WARNING:
If the information in these instructions are not followed exactly, a fi re or explosion may result causing property damage,
personal injury or loss of life.
FOR YOUR SAFETY
Do not store or use gasoline or other fl ammable vapors and
liquids in the vicinity of this or any other appliance.
Installation and service must be performed by a qualifi ed
installer, service agency or the gas supplier.
Tested by:
Installer: Please complete the details on the back cover
and leave this manual with the homeowner.
Homeowner: Please keep these instructions for future reference.
918-518
FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 Venture St., Delta, BC Canada, V4G 1H4
FOR YOUR SAFETY
What to do if you smell gas:
Do not try to light any appliance
Do not touch any electrical switch:
do not use any phone in your
building.
Immediately call your gas supplier
from a neighbour's phone. Follow
the gas supplier's instructions.
If you cannot reach your gas
supplier, call the fi re department.
07/17/06
HAMPTON
®
Direct Vent Freestanding Gas Stove
To the New Owner:
Congratulations!
You are the owner of a state-of-the-art Hampton
The H35 is a hand crafted appliance and has been designed to provide you with all the warmth and charm of a wood
fi replace at the fl ick of a switch. The model H35 has been approved by Warnock Hersey for both safety and effi ciency. As
it also bears our own mark, it promises to provide you with economy, comfort and security for many trouble free years to
follow. Please take a moment now to acquaint yourself with these instructions and the many features of your Hampton®
Stove.
®
Gas Stove by FPI FIREPLACE PRODUCTS INTERNATIONAL LTD.
UNIT DIMENSIONS
2Hampton® H35 Direct Vent Freestanding Gas Stove
TABLE OF CONTENTS
Unit Dimensions ............................................................2
SAFETY LABEL
Copy of Safety Label ..................................................... 4
REQUIREMENTS
MA Code - CO Detector
(for state of Massachusetts only) ..................................5
This is a copy of the label that accompanies
each Direct Vent Freestanding Gas Stove.
We have printed a copy of the contents here
for your review.
NOTE: Hampton® units are constantly being
improved. Check the label on the unit and if
there is a difference, the label on the unit is
the correct one.
COPY OF SAFETY LABEL
For the State of Massachusetts, installation and repair must be done by a plumber or gasfi tter licensed in the Commonwealth of
Massachusetts.
For the State of Massachusetts, fl exible connectors shall not exceed 36 inches in length.
For the State of Massachusetts, the appliances individual manual shut-off must be a t-handle type valve.
The State of Massachusetts requires the installation of a carbon monoxide alarm in accordance with NFPA 720 and a CO alarm with
battery back up in the same room where the gas appliance is installed.
4Hampton® H35 Direct Vent Freestanding Gas Stove
REQUIREMENTS
MA Code - CO Detector
(for the State of Massachusetts only)
5.08: Modifications to NFPA-54, Chapter 10
(2) Revise 10.8.3 by adding the following additional requirements:
(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for
residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than
seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall
be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled
equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is
installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery
operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure
served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of
qualified licensed professionals for the installation of hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon
monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of
thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon
monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions
shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight
(8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The
sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL
OBSTRUCTIONS".
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation
unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR
5.08(2)(a)1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by
the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or
structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product
Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the
instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a
Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies
"special venting systems", the following requirements shall be satisfied by the manufacturer:
1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and
2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and
detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions,
all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of
the installation.
Hampton® H35 Direct Vent Freestanding Gas Stove
5
INSTALLATION
IMPORTANT MESSAGE
SAVE THESE
INSTRUCTIONS
The Direct Vent Freestanding Gas Stove must be
installed in accordance with these instructions.
Carefully read all the instructions in this manual
fi rst. Consult the building authority having
jurisdiction to determine the need for a permit
prior to starting the installation.
Note: Failure to follow the instructions
could cause a malfunction of the
heater which could result in death,
serious bodily injury, and/or property
damage. Failure to follow these
instructions may also void your fi re
insurance and/or warranty.
Note: These instructions take precedence over
Simpson Dura-Vent instructions.
SPECIFICATIONS
Fuels: H35-NG1 is approved for use with
natural gas.
H35-LP1 is approved for use
with liquefied petroleum gases
(propane).
Electrical: 120V A.C. system.
Circulation Fan: Variable speed, 125/75.
Log Sets: Ceramic fi bre, 7 per set.
Vent System: Coaxial (6-5/8" outer / 4" inner
liner) rigid fl ue and termination cap.
The effi ciency rating of the appliance is a
product thermal effi ciency rating determined
under continuous operating conditions and
was determined independent of any installed
system.
