1. WARNINGS AND RECOMMENDATIONS ..............................................................................6
1.1. Transport and storage ................................................................................................................................... 6
1.2. Symbols used in this document. ................................................................................................................... 6
1.3. Qualifi cation of personnel for installing, adjusting, using and maintaining the equipment ............................ 6
1.5. Water characteristics ..................................................................................................................................... 7
2.3. Gas category ............................................................................................................................................... 10
2.4. Gas supply pressures ................................................................................................................................. 11
3.3. Combustion at 15°C and 1013 mbar ........................................................................................................... 15
3.4. Conditions of use ........................................................................................................................................ 17
4.1. Installation of the air fi lter and fi lter matting ................................................................................................. 18
4.2. Installing the boiler ...................................................................................................................................... 19
4.3. Opening / closing of casing doors ............................................................................................................... 20
4.4. Removing the control panel (MMI) .............................................................................................................. 20
4.5. Removing / refi tting the casing doors .......................................................................................................... 21
4.6. Removing / refi tting side panels .................................................................................................................. 22
4.7. Removing / refi tting the top panel ............................................................................................................... 22
6.2. Gas supply .................................................................................................................................................. 42
7.2. Verifi cation of the boiler's environment ........................................................................................................ 44
7.3. Replacing the air fi lter matting ..................................................................................................................... 44
7.8. Setting the gas valve ................................................................................................................................... 48
7.9. Gas fi lter cleaning ....................................................................................................................................... 50
7.10.Cleaning exchangers and changing seals .................................................................................................. 51
7.11.Cleaning the burner and changing the seals .............................................................................................. 53
8. END-OF-LIFE CYCLE OF THE APPARATUS ......................................................................56
9.2. Symbols used in the diagrams .................................................................................................................... 59
9.3. List of diagrams ........................................................................................................................................... 59
10. LIST OF SPARE PARTS .....................................................................................................116
11. TABLE OF CUSTOMER SETTINGS ..................................................................................127
12. ANNEX A .............................................................................................................................144
Page 4 / 146 00BNO9061-J
VARMAX - Installation, Use and Maintenance
Edition: 06 / 2015 Page 5 / 146
VARMAX - Installation, Use and Maintenance
1. WARNINGS AND RECOMMENDATIONS
PLEASE READ THIS MANUAL CAREFULLY BEFORE INSTALLING,
CARRYING OUT MAINTENANCE AND USING THE BOILER. IT CONTAINS
IMPORTANT SAFETY INFORMATION.
VARMAX boilers are available with 2/3 tappings or 4 tappings. It is not
INFORMATION:
1.1. Transport and storage
possible to transform a version with 2/3 tappings into a version with
4 tappings and vice versa.
The boiler:
- must be stored vertically in an environment where the temperature is
between -20°C and +55°C, and where relative humidity is between 5%
and 95%;
- must not be stacked,
- must be protected from humidity.
1.2. Symbols used in this document.
INFORMATION:This symbol draws attention to comments.
Not following these instructions may lead to
damage when installing or to other objects.
Not following these instructions may cause
injuries and serious material damage.
Not following these instructions may cause
electrocution.
!
!
WARNING:
DANGER:
DANGER:
1.3. Qualifi cation of personnel for installing, adjusting, using and
maintaining the equipment
Boiler installation, adjustment and maintenance operations must be
conducted by a qualifi ed and approved professional in accordance with
prevailing local and national regulations. These operations may require work
to be carried out with the power turned on and the casing doors (on the front
of the boiler) open.
Basic utilisation operations must be carried out with the casing doors closed.
1.4. Safety instructions
• Always switch the boiler off and shut off the general gas supply before
carrying out any work on the boiler.
• After performing work on the boiler (maintenance or breakdown), check
that there are no gas leaks from the installation.
Page 6 / 146 00BNO9061-J
!
!
DANGER:
DANGER:
DANGER:
VARMAX - Installation, Use and Maintenance
If you smell gas:
• Do not use a naked fl ame, do not smoke, do not turn on electrical
contacts or switches.
• Cut off the gas supply.
• Air the premises.
• Look for the leak and repair it.
If you see smoke:
• Switch off the boiler.
• Air the premises.
• Look for the leak and repair it.
This boiler's earth bonding is ensured with connecting cables (green/
yellow) and specifi c attachment screws. During any dismantling work,
make sure you reconnect the cables concerned; it is IMPERATIVE to
reuse the original attachment screws.
1.5. Water characteristics
The following rules apply as soon as the boiler is commissioned and remain
valid until the product's end-of-life.
DANGER:It is forbidden to use water containing glycol.
!
1.5.1. Preparation of the water circuit before commissioning the boiler
For all installation work (new or renovation), the water network pipes must be
meticulously cleaned. The purpose of cleaning prior to commissioning is to
remove germs and residues which are the cause of deposits.
In new installations in particular, residue from grease, oxidised metal and
even copper micro deposits must be removed.
In renovated installations, cleaning should focus on removing sludge and the
products of corrosion formed when the unit was last in operation.
There are two types of methods for cleaning and removing sludge: a high
intensity approach that takes a few hours and a slower, more gradual
approach that takes several weeks. This fi rst type of cleaning must be done
before connecting the new boiler, and with the second type, a fi lter should be
installed on the back of the boiler to capture loosened deposits.
Cleaning prior to commissioning helps to improve the equipment's
performance, reduce energy consumption and fi ght against scaling and
corrosion. This operation must be done by a professional (water treatment).
Edition: 06 / 2015 Page 7 / 146
VARMAX - Installation, Use and Maintenance
1.5.2. Protecting the unit against scaling
Water naturally contains dissolved calcium ions and carbonates that cause
scaling (calcium carbonate) to form. To prevent excessive deposits, take
precautions with regard to the water used to fi ll the unit TH < 10°f
Water must be added during the life of the boiler. The new water adds scaling
to the water system. The amount of fi ll water and the amount of make-up
water added throughout the unit's lifecycle must not be more than three times
the water capacity of the heating system. Also, the hardness of the make-up
water must be controlled. Make-up water: TH < 5°f
Adding a large amount of untreated water always contributes a signifi cant
amount of scaling. To monitor this and to detect problems, a system water
meter must be installed.
Failure to comply with these guidelines (such that the fi ll water plus the make-
up water is more than three times the water capacity of the heating system)
requires a full cleaning (to remove sludge and scaling) to be performed.
Additional precautions are required for operation:
- When the unit has a water softener, the equipment must be inspected
on a regular basis in order to ensure that it is not outputting chloriderich water into the system. The concentration of chlorides must always
remain below 50 mg/litre.
- To prevent the build-up of calcium deposits (such as on exchange
surfaces), the unit should be brought into service slowly, starting by
operating at a low power with high primary water fl ow.
- When the tap water lacks the desired qualities (e.g. high level of
hardness), water treatment is required. The fi ll water must be treated,
and whenever new water is added, the make-up water must also be
treated.
- Installations with multiple boilers require all of the boilers to be started
simultaneously at minimal power. Doing this prevents the calcium in the
water from depositing on the exchange surfaces of the fi rst boiler.
- When working on the unit, avoid draining it completely; only the required
parts of the system are to be drained.
The rules listed above are designed to minimise scaling on the exchange
surfaces and thus to increase the life of the boilers.
To optimise the equipment's operation, remove lime scale deposits. This
must be done by a specialised company. Also, before putting the unit into
service, verify that the heating system is not damaged (e.g. leaks). If it has
excessive scaling, the unit's settings for operation and for water treatment
must be adjusted.
1.5.3. Protecting steel and stainless steel boilers against corrosion
Corrosion can affect the iron components used in boilers and heating
systems, which is directly related to the presence of oxygen in the water
heater's water. Dissolved oxygen that enters the unit when it is being fi lled
for the fi rst time reacts with the equipment materials and quickly disappears.
Without refreshing the oxygen through signifi cant contributions of water, the
unit might not experience any damage whatsoever.
However, it is important to follow the sizing rules and installation guidelines
in order to prevent oxygen from continuously fl owing into the heating water.
Page 8 / 146 00BNO9061-J
VARMAX - Installation, Use and Maintenance
These rules include:
- Opt for an expansion vessel with a membrane rather than an open
expansion vessel that allows direct passage.
- Make sure pressure in the equipment is more than 1 bar when cold.
- Remove non-gas-tight components (permeable) and use gas-tight
equipment instead.
If the guidelines above are followed, the unit's system water has the proper
characteristics to last a long time: 8.2 < pH < 9.5 and concentration in
dissolved oxygen < 0.1 mg/litre.
If there is a chance that oxygen could enter the unit, you must take additional
precautions. Adding an oxygen scavenger (e.g. sodium sulphite) is highly
recommended. We recommend you contact specialised companies for
water treatment issues, which will be able to suggest:
- the appropriate treatment based on the characteristics of the installation,
- a monitoring and performance warranty contract.
For units in which the water comes into contact with heterogeneous materials,
such as copper or aluminium, appropriate treatment is recommended in order
to ensure that the unit will last. In most cases, this consists of adding corrosion
inhibitors (in the form of chemical solutions) to the unit. It is recommended to
contact water treatment specialists.
1.5.4. Unit monitoring
If the above recommendations are followed (new installation or renovation),
it should be suffi cient to:
- check the amount of make-up water (fi ll water volume + make-up water
volume < 3 times the unit volume.
- check the pH level (stable or slightly increasing).
- check the TH (stable or slightly decreasing).
We recommend these checks are carried out 2 to 3 times a year. Note that
monitoring the quantity of make-up water is critical to the long life of the unit.
If any of these three parameters deviates from the above recommendations,
refer to a water treatment specialist to correct the problem.
1.5.5. Installation of the plate exchanger
If the recommendations above cannot be met, you can set up a plate
exchanger to separate the primary system from the secondary system, which
protects the boiler from undesirable effects.
1.5.6. Installation of a fi ltration system
A fi ltration system (fi lter, sediment well, etc.) on the back of the boiler is
recommended in order to remove suspended particles from the unit.
Edition: 06 / 2015 Page 9 / 146
VARMAX - Installation, Use and Maintenance
2. APPROVALS
2.1. Compliance with European Directives
- Low voltage (2006/95/CE)
This appliance is not intended for use by persons (including children)
whose physical, sensory or mental abilities are reduced, or persons
without experience or knowledge, unless they have been able to
benefi t, through someone responsible for their safety, from supervision
or prior instruction concerning the use of the appliance.
Children must be supervised to ensure they do not play with the
appliance.
- Electromagnetic compatibility (2004/108/CEE)
- Gas appliances (2009/142/CE)
- Effi ciency (92/42/CEE) until 26/09/2015
- Eco-design (2009/125/EC): from 26/09/2015
In application of the directive and according to the requirements of
the EU regulation No. 813/2013 of 02 August 2013, the technical
parameters of condensation boilers with a power of less than or equal
to 400 kW are available in appendix A.
2.2. Regulatory installation conditions
The appliance must be installed by an approved professional in accordance
with regulations and current professional practices.
2.3. Gas category
This boiler has been adjusted in the factory to work with group H (type G20)
natural gas with a supply pressure of 20 mbar.
INFORMATION:Any work on a sealed element leads to loss of warranty.
VARMAX 120 to 225
VARMAX 275 to 320
VARMAX 390 to 450
B23 - B23 P
C13 - C33 - C53
B23 - B23 P
C53
B23 - B23 P
C53
Category
DK, EE, FI, HU,
LV, NO, SE, TR
I
2H
I
2H
I
2H
CZ, GR, GB, IE,
LT, RO, SI, SK
II
2H3P
I
2H
II
2H3P
I
2H
I
2H
Page 10 / 146 00BNO9061-J
2.4. Gas supply pressures
INFORMATION:The pressures given below must be read at the gas valve inlet.
VARMAX - Installation, Use and Maintenance
Natural gas H G20
20 mbar
G31 Propane gas
(for relevant models
and countries only)
Nominal pressure (mbar)2037
Minimum pressure (mbar)1725
Maximum pressure (mbar)2545
Edition: 06 / 2015 Page 11 / 146
VARMAX - Installation, Use and Maintenance
3. TECHNICAL SPECIFICATIONS
3.1. Dimensions
A
ø AA
B
3°
F
45 mini
60 maxi
S
R
D
E
T
ø
C
ø U
G
ø V
ø W
ø X
L
ø X
Condensate
removal
HI
J
K
ø X
ø X
ø U
Y
Z
R
L
(B23-B23P)
Q
P
O
M
N
U0501956-#
fi gure 1 - Dimensions
Page 12 / 146 00BNO9061-J
VARMAX - Installation, Use and Maintenance
MODELS
120140180225275320390450
A(mm)734734812912
B(mm)1530178018772023
C(mm)1189121813411392
D(mm)148169169168
E(mm)10315010992
F(mm)510630680750
G(mm)138,5138,5138,5138,5
H(mm)115192241274,5
I(mm)350,5350,5399,5449,5
J(mm)150,5150,5200209,5
K(mm)166,5150,5179192
L(mm)1256156416721874
M(mm)165165165165
N(mm)182197,5196,5206,5
O(mm)926117112651402
P(mm)1062131514131577,5
Q(mm)1298160616611933
R(mm)212212244244
S(mm)163163163183
Ø T(*): Smoke outlet(mm)150150180200
Ø U: Purge connecting sleeve1 "1 "1 "1 "
Ø V(*): Air inlet(mm)150150180180
Ø W: Gas connecting sleeve G20
G31
1 " 1/4
1 " 1/4
1 " 1/2
1 " 1/2
2 "
2 "
2 "
--
Ø X: Out / In connecting sleeve2 "DN 65DN 80DN 80
Y(mm)250,5247276289,5
Z(mm)237224,5270,5283,5
Ø AA: Valve connecting sleeve1 "1 "1 " 1/41 " 1/4
(*) The diameter indicated is the inside diameter (only for Ø T and Ø V).
Edition: 06 / 2015 Page 13 / 146
VARMAX - Installation, Use and Maintenance
3.2. Doorways
VARMAX 120 to 225 boilers fi t through doors 700 mm wide with the casing
on (boiler with doors and side jackets).
