicated if ON-OFF has been already selected.
1) Selection of Auto Tuning Type
: Must select one method from the two types: standard auto tuning method and low process value auto
tuning method. The standard auto tuning method is a method that operate based on the set value and low process value auto tuning is operating from the -10% value of the set value scale (set value scale : Scale from the minimum range or the maximum range to the set value scale.) If such method is select­ed, the over shoot on the set value can be reduced since it’s controlling from the operated PID value.
What is Auto Tuning?
--> It refers to the automatic setup function for optimum PID number by a controller that automatically
measures and calculates the characteristics of the control system. The auto tuning method generates limited cycle by producing ON/OFF control output during the 2.25 time frame and then calculates P, I, D base on the time frame and amplitude.
2) Selection of Auto Tuning Operation : As for the auto tuning operation selection, can choose from OFF or 1~4 groups and if OFF is selected,
auto tuning is not executed. If #1 of the groups from 1~4 groups have been selected, then the auto tuning is executed and stored in #1 PID when the operation is completed.
3) Stop on Auto Tuning : If desire to stop the long hours of auto tuning, select off during auto tuning operation. It returns to
PV/SV indication screen after OFF selection.
NP100
After “finishing the setup of the engineering group, go into the program mode by pressing or on “Group mode”. Also, on operation mode condition (initial mode when power is ON), engineering group will be indicated when pressing for 2.5 seconds, and program mode will be represented when pressing or .
Power
ON
Engineering group
Program groupt
(Repeat time setup)
(pattern number is initially set 0 . Use buttons in order to select the pattern number wish to set up. It indicates as a superior group when pressing at the
0 setup condition.).
1 Pattern has been assigned.
See page 24 of “0” segment parameter of program setup.
Set up segment number 1. See 1 segment parameter.
Set up the next segment in the same way as the segment 1.
It turns to operation mode when pressing button for over 2.5 seconds. here, press to turn to program.
or
Run
condition
Standard auto tuning has been selected as the setup item of auto tuning type seleciton.
OFF has been selected as the setup item of auto tuning operation selection.
To execute the PID auto tuning, choose one group from 1 to 4, then auto tuning will be executed (front AT indicator lamp will blink) and save the operation value in the selected PID group. Program temporarily stops while auto tuning is in process but the program continues on when the process finishes.
To operate auto tuning, press button for over 2.5 seconds on program operation condition.
Auto tuning setup group is displayed.
Engineering group is displayed.
It sets up the repeat frequency and set up items.
Signal
Setup range
Display
condition
Initial value
Setup group for program repeat
frequency
0 : limitless frequency
/ 1~99
Always
1
8-2-1. Setup Group for Program Repeat Frequency
Repeat
frequency setup
Item
1)Set up of repeat frequency : It is an item the decides the number of repetition for the program established in each pattern. It keeps repeating when “0” is set and the number could range from 1 to 99.
Setup group for program repeat frequency is indicated if the system is operated as follow when power is ON.
Power
ON
2.5 sec
Setup group for program frequency will be indicated if operated as follow under the power ON
condition (operation indicator mode). However, if you do not operate the key for more than 30 seconds, operation indicator mode will be displayed.
Power
ON
2.5 sec.
Signal
Setup range
Display
condition
Initial value
Program setup group
0~10
Within range
Always
on pattern
selection
on pattern
selection
on pattern
selection
on pattern
selection
on pattern
selection
on pattern
selection
on pattern
selection
PID control
Always
0
-200
SSV
OFF
OFF
OFF
OFF
RST(RESET)
1
-200
Patter number
selection
Item
Setup of n. pattern time
signal-1 ON time
Setup of n. pattern time
signal-1 OFF time
Setup of n. pattern time
signal-2 OFF time
Setup of n. pattern time
signal-2 ON time
Program
completion mode
n pattern 1 segment PID
group no. selection
Target set value
Setup of n pattern 1
segment time
n pattern 10 segment
PID group no. selection
Target set value
Setup of n pattern 10
segment time
SSV : Start SV
PV : Process value
It sets up the program to be controlled after finishing
the engineering mode setup.
OFF / 00.00~99.59
OFF / 00.00~99.59
(ON time < OFF time)
OFF / 00.00~99.59
OFF / 00.00~99.59
(ON time < OFF time)
RST/HOLD/PT-1/PT-2
0~10
Within range
OFF / 00.00~99.59
(Time unit is set at the
control setup group)
1~4
Within range
OFF / 00.00~99.59
(Time unit is set at the
control setup group)
Always
Always
PID control
Always
OFF
OFF
1
-200
NP100
1) Selection of Pattern Number : NP100 temperature controller can set up pattern 1, and pattern 2. Select “pattern 1” to operate in the
setup item of pattern number selection. (Pattern refers to one setup program.)
