hamworthy Varmax 120 User guide

Document No. 00BNO9061-J / 06.06.2015
VARMAX
GAS CONDENSING BOILER
120 to 450 kW
with modulating burner
for natural gas and propane gas
FR EN DE ES IT NL
Installation,
use and
maintenance
instructions
MANUFACTURER:
00BNO3000-#
R
P
O
E
D
V
I
U
T
C
E
L
L
O
C
T
SITE DE PONT-DE-VAUX
1 route de Fleurville - BP 55
FR - 01190 PONT-DE-VAUX
VARMAX - Installation, Use and Maintenance
CONTENTS
1. WARNINGS AND RECOMMENDATIONS ..............................................................................6
1.1. Transport and storage ................................................................................................................................... 6
1.2. Symbols used in this document. ................................................................................................................... 6
1.3. Qualifi cation of personnel for installing, adjusting, using and maintaining the equipment ............................ 6
1.4. Safety instructions ......................................................................................................................................... 6
1.5. Water characteristics ..................................................................................................................................... 7
2. APPROVALS ........................................................................................................................10
2.1. Compliance with European Directives ........................................................................................................ 10
2.2. Regulatory installation conditions ................................................................................................................ 10
2.3. Gas category ............................................................................................................................................... 10
2.4. Gas supply pressures ................................................................................................................................. 11
3. TECHNICAL SPECIFICATIONS ...........................................................................................12
3.1. Dimensions ................................................................................................................................................. 12
3.2. Doorways .................................................................................................................................................... 14
3.3. Combustion at 15°C and 1013 mbar ........................................................................................................... 15
3.4. Conditions of use ........................................................................................................................................ 17
3.5. Electrical connection ................................................................................................................................... 17
4. INSTALLATION .....................................................................................................................18
4.1. Installation of the air fi lter and fi lter matting ................................................................................................. 18
4.2. Installing the boiler ...................................................................................................................................... 19
4.3. Opening / closing of casing doors ............................................................................................................... 20
4.4. Removing the control panel (MMI) .............................................................................................................. 20
4.5. Removing / refi tting the casing doors .......................................................................................................... 21
4.6. Removing / refi tting side panels .................................................................................................................. 22
4.7. Removing / refi tting the top panel ............................................................................................................... 22
4.8. Step ............................................................................................................................................................. 23
4.9.Changing the gas type (G20 to G31) ........................................................................................................... 24
4.10.Exhaust connection .................................................................................................................................... 26
4.11.Hydraulic connection .................................................................................................................................. 34
4.12.Gas connection ..........................................................................................................................................36
4.13.Electrical connection .................................................................................................................................. 36
Edition: 06 / 2015 Page 3 / 146
VARMAX - Installation, Use and Maintenance
5. COMMISSIONING .................................................................................................................40
5.1. Unlocking the boiler ..................................................................................................................................... 40
5.2. Pre-commissioning checks ......................................................................................................................... 40
5.3. Commissioning ............................................................................................................................................ 41
6. POST-COMMISSIONING CHECK ........................................................................................42
6.1. Condensate removal ................................................................................................................................... 42
6.2. Gas supply .................................................................................................................................................. 42
7. MAINTENANCE OPERATIONS ...........................................................................................43
7.2. Verifi cation of the boiler's environment ........................................................................................................ 44
7.3. Replacing the air fi lter matting ..................................................................................................................... 44
7.1. Boiler draining ............................................................................................................................................. 44
7.4. Verifi cation of ignition and ionisation electrodes ......................................................................................... 45
7.5. Siphon cleaning ........................................................................................................................................... 46
7.6. Checking the combustion circuit's gas-tightness ......................................................................................... 46
7.7. Checking combustion quality ...................................................................................................................... 47
7.8. Setting the gas valve ................................................................................................................................... 48
7.9. Gas fi lter cleaning ....................................................................................................................................... 50
7.10.Cleaning exchangers and changing seals .................................................................................................. 51
7.11.Cleaning the burner and changing the seals .............................................................................................. 53
8. END-OF-LIFE CYCLE OF THE APPARATUS ......................................................................56
8.1. Environmental compatibility ........................................................................................................................ 56
8.2. Dismantling, recycling and elimination of the apparatus ............................................................................. 56
9. HYDRAULIC DIAGRAMS AND SETTINGS .........................................................................57
9.1. Selection fl ow diagram ................................................................................................................................ 57
9.2. Symbols used in the diagrams .................................................................................................................... 59
9.3. List of diagrams ........................................................................................................................................... 59
10. LIST OF SPARE PARTS .....................................................................................................116
11. TABLE OF CUSTOMER SETTINGS ..................................................................................127
12. ANNEX A .............................................................................................................................144
Page 4 / 146 00BNO9061-J
VARMAX - Installation, Use and Maintenance
Edition: 06 / 2015 Page 5 / 146
VARMAX - Installation, Use and Maintenance
1. WARNINGS AND RECOMMENDATIONS
PLEASE READ THIS MANUAL CAREFULLY BEFORE INSTALLING, CARRYING OUT MAINTENANCE AND USING THE BOILER. IT CONTAINS IMPORTANT SAFETY INFORMATION.
VARMAX boilers are available with 2/3 tappings or 4 tappings. It is not
INFORMATION:
1.1. Transport and storage
possible to transform a version with 2/3 tappings into a version with 4 tappings and vice versa.
The boiler:
- must be stored vertically in an environment where the temperature is between -20°C and +55°C, and where relative humidity is between 5% and 95%;
- must not be stacked,
- must be protected from humidity.
1.2. Symbols used in this document.
INFORMATION: This symbol draws attention to comments.
Not following these instructions may lead to damage when installing or to other objects.
Not following these instructions may cause injuries and serious material damage.
Not following these instructions may cause electrocution.
!
!
WARNING:
DANGER:
DANGER:
1.3. Qualifi cation of personnel for installing, adjusting, using and maintaining the equipment
Boiler installation, adjustment and maintenance operations must be conducted by a qualifi ed and approved professional in accordance with prevailing local and national regulations. These operations may require work to be carried out with the power turned on and the casing doors (on the front of the boiler) open. Basic utilisation operations must be carried out with the casing doors closed.
1.4. Safety instructions
• Always switch the boiler off and shut off the general gas supply before carrying out any work on the boiler.
• After performing work on the boiler (maintenance or breakdown), check that there are no gas leaks from the installation.
Page 6 / 146 00BNO9061-J
!
!
DANGER:
DANGER:
DANGER:
VARMAX - Installation, Use and Maintenance
If you smell gas:
• Do not use a naked fl ame, do not smoke, do not turn on electrical contacts or switches.
• Cut off the gas supply.
• Air the premises.
• Look for the leak and repair it.
If you see smoke:
• Switch off the boiler.
• Air the premises.
• Look for the leak and repair it.
This boiler's earth bonding is ensured with connecting cables (green/ yellow) and specifi c attachment screws. During any dismantling work, make sure you reconnect the cables concerned; it is IMPERATIVE to reuse the original attachment screws.
1.5. Water characteristics
The following rules apply as soon as the boiler is commissioned and remain valid until the product's end-of-life.
DANGER: It is forbidden to use water containing glycol.
!
1.5.1. Preparation of the water circuit before commissioning the boiler
For all installation work (new or renovation), the water network pipes must be meticulously cleaned. The purpose of cleaning prior to commissioning is to remove germs and residues which are the cause of deposits. In new installations in particular, residue from grease, oxidised metal and even copper micro deposits must be removed. In renovated installations, cleaning should focus on removing sludge and the products of corrosion formed when the unit was last in operation. There are two types of methods for cleaning and removing sludge: a high intensity approach that takes a few hours and a slower, more gradual approach that takes several weeks. This fi rst type of cleaning must be done before connecting the new boiler, and with the second type, a fi lter should be installed on the back of the boiler to capture loosened deposits. Cleaning prior to commissioning helps to improve the equipment's performance, reduce energy consumption and fi ght against scaling and corrosion. This operation must be done by a professional (water treatment).
Edition: 06 / 2015 Page 7 / 146
VARMAX - Installation, Use and Maintenance
1.5.2. Protecting the unit against scaling
Water naturally contains dissolved calcium ions and carbonates that cause scaling (calcium carbonate) to form. To prevent excessive deposits, take
precautions with regard to the water used to fi ll the unit TH < 10°f
Water must be added during the life of the boiler. The new water adds scaling to the water system. The amount of fi ll water and the amount of make-up water added throughout the unit's lifecycle must not be more than three times the water capacity of the heating system. Also, the hardness of the make-up
water must be controlled. Make-up water: TH < 5°f
Adding a large amount of untreated water always contributes a signifi cant amount of scaling. To monitor this and to detect problems, a system water meter must be installed. Failure to comply with these guidelines (such that the fi ll water plus the make- up water is more than three times the water capacity of the heating system) requires a full cleaning (to remove sludge and scaling) to be performed.
Additional precautions are required for operation:
- When the unit has a water softener, the equipment must be inspected on a regular basis in order to ensure that it is not outputting chloride­rich water into the system. The concentration of chlorides must always remain below 50 mg/litre.
- To prevent the build-up of calcium deposits (such as on exchange surfaces), the unit should be brought into service slowly, starting by operating at a low power with high primary water fl ow.
- When the tap water lacks the desired qualities (e.g. high level of hardness), water treatment is required. The fi ll water must be treated, and whenever new water is added, the make-up water must also be treated.
- Installations with multiple boilers require all of the boilers to be started simultaneously at minimal power. Doing this prevents the calcium in the water from depositing on the exchange surfaces of the fi rst boiler.
- When working on the unit, avoid draining it completely; only the required parts of the system are to be drained.
The rules listed above are designed to minimise scaling on the exchange surfaces and thus to increase the life of the boilers. To optimise the equipment's operation, remove lime scale deposits. This must be done by a specialised company. Also, before putting the unit into service, verify that the heating system is not damaged (e.g. leaks). If it has excessive scaling, the unit's settings for operation and for water treatment must be adjusted.
1.5.3. Protecting steel and stainless steel boilers against corrosion
Corrosion can affect the iron components used in boilers and heating systems, which is directly related to the presence of oxygen in the water heater's water. Dissolved oxygen that enters the unit when it is being fi lled for the fi rst time reacts with the equipment materials and quickly disappears. Without refreshing the oxygen through signifi cant contributions of water, the unit might not experience any damage whatsoever. However, it is important to follow the sizing rules and installation guidelines in order to prevent oxygen from continuously fl owing into the heating water.
Page 8 / 146 00BNO9061-J
VARMAX - Installation, Use and Maintenance
These rules include:
- Opt for an expansion vessel with a membrane rather than an open expansion vessel that allows direct passage.
- Make sure pressure in the equipment is more than 1 bar when cold.
- Remove non-gas-tight components (permeable) and use gas-tight equipment instead.
If the guidelines above are followed, the unit's system water has the proper characteristics to last a long time: 8.2 < pH < 9.5 and concentration in dissolved oxygen < 0.1 mg/litre.
If there is a chance that oxygen could enter the unit, you must take additional precautions. Adding an oxygen scavenger (e.g. sodium sulphite) is highly recommended. We recommend you contact specialised companies for water treatment issues, which will be able to suggest:
- the appropriate treatment based on the characteristics of the installation,
- a monitoring and performance warranty contract.
For units in which the water comes into contact with heterogeneous materials, such as copper or aluminium, appropriate treatment is recommended in order to ensure that the unit will last. In most cases, this consists of adding corrosion inhibitors (in the form of chemical solutions) to the unit. It is recommended to contact water treatment specialists.
1.5.4. Unit monitoring
If the above recommendations are followed (new installation or renovation), it should be suffi cient to:
- check the amount of make-up water (fi ll water volume + make-up water volume < 3 times the unit volume.
- check the pH level (stable or slightly increasing).
- check the TH (stable or slightly decreasing).
We recommend these checks are carried out 2 to 3 times a year. Note that monitoring the quantity of make-up water is critical to the long life of the unit. If any of these three parameters deviates from the above recommendations, refer to a water treatment specialist to correct the problem.
1.5.5. Installation of the plate exchanger
If the recommendations above cannot be met, you can set up a plate exchanger to separate the primary system from the secondary system, which protects the boiler from undesirable effects.
1.5.6. Installation of a fi ltration system
A fi ltration system (fi lter, sediment well, etc.) on the back of the boiler is recommended in order to remove suspended particles from the unit.
Edition: 06 / 2015 Page 9 / 146
VARMAX - Installation, Use and Maintenance
2. APPROVALS
2.1. Compliance with European Directives
- Low voltage (2006/95/CE)
This appliance is not intended for use by persons (including children) whose physical, sensory or mental abilities are reduced, or persons without experience or knowledge, unless they have been able to benefi t, through someone responsible for their safety, from supervision or prior instruction concerning the use of the appliance. Children must be supervised to ensure they do not play with the appliance.
- Electromagnetic compatibility (2004/108/CEE)
- Gas appliances (2009/142/CE)
- Effi ciency (92/42/CEE) until 26/09/2015
- Eco-design (2009/125/EC): from 26/09/2015
In application of the directive and according to the requirements of the EU regulation No. 813/2013 of 02 August 2013, the technical parameters of condensation boilers with a power of less than or equal to 400 kW are available in appendix A.
2.2. Regulatory installation conditions
The appliance must be installed by an approved professional in accordance with regulations and current professional practices.
2.3. Gas category
This boiler has been adjusted in the factory to work with group H (type G20) natural gas with a supply pressure of 20 mbar.
INFORMATION: Any work on a sealed element leads to loss of warranty.
VARMAX 120 to 225
VARMAX 275 to 320
VARMAX 390 to 450
B23 - B23 P
C13 - C33 - C53
B23 - B23 P
C53
B23 - B23 P
C53
Category
DK, EE, FI, HU, LV, NO, SE, TR
I
2H
I
2H
I
2H
CZ, GR, GB, IE,
LT, RO, SI, SK
II
2H3P
I
2H
II
2H3P
I
2H
I
2H
Page 10 / 146 00BNO9061-J
2.4. Gas supply pressures
INFORMATION: The pressures given below must be read at the gas valve inlet.
VARMAX - Installation, Use and Maintenance
Natural gas H G20
20 mbar
G31 Propane gas
(for relevant models
and countries only)
Nominal pressure (mbar) 20 37
Minimum pressure (mbar) 17 25
Maximum pressure (mbar) 25 45
Edition: 06 / 2015 Page 11 / 146
VARMAX - Installation, Use and Maintenance
3. TECHNICAL SPECIFICATIONS
3.1. Dimensions
A
ø AA
B
F
45 mini
60 maxi
S
R
D
E
T
ø
C
ø U
G
ø V
ø W ø X
L
ø X
Condensate removal
HI
J
K
ø X
ø X
ø U
Y
Z
R
L
(B23-B23P)
Q
P
O
M
N
U0501956-#
gure 1 - Dimensions
Page 12 / 146 00BNO9061-J
VARMAX - Installation, Use and Maintenance
MODELS
120 140 180 225 275 320 390 450
A (mm) 734 734 812 912
B (mm) 1530 1780 1877 2023
C (mm) 1189 1218 1341 1392
D (mm) 148 169 169 168
E (mm) 103 150 109 92
F (mm) 510 630 680 750
G (mm) 138,5 138,5 138,5 138,5
H (mm) 115 192 241 274,5
I (mm) 350,5 350,5 399,5 449,5
J (mm) 150,5 150,5 200 209,5
K (mm) 166,5 150,5 179 192
L (mm) 1256 1564 1672 1874
M (mm) 165 165 165 165
N (mm) 182 197,5 196,5 206,5
O (mm) 926 1171 1265 1402
P (mm) 1062 1315 1413 1577,5
Q (mm) 1298 1606 1661 1933
R (mm) 212 212 244 244
S (mm) 163 163 163 183
Ø T(*): Smoke outlet (mm) 150 150 180 200
Ø U: Purge connecting sleeve 1 " 1 " 1 " 1 "
Ø V(*): Air inlet (mm) 150 150 180 180
Ø W: Gas connecting sleeve G20
G31
1 " 1/4 1 " 1/4
1 " 1/2 1 " 1/2
2 " 2 "
2 "
--
Ø X: Out / In connecting sleeve 2 " DN 65 DN 80 DN 80
Y (mm) 250,5 247 276 289,5
Z (mm) 237 224,5 270,5 283,5
Ø AA: Valve connecting sleeve 1 " 1 " 1 " 1/4 1 " 1/4
(*) The diameter indicated is the inside diameter (only for Ø T and Ø V).