VARMAX 275 to 320 boilers fi t through doors 735 mm wide without the casing
on (boiler without doors, without side jackets and without side insulating
panels).
However, it is possible to pass through the 700 mm doors if the following
parts are removed, in addition to the parts mentioned above:
• the two inspection doors with their 16 fastening clamps,
• the two lower hinge lugs of the front housing doors (with the step),
• the two upper hinge lugs of the front housing doors (with the step),
• all the cable clamps at the inlet of the high- and low- current wiring
gutter.
VARMAX 390 to 450 boilers fi t through doors 800 mm wide without the casing
on, which means that the following parts must be removed:
• the two front housing doors,
• the side insulating jackets,
• the side insulating panels
• the two lower hinge lugs of the front housing doors (with the step),
• the two upper hinge lugs of the front housing doors (with the step),
• all the cable clamps at the inlet of the high- and low- current wiring
gutter.
Page 14 / 146 00BNO9061-J
3.3. Combustion at 15°C and 1013 mbar
3.3.1. G20 Natural Gas
120140180225275320390450
VARMAX - Installation, Use and Maintenance
MODELS
Nominal power Pn
(80/60°C)
Nominal power when
condensing P (50/30°C)
kW117136175219268312381439
kW127148191238290338415478
Nominal heat input QnkW120140180225275320390450
Minimum heat input
Qmin
Gas fl ow rate at Pnm
CO
value ranges%
2
Flue-gas mass fl ow rate
at Qn / Qmin (80/60°C)
Flue-gas mass fl ow rate
at Qn / Qmin (50/30°C)
Flue-gas temperature at
Qn / Qmin (80/60°C)
Flue-gas temperature at
Qn / Qmin (50/30°C)
Appliance pressure at
nominal Qcal (B23)
Inside diameter of fl ue-
gas output
Maximum allowable
nozzle pressure (B23P) at
Qn / Qmin (80/60°C)
Maximum allowable
nozzle pressure (B23P) at
Qn / Qmin (50/30°C)
Combustion air fl ow rate
at Qn
kW2828434366668787
3
/h12,714,8119,0523,8129,133,8641,347,6
g/s
g/s
°C
°C
52,8 / 1361,3 /
13,1
49,1 /
12,3
60,8 /
56,9
35,7 /
28,8
57,6 /
12,2
62,1 /
57,3
37,7 /
30,2
Qmin : 8,3 % < CO
Qmax : 8,8 % < CO
80,4 /
20,8
75,9 /
19,5
61,0 /
56,6
33,7 /
30,0
99,5 /
21,1
93,0 /
19,5
62,3 /
57,7
36,9 /
30,2
< 8,7 %
2
< 9,2 %
2
113,9 /
26,9
108,7 /
17,1
61,7 /
58,3
36,3 /
29,8
133,2 /
29,1
126,3 /
27,1
63,4 /
57,2
36,2 /
28,3
169 /
39,2
159,6 /
36,7
62,5 /
57,4
200,7 /
35,6
191 /
33,4
64,8 /
57,1
36,7 / 3041,7 /
30,2
Pa88108103147132162152203
mm150150150150180180200200
Pa
Pa
m
200 /5200 / 5115 /5165 /5122 /
5
166 /5164 /
5
3
/h153,8179,4230,7288,3352,4410,1499,8576,7
92 /
5
128 /
5
97 /
5
176 /5180 /5193 /
5
145 /5155 /5173 /
5
NOx class5
Flue-gas removal and air inlet
type classifi cations
Edition: 06 / 2015 Page 15 / 146
B23, B23P
C13, C33, C53
B23, B23P
C53
VARMAX - Installation, Use and Maintenance
3.3.2. G31 Propane Gas (for relevant models and destination countries)
MODELS
120140180225275320
Nominal power Pn (80/60°C)kW117136175219268312
Nominal power when condensing P
(50/30°C)
kW127148191238290338
Nominal heat input QnkW120140180225275320
Minimum heat input Qmin kW393963639090
Gas fl ow rate at Pnm
CO
value ranges%
2
Flue-gas mass fl ow rate at Qn / Qmin
(80/60°C)
Flue-gas mass fl ow rate at Qn / Qmin
(50/30°C)
Flue-gas temperature at Qn / Qmin
(80/60°C)
Flue-gas temperature at Qn / Qmin
(50/30°C)
3
/h4,915,737,369,2111,2513,09
g/s
g/s
°C
°C
53 /
18,3
50,2 /
17,3
60,3 /
56,7
34,6 /
30,6
Qmin : 9,8 % < CO
Qmax : 10,4 % < CO
61,8 /
18,3
58,7 /
17,3
62,6 /
56,7
37,1 /
80 /
29
80 /
28
60,3 /
57,1
37,1 / 3137 /
28,9
< 10,2 %
2
< 10,8 %
2
100 /29122 /42142 /
96 /
117 /39136 /
28
62,2 /
63 / 5865,4 /
57,6
40 /2941,4 /
29,4
42
40
58,4
31,3
Appliance pressure at nominal Qcal (B23)Pa6895102140123165
Inside diameter of fl ue-gas outputmm150150150150180180
Maximum allowable nozzle pressure
(B23P) at Qn / Qmin (80/60°C)
Maximum allowable nozzle pressure
(B23P) at Qn / Qmin (50/30°C)
Pa
Pa
167 / 12200 /8103 /4136 / 7118 / 11157 /
11
140 / 16169 / 1166 /
7
104 /7104 / 16138 /
13
Combustion air fl ow rate at Qnm3/h153,8179,4230,7288,3352,4410,1
NOx class5
Flue-gas removal and air inlet type
classifi cations
B23, B23P
Page 16 / 146 00BNO9061-J
VARMAX - Installation, Use and Maintenance
3.4. Conditions of use
MODELS
120140180225275320390450
Maximum start setting temperature°C85
Start maximum temperature°C88
Safety temperature°C110
Maximum service pressure
Minimum cold pressure
hPa
(bar)
hPa
(bar)
Hydraulic pressure loss at ∆T20
version with 2 or 3 tappings6007505708108201185770970
version with 4 tappings
Main exchanger
Condenser
Nominal water fl ow rate (P/20)m
Maximal water fl ow rate (P/10)m
daPa
500
110
3
/h5,05,87,59,411,513,416,418,9
3
/h10,011,615,018,823,026,832,837,8
650
120
440556607579050106065660
Water contentL116116151151239239287287
Weight without waterkg340340393393502502592592
Sound power at P
Sound power at 1 m at P
Temperature of installation room
(min. / max.)
(Lw) *dB(A)80767784
max
(Lp) *dB(A)65616168
max
°C5 / 45
Relative humidity of installation roombetween 5% and 95%
Protection levelIP20
Maximum altitude of installationm2000
6000
(6)
1000
(1)
190
840
230
* The sound power level is a laboratory measurement of the emitted sound power but contrary to the noise
level, it doesn't correspond to the perceived measurement.
3.5. Electrical connection
MODELS
120140180225275320390450
Electrical supplyV230 V AC (+10% -15%), 50Hz
Electrical power consumption at Qn
(without accessories)
Electrical power consumption in
standby mode
Max length of sensor cables
Power terminal output
W204311179320238352480660
W5
DHW sensor: 10
m
External sensor: 40 in 0.5 mm² (120 in 1.5 mm²)
Ambient thermostat: 200 in 1.5 mm²
Ambient sensor: 200 in 1.5 mm²
V230V AC (+10%, -15%)
A5 mA - 1A
Edition: 06 / 2015 Page 17 / 146
VARMAX - Installation, Use and Maintenance
4. INSTALLATION
Manipulation of the boiler using a hoist requires the use of a frame
!
DANGER:
4.1. Installation of the air fi lter and fi lter matting
(not supplied). This is COMPULSORY. Refer to the label stuck onto
the boiler's packaging.
!
protective
label
WARNING:
If connecting CHIMNEY B23 or B23P, it is COMPULSORY to fi t the air fi lter supplied with the boiler.
screws (x4)
fi gure 2 - Air fi lter
air fi lter
- Remove the protective "air intake" label.
- Insert the air fi lter and attach it to the boiler using
the 4 screws supplied with the fi lter.
U0502530-#
Models 120 to 320:
Models 390 and 450:
fi gure 3 - Filter matting
U0038318-B
mountings
U0024791-B
All models:
- Insert the rectangular fi lter matting between the
fi lter's protective grille and the mounting (see
opposite).
Ensure that the link between both ends of the
matting is under one of the mountings.
Models 390 and 450:
- Insert the square fi lter cloth on the back gate of
the fi lter.
Page 18 / 146 00BNO9061-J
4.2. Installing the boiler
VARMAX boilers must not be installed on an infl ammable surface (wooden
fl oor, plastic fl oor covering, etc.).
Recommended distances from walls and the fl oor:
Ensure there is suffi cient clearance so that work may be carried out easily
on the boilers.
The minimum values (in mm) are indicated in fi gure 4 and in the table below.
The hashed zone above the boiler must remain free of obstacles to
allow for inspections and cleaning of the burner.
!
WARNING:
A 2 cm free space must also be left above the side panels to allow for
their disassembly and reassembly.
These values cannot be replaced by specifi c regulatory requirements.
The boiler must be positioned horizontally using a spirit level to
!
Edition: 06 / 2015 Page 19 / 146
WARNING:
promote effective ventilation of the heat exchanger (use the base as
a reference surface).
To adjust the level, screw or unscrew the 4 adjustable feet as required using
a 17 mm wrench.
VARMAX - Installation, Use and Maintenance
4.3. Opening / closing of casing doors
Opening:
Put the handle locking system in a horizontal
position (mark 1) then press down on it.
The handle is released from its housing; you can
now open the right-hand door, followed by the left-
hand door.
Closing:
Close the left-hand door, followed by the right-
hand door.
Press the door's lever.
U0503482-#
fi gure 5 - Opening casing doors
4.4. Removing the control panel (MMI)
Put the handle locking system in a vertical position
(mark 1).
The control panel (MMI: Man Machine Interface)
may be removed from the casing door to:
• remove the left-hand casing door;
• view the display when setting or carrying out
maintenance work on the boiler;
Open the casing doors.
Remove the locking screw
back of the left-hand casing door.
accessible on the
fi gure 6 - Unlocking the control panel
Page 20 / 146 00BNO9061-J
VARMAX - Installation, Use and Maintenance
You can:
• put the control panel back
• fi t the control panel to the boiler (see opposite,
fi gure 7 - Positions of the control panel
4.5. Removing / refi tting the casing doors
With the doors open, remove the pin on the top of
the door to be removed.
-
-
or carrying out maintenance), or
so that the left-hand casing door can be removed
without any risk to the control panel).
(to view data displayed when adjusting
in its place
pin
Support the door during this operation
because once the pin has been removed, the
door is no longer attached to the boiler.
When refi tting, fi rstly position the bottom of the
door on the lug, and then the top, making sure to
fully insert the pin into its housing.
lug
U0502515-#
fi gure 8 - Removing casing doors
!
Edition: 06 / 2015 Page 21 / 146
WARNING:
Before removing the left-side casing door, do not forget to remove the
control panel (see next paragraph).
VARMAX - Installation, Use and Maintenance
4.6. Removing / refi tting side panels
locking
screw
Open the casing doors.
Remove the locking screw accessible via the
inside of the boiler.
Use the handle in the centre of the panel for this.
Lift up the panel vertically and remove.
When refi tting, re-fasten the locking screws from
inside the boiler after fi tting the panels.
handle
rear side panel
U0501963-#
fi gure 9 - Removing side panels
4.7. Removing / refi tting the top panel
removable part
Note: It may be necessary to remove the rear side
panels in order to fi t through doors. To do
this, unscrew the fi xing screws which hold the
panel onto the boiler's structure and remove
the panel.
Open the casing doors.
Loosen the 2 thumbscrews on the top of the boiler
(1 or 2 turns will be enough. It is not necessary or
recommended to unscrew them completely).
Slightly lift up the panel and remove it from the
front.
To refi t it, follow the procedure in reverse.
U0502250-#
fi gure 10 - Removing the upper panel
Page 22 / 146 00BNO9061-J
4.8. Step
fi gure 11 - Installing the step
VARMAX - Installation, Use and Maintenance
!
WARNING:
The step is a means to access the burner. It cannot be used as a work
platform.
There are steps on models 180 and above.
On models 180 to 320:
Open the doors.
Unfold the step.
U0502519-#
fi gure 12 - Installing the step on models 180-320
On models 390 and 450:
Open the doors.
Remove the blocking element of the step
Unfold the step.
Pull the lower step.
blocking element of the step
U0502519-#
fi gure 13 - Installing the step on models 390 and 450
Edition: 06 / 2015 Page 23 / 146
VARMAX - Installation, Use and Maintenance
4.9. Changing the gas type (G20 to G31)
The boiler has been adjusted in the factory to work with group H (type
G20) natural gas with a supply pressure of 20 mbar.
INFORMATION:
Its adaptation to suit any other type of gas must take place in
compliance with the regulations in effect in the country in which the
appliance is installed.
!
!
WARNING:
WARNING:
Any operations involving changing the type of gas used must be
performed by a qualifi ed professional.
ONLY for relevant boilers (see paragraph 2.6, page 13) and boilers
connected to B23 and B23P.
4.9.1. Changing prepurging, ignition, minimum and maximum speeds
Place the boiler in standby mode (see § 3.3.1 of the NAVISTEM B3000 boiler
command table instructions).
If necessary, press the ESC button to return to the main screen.
Access the Settings menu.
Adjust the prepurging speed (9504), ignition speed (9512), minimum speed
(9524) and maximum speed (9529) settings:
The type of gas is changed by installing the
diaphragm (brass part) provided with the boiler
(engraved B1P for 120 and 140 models or
engraved B3P for 275 and 320 models).
Unscrew the 4 nuts or screws depending on the
model (see opposite).
Install the diaphragm provided.
Screw the 4 nuts back in place.
nut (x4)
fi gure 14 - Diaphragm (120 and 140 models)
diaphragm
U0524542-#
Check the CO
settings (see § 7.7, page 52).
2
After changing the type of gas:
- Check the sealing of the gas line.
