HANKISON HBP, HBP500, HBP600, HBP750, HBP900 Instruction Manual

...
3158050 Rev. E 1/08
XX-XXX-X
Internal Use Only
3158050e / 080102
INSTRUCTION MANUAL
HBP SERIES
MODELS
HBP500 HBP600 HBP750 HBP900 HBP1050
HBP1300 HBP1500 HBP1800 HBP2200 HBP2600
HBP3200 HBP3600 HBP4300
RATED
FLOW
500 SCFM 600 SCFM 750 SCFM 900 SCFM 1050 SCFM
1300 SCFM 1500 SCFM 1800 SCFM 2200 SCFM 2600 SCFM
3200 SCFM 3600 SCFM 4300 SCFM
MODEL
REFERENCE
500 600 750 900
1050
1300 1500 1800 2200 2600
3200 3600 4300
Contents
6.0 Operation ....................................................... 12
7.0 Maintenance .................................................. 29
8.0 Troubleshooting ............................................. 31
BLOWER PURGE
DESICCANT
COMPRESSED
AIR DRYERS
Drawings
P&ID Schematic Models 500 through 600 ............ 34
P&ID Schematic Models 750 through 4300 .......... 36
Electrical Schematic – 460VAC, 3 phase .............. 38
Electrical Schematic – 575VAC, 3 phase .............. 39
Electrical Schematic – 380VAC, 3 phase .............. 40
Electrical Schematic – 415VAC, 3 phase .............. 41
Electrical Data – Fusing & Wire Sizing .................. 42
WARRANTY .......................................................... 44
SERVICE DEPARTMENT : (724) 746-1100

1.0 General Safety Information

DANGER—Immediate hazard which will result in severe injury or death.
This equipment is designed and built with safety as a prime consideration; industry-accepted safety factors have been used in the design. Each dryer is checked at the factory for safety and operation. All pressure ves­sels which fall under the scope of ASME Section VIII, are hydrostatically tested in accordance with the latest addenda. A factory-installed safety relief valve is standard on each dryer.
WARNING — The following safety rules must be observed to ensure safe dryer operation. Failure to follow these rules may void the warranty or result in dryer damage or personal injury.
1. Never install or try to repair any dryer that has been damaged in shipment. See the Receiving and In­spection instructions in this manual for appropriate action.
2. This equipment is a pressure-containing device. Never operate the dryer at pressures or temperatures above the maximum conditions shown on the data plate.
Never dismantle or work on any component of the
dryer or compressed air system under pressure. Vent internal air pressure to the atmosphere before servicing.
3. This equipment requires electricity to operate. Install equipment in compliance with national and local elec­trical codes. Standard equipment is supplied with NEMA 4, 4X electrical enclosures and is not intended for installation in hazardous environments.
Never perform electrical service on the dryer unless
the main power supply has been disconnected. Parts of the control circuit may remain energized when the power switch is turned off.
WARNING—Hazard or unsafe practice which could result in severe injury or death.
CAUTION—Hazard or unsafe practice which could result in minor injury or in product or property damage.
The dryer data plate, attached to the electrical control box, contains critical safety and identification informa­tion. If the data plate is missing or defaced, immediately contact your local distributor for a replacement.

2.0 Receiving, Storing, and Moving

2.1 Receiving and Inspection
This shipment has been thoroughly checked, packed and inspected before leaving our plant. It was received in good condition by the carrier and was so acknowl­edged.
Immediately upon receipt, thoroughly inspect for visible loss or damage that may have occurred during shipping. If this shipment shows evidence of loss or damage at time of delivery to you, insist that a notation of this loss or damage be made on the delivery receipt by the carrier’s agent. Otherwise no claim can be enforced against the carrier.
Also check for concealed loss or damage. When a ship­ment has been delivered to you in apparent good order, but concealed damage is found upon unpacking, notify the carrier immediately and insist on his agent inspecting the shipment. The carrier will not consider any claim for loss or damage unless an inspection has been made. If you give the carrier a clear receipt for goods that have been damaged or lost in transit, you do so at your own risk and expense. Concealed damage claims are not our responsibility as our terms are F.O.B. point of shipment. Shipping damage is not covered by the dryer warranty.
4. Air treated by this equipment may not be suitable for breathing without further purification. Refer to OSHA standard 1910.134 for the requirements for breathing quality air.
5. Certain parts of the dryer are not insulated and may become hot during normal operation of the dryer. Do not touch any of these areas without first determining the surface temperature.
6. Use only genuine replacement parts from the manu­facturer. The manufacturer bears no responsibility for hazards caused by the use of unauthorized parts.
Safety instructions in this manual are boldfaced for emphasis. The signal words DANGER, WARNING and CAUTION are used to indicate hazard seriousness levels as follows:
2
2.2 Storing
Store the dryer indoors to prevent damage to any electri­cal or mechanical components. All packaging material should be left in place until the dryer is in position.
2.3 Handling
The dryer is designed to be moved by means of the ship­ping skid or the base channels. The dryer may also have lifting lugs for use with an overhead crane. Be sure to attach all of the lift points and use appropriate spreader bars to prevent damage to the dryer.
CAUTION — Never lift the dryer by attaching hooks or slings to the piping, or to any part other than the lifting lugs. Severe structural damage could occur.

3.0 Description

3.1 Function
Blower purge type regenerative dryers are an economi­cal and reliable way to dry compressed air to dew points below the freezing point of water. Desiccant dryers lower the dew point of compressed air by adsorbing the water vapor present in the compressed air onto the surface of the desiccant. Adsorption continues until equilibrium is reached between the partial pressure of the water vapor in the air and that on the surface of the desiccant.
systems supplied by a lubricated air compressor, use a High Efficiency Oil Removal Filter. A coarser filter will be required upstream of the Oil Removal Filter if heavy liquid or solid loads are present.
To ensure downstream air purity (prevent desiccant dust from traveling downstream) adequate filtration down­stream of the dryer is required. A High Temperature Afterfilter, typically rated at 450°F (232°C) operating temperature and capable of removing all desiccant fines 1 micron and larger should be installed at the dryer outlet.
These dryers continuously dry compressed air by using two identical towers, each containing a desiccant bed. While one tower is on-stream drying, the other tower is off-stream being regenerated (reactivated, i.e. dried out). The towers are alternated on- and off-stream so that dry desiccant is always in contact with the wet compressed air. In this way a continuous supply of dry air downstream of the dryer is possible. The switching from one tower to the other is controlled by a solid-state controller on either a fixed time basis (standard) or a demand basis (optional).
When a tower is placed off-line, it is slowly depressur­ized and the desiccant is regenerated. First, a blower draws in ambient air which is heated. The heated air flows through the desiccant bed, desorbs the moisture from the desiccant, and carries the desorbed water out of the dryer. The blower and heater are turned off when the desiccant bed is fully heated. When configured for cooling, a portion of the dry compressed air is diverted from the main air flow and throttled to near atmospheric pressure. This extremely dry, low pressure air passes through the hot off-line tower, partially cooling the desic­cant bed and reducing the dew point spike after tower change over. At the end of the cooling stage, the tower is repressurized to full line pressure. This prevents desic­cant bed movement and downstream pressure loss when the tower goes back on-line.

4.0 Installation

4.1 System Arrangement
Install the dryer downstream of an aftercooler, separator, receiver, and high-efficiency oil-removing filter(s) so that the dryer inlet air is between 40°F (4.4°C) and 120°F (49°C) and contains no liquid water or oil. Liquid water and/or inlet air temperatures above 100°F (37.8°C) can reduce drying capacity. Contact your local distributor for information on proper dryer sizing at elevated inlet air temperatures.
Adequate filtration is required upstream of the dryer in order to protect the desiccant bed from liquid and solid contamination. Use an Air Line Filter in systems sup­plied by a non-lubricated (oil-free) air compressor. In
DANGER — This dryer must be fitted with a high efficiency coalescing filter and liquid drainer that is maintained properly. Failure to do so could result in an in-line fire.
WARNING — The afterfilter, if installed, must be rated for 450°F (232°C).
4.2 Ambient Air Temperature
Locate the dryer under cover in an area where the ambi­ent air temperature will remain between 35°F (2°C) and 120°F (49°C).
NOTE: If dryer is installed in ambients below 35°F (2°C), low ambient protection requiring heat tracing and insulation of the prefilter bowls, auto drains and/ or sumps, and lower piping with inlet switching and purge/repressurization valves is necessary to prevent condensate from freezing. If installing heat tracing, ob­serve electrical class code requirements for type of duty specified. Purge mufflers and their relief mechanisms must be kept clear from snow and ice buildup that could prevent proper discharge of compressed air.
4.3 Location and Clearance
Install the dryer on a level pad. Ensure the dryer is level by grouting or shimming as necessary. Holes are provided in the dryer base members for floor anchors. Securely anchor the dryer frame to the floor. Allow 24 inches clearance on all sides of the dryer for servic­ing. Provide adequate clearance for prefilter element, afterfilter element and heater element replacement. Provide protection for the dryer if it is installed where heavy vehicles or similar portable equipment is likely to cause damage.
4.4 Piping and Connections
All external piping must be supplied by the user unless otherwise specified. Refer to Figure 2 for connection sizes. Inlet and outlet isolation valves and a vent valve are recommended so the dryer can be isolated and depressurized for servicing. The connections and pipe fittings must be rated for or exceed the maximum oper­ating pressure given on the dryer nameplate and must be in accordance with industry-wide codes. Be sure all
3
Compressor Aftercooler Separator Receiver Prefilters Afterfilters ReceiverDesiccant Dryer
Figure 1
Typical System Configuration
piping is supported. Do not allow the weight of any pip­ing to bear on the dryer or filters. Piping should be the same size as or larger than the dryer connection. Piping smaller than the dryer connections will cause high pres­sure drop and reduce drying capacity.
If the purge exhaust piping must be extended outside the dryer area, choose a combination of diameters, lengths, and turns that limits the additional pressure drop to 1/4 psid or less. BACK PRESSURE WILL CAUSE DRYER MALFUNCTION. Consult the factory for piping details if required.
WARNING — Do not operate dryer without installed mufflers. Exhausting compressed air directly to atmosphere will result in noise levels above OSHA permissible levels and rapidly expanding gas could potentially cause harm to persons or property.
Dryer bypass piping may be installed to allow uninter­rupted airflow during servicing. If the downstream appli­cation cannot tolerate unprocessed air for short periods, install a second dryer in the bypass line.
CAUTION — Do not hydrostatically test the piping with the dryer in the system. The desiccant will be damaged if saturated with water.
4.5 Electrical Connections
WARNING — These procedures require entering gaining access to the dryer’s electrical enclosure(s). All electrical work must be performed by a qualified electrical technician.
Connect the proper power supply to the dryer according to the electrical drawings in the back of this manual. Be sure to follow all applicable electrical codes.
NOTE: A disconnect switch is not provided as standard equipment and therefore, must be supplied by the cus­tomer.
Dry contacts (voltage free) are provided in the low ten­sion electrical enclosure for a remote alarm. The contact ratings are shown on the electrical drawing.
Connections to voltage-free common alarm contacts with a minimum 5-amp rating can be made at terminals TB4-1 through 3.
• Terminal TB4-3 is the common alarm connection.
• Terminal TB4-1 is the N.O.. (normally open) contact connection.
• Terminal TB4-2 is the N.C. (normally closed) contact connection.
• The alarm relay coil is energized when power is supplied to the controller input terminals and there is no alarms.
• The coil is de-energized when power is removed or when an alarm condition exists.
NOTE: Before turning high voltage on to the dryer, an ohmic test should be performed on the heater elements to insure they are dry before proceeding with start-up. This should be done after extended shut downs and long delays between delivery and start-up. Connect one lead of a megger to an unpainted surface of the control panel or dryer frame. Connect the other lead to each phase on the load side of the contactor. Adjust the megger to the 1500 volt setting. Perform the ohmic test on each zone of the heaters. A minimum value of 500k ohms must be obtained.
CAUTION - Failure to ohmic test heaters after ex­tended periods may cause heater failure.
4.5.1 RS-232 Connections
RS-232 connections can be made at the 3-pin connector labeled J3 and located at the upper left-handed corner of the control board. A cable for this connection can be purchased through your distributor.
4.6 Initial Desiccant Charge
Blower purge type regenerative dryers use activated alumina as the desiccant in the dryer towers.
Models 500 through 1050 are shipped with activated alumina (1/8” bead) in the dryer towers. Desiccant is shipped loose with all other standard models.
4
All desiccant shipped loose must be added to the dryer chambers before the dryer is put into service
Refer to TABLE 1, DESICCANT REQUIREMENTS for desiccant type and quantity per tower.
TO ADD DESICCANT
WARNING — The following procedure provides in­structions for adding the initial desiccant to the tow­ers. If replacing desiccant, refer to the “Procedure for Desiccant Charge Replacement” in Section 7.0.
1. Verify pressure gauges of both towers indicate 0 psig. If not, depressurize the towers according to the shutdown instructions in Section 6.
2. Remove the pipe plug or fill port flange cover (where applicable) from the desiccant fill port at the top of each tower. Refer to Figure 3 for the fill port loca­tion.
CAUTION – Pouring desiccant creates a fine dust; safety goggles, gloves and a dust mask should be worn by personnel installing desiccant. Refer to the Material Safety Data Sheet that accompanies desic­cant shipped loose for more complete information.
CAUTION – Do not tamp the desiccant in the towers. Tamping damages desiccant and causes dusting.
3. Refer to Table 1 for desiccant quantity per tower.
When using Table 1 you will find the desiccant quan-
tities listed in layers. Each layer will vary in depth due to the type, quantity and purpose of the desic­cant. Layer 1 must be installed first at the bottom of the vessel followed by layer number 2 etc., until the complete charge of desiccant has been installed.
TABLE 1 DESICCANT REQUIREMENTS (Quantity per Tower)
Layer
Model
500
600
750
900
1050
1300
1500
1800
2200
2600
3200
3600
4300
* AA = Activated Alumina ** TS = Tabular Support
1 2 3
354#
1/8” bead AA
453#
1/8” bead AA*
590#
1/8” bead AA
590#
1/8” bead AA*
710#
1/8” bead AA
48#
1/4” bead AA*
92#
1/4” bead AA*
92#
1/4” bead AA*
161#
1/4” bead AA
161#
1/4” bead AA*
258#
1/4” bead AA*
258#
1/4” bead AA*
719#
1/2” bead TS**
1/8” bead AA*
1/8” bead AA*
1/8” bead AA*
1/8” bead AA*
1/8” bead AA*
1/8” bead AA*
1/8” bead AA*
1/4” bead AA*
876#
1167#
1167#
1706#
1706#
2119#
2353#
146#
1/8” bead AA*
2679#
4. Utilizing an appropriate sized funnel, fill each desic­cant tower as follows:
a. Install the required quantity of tabular support or
activated alumina in layer 1 of each tower.
b. Level layer 1 and each subsequent layer of desic-
cant as added to each chamber.
c. Finish filling each tower with desiccant until all
desiccant has been installed. LIGHT tapping on the tower sides with a soft-face mallet should yield additional free space to allow installation of all desiccant required. DO NOT TAMP OR RAM DESICCANT.
5. Clean the fill port closure. Replace the fill plug using Teflon tape or another pipe thread sealant suitable for compressed air service. Reinstall fill port flange cover (where applicable) in each desiccant tower.
5
Dimensions and Connections
CENTERLINE OF
CUSTOMER DRY GAS
OUTLET CONNECTIO
N
TOP VIEW
R
SLOT
(TYP 4 PLACES
)
CENTERLINE OF
CUSTOMER WET GA
S
INLET CONNECTION
SIDE VIEW
(RIGHT CHAMBER REMOVED FOR CLARITY)
T
GAS OUTLET
E
(MAX)
F
G
C
D
B
A
(MAX)
H
K
N
(MAX)
P
L
S
GAS INLET
M
FACE OF CUSTOMER
WET GAS INLE
T
CONNECTION
FACE OF CUSTOMER
DRY GAS OUTLET
CONNECTION
R
SLOT
(TYP 4 PLACES)
TOP VIEW
SIDE VIE
W
(RIGHT CHAMBER REMOVED FOR CLARITY)
S
GAS INLET
T
GAS OUTLET
H
E
(MAX)
F
G
C
D
B
A
(MAX)
N
(MAX)
P
L
M
K
E
(MAX)
R SLOTS
(T
YP 4 PLACES)
TOP VIEW
SIDE VIEW
(RIGHT CHAMBER REMOVED FOR CLARITY)
S
AIR INLET
T
AIR OUTLET
F
C
D
B
A
(MAX)
N
(MAX)
M
L
P
K
G
Figure 2 (continued on next page)
(Contact factory to request certified drawings)
VIEW III
3200 through 4300 scfm
VIEW II
6
750 through 2600 scfm
VIEW I
500 — 600 scfm
Dimensions and Connections
Figure 2 (continued from previous page)
DIMENSIONS IN INCHES
A 53 55 60 60 64 66 80 80 85 85 85 85 109
B 46.3/4 47.9/16 52.11/16 52.11/16 56.7/16 57.5/16 69.13/16 69.13/16 73.3/8 73.3/8 82.7/8 82.7/8 93.3/8
MODEL 500 600 750 900 1050 1300 1500 1800 2200 2600 3200 3600 4300
VIEW REF. I I II II II II II II II II III III III
C 1.1/4 1.1/4 1.1/4 1.1/4 1.1/4 1.1/4 1.1/4 1.1/4 1.1/4 1.1/4 1.1/4 1.1/4 1.1/4
E 59 60 68 68 62 73 79 79 86 89 107 116 123
D 23.3/8 23.13/16 26.5/8 26.5/8 29.9/16 30 34.7/8 34.7/8 38.9/16 38.9/16 36.9/16 36.9/16 41.13/16
F 45.1/2 45.1/2 53.1/2 53.1/2 53.1/2 53.1/2 53.1/2 53.1/2 59.1/2 59.1/2 59.1/2 59.1/2 63.1/2
G 22.3/4 22.3/4 26.3/4 26.3/4 26.3/4 26.3/4 26.3/4 26.3/4 29.3/4 29.3/4 29.3/4 29.3/4 31.3/4
DIMENSIONS IN MILLIMETERS
L 12.11/16 13.3/16 13.7/16 13.7/16 13.3/16 13.3/16 15.5/8 15.5/8 17.1/4 17.1/4 14.9/16 16.9/16 16.1/4
H 1.1/4 1.1/4 3.1/4 3.1/4 5.15/16 5.15/16 4.3/8 4.3/8 3/4 5 2
K 3 3 8 8 8 8 8 8 7.1/4 7.1/4 15.7/8 15.7/8 15.7/8
M 96.15/16 100.7/16 100.11/16 100.11/16 99.13/16 104.13/16 101.7/8 101.7/8 115.7/8 115.7/8 115.13/16 122.1/16 118.1/2
P 13.3/16 14.3/16 15.3/4 15.3/4 16.3/4 17.3/4 20.3/4 20.3/4 22.1/4 22.1/4 26.1/2 27.1/2 30.1/2
N 105 108 114 114 113 118 116 116 128 128 128 134 130
S 2 NPT 2 NPT 3 FLANGE 3 FLANGE 3 FLANGE 3 FLANGE 3 FLANGE 4 FLANGE 4 FLANGE 4 FLANGE 4 FLANGE 6 FLANGE 6 FLANGE
R 7/8 X 1.1/4 7/8 X 1.1/4 7/8 X 1.1/4 7/8 X 1.1/4 7/8 X 1.1/4 7/8 X 1.1/4 7/8 X 1.1/4 7/8 X 1.1/4 7/8 X 1.1/4 7/8 X 1.1/4 7/8 X 1.1/4 7/8 X 1.1/4 7/8 X 1.1/4
T 2 NPT 2 NPT 3 FLANGE 3 FLANGE 3 FLANGE 3 FLANGE 3 FLANGE 4 FLANGE 4 FLANGE 4 FLANGE 6 FLANGE 6 FLANGE 6 FLANGE
WT/LBS 1,900 2,200 2,500 2,600 3,000 3,600 5,400 5,500 8,100 8,200 9,400 9,900 12,350
MODEL 500 600 750 900 1050 1300 1500 1800 2200 2600 3200 3600 4300
F 1156 1156 1359 1359 1359 1359 1359 1359 1511 1511 1511 1511 1613
A 1346 1397 1524 1524 1626 1676 2032 2032 2159 2159 2159 2159 2769
B 1187 1208 1338 1338 1434 1456 1773 1773 1864 1864 2106 2106 2372
VIEW REF. I I II II II II II II II II III III III
E 1491 1531 1734 1734 1580 1862 2009 2009 2186 2256 2708 2955 3132
C 32 32 32 32 32 32 32 32 32 32 32 32 32
D 594 604 677 677 750 761 886 886 980 980 929 929 1062
G 578 578 679 679 679 679 679 679 756 756 756 756 806
L 322 335 341 341 335 335 397 397 438 438 370 421 413
H 32 32 83 83 151 151 111 111 19 127 51
K 76 76 203 203 203 203 203 203 184 184 403 403 403
M 2462 2551 2557 2557 2535 2662 2588 2588 2943 2943 2942 3100 3010
N 2664 2753 2903 2903 2870 2997 2946 2946 3246 3246 3246 3404 3313
P 335 360 400 400 425 451 527 527 565 565 673 699 775
S 2 NPT 2 NPT 3 FLANGE 3 FLANGE 3 FLANGE 3 FLANGE 3 FLANGE 4 FLANGE 4 FLANGE 4 FLANGE 4 FLANGE 6 FLANGE 6 FLANGE
R 22 X 32 22 X 32 22 X 32 22 X 32 22 X 32 22 X 32 22 X 32 22 X 32 22 X 32 22 X 32 22 X 32 22 X 32 22 X 32
T 2 NPT 2 NPT 3 FLANGE 3 FLANGE 3 FLANGE 3 FLANGE 3 FLANGE 4 FLANGE 4 FLANGE 4 FLANGE 6 FLANGE 6 FLANGE 6 FLANGE
WT/KGS 862 998 1,134 1,179 1,361 1,633 2,449 2,495 3,674 3,719 4,264 4,491 5,602
7