2) Selection of segment number : It is designed to set up to 10 segments for each pattern. At the beginning, choose
0 segment then
set up basic condition of the program.
Segment number
( 1 ~ 10 )
0~10
Segment number
selection ( 1 ~ 10 )
Always
10
“0” segment setup
Setup of
start set value
Start type selection
1 or 2 pattern
Always 1
3) Setup of Start Set Value : In the program temperature controller, start temperature value can be set up. It could either start from
the current temperature in the beginning of the first operation of the system or can even start from the set value in the start set value.
4) Selection of Start Type : Select the start conditions when operating the program.
If process value (PV) is selected, it starts from the currently sensed temperature and if the start set value (SSV) is selected, it starts from the temperature set up in the start set value item.
5) Setup of n pattern time signal-1 ON time : It turns ON after the set time of time signal -1 of already selected pattern.
6) Setup of n pattern time signal -1 OFF time : It turns OFF after the set time of time signal -1 of already selected pattern.
The ON time and OFF time setup of n pattern time signal-2 is the same as the setup method of time signal -1.
Output turns ON after the setup time in the ON time mode and the output turns OFF after the setup time of OFF time.
7) Program Completion Mode:
When pattern 1 is selected as mode upon the completion of pattern 1, the system operates until the program repetition frequency set in the system and then resets. However, when HOLD is selected, the
last set value is maintained. When pattern 2 is selected upon the completion of pattern 1, patterns 1 and 2 get connected. When pattern 1 is selected upon the completion of pattern 2, pattern 1 will be connected. When pattern 2 is selected upon the completion of pattern 2, it operates repeatedly for the number of RPT frequency. For example, when selecting the pattern 2 as mode upon completing the program Pattern 1 and after setting 3 times for the program repetition frequency, patterns 1 and 2 will be operat­ed once and then the pattern 2 will be operated twice.
8) Selection of n pattern and n segment PID group number: PID group can be applied to each pattern and each segment of 4 types of PID group to be controlled. However, stable control result can be acquired when group 1 is operated besides the peculiar situations.
9) Setup of Target Value: Set up the target temperature value for each pattern and segment under control.
10) Time Setup of n pattern and n segment: Set up the time that reaches or maintain the target tempera-
ture value for each pattern and segment under control.
Each segment can set up to 10 segments with the above method.
Operation (RUN)
Time signal
ON time
OFF time
1 channel
Thermocouple, R.T.D(pt), Direct voltage
Thermocouple, R.T.D : changeable within range
Direct voltage : Variable max. voltage & min. voltage within range
250 ms
Below decimal point of measurement range
Thermocouple / mV input : 1 M
min.
V DC input : Approx. 1 M
Input channel number
Input type
Input range
Sampling time
Input resolution
Input resistance
Lead wire tolerable
resistance
Input tolerable resistance
Input tolerable voltage
Noise removal rate
Standard
Standard junction temp. compensation tolerance
Burn-out detection
Accuracy
9-1. Input
R.T.D input : max. 10 / 1 wire
Thermocouple : max. 250 mV / V DC input : max. 2 K
mV / Thermocouple / RTD : 10 V V DC :
20 V
NMRR: min. 40 dB (50/60 Hz
1 %)
CMRR: min. 12 dB (50/60 Hz
1 %)
TC / RTD (JIS / IEC / DIN)
1.5 (15-35 )
2.0 (0-50 )
T/C : OFF, UP / DOWN Scale R.T.D : UP Scale (Detection current ; Approx. 50 nA)
0.1 % of F.S
NP100
9-4. Retransmission Output
Current output range : 4~20 mA DC Resistive load : 600
max.
Accuracy :
0.3 % of max. scale (4~20mA range) Resolution : Approx. 3,000 Output ripple : 0.1 % (P-P)max. of scale (150Hz) Sampling : 250 mS Power supply for external sensor : 24 V DC 20 mA Max.
If selecting SPS in the retransmission group, power supply for external sensor will be outputed from
terminal
& .