- Stick the label provided in place of the
original label (G20).
Note:
In order to facilitate the operation, the mounting
fl ange located at the entrance to the gas line (on
the side nearest the network connection) may
require unscrewing.
nut (x4)
diaphragm
U0503708-#
fi gure 15 - Diaphragm (275 and 320 models)
Edition: 06 / 2015 Page 25 / 146
VARMAX - Installation, Use and Maintenance
4.9.3. On VARMAX 180 and 225
The type of gas is changed by replacing the
diaphragm located on the gas line.
Unscrew the 4 nuts (see opposite), then remove
the diaphragm in place (brass part).
Replace this with that provided with the boiler
(engraved B2P).
Screw the 4 nuts back in place.
diaphragm
fi gure 16 - Diaphragm
4.10. Exhaust connection
Exhaust system works and national and prefectoral regulations must be
complied with.
A smoke temperature sensor guarantees the protection of exhaust ducts for
type B and C combustion products.
nut (x4)
U0503708-#
Check the CO
After changing the type of gas:
- Check the sealing of the gas line.
- Stick the label provided in place of the
original label (G20).
Note:
In order to facilitate the operation, the mounting
fl ange located at the entrance to the gas line (on
the side nearest the network connection) may
require unscrewing.
settings (see § 7.7, page 52).
2
VARMAX boilers are approved to be connected to:
• a B23 chimney (all models)
• a B23P chimney (all models)
• a C13 air vent (models 120 to 225) except for propane gas (G31)
• a C33 air vent (models 120 to 225) except for propane gas (G31)
• a C53 air vent (all models) except for propane gas (G31)
The lengths of the ducts provided below are in linear metres (lm). The total
INFORMATION:
length of all ducts is reduced to a straight length (elbows having a straight
equivalence).
4.10.1. Connection to a B23 chimney
Type B23 connection:
Air from the unit's premises, extraction of gases through the roof via a fl ue
with natural ventilation.
Check that there are top and bottom ventilations in the boiler premises,
!
WARNING:
that they comply with applicable regulations and that they are not
obstructed.
Page 26 / 146 00BNO9061-J
VARMAX - Installation, Use and Maintenance
Chimney fl ues must be dimensioned considering the combustible gas
pressure at the boiler outlet of 0 Pa (see table § 3.3, page 15).
The fl ue-gas extraction ducts must be made in a material resistant to the
condensate that can form when the boiler is operating. These materials
must also be capable of supporting temperatures up to 120°C. Horizontal
duct runs must be avoided so as not to cause condensate retention.
Check that the fuel gas is extracted via a gas-tight duct.
VARMAX boilers are effi cient boilers with very low fl ue-gas temperatures;
as a result, to maintain favourable ventilation, the ducts must run
upwards from the boiler outlet.
If several boilers are connected to a single fl ue, check:
1. that the fl ue is not under pressure when all the boilers are in
!
IMPORTANT:
operation.
2. If one of the boilers is operating at minimum power, that the
others do not discharge into it.
Sizing recommendations based on a POUJOULAT system (Condensor
type):
øduct
H
øconnection
3 m
fi gure 17 - B23 sizing recommendations
Edition: 06 / 2015 Page 27 / 146
VARMAX - Installation, Use and Maintenance
Height of fl ue-gas duct H in linear metres (lm)
(operating at 50/30°C)
ø
connection
ø
duct
Type of gasG20 G31 G20 G31 G20 G31 G20 G31 G20 G31
1202 to 52 ----3 to 39-----------1407
180----10
225--------1
275------------4
The above values are provided for information purposes only. It is
important to check them with a calculation.
The weight of fl ue-gas ducts must not be supported by the part
connecting to the boiler.
4.10.2. Connection to a B23P chimney
Type B23P connection:
Air coming from the boiler premises, extraction of gases through the roof via
a pressurised duct.
Check that there are top and bottom ventilations in the boiler premises,
!
!
WARNING:
IMPORTANT:
that they comply with applicable regulations and that they are not
obstructed.
For the B23P type connection, it is MANDATORY to use ducts which
have pressurised duct certifi cation, such as CONDENSOR (Poujoulat)
or rigid or fl exible CHEMILUX CONDENSATION (Ubbink).
The duct extracting combustion products must be sized using the
parameters provided in the table in paragraph 3.3.
Depending on the duct's actual confi guration, a calculation is
!
Page 28 / 146 00BNO9061-J
IMPORTANT:
necessary to check that the pressures at the boiler outlet do not
exceed the maximum normative values authorised (200 Pa).
Values corresponding to the 50/30°C regime are to be used for this
calculation.
VARMAX - Installation, Use and Maintenance
Cascade installation case
In this case, where boilers with different powers are connected, the most
powerful models must be closest to the chimney.
The boiler is equipped with an internal check valve smoke diverter, replacing
any other external and functionally identical system.
Sizing recommendations on the basis of a POUJOULAT system
(Condensor type):
ø duct
H
ø connection
3 m
fi gure 18 - B23P (Poujoulat) sizing recommendations
IMPORTANT:The weight of fl ue-gas ducts must not be supported by the boiler.
The above values are provided for information purposes only. It is
important to check them with a calculation.
VARMAX - Installation, Use and Maintenance
Sizing recommendations on the basis of a UBBINK system:
Using a Ubbink duct in PPTL
(reference 041432) at the boiler outlet.
fi gure 19 - B23P (Ubbink) sizing recommendations
ø160 requires a Male 150 / Female 160 adaptor
ø 160
H
ø 160
Height of fl ue-gas duct H in linear metres (lm)
(operating at 50/30°C)
ø
duct
Type of gasG20 G31 G20 G31
12010010010086
1401001008665
MODELS
!
!
IMPORTANT:
IMPORTANT:The weight of fl ue-gas ducts must not be supported by the boiler.
The above values are provided for information purposes only. It is
important to check them with a calculation.
180643230--
225584028--
rigidfl exible
160 mm
4.10.3. Rules for installing air vent terminals
Please refer to national standards and regulations.
Page 30 / 146 00BNO9061-J
4.10.4. Connection to a C13 or C33 air vent
Type C13 connection:
Air inlet and gas extraction via separate ducts connected to a horizontal
concentric terminal (air vent).
Type C33 connection:
Air inlet and gas extraction via separate ducts connected to a vertical
concentric terminal.
Connecting a VARMAX boiler in C13 or C33 confi guration requires use of
!
IMPORTANT:
the "Terminal kit" comprising a terminal, a dual-fl ow adaptor and a male
adaptor
ø150 / female adaptor ø160 (reference 041421).
VARMAX - Installation, Use and Maintenance
Ensure the slope from the concentric
terminal is 3°.
L2
ø160
ø150
L1
fi gure 20 - Type C13 connectionfi gure 21 - Type C33 connection
450 mm
maxi
U0501471-#
450 mm
maxi
ø160
ø150
L1
L2
U0501398-#
The table below shows the maximum straight lengths authorised for air and
fl ue-gas ducts.
MODELS
120140180225
L1 (air)16.5 lm13.5 lm
L2 (fl ue-gases)17.5 lm14.5 lm
The lengths indicated include the lengths of the concentric terminal.
Edition: 06 / 2015 Page 31 / 146
VARMAX - Installation, Use and Maintenance
In addition, in the duct length calculation, the following equivalences must
be used;
- 90° elbow = 1.5 m of straight duct
- 45° elbow = 0.8 m of straight duct
The terminal's installation must comply with the rules in § 4.10.3, page 30.
To facilitate mounting of fl ue-gas ducts (PPTL), coat the joints with liquid
soap or a suitable grease (provided in the "terminal kit").
!
IMPORTANT:
The weight of the ducts (air and fl ue-gas) must not be supported by
the boiler's connecting parts.
4.10.5. Connection to a C53 air vent
Type C53 connection:
Air inlet and gas extraction via 2 separate ducts.
!
IMPORTANT:
Connecting a VARMAX boiler in a C53 confi guration requires the use of
accessory kits.
The table below gives the reference of the available kits depending on the
boiler model and the maximum straight lengths authorised for the air and
fl ue-gas ducts.
MODELS
120140180225275320390450
Accessory kit reference041422041422041423041424
L1 (air)10 lm8 lm10 lm10 lm
L2 (fl ue-gas)40 lm39 lm40 lm40 lm
ø A (air duct)
ø F (fl ue-gas duct)
The lengths given include the lengths of the fl ue-gas terminal but do not
include the air terminal (measure taken on the outside of the wall).
In addition, in the duct length calculation, the following equivalences must
be used;
For ducts with diameters 150 mm and 160 mm:
- 90° elbow = 1.5 m of straight duct
- 45° elbow = 0.8 m of straight duct
For ducts with diameters 180 mm and 200 mm:
- 90° elbow = 2 m of straight duct
- 45° elbow = 1.1 m of straight duct
150 mm150 mm180 mm180 mm
160 mm160 mm180 mm200 mm
Page 32 / 146 00BNO9061-J
VARMAX - Installation, Use and Maintenance
The fl ue-gas terminal's installation must comply with rules in § 4.10.3, page
30.
Ensure the slope towards the boiler is at least 3° (fl ue-gas side). On the air
duct side, adjust a slope to the outside to avoid the risk of rainwater in the
boiler.
To facilitate mounting fl ue-gas ducts for models 120 to 225, coat the joints in
liquid soap or a suitable grease (provided in the "terminal kit").
450 mm
maxi
øF
L1
L2
øA
450 mm
maxi
450 mm
maxi
øF
L2
450 mm
maxi
L1
øA
U0501350-#
fi gure 22 - Type C53 connection (VARMAX
models 120 to 225)
!
Edition: 06 / 2015 Page 33 / 146
IMPORTANT:The weight of fl ue-gas ducts must not be supported by the boiler.
fi gure 23 - Type C53 connection (VARMAX
models 275 to 450)
U0501496-#
VARMAX - Installation, Use and Maintenance
4.11. Hydraulic connection
The presence of an integrated irrigation pump in the boiler and an
intelligent control logic enables optimal operation up to IUP/30 (IUP =
Instant Useful Power expressed in Th/h - 1Th/h = 1.163 kilowatts).
Below this throughput of IUP /30, the boiler will continue to operate, but
will gradually lose power (boiler stops below IUP /46).
In connector sleeves 3 and 4, there is no minimum throughput constraint
on the condenser.
In the main heat exchanger, as in the condenser, you must ensure
that you never exceed the throughput prescribed in section 3.4 (boiler
nominal useful power / 10).
Sizing the pipes connecting the boiler to the installation must be done
carefully, to minimise the pressure losses and so avoid oversized circulating
pumps.
In some cases the diameter of the connection pipes will be greater than the
diameter of the boiler tappings. The diameter can then be usefully increased
after the union connectors, the stop valves, and/or the hydraulic balancing
valves.
VARMAX boilers are equipped with the following elements:
• main exchanger drain valve,
• condenser drain valve.
It is mandatory to fi t the boiler and its installation with the following elements:
• isolating valves on the fl ow and return tappings,
• an expansion vessel,
• an effi cient bleed device,
• a safety valve set to 6 bar,
• A shut-off on the boiler's fi ll circuit in relation to the main supply.
VARMAX boilers are available with 2/3 tappings or 4 tappings. It is not
possible to transform a version with 2/3 tappings into a version with 4
tappings and vice versa.
4.11.1. Boiler with 2 or 3 tappings
Clamp obstructing
2nd return
Flow
2 tappings
If all the circuits have the same return temperatures,
the return tapping located in the lower part must
be used.
Return
U0501961-#
fi gure 24 - Connection with 2 tappings
Page 34 / 146 00BNO9061-J
Flow
nd
return
2
hot return (high temperature circuit)
VARMAX - Installation, Use and Maintenance
3 tappings
VARMAX boilers are fi tted with 2 returns and an
optimised internal water circuit allowing effective
separation of high temperature returns (coming
from DHW preparation circuits, radiators, etc.)
from low temperature circuits (underfl oor heating
circuits, low temperature radiator circuits, etc.).
This circuit separation encourages the
condensation of fl ue-gases in the lower part of
the condenser throughout the year, and therefore
considerably increases the boiler's performance.
cold return (underfl oor
heating and low
temperature radiators)
fi gure 25 - Connection with 3 tappings
4.11.2. Boiler with 4 tappings
1st return
U0501961-#
Main exchanger
fl ow
Condenser fl ow
To use the 2
nd
return, the clamp obstructing the
tapping must be removed.
VARMAX boilers are fi tted with 2 internal water
circuits allowing separation of high temperature
returns (coming from DHW preparation circuits,
radiators, etc.) from low temperature circuits
(underfl oor heating circuits, low temperature
radiator circuits, etc.).
main exchanger
return
Condenser return
fi gure 26 - Connection with 4 tappings
!
WARNING:
Do not connect DHW (domestic hot water) or swimming pool water to
the condenser circuit.
In some installations, additional improvement
may be obtained using 4 tappings. This separates
the condenser (low temperatures) from the main
exchanger (high temperatures).
There are no throughput constraints regarding the
condenser.
U0501961-#
Edition: 06 / 2015 Page 35 / 146
VARMAX - Installation, Use and Maintenance
4.11.3. Condensate removal
Removal to the drains, via a drain hopper, using a P.V.C tube (minimum
diameter 32 mm) is mandatory because the condensates are acidic and thus
aggressive (pH between 3 and 5).
Use a suffi cient slope of 3% to ensure correct fl ow of the condensates.
!
WARNING:
4.12. Gas connection
Neutralise these condensates before removal according to regulations
in force.
Before installing the boiler, it is necessary to clean the inside of the installation's
gas line (metallic particles, soldering residue, etc.). This helps to improve the
product's longevity.
Before commissioning the boiler, check that the natural gas supply pressure
corresponds to the boiler's nominal pressure mentioned on the identifi cation
plate.
Before feeding gas to the installation, ensure that the different connections
are correctly made and gas tight.
In particular, check the presence of a removable connector between the
isolating valve and the boiler gas supply tapping.
The value read at the gas valve input must be between the limits indicated in
the table in chapter 2.5, page 11 for the type of gas used.
The boiler's gas line connection must not be subject to any mechanical
!