5.0 Instrumentation

The following instrumentation helps in monitoring dryer operation and performance. Instruments which are available as options are so noted.
Blower Purge Air dryers are rated NEMA 4 and include the following:
• Solid State Controls
• Chamber Pressure Gauges
• Purge Flow Pressure Gauge
• Energy Management (Option A)
• Energy Management System & Dew Point Transmitter (Option B)
5.1 Controls
The solid-st ate dr yer co ntro ls are locat ed in a polycarbonate, NEMA Class 4/4X, IP66 rated electrical enclosure mounted to a center panel located between the two desiccant towers. Control features include:
• 15 LED’s to indicate operating status and fault conditions.
5.5 Dew Point Transmitter
This option monitors and displays outlet pressure dew points and provides an alarm signal if the dew point exceeds user-specified set point. Recommen ded calibration interval is 12 months. Contact the service department for details.
Operation – The dew point is measured at the dryer operating pressure and is displayed in the operator interface. If the dew point is outside of the temperature range, the display will indicate an over-range (high dew point) or under-range (low dew point) condition. A defective sensor assembly or an electronics malfunction could also cause the transmitter to indicate under­range.
• Two line text display to provide status and diagnostic messages.
• Upon power loss, dryer “fails safe” (inlet valve remains in position). On power recovery, controller resumes where power was lost.
5.2 Chamber Pressure Gauges
A gauge mounted on the gauge panel indicates which chamber is on-stream and which is regenerating. The gauge for the onstream tower indicates operating pressure; the gauge for the regenerating tower indicates 0 psig.
5.3 Purge Flow Pressure Gauge
A gauge mounted on the gauge panel of the dryer indicates purge air pressure.
5.4 Energy Management System
Th e opt ional Energy Manag ement System (EMS) automatically adjusts dryer operation to compensate for changes in operating conditions. Air samples are continuou sly taken from the on-stream to wer and passed ov er a moisture probe which sense s both temperature and relative humidity. The moisture content of the air within the desiccant bed is then precisely determined. The on-stream tower will not depressurize and regenerate until a predetermined set point has been reached. This elimination of unnecessary regeneration reduce s energy cons ump tion and e xte nds d ryer desiccant and component life.
8
RS232
P1
P2
PURGE INLET CHECK VALVE
TOP VIEW
ASME RELIEF VALVE
OUTLET CHECK VALVE
DESICCANT
FILL PORT
LEFT TOWER
PRESSURE GAUGE
PRESSURE REGULATOR
& PILOT AIR FILTER
DEWPOINTER
(OPTIONAL)
TOWER PURG
E
EXHAUST VALVE
FRONT VIEW
TOWER DEPRESS VALV
E
DESICCANT DRAIN POR
T
TO
WER INSULATION (OPTIONAL
)
CONTRO
L
ENCLOSURE
HIGH TENSIO
N
ENCLOSURE
RIGHT TOWER PRESSURE GA
UGE
PURGE PRESSURE GAUGE
REPRESS VALV
E
HEATER TEMP
THERMOCOUPLE
(CENTER END IN PIPE)
(OPPOSITE SIDE)
HEATER OVERTEMP RTD
PURGE
HEATER WITH
INSULATION
PURGE SUCTION FILTER SILENCER
PURGE BLOWER
AND MOTOR
REAR VIEW
TOWER INLET VALV
E
ASME CODE TAG
HOT PIPE INSULATION
P1P
2
P3
P4
TOWER BLOW­DOWN VALVE
General Layout Drawing
Figure 3
(Models 500 through 600)
9
LEFT TOWER PURGE
EXHAUST VALVE
DEWPOINTE
R
(OPTIONAL)
PRESSURE REGULATOR
& PILOT AIR FILTER
LEFT TOWER
PRESSURE GAUGE
DESICCANT
FILL PORT
LEFT OUTLET
CHECK VALV
E
PURG
E
PRESSURE GAUGE
RIGHT TOWER PRESSURE GAUGE
CONTROL ENCLOSURE
HIGH TENSION ENCLOSUR
E
TOWER INSULATION (OPTIONAL)
DESICCANT DRAIN PORT
RIGHT TOWE
R
DEPRESS VALV
E
ASME RELIEF VALV
E
REPRESS VALV
E
TOP VIEW
FRONT VIEW
PURGE
HEATER WITH
INSULATIO
N
PURGE SUCTION FILTER SILENCER
PURGE BLOWER
AND MOTO
R
REAR VIEW
LEFT TOWER INLET VALV
E
ASME CO
DE TAG
LEFT PURGE INLE
T
CHECK VALV
E
HOT PIPE INSULATION
AIR
OUTLET
AIR
INLET
LEFT TOWER
DEPRESS VALV
E
RIGHT TOWER PURGE EXHAUST VALV
E
RIGHT OUTLET CHECK VALV
E
AIR
OUTLET
AIR
INLET
LEFT TOWER
PURGE EXHAUST
VALV
E
PURGE EXHAUST
RIGHT TOWE
R PURGE EXHAUST VALV
E
PURGE EXHAUST
TOWER BLOW
-
DOWN VALV
E
HEATER TEMP
THERMOCOUPLE
(CENTER END IN PIPE)
(OPPOSITE SIDE)
HEATER OVERTEMP RT
D
10
General Layout Drawing
(Models 750 through 2600)
Figure 3a
TOP VIEW
OUTLET CHECK VALV
E
ASME RELIEF VALV
E
DESICCANT
FILL PORT
LEFT TOWER
PRESSURE GAUGE
PRESSURE REGULATOR
& PILOT AIR FILTER
DEWPOINTE
R
(OPTIONAL)
TOWER PURGE
EXHAUST VALV
E
FRONT VIEW
TOWER DEPRESS VALVE
DESICCANT DRAIN PORT
TOWER INSULATION (OPTIONAL)
HIGH TENSION ENCLOSUR
E
CONTROL ENCLOSUR
E
RIGHT TOWER PRESSURE GAUGE
PURGE PRESSUR
E
GAUGE
REPRESS VALV
E
PURGE BLOWER
AND MOTO
R
PURGE BLOWER
THROTTLING VALV
E
PURGE SUCTION FILTER SILENCER
PURGE HEATER
WITH INSULATION
HEATER
OVERTEMP RT
D
HOT PIPE INSULATIO
N
PURGE INLET CHECK VALV
E
TOWE
R
INLET VALV
E
REAR VIEW
HEATER TEMP
THERMOCOUPLE
(CENTER END IN PIPE
)
(OPPOSITE SIDE
)
CHAMBER
BLOW-DOWN
VALV
E
Figure 3b
General Layout Drawing
(Models 3200 through 4300)
11