Edition: 06 / 2015 Page 13 / 146
VARMAX - Installation, Use and Maintenance
3.2. Doorways
VARMAX 120 to 225 boilers fi t through doors 700 mm wide with the casing on (boiler with doors and side jackets).
VARMAX 275 to 320 boilers fi t through doors 735 mm wide without the casing on (boiler without doors, without side jackets and without side insulating panels). However, it is possible to pass through the 700 mm doors if the following parts are removed, in addition to the parts mentioned above:
• the two inspection doors with their 16 fastening clamps,
• the two lower hinge lugs of the front housing doors (with the step),
• the two upper hinge lugs of the front housing doors (with the step),
• all the cable clamps at the inlet of the high- and low- current wiring gutter.
VARMAX 390 to 450 boilers fi t through doors 800 mm wide without the casing on, which means that the following parts must be removed:
• the two front housing doors,
• the side insulating jackets,
• the side insulating panels
• the two lower hinge lugs of the front housing doors (with the step),
• the two upper hinge lugs of the front housing doors (with the step),
• all the cable clamps at the inlet of the high- and low- current wiring gutter.
Page 14 / 146 00BNO9061-J
3.3. Combustion at 15°C and 1013 mbar
3.3.1. G20 Natural Gas
120 140 180 225 275 320 390 450
VARMAX - Installation, Use and Maintenance
MODELS
Nominal power Pn (80/60°C)
Nominal power when condensing P (50/30°C)
kW 117 136 175 219 268 312 381 439
kW 127 148 191 238 290 338 415 478
Nominal heat input Qn kW 120 140 180 225 275 320 390 450
Minimum heat input Qmin
Gas fl ow rate at Pn m
CO
value ranges %
2
Flue-gas mass fl ow rate at Qn / Qmin (80/60°C)
Flue-gas mass fl ow rate at Qn / Qmin (50/30°C)
Flue-gas temperature at Qn / Qmin (80/60°C)
Flue-gas temperature at Qn / Qmin (50/30°C)
Appliance pressure at nominal Qcal (B23)
Inside diameter of fl ue- gas output
Maximum allowable nozzle pressure (B23P) at Qn / Qmin (80/60°C)
Maximum allowable nozzle pressure (B23P) at Qn / Qmin (50/30°C)
Combustion air fl ow rate at Qn
kW 28 28 43 43 66 66 87 87
3
/h 12,7 14,81 19,05 23,81 29,1 33,86 41,3 47,6
g/s
g/s
°C
°C
52,8 / 1361,3 /
13,1
49,1 /
12,3
60,8 /
56,9
35,7 /
28,8
57,6 /
12,2
62,1 /
57,3
37,7 /
30,2
Qmin : 8,3 % < CO
Qmax : 8,8 % < CO
80,4 /
20,8
75,9 /
19,5
61,0 /
56,6
33,7 /
30,0
99,5 /
21,1
93,0 /
19,5
62,3 /
57,7
36,9 /
30,2
< 8,7 %
2
< 9,2 %
2
113,9 /
26,9
108,7 /
17,1
61,7 /
58,3
36,3 /
29,8
133,2 /
29,1
126,3 /
27,1
63,4 /
57,2
36,2 /
28,3
169 /
39,2
159,6 /
36,7
62,5 /
57,4
200,7 /
35,6
191 /
33,4
64,8 /
57,1
36,7 / 3041,7 /
30,2
Pa 88 108 103 147 132 162 152 203
mm 150 150 150 150 180 180 200 200
Pa
Pa
m
200 /5200 / 5115 /5165 /5122 /
5
166 /5164 /
5
3
/h 153,8 179,4 230,7 288,3 352,4 410,1 499,8 576,7
92 /
5
128 /
5
97 /
5
176 /5180 /5193 /
5
145 /5155 /5173 /
5
NOx class 5
Flue-gas removal and air inlet type classifi cations
Edition: 06 / 2015 Page 15 / 146
B23, B23P
C13, C33, C53
B23, B23P
C53
VARMAX - Installation, Use and Maintenance
3.3.2. G31 Propane Gas (for relevant models and destination countries)
MODELS
120 140 180 225 275 320
Nominal power Pn (80/60°C) kW 117 136 175 219 268 312
Nominal power when condensing P (50/30°C)
kW 127 148 191 238 290 338
Nominal heat input Qn kW 120 140 180 225 275 320
Minimum heat input Qmin kW 39 39 63 63 90 90
Gas fl ow rate at Pn m
CO
value ranges %
2
Flue-gas mass fl ow rate at Qn / Qmin (80/60°C)
Flue-gas mass fl ow rate at Qn / Qmin (50/30°C)
Flue-gas temperature at Qn / Qmin (80/60°C)
Flue-gas temperature at Qn / Qmin (50/30°C)
3
/h 4,91 5,73 7,36 9,21 11,25 13,09
g/s
g/s
°C
°C
53 /
18,3
50,2 /
17,3
60,3 /
56,7
34,6 /
30,6
Qmin : 9,8 % < CO
Qmax : 10,4 % < CO 61,8 /
18,3
58,7 /
17,3
62,6 /
56,7
37,1 /
80 /
29
80 /
28
60,3 /
57,1
37,1 / 3137 /
28,9
< 10,2 %
2
< 10,8 %
2
100 /29122 /42142 /
96 /
117 /39136 /
28
62,2 /
63 / 5865,4 /
57,6
40 /2941,4 /
29,4
42
40
58,4
31,3
Appliance pressure at nominal Qcal (B23) Pa 68 95 102 140 123 165
Inside diameter of fl ue-gas output mm 150 150 150 150 180 180
Maximum allowable nozzle pressure (B23P) at Qn / Qmin (80/60°C)
Maximum allowable nozzle pressure (B23P) at Qn / Qmin (50/30°C)
Pa
Pa
167 / 12200 /8103 /4136 / 7118 / 11157 /
11
140 / 16169 / 1166 /
7
104 /7104 / 16138 /
13
Combustion air fl ow rate at Qn m3/h 153,8 179,4 230,7 288,3 352,4 410,1
NOx class 5
Flue-gas removal and air inlet type classifi cations
B23, B23P
Page 16 / 146 00BNO9061-J
VARMAX - Installation, Use and Maintenance
3.4. Conditions of use
MODELS
120 140 180 225 275 320 390 450 Maximum start setting temperature °C 85 Start maximum temperature °C 88 Safety temperature °C 110
Maximum service pressure
Minimum cold pressure
hPa
(bar)
hPa
(bar)
Hydraulic pressure loss at T20
version with 2 or 3 tappings 600 750 570 810 820 1185 770 970 version with 4 tappings
Main exchanger
Condenser Nominal water fl ow rate (P/20) m Maximal water fl ow rate (P/10) m
daPa
500 110
3
/h 5,0 5,8 7,5 9,4 11,5 13,4 16,4 18,9
3
/h 10,0 11,6 15,0 18,8 23,0 26,8 32,8 37,8
650 120
440556607579050106065660
Water content L 116 116 151 151 239 239 287 287 Weight without water kg 340 340 393 393 502 502 592 592 Sound power at P Sound power at 1 m at P Temperature of installation room
(min. / max.)
(Lw) * dB(A) 80 76 77 84
max
(Lp) * dB(A) 65 61 61 68
max
°C 5 / 45
Relative humidity of installation room between 5% and 95% Protection level IP20 Maximum altitude of installation m 2000
6000
(6)
1000
(1)
190
840 230
* The sound power level is a laboratory measurement of the emitted sound power but contrary to the noise level, it doesn't correspond to the perceived measurement.
3.5. Electrical connection
MODELS
120 140 180 225 275 320 390 450 Electrical supply V 230 V AC (+10% -15%), 50Hz Electrical power consumption at Qn
(without accessories) Electrical power consumption in
standby mode
Max length of sensor cables
Power terminal output
W 204 311 179 320 238 352 480 660
W5
DHW sensor: 10
m
External sensor: 40 in 0.5 mm² (120 in 1.5 mm²)
Ambient thermostat: 200 in 1.5 mm²
Ambient sensor: 200 in 1.5 mm²
V 230V AC (+10%, -15%)
A 5 mA - 1A
Edition: 06 / 2015 Page 17 / 146
VARMAX - Installation, Use and Maintenance
4. INSTALLATION
Manipulation of the boiler using a hoist requires the use of a frame
!
DANGER:
4.1. Installation of the air fi lter and fi lter matting
(not supplied). This is COMPULSORY. Refer to the label stuck onto the boiler's packaging.
!
protective label
WARNING:
If connecting CHIMNEY B23 or B23P, it is COMPULSORY to fi t the air lter supplied with the boiler.
screws (x4)
gure 2 - Air fi lter
air fi lter
- Remove the protective "air intake" label.
- Insert the air fi lter and attach it to the boiler using the 4 screws supplied with the fi lter.
U0502530-#
Models 120 to 320:
Models 390 and 450:
gure 3 - Filter matting
U0038318-B
mountings
U0024791-B
All models:
- Insert the rectangular lter matting between the lter's protective grille and the mounting (see
opposite).
Ensure that the link between both ends of the matting is under one of the mountings.
Models 390 and 450:
- Insert the square fi lter cloth on the back gate of the fi lter.
Page 18 / 146 00BNO9061-J
4.2. Installing the boiler
VARMAX boilers must not be installed on an in ammable surface (wooden oor, plastic fl oor covering, etc.).
Recommended distances from walls and the fl oor:
Ensure there is suffi cient clearance so that work may be carried out easily on the boilers. The minimum values (in mm) are indicated in fi gure 4 and in the table below.
VARMAX - Installation, Use and Maintenance
ABCDH 120 450 500 150 140 450 500 150 180 450 500 320 225 450 500 320 275 450 600 500 263
MODELS
320 450 600 500 263 390 450 700 500 427 450 450 700 500 427
A
D
H
B
C
00BET9005-#
gure 4 - Peripheral clearance
The hashed zone above the boiler must remain free of obstacles to allow for inspections and cleaning of the burner.
!
WARNING:
A 2 cm free space must also be left above the side panels to allow for their disassembly and reassembly.
These values cannot be replaced by specifi c regulatory requirements.
The boiler must be positioned horizontally using a spirit level to
!
Edition: 06 / 2015 Page 19 / 146
WARNING:
promote effective ventilation of the heat exchanger (use the base as a reference surface).
To adjust the level, screw or unscrew the 4 adjustable feet as required using a 17 mm wrench.
VARMAX - Installation, Use and Maintenance
4.3. Opening / closing of casing doors
Opening:
Put the handle locking system in a horizontal
position (mark 1) then press down on it.
The handle is released from its housing; you can
now open the right-hand door, followed by the left-
hand door.
Closing:
Close the left-hand door, followed by the right-
hand door.
Press the door's lever.
U0503482-#
gure 5 - Opening casing doors
4.4. Removing the control panel (MMI)
Put the handle locking system in a vertical position
(mark 1).
The control panel (MMI: Man Machine Interface)
may be removed from the casing door to:
• remove the left-hand casing door;
• view the display when setting or carrying out maintenance work on the boiler;
Open the casing doors.
Remove the locking screw back of the left-hand casing door.
accessible on the
gure 6 - Unlocking the control panel
Page 20 / 146 00BNO9061-J
VARMAX - Installation, Use and Maintenance
You can:
• put the control panel back
fi t the control panel to the boiler (see opposite,
gure 7 - Positions of the control panel
4.5. Removing / refi tting the casing doors
With the doors open, remove the pin on the top of the door to be removed.
-
-
or carrying out maintenance), or
so that the left-hand casing door can be removed without any risk to the control panel).
(to view data displayed when adjusting
in its place
pin
Support the door during this operation because once the pin has been removed, the door is no longer attached to the boiler.
When refi tting, fi rstly position the bottom of the door on the lug, and then the top, making sure to fully insert the pin into its housing.
lug
U0502515-#
gure 8 - Removing casing doors
!
Edition: 06 / 2015 Page 21 / 146
WARNING:
Before removing the left-side casing door, do not forget to remove the control panel (see next paragraph).
VARMAX - Installation, Use and Maintenance
4.6. Removing / refi tting side panels
locking screw
Open the casing doors.
Remove the locking screw accessible via the inside of the boiler.
Use the handle in the centre of the panel for this.
Lift up the panel vertically and remove.
When refi tting, re-fasten the locking screws from inside the boiler after fi tting the panels.
handle
rear side panel
U0501963-#
gure 9 - Removing side panels
4.7. Removing / refi tting the top panel
removable part
Note: It may be necessary to remove the rear side
panels in order to fi t through doors. To do this, unscrew the fi xing screws which hold the panel onto the boiler's structure and remove the panel.
Open the casing doors.
Loosen the 2 thumbscrews on the top of the boiler (1 or 2 turns will be enough. It is not necessary or recommended to unscrew them completely).
Slightly lift up the panel and remove it from the front.
To refi t it, follow the procedure in reverse.
U0502250-#
gure 10 - Removing the upper panel
Page 22 / 146 00BNO9061-J
4.8. Step
gure 11 - Installing the step
VARMAX - Installation, Use and Maintenance
!
WARNING:
The step is a means to access the burner. It cannot be used as a work platform.
There are steps on models 180 and above.
On models 180 to 320:
Open the doors.
Unfold the step.
U0502519-#
gure 12 - Installing the step on models 180-320
On models 390 and 450:
Open the doors.
Remove the blocking element of the step
Unfold the step.
Pull the lower step.
blocking element of the step
U0502519-#
gure 13 - Installing the step on models 390 and 450
Edition: 06 / 2015 Page 23 / 146
VARMAX - Installation, Use and Maintenance
4.9. Changing the gas type (G20 to G31)
The boiler has been adjusted in the factory to work with group H (type G20) natural gas with a supply pressure of 20 mbar.
INFORMATION:
Its adaptation to suit any other type of gas must take place in compliance with the regulations in effect in the country in which the appliance is installed.
!
!
WARNING:
WARNING:
Any operations involving changing the type of gas used must be performed by a qualifi ed professional.
ONLY for relevant boilers (see paragraph 2.6, page 13) and boilers connected to B23 and B23P.
4.9.1. Changing prepurging, ignition, minimum and maximum speeds
Place the boiler in standby mode (see § 3.3.1 of the NAVISTEM B3000 boiler command table instructions).