WARNING:
stress (risk of loss of gas tightness of the gas valve).
Check that the natural gas supply corresponds to the nominal boiler
pressure stated on the identifi cation plate.
4.13. Electrical connection
DANGER:
!
!
WARNING:Observe the phase polarity - neutral for electrical connections.
WARNING:
Ensure that the general electrical power supply has been cut off
before starting any work.
It is mandatory to connect this boiler correctly to earth and to comply
with applicable standards for low voltage electrical installations in the
United Kingdom.
Provide a two pole circuit breaker upstream of the boiler (distance
between contacts: 3.5 mm minimum).
It is strongly recommended to fi t the electrical installation with a
30 mA differential protection.
Page 36 / 146 00BNO9061-J
4.13.1. Control panel
VARMAX - Installation, Use and Maintenance
Refer to the instructions of installation and use of the NAVISTEM B3000
boiler command table for information concerning electrical connections to
the control panel (characteristics of the electrical power supply, cable section
and connection to terminal blocks).
To access the control panel, open the casing
doors on the front of the boiler.
The control panel is on the upper front left of the
boiler.
Unscrew the turn screw at the bottom of the cover.
Cover
Turn screw
fi gure 27 - Opening the electrical box
4.13.2. Cable bushing
Cable clamp
U0501960-#
High voltage tray
(power supply)
Lift up the cover and pull backwards.
Use the cable trays located on the top left of the
boiler to insert the connection cables:
• The upper tray must be reserved for the power connections (boiler power supply, alarm feedback
or circulating pump control).
• The lower tray is dedicated to signal connections (sensors, communication bus, etc.).
Low voltage tray
(sensors / buses)
Use the cable clamp located at the inputs to the
trays to lock the cable mechanically.
U0501963-#
fi gure 28 - Electrical cable bushing
Edition: 06 / 2015 Page 37 / 146
VARMAX - Installation, Use and Maintenance
4.13.3. Connection of the boiler command table to the terminal blocks
To connect the boiler command table, refer to the relevant instructions of
installation and use.
!
ATTENTION :
For connection, comply with the wiring diagram, in particular the
phase, neutral and earth polarities.
4.13.4. Connection of AVS75 extension module(s) (optional)
To install AVS75 module(s) (3 max), refer to
the instructions provided with the accessory
(reference 059751).
AVS75 location (behind
side door)
U0501963-#
fi gure 29 - AVS75 location
4.13.5. Connection of OCI345 communication module (optional)
To install the OCI345 module, refer to the instructions provided with the
accessory (reference 059752).
4.13.6. Fuses
The VARMAX boiler is fi tted with 4 fuses on the boiler command table (refer
to the sticker on the protective cover for their locations and characteristics).
3 spare fuses are also available on the boiler command table.
Page 38 / 146 00BNO9061-J
H6
B8
OCI 345
AVS75
B2B7
H3
4.13.7. Electrical wiring diagram
VARMAX - Installation, Use and Maintenance
Refer to the boiler command table instructions of installation and use.
Refer to the instructions supplied with the optional accessory AVS75.
Refer to the instructions supplied with the optional accessory OCI 345
fi gure 30 - Electrical wiring diagram
Edition: 06 / 2015 Page 39 / 146
00BET9008-#
VARMAX - Installation, Use and Maintenance
5. COMMISSIONING
5.1. Unlocking the boiler
During commissioning, the unlocking of the boiler can only be achieved
!
WARNING:
if the hydraulic system is compliant with the recommendations
mentioned in the hydraulic diagrams (see section 8.3, page 54). The
person in charge of this operation must ensure such compliance.
Unlocking the temperature:
Modify parameter 2212 from 70° C to the desired value (Maximum 85°C).
Unlocking the power:
Increase the value of parameter 9529 up to the value of parameter 9530
(corresponding with the nominal power of the boiler).
Adjusting the boiler to operate using propane results in the
!
Parameter 9529 value120140180225275320390450
WARNING:
power locked46105300318038703360393034403900
power unlocked64907460441054004620545048105480
modifi cation of parameter 9529; the boiler power locking function is
therefore no longer active.
MODELS
5.2. Pre-commissioning checks
For a cascade installation, check the hydraulic balance of the boilers.
Check that pressure when cold is at least 1 bar.
If this is a boiler room renovation, ensure that fl ushing and if necessary
silt removal from the installation have been correctly done (see
paragraph 1.5, page 7 of these instructions).
Check the fl ue-gas connections depending on the type of chimney (refer to
paragraph 4.9, page 24).
Check that the gas pressure and type are suitable for the products.
DANGER:It is forbidden to use water containing glycol.
!
!
Page 40 / 146 00BNO9061-J
WARNING:
If connecting CHIMNEY B23 or B23P, it is COMPULSORY to fi t the air fi lter supplied with the boiler.
5.3. Commissioning
VARMAX - Installation, Use and Maintenance
Before being packed up, all boilers are tested in the factory operating on
group H natural gas (type G20), during which all settings are made.
For commissioning, carry out the following operations:
1. Switch on the main power.
Flue-gas sample
point
fi gure 31 - Taking a sample
U0501961-#
2. Create a request for heat via the comfort mode
using the customer interface (see chapter "3 Interface utilisateur" of the LMS boiler command
table instructions).
3. After starting up the burner, check the gas
tightness of the gas line connections using a
foaming product. Check combustion health using
a fl ue-gas analyser via a sample taken from the fl ue outlet (see diagram opposite).
CO
value range:
2
G20:
at Qmin: 8,3 % < CO
at Qmax: 8,8 % < CO
< 8,7 %
2
< 9,2 %
2
G31:
at Qmin: 9,8 % < CO
at Qmax: 10,4 % < CO
< 10,2 %
2
< 10,8 %
2
4. Adjust the boiler setting (refer to the table
summarising customer parameters at the end of
this manual).
!
WARNING:Any work on a sealed element leads to loss of warranty.
Edition: 06 / 2015 Page 41 / 146
VARMAX - Installation, Use and Maintenance
6. POST-COMMISSIONING CHECK
6.1. Condensate removal
Check that the removal of condensates is not obstructed, on both the boiler
side and the pipe side
6.2. Gas supply
Check that the gas pipe diameter is correctly sized:
It is necessary to stop all the boilers together abruptly using the boiler room
main circuit breaker to check that the gas pressure regulator safety device is
not triggered.
If this is triggered, the gas pipe is undersized. After this operation, reengage
the circuit breaker. The boilers must start automatically, if not, consult the
supplier of the gas pressure regulator.
Page 42 / 146 00BNO9061-J
7. MAINTENANCE OPERATIONS
There are two types of maintenance operations:
• yearly maintenance
DANGER:
• in-depth maintenance every 3 years.
The table below shows which actions to undertake depending on the
type of maintenance to be performed.
In all events, these operations must be performed by a qualifi ed
professional.
Before carrying out the following operations:
• Switch off the main power
• Close the gas supply shut-off valve.
This boiler's earth bonding is ensured with connecting cables (green/
yellow) and specifi c attachment screws. During any dismantling work,
make sure you reconnect the cables concerned; it is IMPERATIVE to
reuse the original attachment screws.
VARMAX - Installation, Use and Maintenance
No. of
paragraph to
consult
7.2Verifi cation of the boiler's environmentX
7.3Replacing the air fi lter mattingX
7.4Verifi cation of ignition and ionisation electrodesX
7.5Siphon cleaningX
7.6Checking the combustion circuit's gas-tightnessX
7.7Checking combustion qualityX
7.9Gas fi lter cleaningX
7.10Cleaning exchangers and changing of seals on service doorsX
Maintenance
every
year
every
three
years
7.11
Edition: 06 / 2015 Page 43 / 146
Check the condition of the gas manifold coating
Cleaning the burner and changing the seals
X
VARMAX - Installation, Use and Maintenance
7.1. Boiler draining
Main exchanger drain valve
(front of boiler)
Condenser drain valve (rear of
boiler)
fi gure 32 - Drain valves
• Close the shut-off valves of the fl ow and return
tappings.
• Connect the drain valves (main exchanger and
condenser) to the drain with a suitable hose.
• Create an air intake on the "main exchanger"
fl ow nozzle (open the safety valve).
• Open the drain valve.
U0502206-#
7.2. Verifi cation of the boiler's environment
Before carrying out any maintenance work, it is necessary to perform a
certain number of checks concerning the installation's use.
• Water pressure: check that the water pressure is higher than 1 bar when
cold.
• Read the makeup water meter. This operation helps to identify any
hydraulic leaks. If consumption of makeup water changes, seek the
cause and repair.
7.3. Replacing the air fi lter matting
!
DANGER:
To make sure this task is performed in safety, switch off the boiler and
cut off the upstream power.
!
Page 44 / 146 00BNO9061-J
DANGER:
INFORMATION:
Use personal protective equipment (mask and gloves) to remove the
used air fi lter.
The air fi lter is only present on boilers connected to a B23 or B23P
chimney.
INFORMATION:
VARMAX - Installation, Use and Maintenance
The air fi lter is an important element of the boiler. It limits the burner
and the exchangers becoming sooty. Changing it regularly (at
least every year) makes burner and exchanger cleaning operations
considerably easier.
Models 120 to 320:
Models 390 and 450:
fi gure 33 - Filter matting
mountings
U0038318-B
U0024791-B
- Remove the used fi lter matting (no tool required).
- Be careful not to let any dust or other foreign
bodies enter the air duct (see opposite).
- Insert the new rectangular fi lter matting between
the fi lter's protective grille and the mountings
(see opposite).
Ensure that the link between both ends of the
matting is under one of the mountings.
- For models 390 and 450, insert the square fi lter
cloth on the back gate of the fi lter.
7.4. Verifi cation of ignition and ionisation electrodes
Ionisation
electrode
Ignition
electrode
U0502214-#
fi gure 34 - Position of electrodes
2.5-3.5 mm
U0502273-#
fi gure 35 - Spacing
Electrode removal
Unscrew the two M4 Torx screws holding the
electrode that needs to be removed.
If necessary and if there is a large amount of
oxidation, clean the electrodes by rubbing them
with an emery cloth.
Check the space between the ignition electrode
and the ground electrode (see diagram opposite).
It must be between 2.5 and 3.5 mm. If this is not
the case, replace the electrode.
Edition: 06 / 2015 Page 45 / 146
VARMAX - Installation, Use and Maintenance
fi gure 36 - Geometry
7.5. Siphon cleaning
Siphon
Hatch
13.8 mm
U0502273-#
U0502274-#
Check the geometry of the arc electrode:
If deformed more than ±3 mm, replace the
electrode.
Re-assemble the electrode block(s). Tightening
torque of the block fi xing screws = 2.5 N.m.
Check the siphon and clean if necessary. The
siphon must be located between the main
exchanger and the condenser on the right-hand
side (it can be accessed via the hatch without
removing the side panel).
To do this:
• Dislodge the siphon by pulling it downwards.
• Clean with water.
• Re-assemble the siphon after checking the
presence and the possibility of free movement
of the fl oat (ball). Also check that the seal is not
damaged.
fi gure 37 - Siphon
7.6. Checking the combustion circuit's gas-tightness
Check the gas-tightness of the 3 service doors
using the foaming product. The areas to check are
shown on the diagram opposite.
The check must be performed when the boiler is
off, but with the ventilator operating at its maximum
seal checking
zone
exchanger
service door
(check the other
2 doors)
U0502275-#
fi gure 38 - Gas-tightness of the service door
speed (obtained by disconnecting the PWM signal
connector).
If a leak is detected, replace the seal with the
appropriate kit.
It is recommended to replace the seals each time
the exchanger service doors are removed. If they
are not replaced, do not cross the doors when reassembling.
Page 46 / 146 00BNO9061-J
7.7. Checking combustion quality
Flue-gas sample
point
U0501961-#
fi gure 39 - Sample taking
VARMAX - Installation, Use and Maintenance
This check is performed using a calibrated
combustion case. To do this, insert the measuring
stick into the fl ue outlet (see diagram opposite).
The boiler's starting temperature must be above
70°C.
Do not forget to re-position the stopper on
the orifi ce from where the sample is taken
afterwards.
For the G20, the CO
content measured in these circumstances must be
2
between 8.3% and 8.7% at Qmini (0% on display) and between 8.8% and
9.2% at Qmaxi (100% on display).
If this is not the case, it is necessary to alter the setting of the gas valve (see
next paragraph).
After this check, it is necessary to either take a measurement of the "gas"
throughput or the ∆P valve. These measurements check the state of soiling
of the combustion circuit (burner, body, exchanger(s)).
For the G31 (relevant modls only), the CO
content measured in these
2
circumstances must be between 9,8% and 10,2% at Qmini (0% on
display) and between 10,4% and 10,8% at Qmaxi (100% on display).
If this is not the case, it is necessary to alter the setting of the gas valve (see
next paragraph).
After this check, it is necessary to either take a measurement of the "gas"
throughput or the ∆P valve. These measurements check the state of soiling
of the combustion circuit (burner, body, exchanger(s)).
For installations with B23 and B23P, we recommend you take this
measurement using a new air fi lter.
The measurement must be done for a duration of more than 3 minutes to
obtain a suffi ciently precise measurement.
If the gas throughput is less than 20% in relation to the value indicated in
paragraph 3.3, page 15, it is necessary to clean the main exchanger and
the burner (see § 7.10 and 7.11).
If you choose to take a measurement of the ∆P valve, refer to the next
paragraph to fi nd out how to do it. If the value measured is lower than the
values defi ned in the table on page 49, it is necessary to clean the main
exchanger and the burner (see § 7.10 and 7.11).
Edition: 06 / 2015 Page 47 / 146
VARMAX - Installation, Use and Maintenance
7.8. Setting the gas valve
This VARMAX boiler has been adjusted in the factory to operate with group
H natural gas (type G20) with inlet gas pressure of 20 mbar.
!
WARNING:
Any work on adjusting the gas valve must be performed by a qualifi ed
professional.
The valve must be adjusted with the boiler working at maximum and minimum
pressure. To do this, use the operating "Manual operating" mode (see § 3.3.4
of the NAVISTEM B3000 boiler command table instructions), which makes it
possible to switch directly to the minimum or maximum value (0% or 100%).