6.0 Operation

6.1 Controls
A solid-state controller controls valve and heater opera­tion, monitors all critical operating conditions, and indi­cates operating status on a 2-line LCD display operator interface. The controller receives input data from pres­sure switches, temperature sensors and the operator interface. The operator interface displays information about the dryer operating status and is used to change the dryer operating mode.
6.2 Operating Modes
6.2.1 Automatic and Manual Advance
The drying and regeneration cycles are divided into discrete steps. The operator selects either one of the automatic advance modes (Energy Management, Dew Point Control, or Fixed Cycle) or manual advance mode (Test Cycle) through the operator interface.
Selecting any of the automatic advance modes enables a timer in the controller to advance the program step-by­step according to the programmed schedule.
Setting up the controller for manual advance disables the timer and the operator can advance the program one step at a time. This mode is used for diagnostic purposes.
6.2.2 Fixed, Energy Management or Dew Point Control Operation
The operator interface is used to select either Fixed, Energy Management or Dew Point Control operation. In Fixed Cycle operation, each tower is on-line (drying) for a fixed time period regardless of the operating conditions. In Energy Management or Dew Point Control operation, a tower remains on-line until the desiccant bed has been fully utilized. For lower than designed moisture loads, this results in longer drying cycles, longer time between regenerations and, therefore lower energy consumption. Energy Management or Dew Point Control operation are optional features.
6.3 Operating Sequence Description
1. Left Tower Drying – Right Tower Regenerating
At the start of the Left Tower Drying cycle, Left Inlet
Valve V1 opens, Right Inlet Valve V2 closes to iso­late the two towers. Wet, compressed air flows up through the left tower where it is dried. The dry air exits the dryer through the Left Outlet Check Valve V7.
Next, the Right Depressurization Valve V10 is
opened and the right tower is slowly depressurized. Air exits through exhaust muffler M2.
After the right tower has depressurized, the Right
Purge Valve V4 is opened and the Blower M and Heater H1 are energized. The heated air flows through the Right Purge Check Valve V6, down through the right tower, and exits through the Right Purge Valve V4. The Blower intake air is filtered to keep dust and dirt from entering the dryer. The Blower M and Heater H1 are de-energized when the temperature at the bottom of the right tower, as sensed by the Right Tower Temperature Sensor RTD2, reaches the Heat Termination set point. This indicates that the bed has been fully heated.
Note: Blower will continue to run briefly at the end
of the Heating Step to sweep residual heat from the heater.
The Repressurization Valve V11 is opened. A portion
of the dry air from the left tower now flows through Repressurization Valve V11. This air is throttled to near atmospheric pressure by Repressurization/ Sweep Orifice O2. The dry, low pressure air flows down through the right tower cooling the desiccant bed, and exits through the Right Tower Purge Ex­haust Valve V4.
The Cooling Step continues until:
a) the right tower bed temperature falls to 150°F
or,
b) it is time to repressurize the right tower,
whichever occurs first.
Note: In fixed cycle, the bed will normally be partially
cooled because the repressurization step will occur before the bed temperature can fall to 150°F.
Note: In Energy Management or Dew Point Control,
as the drying time extends beyond 4 hours, additional cooling time becomes available thus the cooling step will frequently terminate based on temperature providing complete bed cooling.
At the end of the Cooling Step, the Right Tower Purge
Exhaust Valve V4 is closed. The right tower slowly repressurizes to full line pressure and is ready to go back on-line.
Note: Bed cooling can be disabled by moving JP4
to the “ON” position.
2. Right Tower Drying – Left Tower Regenerating At the start of the Right Tower Drying cycle, Right
Inlet Valve V2 opens, Left Inlet Valve V1 closes to isolate the two towers. Wet, compressed air flows up through the right tower where it is dried. The dry air exits the dryer through the Right Outlet Check Valve V8.
Next, the Left Depressurization Valve V9 is opened
and the left tower is slowly depressurized. Air exits through exhaust muffler M1.
12
WET GAS INLET
DRY GA
S
OUTLET
SOL 'D'
V1
SOL 'F'
M1
V9
RTD
1
V3
V4
V2
SOL 'B
'
M2
SOL 'A
'
SOL 'G'
V1
0
RTD
2
V6
1PS
(RTD4/HS1)
ENERGY MGMT OPTION
SET @ 176°F
DRYING
EXH.
3PS
SET
@
5 PSIG
SOL 'C'
2
1
3
LEFT
TOWER
SET
@
45 PSI
G
M
RTD
3
SET @ 650°F
1T
C
SET @ 370°F
V5
2P
S
SET @ 176°F
4P
S
SET
@
5 PSI
G
REGE
N
SET
@
45 PSIG
SET AT 100 PSIG
RIGH
T
TOWE
R
V8
V12 V13
SOL 'E'
V7 V11
RV
1
SET @ 165 PSI
G
DEWPOINTER OPTION
DP
A
SOLENOID VA
LVES 'B', 'D', & 'G' ARE SHOWN ENERGIZED,
SYMBOLS ARE PER ANSI Y32.10 "GRAPHIC SYMBOLS FOR FLUID POWER DIAGRAMS."
SOLENOID VA
LVES 'A', 'C', 'E', & 'F' ARE SHOWN DE-ENERGIZED.
AS SHOWN FLOW DIRECTION IS:
INDICATES OPTION
3.
2.
1.
PILOT GAS LINE
RIGHT CHAMBER REGEN
LEFT CHAMBER DRYING
NOTES
4.
BD2BD1
H1
PI3
PI1
PI2
F1
PR&G
F2
O2
V1
4
O1
Figure 4
Sequence of Operation — Fixed Cycle Operation
Left Chamber Drying – Right Chamber Regenerating (shown)
(continued on next page)
13
After the left tower has depressurized, the Left Purge
P
EM
S
LEFT
TOWER
RIGHT
TOWER
Valve V3 is opened and the Blower M and Heater H1 are energized. The heated air flows through the
Left Purge Check Valve V5, down through the left tower, and exits through the Left Purge Valve V3. The Blower intake air is filtered to keep dust and dirt from entering the dryer. The Blower M and Heater H1 are de-energized when the temperature at the bottom of the left tower, as sensed by the Left Tower Temperature Sensor RTD1, reaches the Heat Ter­mination set point. This indicates that the bed has been fully heated.
The Repressurization Valve V11 is opened. A portion
of the dry air from the right tower now flows through Repressurization Valve V11. This air is throttled to near atmospheric pressure by Repressurization/ Sweep Orifice O1. The dry, low pressure air flows down through the left tower cooling the desiccant bed, and exits through the Left Tower Purge Exhaust Valve V3.
The Cooling Step continues until:
a) the left tower bed temperature falls to 150°F
or,
b) it is time to repressurize the left tower,
whichever occurs first.
6.3.1 Energy Management Control (optional)
Operation of the Energy Management Control cycle is identical to the fixed cycle except the cycle is extended until the desiccant bed in the on-line tower has been fully utilized. The off-line tower is regenerated and remains in a stand-by mode after being repressurized.
Figure 5 shows the air sampling system for the Energy Management System – EMS option. A 3-way pilot valve directs an air sample from the drying tower to the EMS sensor. The EMS sensor detects the relative humidity and temperature of the air sample. The air sample then exhausts to atmosphere. The drying tower remains on­line until the moisture front arrives at the sensor.
Note: In fixed cycle, the bed will normally be partially
cooled because the repressurization step will occur before the bed temperature can fall to 150°F.
Note: In Energy Management or Dew Point Control,
as the drying time extends beyond 4 hours, additional cooling time becomes available thus the cooling step will frequently terminate based on temperature providing complete bed cooling.
At the end of the Cooling Step, the Left Tower Purge
Exhaust Valve V3 is closed. The left tower slowly repressurizes to full line pressure and is ready to go back on-line.
Note: Bed cooling can be disabled by moving JP4
to the “ON” position.
Figure 5
Optional Moisture Sensing
Energy Management System (EMS)
14
6.4 Control Board Jumpers
In the upper left hand corner of the control board there are eight two-pin jumpers labeled JP1 through JP8. Only five of the eight jumper pairs are utilized. Pairs JP6-JP8 are used for factory settings and testing. NOTE: Do
not install jumpers in the ON position on pairs JP6 through JP8. The jumper is a removable bridge that is
used to make or break continuity between two pins that form a pair. When installed in the ON position, the jumper is place on both pins of the pair and continuity between the pins is established. When installed in the OFF posi­tion, the jumper is removed or stored on a single pin and continuity is broken. Jumper functions are as follows:
1. JP1 – Dryer Type Jumper JP1 is used to select the dryer type configu-
ration. It is installed in the ON position for Blower Purge dryer configuration.
2. JP2 – Energy Management Jumper JP2 is installed in the ON position when an
Energy Management sensor is installed. The jumper is installed in the OFF position when no Energy Management sensor is installed.
3. JP3 – Dew Point Transmitter Jumper JP3 is installed in the ON position when a
Dew Point Transmitter is installed. The jumper is installed in the OFF position when no Dew Point Transmitter is installed.
NOTE: “Energy Management” can co-exist with the
dew point transmitter option. Dryer control based on the ENERGY MANAGEMENT or DEWPOINT CONTROL is selected on Screen 1 of the Set Up Mode.
If DEWPOINT CONTROL is not selected then the
dew point signal does not control the dryer cycle but still serves a monitoring and alarm function.
8. JP8 – Set Up Jumper JP8 is factory installed in the OFF position
to disable access to “factory” set up screens. The jumper is installed in the ON position during final inspection at the factory to set controller to match customer requirements.
6.5 Operator Interface
Refer to Figure 6 , Front Panel Overlay for information regarding the location and function of the LEDs, switches, and text display.
6.5.1 Front Panel LED’s
• Power On - green
• Alarm - red
• Service / Maintenance reminder - amber
• Filters (pre, after, and pilot) service / maintenance reminders - amber
• Inlet switching and purge / repressurization valve sta­tus (On = valve open; Off = valve closed) - green
• Left and right tower status (heating) - amber
• Left and right tower status (drying) - green
• Left and right tower pressure switch status (On = switch closed; Off = switch open) - green
6.5.2 Front Panel Switches
The front panel contains four momentary-contact push­button switches. Refer to Figure 6, Front Panel Overlay for the appropriate icon associated with each switch. Pushing on the overlay icon actuates the switch.
Data Display Switch
Th is switch is used to step th rough the display screens.
Select Switch
This button is located to the left of the text display window. Refer to the Front Panel Operation Section for additional information.
4. JP4 – Cooling Cycle Jumper JP4 is installed in the ON position to disable
the Cooling Cycle. The jumper is installed in the OFF position to enable a Cooling Cycle.
5. JP5 – Switching Failure Jumper JP5 is installed in the ON position to enable
Switching Failure. The jumper is installed in the OFF position if Switching Failure is disabled.
6. JP6 – Not Used
NOTE: Jumpers JP7 and JP8 are used by the factory during final inspection to download language text and to enable ‘factory’ set-up screens.
7. JP7 – Download Language Text Jumper JP7 is factory installed in the OFF position
to disable Language Text download. The jumper is installed in the ON position to allow for language text download due to either language corrections or new language installation.
ENTER Switch
This button is located to the right of the text display window. Refer to the Front Panel Operation Section for additional information.
Alarm Reset Switch
This button is normally used to reset an alarm or service reminder. Refer to the Front Panel Operation Section for additional information.
15
Left Tower Drying LED
Left Purge Valve LED On=valve open Off=valve closed
Left Inlet Valve LED On=valve open Off=valve closed
Left Tower Heating LED
Filter Service / Maintenance LED
Vacuum Fluorescent Text Display
Select switch
Power On LED
Data Display Switch
Communications Icon
Filter Service / Maintenance LED
Filter Service / Maintenance LED
Right Tower Pressure Switch LED: On=Tower pressurized
Right Tower Drying LED
Right Purge Valve LED On=valve open Off=valve closed
Right Tower Heating LED
Right Inlet Valve LED On=valve open Off=valve closed
Enter Switch
Maintenance / Service Reminder LED
Alarm LED
Reset Switch for Alarm
Left Tower Pressure Switch LED: On=Tower Pressurized
RS232
6.5.3 Front Panel Operation
1. There are five operating modes for the Heated Desiccant Dryer Control. a. Program Mode b. Setup Mode c. Alarm & Service Mode d. Display Mode e. Test Mode
2. Each Mode is described below.
6.5.4 Program Mode
1. Press and hold and for 3 seconds to enter Program Mode.
2. Program Mode is comprised of the screens that are described below.
3. There are three (3) ways to exit Program Mode.
a. Press after making the selection in the final
b. At any screen, press and hold for 3 sec-
c. The controller automatically exits Program Mode
16
screen.
onds.
if no button is pressed within 60 seconds.
Figure 6
Front Panel Overlay
4. Upon exiting Program Mode the controller will switch
Screen 1: Select the Language
1. Press to scroll through the choices: ENGLISH,
2. When finished, press to save the selection and
Screen 2: Select the Service Level
1. Pr ess to toggle bet w een N ORMA L and
to Display Mode.
ENGLISH
FRANCAIS and ESPANOL.
move to next screen.
SERVICE LEVEL NORMAL
SEVERE. a. NORMAL Service Intervals are:
i. 4000 hours for filters ii. 8000 hours for desiccant iii. 8000 hours for valves
b. SEVERE Service Intervals are:
i. 2000 hours for filters ii. 4000 hours for desiccant iii. 4000 hours for valves
2. When finished, press to save the selection and
move to next screen.
Screen 3: Reset the Timer for Filter Service
FILTER SERVICE RESET? NO
1. Press to toggle between NO and YES.
2. When finished, press to acknowledge the
selection and move to next screen.
Screen 4: Reset the Timer for Desiccant Service
DESICCANT SERVICE RESET? NO
1. Press to toggle between NO and YES.
2. When finished, press to acknowledge the
selection and move to next screen.
Screen 5: Reset the Timer for Valve Service
VALVE SERVICE RESET? NO
Screen 7: Set Point for Dew Point Demand Control
(Displayed only when JP3 “on”)
DPNT CNTL SETPT ±XX°C ±XXX°F
1. Press to increment the setting to the desired value. a. Standard set point is
-30°C -22°F
.
b. The allowable range of values is from
-80°C -112°F
+10°C +50°F
to
in 5°C/9°F
increments.
Note: Must be set “drier” than Dew Point Sensor
Alarm Set Point (screen 6).
2. When finished, press to acknowledge the selection and exit the Program Mode.
Screen 8: Set the Heat Termination Set Point
HEAT TERM SET-PT XX°C XXX°F
1. Press to increment the setting to the desired temperature value. a. Refer to P&ID diagrams in the back of this manual
for Heat Termination set points (see set point values for RTD1 and RTD2).
b. The allowable range of values are:
60° - 160°C 140° - 320°F
in 10°C increments.
1. Press to toggle between NO and YES.
2. When finished, press to acknowledge the selec­tion and move to next screen.
Screen 6: Set Alarm Point for the Dew Point
Sensor (Displayed only when JP3 “on”)
DEWPOINT ALARM ±XX°C ±XXX°F XX MIN SW DELAY
1. Press to increment the setting to the desired value. a. Standard set point is
-20°C -4°F
.
b. Th e a l l o w a b l e r a n g e o f v a l u e s i s f r o m
-80°C -112°F
+10°C +50°F
to
in 5°C/9°F
increments.
2. When finished, press to acknowledge the se­lection and scroll to the switchover delay set point screen. a. Standard set point is b. The allowable range of values are
60 MIN
.
30 to 120 MIN
in 10 minute increments.
3. When finished, press to acknowledge the selec­tion and move to next screen. Exit Program Mode when there are no more active screens to display.
2. When finished, press to acknowledge the selec­tion and move to next screen. Exit Program Mode when there are no more active screens to display.
Screen 9: Set Points for Energy Management (Displayed only when JP8 “on”)
ENRGY MGMT SETPT XX%RH XX MBAR .XXX PSI
1. Press to increment the setting to the desired maximum RH value. a. Factory set point is
60%RH
. The factory setting
should not require adjustment.
b. The allowable range of values are
20 to 80%RH
in 5% increments.
2. When finished, press to acknowledge the selec­tion and scroll to the pressure set point screen.
3. Press to increment the setting to the desired maximum vapor pressure value.
a. Standard set point for a -40°F dew point dryer
16 MBAR (0.232 PSI)
.
is
Note: Standard set point for a -100°F dew point
dryer
b. The allowable range of values
3 to 34 MBAR (0.044 to 0.493 PSI)
4 MBAR (0.058 PSI)
is
.
in
is
1 MBAR
increments.
17
c. This setting may be field adjusted to increase or
decrease the outlet dew point at tower switch­over.
4. When finished, press to acknowledge the selec­tion and move to next screen.
Screen 10: Set Points for High Humidity Alarm (Displayed only when JP8 “on”)
HIGH HUMIDITY XX%RH XX MBAR .XXX PSI XX MIN SW DELAY
1
. Press to increment the setting to the desired
maximum RH value. a. Factory set point is
75%RH
. The factory setting
should not require adjustment.
b. The allowable range of values are
20 TO 80%RH
in 5% increments.
Note: Value must be set above Energy Manage-
ment Maximum RH Value Set Point (screen 9).
6.5.5 Setup Mode
1. Press and hold for 3 seconds to enter Setup Mode.
2. Setup Mode is comprised of the screens that are described below.
3. There are two ways to exit Setup Mode.
a.
Press after making the selection in Screen 1.
b. The controller automatically exits Setup Mode if
no button is pressed with 60 seconds.
4. One of two things will happen upon exiting Setup Mode. a. The controller will switch to Display Mode if
ENERGY MANAGEMNT, FIXED CYCLE or DEWPOINT CONTROL is selected.
b. The controller will switch to Test Mode if TEST
CYCLE is selected.
Screen 1: Select the Cycle Type
CYCLE TYPE ENERGY MANAGEMNT
2. When finished, press to acknowledge the selec­tion and scroll to the pressure set point screen.
3. Press to increment the setting to the desired maximum vapor pressure value.
a. Factory set point for a -40°F dew point dryer is
24 MBAR (0.348 PSI)
.
Note: Factory set point for a -100°F dew point
dryer is
5 MBAR (0.073 PSI)
.
b. The allowable range of values is
3 to 34 MBAR (0.044 to 0.493 PSI)
in 1 MBAR incre-
ments.
Note: Value must be set above Energy Man-
agement Maximum Vapor Pressure Set Point (screen 9).
4. When finished, press to acknowledge the se­lection and scroll to the switchover delay set point screen. a. Factory set point is b. The allowable range of values are
60 MIN.
.
30 to 120 MIN
in 10 minute increments.
5. When finished, press to acknowledge the selec­tion and move to next screen. Exit Program Mode when there are no more active screens to display.
1. Press to scroll through the choices: a. ENERGY MANAGEMNT (displayed only when
JP2 is in the ON position)
b. DEWPOINT CONTROL (displayed only when JP3
is in the ON position) c. FIXED CYCLE d. MANUAL CYCLE
2. When finished, press to save the selection and exit the Setup Mode.
18
6.5.6 Alarm & Service Mode
1. Alarm & Service Mode is active when the controller is in Display Mode. It is not active in Program Mode, Setup Mode, or Test Mode.
2. Local alarm consists of a blinking alarm LED and an alarm message display.
3. Alarm messages have prior ity over Se rvice messages. Service messages have priority over Display Messages.
4. After an alarm condition has been corrected, if: a. Alarm is “self-clearing” then,
i. The alarm LED stops blinking (LED on); the
alarm message continues to be displayed.
ii. The alarm reset button must be depressed to
clear the alarm LED (LED off) and the alarm message.
b. Alarm must be manually reset, then:
i. The alarm LED continues to blink and the
alarm message continues to be displayed.
ii. The alarm reset button must be depressed
to:
1. Clear the alarm LED (LED off)
2. Clear the alarm message and
3. Restart the dryer cycle.
5. When an alarm condition has not been corrected and the “alarm reset” button is pressed, the alarm will not clear except as follows: a. The alarm conditions will clear for 5 seconds,
then reappear if the alarm condition persists, this applies to the following alarms: i. Heater: High Inlet Temperature. ii. Heater: Low Temperature iii. Humidity Sensor: High Humidity Alarm iv. Humidity Sensor: Under-Range or Over-
Range Alarm v. Dew Point Sensor: High Dew Point Alarm vi. Dew Point Sensor: Under-Range or Over-
Range Alarm
6. There are three alarms for each tower that are triggered by the tower pressure switches. These alarms can occur in any operating mode (Manual, Fixed, Energy Management, or Dew Point Demand Cycle).
Following is a brief description of each alarm.
a. Left or Right tower, drying, low pressure
i. Drying tower pressure switch is open during
the drying cycle.
b. Left or Right tower, regenerating, high pressure
i. Regenerating tower pressure switch is closed
while purge valve is open (after an initial time delay).
c. Left or Right tower, regenerating, low pressure
i. Regenerating tower pressure switch is open
at the end of the regenerating cycle.
d. On alarm condition, the blower and heater are
de-energize, the cycle sequence is stopped, a local alarm is displayed and the common alarm relay is de-energized.
e. These alarms are self-clearing.
7. Heater High Inlet Temperature a. Model sizes 3200, 3600 and 4300 are equipped
with a temperature switch located in the piping between the blower and heater.
b. If during the Heat Cycle this temperature switch
opens, indicating a rise in temperature above the factory setting (refer to Electrical Schematic drawings at the back of this manual for set point), an alarm is activated.
c. On alarm condition, the blower and heater are
de-energized, the cycle sequence is stopped, a local alarm is displayed and the common alarm relay is de-energized.
d. This alarm must be manually reset.
8. The dryer is equipped with RTD temperature sensors. There are out of range alarms for each.