If necessary, press the ESC button to return to the main screen.
Access the Settings menu.
Adjust the prepurging speed (9504), ignition speed (9512), minimum speed (9524) and maximum speed (9529) settings:
Models Gas 9504 9512 9524 9529
120
140
180
225
275
320
G20 1690 6490 G31 2040 5800 G20 1690 7460 G31 2040 6800 G20 2390 2390 1280 4410 G31 2575 2575 1640 4240 G20 2390 2390 1280 5400 G31 2575 2575 1640 5060 G20 1360 4620 G31 1700 4500 G20 1360 5450 G31 1700 5300
Page 24 / 146 00BNO9061-J
4.9.2. On VARMAX 120, 140, 275 and 320
VARMAX - Installation, Use and Maintenance
The type of gas is changed by installing the diaphragm (brass part) provided with the boiler (engraved B1P for 120 and 140 models or engraved B3P for 275 and 320 models).
Unscrew the 4 nuts or screws depending on the model (see opposite). Install the diaphragm provided. Screw the 4 nuts back in place.
nut (x4)
gure 14 - Diaphragm (120 and 140 models)
diaphragm
U0524542-#
Check the CO
settings (see § 7.7, page 52).
2
After changing the type of gas:
- Check the sealing of the gas line.
- Stick the label provided in place of the
original label (G20).
Note: In order to facilitate the operation, the mounting ange located at the entrance to the gas line (on the side nearest the network connection) may require unscrewing.
nut (x4)
diaphragm
U0503708-#
gure 15 - Diaphragm (275 and 320 models)
Edition: 06 / 2015 Page 25 / 146
VARMAX - Installation, Use and Maintenance
4.9.3. On VARMAX 180 and 225
The type of gas is changed by replacing the diaphragm located on the gas line.
Unscrew the 4 nuts (see opposite), then remove the diaphragm in place (brass part). Replace this with that provided with the boiler (engraved B2P). Screw the 4 nuts back in place.
diaphragm
gure 16 - Diaphragm
4.10. Exhaust connection
Exhaust system works and national and prefectoral regulations must be complied with.
A smoke temperature sensor guarantees the protection of exhaust ducts for type B and C combustion products.
nut (x4)
U0503708-#
Check the CO
After changing the type of gas:
- Check the sealing of the gas line.
- Stick the label provided in place of the
original label (G20).
Note: In order to facilitate the operation, the mounting ange located at the entrance to the gas line (on the side nearest the network connection) may require unscrewing.
settings (see § 7.7, page 52).
2
VARMAX boilers are approved to be connected to:
• a B23 chimney (all models)
• a B23P chimney (all models)
• a C13 air vent (models 120 to 225) except for propane gas (G31)
• a C33 air vent (models 120 to 225) except for propane gas (G31)
• a C53 air vent (all models) except for propane gas (G31)
The lengths of the ducts provided below are in linear metres (lm). The total
INFORMATION:
length of all ducts is reduced to a straight length (elbows having a straight equivalence).
4.10.1. Connection to a B23 chimney
Type B23 connection:
Air from the unit's premises, extraction of gases through the roof via a fl ue with natural ventilation.
Check that there are top and bottom ventilations in the boiler premises,
!
WARNING:
that they comply with applicable regulations and that they are not obstructed.
Page 26 / 146 00BNO9061-J
VARMAX - Installation, Use and Maintenance
Chimney fl ues must be dimensioned considering the combustible gas pressure at the boiler outlet of 0 Pa (see table § 3.3, page 15).
The fl ue-gas extraction ducts must be made in a material resistant to the condensate that can form when the boiler is operating. These materials
must also be capable of supporting temperatures up to 120°C. Horizontal duct runs must be avoided so as not to cause condensate retention.
Check that the fuel gas is extracted via a gas-tight duct.
VARMAX boilers are effi cient boilers with very low fl ue-gas temperatures; as a result, to maintain favourable ventilation, the ducts must run upwards from the boiler outlet.
If several boilers are connected to a single fl ue, check:
1. that the fl ue is not under pressure when all the boilers are in
!
IMPORTANT:
operation.
2. If one of the boilers is operating at minimum power, that the others do not discharge into it.
Sizing recommendations based on a POUJOULAT system (Condensor type):
ø duct
H
ø connection
3 m
gure 17 - B23 sizing recommendations
Edition: 06 / 2015 Page 27 / 146
VARMAX - Installation, Use and Maintenance
Height of ue-gas duct H in linear metres (lm)
(operating at 50/30°C)
ø
connection
ø
duct
Type of gas G20 G31 G20 G31 G20 G31 G20 G31 G20 G31
120 2 to 52 -- -- 3 to 39 -- -- -- -- -- -­140 7 180 -- -- 10 225 -- -- -- -- 1 275 -- -- -- -- -- -- 4
MODELS
320 -- -- -- -- -- -- 5 390 -- -- -- -- -- -- -- -- 2 450 -- -- -- -- -- -- -- -- 2
180 mm 200 mm 250 mm 250 mm 300 mm
to 39 -- 3 to 94 4 to 38 -- -- -- -- -- --
150 mm 180 mm 200 mm
to 29 -- 1 to 100 4 to 73 -- -- -- --
to 100 3 to 65 -- -- -- --
to 99 4 to 61 -- -- to 81 6 to 53 -- --
to 100 -- to 100 --
!
!
IMPORTANT:
IMPORTANT:
The above values are provided for information purposes only. It is important to check them with a calculation.
The weight of fl ue-gas ducts must not be supported by the part connecting to the boiler.
4.10.2. Connection to a B23P chimney
Type B23P connection:
Air coming from the boiler premises, extraction of gases through the roof via a pressurised duct.
Check that there are top and bottom ventilations in the boiler premises,
!
!
WARNING:
IMPORTANT:
that they comply with applicable regulations and that they are not obstructed.
For the B23P type connection, it is MANDATORY to use ducts which have pressurised duct certifi cation, such as CONDENSOR (Poujoulat) or rigid or fl exible CHEMILUX CONDENSATION (Ubbink).
The duct extracting combustion products must be sized using the parameters provided in the table in paragraph 3.3. Depending on the duct's actual confi guration, a calculation is
!
Page 28 / 146 00BNO9061-J
IMPORTANT:
necessary to check that the pressures at the boiler outlet do not exceed the maximum normative values authorised (200 Pa). Values corresponding to the 50/30°C regime are to be used for this calculation.
VARMAX - Installation, Use and Maintenance
Cascade installation case
In this case, where boilers with different powers are connected, the most powerful models must be closest to the chimney.
The boiler is equipped with an internal check valve smoke diverter, replacing any other external and functionally identical system.
Sizing recommendations on the basis of a POUJOULAT system (Condensor type):
ø duct
H
ø connection
3 m
gure 18 - B23P (Poujoulat) sizing recommendations
Height of ue-gas duct H in linear metres (lm)
(operating at 50/30°C)
ø
connection
ø
duct
Type of gas G20 G31 G20 G31 G20 G31 G20 G31
120 79 60 -- -- -- -- -- -­140 87 39 -- -- -- -- -- -­180 -- -- 74 23 -- -- -- -­225 -- -- 69 20 -- -- -- -­275 -- -- -- -- 100 73 -- --
MODELS
320 -- -- -- -- 100 64 -- -­390 -- -- -- -- -- -- 100 -­450 -- -- -- -- -- -- 100 --
130 mm 150 mm 180 mm 200 mm
150 mm 180 mm 200 mm
!
!
Edition: 06 / 2015 Page 29 / 146
IMPORTANT:
IMPORTANT: The weight of fl ue-gas ducts must not be supported by the boiler.
The above values are provided for information purposes only. It is important to check them with a calculation.
VARMAX - Installation, Use and Maintenance
Sizing recommendations on the basis of a UBBINK system:
Using a Ubbink duct in PPTL (reference 041432) at the boiler outlet.
gure 19 - B23P (Ubbink) sizing recommendations
ø160 requires a Male 150 / Female 160 adaptor
ø 160
H
ø 160
Height of ue-gas duct H in linear metres (lm)
(operating at 50/30°C)
ø
duct
Type of gas G20 G31 G20 G31
120 100 100 100 86
140 100 100 86 65
MODELS
!
!
IMPORTANT:
IMPORTANT: The weight of fl ue-gas ducts must not be supported by the boiler.
The above values are provided for information purposes only. It is important to check them with a calculation.
180 64 32 30 --
225 58 40 28 --
rigid fl exible
160 mm
4.10.3. Rules for installing air vent terminals
Please refer to national standards and regulations.
Page 30 / 146 00BNO9061-J
4.10.4. Connection to a C13 or C33 air vent
Type C13 connection:
Air inlet and gas extraction via separate ducts connected to a horizontal concentric terminal (air vent).
Type C33 connection:
Air inlet and gas extraction via separate ducts connected to a vertical concentric terminal.
Connecting a VARMAX boiler in C13 or C33 confi guration requires use of
!
IMPORTANT:
the "Terminal kit" comprising a terminal, a dual-fl ow adaptor and a male adaptor
ø150 / female adaptor ø160 (reference 041421).
VARMAX - Installation, Use and Maintenance
Ensure the slope from the concentric terminal is 3°.
L2
ø160 ø150
L1
gure 20 - Type C13 connection gure 21 - Type C33 connection
450 mm maxi
U0501471-#
450 mm maxi
ø160
ø150
L1
L2
U0501398-#
The table below shows the maximum straight lengths authorised for air and ue-gas ducts.
MODELS
120 140 180 225
L1 (air) 16.5 lm 13.5 lm
L2 (fl ue-gases) 17.5 lm 14.5 lm
The lengths indicated include the lengths of the concentric terminal.
Edition: 06 / 2015 Page 31 / 146
VARMAX - Installation, Use and Maintenance
In addition, in the duct length calculation, the following equivalences must be used;
- 90° elbow = 1.5 m of straight duct
- 45° elbow = 0.8 m of straight duct
The terminal's installation must comply with the rules in § 4.10.3, page 30.
To facilitate mounting of fl ue-gas ducts (PPTL), coat the joints with liquid soap or a suitable grease (provided in the "terminal kit").
!
IMPORTANT:
The weight of the ducts (air and fl ue-gas) must not be supported by the boiler's connecting parts.
4.10.5. Connection to a C53 air vent
Type C53 connection:
Air inlet and gas extraction via 2 separate ducts.
!
IMPORTANT:
Connecting a VARMAX boiler in a C53 confi guration requires the use of accessory kits.
The table below gives the reference of the available kits depending on the boiler model and the maximum straight lengths authorised for the air and ue-gas ducts.
MODELS
120 140 180 225 275 320 390 450
Accessory kit reference 041422 041422 041423 041424
L1 (air) 10 lm 8 lm 10 lm 10 lm
L2 (fl ue-gas) 40 lm 39 lm 40 lm 40 lm
ø A (air duct) ø F ( ue-gas duct)
The lengths given include the lengths of the fl ue-gas terminal but do not include the air terminal (measure taken on the outside of the wall).
In addition, in the duct length calculation, the following equivalences must be used;
For ducts with diameters 150 mm and 160 mm:
- 90° elbow = 1.5 m of straight duct
- 45° elbow = 0.8 m of straight duct
For ducts with diameters 180 mm and 200 mm:
- 90° elbow = 2 m of straight duct
- 45° elbow = 1.1 m of straight duct
150 mm 150 mm 180 mm 180 mm
160 mm 160 mm 180 mm 200 mm
Page 32 / 146 00BNO9061-J
VARMAX - Installation, Use and Maintenance
The fl ue-gas terminal's installation must comply with rules in § 4.10.3, page
30.
Ensure the slope towards the boiler is at least 3° (fl ue-gas side). On the air duct side, adjust a slope to the outside to avoid the risk of rainwater in the boiler.
To facilitate mounting fl ue-gas ducts for models 120 to 225, coat the joints in liquid soap or a suitable grease (provided in the "terminal kit").
450 mm maxi
øF
L1
L2
øA
450 mm maxi
450 mm maxi
øF
L2
450 mm maxi
L1
øA
U0501350-#
gure 22 - Type C53 connection (VARMAX
models 120 to 225)
!
Edition: 06 / 2015 Page 33 / 146
IMPORTANT: The weight of fl ue-gas ducts must not be supported by the boiler.
gure 23 - Type C53 connection (VARMAX
models 275 to 450)
U0501496-#
VARMAX - Installation, Use and Maintenance
4.11. Hydraulic connection
The presence of an integrated irrigation pump in the boiler and an intelligent control logic enables optimal operation up to IUP/30 (IUP = Instant Useful Power expressed in Th/h - 1Th/h = 1.163 kilowatts). Below this throughput of IUP /30, the boiler will continue to operate, but will gradually lose power (boiler stops below IUP /46). In connector sleeves 3 and 4, there is no minimum throughput constraint on the condenser. In the main heat exchanger, as in the condenser, you must ensure that you never exceed the throughput prescribed in section 3.4 (boiler nominal useful power / 10).
Sizing the pipes connecting the boiler to the installation must be done carefully, to minimise the pressure losses and so avoid oversized circulating pumps. In some cases the diameter of the connection pipes will be greater than the diameter of the boiler tappings. The diameter can then be usefully increased after the union connectors, the stop valves, and/or the hydraulic balancing valves. VARMAX boilers are equipped with the following elements:
• main exchanger drain valve,
• condenser drain valve.
It is mandatory to fi t the boiler and its installation with the following elements:
• isolating valves on the fl ow and return tappings,
• an expansion vessel,
• an effi cient bleed device,
• a safety valve set to 6 bar,
• A shut-off on the boiler's fi ll circuit in relation to the main supply.
VARMAX boilers are available with 2/3 tappings or 4 tappings. It is not possible to transform a version with 2/3 tappings into a version with 4 tappings and vice versa.
4.11.1. Boiler with 2 or 3 tappings
Clamp obstructing
2nd return
Flow
2 tappings
If all the circuits have the same return temperatures, the return tapping located in the lower part must be used.
Return
U0501961-#
gure 24 - Connection with 2 tappings
Page 34 / 146 00BNO9061-J
Flow
nd
return
2
hot return (high tem­perature circuit)
VARMAX - Installation, Use and Maintenance
3 tappings
VARMAX boilers are fi tted with 2 returns and an optimised internal water circuit allowing effective separation of high temperature returns (coming from DHW preparation circuits, radiators, etc.) from low temperature circuits (underfl oor heating circuits, low temperature radiator circuits, etc.). This circuit separation encourages the condensation of fl ue-gases in the lower part of the condenser throughout the year, and therefore considerably increases the boiler's performance.
cold return (underfl oor heating and low temperature radiators)
gure 25 - Connection with 3 tappings
4.11.2. Boiler with 4 tappings
1st return
U0501961-#
Main exchanger
ow
Condenser fl ow
To use the 2
nd
return, the clamp obstructing the
tapping must be removed.
VARMAX boilers are fi tted with 2 internal water circuits allowing separation of high temperature returns (coming from DHW preparation circuits, radiators, etc.) from low temperature circuits (underfl oor heating circuits, low temperature radiator circuits, etc.).
main exchanger return
Condenser return
gure 26 - Connection with 4 tappings
!
WARNING:
Do not connect DHW (domestic hot water) or swimming pool water to the condenser circuit.
In some installations, additional improvement may be obtained using 4 tappings. This separates the condenser (low temperatures) from the main exchanger (high temperatures).