7.8.1. For models 120 and 140
Start the burner up at maximum power.
Using the combustion analyser, measure the rate
of CO
in the fl ue-gases in the fl ue outlet (see
2
fi gure 39).
Check the CO
value at Maximum power and, if
2
necessary, manipulate the valve's gas throughput
adjustment screw to obtain CO
values between
2
8.8% and 9.2% or between 10,4% and 10,8%
(G31).
Offset
regulator
Gas throughput
adjustment
screw
U0501967-#
fi gure 40 - VARMAX gas valve models 120 and 140
Move to Minimum power and check that the CO
2
value is between 8.3% and 8.7% (G20) or between
9,8% and 10,2% (G31). If necessary, adjust the
Offset regulator by removing the stopper using a
fl at screwdriver and adjust the screw with a Philips
screwdriver.
If changing the setting while on minimum power,
switch back to Maximum power and check the CO
2
value again. Repeat until both values conform.
Go back to standard operating mode.
Air relay pipe
connection points
Page 48 / 146 00BNO9061-J
7.8.2. For models 180 to 450
VARMAX - Installation, Use and Maintenance
Hexagonal
3 mm
wrench
Offset
regulator
Pvalve
Pupstream
fi gure 41 - Gas valve setting
Cover
U0501967-#
The measurements for setting the valve must
be taken using the pressures indicated Pvalve
and Pupstream (see diagram opposite).
Air relay pipe connection
points
(Models 180 and 225)
Air relay pipe connection
points
(Models 275 and 320)
Air relay pipe connection
points
(Models 390 and 450)
Edition: 06 / 2015 Page 49 / 146
VARMAX - Installation, Use and Maintenance
Models
Valve
type
Type of
gas
G203,8
180VR420
G311,6
G205,9
225VR420
G312,4
G203,6
275VR432
G311,7
G205,2
320VR432
G312,4
390VR434G205,4
450VR434G207,1
∆P
valve
= (P
upstream
- P
valve
)
∆P
Schieber
(mbar)
Setting at maximum power:
Start the burner up at maximum power.
Remove the cover (see fi gure 41).
Measure the inlet gas pressure (Pupstream).
Adjust the valve pressure (Pvalve) taking into
account ∆P
valve
= (P
upstream
- P
) given in the table
valve
opposite (set the pressure by manipulating the
adjustment screw on the top of the valve underneath
the black cover, 3 mm hexagonal wrench).
If necessary, adjust the valve pressure to obtain a
CO
rate between 8.8% and 9.2% (G20) or between
2
10,4% and 10,8% (G31).
Then switch to minimum power:
Adjust the offset regulator (see fi gure 41) to get
a CO
rate at minimum power between 8.3% and
2
8.7% (G20) or between 9,8% and 10,2% (G31). Use
a fl at screwdriver to remove the protective stopper
and a Torx wrench to adjust.
To validate the correct setting of the valve increase
to Pmaxi (HMI = 100%) and check the CO
rate in
2
the fl ue-gases in the fl ue outlet (see fi gure 39).
If the setting is not correct, perform the above steps
again.
7.9. Gas fi lter cleaning
- Unscrew the 4 screws that hold the gas fi lter in place.
- Carefully remove the gas fi lter.
- Clean the gas fi lter ONLY with a blower.
- Refi t the fi lter and tighten the 4 M5 screws (tightening torque = 5 N.m).
Gas fi lter
screws
(x4)
screws (x4)
Gas fi lter
U0503716-#U0503711-#
fi gure 42 - Gas fi lter on VARMAX 120 and 140
!
Page 50 / 146 00BNO9061-J
WARNING:Check gas-tightness after refi tting.
fi gure 43 - Gas fi lter on VARMAX 180 to 450
7.10. Cleaning exchangers and changing seals
Removal of exchanger doors:
- Remove the front and side cladding to access
the 3 service doors.
- Using a 13mm wrench, unscrew the service door
attachment screws until the tightening bolts turn.
VARMAX - Installation, Use and Maintenance
fi gure 44 - Removal of exchanger doors
6 screws
U0502425-#
- Then remove the door.
- Repeat for the other 2 service doors.
Removal of baffl es:
- Open the fastenings (mark 1) that close the 2
fl ue-gas baffl e strappings (mark 2).
fi gure 45 - Removal of baffl es
Edition: 06 / 2015 Page 51 / 146
- Remove the 2 strappings (mark them in some
way so that you can refi t them in the same order)
and then remove the fl ue-gas baffl es (marks 3).
Mark these too so that you can refi t them in the
same position.
Cleaning baffl es and exchangers:
- Brush the fl ue-gas baffl es with a stainless steel
or plastic brush, so as not to geometrically deform them.
- Clean by brushing or if the exchanger is very
dirty, wash with water and then dry. If washing
with water, be careful of the electrical parts.
VARMAX - Installation, Use and Maintenance
Changing door seals:
service
door
groove
- Remove the seals from their groove and replace
with new seals from the maintenance kit (see
fi gure 46).
seal
U0502445-#
fi gure 46 - Changing door seals
Refi tting:
wire spring
- Insert the baffl es under the wire spring between
the top part of the exchanger tubes (see detail).
Replace the baffl es holding the strappings (mark
3) as shown on the diagram opposite.
- Position the strappings inside the pins of the
baffl es holding the strappings.
baffl es
fi gure 47 - Refi tting
- Tighten the fastenings and ensure the baffl es are
correctly fi tted to the exchanger tubes and check
that each of the baffl es are correctly fi tted on
the exchanger tubes at their lower and upper
ends.
Note:
It is normal that the baffl es are not fi tted tightly in
the area between the 2 strappings.
U0503496-#
Checking gas-tightness:
- After refi tting the 3 service doors (tightening
torque of screws = 15 N.m), check the gas
tightness using the foaming product around the
service doors before starting the boiler up again
(see chapter 7.6).
Page 52 / 146 00BNO9061-J
VARMAX - Installation, Use and Maintenance
7.11. Cleaning the burner and changing the seals
To facilitate access to the spool piece and then the
removable part
U0502250-#
fi gure 48 - Removable upper door
gas tube, part of the upper door is removable.
spool piece
cover
fi gure 49 - Removal of spool piece cover
removal / mounting
tool
U0502457-#
Spanner
of 24
Removing the burner tube:
- Remove the 2 electrode blocks before removing
the burner tube (see chapter 7.4).
- Unscrew the attachment screws from the spool
piece cover to remove it.
- Put the burner tube's removal / mounting tool in
position (the tool is located under the gas line to
the right of the sleeve cover).
- Position the tool in the slots of the tightening
fl ange and compress on it (by pressing down) .
U0503721-#
fi gure 50 - Release the burner tube
Edition: 06 / 2015 Page 53 / 146
VARMAX - Installation, Use and Maintenance
Plastic valve
Lug
- Rotate the tool anticlockwise to unlock the ramp.
Unlocked
Locked
U0516842-#
fi gure 51 - Positions of the fastening clamps
- Remove the clamp from the burner tube.
- Remove the burner tube.
!
!
WARNING:
WARNING:
Remove the plastic valve on the spool piece before removing the burner
tube. Do not forget to put it back when refi tting.
When removing the burner tube, be careful not to rub metal mesh
against the spool piece.
Cleaning the burner tube:
gas tube
U0502459-#
fi gure 52 - Cleaning the gas tube
Page 54 / 146 00BNO9061-J
- Suck out the entire surface in metal mesh using a
vacuum cleaner.
VARMAX - Installation, Use and Maintenance
Keep a distance of 10 mm between the suction nozzle and the metal
!
WARNING:
mesh. Any rubbing of the boiler tube may cause damage.
NEVER USE A METAL BRUSH.
!
WARNING:Replace the seal under the clamp on the burner tube.
Refi tting:
- Put the burner tube into the spool piece (be careful not to rub the metal mesh
on the spool piece). A directional pin enables the burner tube to be correctly
positioned.
- Position the clamp (the word "UP" must be visible and the inner lug must be
positioned on the rear axis of the boiler - see fi gure 47)
- Position the burner tube's removal / mounting tool in the slots in the clamp.
- Compress by pushing downwards and rotate the tool in a clockwise direction
to lock the tube (see fi gure 47).
- Check the seal on the spool piece's cover and replace if necessary.
- Position the cover over the spool piece.
- Screw the cover onto the spool piece using the screws (tightening torque =
5 N.m).
- Refi t the 2 electrode blocks.
!
WARNING:
Check the different seals after mounting. If using a foaming product, be
careful of the ionisation electrode's electrical connection.
Edition: 06 / 2015 Page 55 / 146
VARMAX - Installation, Use and Maintenance
8. END-OF-LIFE CYCLE OF THE APPARATUS
8.1. Environmental compatibility
This appliance contains electrical and electronic elements which must not be
thrown away with household waste.
Local legislation must be complied with.
8.2. Dismantling, recycling and elimination of the apparatus
Regulatory disposal and managed recycling of this product can prevent
damage to the environment and health risks.
a) For the disposal of the product and the component parts, the services of
an accredited waste disposal company should be used.
b) For more information on waste disposal/management, contact the Local
Authority responsible for waste management or the point of sales where
the product was purchased
Page 56 / 146 00BNO9061-J
VARMAX - Installation, Use and Maintenance
9. HYDRAULIC DIAGRAMS AND SETTINGS
9.1. Selection fl ow diagram
Without management
Single boiler
With management of
secondary networks
of secondary
systems
Not
communicating
Communicating via
signal 0…10V
Communicating via
LPB bus
direct circuit
1, 2 or 3
regulated
networks
without DHW
With
3-channel
valve
Accumulated
DHW
Non communicating existing
secondary system
VX101
Page 60
Secondary networks via
existing communicating
system
VX111
Page 75
Secondary networks via
existing communicating
system
VX111
Page 75
1 direct heating network
VX100
Page 60
Networks (1, 2 or 3) regula-
ted by 3-channel valve
without DHW
VX102
Page 64
Networks (1, 2 or 3) regulated by 3-channel valve with
accumulated DHW
VX110
Page 70
regulated
network + low
level direct circuit
+
regulated network +
consumer circuit constant
T° and throughput
+
semi-instanta-
neous DHW
Networks (1, 2 or 3) regulated by 3-channel valve with
Operation at constant temperature with variable fl ow and immediate
!
WARNING:
SINGLE BOILER .........................................................................................................................60
1 direct heating network or existing non-communicative secondary system ...................................................... 60
VX100, VX101
3 regulated networks with or without DHW production ....................................................................................... 64
VX102, VX112
1 network regulated by a 3-channel valve, and DHW production ...................................................................... 70
VX110
Secondary networks with existing regulation communicating by LPB bus or 0...10V ........................................ 75
VX111
1 network regulated by a 3-channel valve, 1 direct circuit with 60°C low level ..................................................78
VX113
1 network regulated by a three-channel valve, 1 circulation circuit with constant temperature and throughput 82
VX120
DHW production directly on heat plate exchanger without buffer tank
forbidden.
BOILERS IN A CASCADE CONFIGURATION ...........................................................................86
1 direct network, no communication with the secondary network ...................................................................... 86
VX200, VX201
1 network regulated by a three-channel valve, DHW production or 1 direct circuit with constant temperature
and throughput ................................................................................................................................................... 92
VX210, VX220
Secondary networks regulated by external regulated communicating by LPB bus or 0...10V ......................... 100
VX211
3 or 4 networks regulated by a three-channel valve with or without DHW production ..................................... 106
VX202, VX212
Edition: 06 / 2015 Page 59 / 146
VARMAX - Installation, Use and Maintenance
SINGLEBOILER
1 direct heating network or existing non-communicative
secondary system
A. MAIN AND ALTERNATIVE HYDRAULIC DIAGRAMS
B9
B3000
Q2
Diagrams
VX100
VX101
page 1 / 4
B9
B3000
fi gure 53 - Diagram VX100
NON-COMMUNICATING
REGULATEUR
REGULATEUR
REGULATEUR
REGULATEUR
REGULATEUR
REGULATEUR
REGULATOR
NON COMMUNICANT
NON COMMUNICANT
NON COMMUNICANT
NON COMMUNICANT
NON COMMUNICANT
NON COMMUNICANT
SAFETY BY-PASS IF
BY-PASS DE SECURITE
BY-PASS DE SECURITE
BY-PASS DE SECURITE
BY-PASS DE SECURITE
BY-PASS DE SECURITE
BY-PASS DE SECURITE
HEATED FLOOR
SI PLANCHER CHAUFFANT
SI PLANCHER CHAUFFANT
SI PLANCHER CHAUFFANT
SI PLANCHER CHAUFFANT
SI PLANCHER CHAUFFANT
SI PLANCHER CHAUFFANT
fi gure 54 - Diagram VX101 (alternative)
Page 60 / 146 00BNO9061-J
VARMAX - Installation, Use and Maintenance
Diagrams: VX100 / VX101
page 2 / 4
B. NECESSARY ADJUSTMENT ACCESSORY
Quantity
External sensor kit1QAC 34059260
Appliance
reference
Order No.
C. CUSTOMER ELECTRICAL CONNECTION
Mains supply 230
VAC 50 Hz
Diagram VX100:
Circulation pump on
direct circuit Q2
LNY1NY2L NLNLN
QX2QX3QX1AUX2AUX1
}
Alarm relay
}
D. SPECIFIC START-UP PROCEDURE
Fit the accessories and make their electrical connections.
Start up the boiler alone.