a. The standard left tower, right tower, and heater
RTDs (RTD1, RTD2, RTD3) are scaled from
-20°F(-28°C) to 890°F (477°C), “Out of Range” conditions are as follows: i. Over-range - temperature abov e 850°F
(454°C)
ii. Under-range - temperature below -20°F
(-28°C)
iii. Note: The controller will annunciate a “Heater
Overtemperature” alarm in lieu of an “Over Range” alarm when the heater sensor is disconnected.
b. The Energy Management RTD4 is scaled from
-20°F(-28°C) to 429°F(220°C), “Out of Range” conditions are as follows:
i. Over-range - temperatures above 400°F
(204°C)
ii. Under-range - temperatures below -20°F (-
28°C)
c. On alarm condition, a local alarm is displayed and
the common alarm relay is de-energized.
d. Over-range and Under-range alarms are self-
clearing.
19
ALARM MESSAGES
LEFT TOWER ALARMS RIGHT TOWER ALARMS OTHER ALARMS
ALARM LEFT TOWER DRYING LOW PRESSURE
ALARM LEFT TOWER REGENERATING HIGH PRESSURE
ALARM LEFT TOWER REGENERATING LOW PRESSURE
ALARM LEFT TOWER TEMP UNDER-RANGE
ALARM LEFT TOWER TEMP OVER-RANGE
ALARM LEFT TOWER OUTLET DEW POINT
ALARM RIGHT TWR DRYING LOW PRESSURE
ALARM RIGHT TWR REGENERATING HIGH PRESSURE
ALARM RIGHT TWR REGENERATING LOW PRESSURE
ALARM RIGHT TWR TEMP UNDER-RANGE
ALARM RIGHT TWR TEMP OVER-RANGE
ALARM RIGHT TWR OUTLET DEW POINT
ALARM HEATER OVER-TEMPERATURE
ALARM HEATER LOW TEMPERATURE
ALARM ENRGY MGNT UNDER-RANGE
ALARM ENRGY MGNT OVER-RANGE
ALARM BLOWER MOTOR OVERLOAD
ALARM HEATER HIGH TEMP IN
ALARM LEFT TOWER HIGH HUMIDITY
ALARM LEFT TOWER DEW POINT UNDER-RANGE
ALARM LEFT TOWER DEW POINT OVER-RANGE
ALARM RIGHT TWR HIGH HUMIDITY
ALARM RIGHT TWR DEW POINT UNDER-RANGE
ALARM RIGHT TWR DEW POINT OVER-RANGE
20
9. Heat Low Temperature a. RTD3 is used to detect Heater Low Tempera-
ture.
b. Alarm if the heater temperature is less than 250°F
(121°C) within 15 minutes after the Heat Cycle is initiated (15 minute delay also applies after power recovery).
c. On alarm condition, display local alarm and de-
energize common alarm relay.
d. This alarm is self-clearing.
10. Heater Over-Temperature a. RTD3 is used to detect Heater Over-Tempera-
ture.
b. Alarms anytime that the Heater temperature
exceeds 650°F (343°C).
c. On alarm condition, de-energize heat cycle, stop
cycle sequence, display local alarm and de-ener­gize common alarm relay.
d. This alarm must be manually reset.
11. Blower Overload a. Alarm condition when blower overload contact
closes.
13. Dew Point Sensor a. High Dewpoint Alarm
i. The user enters an alarm value through the
Program Mode.
ii. If the measured dew point exceeds the alarm
value, the outlet dew point alarm is indicat­ed.
b. Under-range alarm - Dew point below -148°F
(-100°C)
c. Over-range alarm - Dew point greater than
+109°F (+43°C)
d. On alarm condition,
i. Local alarm is displayed and the common
alarm relay is de-energized.
ii. If dryer is set up for Dewpoint Control, the dryer
sequence continues, but bypasses the “HOLD” step and proceeds to tower switchover after 4 hours of drying.
iii. This alarm is self-clearing, at which time the
alarm LED stops blinking and control switches back to Dewpoint Control.
b. On alarm condition, de-energize heat cycle, stop
cycle sequence, display local alarm and de-ener­gize common alarm relay.
c. This alarm must be manually reset.
Alarms for Optional Devices
12. Energy Management ­a. High Humidity Alarm:
i. Measured moisture level exceeds the air alarm
value entered through the Program Mode.
b. Humidity Sensor:
i. Under-range: RH% < -15% ii. Over-range: RH% > 115%
c. RTD:
i. Over-range: Temperature above 448°F
(231°C) ii. Under-range: Temperature below -20°F (-28°C)
d. On alarm condition:
i. Local alarm is displayed and the common
alarm relay is de-energized. ii. If the dryer is set up for Energy Management
Control, the dryer sequence continues, but
bypasses the “HOLD” step and proceeds to
tower switchover after 4 hours of drying. iii. This alarm is self-clearing, at which time the
alarm LED stops blinking and control switches
back to Energy Management control.
21
Service Due Messages
14. There are two service levels (normal and severe) as described in Program Mode. Each service level has preset time intervals for servicing the filters, desiccant, and valves. Time continues to accumulate as long as power is supplied to the controller, whether the controller is switched on or off.
When a service time interval expires (see also 14.d
below), the controller operates as follows.
a. The service LED blinks and the appropriate
service message is shown on the text display.
i. When the service interval for filters has expired
(see also d below), the three filter LED’s also blink.
b. The dryer continues to cycle normally. The LED’s
for the valve’s, pressure switches, and desiccant towers are not used for service indication.
c. Press the Reset button to extinguish the service
LED and to clear the service message from the text display.
d. If the dryer has 1 or 2 filter monitors, the timer
for filter service is disabled. When the filter monitor(s) send an alarm signal (change filter) to the controller, the controller displays the same LED’s and messages it would if the timer for filter service had expired.
6.5.7 Display Mode
1. Display Mode is active when the user exits Program Mode or Setup Mode and no alarms are active (unless MANUAL CYCLE was selected in Setup Mode).
2. Display Mode is comprised of dryer status screens and dryer display screens (described below). The controller automatically alternates the display between the Status Screens and selected Display Screens.
3. The user can override the automatic screen scroll by pressing to step through each of the Display Screens shown on the next page. Automatic scrolling will resume when is pressed or if not depressed for 60 seconds.
4. The Ene rgy Sa vings and Service Reminders Display Screens (Filters, Desiccant, and Valves) are alternated in sequence with the current dryer status screen.
15. Examples of the text display are shown on page 18 and below for each alarm and service reminder. The second line of the alarm screens contains up to three messages which are scrolled through, displaying each one for 2 seconds.
SERVICE DUE MESSAGES
SERVICE DRYER FILTERS
SERVICE DRYER DESICCANT
SERVICE DRYER VALVES
22
DRYER STATUS SCREENS
LEFT TOWER DRYING
LT DRYING RT DEPRESSURIZE
LT DRYING RT HEATING
LT DRYING RT COOLING
LT DRYING RT REPRESSURIZE
LT DRYING RT HOLDING
(Not displayed in FIXED Cycle)
TOWER SWITCHOVER TOWER SWITCHOVER
RIGHT TOWER DRYING
LT DEPRESSURIZE RT DRYING
LT HEATING RT DRYING
LT COOLING RT DRYING
LT REPRESSURIZE RT DRYING
LT HOLDING RT DRYING
(Not displayed in FIXED Cycle)
Energy Savings
(Not displayed in FIXED Cycle)
ENERGY SAVINGS XX%
Note: Energy Savings will appear after seven days of continuous use.
Service reminder (filters)
HOURS TO SERVICE FILTERS: XXXX
Service reminder (desiccant)
HOURS TO SERVICE DESICCANT: XXXX
Service reminder (valves)
HOURS TO SERVICE VALVES: XXXX
DRYER DISPLAY SCREENS
Outlet Dew Point
(Displayed only if JP3 is ON)
DEW POINT ±XX°C ±XXX°F
Left Tower Temperature
LT TEMP ±XX°C ±XXX°F
Right Tower Temperature
RT TEMP ±XX°C ±XXX°F
Heater Temperature
HEATER TEMP ±XX°C ±XXX°F
Dewpoint Demand SetPoint
(Displayed only if JP3 is ON)
DWPT CNTL SETPT ±XX°C ±XXX°F
Energy Mgmt Signal
(Displayed only if JP2 is ON)
ENERGY MGMT SGNL XX%RH XXX°F XX°C XX MBAR X.XX PSI
Energy Mgmt Setpoint
(Displayed only if JP2 is ON)
ENERGY MGMT SET XX MBAR X.XX PSI
(This is the calculated “hold” set-point, which is based on the sample air tem­perature.)
23
6.5.8 Test Mode
1. Test Mode is active when the user exits Program
5. Upon entering Test Mode, the program can be at any one of the ten steps.
Mode after selecting operation in MANUAL CY­CLE.
6. To exit Test Mode: a. Press and hold for 3 seconds to exit Test
2. Test Mode is comprised of ten (10) screens (screen descriptions follow the table below on the next page). Each screen corresponds to one of ten program steps (described in the table below).
3. Press to advance from one screen (test step) to the next.
Mode. The display switches to Screen 2 of Setup Mode.
b. Use to select ENERGY MANAGEMENT,
DEWPOINT CONTROL or FIXED CYCLE.
c. Press and hold for 3 seconds to exit Setup
Mode and activate Display Mode.
d. Dryer operation continues from the last step active
IMPORTANT: Be sure to read and understand all
when exiting the Test Mode.
cautions listed with the screen (program step) de­scriptions.
4. If the temperature is out of range, the second line of the display will read “OVER-RANGE” or “UNDER­RANGE” instead of the temperature reading. (Refer to screens 2, 3, 4, 6, 7, and 8.)
Program Step 1 2 3 4 5 6 7 8 9 10
LT status Drying Drying Drying Drying Drying Off Depress Heat Cool Repress
RT status Off Depress Heat Cool Repress Drying Drying Drying Drying Drying
1PS Closed Closed Closed Closed Closed Closed
2PS Closed
3PS Closed Closed Closed Closed Closed Closed
4PS Closed
LT drying solenoid (B) On On On On On Off Off Off Off Off
LT depress solenoid (F) Off Off Off Off Off Off On On On Off
LT purge solenoid (C) Off Off Off Off Off Off Off On On Off
RT drying solenoid (A) Off Off Off Off Off On On On On On
RT depress solenoid (G) Off On On On Off Off Off Off Off Off
RT purge solenoid (D) Off Off On On Off Off Off Off Off Off
LT inlet valve (V1) Open Open Open Open Open Closed Closed Closed Closed Closed
LT depress valve (V9) Closed Closed Closed Closed Closed Closed Open Open Open Closed
LT purge valve (V3) Closed Closed Closed Closed Closed Closed Closed Open Open Closed
RT inlet valve (V2) Closed Closed Closed Closed Closed Open Open Open Open Open
RT depress valve (V10) Closed Open Open Open Closed Closed Closed Closed Closed Closed
RT purge valve (V4) Closed Open Open Open Closed Closed Closed Closed Closed Closed
Repress valve (V11) Open Closed Closed Open Open Open Closed Closed Open Open
Temp display - location Left Right Right Right Right Right Left Left Left Left
Closed
then Open
Closed
then Open
Open Open
Open Open
Open then
Closed
Open then
Closed
Closed Closed Closed Closed Closed
Closed Closed Closed Closed Closed
Closed
then Open
Closed
then Open
Open Open
Open Open
Open then
Closed
Open then
Closed
24
Table 2
Cycle Sequence Steps
TEST MODE SCREENS
Screen 1: Step 1
TEST1: LT DRYING LT: XX°C XXX°F
Screen 2: Step 2
TEST2: DEPR RT RT: XX°C XXX°F
Note: Sequence step will not advance to HEAT
until depressurization time has elapsed and tower has fully depressurized. Exception: If switching failure is disabled then pressure condition is ignored.
Screen 3: Step 3
TEST3: HEAT RT RT: XX°C XXX°F
To prevent bed over-heating in test mode: If the RT temperature > heat termination set point, then Screen 3 will display for a maximum of 1 minute before automatically advancing to next step.
Screen 6: Step 6
TEST6: RT DRYING RT: XX°C XXX°F
Screen 7: Step 7
TEST7: DEPR LT LT: XX°C XXX°F
Note: Sequence step will not advance to HEAT
until depressurization time has elapsed and tower has fully depressurized. Exception: If switching failure is disabled then pressure condition is ignored.
Screen 8: Step 8
TEST8: HEAT LT LT: XX°C XXX°F
To prevent bed over-heating in test mode: If the LT temperature > heat termination set point, then Screen 8 will display for a maximum of 1 minute before automatically advancing to next step.
Screen 4: Step 4
TEST4: COOL RT LT: XX°C XXX°F
If the RT temperature < cool termination set point, then Screen 4 will display for a maximum of 1 minute before automatically advancing to next step.
Screen 5: Step 5
TEST5: REPR RT LT: XX°C XXX°F
Note: Sequence step will not advance to tower
SWITCHOVER until repressurization time has elapsed and tower has fully pressurized. Exception: If switching failure is disabled then pressure condition is ignored.
Screen 9: Step 9
TEST9: COOL LT LT: XX°C XXX°F
If the LT temperature < cool termination set point, then Screen 9 will display for a maximum of 1 minute before automatically advancing to next step.
Screen 10: Step 10
TEST10: REPR LT LT: XX°C XXX°F
Note: Sequence step will not advance to tower
SWITCHOVER until repressurization time has elapsed and tower has fully pressurized. Exception: If switching failure is disabled then pressure condition is ignored.
25
6.6 Start-up
6.6.1 Controller Settings
Set or verify settings on Controller. Detailed operational points are presented in section 6.5.
WARNING - Enclosure may have live electric parts. De-energize dryer before opening enclosure.
6.6.2 Initial Pressurization
SLOWLY pressurize dryer to full line pressure. (If the
dryer was installed with inlet and outlet isolation valves, the inlet isolation valve should be slowly opened while the outlet isolation valve remains closed.)
During initial start-up, check the entire system for leaks. If necessary, de-pressurize the dryer and correct any leaks.
NOTE: Read the off-line tower pressure gauge when the tower is purging (air exhausting from muffler).
6.7.5 Process Valves
Determine if air control valves are operating and sequencing correctly.
6.7.5.1 Valves – Models 500 and 600
Inlet switching valves are normally open, pneumatically piston-actuated, Y-angle poppet valves. A yellow indicator can be seen through a clear window at the top of the ac­tuator housing when the valve is in the open position.
Purge exhaust valves are normally closed, pneumati­cally piston-actuated, Y-angle poppet valves. A yellow indicator can be seen through a clear window at the top of the actuator housing when the valve is in the open position.
6.6.2.1 Energy Management Sensor (if installed)
Open and adjust the sample exhaust valve until a very slight, continuous gas bleed is felt exhausting out of the sample cell.
6.6.2.2 Dew Point Sensor (if installed)
Ensure that the supply air valve is open (one turn). Open and adjust the sample exhaust valve until a very slight, continuous gas bleed is felt exhausting out of the sample cell.
6.6.3 Energizing the Dryer
Energize the dryer controls.
NOTE: The switching failure alarm may be activated if the unit is energized before it is pressurized. To deactivate alarm, allow dryer to cycle to next step and press the reset button.
6.6.4 Bringing the Dryer On-line
Establish a normal flow through the dryer. Slowly open the outlet isolation valve if present. Close any dryer bypass valves.
6.7 Operational Check Points
6.7.1 Power to unit
Check periodically that there is power to the unit (indicating lights illuminated).
6.7.2 Alarms
Periodically check for flashing red alarm LED.
6.7.3 Tower Status LEDs
Illuminated LEDs indicate which tower is on-line drying or off-line regenerating.
6.7.4 Tower Pressure Gauges
Periodically check tower pressure gauges to verify that the pressure gauge of the on-line tower reads line pressure and the pressure gauge of the off-line tower reads below 2 psig (0.14 kgf/ cm2).
12 volt DC, normally-closed, 3-way pilot solenoid valves are wired to the controller and are used to direct pilot air to the actuators of the inlet switching and purge/repres­surization valves.
Dryers are equipped with a safety relief valve that has been sized to provide overpressure protection due to a fire for both desiccant towers.
6.7.5.2 Valves – Models 750 through 4300
Inlet switching valves are resilient seated butterfly valves with double acting pneumatic rack and pinion actuators. A yellow arrow indicator located on the top of the actuator output shaft points to valve position indicator icons. Pilot air is directed to actuator ports to open both inlet valves upon loss of power.
(Model 750 only) Purge exhaust valves are normally closed, pneumatically piston-actuated, Y-angle poppet valves. A yellow indicator can be seen through a clear window at the top of the actuator housing when the valve is in the open position.
(Models 900 through 4300) Purge exhaust valves are resilient seated butterfly valves with spring return, fail closed, pneumatic rack and pinion actuators. A yellow arrow indicator located on the top of the actuator output shaft points to valve position indicator icons. Pilot air is directed to actuator ports to close both purge/repres­surization valves upon loss of power.
12 volt DC, single solenoid, 4-way pilot valves are wired to the controller and are used to direct pilot air to the actuators of the inlet switching and purge/repressuriza­tion valves.
Two mainline outlet and two purge line check valves are installed in the upper piping to control the flow of outlet and purge air. Check valve sticking will result in excessive air discharge through a muffler. Excessive air discharge through the muffler can be associated with a leaking outlet check valve on the same side or a purge check valve of the opposite side tower.
26
Dryers are equipped with a safety relief valve that has been sized to provide overpressure protection due to a fire for both desiccant towers.
b. Advances directly to the beginning of whichever
stage of HEAT or COOL it had been at when power was interrupted.
The tower pressure gauge of the on-line tower should read line pressure. Air should not be leaking from the purge-repressurization valve of the on-line tower.
The tower pressure gauge of the off-line tower should read below 2 psig (0.14 kgf/ cm2) while that tower is purging. If excessive air is exhausting during the purge cycle, the inlet-switching valve on the same side may have failed to close or a check valve may be sticking.
6.8 Dryer Shut Down
1. If the dryer installation is equipped with dryer bypass
and inlet and outlet isolation valves, the bypass valve should be opened and the inlet and outlet isolation valves closed.
2. De-energize the dryer’s electrical supply.
3. SLOWLY open the tower blow down valves (refer
to Figure 3 for general location) to vent the dryer internal pressure.
4. When all dryer pressure gauges indicate zero pres-
sure, close the tower blow down valves. Depres­surization is complete.
2. If th e off-li ne tower was at any oth er step (SWITCHOVER, DEPRESSURIZATION, REPRES­SURIZATION or HOLD) when power was lost, then the sequence simply resumes at that step.
6.10 Operating Parameters
Control valves are designed so that upon loss of power the air dryer is capable of drying air until the desiccant exposed to the airflow is saturated.
6.11 Using the RS-232 Port
The RS-232 port is used to monitor dryer operation from a host computer.
RS-232 connections are made at the 3-pin connector labeled J3 and located at the upper left-hand corner of the control board.
Interface to a PC requires a (1 to 1) DB-9 cable.
Cable Pin Out:
- Data transmitted on pin 2
- Data received on pin 3
- Ground is pin 5
- Pins 7 and 8 are jumpered at the dryer
6.9 Loss of Power
Control valves are designed so that upon loss of power the air dryer is capable of drying air until the desiccant exposed to the airflow is saturated.
6.9.1 Power Recovery:
6.9.1.1 On loss of electrical power –
All controller outputs turn off causing the dryer operating valves to react as follows:
1a. For models with poppet style inlet valves (models
500 - 600): both inlet valves will open. Both towers will repressurize.
1b. For models with butterfly inlet valves (models 750 -
4300): inlet valves will remain in position. Any minor leakage through the inlet valve or check valve will slowly repressurize the off-line tower.
2. Purge exhaust valves close.
3. Depressurization solenoid valves close.
4. Repressurization valve closes.
6.9.1.2 On restoration of power –
1. If power is lost when the off-line tower is in either the HEAT or COOL step, the off-line tower will be either partially or fully repressurized. On power recovery the sequence:
a. Resumes at the DEPRESSURIZATION step to
let down the pressure in the off-line tower then,
Operation:
1. Fixed baud rate of 9600
2. Asynchronous format is 8 bit, no parity, 1 stop bit (“8,N,1”)
3. No check sum or error correction values are pro­vided. If required, request status string two (or more) times and compare for agreement.
4. Request data by sending ASCII ? character (3FH). Response may take up to two seconds as certain processing functions may require completion before the serial port is acknowledged.
5. The dryer responds with line feed (0AH), carriage return (0DH), and a character string as follows:
STX Start of text character 0x02
109 Three character ASCII device identifier
, comma character x ASCII representation of the cycle type , xx ASCII representation of the cycle step , xxxxx ASCII representation of the current cycle time
in seconds , xxx ASCII representation of the inlet temperature
(°F)
27
, xxx ASCII representation of the heater tempera-
ture (°F) , xxx ASCII representation of the left bed tempera-
ture (°F) , xxx ASCII representation of the right bed tem-
perature (°F) , xxx ASCII representation of the humidity sensor
temperature (°F) , xxx ASCII representation of the humidity sensor
relative humidity (%) , xxxx ASCII representation of the dew point reading
(°F) , xxxx ASCII representation of the filter time to ser-
vice (hours) , xxxx ASCII representation of the desiccant time to
service (hours) , xxxx ASCII representation of the valve time to
service (hours) , x ASCII representation of programming jump-
ers , 1 or 0 Is the unit alarmed? 1 = alarm , 1 or 0 Is service required? 1 = service , xx ASCII representation of the energy savings
(%) , x Reserved for future use, always 1 for now , ETX end of text character OxO3 CR carriage return LF line feed
Determining jumper positions:
Each jumper 8 bits weighted by position
JP Value 8 128
7 64 6 32 5 16 4 8 3 4 2 2 1 1
Example:
If jumper 8, 5, and 1 are installed, a value of 128+16+1 = 145 is returned
To decode, the algorithm:
· If (number >= 128) jumper 8 = on
· number = number - 128
· If (number >= 64)  jumper 7 = on
· number = number - 64;
· etc.....
JUMPERS:
The programming jumpers are as follows (0=off, 1=on):
JP Bit 1 0 off = externally heated on = blower dryer 2 1 on = energy management sensor installed 3 2 on = dew point sensor installed 4 3 on = no cooling (blower purge only) 5 4 on = tower pressure switches installed 6 5 on = not used (fast cycle for development,
V3.5 and prior)
7 6 on = to download language text (factory
use)
8 7 on = to enable factory set-up screens
28