9-2. Control output
9-3. Alarm Output
Retransmission
output
Relay output
Contact capacity : 240 V AC 1 A, 30 V DC 1 A (resistive load) Setup point : 1a
2 Output : ON / OFF Dead band : 0.0 ~ 100.0 % EUS
Relay
contact output
SSR drive
voltage output
Current output
Contact capacity : 240 V AC 3 A, 30 V DC 3 A (resistive load) Contact : 1C Output operation : P.I.D control, ON / OFF Proportional cycle : 1 ~ 1000 sec. Output limit : 0.0 ~ 100.0 % range, higher limit(OL-H) or lower limit(OL-L)
selectable (valid when AT) ON/OFF hysteresis : 0 ~ 100 % Time resolution : 0.1 % or 10 mS ON voltage : 25 V DC min.(resistive load 600
min., 30mA limit when short) OFF voltage : 0.1 V DC max. Proportional cycle : 1 ~ 1000 sec. Output operation : P.I.D control Output limit : 0.0 ~ 100.0 % range, higher limit(OL-H) or lower limit(OL-L)
selectable (valid when AT) Time resolution : 0.1 % or 10 mS Current output range : 4 ~ 20 mA DC Resistive load : 600
max.
Accuracy :
0.3 % of full scale (4 ~ 20 mA range), Resolution : Approx. 3,000 Output ripple : 0.1 % (P-P) of max. scale (150 Hz) Sampling time : 250 mS Output operation : P.I.D control Output limit : -5.0 ~ 105.0 % range, higher limit(OL-H) or lower limit(OL-L)
selectable (valid when AT)
9-5. Communication Interface
9-7. Storage Condition
9-8. Structure
9-6. Operating Environment
NP100
Standard
Communication address
Communication method
Synchronization
Communication sequence
Communication distance
Communication speed
Start bit
Data bit
Parity bit
Stop bit
Communication protocol
Response time
EIA RS485 31, 1~99 setting available 2 wire half duplex Start-stop synchronous mode None
1.2Km max.
600, 1200, 2400, 4800, 9600 BPS
1 BIT 7 or 8 BIT None, even numbers, odd numbers 1 or 2 BIT PC LINK Reception treatment time + (Response time
10mS)
Installation environment
Normal operation
condition
Influence of ambient
temperature
Influence of voltage
regulation
Continuous vibration (5 ~ 14 Hz) : Forward width 1.2 mm max.
(4 ~ 150 Hz) : 4.9
(0.5 G) max.
Vibration : 14.7
(1.5 G), 15 sec. max. (each 3 direction)
Shock : 147
(15 G), 11msec max. (6 direction each 3 times)
Ambient temperature : 0 ~ 50 Ambient humidity : 35 ~ 85 % RH (no condensation) Influence of magnetic : 400 AT/m max.
Warm-up time : 30 min. min. T/C, Voltage input :
1 V/ or 0.01 %/ of F.S.
R.T.D input :
0.05 / max.
Analog output :
0.05 % / max. (continuous output)
Analog input :
V / 10 V or
Analog output : 0.05 % of F.S / 10 V max.
Storage temperature
Storage humidity
Shock
-25 ~ 70 5 ~ 95 % RH (no condensation) 1 m max. in packing condition
Material
Weight
Panel cutout
Plastic case 696 g (including brackets & box) 96(W)
96(H) 100(D)
Rated voltage
Tolerable voltage regulation
Power consumption
100 - 240 V AC, 50 - 60 Hz
10 % of rated voltage
MAX 10 VA(6.0 W max)
9-9. Power Supply
Safety standard
9-12. Standard
Primary terminal
Primary terminal
Ground
MIN. 500 V DC 20 M
MIN. 500 V DC 20 M
MIN. 500 V DC 20 M
9-10. Insulation Resistance
Secondary terminal
Ground
Secondary terminal
9-11. Dielectric strength
E M C
Primary terminal
Primary terminal
F.G.
2300 V AC 50/60 Hz for 1 minute
2300 V AC 50/60 Hz for 1 minute
1500 V AC 50/60 Hz for 1 minute
Secondary terminal
Ground
Secondary terminal
UL, C-UL approval (UL3121-1)
EN61010-1 (1993)
Plan
EMC emission EN 50081-2 (1993)
Plan
EMC Immunity EN 50082-2 (1995)
Plan
9-13. Function
NP100
Bias
Scaling
Filter
Pattern
Segment
PID Group
Auto Tuning
Proportional Band (P)
Integral Time (I)
Differential Time (D)
ON, OFF Control
Manual Reset
Direct/Reverse action
Emergency (Preset)
ON/OFF Hysteresis
Auto/Man
ARW
Fuzzy
Retransmission Signal
Scaling
SPS
Setup Point
Type of Alarm
Setup Range
Alarm Hysteresis
-100.0 ~ 100.0 % for measuring input range Valid setting a correction value.