There are no throughput constraints regarding the condenser.
U0501961-#
Edition: 06 / 2015 Page 35 / 146
VARMAX - Installation, Use and Maintenance
4.11.3. Condensate removal
Removal to the drains, via a drain hopper, using a P.V.C tube (minimum diameter 32 mm) is mandatory because the condensates are acidic and thus aggressive (pH between 3 and 5). Use a suffi cient slope of 3% to ensure correct fl ow of the condensates.
!
WARNING:
4.12. Gas connection
Neutralise these condensates before removal according to regulations in force.
Before installing the boiler, it is necessary to clean the inside of the installation's gas line (metallic particles, soldering residue, etc.). This helps to improve the product's longevity. Before commissioning the boiler, check that the natural gas supply pressure corresponds to the boiler's nominal pressure mentioned on the identifi cation plate. Before feeding gas to the installation, ensure that the different connections are correctly made and gas tight.
In particular, check the presence of a removable connector between the isolating valve and the boiler gas supply tapping. The value read at the gas valve input must be between the limits indicated in the table in chapter 2.5, page 11 for the type of gas used.
The boiler's gas line connection must not be subject to any mechanical
!
WARNING:
stress (risk of loss of gas tightness of the gas valve). Check that the natural gas supply corresponds to the nominal boiler pressure stated on the identifi cation plate.
4.13. Electrical connection
DANGER:
!
!
WARNING: Observe the phase polarity - neutral for electrical connections.
WARNING:
Ensure that the general electrical power supply has been cut off before starting any work.
It is mandatory to connect this boiler correctly to earth and to comply with applicable standards for low voltage electrical installations in the United Kingdom. Provide a two pole circuit breaker upstream of the boiler (distance between contacts: 3.5 mm minimum). It is strongly recommended to fi t the electrical installation with a 30 mA differential protection.
Page 36 / 146 00BNO9061-J
4.13.1. Control panel
VARMAX - Installation, Use and Maintenance
Refer to the instructions of installation and use of the NAVISTEM B3000 boiler command table for information concerning electrical connections to the control panel (characteristics of the electrical power supply, cable section and connection to terminal blocks).
To access the control panel, open the casing doors on the front of the boiler.
The control panel is on the upper front left of the boiler.
Unscrew the turn screw at the bottom of the cover.
Cover
Turn screw
gure 27 - Opening the electrical box
4.13.2. Cable bushing
Cable clamp
U0501960-#
High voltage tray (power supply)
Lift up the cover and pull backwards.
Use the cable trays located on the top left of the boiler to insert the connection cables:
• The upper tray must be reserved for the power connections (boiler power supply, alarm feedback or circulating pump control).
• The lower tray is dedicated to signal connections (sensors, communication bus, etc.).
Low voltage tray (sensors / buses)
Use the cable clamp located at the inputs to the trays to lock the cable mechanically.
U0501963-#
gure 28 - Electrical cable bushing
Edition: 06 / 2015 Page 37 / 146
VARMAX - Installation, Use and Maintenance
4.13.3. Connection of the boiler command table to the terminal blocks
To connect the boiler command table, refer to the relevant instructions of installation and use.
!
ATTENTION :
For connection, comply with the wiring diagram, in particular the phase, neutral and earth polarities.
4.13.4. Connection of AVS75 extension module(s) (optional)
To install AVS75 module(s) (3 max), refer to the instructions provided with the accessory (reference 059751).
AVS75 location (behind side door)
U0501963-#
gure 29 - AVS75 location
4.13.5. Connection of OCI345 communication module (optional)
To install the OCI345 module, refer to the instructions provided with the accessory (reference 059752).
4.13.6. Fuses
The VARMAX boiler is fi tted with 4 fuses on the boiler command table (refer to the sticker on the protective cover for their locations and characteristics).
3 spare fuses are also available on the boiler command table.
Page 38 / 146 00BNO9061-J
H6
B8
OCI 345
AVS75
B2 B7
H3
4.13.7. Electrical wiring diagram
VARMAX - Installation, Use and Maintenance
Refer to the boiler command table instructions of installation and use.
Refer to the instructions supplied with the optional accessory AVS75.
Refer to the instructions supplied with the optional accessory OCI 345
gure 30 - Electrical wiring diagram
Edition: 06 / 2015 Page 39 / 146
00BET9008-#
VARMAX - Installation, Use and Maintenance
5. COMMISSIONING
5.1. Unlocking the boiler
During commissioning, the unlocking of the boiler can only be achieved
!
WARNING:
if the hydraulic system is compliant with the recommendations mentioned in the hydraulic diagrams (see section 8.3, page 54). The person in charge of this operation must ensure such compliance.
Unlocking the temperature:
Modify parameter 2212 from 70° C to the desired value (Maximum 85°C).
Unlocking the power:
Increase the value of parameter 9529 up to the value of parameter 9530 (corresponding with the nominal power of the boiler).
Adjusting the boiler to operate using propane results in the
!
Parameter 9529 value 120 140 180 225 275 320 390 450
WARNING:
power locked 4610 5300 3180 3870 3360 3930 3440 3900
power unlocked 6490 7460 4410 5400 4620 5450 4810 5480
modifi cation of parameter 9529; the boiler power locking function is therefore no longer active.
MODELS
5.2. Pre-commissioning checks
For a cascade installation, check the hydraulic balance of the boilers.
Check that pressure when cold is at least 1 bar.
If this is a boiler room renovation, ensure that fl ushing and if necessary silt removal from the installation have been correctly done (see paragraph 1.5, page 7 of these instructions).
Check the fl ue-gas connections depending on the type of chimney (refer to paragraph 4.9, page 24).
Check that the gas pressure and type are suitable for the products.
DANGER: It is forbidden to use water containing glycol.
!
!
Page 40 / 146 00BNO9061-J
WARNING:
If connecting CHIMNEY B23 or B23P, it is COMPULSORY to fi t the air lter supplied with the boiler.
5.3. Commissioning
VARMAX - Installation, Use and Maintenance
Before being packed up, all boilers are tested in the factory operating on group H natural gas (type G20), during which all settings are made.
For commissioning, carry out the following operations:
1. Switch on the main power.
Flue-gas sample
point
gure 31 - Taking a sample
U0501961-#
2. Create a request for heat via the comfort mode using the customer interface (see chapter "3 ­Interface utilisateur" of the LMS boiler command table instructions).
3. After starting up the burner, check the gas tightness of the gas line connections using a foaming product. Check combustion health using a fl ue-gas analyser via a sample taken from the ue outlet (see diagram opposite).
CO
value range:
2
G20:
at Qmin: 8,3 % < CO at Qmax: 8,8 % < CO
< 8,7 %
2
< 9,2 %
2
G31:
at Qmin: 9,8 % < CO at Qmax: 10,4 % < CO
< 10,2 %
2
< 10,8 %
2
4. Adjust the boiler setting (refer to the table summarising customer parameters at the end of this manual).
!
WARNING: Any work on a sealed element leads to loss of warranty.
Edition: 06 / 2015 Page 41 / 146
VARMAX - Installation, Use and Maintenance
6. POST-COMMISSIONING CHECK
6.1. Condensate removal
Check that the removal of condensates is not obstructed, on both the boiler side and the pipe side
6.2. Gas supply
Check that the gas pipe diameter is correctly sized:
It is necessary to stop all the boilers together abruptly using the boiler room main circuit breaker to check that the gas pressure regulator safety device is not triggered.
If this is triggered, the gas pipe is undersized. After this operation, reengage the circuit breaker. The boilers must start automatically, if not, consult the supplier of the gas pressure regulator.
Page 42 / 146 00BNO9061-J
7. MAINTENANCE OPERATIONS
There are two types of maintenance operations:
• yearly maintenance
DANGER:
• in-depth maintenance every 3 years.
The table below shows which actions to undertake depending on the type of maintenance to be performed. In all events, these operations must be performed by a qualifi ed professional.
Before carrying out the following operations:
• Switch off the main power
• Close the gas supply shut-off valve.
This boiler's earth bonding is ensured with connecting cables (green/ yellow) and specifi c attachment screws. During any dismantling work, make sure you reconnect the cables concerned; it is IMPERATIVE to reuse the original attachment screws.
VARMAX - Installation, Use and Maintenance
No. of
paragraph to
consult
7.2 Verifi cation of the boiler's environment X
7.3 Replacing the air fi lter matting X
7.4 Verifi cation of ignition and ionisation electrodes X
7.5 Siphon cleaning X
7.6 Checking the combustion circuit's gas-tightness X
7.7 Checking combustion quality X
7.9 Gas fi lter cleaning X
7.10 Cleaning exchangers and changing of seals on service doors X
Maintenance
every
year
every
three
years
7.11
Edition: 06 / 2015 Page 43 / 146
Check the condition of the gas manifold coating Cleaning the burner and changing the seals
X
VARMAX - Installation, Use and Maintenance
7.1. Boiler draining
Main exchanger drain valve
(front of boiler)
Condenser drain valve (rear of boiler)
gure 32 - Drain valves
• Close the shut-off valves of the fl ow and return tappings.
• Connect the drain valves (main exchanger and condenser) to the drain with a suitable hose.
• Create an air intake on the "main exchanger" ow nozzle (open the safety valve).
• Open the drain valve.
U0502206-#
7.2. Verifi cation of the boiler's environment
Before carrying out any maintenance work, it is necessary to perform a certain number of checks concerning the installation's use.
• Water pressure: check that the water pressure is higher than 1 bar when cold.
• Read the makeup water meter. This operation helps to identify any hydraulic leaks. If consumption of makeup water changes, seek the cause and repair.
7.3. Replacing the air fi lter matting
!
DANGER:
To make sure this task is performed in safety, switch off the boiler and cut off the upstream power.
!
Page 44 / 146 00BNO9061-J
DANGER:
INFORMATION:
Use personal protective equipment (mask and gloves) to remove the used air fi lter.
The air fi lter is only present on boilers connected to a B23 or B23P chimney.
INFORMATION:
VARMAX - Installation, Use and Maintenance
The air fi lter is an important element of the boiler. It limits the burner and the exchangers becoming sooty. Changing it regularly (at least every year) makes burner and exchanger cleaning operations considerably easier.
Models 120 to 320:
Models 390 and 450:
gure 33 - Filter matting
mountings
U0038318-B
U0024791-B
- Remove the used fi lter matting (no tool required).
- Be careful not to let any dust or other foreign bodies enter the air duct (see opposite).
- Insert the new rectangular fi lter matting between the fi lter's protective grille and the mountings (see opposite).
Ensure that the link between both ends of the matting is under one of the mountings.
- For models 390 and 450, insert the square fi lter cloth on the back gate of the fi lter.
7.4. Verifi cation of ignition and ionisation electrodes
Ionisation electrode
Ignition electrode
U0502214-#
gure 34 - Position of electrodes
2.5-3.5 mm
U0502273-#
gure 35 - Spacing
Electrode removal
Unscrew the two M4 Torx screws holding the electrode that needs to be removed.
If necessary and if there is a large amount of oxidation, clean the electrodes by rubbing them with an emery cloth.
Check the space between the ignition electrode and the ground electrode (see diagram opposite). It must be between 2.5 and 3.5 mm. If this is not the case, replace the electrode.
Edition: 06 / 2015 Page 45 / 146
VARMAX - Installation, Use and Maintenance
gure 36 - Geometry
7.5. Siphon cleaning
Siphon
Hatch
13.8 mm
U0502273-#
U0502274-#
Check the geometry of the arc electrode: If deformed more than ±3 mm, replace the electrode.
Re-assemble the electrode block(s). Tightening torque of the block fi xing screws = 2.5 N.m.
Check the siphon and clean if necessary. The siphon must be located between the main exchanger and the condenser on the right-hand side (it can be accessed via the hatch without removing the side panel). To do this:
• Dislodge the siphon by pulling it downwards.
• Clean with water.
• Re-assemble the siphon after checking the presence and the possibility of free movement of the fl oat (ball). Also check that the seal is not damaged.
gure 37 - Siphon
7.6. Checking the combustion circuit's gas-tightness
Check the gas-tightness of the 3 service doors using the foaming product. The areas to check are shown on the diagram opposite. The check must be performed when the boiler is off, but with the ventilator operating at its maximum
seal checking zone
exchanger service door (check the other 2 doors)
U0502275-#
gure 38 - Gas-tightness of the service door
speed (obtained by disconnecting the PWM signal connector).
If a leak is detected, replace the seal with the appropriate kit.
It is recommended to replace the seals each time the exchanger service doors are removed. If they are not replaced, do not cross the doors when re­assembling.
Page 46 / 146 00BNO9061-J
7.7. Checking combustion quality
Flue-gas sample
point
U0501961-#
gure 39 - Sample taking
VARMAX - Installation, Use and Maintenance
This check is performed using a calibrated combustion case. To do this, insert the measuring stick into the fl ue outlet (see diagram opposite).
The boiler's starting temperature must be above 70°C.
Do not forget to re-position the stopper on the orifi ce from where the sample is taken afterwards.
For the G20, the CO
content measured in these circumstances must be
2
between 8.3% and 8.7% at Qmini (0% on display) and between 8.8% and
9.2% at Qmaxi (100% on display).
If this is not the case, it is necessary to alter the setting of the gas valve (see next paragraph). After this check, it is necessary to either take a measurement of the "gas" throughput or the P valve. These measurements check the state of soiling of the combustion circuit (burner, body, exchanger(s)).
For the G31 (relevant modls only), the CO
content measured in these
2
circumstances must be between 9,8% and 10,2% at Qmini (0% on display) and between 10,4% and 10,8% at Qmaxi (100% on display).
If this is not the case, it is necessary to alter the setting of the gas valve (see next paragraph). After this check, it is necessary to either take a measurement of the "gas" throughput or the P valve. These measurements check the state of soiling of the combustion circuit (burner, body, exchanger(s)).
For installations with B23 and B23P, we recommend you take this measurement using a new air fi lter.
The measurement must be done for a duration of more than 3 minutes to obtain a suffi ciently precise measurement. If the gas throughput is less than 20% in relation to the value indicated in paragraph 3.3, page 15, it is necessary to clean the main exchanger and the burner (see § 7.10 and 7.11). If you choose to take a measurement of the P valve, refer to the next paragraph to fi nd out how to do it. If the value measured is lower than the values defi ned in the table on page 49, it is necessary to clean the main exchanger and the burner (see § 7.10 and 7.11).
Edition: 06 / 2015 Page 47 / 146
VARMAX - Installation, Use and Maintenance
7.8. Setting the gas valve
This VARMAX boiler has been adjusted in the factory to operate with group H natural gas (type G20) with inlet gas pressure of 20 mbar.
!
WARNING:
Any work on adjusting the gas valve must be performed by a qualifi ed professional.
The valve must be adjusted with the boiler working at maximum and minimum pressure. To do this, use the operating "Manual operating" mode (see § 3.3.4 of the NAVISTEM B3000 boiler command table instructions), which makes it possible to switch directly to the minimum or maximum value (0% or 100%).
7.8.1. For models 120 and 140
Start the burner up at maximum power.
Using the combustion analyser, measure the rate of CO
in the fl ue-gases in the fl ue outlet (see
2
gure 39).
Check the CO
value at Maximum power and, if
2
necessary, manipulate the valve's gas throughput adjustment screw to obtain CO
values between
2
8.8% and 9.2% or between 10,4% and 10,8% (G31).