7.0 Maintenance

WARNING - This equipment is a pressure-containing device. Depressurize before servicing.
Note: The Dryer Controller is equipped with Service Reminder functions for filters, desiccant and valves.
7.1 Desiccant Replacement
NOTE: The use of the correct replacement desiccant
is necessary for proper dryer operation. Never use hygroscopic sa lts of the type commonly used in “deliquescent ” type dryers.
1. Frequency Of Desiccant Replacement
Desiccant should be replaced whenever the required
dew point cannot be maintained while the dryer is being operated within its design conditions and there are no mechanical malfunctions.
NOTE: Desiccant life is determined by the quality of
the inlet air. Proper filtering of the inlet air will extend the life of the desiccant. Typically desiccant life is 2 years.
2. Procedure for Desiccant Charge Replacement
a. Depressurize and de-energize the dryer.
b. Remove the fill and drain plugs or flanges (where
applicable) from the desiccant tower and drain the
spent desiccant. Place a container at the base of
the vessel to collect the desiccant. If necessary
tap the sides of the vessels with a rubber mallet
to loosen desiccant.
NOTE: Use extreme care when inserting rods or
other tools through the desiccant fill or drain ports to loosen packed desiccant. Internal flow diffusers at the ends of the desiccant beds can be damaged or punctured by sharp instruments. These diffusers are necessary to distribute the airflow and keep the desiccant beads within the tower. Desiccant beads in exhaust mufflers, afterfilters, or the piping connected to the desiccant towers may indicate a perforation of a diffuser.
c. Replace the drain plug using Teflon tape or another
pipe thread sealant suitable for compressed air
service. Reinstall drain port flange cover (where
applicable) in each desiccant tower.
d. Refer to Table 1 (on page 5) for desiccant quan-
tity per tower.
When using Table 1 you will find the desiccant
quantities listed in layers. Each layer will vary in
depth due to the type, quantity and purpose of the
desiccant. Layer 1 must be installed first at the
bottom of the vessel followed by layer number 2
etc., until the complete charge of desiccant has
been installed.
e. Utilizing an appropriate sized funnel, fill each
desiccant tower as follows:
1) Install the required quantity of tabular support (model 4300 only) or activated alumina in layer 1 of each tower.
2) Level layer 1 and each subsequent layer of desiccant as added to each tower.
3) Finish filling each tower with desiccant until all desiccant has been installed. LIGHT tap­ping on the tower sides with a soft-face mallet should yield additional free space to allow installation of all desiccant required. DO NOT TAMP OR RAM DESICCANT.
f. Clean the fill port closure. Replace the fill plug
using Teflon tape or another pipe thread sealant suitable for compressed air service. Reinstall fill port flange cover (where applicable) in desiccant tower.
3. Insuring Desiccant Dryness
Replacement desiccant is shipped in airtight
containers. Keep the covers on these containers tightly closed until use to avoid moisture contamination. If desiccant is exposed to air it can be heated in an oven at 400°F (204°C) for four hours before use. Alternatively, if the dryer is not refilled with dry desiccant, it may be necessary to operate the unit with an inlet flow rate of less than 50% of maximum rated inlet capacity until the desiccant has regenerated fully.
7.2 Purge Mufflers
Purge mufflers should be checked regularly, changed annually. Muffler disseminator elements become clogged with desiccant dust over time, creating back pressure and restricted purge flow.
7.3 Valves
1. Process and pilot valves should be checked fre­quently for leaks and proper operation.
2. Purge pressure adjustment valve should be checked frequently for proper adjustment.
7.4 Pilot Air Filter Element Replacement
1. Frequency of replacement
The pilot air filter contains a filter element that should
be changed yearly. Replacement may be required sooner if pressure drop across cartridge prevents valves from actuating properly.
Warning – The pilot air filter housing is a pressure­containing device, depressurize before servicing. Slowly open manual drain valve on bottom of filter bowl by turning clockwise to verify that the housing is depressurized before removing bowl.
29
2. Procedure for element replacement
a. Isolate dryer from air supply
b. Depressurize dryer by running dryer and allowing
system pressure to purge to atmosphere. Loss of pilot pressure will eventually prevent purge/ repressurization valves from opening. Remaining pressure can be vented to atmosphere through the manual drain on the pilot air filter. The system must be fully depressurized before removing the bowl.
c. Remove the filter bowl by pushing up, turn-
ing counterclockwise and then pulling straight down.
d. Clean the filter bowl.
e. Replace the element.
f. Clean and lubricate o-ring at top of bowl and
reassemble in reverse order.
7.5 Dew Point Analyzer Filter (optional) Element Replacement
1. Frequency of replacement
The Dew Point Analyzer filter contains a filter element
that should be changed yearly. Replacement may be required sooner if pressure drop across cartridge prevents the Dew Point Analyzer from operating properly.
Warning – The Dew Point Analyzer filter housing is a pressure-containing device, depressurize before servicing. Slowly open manual drain valve on bottom of filter bowl by turning clockwise to verify that the housing is depressurized before removing bowl.
2. Procedure for element replacement
a. Isolate dryer from air supply
b. Depressurize dryer by running dryer and allowing
system pressure to purge to atmosphere. Loss of pilot pressure will eventually prevent purge/ repressurization valves from opening. Remaining pressure can be vented to atmosphere through the manual drain on the pilot air filter. The system must be fully depressurized before removing the bowl.
c. Remove the filter bowl by pushing up, turn-
ing counterclockwise and then pulling straight down.
d. Clean the filter bowl.
e. Replace the element.
f. Clean and lubricate o-ring at top of bowl and
reassemble in reverse order.
30