Make the following settings:
BX2
Gnd
BX3
Gnd
B3
Gnd
B9
Gnd
H1
Gnd
H5
Gnd
Line No. Value
External sensor B9
}
• Time and date menu
Set the time
Set the date
Set the year
• Configuration menu
Start up the heating circuit 1
Defi ne the pump outlet Q2 (diagram VX100)
Edition: 06 / 2015 Page 61 / 146
Time / minute (1)HH.MM
Day / month (2)DD.MM
Year (3)YYYY
Heating circuit 1 (5710)On
QX2 relay outlet (5891)Pump CC1 Q2
VARMAX - Installation, Use and Maintenance
Diagrams: VX100 / VX101
• Heating circuit 1 menu
Set the comfort setting
Set the curve slope
• Switch the heating mode to permanent comfort
Comfort setting temperature (710)- - -
Heating curve slope (720)- - -
E. ELECTRICAL AND HYDRAULIC VALIDATION
• Input/output test menu
Check the outputs
Alarm relay
Heating circuit No. 1 pump (diagram VX100)
Reset outputs
page 3 / 4
Line No. Value
Relay test (7700)Relay output QX1
Relay test (7700)Relay output QX2
Relay test (7700)No test
Check sensor values
External sensor B9
• Configuration menu
Check the hydraulic diagram
F. OPTIMISATION OF SETTINGS
• Heating circuit 1 menu
Set the reduced setting
• CC1 time programme menu
Preselection
External T° B9 (7730)in °C
Generator 1 check (6212)14
Generator 2 check (6213)0
Information on DHW (6215)0
Information on heating circuits 3, 2 and 1 (6217)1 (for VX101)
2 (for VX100)
Reduced temperature setting (712)- - -
Preselection (500)- - -
Adjust the time programme
• Circuit CC1 holiday menu
Preselection
Adjust the time programme
• Switch the heating mode to automatic
Page 62 / 146 00BNO9061-J
On / Off phases (501...506)- - -
Preselection (641)- - -
On / Off phases (642-643)- - -
AUTO
VARMAX - Installation, Use and Maintenance
Diagrams: VX100 / VX101
page 4 / 4
Maintenance optimisation:
It is possible to generate a maintenance message without harming the boiler. This maintenance
message may appear when the 3 following meters have elapsed:
• Time since last maintenance (or commissioning): set parameter 7044 to 12 months
• Operating hours of the burner (parameter 7040)
• Number of start-ups (parameter 7042)
The last 2 parameters depend on the boiler room's hydraulic installation. It is recommended to
use at least parameter 7044 for yearly maintenance.
Edition: 06 / 2015 Page 63 / 146
VARMAX - Installation, Use and Maintenance
SINGLEBOILER
Diagrams
VX102
3 regulated networks with or without DHW production
A. MAIN AND ALTERNATIVE HYDRAULIC DIAGRAMS
B9
B12
B3000
B1
Y1/Y2
x
Q2
x
Q6
Y5/Y6
VX112
page 1 / 6
B14
x
Q20
Y11/
Y12
B9
B3000
fi gure 55 - Diagram VX102
B1
x
Q2
Y1/Y2
Y5/
Y6
B12B14
x
Q6
Y11/
Y12
B3
bouclage
bouclage
ECS
ECS
x
Q20
ECS
Cold
Entrée
Entrée
water inlet
eau froide
eau froide
fi gure 56 - Diagram VX112 (alternative)
Page 64 / 146 00BNO9061-J
VARMAX - Installation, Use and Maintenance
Diagrams: VX102 / VX112
page 2 / 6
B. NECESSARY ADJUSTMENT ACCESSORIES
Quantity
Extension module kit (delivered with a
QAD 36 network sensor)
Fit the accessories and make their electrical connections.
WARNING:
!
Start up the boiler alone.
Make the following settings:
Ensure the switches on the extension modules AVS75 are properly
confi gured.
BX21
Gnd
BX22
Gnd
H2
Gnd
Module 3
}
Flow sensor for regulated circuit
}
B14
Line No. Value
• Time and date menu
Set the time
Set the date
Set the year
• Configuration menu
Start up the heating circuit 1
Start up the heating circuit 2
Start up the heating circuit 3
Page 66 / 146 00BNO9061-J
Heating circuit 1 (5710)On
Heating circuit 2 (5715)On
Heating circuit 3 (5721)On
Time / minute (1)HH.MM
Day / month (2)DD.MM
Year (3)YYYY
VARMAX - Installation, Use and Maintenance
Diagrams: VX102 / VX112
Diagram VX112 only:
Defi ne a low level
Install a shunt on H1 OR reverse
the direction of contact
For the DHW to be effective, it is
necessary to defi ne a trigger, even
if it is not connected.
Confi gure the extension modules
page 4 / 6
Line No. Value
Input function H1 (5950)Circulation circuit
demand 1
Type of contact (5951)Rest contact
Output via relay QX2 (5891)Pump/valve ECS
Q3
Function of extension module 1 (6020)Heating circuit 1
Function of extension module 2 (6021)Heating circuit 2
Function of extension module 3 (6022)Heating circuit 3
• Heating circuit 1 / 2 / 3 menu
For each circuit
Set the comfort setting
Set the curve slope
• Switch the heating mode to permanent comfort
Diagram VX112 only:
• Circulation circuit 1 menu
Set the starting value to use in
the event of a demand from the
circulation circuit
• Domestic hot water menu
Set the comfort setting
Temperature of comfort setting (710/1010/1310)- - -
Slope of the heating curve(720/1020/1320)- - -
Starting value in case of circuit demand
60°C (depends on
(1859)
Comfort setpoint (1610)55 °C
Rubis setting)
Set the DHW release mode
• Activate DHW mode
Edition: 06 / 2015 Page 67 / 146
DHW release (1620)24/7
VARMAX - Installation, Use and Maintenance
Diagrams: VX102 / VX112
E. ELECTRICAL AND HYDRAULIC VALIDATION
• Input/output test menu
Check the outputs
Alarm relay
All relays of extension modules
Reset outputs
Check sensor values
External sensor B9
DHW sensor B3
Flow sensor B1
Flow sensor B12
Flow sensor B14
Temperature sensor BX21 module 1 (7830)in °C
Temperature sensor BX21 module 2 (7832)in °C
Temperature sensor BX21 module 3 (7834)in °C
DHW temperature B3/B38 (7750)in °C
page 5 / 6
Line No. Value
Relay test (7700)Relay output QX1
Relay test (7700)Relay output QX
Relay test (7700)No test
External T° B9 (7730)in °C
Diagram VX112 only:
Check the condition of contact H1
• Configuration menu
Check the hydraulic diagram
F. OPTIMISATION OF SETTINGS
Optimisation of the heating circuits:
• Heating circuit 1 / 2 / 3 menu
Set the reduced setting
Condition of contact H1 (7841)Closed if the shunt
is in place
Generator 1 check (6212)14
Generator 2 check (6213)0
Information on DHW (6215)0
Information on heating circuits 3, 2 and 1 (6217)30303
Line No. Value
Reduced temperature setting (712/1012/1312)- - -
(diagram VX102)
4
(diagram VX112)
• Time programme CC1 / CC2 / CC3 menu
Preselection
Adjust the time programme
Page 68 / 146 00BNO9061-J
Preselection (500/520/540)- - -
On / Off phases (501...506)
(521...526)
(541...546)
- - -
VARMAX - Installation, Use and Maintenance
Diagrams: VX102 / VX112
• Holiday circuit CC1 / CC2 / CC3 menu
Preselection
Adjust the time programme
• Switch the heating mode to automatic
Optimisation of DHW:
• DHW storage tank menu
Adjust the boost
Line No. Value
Preselection (641/651/661)- - -
On / Off phases (642-643)
(652-653)
(662-663)
Line No. Value
Starting value of boost temperature (5020)16 °C
- - -
AUTO
page 6 / 6
Maintenance optimisation:
It is possible to generate a maintenance message without harming the boiler. This maintenance
message may appear when the 3 following meters have elapsed:
• Time since last maintenance (or commissioning): set parameter 7044 to 12 months
• Operating hours of the burner (parameter 7040)
• Number of start-ups (parameter 7042)
The last 2 parameters depend on the boiler room's hydraulic installation. It is recommended to
use at least parameter 7044 for yearly maintenance.
G. SETTING AMBIENT SENSORS
Connect each sensor to a heating circuit:
Line No. Value
• User interface menu of each ambient sensor
Confi gure the ambient sensor with a heating circuit
Use (40)Ambient appliance
1 or 2 or 3
Each ambient sensor allows its heating circuit to be confi gured. Ambient sensors 1, 2 and 3 respectively
set parameters 712 (heating circuit 1), 1012 (heating circuit 2) and 1312 (heating circuit 3).
Edition: 06 / 2015 Page 69 / 146
VARMAX - Installation, Use and Maintenance
SINGLEBOILER
1 network regulated by a 3-channel valve, and DHW production
A. HYDRAULIC DIAGRAM
B9
B1
x
Q2
Y1/Y2
Diagram
VX110
page 1 / 5
Q3
B3000
B3
fi gure 57 - VX110 diagram
B. NECESSARY ADJUSTMENT ACCESSORIES
Quantity
Extension module kit (delivered with a
QAD 36 network sensor)
Fit the accessories and make their electrical connections.
WARNING:
!
Start up the boiler alone.
Make the following settings.
Edition: 06 / 2015 Page 71 / 146
Ensure the switches on the extension modules AVS75 are properly
confi gured.
VARMAX - Installation, Use and Maintenance
• Time and date menu
Set the time
Set the date
Set the year
• Configuration menu
Start up the heating circuit 1
Confi gure the DHW pump
Confi gure extension module 1
• Heating circuit 1 menu
Set the comfort setting
Diagram VX110
Function of extension module 1 (6020)Heating circuit 1
page 3 / 5
Line No. Value
Time / minute (1)HH.MM
Day / month (2)DD.MM
Year (3)YYYY
Heating circuit 1 (5710)On
Output via relay QX2 (5891)Pump/valve ECS
Q3
Comfort setting temperature (710)- - -
Set the curve slope
• Switch the heating mode to permanent comfort
• Domestic hot watermenu
Set the comfort setting
• Activate DHW mode
Heating curve slope (720)- - -
E. ELECTRICAL AND HYDRAULIC VALIDATION
• Input/output test menu
Check the outputs
Alarm relay
Comfort setpoint(1610)- - -
Line No. Value
Relay test (7700)Relay output QX1
DHW pump Q3
Opening V3V CC
Closing V3V CC
CC pump
Page 72 / 146 00BNO9061-J
Relay test (7700)Relay output QX2
Relay test (7700)Relay output QX21
module 1
Relay test (7700)Relay output QX22
module 1
Relay test (7700)Relay output QX23
module 1
VARMAX - Installation, Use and Maintenance
Diagram VX110
Line No. Value
Reset outputs...module...Relay test (7700)No test
Check sensor values
External sensor B9
DHW sensor B3
Flow sensor B1
• Configuration menu
Check the hydraulic diagram
DHW temperature B3/B38 (7750)in °C
Temperature sensor BX21 module 1 (7830)in °C
Information on heating circuits 3, 2 and 1 (6217)3
External T° B9 (7730)in °C
Generator 1 check (6212)14
Generator 2 check (6213)0
Information on DHW (6215)4
page 4 / 5
F. OPTIMISATION OF SETTINGS
Optimisation of heating circuit:
• Heating circuit 1 menu
Set the reduced setting
• CC1 time programme menu
Preselection
Adjust the time programme
• Circuit CC1 holiday menu
Preselection
Adjust the time programme
• Switch the heating mode to automatic
Line No. Value
Reduced temperature setting (712)- - -
Preselection (500)- - -
On / Off phases (501...506)- - -
Preselection (641)- - -
On / Off phases (642-643)- - -
AUTO
Optimisation of DHW:
Line No. Value
• Domestic hot water menu
Set the reduced setting
Set the DHW release mode
Edition: 06 / 2015 Page 73 / 146
Reduced setting (1612)- - -
DHW release (1620)Time programme 4/
DHW
VARMAX - Installation, Use and Maintenance
Diagram VX110
• Time programme 4 / ECS menu
Preselection
Adjust the time programme
• DHW storage tank menu
Adjust the boost
• Domestic hot water menu
Confi gure an anti-legionella function
Line No. Value
Preselection (560)- - -
On / Off phases (561...566)- - -
Starting value of boost temperature (5020)- - -
Anti-legionella function (1640)- - -
Periodic anti-legionella function
(1641)
Day week anti-legionella function (1642)- - -
Anti-legionella temperature setting (1645)- - -
- - -
page 5 / 5
Duration of anti-legionella function (1646)- - -
Maintenance optimisation:
It is possible to generate a maintenance message without harming the boiler. This maintenance
message may appear when the 3 following meters have elapsed:
• Time since last maintenance (or commissioning): set parameter 7044 to 12 months
• Operating hours of the burner (parameter 7040)
• Number of start-ups (parameter 7042)
The last 2 parameters depend on the boiler room's hydraulic installation. It is recommended to
use at least parameter 7044 for yearly maintenance.
Page 74 / 146 00BNO9061-J
VARMAX - Installation, Use and Maintenance
Secondary networks with existing regulation
communicating by LPB bus or 0...10V
A. HYDRAULIC DIAGRAM
COMMUNICATING REGULATOR
REGULATEUR COMMUNICANT
SIGNAL 0/10 V VERS LMS
ou bus LPB vers OCI345
0/10 V SIGNAL TO NAVISTEM B3000
or LPB bus to OCI345
SINGLEBOILER
Diagram
VX111
page 1 / 3
B3000
fi gure 58 - Diagram VX111
B. NECESSARY ADJUSTMENT ACCESSOR Y
Quantity
Communication kit for LPB bus1OCI 345059572
Appliance
reference
Order No.
Edition: 06 / 2015 Page 75 / 146
VARMAX - Installation, Use and Maintenance
Diagram VX111
C. CUSTOMER ELECTRICAL CONNECTION
Alarm
relay
Mains supply 230
VAC 50 Hz
LPB bus
LNY1NY2L NLNLN
QX2QX3QX1AUX2AUX1
}
DB MB
}
BX2
Gnd
BX3
Gnd
B3
Gnd
B9
Gnd
H1
Gnd
page 2 / 3
Analogue input
}
0...10V
D. SPECIFIC START-UP PROCEDURE
Fit the accessories and make their electrical connections.
Start up the boiler alone.