According to setup of SL-H, SL-L of measuring range,
scaling is available.
OFF, 1 ~ 120 sec.
2 Patterns
10 Segments / 1 pattern
4 Kinds
According to SV, AT is operating.
Selection STD or Low PV
0.1 % ~ 999.9 %.
OFF, 1 ~ 6000 sec.
OFF, 1 ~ 6000 sec.
Select ON-OFF control in output group.
-0.5 ~ 105.0 %.
Valid when I=OFF
Select Direct or Reverse action in output group.
-0.5 ~ 105.0 % of output value.
0.0 ~ 100.0 % of range.
Changeable by front button
AUTO, 50.0 ~ 200.0 % at the PID group.
Selection ON or OFF on the control group.
PV, SV, MV, SPS
Setting PV, SV
24 V DC 20 mA max.
2 points.
High / Low alarm, High / Low deviation alarm.
Process alarm : 0 ~ 100 % of Range. Deviation alarm : -100 ~ 100 % of Range.
0.0 ~ 100.0 % of instrument range.
Measuring
Input
Control
Retransmission
Alarm
PV ALM HYS
PV
ALM+HYS
DEV
ALM HYS
DEV
ALM+HYS
DEV
ALM HYS
DEV
ALM+HYS
DEV
ALM HYS
(DEV
ALM+HYS)
DEV
ALM HYS
(DEV
ALM+HYS)
PV ALM HYS
PV ALM+HYS
9-14. Alarm Type
1) Output
High absolute alarm
Low absolute alarm
High deviation alarm
Low deviation alarm
High deviation alarm(inverted)
Low deviation alarm(inverted)
High
Low deviation alarm
High
Low deviation band alarm
High absolute alarm(inverted)
Low absolute alarm(inverted)
Pattern ending signal
1(11)
2(12)
3(13)
4(14)
5(15)
6(16)
7(17)
8(18)
9(19)
10(20)
21
Code ON condition OFF conditionName
PV ALM
PV ALM
DEV ALM
DEV ALM
DEV
ALM
DEV ALM
DEV
ALM
(DEV
ALM)
DEV ALM
DEV
ALM
PV
ALM
PV
ALM
The number in ( ) are for the waiting process. PV : Process value
ALM : Alarm setup value DEV : Deviation setup value
Pattern ending signal (see 21 page)
NP100
( : Set point , : Mins Alarm set pooint : Alarm set point )
Code
NO.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
High absolute alarm
Low absolute alarm
High deviation alarm
Low deviation alarm
High deviation alarm (inverted)
Low deviation alarm (inverted)
High
Low deviation alarm
High
Low band
High absolute (inverted)
Low absolute (inverted)
High absolute
with hold function
Low absolute
with hold function
High deviation
with hold function
Low deviation
with hold function
High deviation
with hold function (inverted)
Low deviation
with hold function (inverted)
High
Low deviation
with hold function
High
Low band
with hold function
High absolute alarm
with hold function (inverted)
Low absolute alarm
with hold function (inverted)
Pattern ending alarm
Function
Alarm type
Hysteresis
(Notice) : Display lamp will be ON when output OFF in inverted type.
FND display in English
Alphabet
FND Alphabet Number
FND
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
1
2
3
4
5
6
7
8
9
0
None
FND
NP100
8-1-1
Input setup group
Input type High limit range Low limit range High limit scale Low limit scale
8-1-6
Cntrol setup group
Fuzzy Time unit Wait zone Wait time
Power recovery
motion mode
8-1-5
Alarm setup group
Alarm-1
Alarm-2
Alarm type
Alarm dead band
Set value of alarm
Pattern ending
signal
Pattern-1:
Pattern-2:
8-1-2
Output setup group
Output type Cycle time hysteresis Preset output Max. output Min. output
8-1-8
Auto tuning
AT type AT operation
8-2-1
Program repeat
frequency
Frequency
8-2-2
Program setup
mode
Start SV
Start type
TS-1
ON time
OFF time
ON time
OFF time
TS-2
Program com-
pletion mode
8-1-7
PID setup group
Group 1
Group 2
Group 3
Group 4
ARW P
I
D
Manual reset
SV
Segment
Mode
Pattern
setup mode
Time
signal
Time
PID segment
TS-1
TS-2
12345678910