Offset regulator
Gas throughput adjustment screw
U0501967-#
gure 40 - VARMAX gas valve models 120 and 140
Move to Minimum power and check that the CO
2
value is between 8.3% and 8.7% (G20) or between 9,8% and 10,2% (G31). If necessary, adjust the Offset regulator by removing the stopper using a at screwdriver and adjust the screw with a Philips screwdriver.
If changing the setting while on minimum power, switch back to Maximum power and check the CO
2
value again. Repeat until both values conform.
Go back to standard operating mode.
Air relay pipe connection points
Page 48 / 146 00BNO9061-J
7.8.2. For models 180 to 450
VARMAX - Installation, Use and Maintenance
Hexagonal 3 mm wrench
Offset regulator
Pvalve
Pupstream
gure 41 - Gas valve setting
Cover
U0501967-#
The measurements for setting the valve must be taken using the pressures indicated Pvalve and Pupstream (see diagram opposite).
Air relay pipe connection points
(Models 180 and 225)
Air relay pipe connection points
(Models 275 and 320)
Air relay pipe connection points
(Models 390 and 450)
Edition: 06 / 2015 Page 49 / 146
VARMAX - Installation, Use and Maintenance
Models
Valve
type
Type of
gas
G20 3,8
180 VR420
G31 1,6 G20 5,9
225 VR420
G31 2,4 G20 3,6
275 VR432
G31 1,7 G20 5,2
320 VR432
G31 2,4 390 VR434 G20 5,4 450 VR434 G20 7,1
P
valve
= (P
upstream
- P
valve
)
P
Schieber
(mbar)
Setting at maximum power: Start the burner up at maximum power. Remove the cover (see fi gure 41). Measure the inlet gas pressure (Pupstream). Adjust the valve pressure (Pvalve) taking into account P
valve
= (P
upstream
- P
) given in the table
valve
opposite (set the pressure by manipulating the adjustment screw on the top of the valve underneath the black cover, 3 mm hexagonal wrench). If necessary, adjust the valve pressure to obtain a CO
rate between 8.8% and 9.2% (G20) or between
2
10,4% and 10,8% (G31).
Then switch to minimum power: Adjust the offset regulator (see fi gure 41) to get a CO
rate at minimum power between 8.3% and
2
8.7% (G20) or between 9,8% and 10,2% (G31). Use a fl at screwdriver to remove the protective stopper
and a Torx wrench to adjust. To validate the correct setting of the valve increase to Pmaxi (HMI = 100%) and check the CO
rate in
2
the fl ue-gases in the fl ue outlet (see fi gure 39). If the setting is not correct, perform the above steps again.
7.9. Gas fi lter cleaning
- Unscrew the 4 screws that hold the gas fi lter in place.
- Carefully remove the gas fi lter.
- Clean the gas fi lter ONLY with a blower.
- Refi t the fi lter and tighten the 4 M5 screws (tightening torque = 5 N.m).
Gas fi lter
screws
(x4)
screws (x4)
Gas fi lter
U0503716-# U0503711-#
gure 42 - Gas fi lter on VARMAX 120 and 140
!
Page 50 / 146 00BNO9061-J
WARNING: Check gas-tightness after refi tting.
gure 43 - Gas fi lter on VARMAX 180 to 450
7.10. Cleaning exchangers and changing seals
Removal of exchanger doors:
- Remove the front and side cladding to access the 3 service doors.
- Using a 13mm wrench, unscrew the service door attachment screws until the tightening bolts turn.
VARMAX - Installation, Use and Maintenance
gure 44 - Removal of exchanger doors
6 screws
U0502425-#
- Then remove the door.
- Repeat for the other 2 service doors.
Removal of baffl es:
- Open the fastenings (mark 1) that close the 2 ue-gas baffl e strappings (mark 2).
gure 45 - Removal of baffl es
Edition: 06 / 2015 Page 51 / 146
- Remove the 2 strappings (mark them in some way so that you can refi t them in the same order) and then remove the fl ue-gas baffl es (marks 3). Mark these too so that you can refi t them in the same position.
Cleaning baffl es and exchangers:
- Brush the fl ue-gas baffl es with a stainless steel or plastic brush, so as not to geometrically deform them.
- Clean by brushing or if the exchanger is very dirty, wash with water and then dry. If washing with water, be careful of the electrical parts.
VARMAX - Installation, Use and Maintenance
Changing door seals:
service door
groove
- Remove the seals from their groove and replace with new seals from the maintenance kit (see gure 46).
seal
U0502445-#
gure 46 - Changing door seals
Refi tting:
wire spring
- Insert the baffl es under the wire spring between the top part of the exchanger tubes (see detail).
Replace the baffl es holding the strappings (mark
3) as shown on the diagram opposite.
- Position the strappings inside the pins of the baffl es holding the strappings.
baffl es
gure 47 - Refi tting
- Tighten the fastenings and ensure the baffl es are correctly fi tted to the exchanger tubes and check
that each of the baffl es are correctly fi tted on the exchanger tubes at their lower and upper ends.
Note: It is normal that the baffl es are not fi tted tightly in the area between the 2 strappings.
U0503496-#
Checking gas-tightness:
- After refi tting the 3 service doors (tightening
torque of screws = 15 N.m), check the gas tightness using the foaming product around the service doors before starting the boiler up again (see chapter 7.6).
Page 52 / 146 00BNO9061-J
VARMAX - Installation, Use and Maintenance
7.11. Cleaning the burner and changing the seals
To facilitate access to the spool piece and then the
removable part
U0502250-#
gure 48 - Removable upper door
gas tube, part of the upper door is removable.
spool piece
cover
gure 49 - Removal of spool piece cover
removal / mounting tool
U0502457-#
Spanner of 24
Removing the burner tube:
- Remove the 2 electrode blocks before removing the burner tube (see chapter 7.4).
- Unscrew the attachment screws from the spool piece cover to remove it.
- Put the burner tube's removal / mounting tool in position (the tool is located under the gas line to the right of the sleeve cover).
- Position the tool in the slots of the tightening ange and compress on it (by pressing down) .
U0503721-#
gure 50 - Release the burner tube
Edition: 06 / 2015 Page 53 / 146
VARMAX - Installation, Use and Maintenance
Plastic valve
Lug
- Rotate the tool anticlockwise to unlock the ramp.
Unlocked
Locked
U0516842-#
gure 51 - Positions of the fastening clamps
- Remove the clamp from the burner tube.
- Remove the burner tube.
!
!
WARNING:
WARNING:
Remove the plastic valve on the spool piece before removing the burner tube. Do not forget to put it back when refi tting.
When removing the burner tube, be careful not to rub metal mesh against the spool piece.
Cleaning the burner tube:
gas tube
U0502459-#
gure 52 - Cleaning the gas tube
Page 54 / 146 00BNO9061-J
- Suck out the entire surface in metal mesh using a vacuum cleaner.
VARMAX - Installation, Use and Maintenance
Keep a distance of 10 mm between the suction nozzle and the metal
!
WARNING:
mesh. Any rubbing of the boiler tube may cause damage. NEVER USE A METAL BRUSH.
!
WARNING: Replace the seal under the clamp on the burner tube.
Refi tting:
- Put the burner tube into the spool piece (be careful not to rub the metal mesh on the spool piece). A directional pin enables the burner tube to be correctly positioned.
- Position the clamp (the word "UP" must be visible and the inner lug must be positioned on the rear axis of the boiler - see fi gure 47)
- Position the burner tube's removal / mounting tool in the slots in the clamp.
- Compress by pushing downwards and rotate the tool in a clockwise direction to lock the tube (see fi gure 47).
- Check the seal on the spool piece's cover and replace if necessary.
- Position the cover over the spool piece.
- Screw the cover onto the spool piece using the screws (tightening torque = 5 N.m).
- Refi t the 2 electrode blocks.
!
WARNING:
Check the different seals after mounting. If using a foaming product, be careful of the ionisation electrode's electrical connection.
Edition: 06 / 2015 Page 55 / 146
VARMAX - Installation, Use and Maintenance
8. END-OF-LIFE CYCLE OF THE APPARATUS
8.1. Environmental compatibility
This appliance contains electrical and electronic elements which must not be thrown away with household waste. Local legislation must be complied with.
8.2. Dismantling, recycling and elimination of the apparatus
Regulatory disposal and managed recycling of this product can prevent damage to the environment and health risks.
a) For the disposal of the product and the component parts, the services of
an accredited waste disposal company should be used.
b) For more information on waste disposal/management, contact the Local
Authority responsible for waste management or the point of sales where the product was purchased
Page 56 / 146 00BNO9061-J
VARMAX - Installation, Use and Maintenance
9. HYDRAULIC DIAGRAMS AND SETTINGS
9.1. Selection fl ow diagram
Without management
Single boiler
With management of
secondary networks
of secondary
systems
Not
communicating
Communicating via
signal 0…10V
Communicating via
LPB bus
direct circuit
1, 2 or 3
regulated
networks
without DHW
With
3-channel
valve
Accumulated
DHW
Non communicating existing
secondary system
VX101
Page 60
Secondary networks via
existing communicating
system
VX111
Page 75
Secondary networks via
existing communicating
system
VX111
Page 75
1 direct heating network
VX100
Page 60
Networks (1, 2 or 3) regula-
ted by 3-channel valve
without DHW
VX102
Page 64
Networks (1, 2 or 3) regula­ted by 3-channel valve with
accumulated DHW
VX110
Page 70
regulated
network + low
level direct circuit
+
regulated network +
consumer circuit constant
T° and throughput
+
semi-instanta-
neous DHW
Networks (1, 2 or 3) regula­ted by 3-channel valve with
instantaneous DHW
VX112
Page 64
1 network regulated by
3-channel valve, 1 direct
circuit with low level
VX113
Page 78
1 network regulated by
3-channel valve, 1 consumer
circuit with constant T° and
throughput
VX120
Page 82
Edition: 06 / 2015 Page 57 / 146
VARMAX - Installation, Use and Maintenance
Management of secon-
dary systems by
external regulation
Cascade
management by
ATLANTIC
Cascade manage-
ment by external
regulation
direct circuit
regulated network +
consumer circuit constant
T° and throughput
+
Not
communicating
Communicating
via signal
0…10V
Communicating via
LPB bus
Not
communicating
No communication with the
secondary system
VX201
Page 86
Secondary networks regula-
ted by communicating
external regulation
VX211
Page 100
Secondary networks regula-
ted by communicating
external regulation
VX211
Page 100
No communication with the
secondary system
Contact the before-sales service
1 direct network
VX200
1 network regulated by 3-channel
valve and 1 circuit with constant
temperature and throughput
VX220
Page 86
Page <?>
arrangement
Boiler cascade
Management of
secondary systems
by A TLANTIC
Mixed
1 regulated network
with accumulated DHW
+
3 or 4 regulated
networks
...
3 or 4 regulated networks with
semi-instantaneous DHW
...
+
1 network regulated by V3V
with accumulated DHW
VX210
Page 92
3 or 4 networks regulated by
3-channel valve, without DHW
VX202
Page 106
3 or 4 networks regulated by
3-channel valve, with semi-
instantaneous DHW
VX212
Page 106
with TRAD
Contact the before-sales service
with LMU
Contact the before-sales service
Page 58 / 146 00BNO9061-J
VARMAX - Installation, Use and Maintenance
9.2. Symbols used in the diagrams
Symbol Function Symbol Function
Open isolating valve Balancing valve
Motorised 2 channel valve Motorised 3 channel valve
Filter Non-return valve
Safety unit Pump
Sediment well Drain valve
External sensor Temperature sensor
9.3. List of diagrams
Operation at constant temperature with variable fl ow and immediate
!
WARNING:
SINGLE BOILER .........................................................................................................................60
1 direct heating network or existing non-communicative secondary system ...................................................... 60
VX100, VX101
3 regulated networks with or without DHW production ....................................................................................... 64
VX102, VX112
1 network regulated by a 3-channel valve, and DHW production ...................................................................... 70
VX110
Secondary networks with existing regulation communicating by LPB bus or 0...10V ........................................ 75
VX111
1 network regulated by a 3-channel valve, 1 direct circuit with 60°C low level ..................................................78
VX113
1 network regulated by a three-channel valve, 1 circulation circuit with constant temperature and throughput 82
VX120
DHW production directly on heat plate exchanger without buffer tank forbidden.
BOILERS IN A CASCADE CONFIGURATION ...........................................................................86
1 direct network, no communication with the secondary network ...................................................................... 86
VX200, VX201
1 network regulated by a three-channel valve, DHW production or 1 direct circuit with constant temperature
and throughput ................................................................................................................................................... 92
VX210, VX220
Secondary networks regulated by external regulated communicating by LPB bus or 0...10V ......................... 100
VX211
3 or 4 networks regulated by a three-channel valve with or without DHW production ..................................... 106
VX202, VX212
Edition: 06 / 2015 Page 59 / 146
VARMAX - Installation, Use and Maintenance
SINGLE BOILER
1 direct heating network or existing non-communicative
secondary system
A. MAIN AND ALTERNATIVE HYDRAULIC DIAGRAMS
B9
B3000
Q2
Diagrams
VX100 VX101
page 1 / 4
B9
B3000
gure 53 - Diagram VX100
NON-COMMUNICATING
REGULATEUR
REGULATEUR
REGULATEUR
REGULATEUR
REGULATEUR
REGULATEUR
REGULATOR
NON COMMUNICANT
NON COMMUNICANT
NON COMMUNICANT
NON COMMUNICANT
NON COMMUNICANT
NON COMMUNICANT
SAFETY BY-PASS IF
BY-PASS DE SECURITE
BY-PASS DE SECURITE
BY-PASS DE SECURITE
BY-PASS DE SECURITE
BY-PASS DE SECURITE
BY-PASS DE SECURITE
HEATED FLOOR
SI PLANCHER CHAUFFANT
SI PLANCHER CHAUFFANT
SI PLANCHER CHAUFFANT
SI PLANCHER CHAUFFANT
SI PLANCHER CHAUFFANT
SI PLANCHER CHAUFFANT
gure 54 - Diagram VX101 (alternative)
Page 60 / 146 00BNO9061-J
VARMAX - Installation, Use and Maintenance
Diagrams: VX100 / VX101
page 2 / 4
B. NECESSARY ADJUSTMENT ACCESSORY
Quantity
External sensor kit 1 QAC 34 059260
Appliance
reference
Order No.
C. CUSTOMER ELECTRICAL CONNECTION
Mains supply 230
VAC 50 Hz
Diagram VX100:
Circulation pump on
direct circuit Q2
L NY1 NY2L NL NL N
QX2 QX3 QX1 AUX2 AUX1
}
Alarm relay
}
D. SPECIFIC START-UP PROCEDURE
Fit the accessories and make their electrical connections.
Start up the boiler alone.