8.0 Troubleshooting

WARNING - A POTENTIAL ELECTRICAL SHOCK HAZARD EXISTS. Some of the troubleshooting checks may require gaining access to the dryer’s electrical enclosure(s) while the power supply is energized and should be performed by a qualified electrical technician.
WARNING - Before performing any electrical or mechanical repairs or maintenance, or removing or disassembling any component, be sure to de­energize and depressurize the dryer.
SYMPTOM POSSIBLE CAUSE(S) CORRECTIVE ACTION
Indicator lights not illuminated 1. No power to unit.
2. Loss of power supply to (or at) dryer’s electrical disconnect switch or breaker. (customer supplied)
3. Blown fuse.
4. Board malfunction.
Excessive pressure drop in dryer 1. Inlet/Outlet screens on desiccant tow-
Low Pressure Alarm
Left Tower or Right Tower Drying
ers are dirty
2. Excessive flow rate
1. Loss of dryer air supply.
2. Excessive air demand.
3. Faulty drying tower pressure switch
4. Drying tower Inlet Valve failed to open
5. Drying tower Purge Exhaust Valve failed to close.
6. Drying tower Depressurization Valve failed to close
7. Regenerating tower Outlet Check Valve failed to close
8. Drying tower Purge Check Valve leak­ing
1. Check voltage at terminal board.
2. Check disconnect switch or breaker closed. If tripped breaker or blown fuse is noted, investigate and Remedy cause.
3. Replace fuse.
4. Replace board.
1. Clean screens; follow desiccant removal instructions in the Maintenance section.
2. Check flow rate of inlet air. Reduce to design flow rate.
1. Check compressor supplying dryer.
2. Check equipment downstream of dryer.
3. Check pressure switch operation using tower pressure gauge for comparison. Replace switch if defective.
4a. Check for loss of pilot air - ensure manual drain valve on
bottom of pilot air filter is fully closed, ensure pilot air filter cartridge is not clogged, ensure pilot air shut-off valve is open
4b. Check for inlet pilot air solenoid valve failure. Check valve
operation. Repair or replace as necessary.
4c. Check for drying tower Inlet Valve failure - examine valve
and actuator for damage. Repair or replace as necessary.
5a. Check for air flow out of drying tower Purge Valve or ex-
haust piping indicating valve is not completely closed.
5b. Check for loss of pilot air - ensure manual drain valve on
bottom of pilot air filter is fully closed, ensure pilot air filter cartridge is not clogged, ensure pilot air shut-off valve is open
5c. Check for purge pilot air solenoid valve failure. Check valve
operation. Repair or replace as necessary.
5d. Check for drying tower Purge Exhaust Valve failure - exam-
ine valve and actuator for damage. Repair or replace as necessary.
6. Check for air flow out of drying tower Depressurization Muffler indicating valve is not completely closed. Repair or replace as necessary.
7. Indicated by excessive flow out of regenerating tower Purge Valve. Examine valve internals. Repair or replace as necessary.
8. Indicated by excessive flow out of regenerating tower Purge Valve or reverse air flow through heater and blower, i.e., out of the blower intake filter, examine valve internals. Repair or replace as necessary.
CAUTION: Air flowing backwards through heater and
blower may be very hot.
31
SYMPTOM POSSIBLE CAUSE(S) CORRECTIVE ACTION
High Pressure Alarm
Left Tower or Right Tower Re­generating
Low Pressure Alarm
Left Tower or Right Tower Re­generating
Temperature Under-Range or Temperature Over-Range Alarm
Left Tower or Right Tower
Dew Point Under-Range or Dew Point Over-Range Alarm
Left Tower or Right Tower Re­generating
1. Faulty regenerating tower pressure switch
2. Regenerating tower Depressurization Muffler clogged.
3. Regenerating tower Depressurization Valve failed to open.
4. Regenerating tower purge exhaust pip­ing obstructed.
5. Regenerating tower Purge Exhaust Valve failed to open.
6. Repressurization valve (V11) failed to close.
1. Faulty left tower pressure switch.
2. Regenerating tower Purge Exhaust Valve failed to close.
3. Regenerating tower Depressurization Valve failed to close.
4. Repressurization valve (V11) failed to open.
5. Repressurization orifices are blocked.
1. Tower temperature sensor failure.
Under-Range Short circuit on sensor Over-Range Open circuit on sensor
1. Energy Management temperature sen­sor (RTD4) failure.
1. Check pressure switch operation using tower pressure gauge for comparison. Replace switch if defective.
2. Examine inner core and clean or replace as necessary.
3. Check valve operation. Repair or replace as possible.
4. Ensure piping is free of obstructions.
5a. Check for loss of pilot air - ensure manual drain valve on
bottom of pilot air filter is fully closed, ensure pilot air filter cartridge is not clogged, ensure pilot air shut-off valve is open.
5b. Check for purge pilot air solenoid valve failure. Check valve
operation. Repair or replace as necessary.
5c. Check for regenerating tower Purge Exhaust Valve failure -
examine valve and actuator for damage. Repair or replace as necessary.
6a. Check for loss of pilot air - ensure manual drain valve on
bottom of pilot air filter is fully closed, ensure pilot air filter cartridge is not clogged, ensure pilot air shut-off valve is open.
6b. Check for Repressurization Valve (V11) failure. Check valve
operation. Repair or replace as necessary.
1. Check pressure switch operation using tower pressure gauge for comparison. Replace switch if defective.
2a. Check for air flow out of regenerating tower Purge Valve or
exhaust piping indicating valve is not completely closed.
2b. Check for loss of pilot air - ensure manual drain valve on
bottom of pilot air filter is fully closed, ensure pilot air filter cartridge is not clogged, ensure pilot air shut-off valve is open
2c. Check for purge pilot air solenoid valve failure. Check valve
operation. Repair or replace as necessary.
2d. Check for regenerating tower Purge Exhaust Valve failure -
examine valve and actuator for damage. Repair or replace as necessary.
3. Check for air flow out of regenerating tower Depressur­ization Muffler indicating valve is not completely closed. Repair or replace as necessary.
4a. Check for loss of pilot air - ensure manual drain valve on
bottom of pilot air filter is fully closed, ensure pilot air filter cartridge is not clogged, ensure pilot air shut-off valve is open.
4b. Examine repressurization valve (V11) for damage. Repair
or replace as necessary.
5. Check orifices for obstruction and clean as necessary.
1. Check temperature circuit for continuity. Repair or replace as necessary.
1. Check temperature circuit for continuity. Repair or replace as necessary.
32
SYMPTOM POSSIBLE CAUSE(S) CORRECTIVE ACTION
Outlet Dew Point Alarm
Left Tower or Right Tower
High Humidity Alarm
Left Tower or Right Tower
Heater Over-Temperature Alarm
Heater Low-Temperature Alarm
Energy Management Under­Range Alarm or Energy Management Over­Range Alarm
Blower Motor Overload Alarm 1. Restricted or blocked purge air flow.
Heater High Inlet Temperature
(models 3200, 3600, & 4300 only)
1. Inlet air flow higher than the sizing condition.
2. Liquids entering the dryer inlet.
3. Inlet air temperature higher than the sizing condition.
4. Desiccant dusting.
5. Contaminated desiccant (e.g. with oil).
6. Heater temperature set too low.
7. Heating malfunction due to heater failure or heater contactor failure.
1. Desiccant bed overloaded.
2. Dew point sensor or monitor damaged or defective.
3. Loss of desiccant drying capacity
1. Insufficient purge gas flow.
2. Temperature sensor failure.
1. Heating malfunction due to heater failure or heater contactor failure.
2. Temperature sensor failure.
1. Energy Management sensor failure. 1. Check circuit for continuity. Repair or replace as neces-
2. Line failure
1. On-line tower purge check valve is leaking.
2. Temperature sensor failure.
1. Reduce inlet flow to sizing condition.
2. Check the inlet air line for liquids. Inspect prefilter and drain valve. Clean, repair or replace automatic drain valve.
3. Check the compressor aftercooler and cooling system. Reduce inlet air temperature to sizing condition.
4. Check air pressure, airflow and airflow surges and correct as necessary. Replace desiccant.
5. Check prefilter and automatic drain valve. Replace prefilter element. Clean, repair or replace drain valve as necessary. Consult factory concerning need for desiccant replacement.
6. Adjust controller set point.
7. Replace heater or heater contactor.
1. Check inlet air flow rate, temperature and pressure. Higher than design flow, and temperature, and lower than design pressure will result in overloading of the dryer.
2. Examine sensor for physical damage and check monitor/ sensor operation. Replace sensor or monitor as necessary.
3. Inlet air improperly filtered causing desiccant contamination
- examine filter elements and drains. Repair or replace as necessary. Useful life of desiccant has been exceeded.
1. Check for purge blockage, temperature sensor failure, etc.
2. Repair and replace as required.
1. Replace heater or heater contactor.
2. Repair and replace as required.
sary.
1a. Dirty intake filter on blower - examine filter element and
clean or replace.
1b. Regenerating tower purge exhaust valve failed to open -
1) Check for loss of pilot air - ensure manual drain valve on bottom of pilot air filter is fully closed, ensure pilot air filter cartridge is not clogged, ensure pilot air shut-off valve is open.
2) Check for purge pilot air solenoid valve failure. Check valve operation. Repair or replace as necessary.
3) Check for regenerating tower Purge Exhaust Valve failure ­examine valve and actuator for damage. Repair or replace as necessary.
1c. Purge exhaust piping obstructed - ensure piping is free of
obstructions.
1d. Regenerating tower purge check valve failed to open - ex-
amine valve internals. Repair or replace as necessary.
2. Check voltages and currents in the motor circuit.
1. Examine valve internals. Repair or replace as required.
2. Repair and replace as required.
33
P&ID Schematic
10
WET GAS INLET
2
1
17
5
19
21
29
19
16
42
43
13
6
23
24
20
DRY GAS OUTLET
25
28
27
4
54
SOL 'D'
V1
SOL 'F'
EXH.
V9
RTD
1
V3
V4
V2
SOL 'B
'
EXH.
SOL 'A
'
SOL 'G'
V1
0
RTD
2
V6
1PS
(RTD4/HS1)
ENERGY MGMT OPTION
SET @ 176°F
DRYING
EXH.
3PS
SET
@
5 PSIG
SOL 'C'
2
1
3
LEFT
TOWER
SET
@
45 PSI
G
M
RTD 3
SET @ 650°F
1TC
SET @ 370°F
V5
2PS
SET @ 176°F
4PS
SET
@
5 PSIG
18
REGE
N
9
SET
@
45 PSIG
SET AT 100 PSIG
RIGH
T
TOWE
R
12
11
8
7
V8
26
V12 V13
SOL 'E'
V7 V11
SET @ 165 PSI
G
DEWPOINTER OPTION
DP
A
15
3
22
14
13
44
A
SOLENOID VA
LVES 'B'� 'D'� � 'G' ARE SHOWN ENERGI�ED �
SYMBOLS ARE PER ANSI Y32.10 �GRAPHIC SYMBOLS FOR FLUID POWER DIAGRAMS.�
SOLENOID VALVES 'A'� 'C'� 'E'� � 'F' ARE SHOWN DE�ENERGI�ED .
AS SHOWN FLOW DIRECTION IS
INDICATES OPTIO
N
3.
2.
1.
PILOT GAS LINE
RIGHT CHAMBER REGEN
LEFT CHAMBER DRYING
NOTES
4.
44
Models 500 through 600 (Contact factory to request certified drawings)
34
LEGEND
LEFT CHAMBER DRYING (RIGHT CHAMBER REGEN)
CLOSED
NO
3 WAY
3 WA
Y
SOLENOID VALVE 'D'
SOLENOID VALV
E 'C'
N.O.
VALV
E 'E'
SOLENOID
3 WAY
HEATER
OPEN
CLOSED
OPEN
CLOSED
NO
YES
NO
V4
YES
V3
CLOSED
OPEN
ON
OFF
YES
NO
YES
NO
FIXED CYCLE TIMING
(T
IME IN MINUTES)
ENER
G
IZED
PROCESS
CO
MPONENT
ELECTRIC
AL CO
MPONENT
3 WAY
SOLENOID VALVE 'A'
SOLENOID VALV
E 'B'
ST
ATUS
PROCESS
CO
MPONENT
DEPRESSURIZA
TION
HE
ATIN
G
OPEN
CLOSED
OPEN
YES
NO
YES
V2
V1
257178
RIGHT CHAMBER DRYING (LEFT CHAMBER REGEN)
HE
ATIN
G
HOL
D
2ND ST
AG
E RE
GENERA
TION
REPRESSURIZA
TION
DEPRESSURIZA
TION
3 1782
HOL
D
REPRESSURI
ZA
TION
3
57
VALVE 'F'
V9
SOLENOID VALV
E 'G'
N.C.
N.C.
NO
YES
NO
OPEN
CLOSED
CLOSED
V10
SOLENOID
YES OPEN
MOTOR
OFF
ON
NO
YES
V11
BLOWER
(JUMPE
R SELECT
AB
LE
)
2ND ST
AG
E REGENERA
TI
ON
(JUMPE
R
SELECT
AB
LE
)
1. INLET VALVE (V1 LEFT, V2 RIGHT)
2. PURGE EXHAUST VALVE (V3 LEFT, V4 RIGHT)
3. PURGE CHECK VALVE (V5 LEFT, V6 RIGHT)
4. OUTLET CHECK VALVE (V7 LEFT, V8 RIGHT)
5. DEPRESS SOLENOID VALVE (V9 LEFT, V10 RIGHT)
6. PURGE HEATER WITH INSULATION
7. HEATER TEMPERATURE THERMOCOUPLE
8. HEATER OVERTEMPERATURE RTD
9. CHAMBER RTD (LEFT & RIGHT)
10. RELIEF VALVE
11. CHAMBER PRESSURE GAUGES (LEFT & RIGHT)
12. CHAMBER PRESSURE SWITCH (LEFT & RIGHT)
13. SERVICE VALVE
14. PILOT AIR FILTER
15. PRESSURE REGULATOR & GAUGE
16. SOLENOID VALVE
17. MUFFLER
18. DESICCANT CHAMBER
19. DESICCANT RETAINING SCREEN (TOP & BOTTOM)
20. DESICCANT FILL PORT
21. DESICCANT DRAIN PORT
22. HOT PIPE INSULATION
23. PURGE PRESSURE GAUGE
24. PURGE BLOWER AND MOTOR
25. PURGE SUCTION FILTER SILENCER
26. REPRESS/SWEEP SOLENOID VALVE (V11)
27. REPRESS/SWEEP CHECK VALVE (V12 LEFT, V13 RIGHT)
28. REPRESS/SWEEP ORIFICE
29. CHAMBER BLOW-DOWN VALVE
ENERGY MANAGEMENT OPTION
42. ENERGY MANAGEMENT PILOT OPERATED VALVE
43. ENERGY MANAGEMENT SENSOR (RTD4/HS1)
DEWPOINTER OPTION
44. DEWPOINT ANALYZER 44A. DEWPOINT ANALYZER FILTER
INSULATION OPTION
54. CHAMBER INSULATION
Sequence of Operation
(Models 500 through 600)
35
P&ID Schematic
10
WET GAS INLET
2
1
17
5
19
21
29
19
16
42
43
13
30
6
23
24
20
DRY GAS OUTLET
25
28
27
4
54
V2
SOL 'D'
1A
V1
SOL 'F'
EXH.
V9
RTD
1
V3
V4
SOL 'B
'
SOL 'A
'
EXH.
SOL 'G
'
V1
0
RTD
2
1PS
(RTD4/HS1)
ENERGY MGMT OPTION
SET @ 176°F
DRYING
EXH.
3PS
SET
@
5 PSIG
SOL 'C'
2
1
3
LEFT
TOWER
SET
@
45 PSI
G
M
1T
S
(225°F)
RTD
3
SET @ 650°F
1TC
SET @ 370°F
V5
V6
2PS
REGE
N
SET @ 176°F
4PS
SET
@
5 PSIG
18
9
RIGH
T
TOWER
SET
@
45 PSIG
SET AT 100 PSIG
12
11
8
7
26
V12 V13
SOL 'E'
V11V7
V8
SET @ 165 PSI
G
DEWPOINTER OPTION
DPA
15
3
22
14
13
44A
MODEL 750 ONLY
(SEE DETAIL 'A
'
FOR 900-4300)
SOLENOID VA
LVES 'B', 'D', & 'G' ARE SHOWN ENERGIZED,
SYMBOLS ARE PER ANSI Y32.10 "GRAPHIC SYMBOLS FOR FLUID POWER DIAGRAMS."
SOLENOID VA
LVES 'A', 'C', 'E', & 'F' ARE SHOWN DE-ENERGIZED.
AS SHOWN FLOW DIRECTION IS:
INDICATES OPTION
3.
2.
1.
PILOT GAS LINE
RIGHT CHAMBER REGEN
LEFT CHAMBER DRYING
NOTES
4.
44
OPEN 5 TURNS FROM FULL CLOSED AND LOCK IN PLAC
E
Models 750 through 4300 (Contact factory to request certified drawings)
36
LEGEND
*
= FAILS IN POSITION
LEFT CHAMBER DRYING (RIGHT CHAMBER REGEN)
CLOSEDNO
3 WAY
3 WA
Y
SOLENOID VALVE 'D'
SOLENOID VALV
E 'C'
N.O.
VALV
E 'E'
SOLENOID
3 WA
Y
HEATER
OPEN
CLOSED
OPEN
CLOSED
NO
YES
NO
V4
YES
V3
CLOSED
OPEN
ON
OFF
YES
NO
YES
NO
FIXED CYCLE TIMING
(T
IME IN MINUTES)
ENER
G
IZED
PROCESS
CO
MPONENT
ELECTRICAL CO
MPONEN
T
3 WAY
SOLENOID VALVE 'A'
SOLENOID VALV
E 'B'
ST
ATUS
PROCESS
CO
MPONENT
DEPRESSURIZ
A
TION
HE
ATIN
G
OPEN
CLOSED
