Added Hanbell Flooded Type Compressor with Oil Separator
Update Manual to Rev L
Inserted Table of Contents
Update Manual to Rev M
Updated images Hanbell VFD & Solenoids
DEW
DEW
DEW
DEW
e MCS Commitment: Our commitment is to provide practical solutions for the industry’s needs and to be both a
leader and a partner in the effective use of microprocessor controls.
(W
ebsite contains product descriptions, manuals, software releases and troubleshooting aids among others)
All information contained within this document is considered to be proprietary information of M ic ro Co ntr ol Sy stem s, I nc. No
information or data from thi s d ocu ment sha ll b e published, used, reprod uced, tr ans mitted, or disclosed to others outside your
organization without the prior expressed written consent of Micro Control Systems, Inc. This document and the information
contained herein shall be treated as proprietary. Reasonable provisions shall be provided to ensure that this information
remains proprietary by your employees, agents and other personnel that may have access to this document.
Revision:
Updated Hanbell Liquid Injection Piping
12/03/12
M. Schreiber / X. Beltran
ATTENTION: Step Control Loading Plate Design In RC2 Series
Added Revision Chart
12/06/12
05/24/13
06/13/13
6/18/13
11/04/14
7/30/15
8/27/15
11-16-16
04-18-17
11-27-17
M. Schreiber
M. Schreiber
K. Mitchell
X. Beltran
DEW
Update Manual to REV I
Added Hanbell Compressor Picture
Updated Hanbell Liquid Injection Piping
Update Manual to REV K
Updated Hanbell Liquid Injection Piping
Updated wiring of electrical power terminals
Added rotation of compressor
Hanbell with VFD ............................................................................................................................................. 26
Handling POE Oil Information .......................................................................................................................... 39
Warranty / Maintenance Information ................................................................................................................ 40
COMPRESSOR INSTALLATION & START-UP GUIDE
REVISION M
4
1.
Qty
Description
1
Stop Valve Assembly
bonnet
1
Discharge bushing connector
1
Suction bushing connector
1
Motor Terminal Junction Box Assembly
(refer to Figure 4-B)
Compressor Crate Unpacking & Inspection
1.1.
Inspect crate and compressor for any shipping
damage.
1.2.
The compressor is in an easy open crate, cut straps
and lift off crate top from base.
1.3.
Use either steel cable or safety ropes to lift the
compressor, see Figure 1. The cable should be
capable of holding up to a minimum of 2 tons.
Use caution while lifting the compressor
⇒Make sure that the steel cable does not touch the Solenoid Valves, Capillary, Oil Heater, Discharge
T
emperature Sensor and or Power Terminals, e tc. to prevent damage.
⇒ Use only steel cable or safety ropes to lift the compressor; make sure that the cabl e/r ope has the
pr
oper strength to lift the compressor.
⇒ Keep the compressor horizontal while lifting.
1.4.
Check compressor nameplate for correct model and voltage designation.
1.5.
To facilitate customer installation requirements, the parts listed in Table 1 are factory supplied in separate boxes
located in the compressor terminal box or packed in the compressor shipping container. Please verify that you
have received all accessory parts.
Table 1: Compressor Accessories & Service Valve Parts
Figure 1
Lifting Compressor with Steel Cable
1 stop valve, 2 gaskets, 1 charging valve, 4 bolts, 1 half union connector, 1 flare nut, 1 flare seal
Follow recognized safety procedures and practices.
2.2.
In order to prevent the penetration of moisture, air or impurities, the compressor has been charged with Nitrogen
gas. Do not remove any compressor bolts or fittings until the factory supplied holding charge has been relieved
2.3.
Do not apply any power to the compressor unless all valves are open and solenoids are energized (suction /
discharge, service valves, economizer and oil shut off valves).
2.4.
Do not operate or provide any electrical power to the compressor unless the terminal box cover is in place and
secured. Measurements of the current and voltage during running conditions must be taken at other points in the
power supply.
2.5.
Do not remove terminal box cover until all electrical sources have been disconnected.
WARNING: Failure to follow these instructions could result in serious personal injury.
3.
Installation Procedures
3.1.
Holding Charge: The screw compressor is factory supplied with 7 psig (0.5 bar) holding charge of nitrogen gas.
The internal pressure must be relieved before attempting to remove any compressor fittings or parts. Relieve the
holding charge by removing the threaded cap on the low pressure Schrader connection fitting and depressing
the internal Schrader stem.
CAUTION: This compressor may contain trace amounts of oil. Do not relieve the holding
charge or open th e c o mp resso r p ot s u nt i l i t i s re ad y t o b e co n n ect ed t o a closed dry system .
Excessive moisture may shorten compressor life.
3.2.
Installation of the Compressor Electr ical Terminal Box: Four bolts located on the top of the electrical terminal
box cover mount the electrical terminal box; it is adjustable to the cable hole direction to meet the power cables’
optional connection direction from the chiller.
3.3.
Oils: Adding and removing oil is done through the Drain valve located on the solenoid side of compressor. The
compressor has no oil and is not charged with oil. When adding or doing a complete change, use only the
listed Hanbell approved oils. POE oils readily absorb moisture and cause acid formation in the system.
Keep oil exposure to the atmosphere to a minimum.
3.4.
Installation of the Service/Stop Valve: Unpack the service/stop valve’s box then check against the list on the
outside of the box to ensure correct parts. Be sure that all parts inside the carton are clean. Use the four bolts to
secure the service/stop valve. Use PTFE sealer to seal the adapter while tightening it. Please refer to Figure 5-A
for space requirements for future service and maintenance needs.
3.5.