INFORMATION FOR
MOBILE /
MANUFACTURED
HOMES
AFTER FIRST SALE
This Hampton® product has been tested and
listed by ITS Testing Services as a Direct Vent
Wall Furnace to the following standards:
CGA-2.17-M91, and ANSI Z21.88b-2003/CSA
2.33b-2003.
This Direct Vent System Appliance must be
installed in accordance with the manufacturer's
installation instructions and the Manufactured
Home Construction and Safety Standard, Title
24 CFR, Part 3280, or the current Standard
of Fire Safety Criteria for Manufactured
Home Installations, Sites, and Communities
ANSI/NFPA 501A, and with CAN/CSA Z240-MH
Mobile Home Standard in Canada.
This appliance installation must comply with
the manufacturer's installation instructions and
local codes, if any. In the absence of local codes
follow the current National Fuel Gas Code, ANSI
Z223.1 and the current National Electrical Code
ANSI/NFPA 70 in the U.S.A., and the current
CAN/CGA B149 Gas Installation Code and the
current Canadian Electrical Code CSA C22.1
in Canada.
This Hampton® Mobile/Manufactured
Home Listed appliance comes factory
equipped with a means to secure the
unit.
This Hampton® Mobile/Manufactured
Home listed appliance comes equipped
with a dedicated #8 ground lug to which
an 18 gauge copper wire from the steel
chassis ground must be attached.
This appliance may only be installed in
an aftermarket permanently located,
manufactured (USA only )or mobile
home, where not prohibited by local
codes.
This appliance is only for use with
the type of gas indicated on the
rating plate. This appliance is not
convertible for use with other gases,
unless a certifi ed kit is used.
BEFORE YOU START
Safe installation and operation of this appliance
requires common sense, however, we are
required by the Canadian Safety Standards
and ANSI Standards to make you aware of
the following:
INSTALLATION AND REPAIRS
SHOULD BE DONE BY A QUALIFIED SERVICE PERSON. THIS APPLIANCE SHOULD BE INSTALLED,
REPAIRED, INSPECTED BEFORE
USE AND AT LEAST ANNUALLY
BY A QUALIFIED SERVICE PERSON. MORE FREQUENT CLEANING MAY BE REQUIRED DUE TO
EXCESSIVE LINT FROM CARPETING, ETC. IT IS IMPERATIVE THAT
THE CONTROL COMPARTMENT,
BURNERS AND CIRCULATING
AIR PASSAGEWAYS OF THE APPLIANCE BE KEPT CLEAN.
DUE TO HIGH TEMPERATURES,
THE APPLIANCE SHOULD BE
LOCATED OUT OF TRAFFIC AND
AWAY FROM FURNITURE AND
DRAPERIES.
WARNING: FAILURE TO INSTALL
THIS APPLIANCE CORRECTLY
WILL VOID YOUR WARRANTY
AND MAY CAUSE A SERIOUS
HOUSE FIRE.
CHILDREN AND ADULTS SHOULD
BE ALERTED TO THE HAZARDS
OF HIGH SURFACE TEMPERATURES, ESPECIALLY THE FIREPLACE GLASS, AND SHOULD
STAY AWAY TO AVOID BURNS
OR CLOTHING IGNITION.
YOUNG CHILDREN SHOULD
BE CAREFULLY SUPERVISED
WHEN THEY ARE IN THE SAME
ROOM AS THE APPLIANCE.
CLOTHING OR OTHER FLAMMABLE MATERIAL SHOULD NOT
BE PLACED ON OR NEAR THE
APPLIANCE.
1) Provide adequate clearances for servicing,
proper operation and around the air openings
into the combustion chamber.
2) The appliance must be installed on a fl at,
solid, continuous surface (e.g. wood, metal,
concrete). This may be the fl oor, or it can be
raised up on a platform to enhance its visual
impact. The appliance may be installed on
carpeting, tile, wood fl ooring or other combustible material, because the appliance's
base extends the full width and depth of the
appliance. The Direct Vent Freestanding
Gas Stove can be installed in a wide variety
of ways and will fi t nearly any room layout.
It may be installed in a recessed position,
framed out into the room, or across a corner.
3) The Direct Vent Freestanding Gas Stove
is approved for alcove installations, which
meet the clearances listed in the "Clearance to Combustibles" section. This unit is
approved for manufactured home installations, see the "Manufactured Mobile Home
Additional Requirements" section and the
"Venting Arrangement" section for the required vent arrangements. If installed into a
6Hampton® H35 Direct Vent Freestanding Gas Stove
INSTALLATION
manufactured home the unit must be bolted
down to the fl oor.
4) This appliance is Listed for bedroom instal-
lations when used with a Listed Millivolt
Thermostat. Some areas may have further
requirements, check local codes before
installation.