OPEN
YES
NO
YES
V1
V2
257178
*
*
*
*
RIGHT CHAMBER DRYING (LEFT CHAMBER REGEN)
HE
ATIN
G
HOL
D
2ND ST
AG
E REGENE
R
A
TIO
N
REPRESSURI
ZA
TI
ON
DEPRESSURIZ
A
TION
3 1782
HOL
D
LO
SS OF POWER
REPRESSURI
ZA
TION
3
57
VALVE 'F'
V9
SOLENOID VALV
E 'G'
N.C.
N.C.
NO
YES
NO
OPEN
CLOSED
CLOSED
V10
SOLENOID
YES OPEN
MOTOR
OFF
ON
NO
YES
V11
BLOWER
(JUMPER SE
L
ECTABLE)
2ND ST
AGE RE
GENE
R
AT
IO
N
(JUMPER
SELECT
ABL
E)
DETAIL 'A' (MODELS 900-4300)
V4
SOL 'C'
V3
2
3
4
1
5
2
3
SOL 'D'
4
1
5
1. INLET VALVE (V1 LEFT, V2 RIGHT) 1A. FLOW CONTROL VALVE
2. PURGE EXHAUST VALVE (V3 LEFT, V4 RIGHT)
3. PURGE CHECK VALVE (V5 LEFT, V6 RIGHT) (NO SPRING)
4. OUTLET CHECK VALVE (V7 LEFT, V8 RIGHT)
5. DEPRESS SOLENOID VALVE (V9 LEFT, V10 RIGHT)
6. PURGE HEATER WITH INSULATION
7. HEATER TEMPERATURE THERMOCOUPLE
8. HEATER OVERTEMPERATURE RTD
9. CHAMBER RTD (LEFT & RIGHT)
10. RELIEF VALVE
11. CHAMBER PRESSURE GAUGES (LEFT & RIGHT)
12. CHAMBER PRESSURE SWITCH (LEFT & RIGHT)
13. SERVICE VALVE
14. PILOT AIR FILTER
15. PRESSURE REGULATOR & GAUGE
16. SOLENOID VALVE
17. MUFFLER
18. DESICCANT CHAMBER
19. DESICCANT RETAINING SCREEN (TOP & BOTTOM)
20. DESICCANT FILL PORT
21. DESICCANT DRAIN PORT
22. HOT PIPE INSULATION
23. PURGE PRESSURE GAUGE
24. PURGE BLOWER AND MOTOR
25. PURGE SUCTION FILTER SILENCER
26. REPRESS/SWEEP SOLENOID VALVE (V11)
27. REPRESS/SWEEP CHECK VALVE (V12 LEFT, V13 RIGHT)
28. REPRESS/SWEEP ORIFICE
29. CHAMBER BLOW-DOWN VALVE
30. TEMPERATURE SWITCH (MODELS 3200 - 4300 ONLY)
ENERGY MANAGEMENT OPTION
42. ENERGY MANAGEMENT PILOT OPERATED VALVE
43. ENERGY MANAGEMENT SENSOR (RTD4/HS1)
DEWPOINTER OPTION
44. DEWPOINT ANALYZER 44A. DEWPOINT ANALYZER FILTER
INSULATION OPTION
54. CHAMBER INSULATION
Sequence of Operation
(Model 750 through 4300)
37
Electrical Schematic – 460VAC, 3 phase
LOCATED
EXTERNALLY
HEATER OVERTEMPERATURE
RPS
RPS
IN2
RT
D5-
IN1
LPS
LPS
RT
D3-
RT
D3+
RT
D5+
RT
D4-
RT
D4+
RTD1
RT
D
RTD
RIGHT CHAMBER
LEFT CHAMBER
RT
D
RTD3
RTD2
ANLG2+
ANLG2-
RT
D2-
RTD2+
+5VDC
DC COM
RT
D1-
RT
D1+
ANLG1-
ANLG1+
+12VDC
DC COM
PE
PE
N
L
L
N
SET @ 45 PSIG2PS
PRESSURE SWITCH
RIGHT CHAMBER
SET @ 45 PSIG1PS
PRESSURE SWITCH
LEFT CHAMBER
SENSOR
5VDC
1-5VDC OUT
+
DEWPOINT
TRANSMITTER
1TC
+ -
L1
N
K TYPE
HC
L DRY
ALARM
OUT2
CONTACTS
NO
C
NC
R DRY
OUT1
R DRY
L
DRY
SOLENOID "B"
SOLENOID "A"
L
PURGE
L
PURGE
R PURGE
R PURGE
IN3
2CR
3CR
LOW TENSION ENCLOSURE
HIGH TENSION ENCLOSURE
CUSTOMER PROVIDED
460VAC, 3 PHASE
(FOR FUSING AND WIRE
407
40
8
101A
460V
AC
115V
AC
2CR1
3CR1
SOLENOID "F
"
SOLENOID "G
"
1T
2FU
1FU
3FU
L2
L1
L4
L5
L6
HC1
HC2
HC3
404
405
406
+ 4-20MA OUT
ENERGY MGMT
OPTION
RT
D4
+
-
1HTR
102
101
102
102
102
1CR
102
101
101
101
109
111
101
107
SOLENOID "C"
21
LEFT CHAMBER PURGE EXHAUST
HEAT ENABLE
C NO
101
102
20
21
80
81
70
72
21
10
11
84
85
86
87
88
89
32
33
34
35
50
51
52
53
54
55
56
57
59
20
20
21
TO
TB3
+12VDC
FROM TB6
SOLENOID "E
"
+12VDC
20 21
+
-
-
+
-
+
-
+
4CR
1CR1
104
105
102
+ -
+ -
+ -
+ -
3
G
1
RED
ORANGE
GREEN
BROWN
BLACK
249 OHM
1/8W
EXTERNALLY
LOCATED
OPTION
102
120VAC TO
TB3
101
102
101
120VAC
FROM TB5
101
11
5
21
109
3PS
110
CLOSES @ 5 PSIG
4CR1
104
101
5CR1
MC-AUX
LEFT CHAMBER DEPRESS
111
4PS
SOLENOID "D
"
21
102
102
11
2
5CR
RIGHT CHAMBER DEPRESS
EXHAUST
RIGHT CHAMBER PURG
E
L3
L2
L1
MC1
MC3
MC2
403
402
401
MOTOR
1M
{
SIZING SEE TABLE 1)
106
20
4CR2
23
20
5CR2
24
~
~
+12VDC FROM TB6-1 FROM TB6-
2
DC COM
OL-AUX
36
37
H1 H3
X1 X2
OL1
OL2
OL3
H2 H4
21
GREEN
BLACK
RED
SET @ 225°F
1TS
3200, 3600 & 4300
USED ON MODEL
S
38
39
0.5 AM
P
0.5 AM
P
1.25 AMP
TB5
CLOSES @ 5 PSIG
1TR (OFF-DELAY, SET @ 180S)
108
102
15 18
1TR1
A1B1A2
MC
102
102
105
101
OL-AUX
104
11
4
101
NOTE
: SET 1TR ON MODE "D". (SIGNAL OFF-DELAY)
G
YELLOW
(Contact factory to request certified drawings)
38
Electrical Schematic – 575VAC, 3 phase
LOCATED
EXTERNALLY
HEATER OVERTEMPERATURE
TB1-12
TB1-11
TB1-13
TB2-1
TB1-16
TB1-15
TB1-14
TB2-2
TB2-6
TB2-5
TB2-4
TB2-7
TB2-8
TB2-3
RPS
RPS
IN2
RTD5
-
IN1
LPS
LPS
RTD3
-
RTD3
+
RTD5
+
RTD4
-
RTD4
+
RT
D1
RT
D
RT
D
RIGHT CHAMBER
LEFT CHAMBER
RT
D
RT
D3
RT
D2
TB5-1
TB5-1
TB5-3
TB5-3
TB5-2
TB5-2
TB6-2
TB1-1
TB1-2
TB1-7
TB1-6
TB1-5
TB1-4
TB1-8
TB1-3
TB6-1
TB1-10
TB1-9
ANLG2+
ANLG2-
RTD2
-
RTD2
+
+5VDC
DC COM
RTD1
-
RTD1
+
ANLG1-
ANLG1+
+12VDC
DC COM
PE
PE
N
L
L
N
SET @ 45 PSIG2PS
PRESSURE SWITCH
RIGHT CHAMBER
SET @ 45 PSIG1PS
PRESSURE SWITCH
LEFT CHAMBER
SENSOR
5VDC
1-5VDC OUT
+
DEWPOINT
TRANSMITTER
1TC
+ -
L1
N
K TYPE
1HC
TB3-5L DRY
TB3-6
TB3-8
TB3-7
TB3-11
TB3-10
TB3-9
TB3-12
TB4-1
TB4-3
TB4-2
ALARM
OUT2
CONTACTS
NO
C
NC
R DRY
OUT1
R DRY
L
DRY
SOLENOID "B"
SOLENOID "A"
TB2-10
TB3-1
TB2-9
TB3-3
TB3-2
TB3-4
L
PURGE
L
PURGE
R PURGE
R PURGE
IN3
2CR
3CR
LOW TENSION ENCLOSURE
HIGH TENSION ENCLOSURE
510
51
1
101A
575V
AC
115V
AC
2CR1
3CR1
SOLENOID "F
"
SOLENOID "G
"
1T
2FU
1FU
3FU
L2
L1
L7
L8
L9
2HC1
2HC2
2HC3
507
508
509
+ 4-20MA OUT
ENERGY MGMT
OPTION
RT
D4
+
-
2HTR
102
101
102
102
102
1CR
102
101
101
101
109
11
1
101
107
SOLENOID "C
"
21
LEFT CHAMBER DEPRESS
LEFT CHAMBER PURGE EXHAUST
HEAT ENABLE
C NO
101
102
20
21
80
81
70
72
21
10
11
84
85
86
87
88
89
32
33
34
35
50
51
52
53
54
55
56
57
59
20
20
21
TO
TB3
+12VDC
FROM TB6
SOLENOID "E"
+12VDC
20 21
+
-
-
+
-
+
-
+
4CR
1CR1
104
105
102
+ -
+ -
+ -
+ -
3
G
1
RED
ORANGE
GREEN
BROWN
BLACK
249 OHM
1/8W
EXTERNALLY LOCATED
OPTION
102
120VAC TO
TB3
101
102
101
120VAC
FROM TB5
101
11
0
21
109
3PS
11
0
CLOSES @ 5 PSI
G
4CR1
104
101
5CR1
MC-AUX
LEFT CHAMBER DEPRESS
CLOSES @ 5 PSI
G
111
4PS
SOLENOID "D
"
21
102
102
11
2
5CR
RIGHT CHAMBER DEPRESS
EXHAUST
RIGHT CHAMBER PURGE
RIGHT CHAMBER DEPRESS
L6
L5
L4
106
20
4CR2
23
20
5CR2
24
~ ~
+12VDC FROM TB6-1 FROM TB6-2
DC COM
OL-AUX
36
37
H1
X1 X3
H5
21
GREEN
BLACK
RED
SET @ 225°F
1TS
3200, 3600 & 4300
USED ON MODELS
OL
2
{
MC2
(FOR FUSING AND WIRE
L3
SIZING SEE TABLE 1)
MC3 OL
3
503
L2
575VAC, 3 PHASE
CUSTOMER PROVIDED
L1
MC1 OL
1
501
502
MOTOR
1M
1HC1
1HC3
1HC2
506
505
504
1HTR
2HC
102
3200, 3600 & 4300
USED ON MODEL
S
3200, 3600 & 4300
USED ON MODEL
S
38
39
101
11
4
101
OL-AUX
105
B1
1TR1
108
15 18
A1 A2
102
102
MC
102
(SIGNAL OFF-DELAY
)
SET 1TR ON MODE "D".
NOTE:
1TR (OFF-DELAY, SET @ 180S
)
0.5 AM
P
0.5 AM
P
1.25 AM
P
YELLOW
G
(Contact factory to request certified drawings)
39
Electrical Schematic – 380VAC, 3 phase
LOCATED
EXTERNALLY
HEATER OVERTEMPERATURE
RPS
RPS
IN2
RT
D5-
IN1
LPS
LPS
RT
D3-
RT
D3+
RTD5+
RT
D4-
RT
D4+
RT
D1
RT
D
RTD
RIGHT CHAMBER
LEFT CHAMBER
RTD
RT
D3
RT
D2
ANLG2+
ANLG2-
RT
D2-
RT
D2+
+5VDC
DC COM
RT
D1-
RT
D1+
ANLG1-
ANLG1+
+12VDC
DC COM
PE
PE
N
L
L
N
SET @ 45 PSIG2PS
PRESSURE SWITCH
RIGHT CHAMBER
SET @ 45 PSIG1PS
PRESSURE SWITCH
LEFT CHAMBER
SENSOR
5VDC
1-5VDC OUT
+
DEWPOINT
TRANSMITTER
1TC
+ -
L1 N
K TYPE
HC
L
DRY
ALARM
OUT2
CONTACTS
NO
C
NC
R DRY
OUT1
R DRY
L
DRY
SOLENOID "B
"
SOLENOID "A"
L
PURGE
L
PURGE
R PURGE
R PURGE
IN3
2CR
3CR
LOW TENSION ENCLOSURE
HIGH TENSION ENCLOSURE
CUSTOMER PROVIDED
380VAC, 3 PHASE
(FOR FUSING AND WIRE
307
30
8
101A
380VAC
110V
AC
2CR1
3CR1
SOLENOID "F
"
SOLENOID "G
"
1T
2FU
1FU
3FU
L2
L1
L4
L5
L6
HC1
HC2
HC3
304
305
306
+ 4-20MA OUT
ENERGY MGMT
OPTION
RT
D4
+
-
1HTR
102
101
102
102
102
1CR
102
101
101
101
109
111
101 107
SOLENOID "C"
21
LEFT CHAMBER DEPRESS
LEFT CHAMBER PURGE EXHAUST
HEAT ENABLE
C NO
101
102
20
21
80
81
70
72
21
10
11
84
85
86
87
88
89
32
33
34
35
50
51
52
53
54
55
56
57
59
20
20
21
TO
TB3
+12VDC
FROM TB6
SOLENOID "E"
+12VDC
20 21
+
-
-
+
-
+
-
+
4CR
1CR1
104
105
102
+ -
+ -
+ -
+ -
3
G
1
RED
ORANGE
GREEN
ORANGE
BLACK
249 OHM
1/8W
EXTERNALLY LOCATED
OPTION
102
120VAC TO
TB3
101
102
101
120VAC
FROM TB5
101
11
5
21
109
3PS
110
CLOSES @ 5 PSIG
4CR1
104
101
5CR1
MC-AUX
LEFT CHAMBER DEPRESS
CLOSES @ 5 PSIG
111
4PS
SOLENOID "D
"
21
102
102
11
2
5CR
RIGHT CHAMBER DEPRES
S
EXHAUST
RIGHT CHAMBER PURG
E
RIGHT CHAMBER DEPRES
S
L3
L2
L1
MC1
MC3
MC2
303
302
301
MOTOR
1M
{
SIZING SEE TABLE 1)
106
20
4CR2
23
20
5CR2
24
~
~
+12VDC FROM TB6-1 FROM TB6-2
DC COM
OL-AUX
36
37
H1 H3
X1 X4
OL1
OL
2
OL
3
BLACK
GREEN
RED
21
1TS
USED ON MODELS 3200, 3600 & 4300
SET @ 225°F
39
38
(.5AMP
)
(.5 AMP
)
(1.25 AMP
)
TB5
104
101
1TR (OFF-DELAY, SET @ 180S
)
OL-AUX
114
1815
1TR1
MC
108
105
101
A1B1A2
102
102
NOTE
:
(SIGNAL OFF-DELAY)
SET 1TR ON MODE "D".
102
YELLOW
G
(Contact factory to request certified drawings)
40
Electrical Schematic – 415VAC, 3 phase
LOCATED
EXTERNALLY
HEATER OVERTEMPERATURE
RPS
RPS
IN2
RT
D5-
IN1
LPS
LPS
RT
D3-
RT
D3+
RT
D5+
RT
D4-
RT
D4+
RT
D1
RT
D
RTD
RIGHT CHAMBER
LEFT CHAMBER
RTD
RT
D3
RT
D2
ANLG2+
ANLG2-
RT
D2-
RT
D2+
+5VDC
DC COM
RT
D1-
RT
D1+
ANLG1-
ANLG1+
+12VDC
DC COM
PE
PE
N
L
L
N
SET @ 45 PSIG2PS
PRESSURE SWITCH
RIGHT CHAMBER
SET @ 45 PSIG1PS
PRESSURE SWITCH
LEFT CHAMBER
SENSOR
5VDC
1-5VDC OUT
+
DEWPOINT
TRANSMITTER
1TC
+ -
L1
N
K TYPE
HC
L
DRY
ALARM
OUT2
CONTACTS
NO
C
NC
R DRY
OUT1
R DRY
L
DRY
SOLENOID "B"
SOLENOID "A"
L
PURGE
L PURGE
R PURGE
R PURGE
IN3
2CR
3CR
LOW TENSION ENCLOSURE
HIGH TENSION ENCLOSURE
CUSTOMER PROVIDED
415VAC, 3 PHASE
(FOR FUSING AND WIRE
407
40
8
101A
415VAC
120V
AC
2CR1
3CR1
SOLENOID "F
"
SOLENOID "G
"
1T
2FU
1FU
3FU
L2
L1
L4
L5
L6
HC1
HC2
HC3
404
405
406
+ 4-20MA OUT
ENERGY MGMT
OPTION
RT
D4
+
-
1HTR
102
101
102
102
102
1CR
102
101
101
101
109
111
101 107
SOLENOID "C"
21
LEFT CHAMBER DEPRESS
LEFT CHAMBER PURGE EXHAUST
HEAT ENABLE
C NO
101
102
20
21
80
81
70
72
21
10
11
84
85
86
87
88
89
32
33
34
35
50
51
52
53
54
55
56
57
59
20
20
21
TO
TB3
+12VDC
FROM TB6
SOLENOID "E"
+12VDC
20 21
+
-
-
+
-
+
-
+
4CR
1CR1
104
105
102
+ -
+ -
+ -
+ -
3
G
1
RED
ORANGE
GREEN
ORANGE
BLACK
249 OHM
1/8W
EXTERNALLY LOCATED
OPTION
102
120VAC TO
TB3
101
102
101
120VAC
FROM TB5
101
11
5
21
109
3PS
110
CLOSES @ 5 PSIG
4CR1
104
101
5CR1
MC-AUX
LEFT CHAMBER DEPRESS
CLOSES @ 5 PSIG
111
4PS
SOLENOID "D
"
21
102
102
11
2
5CR
RIGHT CHAMBER DEPRESS
EXHAUST
RIGHT CHAMBER PURG
E
RIGHT CHAMBER DEPRES
S
L3
L2
L1
MC1
MC3
MC2
403
402
401
MOTOR
1M
{
SIZING SEE TABLE 1)
106
20
4CR2
23
20
5CR2
24
~
~
+12VDC FROM TB6-1 FROM TB6-2
DC COM
OL-AUX
36
37
H1 H3
X2 X4
OL1
OL2
OL3
BLACK
GREEN
RED
21
1TS
USED ON MODELS 3200, 3600 & 4300
SET @ 225°F
39
38
0.5 AM
P
0.5 AM
P
1.25 AMP
TB5
HEATER & MOTOR FUSES BY CUSTOMER
101
11
4
101
OL-AUX
105
B1
1TR1
108
15 18
A1 A2
102
102
MC
102
(SIGNAL OFF-DELAY)
SET 1TR ON MODE "D".
NOTE
:
1TR (OFF-DELAY, SET @ 180S
)
YELLOW
G
(Contact factory to request certified drawings)
41
Electrical Data – Fusing & Wire Sizing
Electrical Service: 460VAC, 3 phase
MODEL COMPONENT RATING
HEATER 10 KW 12.6 20 AMPS #12 AWG
500
600
750
900
1050
1300
1500
1800
2200
2600
3200
3600
4300
MOTOR 2.5 HP 4.1 7.5 AMPS #12 AWG
HEATER 12 KW 15.1 20 AMPS #12 AWG
MOTOR 4 HP 6.2 10 AMPS #12 AWG
HEATER 14 KW 17.6 25 AMPS #12 AWG
MOTOR 4 HP 6.2 10 AMPS #12 AWG
HEATER 17 KW 21.3 30 AMPS #10 AWG
MOTOR 4 HP 6.2 10 AMPS #12 AWG
HEATER 19 KW 23.8 30 AMPS #10 AWG
MOTOR 5 HP 7.6 12 AMPS #12 AWG
HEATER 23 KW 28.9 40 AMPS #8 AWG
MOTOR 7.5 HP 11 17.5 AMPS #12 AWG
HEATER 28 KW 35.1 45 AMPS #8 AWG
MOTOR 10 HP 14 20 AMPS #12 AWG
HEATER 33 KW 41.4 60 AMPS #6 AWG
MOTOR 10 HP 14 20 AMPS #12 AWG
HEATER 40 KW 50.2 70 AMPS #4 AWG
MOTOR 10 HP 14 20 AMPS #12 AWG
HEATER 45 KW 56.5 80 AMPS #4 AWG
MOTOR 15 HP 21 30 AMPS #10 AWG
HEATER 54 KW 67.8 90 AMPS #2 AWG
MOTOR 5 HP 7.6 12 AMPS #12 AWG
HEATER 60 KW 75.3 100 AMPS #2 AWG
MOTOR 5 HP 7.6 12 AMPS #12 AWG
HEATER 70 KW 87.9 110 AMPS #2 AWG
MOTOR 7.5 HP 11 17.5 AMPS #12 AWG
F.L.A.
@460VAC
SUGGESTED
FUSING
WIRE SIZE
Electrical Service: 575VAC, 3 phase
MODEL COMPONENT RATING
HEATER 10 KW 10.0 15 AMPS #12 AWG
500
600
750
900
1050
1300
1500
1800
2200
2600
3200*
3600*
4300*
MOTOR 2.5 HP 3.3 6 AMPS #12 AWG
HEATER 12 KW 12.0 20 AMPS #12 AWG
MOTOR 4 HP 5 9 AMPS #12 AWG
HEATER 14 KW 14.1 20 AMPS #12 AWG
MOTOR 4 HP 5 9 AMPS #12 AWG
HEATER 17 KW 17.1 25 AMPS #12 AWG
MOTOR 4 HP 5 9 AMPS #12 AWG
HEATER 19 KW 19.1 25 AMPS #12 AWG
MOTOR 5 HP 6.1 9 AMPS #12 AWG
HEATER 23 KW 23.1 30 AMPS #8 AWG
MOTOR 7.5 HP 9 15 AMPS #12 AWG
HEATER 28 KW 28.1 40 AMPS #8 AWG
MOTOR 10 HP 11 17.5 AMPS #12 AWG
HEATER 33 KW 33.1 50 AMPS #8 AWG
MOTOR 10 HP 11 17.5 AMPS #12 AWG
HEATER 40 KW 40.2 60 AMPS #6 AWG
MOTOR 10 HP 11 17.5 AMPS #12 AWG
HEATER 45 KW 45.2 60 AMPS #6 AWG
MOTOR 15 HP 17 25 AMPS #10 AWG
HEATER 2 – 27 KW 2 – 27.1 2 – 40 AMPS 2 – #8 AWG
MOTOR 5 HP 6.1 9 AMPS #12 AWG
HEATER 2 – 30 KW 2 – 31.1 2 – 40 AMPS 2 – #8 AWG
MOTOR 5 HP 6.1 9 AMPS #12 AWG
HEATER 2 – 35 KW 2 – 35.1 2 – 40 AMPS 2 – #8 AWG
MOTOR 7.5 HP 9 15 AMPS #12 AWG
F.L.A.
@575VAC
* Models 3200, 3600 and 4300 use a two-stage heater circuit with two contactors,
six fuses, and six wires.
SUGGESTED
FUSING
WIRE SIZE
Electrical Service: 380VAC, 3 phase
MODEL COMPONENT RATING
HEATER 10 KW 15.2 25 AMPS #12 AWG
500
600
750
900
1050
1300
1500
1800
2200
2600
3200
3600
4300
MOTOR 3 HP 6 12 AMPS #12 AWG
HEATER 12 KW 18.2 25 AMPS #12 AWG
MOTOR 5 HP 9 17.5 AMPS #12 AWG
HEATER 14 KW 21.3 30 AMPS #10 AWG
MOTOR 3 HP 6 12 AMPS #12 AWG
HEATER 17 KW 25.8 35 AMPS #10 AWG
MOTOR 3 HP 6 12 AMPS #12 AWG
HEATER 19 KW 28.9 40 AMPS #8 AWG
MOTOR 5 HP 9 17.5 AMPS #12 AWG
HEATER 23 KW 34.9 45 AMPS #8 AWG
MOTOR 7.5 HP 13 20 AMPS #12 AWG
HEATER 28 KW 42.5 55 AMPS #6 AWG
MOTOR 10 HP 16 30 AMPS #10 AWG
HEATER 33 KW 50.1 65 AMPS #6 AWG
MOTOR 12.5 HP 23.7 40 AMPS #10 AWG
HEATER 40 KW 60.8 80 AMPS #4 AWG
MOTOR 7.5 HP 13 20 AMPS #12 AWG
HEATER 45 KW 68.4 90 AMPS #2 AWG
MOTOR 15 HP 24 40 AMPS #12 AWG
HEATER 54 KW 82.0 100 AMPS #2 AWG
MOTOR 7.5 HP 13 20 AMPS #12 AWG
HEATER 58 KW 88.1 110 AMPS #2 AWG
MOTOR 7.5 HP 13 20 AMPS #12 AWG
HEATER 70 KW 106.4 150 AMPS #1/0 AWG
MOTOR 7.5 HP 13 20 AMPS #12 AWG
F.L.A.
@380VAC
SUGGESTED
FUSING
WIRE SIZE
Electrical Service: 415VAC, 3 phase
MODEL COMPONENT RATING
HEATER 10 KW 13.9 20 AMPS #12 AWG
500
600
750
900
1050
1300
1500
1800
2200
2600
3200
3600
4300
MOTOR 3 HP 6 10 AMPS #12 AWG
HEATER 12 KW 16.7 25 AMPS #10 AWG
MOTOR 5 HP 8 15 AMPS #12 AWG
HEATER 14 KW 19.5 25 AMPS #10 AWG
MOTOR 3 HP 6 10 AMPS #12 AWG
HEATER 17 KW 23.7 30 AMPS #10 AWG
MOTOR 4.2 HP 5.6 15 AMPS #12 AWG
HEATER 19 KW 26.4 40 AMPS #8 AWG
MOTOR 5 HP 8 15 AMPS #12 AWG
HEATER 23 KW 32.0 40 AMPS #8 AWG
MOTOR 7.5 HP 12 20 AMPS #12 AWG
HEATER 28 KW 39.0 50 AMPS #8 AWG
MOTOR 10 HP 15 25 AMPS #10 AWG
HEATER 33 KW 45.9 60 AMPS #6 AWG
MOTOR 12.5 HP 17 30 AMPS #10 AWG
HEATER 40 KW 55.6 70 AMPS #4 AWG
MOTOR 7.5 HP 12 20 AMPS #12 AWG
HEATER 45 KW 62.6 80 AMPS #4 AWG
MOTOR 15 HP 22 40 AMPS #8 AWG
HEATER 53 KW 73.7 100 AMPS #2 AWG
MOTOR 5 HP 8 15 AMPS #12 AWG
HEATER 58 KW 80.7 110 AMPS #2 AWG
MOTOR 7.5 HP 12 20 AMPS #12 AWG
HEATER 70 KW 97.4 125 AMPS #1 AWG
MOTOR 7.5 HP 12 20 AMPS #12 AWG
F.L.A.
@415VAC
SUGGESTED
FUSING
WIRE SIZE
42
43