Make the following settings:
BX2 Gnd BX3 Gnd
B3
Gnd
B9
Gnd
H1
Gnd
H5
Gnd
Line No. Value
External sensor B9
}
• Time and date menu
Set the time
Set the date
Set the year
• Configuration menu
Start up the heating circuit 1
Defi ne the pump outlet Q2 (diagram VX100)
Edition: 06 / 2015 Page 61 / 146
Time / minute (1) HH.MM
Day / month (2) DD.MM
Year (3) YYYY
Heating circuit 1 (5710) On
QX2 relay outlet (5891) Pump CC1 Q2
VARMAX - Installation, Use and Maintenance
Diagrams: VX100 / VX101
• Heating circuit 1 menu
Set the comfort setting
Set the curve slope
• Switch the heating mode to permanent comfort
Comfort setting temperature (710) - - -
Heating curve slope (720) - - -
E. ELECTRICAL AND HYDRAULIC VALIDATION
• Input/output test menu
Check the outputs
Alarm relay
Heating circuit No. 1 pump (diagram VX100)
Reset outputs
page 3 / 4
Line No. Value
Relay test (7700) Relay output QX1
Relay test (7700) Relay output QX2
Relay test (7700) No test
Check sensor values
External sensor B9
• Configuration menu
Check the hydraulic diagram
F. OPTIMISATION OF SETTINGS
• Heating circuit 1 menu
Set the reduced setting
• CC1 time programme menu
Preselection
External T° B9 (7730) in °C
Generator 1 check (6212) 14
Generator 2 check (6213) 0
Information on DHW (6215) 0
Information on heating circuits 3, 2 and 1 (6217) 1 (for VX101)
2 (for VX100)
Reduced temperature setting (712) - - -
Preselection (500) - - -
Adjust the time programme
• Circuit CC1 holiday menu
Preselection
Adjust the time programme
• Switch the heating mode to automatic
Page 62 / 146 00BNO9061-J
On / Off phases (501...506) - - -
Preselection (641) - - -
On / Off phases (642-643) - - -
AUTO
VARMAX - Installation, Use and Maintenance
Diagrams: VX100 / VX101
page 4 / 4
Maintenance optimisation:
It is possible to generate a maintenance message without harming the boiler. This maintenance message may appear when the 3 following meters have elapsed:
• Time since last maintenance (or commissioning): set parameter 7044 to 12 months
• Operating hours of the burner (parameter 7040)
• Number of start-ups (parameter 7042)
The last 2 parameters depend on the boiler room's hydraulic installation. It is recommended to use at least parameter 7044 for yearly maintenance.
Edition: 06 / 2015 Page 63 / 146
VARMAX - Installation, Use and Maintenance
SINGLE BOILER
Diagrams
VX102
3 regulated networks with or without DHW production
A. MAIN AND ALTERNATIVE HYDRAULIC DIAGRAMS
B9
B12
B3000
B1
Y1/Y2
x
Q2
x
Q6
Y5/Y6
VX112
page 1 / 6
B14
x
Q20
Y11/ Y12
B9
B3000
gure 55 - Diagram VX102
B1
x
Q2
Y1/Y2
Y5/ Y6
B12 B14
x
Q6
Y11/ Y12
B3
bouclage
bouclage ECS
ECS
x
Q20
ECS
Cold
Entrée
Entrée
water inlet
eau froide
eau froide
gure 56 - Diagram VX112 (alternative)
Page 64 / 146 00BNO9061-J
VARMAX - Installation, Use and Maintenance
Diagrams: VX102 / VX112
page 2 / 6
B. NECESSARY ADJUSTMENT ACCESSORIES
Quantity
Extension module kit (delivered with a QAD 36 network sensor)
External sensor kit 1 QAC 34 059260 Ambient sensor kit (diagram VX102) 3 QAA 75 040954 DHW sensor kit (diagram VX112) 1 QAZ 36 059261
3 AVS 75 059751
Appliance
reference
Order No.
C. CUSTOMER ELECTRICAL CONNECTION
Alarm
relay
}
Mains supply 230
VAC 50 Hz
L NY1 NY2L NL NL N
QX2 QX3 QX1 AUX2 AUX1
G+ CL- CL+ G+ CL- CL+
Diagram VX102:
Ambient sensor QAA 75 for
}
heating circuit No. 3
Diagram VX102:
Ambient sensor QAA 75 for
}
heating circuit No. 2
Diagram VX102:
Ambient sensor QAA 75 for
}
heating circuit No. 1
BX2 Gnd BX3 Gnd
B3
Gnd
B9
Gnd
H1
Gnd
H5
Gnd
Diagram VX112:
}
DHW sensor B3
External sensor B9
}
Diagram VX112 only
Edition: 06 / 2015 Page 65 / 146
VARMAX - Installation, Use and Maintenance
Mixing valve for heating
circuit No. 1 Y1/Y2
Circulator for heating circuit
No. 1 Q2
Mixing valve for heating
circuit No. 2 Y5/Y6
Circulator for heating circuit
No. 2 Q6
Diagrams: VX102 / VX112
QX21
}
N
QX22
}
QX23
QX21
}
N
QX22
}
N
QX23
N
AVS75
AVS75
BX21
Gnd
BX22
Gnd
H2
Gnd
BX21
Gnd
BX22
Gnd
H2
Gnd
page 3 / 6
Module 1
}
Flow sensor for regulated circuit
}
B1
Module 2
}
Flow sensor for regulated circuit
}
B12
QX21
Mixing valve for heating
circuit No. 3 Y11/Y12
Circulator for heating circuit
No. 3 Q20
}
N
QX22
}
N
QX23
AVS75
D. SPECIFIC START-UP PROCEDURE
Fit the accessories and make their electrical connections.
WARNING:
!
Start up the boiler alone.
Make the following settings:
Ensure the switches on the extension modules AVS75 are properly confi gured.
BX21
Gnd
BX22
Gnd
H2
Gnd
Module 3
}
Flow sensor for regulated circuit
}
B14
Line No. Value
• Time and date menu
Set the time
Set the date
Set the year
• Configuration menu
Start up the heating circuit 1
Start up the heating circuit 2
Start up the heating circuit 3
Page 66 / 146 00BNO9061-J
Heating circuit 1 (5710) On
Heating circuit 2 (5715) On
Heating circuit 3 (5721) On
Time / minute (1) HH.MM
Day / month (2) DD.MM
Year (3) YYYY
VARMAX - Installation, Use and Maintenance
Diagrams: VX102 / VX112
Diagram VX112 only:
Defi ne a low level
Install a shunt on H1 OR reverse
the direction of contact
For the DHW to be effective, it is necessary to defi ne a trigger, even if it is not connected.
Confi gure the extension modules
page 4 / 6
Line No. Value
Input function H1 (5950) Circulation circuit
demand 1
Type of contact (5951) Rest contact
Output via relay QX2 (5891) Pump/valve ECS
Q3
Function of extension module 1 (6020) Heating circuit 1
Function of extension module 2 (6021) Heating circuit 2
Function of extension module 3 (6022) Heating circuit 3
• Heating circuit 1 / 2 / 3 menu
For each circuit
Set the comfort setting
Set the curve slope
• Switch the heating mode to permanent comfort
Diagram VX112 only:
• Circulation circuit 1 menu
Set the starting value to use in the event of a demand from the circulation circuit
• Domestic hot water menu
Set the comfort setting
Temperature of comfort setting (710/1010/1310) - - -
Slope of the heating curve(720/1020/1320) - - -
Starting value in case of circuit demand
60°C (depends on
(1859)
Comfort setpoint (1610) 55 °C
Rubis setting)
Set the DHW release mode
• Activate DHW mode
Edition: 06 / 2015 Page 67 / 146
DHW release (1620) 24/7
VARMAX - Installation, Use and Maintenance
Diagrams: VX102 / VX112
E. ELECTRICAL AND HYDRAULIC VALIDATION
• Input/output test menu
Check the outputs
Alarm relay
All relays of extension modules
Reset outputs
Check sensor values
External sensor B9
DHW sensor B3
Flow sensor B1
Flow sensor B12
Flow sensor B14
Temperature sensor BX21 module 1 (7830) in °C
Temperature sensor BX21 module 2 (7832) in °C
Temperature sensor BX21 module 3 (7834) in °C
DHW temperature B3/B38 (7750) in °C
page 5 / 6
Line No. Value
Relay test (7700) Relay output QX1
Relay test (7700) Relay output QX
Relay test (7700) No test
External T° B9 (7730) in °C
Diagram VX112 only:
Check the condition of contact H1
• Configuration menu
Check the hydraulic diagram
F. OPTIMISATION OF SETTINGS
Optimisation of the heating circuits:
• Heating circuit 1 / 2 / 3 menu
Set the reduced setting
Condition of contact H1 (7841) Closed if the shunt
is in place
Generator 1 check (6212) 14
Generator 2 check (6213) 0
Information on DHW (6215) 0
Information on heating circuits 3, 2 and 1 (6217) 30303
Line No. Value
Reduced temperature setting (712/1012/1312) - - -
(diagram VX102)
4
(diagram VX112)
• Time programme CC1 / CC2 / CC3 menu
Preselection
Adjust the time programme
Page 68 / 146 00BNO9061-J
Preselection (500/520/540) - - -
On / Off phases (501...506)
(521...526) (541...546)
- - -
VARMAX - Installation, Use and Maintenance
Diagrams: VX102 / VX112
• Holiday circuit CC1 / CC2 / CC3 menu
Preselection
Adjust the time programme
• Switch the heating mode to automatic
Optimisation of DHW:
• DHW storage tank menu
Adjust the boost
Line No. Value
Preselection (641/651/661) - - -
On / Off phases (642-643)
(652-653) (662-663)
Line No. Value
Starting value of boost temperature (5020) 16 °C
- - -
AUTO
page 6 / 6
Maintenance optimisation:
It is possible to generate a maintenance message without harming the boiler. This maintenance message may appear when the 3 following meters have elapsed:
• Time since last maintenance (or commissioning): set parameter 7044 to 12 months
• Operating hours of the burner (parameter 7040)
• Number of start-ups (parameter 7042)
The last 2 parameters depend on the boiler room's hydraulic installation. It is recommended to use at least parameter 7044 for yearly maintenance.
G. SETTING AMBIENT SENSORS
Connect each sensor to a heating circuit:
Line No. Value
• User interface menu of each ambient sensor
Confi gure the ambient sensor with a heating circuit
Use (40) Ambient appliance
1 or 2 or 3
Each ambient sensor allows its heating circuit to be confi gured. Ambient sensors 1, 2 and 3 respectively set parameters 712 (heating circuit 1), 1012 (heating circuit 2) and 1312 (heating circuit 3).
Edition: 06 / 2015 Page 69 / 146
VARMAX - Installation, Use and Maintenance
SINGLE BOILER
1 network regulated by a 3-channel valve, and DHW production
A. HYDRAULIC DIAGRAM
B9
B1
x
Q2
Y1/Y2
Diagram
VX110
page 1 / 5
Q3
B3000
B3
gure 57 - VX110 diagram
B. NECESSARY ADJUSTMENT ACCESSORIES
Quantity
Extension module kit (delivered with a QAD 36 network sensor)
1 AVS 75 059751
DHW sensor kit 1 QAZ 36 059261 External sensor kit 1 QAC 34 059260
Appliance
reference
Order No.
Page 70 / 146 00BNO9061-J
VARMAX - Installation, Use and Maintenance
Diagram VX110
C. CUSTOMER ELECTRICAL CONNECTION
DHW
circulator
Q3
Alarm
relay
}
Mains supply 230
VAC 50 Hz
L NY1 NY2L NL NL N
QX2 QX3 QX1 AUX2 AUX1
}
BX2 Gnd BX3 Gnd
B3
Gnd
B9
Gnd
page 2 / 5
DHW sensor B3
}
External sensor B9
}
QX21
}
QX22
}
QX23
N
AVS75
N
Mixing valve for heating
circuit No. 1 Y1/Y2
Circulator for heating circuit
No. 1 Q2
D. SPECIFIC START-UP PROCEDURE
BX21
Gnd
BX22
Gnd
H2
Gnd
H1
Gnd
H5
Gnd
Module 1
}
Flow sensor for regulated circuit
}
B1
Fit the accessories and make their electrical connections.
WARNING:
!
Start up the boiler alone.
Make the following settings.
Edition: 06 / 2015 Page 71 / 146
Ensure the switches on the extension modules AVS75 are properly confi gured.
VARMAX - Installation, Use and Maintenance
• Time and date menu
Set the time
Set the date
Set the year
• Configuration menu
Start up the heating circuit 1
Confi gure the DHW pump
Confi gure extension module 1
• Heating circuit 1 menu
Set the comfort setting
Diagram VX110
Function of extension module 1 (6020) Heating circuit 1
page 3 / 5
Line No. Value
Time / minute (1) HH.MM
Day / month (2) DD.MM
Year (3) YYYY
Heating circuit 1 (5710) On
Output via relay QX2 (5891) Pump/valve ECS
Q3
Comfort setting temperature (710) - - -
Set the curve slope
• Switch the heating mode to permanent comfort
• Domestic hot water menu
Set the comfort setting
• Activate DHW mode
Heating curve slope (720) - - -
E. ELECTRICAL AND HYDRAULIC VALIDATION
• Input/output test menu
Check the outputs
Alarm relay
Comfort setpoint (1610) - - -
Line No. Value
Relay test (7700) Relay output QX1
DHW pump Q3
Opening V3V CC
Closing V3V CC
CC pump
Page 72 / 146 00BNO9061-J
Relay test (7700) Relay output QX2
Relay test (7700) Relay output QX21
module 1
Relay test (7700) Relay output QX22
module 1
Relay test (7700) Relay output QX23
module 1
VARMAX - Installation, Use and Maintenance
Diagram VX110
Line No. Value
Reset outputs...module... Relay test (7700) No test
Check sensor values
External sensor B9
DHW sensor B3
Flow sensor B1
• Configuration menu
Check the hydraulic diagram
DHW temperature B3/B38 (7750) in °C
Temperature sensor BX21 module 1 (7830) in °C
Information on heating circuits 3, 2 and 1 (6217) 3
External T° B9 (7730) in °C
Generator 1 check (6212) 14
Generator 2 check (6213) 0
Information on DHW (6215) 4
page 4 / 5
F. OPTIMISATION OF SETTINGS
Optimisation of heating circuit:
• Heating circuit 1 menu
Set the reduced setting
• CC1 time programme menu
Preselection
Adjust the time programme
• Circuit CC1 holiday menu
Preselection
Adjust the time programme
• Switch the heating mode to automatic
Line No. Value
Reduced temperature setting (712) - - -
Preselection (500) - - -
On / Off phases (501...506) - - -
Preselection (641) - - -
On / Off phases (642-643) - - -
AUTO
Optimisation of DHW:
Line No. Value
• Domestic hot water menu
Set the reduced setting
Set the DHW release mode
Edition: 06 / 2015 Page 73 / 146
Reduced setting (1612) - - -
DHW release (1620) Time programme 4/
DHW
VARMAX - Installation, Use and Maintenance
Diagram VX110
• Time programme 4 / ECS menu
Preselection
Adjust the time programme
• DHW storage tank menu
Adjust the boost
• Domestic hot water menu
Confi gure an anti-legionella function
Line No. Value
Preselection (560) - - -
On / Off phases (561...566) - - -
Starting value of boost temperature (5020) - - -
Anti-legionella function (1640) - - -
Periodic anti-legionella function
(1641)
Day week anti-legionella function (1642) - - -
Anti-legionella temperature setting (1645) - - -
- - -
page 5 / 5
Duration of anti-legionella function (1646) - - -
Maintenance optimisation:
It is possible to generate a maintenance message without harming the boiler. This maintenance message may appear when the 3 following meters have elapsed:
• Time since last maintenance (or commissioning): set parameter 7044 to 12 months
• Operating hours of the burner (parameter 7040)
• Number of start-ups (parameter 7042)
The last 2 parameters depend on the boiler room's hydraulic installation. It is recommended to use at least parameter 7044 for yearly maintenance.