5) This appliance is Listed for Alcove installa-
tions, maintain minimum Alcove clearances
as follows, minimum width of 40" (1016mm),
a maximum depth of 36" (914mm), and
minimum ceiling height of 64" (1626mm)
from fl oor to ceiling.
6) We recommend that you plan your instal-
lation on paper using exact measurements
for clearances and fl oor protection before
actually installing this appliance. Have a
qualifi ed building inspector review your plans
before installation.
GENERAL SAFETY
INFORMATION
1) The appliance installation must conform with
local Canadian Electrical Code.
2) The appliance when installed, must be
electrically grounded in accordance with
local codes, or in the absence of local codes
with the current National Electrical Code,
ANSI/NFPA 70 or CSA C22.1 Canadian
Electrical Code.
3) The appliance should be inspected for
shipping damage before use and serv-
iced annually by a professional service
person. More frequent cleaning may be
required due to excessive lint from carpeting, bedding material, etc. It is imperative
that control compartments, and circulating
air passageways of the appliance be kept
clean and free from excessive lint from
carpeting.
4) See general construction and assembly
instructions. The appliance and vent should
be enclosed when installed in or passing
through a living area, where children may
come in contact with it.
8) Any safety glass removed for servicing
must be replaced prior to operating the appliance.
9) To prevent injury, do not allow anyone who
is unfamiliar with the operation to use the
fi replace.
Emissions from burning wood or gas could
contain chemicals known to the State of California to cause cancer, birth defects or other
reproductive harm.
INSTALLATION
CHECKLIST
1) Locate your appliance. Refer to the following
sections:
a. Clearances to combustibles
b. Locating Your Gas Stove
c. For venting requirements, see "Venting
Introduction" to "Venting Arrangements"
sections.
2) Install Optional Fan. Refer to the "Optional
Fan Installation" section.
3) Set vent restrictors. Refer to the "Vent Re-
strictor Position" section.
4) Install venting. Refer to the following sections
where applicable:
a. Check all venting requirements.
See "Venting Introduction" to "Venting
Arrangements" sections.
b. Vertical Termination with Co-linear Flex
System
c. DV Stove Horizontal Vent Kit
d. Dura-Vent Termination Kit.
5) Make gas connections. Refer to the "Gas
Connection" section
Test the pilot. Must be as per diagram in the
"Maintenance Instruction" section.
If converting to Propane, make changes
prior see the "Conversion from Natrual Gas
to Propane" section.
8) Final check. Refer to the "Final Check" sec-
tion.
Before leaving this unit with the customer,
the installer must ensure that the appliance is fi ring correctly and operation fully
explained to customer.
This includes:
1) Clocking the appliance to ensure the correct
fi ring rate (rate noted on label) after burning
appliance for 15 minutes.
2) If required, adjusting the primary air to ensure
that the fl ame does not carbon. First allow
the unit to burn for 15-20 min. to stabilize.
CAUTION: Any alteration to the product that
causes sooting or carboning that results
in damage is not the responsibility of the
manufacturer.
CLEARANCES TO
COMBUSTIBLES
The clearances listed are MINIMUM distances.
Measure the clearance to both the appliance
and the chimney connector. The farthest
distance is correct if the two clearances do
not coincide.
For example, if the appliance is set as indicated
in one of the fi gures but the connector is too
close, move the stove until the correct clearance
to the connector is obtained.
This appliance may be installed only with the
clearances as shown in the situations pictured.
Do not combine clearances from one type of
installation with another in order to achieve
closer clearances.
5) This appliance must be connected to the
specifi ed vent and termination cap to the
outside of the building envelope. Never
vent to another room or inside a building.
Make sure that the vent is fi tted as per the
instructions starting in the "Exterior Vent
Terminal Locations" section.
6) Inspect the venting system annually for
blockage and any signs of deterioration.
7) Venting terminals shall not be recessed into
a wall or siding.
Hampton® H35 Direct Vent Freestanding Gas Stove
6) Test Gas Pressure. Refer to the "Gas Pipe
7) Install standard and optional features. Refer
a. Log Set Installation
b. Double Door Installation
c. Decorative Door Grill Installation
d. Tile Inset Installation
e. Wall Thermostat
f. Remote Control
Pressure Testing" section.
to the following sections where applicable:
7
INSTALLATION
LOCATING YOUR
GAS STOVE
When selecting a location for your stove, ensure
that the clearances listed above are met as well
as ensuring that there is adequate accessibility
for servicing and proper operation.
A) Cross Corner
B) Room Divider
C) Island
D) Flat on Wall
E) Flat on Wall Corner
F) Flush with Wall/Alcove
For Vent Termination requirements, see the
"Exterior Vent Terminal Locations" section.