WARRANTY

SPX Dehydration & Filtration
1000 Philadelphia Street Canonsburg, PA 15317-1700 U.S.A. Phone: 724-745-1555 • Fax: 724-745-6040 Email: hankison.service@dehydration.spx.com www.hankisonintl.com
© 2008 SPX Dehydration & Filtration. All rights reserved.
The manufacturer warrants the product manufactured by it, when properly installed, operated, applied, and maintained in accor­dance with the procedures and recommendations outlined in the manufacturer’s instruction manuals, to be free from defects in material or workmanship for a period of one (1) year from the date of shipment from the manufacturer or the manufacturer’s authorized distributor, or eighteen months from the date of shipment from the factory, whichever occurs first, provided such defect is discovered and brought to the manufacturer’s attention the aforesaid warranty period. The manufacturer will repair or replace any product or part determined to be defective by the manufacturer within the warranty period, provided such defect occurred in normal service and not as the result of misuse, abuse, neglect, or accident.
The warranty covers parts and labor for the warranty period. Repair or replacement shall be made at the factory or the installation site, at the sole option of the manufacturer. The manufacturer must first authorize any service performed on the product by anyone other than the manufacturer. Normal maintenance items requiring routine replacement are not warranted. Unauthorized service voids the warranty and any resulting charge or subsequent claim will not be paid.
THE FOREGOING WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES, WRITTEN, ORAL, OR STATUTORY,
AND IS EXPRESSED IN LIEU OF THE IMPLIED WARRANTY OF MERCHANTABILITY AND THE IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE. THE MANUFACTURER SHALL NOT BE LIABLE FOR LOSS OR DAMAGE BY REASON OF STRICT
LIABILITY IN TORT OR ITS NEGLIGENCE IN WHATEVER MANNER INCLUDING DESIGN, MANUFACTURE, OR INSPECTION OF THE EQUIPMENT OR ITS FAILURE TO DISCOVER, REPORT, REPAIR, OR MODIFY LATENT DEFECTS INHERENT THEREIN. THE MANUFACTURER, HIS REPRESENTATIVE OR DISTRIBUTOR SHALL NOT BE LIABLE FOR LOSS OF USE OF THE PRODUCT OR OTHER INCIDENTAL OR CONSEQUENTIAL COSTS, EXPENSES, OR DAMAGES INCURRED BY THE BUYER, WHETHER ARISING FROM BREACH OF WARRANTY, NEGLIGENCE OR STRICT LIABILITY IN TORT.
The manufacturer does not warranty any product, part, material, component, or accessory manufactured by others and sold or sup­plied in connection with the sale of the manufacturer’s products.
AUTHORIZATION FROM THE SERVICE DEPARTMENT IS NECESSARY BEFORE
MATERIAL IS RETURNED TO THE FACTORY OR IN-WARRANTY REPAIRS ARE MADE.
SERVICE DEPARTMENT : (724) 746-1100
Loading...