Page 74 / 146 00BNO9061-J
VARMAX - Installation, Use and Maintenance
Secondary networks with existing regulation
communicating by LPB bus or 0...10V
A. HYDRAULIC DIAGRAM
COMMUNICATING REGULATOR
REGULATEUR COMMUNICANT
SIGNAL 0/10 V VERS LMS
ou bus LPB vers OCI345
0/10 V SIGNAL TO NAVISTEM B3000
or LPB bus to OCI345
SINGLE BOILER
Diagram
VX111
page 1 / 3
B3000
gure 58 - Diagram VX111
B. NECESSARY ADJUSTMENT ACCESSOR Y
Quantity
Communication kit for LPB bus 1 OCI 345 059572
Appliance
reference
Order No.
Edition: 06 / 2015 Page 75 / 146
VARMAX - Installation, Use and Maintenance
Diagram VX111
C. CUSTOMER ELECTRICAL CONNECTION
Alarm
relay
Mains supply 230
VAC 50 Hz
LPB bus
L NY1 NY2L NL NL N
QX2 QX3 QX1 AUX2 AUX1
}
DB MB
}
BX2 Gnd BX3 Gnd
B3
Gnd
B9
Gnd
H1
Gnd
page 2 / 3
Analogue input
}
0...10V
D. SPECIFIC START-UP PROCEDURE
Fit the accessories and make their electrical connections.
Start up the boiler alone.
Make the following settings:
• Time and date menu
Set the time Set the date Set the year
For a demand via input 0...10V
• Configuration menu
Confi gure input H1
H5
Gnd
Line No. Value
Time / minute (1) HH.MM
Day / month (2) DD.MM
Year (3) YYYY
Input function H1 (5950) Demand from
circulation circuit 1 10V
Voltage value 1 H1 (5953) 0.0
Function value H1 (5954) 0
Voltage value 2 H1 (5955) 10.0
Page 76 / 146 00BNO9061-J
VARMAX - Installation, Use and Maintenance
Diagram VX111
Function value 2 H1 (5956) 1000 (for 10 V = 100
For a demand via LPB (LPB network menu)
• LPB network menu
Check that the boiler has been defi ned as the master generator
Appliance address (6600) 1
Bus supply function (6604) Automatic
E. ELECTRICAL AND HYDRAULIC VALIDATION
For a demand via input 0...10V
• Input/output test menu
Voltage in H1
page 3 / 3
Line No. Value
°C equivalence)
Segment address (6601) 0
Clock function (6640) Slave with
adjustment
Voltage signal H1 (7840) To validate with
the voltage sent by the boiler room machine
For a demand via LPB
If the boiler room regulator is confi gured as the master clock, the boiler command table must recover the date and time.
In both cases
• Configuration menu
Check the hydraulic diagram
Information on heating circuits 3, 2 and 1 (6217) 0
Generator 1 check (6212) 14
Generator 2 check (6213) 0
Information on DHW (6215) 0
F. OPTIMISATION OF SETTINGS
Maintenance optimisation:
It is possible to generate a maintenance message without harming the boiler. This maintenance message may appear when the 3 following meters have elapsed:
• Time since last maintenance (or commissioning): set parameter 7044 to 12 months
• Operating hours of the burner (parameter 7040)
• Number of start-ups (parameter 7042)
The last 2 parameters depend on the boiler room's hydraulic installation. It is recommended to use at least parameter 7044 for yearly maintenance.
Edition: 06 / 2015 Page 77 / 146
VARMAX - Installation, Use and Maintenance
SINGLE BOILER
1 network regulated by a 3-channel valve, 1 direct circuit
with 60°C low level
A. HYDRAULIC DIAGRAM
DIRECT CIRCUIT
B9
B1
Q2
Y1/Y2
x
CIRCUIT DIRECT
WITH LOW LEVEL
AVEC TALON BAS
FOR FLOW AT 60°C
DEPART A 60 °C
Q6
Diagram
VX113
page 1 / 4
B3000
gure 59 - Diagram VX113
B. NECESSARY ADJUSTMENT ACCESSORIES
Quantity
Extension module kit (delivered with a QAD 36 network sensor)
1 AVS 75 059751
External sensor kit 1 QAC 34 059260
Appliance
reference
Order No.
Page 78 / 146 00BNO9061-J
VARMAX - Installation, Use and Maintenance
Diagram VX113
C. CUSTOMER ELECTRICAL CONNECTION
Direct
circulation
pump Q6
Alarm
relay
}
Mains supply 230
VAC 50 Hz
L NY1 NY2L NL NL N
QX2 QX3 QX1 AUX2 AUX1
}
BX2 Gnd BX3 Gnd
B3
Gnd
B9
Gnd
page 2 / 4
External sensor B9
}
QX21
}
QX22
}
QX23
N
AVS75
N
Mixing valve for heating
circuit No. 1 Y1/Y2
Circulator for heating circuit
No. 1 Q2
D. SPECIFIC START-UP PROCEDURE
BX21
Gnd
BX22
Gnd
H2
Gnd
H1
Gnd
H5
Gnd
Module 1
}
Flow sensor for regulated circuit
}
B1
Fit the accessories and make their electrical connections.
WARNING:
!
Start up the boiler alone.
Make the following settings.
Edition: 06 / 2015 Page 79 / 146
Ensure the switches on extension module AVS75 are correctly confi gured.
VARMAX - Installation, Use and Maintenance
• Time and date menu
Set the time
Set the date
Set the year
• Configuration menu
Start up the heating circuit 1
Start up the heating circuit 2
Confi gure the pump CC2
Confi gure extension module 1
• Heating circuit 1 menu
Diagram VX113
page 3 / 4
Line No. Value
Time / minute (1) HH.MM
Day / month (2) DD.MM
Year (3) YYYY
Heating circuit 1 (5710) On
Heating circuit 2 (5715) On
Output via relay QX2 (5891) Pump CC2 Q6
Function of extension module 1
(6020)
Heating circuit 1
Set the comfort setting
Set the curve slope
• Heating circuit 2 menu
Set the comfort setting
Set the curve slope
Set the minimum starting temperature
• Switch the heating mode to permanent comfort
Comfort setting temperature (710) - - -
Heating curve slope (720) - - -
Comfort setting temperature (1010) - - -
Heating curve slope (1020) - - -
Minimum starting T° value (1040) 60°C (adjust
E. ELECTRICAL AND HYDRAULIC VALIDATION
• Input/output test menu
Check the outputs
depending on low level)
Line No. Value
Alarm relay
CC2 pump
Opening V3V CC
Closing V3V CC
Page 80 / 146 00BNO9061-J
Relay test (7700) Relay output QX1
Relay test (7700) Relay output QX2
Relay test (7700) Relay output QX21
module 1
Relay test (7700) Relay output QX22
module 1
VARMAX - Installation, Use and Maintenance
Diagram VX113
Line No. Value
CC pump Relay test (7700) Relay output QX23
Reset outputs
Check sensor values
External sensor B9
Flow sensor B1
• Configuration menu
Check the hydraulic diagram
Temperature sensor BX21 module 1 (7830) in °C
Generator 1 check (6212) 14
Generator 2 check (6213) 0
Information on DHW (6215) 0
Information on heating circuits 3, 2 and 1 (6217) 203
Relay test (7700) No test
External T° B9 (7730) in °C
page 4 / 4
module 1
F. OPTIMISATION OF SETTINGS
• Heating circuit 1 / 2 menu
Set the reduced setting
• Time programme CC1 / CC2 menu
Preselection
Adjust the time programme
• Holiday circuit CC1 / CC2 menu
Preselection
Adjust the time programme
• Switch the heating mode to automatic
Maintenance optimisation:
Line No. Value
Temperature of reduced setting (712/1012) - - -
Preselection (500/520) - - -
On / Off phases (501...506)
(521...526)
Preselection (641/651) - - -
On / Off phases (642-643)
(652-653)
- - -
- - -
AUTO
It is possible to generate a maintenance message without harming the boiler. This maintenance message may appear when the 3 following meters have elapsed:
• Time since last maintenance (or commissioning): set parameter 7044 to 12 months
• Operating hours of the burner (parameter 7040)
• Number of start-ups (parameter 7042)
The last 2 parameters depend on the boiler room's hydraulic installation. It is recommended to use at least parameter 7044 for yearly maintenance.
Edition: 06 / 2015 Page 81 / 146
VARMAX - Installation, Use and Maintenance
SINGLE BOILER
1 network regulated by a three-channel valve, 1 circulation
circuit with constant temperature and throughput
A. HYDRAULIC DIAGRAM
DIRECT CIRCUIT WITH
CIRCUIT DIRECT AVEC
CONSTANT TEMPERATURE
TEMPERATURE ET DEBIT
AND THROUGHPUT
B9
B1
Q2
Y1/Y2
x
CONSTANT
Q15
Diagram
VX120
page 1 / 4
B3000
gure 60 - Diagram VX120
B. NECESSARY ADJUSTMENT ACCESSORIES
Quantity
Extension module kit (delivered with a QAD 36 network sensor)
1 AVS 75 059751
External sensor kit 1 QAC 34 059260
Appliance
reference
Order No.
Page 82 / 146 00BNO9061-J
VARMAX - Installation, Use and Maintenance
Diagram VX120
C. CUSTOMER ELECTRICAL CONNECTION
Direct
circulation
pump Q15
Alarm
relay
}
Mains supply 230
VAC 50 Hz
L NY1 NY2L NL NL N
QX2 QX3 QX1 AUX2 AUX1
}
BX2 Gnd BX3 Gnd
B3
Gnd
B9
Gnd
page 2 / 4
External sensor B9
}
QX21
}
QX22
}
QX23
N
AVS75
N
Mixing valve for heating
circuit No. 1 Y1/Y2
Circulator for heating circuit
No. 1 Q2
D. SPECIFIC START-UP PROCEDURE
Fit the accessories and make their electrical connections.
BX21
Gnd
BX22
Gnd
H2
Gnd
H1
Gnd
H5
Gnd
Module 1
}
Flow sensor for regulated circuit
}
B1
Shunt to install
WARNING:
!
Start up the boiler alone.
Make the following settings.
Edition: 06 / 2015 Page 83 / 146
Ensure the switches on extension module AVS75 are correctly confi gured.
VARMAX - Installation, Use and Maintenance
• Time and date menu
Set the time
Set the date
Set the year
• Configuration menu
Start up the heating circuit 1
Confi gure pump Q15
Confi gure input H1
Confi gure extension module 1
Diagram VX120
Function of extension module 1 (6020) Heating circuit 1
page 3 / 4
Line No. Value
Time / minute (1) HH.MM
Day / month (2) DD.MM
Year (3) YYYY
Heating circuit 1 (5710) On
Output via relay QX2 (5891) Pump for circulation
circuit 1 Q15
Input function H1 (5891 Demand for
circulation circuit 1
• Heating circuit 1 menu
Set the comfort setting
Set the curve slope
• Circulation circuit 1 menu
Set the starting value to use in the event of demand from the circulation circuit
• Switch the heating mode to permanent comfort
Comfort setting temperature (710) - - -
Heating curve slope (720) - - -
Value of starting temperature for
circulation circuit demand (1859)
E. ELECTRICAL AND HYDRAULIC VALIDATION
• Input/output test menu
Check the outputs
Alarm relay
- - -
Line No. Value
Relay test (7700) Relay output QX1
Constant circuit pump
Opening V3V CC
Closing V3V CC
CC pump
Reset outputs
Page 84 / 146 00BNO9061-J
Relay test (7700) Relay output QX2
Relay test (7700) Relay output QX21
module 1
Relay test (7700) Relay output QX22
module 1
Relay test (7700) Relay output QX23
module 1
Relay test (7700) No test
VARMAX - Installation, Use and Maintenance
Diagram VX120
Check sensor values
External sensor B9
Flow sensor B1
• Configuration menu
Check the hydraulic diagram
F. OPTIMISATION OF SETTINGS
page 4 / 4
Line No. Value
External T° B9 (7730) in °C
Temperature sensor BX21 module 1 (7830) in °C
Generator 1 check (6212) 14
Generator 2 check (6213) 0
Information on DHW (6215) 0
Information on heating circuits 3, 2 and 1 (6217) 3
Line No. Value
• Heating circuit 1 menu
Set the reduced setting
• CC1 time programme menu
Preselection
Adjust the time programme
• Circuit CC1 holiday menu
Preselection
Adjust the time programme
• Switch the heating mode to automatic
Maintenance optimisation:
Reduced temperature setting (712) - - -
Preselection (500) - - -
On / Off phases (501...506) - - -
Preselection (641) - - -
On / Off phases (642-643) - - -
AUTO
It is possible to generate a maintenance message without harming the boiler. This maintenance message may appear when the 3 following meters have elapsed:
• Time since last maintenance (or commissioning): set parameter 7044 to 12 months
• Operating hours of the burner (parameter 7040)
• Number of start-ups (parameter 7042)
The last 2 parameters depend on the boiler room's hydraulic installation. It is recommended to use at least parameter 7044 for yearly maintenance.
Edition: 06 / 2015 Page 85 / 146
VARMAX - Installation, Use and Maintenance
x
B3000
B3000
REGULATEUR NON COMMUNICANT
BOILERS IN A CASCADE CONFIGURATION
1 direct network, no communication with the secondary
network
A. MAIN AND ALTERNATIVE HYDRAULIC DIAGRAMS
B9
x
Diagram
VX200 VX201
page 1 / 6
Q2
B10
B9
B3000
B3000
gure 61 - Diagram VX200
NON-COMMUNICATING REGULATOR
Q1.2Q1.1
B10
Q1.2
Q1.1
gure 62 - Diagram VX201 (alternative)
Page 86 / 146 00BNO9061-J
VARMAX - Installation, Use and Maintenance
Diagrams: VX200 / VX201
page 2 / 6
B. NECESSARY ADJUSTMENT ACCESSORIES
Quantity
Communication kit 2 OCI 345 059572
Network sensor kit 1 QAx 36
External sensor kit 1 QAC 34 059260
Appliance
reference
Order No.
059261 (QAZ 36)
059592 (QAD 36)
C. CUSTOMER ELECTRICAL CONNECTION
Boiler No. 1:
INFORMATION:
If the insulating valve is not fi tted with an automatic reset, reconnect the Q1.1 insulating valve closing contact on Y2.
Mains supply 230
VAC 50 Hz
LPB bus
}
DB MB
Diagram VX200:
Circulation pump on
direct circuit Q2
}
L NY1 NY2L NL NL N
QX2 QX3 QX1 AUX2 AUX1
Insulating
valve Q1.1
}
Alarm
relay
}
BX2 Gnd BX3 Gnd
B3
Gnd
B9
Gnd
H1
Gnd
Flow sensor in
}
cascade B10
External sensor B9
}
H5
Gnd
Boiler No. 2:
INFORMATION:
Edition: 06 / 2015 Page 87 / 146
If the insulating valve is not fi tted with an automatic reset, reconnect the Q1.2 insulating valve closing contact on Y2.