Make the following settings:
• Time and date menu
Set the time
Set the date
Set the year
For a demand via input 0...10V
• Configuration menu
Confi gure input H1
H5
Gnd
Line No. Value
Time / minute (1)HH.MM
Day / month (2)DD.MM
Year (3)YYYY
Input function H1 (5950)Demand from
circulation circuit
1 10V
Voltage value 1 H1 (5953)0.0
Function value H1 (5954)0
Voltage value 2 H1 (5955)10.0
Page 76 / 146 00BNO9061-J
VARMAX - Installation, Use and Maintenance
Diagram VX111
Function value 2 H1 (5956)1000 (for 10 V = 100
For a demand via LPB (LPB network menu)
• LPB network menu
Check that the boiler has been defi ned
as the master generator
Appliance address (6600)1
Bus supply function (6604)Automatic
E. ELECTRICAL AND HYDRAULIC VALIDATION
For a demand via input 0...10V
• Input/output test menu
Voltage in H1
page 3 / 3
Line No. Value
°C equivalence)
Segment address (6601)0
Clock function (6640)Slave with
adjustment
Voltage signal H1 (7840)To validate with
the voltage sent
by the boiler room
machine
For a demand via LPB
If the boiler room regulator is confi gured as the master clock, the boiler
command table must recover the date and time.
In both cases
• Configuration menu
Check the hydraulic diagram
Information on heating circuits 3, 2 and 1 (6217)0
Generator 1 check (6212)14
Generator 2 check (6213)0
Information on DHW (6215)0
F. OPTIMISATION OF SETTINGS
Maintenance optimisation:
It is possible to generate a maintenance message without harming the boiler. This maintenance
message may appear when the 3 following meters have elapsed:
• Time since last maintenance (or commissioning): set parameter 7044 to 12 months
• Operating hours of the burner (parameter 7040)
• Number of start-ups (parameter 7042)
The last 2 parameters depend on the boiler room's hydraulic installation. It is recommended to
use at least parameter 7044 for yearly maintenance.
Edition: 06 / 2015 Page 77 / 146
VARMAX - Installation, Use and Maintenance
SINGLEBOILER
1 network regulated by a 3-channel valve, 1 direct circuit
with 60°C low level
A. HYDRAULIC DIAGRAM
DIRECT CIRCUIT
B9
B1
Q2
Y1/Y2
x
CIRCUIT DIRECT
WITH LOW LEVEL
AVEC TALON BAS
FOR FLOW AT 60°C
DEPARTA 60 °C
Q6
Diagram
VX113
page 1 / 4
B3000
fi gure 59 - Diagram VX113
B. NECESSARY ADJUSTMENT ACCESSORIES
Quantity
Extension module kit (delivered with a
QAD 36 network sensor)
1AVS 75059751
External sensor kit1QAC 34059260
Appliance
reference
Order No.
Page 78 / 146 00BNO9061-J
VARMAX - Installation, Use and Maintenance
Diagram VX113
C. CUSTOMER ELECTRICAL CONNECTION
Direct
circulation
pump Q6
Alarm
relay
}
Mains supply 230
VAC 50 Hz
LNY1NY2L NLNLN
QX2QX3QX1AUX2AUX1
}
BX2
Gnd
BX3
Gnd
B3
Gnd
B9
Gnd
page 2 / 4
External sensor B9
}
QX21
}
QX22
}
QX23
N
AVS75
N
Mixing valve for heating
circuit No. 1 Y1/Y2
Circulator for heating circuit
No. 1 Q2
D. SPECIFIC START-UP PROCEDURE
BX21
Gnd
BX22
Gnd
H2
Gnd
H1
Gnd
H5
Gnd
Module 1
}
Flow sensor for regulated circuit
}
B1
Fit the accessories and make their electrical connections.
WARNING:
!
Start up the boiler alone.
Make the following settings.
Edition: 06 / 2015 Page 79 / 146
Ensure the switches on extension module AVS75 are correctly
confi gured.
VARMAX - Installation, Use and Maintenance
• Time and date menu
Set the time
Set the date
Set the year
• Configuration menu
Start up the heating circuit 1
Start up the heating circuit 2
Confi gure the pump CC2
Confi gure extension module 1
• Heating circuit 1 menu
Diagram VX113
page 3 / 4
Line No. Value
Time / minute (1)HH.MM
Day / month (2)DD.MM
Year (3)YYYY
Heating circuit 1 (5710)On
Heating circuit 2 (5715)On
Output via relay QX2 (5891)Pump CC2 Q6
Function of extension module 1
(6020)
Heating circuit 1
Set the comfort setting
Set the curve slope
• Heating circuit 2 menu
Set the comfort setting
Set the curve slope
Set the minimum starting temperature
• Switch the heating mode to permanent comfort
Comfort setting temperature (710)- - -
Heating curve slope (720)- - -
Comfort setting temperature (1010)- - -
Heating curve slope (1020)- - -
Minimum starting T° value (1040)60°C (adjust
E. ELECTRICAL AND HYDRAULIC VALIDATION
• Input/output test menu
Check the outputs
depending on low
level)
Line No. Value
Alarm relay
CC2 pump
Opening V3V CC
Closing V3V CC
Page 80 / 146 00BNO9061-J
Relay test (7700)Relay output QX1
Relay test (7700)Relay output QX2
Relay test (7700)Relay output QX21
module 1
Relay test (7700)Relay output QX22
module 1
VARMAX - Installation, Use and Maintenance
Diagram VX113
Line No. Value
CC pumpRelay test (7700)Relay output QX23
Reset outputs
Check sensor values
External sensor B9
Flow sensor B1
• Configuration menu
Check the hydraulic diagram
Temperature sensor BX21 module 1 (7830)in °C
Generator 1 check (6212)14
Generator 2 check (6213)0
Information on DHW (6215)0
Information on heating circuits 3, 2 and 1 (6217)203
Relay test (7700)No test
External T° B9 (7730)in °C
page 4 / 4
module 1
F. OPTIMISATION OF SETTINGS
• Heating circuit 1 / 2 menu
Set the reduced setting
• Time programme CC1 / CC2 menu
Preselection
Adjust the time programme
• Holiday circuit CC1 / CC2 menu
Preselection
Adjust the time programme
• Switch the heating mode to automatic
Maintenance optimisation:
Line No. Value
Temperature of reduced setting (712/1012)- - -
Preselection (500/520)- - -
On / Off phases (501...506)
(521...526)
Preselection (641/651)- - -
On / Off phases (642-643)
(652-653)
- - -
- - -
AUTO
It is possible to generate a maintenance message without harming the boiler. This maintenance
message may appear when the 3 following meters have elapsed:
• Time since last maintenance (or commissioning): set parameter 7044 to 12 months
• Operating hours of the burner (parameter 7040)
• Number of start-ups (parameter 7042)
The last 2 parameters depend on the boiler room's hydraulic installation. It is recommended to
use at least parameter 7044 for yearly maintenance.
Edition: 06 / 2015 Page 81 / 146
VARMAX - Installation, Use and Maintenance
SINGLEBOILER
1 network regulated by a three-channel valve, 1 circulation
circuit with constant temperature and throughput
A. HYDRAULIC DIAGRAM
DIRECT CIRCUIT WITH
CIRCUIT DIRECT AVEC
CONSTANT TEMPERATURE
TEMPERATURE ET DEBIT
AND THROUGHPUT
B9
B1
Q2
Y1/Y2
x
CONSTANT
Q15
Diagram
VX120
page 1 / 4
B3000
fi gure 60 - Diagram VX120
B. NECESSARY ADJUSTMENT ACCESSORIES
Quantity
Extension module kit (delivered with a
QAD 36 network sensor)
1AVS 75059751
External sensor kit1QAC 34059260
Appliance
reference
Order No.
Page 82 / 146 00BNO9061-J
VARMAX - Installation, Use and Maintenance
Diagram VX120
C. CUSTOMER ELECTRICAL CONNECTION
Direct
circulation
pump Q15
Alarm
relay
}
Mains supply 230
VAC 50 Hz
LNY1NY2L NLNLN
QX2QX3QX1AUX2AUX1
}
BX2
Gnd
BX3
Gnd
B3
Gnd
B9
Gnd
page 2 / 4
External sensor B9
}
QX21
}
QX22
}
QX23
N
AVS75
N
Mixing valve for heating
circuit No. 1 Y1/Y2
Circulator for heating circuit
No. 1 Q2
D. SPECIFIC START-UP PROCEDURE
Fit the accessories and make their electrical connections.
BX21
Gnd
BX22
Gnd
H2
Gnd
H1
Gnd
H5
Gnd
Module 1
}
Flow sensor for regulated circuit
}
B1
Shunt to install
WARNING:
!
Start up the boiler alone.
Make the following settings.
Edition: 06 / 2015 Page 83 / 146
Ensure the switches on extension module AVS75 are correctly
confi gured.
VARMAX - Installation, Use and Maintenance
• Time and date menu
Set the time
Set the date
Set the year
• Configuration menu
Start up the heating circuit 1
Confi gure pump Q15
Confi gure input H1
Confi gure extension module 1
Diagram VX120
Function of extension module 1 (6020)Heating circuit 1
page 3 / 4
Line No. Value
Time / minute (1)HH.MM
Day / month (2)DD.MM
Year (3)YYYY
Heating circuit 1 (5710)On
Output via relay QX2 (5891)Pump for circulation
circuit 1 Q15
Input function H1 (5891Demand for
circulation circuit 1
• Heating circuit 1 menu
Set the comfort setting
Set the curve slope
• Circulation circuit 1menu
Set the starting value to use in the event
of demand from the circulation circuit
• Switch the heating mode to permanent comfort
Comfort setting temperature (710)- - -
Heating curve slope (720)- - -
Value of starting temperature for
circulation circuit demand (1859)
E. ELECTRICAL AND HYDRAULIC VALIDATION
• Input/output test menu
Check the outputs
Alarm relay
- - -
Line No. Value
Relay test (7700)Relay output QX1
Constant circuit pump
Opening V3V CC
Closing V3V CC
CC pump
Reset outputs
Page 84 / 146 00BNO9061-J
Relay test (7700)Relay output QX2
Relay test (7700)Relay output QX21
module 1
Relay test (7700)Relay output QX22
module 1
Relay test (7700)Relay output QX23
module 1
Relay test (7700)No test
VARMAX - Installation, Use and Maintenance
Diagram VX120
Check sensor values
External sensor B9
Flow sensor B1
• Configuration menu
Check the hydraulic diagram
F. OPTIMISATION OF SETTINGS
page 4 / 4
Line No. Value
External T° B9 (7730)in °C
Temperature sensor BX21 module 1 (7830)in °C
Generator 1 check (6212)14
Generator 2 check (6213)0
Information on DHW (6215)0
Information on heating circuits 3, 2 and 1 (6217)3
Line No. Value
• Heating circuit 1 menu
Set the reduced setting
• CC1 time programme menu
Preselection
Adjust the time programme
• Circuit CC1 holiday menu
Preselection
Adjust the time programme
• Switch the heating mode to automatic
Maintenance optimisation:
Reduced temperature setting (712)- - -
Preselection (500)- - -
On / Off phases (501...506)- - -
Preselection (641)- - -
On / Off phases (642-643)- - -
AUTO
It is possible to generate a maintenance message without harming the boiler. This maintenance
message may appear when the 3 following meters have elapsed:
• Time since last maintenance (or commissioning): set parameter 7044 to 12 months
• Operating hours of the burner (parameter 7040)
• Number of start-ups (parameter 7042)
The last 2 parameters depend on the boiler room's hydraulic installation. It is recommended to
use at least parameter 7044 for yearly maintenance.
Edition: 06 / 2015 Page 85 / 146
VARMAX - Installation, Use and Maintenance
x
B3000
B3000
REGULATEUR NON COMMUNICANT
BOILERSINACASCADECONFIGURATION
1 direct network, no communication with the secondary
network
A. MAIN AND ALTERNATIVE HYDRAULIC DIAGRAMS
B9
x
Diagram
VX200
VX201
page 1 / 6
Q2
B10
B9
B3000
B3000
fi gure 61 - Diagram VX200
NON-COMMUNICATING
REGULATOR
Q1.2Q1.1
B10
Q1.2
Q1.1
fi gure 62 - Diagram VX201 (alternative)
Page 86 / 146 00BNO9061-J
VARMAX - Installation, Use and Maintenance
Diagrams: VX200 / VX201
page 2 / 6
B. NECESSARY ADJUSTMENT ACCESSORIES
Quantity
Communication kit 2OCI 345059572
Network sensor kit1QAx 36
External sensor kit1QAC 34059260
Appliance
reference
Order No.
059261 (QAZ 36)
059592 (QAD 36)
C. CUSTOMER ELECTRICAL CONNECTION
Boiler No. 1:
INFORMATION:
If the insulating valve is not fi tted with an automatic reset, reconnect the
Q1.1 insulating valve closing contact on Y2.
Mains supply 230
VAC 50 Hz
LPB bus
}
DB MB
Diagram VX200:
Circulation pump on
direct circuit Q2
}
LNY1NY2L NLNLN
QX2QX3QX1AUX2AUX1
Insulating
valve Q1.1
}
Alarm
relay
}
BX2
Gnd
BX3
Gnd
B3
Gnd
B9
Gnd
H1
Gnd
Flow sensor in
}
cascade B10
External sensor B9
}
H5
Gnd
Boiler No. 2:
INFORMATION:
Edition: 06 / 2015 Page 87 / 146
If the insulating valve is not fi tted with an automatic reset, reconnect the
Q1.2 insulating valve closing contact on Y2.
VARMAX - Installation, Use and Maintenance
Mains supply 230
VAC 50 Hz
LPB bus
}
DB MB
Diagrams: VX200 / VX201
Insulating
valve Q1.2
Alarm
relay
}
LNY1NY2L NLNLN
QX2QX3QX1AUX2AUX1
page 3 / 6
}
D. SPECIFIC START-UP PROCEDURE
Fit the accessories and make their electrical connections.
Start up the boiler alone.