Service/stop Valve Recommended Connection
Figure 3-A RC2-100, 140 & 180
Figure 3-B RC2-170, 200~580 & 620
Figure 3-C RC2-610, 710~930
COMPRESSOR INSTALLATION & START-UP GUIDE
REVISION M
6
3.6.
Liquid Injection Solenoid Valve and Expansion Valve (Required, Not included with compressor): The
liquid injection system may be piped, but it is necessary to consider the required space for adjustment of the
expansion valve while testing or running the compressor. Please refer to installation guide in the following
section for connection points.
3.7.
PTC Discharge Temperature Protection: Each compressor comes standard with three PTC sensors in the
motor windings and one located at the discharge port. A motor module (INT69HBY) is installed in the electrical
terminal box. Refer to Figure 4-B showing the connection of motor and discharge PTCs in series to the motor
module corresponding terminal blocks.
4.
Recommended Liquid Injection Piping
Note A: It is necessary to adjust the Ball Valve to feed small amounts of liquid (drops) to the
compressor motor.
COMPRESSOR INSTALLATION & START-UP GUIDE
REVISION M
7
5.
Screw Compressor Wi rin g Procedures
Following the diagrams below will prevent damage to the electrical terminals and the
possibility of personal injury.
COMPRESSOR INSTALLATION & START-UP GUIDE
REVISION M
8
The method to tell the terminals (V-Phase)
1. By alphabet: Refer to the alphabet beside each terminal bolt in a star-delta motor.
2. By numbers: Refer to the number beside each bolt in a PWS motor.
Terminal
V2
COMPRESSOR INSTALLATION & START-UP GUIDE
REVISION M
9
Figure 5-A Motor Wiring
COMPRESSOR INSTALLATION & START-UP GUIDE
REVISION M
10
5.1.
Electrical Power Terminals
The power terminals of Hanbell compressors are made from ceramic materials and well insulated
more than 1000MΩ. Be careful connecting the wiring and follow the list below.
⇒ The ceramic part on the power terminal should not be tighten by hitting otherwise the insulation of
the power terminal could be degraded.
⇒ Follow the drawing shown below for the wiring to prevent the power terminal from being damaged.
⇒ The setting of the torque wrench for tightening the copper nut of the terminal bolts should be set less
than 500 kg-cm (36 pound/inch)
The insulation of the ceramic power terminals are very easily degraded by water, so DO NOT take
the leakage test by immersing the whole compressor in the water. Shut down the chiller first for
service if the insulation valve of the power terminal is lower than 5MΩ.
COMPRESSOR INSTALLATION & START-UP GUIDE
REVISION M
11
5.2.
Across the Line Jumper Bar Installation
Photo shows extra nuts installed under jumper bar for
clearance of power bolt Insulation.
Connect line voltage directly on Terminal post.
COMPRESSOR INSTALLATION & START-UP GUIDE
REVISION M
12
RED
ORANGE
RED
ORANGE
6.
Description - INT69HBY DIAGNOSE
Hanbell supplies INT69 HBY Diagnose for motor protection with monitoring functions of phase loss, phase
sequence, motor temperature, and discharge temperature. The module has built in flash codes that are helpful for diagnosing safety faults.
In order t o pr otect th e c om pr e s s or , e ac h RC 2 series compressor has been built with three PTC temperature
sensors inside the motor coil and one at the discharge port neck of the compressor. These sensors are connected to the motor module to monitor coil temperature and discharge temperature. Up to 9 sensors can be
connected in series and used with one module.
If the temperature in one of the positions monitored exceeds nominal response temperature of the respective
PTC thermistor (230° F, 4.5 ohms ±20%), the sensor resistance increases and the module trips (M1 and M2
open). The failure results in a lockout. The module resets when the response temperature drops 3kΩ(when
temp
decreases below 212°F, 2.75 ohms ±20%). 5 min delay for the first PTC failure, 60 min delay for the 2
ure, latching lockout for the 3
to prevent nuisance trips from brief reverse rotation.
Phase failure (loss) and Phase sequence safety trips result in a first time lockout. Phase sequence monitoring is active 1 second after motor start for 10 seconds. Phase loss is monitored 1 second after motor start till
motor stop.
nd
rd
within 24 hour period. Monitoring is inactive for 20 seconds after motor stop
fail-
Lockout and time delay can be cancelled by interrupting power to the module for 5 second’s. An optional
power supply reset button can be added to electrical connection box.
Flash Codes
COMPRESSOR INSTALLATION & START-UP GUIDE
REVISION M
13
Green lit
Compressor Operational
Green flashing
Compressor Running
Red/Orange flashing
Error, Compressor is switched off; for description see
table below
1st flashing sequence
(Red LED)
2nd flashing sequence
(Orange LED)
Description
1
1 Motor temperature;
ture exceeded
3
Motor temperature;
Reset delay after static switch off
4
Motor temperature;
circuit or short circuit
2
1
Motor voltage;
Incorrect phasesequence
2
Motor voltage;
Phase failure/asymmetry
3
1
General;
Supply voltage too low
5
General;
Reset delay after “General” error
Error
Active
Condition
Time delay
Motor temperature
Always
Rtrip 4,5kΩ ±20%
1. / 24h 5min 2. / 24h 60min
Operation cycle
Always
>3 switch off within 30s
5min
Phase sequence
1s after motor start for 10s
Locked out
Phase loss
1s after motor start till motor stop,
trips from brief reverse rotation.
Locked out
Flash Code Overview
Static switch off,
Permissible winding te mpera-
Sensor input detected open
static trip
Rreset 2,75kΩ ±20%
limitation
failure
monitoring is inactive for 20 seconds after
motor stop to prevent nuisance
3. / 24h locked out
Time delay starts after cooling down
Loading...
+ 28 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.