VARMAX - Installation, Use and Maintenance
Mains supply 230
VAC 50 Hz
LPB bus
}
DB MB
Diagrams: VX200 / VX201
Insulating
valve Q1.2
Alarm
relay
}
L NY1 NY2L NL NL N
QX2 QX3 QX1 AUX2 AUX1
page 3 / 6
}
D. SPECIFIC START-UP PROCEDURE
Fit the accessories and make their electrical connections.
Start up the boiler alone.
Make the following settings:
On boiler No. 1: master
• Set the time and date: Time and date menu
Set the time
Set the date
Set the year
• Configuration menu
Start up the heating circuit 1
Diagram VX200 only:
Confi gure the pump Q2
Line No. Value
Time / minute (1) HH.MM
Day / month (2) DD.MM
Year (3) YYYY
Heating circuit 1 (5710) On
QX2 relay outlet (5891) Pump CC1 Q2
All diagrams:
Con gure ow sensor in cascade B10 Sensor input BX2 (5931) Common fl ow
sensor B10
Page 88 / 146 00BNO9061-J
VARMAX - Installation, Use and Maintenance
Diagrams: VX200 / VX201
• Confi gure as master in the cascade: LPB network menu
Appliance number
Segment number
Set the bus power supply.
Set the clock mode
• Set the heating circuit: Heating circuit 1 menu
Set the comfort setting
Set the curve slope
• Switch the heating mode to permanent comfort
Comfort setting temperature (710) - - -
Appliance address (6600) 1
Segment address (6601) 0
Bus supply function (6604) Automatic
Heating curve slope (720) - - -
page 4 / 6
Line No. Value
Clock function (6640) Master
On boiler(s) No. 2 (and later): slave
Line No. Value
• Con gure as slave in the cascade: LPB network menu
Appliance number
Segment number
Set the bus power supply.
Set the clock mode
• Connect the bus between the boilers (
• Turn off the slave boiler(s) and then turn on again. If communication is successful, the clock is correctly updated.
respect the polarity).
!
Appliance address (6600) 2 (or later for the
other slaves)
Segment address (6601) 0
Bus supply function (6604) Automatic
Clock function (6640) Slave without
adjustment
E. ELECTRICAL AND HYDRAULIC VALIDATION
On boiler No. 1: master
Line No. Value
• Cascade diagnostic menu
Check that all boilers are present in the cascade
Status of generator 1 (8100) Released / not
released
Status of generator 2 (8101) Released / not
released
Edition: 06 / 2015 Page 89 / 146
VARMAX - Installation, Use and Maintenance
Diagrams: VX200 / VX201
• Input/output test menu
Check the outputs
Alarm relay
Pump Q2 (diagram VX200)
Insulating valve Q1.1
Reset outputs
Check sensor values
External sensor B9
Flow sensor in cascade B10
page 5 / 6
Line No. Value
...............................
Relay test (7700) Relay output QX1
Relay test (7700) Relay output QX2
Relay test (7700) Relay output QX3
Relay test (7700) No test
External T° B9 (7730) in °C
Sensor T° BX2 (7821) in °C
• Configuration menu
Check the hydraulic diagram
Information on heating circuits 3, 2 and 1 (6217) 1
On boiler(s) No. 2 (and later): slave
• Input/output test menu
Check the outputs
Alarm relay
Insulating valve Q1.2
Reset outputs
• Configuration menu
Generator 1 check (6212) 14
Generator 2 check (6213) 0
Information on DHW (6215) 0
Line No. Value
Relay test (7700) Relay output QX1
Relay test (7700) Relay output QX3
Relay test (7700) No test
Check the hydraulic diagram
Information on heating circuits 3, 2 and 1 (6217) 0
Page 90 / 146 00BNO9061-J
Generator 1 check (6212) 14
Generator 2 check (6213) 0
Information on DHW (6215) 0
VARMAX - Installation, Use and Maintenance
Diagrams: VX200 / VX201
F. OPTIMISATION OF SETTINGS
On boiler No. 1: master
Optimisation of heating circuit:
• Heating circuit 1 menu
Set the reduced setting
• CC1 time programme menu
Preselection
Adjust the time programme
• Circuit CC1 holiday menu
Preselection
page 6 / 6
Line No. Value
Reduced temperature setting (712) - - -
Preselection (500) - - -
On / Off phases (501...506) - - -
Preselection (641) - - -
Adjust the time programme
• Switch the heating mode to automatic
On / Off phases (642-643) - - -
AUTO
Optimisation of the cascade:
The cascade may be optimised as required with the parameters of the Cascade menu. Refer to the LMS boiler command table instructions for more details.
Maintenance optimisation:
It is possible to generate a maintenance message without harming the boiler. This maintenance message may appear when the 3 following meters have elapsed:
• Time since last maintenance (or commissioning): set parameter 7044 to 12 months
• Operating hours of the burner (parameter 7040)
• Number of start-ups (parameter 7042)
The last 2 parameters depend on the boiler room's hydraulic installation. It is recommended to use at least parameter 7044 for yearly maintenance.
Edition: 06 / 2015 Page 91 / 146
VARMAX - Installation, Use and Maintenance
BOILERS IN A CASCADE CONFIGURATION
1 network regulated by a three-channel valve, DHW
production or 1 direct circuit with constant temperature and
throughput
A. HYDRAULIC DIAGRAM
B9
B10
x
B3000
Q1.1
B3000
Q1.2
B1
Q2
Y1/Y2
Q3
B3
Diagram
VX210 VX220
page 1 / 8
x
B3000
B9
Q1.1
gure 63 - Diagram VX210
B3000
Q1.2
DIRECT CIRCUIT WITH
CIRCUIT DIRECT AVEC
CONSTANT TEMPERATURE
TEMPERATURE ET DEBIT
AND THROUGHPUT
CONSTANT
B1
x
Q2
Q15
Y1/Y2
x
B10
gure 64 - Diagram VX220
Page 92 / 146 00BNO9061-J
VARMAX - Installation, Use and Maintenance
Diagrams: VX210 / VX220
page 2 / 8
B. NECESSARY ADJUSTMENT ACCESSORIES
Quantity
Extension module kit (delivered with a QAD 36 network sensor)
Communication kit 2 OCI 345 059572
Network sensor kit 1 QAx 36
DHW sensor kit (diagram VX210) 1 QAZ 36 059261 External sensor kit 1 QAC 34 059260
1 AVS 75 059751
Appliance
reference
Order No.
059261 (QAZ 36)
059592 (QAD 36)
C. CUSTOMER ELECTRICAL CONNECTION
Boiler No. 1:
INFORMATION:
Diagram VX210:
Diagram VX220:
Mains supply 230
DHW circulation pump Q3
Direct circulation pump Q15
VAC 50 Hz
LPB bus
DB MB
}
If the insulating valve is not fi tted with an automatic reset, reconnect the Q1.1 insulating valve closing contact on Y2.
Insulating
valve Q1.1
}
L NY1 NY2L NL NL N
QX2 QX3 QX1 AUX2 AUX1
}
Alarm
relay
}
BX2 Gnd BX3 Gnd
B3
Gnd
B9
Gnd
Flow sensor in
}
cascade B10
Diagram VX210:
}
DHW sensor B3
External sensor B9
}
H1
Gnd
H5
Gnd
Edition: 06 / 2015 Page 93 / 146
Diagram VX220:
Shunt to install
VARMAX - Installation, Use and Maintenance
Mixing valve for heating
circuit No. 1 Y1/Y2
Circulator for heating circuit
No. 1 Q2
Boiler No. 2:
INFORMATION:
Diagrams: VX210 / VX220
Module 1
Gnd
Gnd
H2
Gnd
}
Flow sensor for regulated circuit
}
B1
QX21
}
N
QX22
}
N
QX23
If the insulating valve is not fi tted with an automatic reset, reconnect the Q1.2 insulating valve closing contact on Y2.
AVS75
BX21
BX22
page 3 / 8
Mains supply 230
VAC 50 Hz
LPB bus
}
DB MB
Insulating
valve Q1.2
L NY1 NY2L NL NL N
QX2 QX3 QX1 AUX2 AUX1
Alarm
}
relay
}
Page 94 / 146 00BNO9061-J
VARMAX - Installation, Use and Maintenance
Diagrams: VX210 / VX220
D. SPECIFIC START-UP PROCEDURE
Fit the accessories and make their electrical connections.
WARNING:
!
Start up the boiler alone.
Make the following settings:
On boiler No. 1: master
• Time and date menu
Set the time
Set the date
Set the year
Ensure the switches on extension module AVS75 are correctly confi gured.
page 4 / 8
Line No. Value
Time / minute (1) HH.MM
Day / month (2) DD.MM
Year (3) YYYY
• Configuration menu
Con gure the DHW pump (diagram VX210)
Confi gure pump Q15 (diagram VX220)
Confi gure the fl ow sensor in cascade B10
Confi gure input H1 (diagram VX220)
Confi gure the extension module
• Con gure as master in the cascade: LPB network menu
Appliance number
Segment number
Set the bus power supply.
Set the clock mode
Function of extension module 1 (6020) Heating circuit 1
QX2 relay outlet (5891) Pump/valve ECS
QX2 relay outlet (5891) Pump for circulation
Sensor input BX2 (5931) Common fl ow
Input function H1 (5977) Demand for
Appliance address (6600) 1
Segment address (6601) 0
Bus supply function (6604) Automatic
Q3
circuit 1 Q15
sensor B10
circulation circuit 1
Clock function (6640) Master
• Heating circuit 1 menu
Set the comfort setting
Set the curve slope
• Switch the heating mode to permanent comfort
Edition: 06 / 2015 Page 95 / 146
Comfort setting temperature (710) - - -
Heating curve slope (720) - - -
VARMAX - Installation, Use and Maintenance
Diagrams: VX210 / VX220
Diagram VX210 only:
• Domestic hot water menu
Set the comfort setting
• Activate DHW mode
Diagram VX220 only:
• Circulation circuit 1 menu
Set the starting value to use in the event of a demand from the circulation circuit
Line No. Value
Comfort setpoint (1610) - - -
Value of starting temperature for
circulation circuit demand (1859)
page 5 / 8
- - -
On boiler(s) No. 2 (and later): slave
• Con gure as slave in the cascade: LPB network menu
Appliance number
Segment number
Set the bus power supply.
Set the clock mode
• Connect the bus between the boilers (
• Turn off the slave boiler(s) and then turn on again. If communication is successful, the clock is correctly updated.
respect the polarity).
!
Appliance address (6600) 2 (or later for the
other slaves)
Segment address (6601) 0
Bus supply function (6604) Automatic
Clock function (6640) Slave without
adjustment
E. ELECTRICAL AND HYDRAULIC VALIDATION
On boiler No. 1: master
• Cascade diagnostic menu
Check that all boilers are present in the cascade
Status of generator 1 (8100) Released / not
released
Status of generator 2 (8101) Released / not
released
Page 96 / 146 00BNO9061-J
VARMAX - Installation, Use and Maintenance
Diagrams: VX210 / VX220
• Input/output test menu
Check the outputs
Alarm relay
DHW pump Q3 (diagram VX210)
Constant circuit pump Q15 (diagram VX220)
Opening V3V CC
Closing V3V CC
CC pump
Reset outputs
page 6 / 8
Line No. Value
Relay test (7700) Relay output QX1
Relay test (7700) Relay output QX2
Relay test (7700) Relay output QX2
Relay test (7700) Relay output QX21
module 1
Relay test (7700) Relay output QX22
module 1
Relay test (7700) Relay output QX23
module 1
Relay test (7700) No test
Check sensor values
External sensor B9 External T° B9 (7730) in °C
DHW sensor B3
Flow sensor B1
• Configuration menu
Check the hydraulic diagram
On boiler No. 2: slave
• Input/output test menu
Check the outputs
Temperature sensor BX21 module 1 (7830) in °C
Information on heating circuits 3, 2 and 1 (6217) 3
DHW temperature B3/B38 (7750) in °C
Generator 1 check (6212) 14
Generator 2 check (6213) 0
Information on DHW (6215) 4
(
Diagram VX210)
0
(
Diagram VX220)
Alarm relay
Insulating valve Q1.2
Reset outputs
Edition: 06 / 2015 Page 97 / 146
Relay test (7700) Relay output QX1
Relay test (7700) Relay output QX3
Relay test (7700) No test
VARMAX - Installation, Use and Maintenance
Diagrams: VX210 / VX220
• Configuration menu
Check the hydraulic diagram
F. OPTIMISATION OF SETTINGS
Optimisation of heating circuit:
• Heating circuit 1 menu
Set the reduced setting
• CC1 time programme menu
page 7 / 8
Line No. Value
Generator 1 check (6212) 14
Generator 2 check (6213) 0
Information on DHW (6215) 0
Information on heating circuits 3, 2 and 1 (6217) 0
Reduced temperature setting (712) - - -
Preselection
Adjust the time programme
• Circuit CC1 holiday menu
Preselection
Adjust the time programme
• Switch the heating mode to automatic
Optimisation of DHW:
• Domestic hot water menu
Set the comfort setting
Set the DHW release mode
Preselection (500) - - -
On / Off phases (501...506) - - -
Preselection (641) - - -
On / Off phases (642-643) - - -
AUTO
Reduced setting (1612) - - -
DHW release (1620) Time programme 4/
DHW
• Time programme 4 / DHW menu
Preselection
Adjust the time programme
• DHW storage tank menu
Adjust the boost
Page 98 / 146 00BNO9061-J
Starting value of boost temperature (5020) - - -
On / Off phases (561...566) - - -
Preselection (560) - - -
VARMAX - Installation, Use and Maintenance
Diagrams: VX210 / VX220
Diagram VX210 only:
• Domestic hot water menu
Confi gure an anti-legionella function
Line No. Value
Anti-legionella function (1640) - - -
Periodic anti-legionella function
(1641)
Day week anti-legionella function (1642) - - -
Anti-legionella temperature setting (1645) - - -
Duration of anti-legionella function (1646) - - -
page 8 / 8
- - -
Optimisation of the cascade:
The cascade may be optimised as required with the parameters of the Cascade menu. Refer to the LMS boiler command table instructions for more details.
Maintenance optimisation:
It is possible to generate a maintenance message without harming the boiler. This maintenance message may appear when the 3 following meters have elapsed:
• Time since last maintenance (or commissioning): set parameter 7044 to 12 months
• Operating hours of the burner (parameter 7040)
• Number of start-ups (parameter 7042)
The last 2 parameters depend on the boiler room's hydraulic installation. It is recommended to use at least parameter 7044 for yearly maintenance.
Edition: 06 / 2015 Page 99 / 146
VARMAX - Installation, Use and Maintenance
BOILERS IN A CASCADE CONFIGURATION
Secondary networks regulated by external regulated
communicating by LPB bus or 0...10V
A. HYDRAULIC DIAGRAM
0/10 V SIGNAL TO NAVISTEM B3000
SIGNAL 0/10 V VERS LMS
or LPB BUS TO OCI345
ou bus LPB sur OCI 345
COMMUNICATING REGULATOR
REGULATEUR COMMUNICANT
B10
x
Diagram
VX211
page 1 / 6
Q1.1 Q1.2
B3000 B3000
gure 65 - Diagram VX211
B. NECESSARY ADJUSTMENT ACCESSORIES
Quantity
Communication kit 2 OCI 345 059572 Network sensor kit 1 QAx 36
Appliance
reference
Order No.
059261 (QAZ 36)
059592 (QAD 36)
Page 100 / 146 00BNO9061-J
Loading...