Make the following settings:
On boiler No. 1: master
• Set the time and date: Time and date menu
Set the time
Set the date
Set the year
• Configuration menu
Start up the heating circuit 1
Diagram VX200 only:
Confi gure the pump Q2
Line No. Value
Time / minute (1)HH.MM
Day / month (2)DD.MM
Year (3)YYYY
Heating circuit 1 (5710)On
QX2 relay outlet (5891)Pump CC1 Q2
All diagrams:
Confi gure fl ow sensor in cascade B10Sensor input BX2 (5931)Common fl ow
sensor B10
Page 88 / 146 00BNO9061-J
VARMAX - Installation, Use and Maintenance
Diagrams: VX200 / VX201
• Confi gure as master in the cascade: LPB network menu
Appliance number
Segment number
Set the bus power supply.
Set the clock mode
• Set the heating circuit: Heating circuit 1 menu
Set the comfort setting
Set the curve slope
• Switch the heating mode to permanent comfort
Comfort setting temperature (710)- - -
Appliance address (6600)1
Segment address (6601)0
Bus supply function (6604)Automatic
Heating curve slope (720)- - -
page 4 / 6
Line No. Value
Clock function (6640)Master
On boiler(s) No. 2 (and later): slave
Line No. Value
• Confi gure as slave in the cascade: LPB network menu
Appliance number
Segment number
Set the bus power supply.
Set the clock mode
• Connect the bus between the boilers (
• Turn off the slave boiler(s) and then turn on again. If communication is successful, the clock is
correctly updated.
respect the polarity).
!
Appliance address (6600)2 (or later for the
other slaves)
Segment address (6601)0
Bus supply function (6604)Automatic
Clock function (6640)Slave without
adjustment
E. ELECTRICAL AND HYDRAULIC VALIDATION
On boiler No. 1: master
Line No. Value
• Cascade diagnostic menu
Check that all boilers are present in the cascade
Status of generator 1 (8100)Released / not
released
Status of generator 2 (8101)Released / not
released
Edition: 06 / 2015 Page 89 / 146
VARMAX - Installation, Use and Maintenance
Diagrams: VX200 / VX201
• Input/output test menu
Check the outputs
Alarm relay
Pump Q2 (diagram VX200)
Insulating valve Q1.1
Reset outputs
Check sensor values
External sensor B9
Flow sensor in cascade B10
page 5 / 6
Line No. Value
...............................
Relay test (7700)Relay output QX1
Relay test (7700)Relay output QX2
Relay test (7700)Relay output QX3
Relay test (7700)No test
External T° B9 (7730)in °C
Sensor T° BX2 (7821)in °C
• Configuration menu
Check the hydraulic diagram
Information on heating circuits 3, 2 and 1 (6217)1
On boiler(s) No. 2 (and later): slave
• Input/output test menu
Check the outputs
Alarm relay
Insulating valve Q1.2
Reset outputs
• Configuration menu
Generator 1 check (6212)14
Generator 2 check (6213)0
Information on DHW (6215)0
Line No. Value
Relay test (7700)Relay output QX1
Relay test (7700)Relay output QX3
Relay test (7700)No test
Check the hydraulic diagram
Information on heating circuits 3, 2 and 1 (6217)0
Page 90 / 146 00BNO9061-J
Generator 1 check (6212)14
Generator 2 check (6213)0
Information on DHW (6215)0
VARMAX - Installation, Use and Maintenance
Diagrams: VX200 / VX201
F. OPTIMISATION OF SETTINGS
On boiler No. 1: master
Optimisation of heating circuit:
• Heating circuit 1 menu
Set the reduced setting
• CC1 time programme menu
Preselection
Adjust the time programme
• Circuit CC1 holiday menu
Preselection
page 6 / 6
Line No. Value
Reduced temperature setting (712)- - -
Preselection (500)- - -
On / Off phases (501...506)- - -
Preselection (641)- - -
Adjust the time programme
• Switch the heating mode to automatic
On / Off phases (642-643)- - -
AUTO
Optimisation of the cascade:
The cascade may be optimised as required with the parameters of the Cascade menu. Refer to the
LMS boiler command table instructions for more details.
Maintenance optimisation:
It is possible to generate a maintenance message without harming the boiler. This maintenance
message may appear when the 3 following meters have elapsed:
• Time since last maintenance (or commissioning): set parameter 7044 to 12 months
• Operating hours of the burner (parameter 7040)
• Number of start-ups (parameter 7042)
The last 2 parameters depend on the boiler room's hydraulic installation. It is recommended to
use at least parameter 7044 for yearly maintenance.
Edition: 06 / 2015 Page 91 / 146
VARMAX - Installation, Use and Maintenance
BOILERSINACASCADECONFIGURATION
1 network regulated by a three-channel valve, DHW
production or 1 direct circuit with constant temperature and
throughput
A. HYDRAULIC DIAGRAM
B9
B10
x
B3000
Q1.1
B3000
Q1.2
B1
Q2
Y1/Y2
Q3
B3
Diagram
VX210
VX220
page 1 / 8
x
B3000
B9
Q1.1
fi gure 63 - Diagram VX210
B3000
Q1.2
DIRECT CIRCUIT WITH
CIRCUIT DIRECTAVEC
CONSTANT TEMPERATURE
TEMPERATURE ET DEBIT
AND THROUGHPUT
CONSTANT
B1
x
Q2
Q15
Y1/Y2
x
B10
fi gure 64 - Diagram VX220
Page 92 / 146 00BNO9061-J
VARMAX - Installation, Use and Maintenance
Diagrams: VX210 / VX220
page 2 / 8
B. NECESSARY ADJUSTMENT ACCESSORIES
Quantity
Extension module kit (delivered with a
QAD 36 network sensor)
If the insulating valve is not fi tted with an automatic reset, reconnect the
Q1.1 insulating valve closing contact on Y2.
Insulating
valve Q1.1
}
LNY1NY2L NLNLN
QX2QX3QX1AUX2AUX1
}
Alarm
relay
}
BX2
Gnd
BX3
Gnd
B3
Gnd
B9
Gnd
Flow sensor in
}
cascade B10
Diagram VX210:
}
DHW sensor B3
External sensor B9
}
H1
Gnd
H5
Gnd
Edition: 06 / 2015 Page 93 / 146
Diagram VX220:
Shunt to install
VARMAX - Installation, Use and Maintenance
Mixing valve for heating
circuit No. 1 Y1/Y2
Circulator for heating circuit
No. 1 Q2
Boiler No. 2:
INFORMATION:
Diagrams: VX210 / VX220
Module 1
Gnd
Gnd
H2
Gnd
}
Flow sensor for regulated circuit
}
B1
QX21
}
N
QX22
}
N
QX23
If the insulating valve is not fi tted with an automatic reset, reconnect the
Q1.2 insulating valve closing contact on Y2.
AVS75
BX21
BX22
page 3 / 8
Mains supply 230
VAC 50 Hz
LPB bus
}
DB MB
Insulating
valve Q1.2
LNY1NY2L NLNLN
QX2QX3QX1AUX2AUX1
Alarm
}
relay
}
Page 94 / 146 00BNO9061-J
VARMAX - Installation, Use and Maintenance
Diagrams: VX210 / VX220
D. SPECIFIC START-UP PROCEDURE
Fit the accessories and make their electrical connections.
WARNING:
!
Start up the boiler alone.
Make the following settings:
On boiler No. 1: master
• Time and date menu
Set the time
Set the date
Set the year
Ensure the switches on extension module AVS75 are correctly
confi gured.
page 4 / 8
Line No. Value
Time / minute (1)HH.MM
Day / month (2)DD.MM
Year (3)YYYY
• Configuration menu
Confi gure the DHW pump (diagram
VX210)
Confi gure pump Q15 (diagram VX220)
Confi gure the fl ow sensor in cascade B10
Confi gure input H1 (diagram VX220)
Confi gure the extension module
• Confi gure as master in the cascade: LPB network menu
Appliance number
Segment number
Set the bus power supply.
Set the clock mode
Function of extension module 1 (6020)Heating circuit 1
QX2 relay outlet (5891)Pump/valve ECS
QX2 relay outlet (5891)Pump for circulation
Sensor input BX2 (5931)Common fl ow
Input function H1 (5977)Demand for
Appliance address (6600)1
Segment address (6601)0
Bus supply function (6604)Automatic
Q3
circuit 1 Q15
sensor B10
circulation circuit 1
Clock function (6640)Master
• Heating circuit 1menu
Set the comfort setting
Set the curve slope
• Switch the heating mode to permanent comfort
Edition: 06 / 2015 Page 95 / 146
Comfort setting temperature (710)- - -
Heating curve slope (720)- - -
VARMAX - Installation, Use and Maintenance
Diagrams: VX210 / VX220
Diagram VX210 only:
• Domestic hot water menu
Set the comfort setting
• Activate DHW mode
Diagram VX220 only:
• Circulation circuit 1 menu
Set the starting value to use in the event of
a demand from the circulation circuit
Line No.Value
Comfort setpoint (1610)- - -
Value of starting temperature for
circulation circuit demand (1859)
page 5 / 8
- - -
On boiler(s) No. 2 (and later): slave
• Confi gure as slave in the cascade: LPB network menu
Appliance number
Segment number
Set the bus power supply.
Set the clock mode
• Connect the bus between the boilers (
• Turn off the slave boiler(s) and then turn on again. If communication is successful, the clock is
correctly updated.
respect the polarity).
!
Appliance address (6600)2 (or later for the
other slaves)
Segment address (6601)0
Bus supply function (6604)Automatic
Clock function (6640)Slave without
adjustment
E. ELECTRICAL AND HYDRAULIC VALIDATION
On boiler No. 1: master
• Cascade diagnostic menu
Check that all boilers are present in the cascade
Status of generator 1 (8100)Released / not
released
Status of generator 2 (8101)Released / not
released
Page 96 / 146 00BNO9061-J
VARMAX - Installation, Use and Maintenance
Diagrams: VX210 / VX220
• Input/output test menu
Check the outputs
Alarm relay
DHW pump Q3 (diagram VX210)
Constant circuit pump Q15 (diagram VX220)
Opening V3V CC
Closing V3V CC
CC pump
Reset outputs
page 6 / 8
Line No.Value
Relay test (7700)Relay output QX1
Relay test (7700)Relay output QX2
Relay test (7700)Relay output QX2
Relay test (7700)Relay output QX21
module 1
Relay test (7700)Relay output QX22
module 1
Relay test (7700)Relay output QX23
module 1
Relay test (7700)No test
Check sensor values
External sensor B9External T° B9 (7730)in °C
DHW sensor B3
Flow sensor B1
• Configuration menu
Check the hydraulic diagram
On boiler No. 2: slave
• Input/output test menu
Check the outputs
Temperature sensor BX21 module 1 (7830)in °C
Information on heating circuits 3, 2 and 1 (6217)3
DHW temperature B3/B38 (7750)in °C
Generator 1 check (6212)14
Generator 2 check (6213)0
Information on DHW (6215)4
(
Diagram VX210)
0
(
Diagram VX220)
Alarm relay
Insulating valve Q1.2
Reset outputs
Edition: 06 / 2015 Page 97 / 146
Relay test (7700)Relay output QX1
Relay test (7700)Relay output QX3
Relay test (7700)No test
VARMAX - Installation, Use and Maintenance
Diagrams: VX210 / VX220
• Configuration menu
Check the hydraulic diagram
F. OPTIMISATION OF SETTINGS
Optimisation of heating circuit:
• Heating circuit 1 menu
Set the reduced setting
• CC1 time programme menu
page 7 / 8
Line No.Value
Generator 1 check (6212)14
Generator 2 check (6213)0
Information on DHW (6215)0
Information on heating circuits 3, 2 and 1 (6217)0
Reduced temperature setting (712)- - -
Preselection
Adjust the time programme
• Circuit CC1 holiday menu
Preselection
Adjust the time programme
• Switch the heating mode to automatic
Optimisation of DHW:
• Domestic hot water menu
Set the comfort setting
Set the DHW release mode
Preselection (500)- - -
On / Off phases (501...506)- - -
Preselection (641)- - -
On / Off phases (642-643)- - -
AUTO
Reduced setting (1612)- - -
DHW release (1620)Time programme 4/
DHW
• Time programme 4 / DHW menu
Preselection
Adjust the time programme
• DHW storage tank menu
Adjust the boost
Page 98 / 146 00BNO9061-J
Starting value of boost temperature (5020)- - -
On / Off phases (561...566)- - -
Preselection (560)- - -
VARMAX - Installation, Use and Maintenance
Diagrams: VX210 / VX220
Diagram VX210 only:
• Domestic hot water menu
Confi gure an anti-legionella function
Line No.Value
Anti-legionella function (1640)- - -
Periodic anti-legionella function
(1641)
Day week anti-legionella function (1642)- - -
Anti-legionella temperature setting (1645)- - -
Duration of anti-legionella function (1646)- - -
page 8 / 8
- - -
Optimisation of the cascade:
The cascade may be optimised as required with the parameters of the Cascade menu. Refer to the
LMS boiler command table instructions for more details.
Maintenance optimisation:
It is possible to generate a maintenance message without harming the boiler. This maintenance
message may appear when the 3 following meters have elapsed:
• Time since last maintenance (or commissioning): set parameter 7044 to 12 months
• Operating hours of the burner (parameter 7040)
• Number of start-ups (parameter 7042)
The last 2 parameters depend on the boiler room's hydraulic installation. It is recommended to
use at least parameter 7044 for yearly maintenance.
Edition: 06 / 2015 Page 99 / 146
VARMAX - Installation, Use and Maintenance
BOILERSINACASCADECONFIGURATION
Secondary networks regulated by external regulated
communicating by LPB bus or 0...10V
A. HYDRAULIC DIAGRAM
0/10 V SIGNAL TO NAVISTEM B3000
SIGNAL 0/10 V VERS LMS
or LPB BUS TO OCI345
ou bus LPB sur OCI 345
COMMUNICATING REGULATOR
REGULATEUR COMMUNICANT
B10
x
Diagram
VX211
page 1 / 6
Q1.1Q1.2
B3000B3000
fi gure 65 - Diagram VX211
B. NECESSARY ADJUSTMENT ACCESSORIES
Quantity
Communication kit2OCI 345059572
Network sensor kit1QAx 36
Appliance
reference
Order No.
059261 (QAZ 36)
059592 (QAD 36)
Page 100 / 146 00BNO9061-J
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.