MANUFACTURED
MOBILE HOME
ADDITIONAL
REQUIREMENTS
1) Ensure that structural members are not cut
or weakened during installation.
2) Ensure proper grounding using the #8
ground lug provided.
OPTIONAL FAN INSTALLATION
Fan Kit Contains:
Qty. Description
1 Fan Speed Controller with nut, and
knob.
1 Fan Assembly c/w green wire
attached
1 Power cord
1 Plastic locking grommet
1) Remove the Top Control Panel Assembly
by removing the three screws. Diagram 1.
Diagram 1
2) Remove the nylon hole plug from the control
panel.
3) Install the fan speed controller onto the
control panel and secure with nut. Connect
remaining wire harness wires to speed
control. NOTE: Speed control wires must
be in the down position when control panel
is in place.
4) Push black knob onto speed control.
5) Remove the rear access panel on the back
of the stove by removing the 6 screws. Install
the fan onto pins as per Diagram 2.
7) Install locking grommet to power cord and
push through hole in the rear panel and give
a 1/4 turn to secure.
NOTE: When running wires, keep them clear
of valve assembly and tubing to avoid
tangling of wires and valve.
NOTE: Be careful not to cut wires when pass-
ing through holes in the fi rebox.
8) Run green ground wire from fan and connect
to grounding lug.
9) Connect green power cord ground wire to
grounding lug.
10) Run the neutral black wire from power cord
and connect to fan motor.
11) Run the live black wire from power cord and
connect to speed control wire.
12) Connect the white wire of the wire harness
to the fan terminal.
NOTE: Pull excess wire next to fan to
avoid excessive heat from the fi rebox.
13) Ensure all wires are pulled away from fi rebox
to avoid excessive heat and secure with
stick-on wire clip.
3) Appliance must be anchored to the fl oor
with the supplied anchoring methods.
COMBUSTION AND
VENTILATION AIR
The combustion air from this appliance is drawn
from outside the building through the outer fl ue.
Extra provision for combustion air inside the
room is not required.
NOTE: When power cord is plugged in, speed
control is in the ON position and stove is
burning, allow 10 - 15 minutes for the thermodisc (temperature switch) to activate and
turn on the Fan automatically.
WARNING:
Electrical Grounding Instructions
This appliance is equipped with
a three pronged (grounding) plug
for your protection against shock
hazard and should be plugged
directly into a properly grounded
three-prong receptacle. Do not cut
or remove the grounding prong
from this plug.
INSTALLATION
VENTING
INTRODUCTION
The Horizontal Termination Kit and the Simpson
Dura-Vent Direct Vent System Model DV-GS
venting systems, in combination with the Direct
Vent Freestanding Gas Stoves, H35-NG1, and
H35-LP1, have been tested and listed as direct
vent heater systems by Warnock Hersey.
These units use the "balanced fl ue" technology
Co-Axial system. The inner liner vents products
of combustion to the outside while the outer pipe
draws outside combustion air into the combustion chamber thereby eliminating the need to
use heated room air for combustion and losing
warm room air up the chimney.
Note: These fl ue pipes must not be
connected to any other appliance.
The gas appliance and vent system must be
vented directly to the outside of the building,
and never be attached to a chimney serving a
separate solid fuel or gas burning appliance.
Each direct vent gas appliance must use it's own
separate vent system. Common vent systems
are prohibited.
IMPORTANT
Read all instructions carefully before starting
the installation. Failure to follow these instructions may create a fi re or other safety hazard,
and will void the warranty. Be sure to check the
venting and clearance to combustible requirements. Consult your local building codes before
beginning installation.
The location of the termination cap must conform
to the requirements in the "Exterior Vent Terminal
Locations" section.
INSTALLATION
PRECAUTIONS
These venting systems are engineered products
that have been designed and tested for use
with the H35-NG1, and H35-LP1. The warranty
will be voided and serious fi re, health or other
safety hazards may result from any of the following actions:
1) Installation of any damaged Direct Vent
component
2) Unauthorized modifi cation of the Direct Vent
System
3) Installation of any component part not manu-
factured or approved by Simpson Dura-Vent
or FPI Fireplace Products International
Ltd.
4) Installation other than as instructed by Simp-
son Dura-Vent and FPI Fireplace Products
International Ltd.
Warning: Always maintain required
clearances (air spaces) to nearby
combustibles to prevent a fire
hazard. Do not fi ll air spaces with
insulation.
Be sure to check the vent termination clearance
requirements from decks, windows, soffi ts,
gas regulators, air supply inlets and public
walkways as specifi ed in the "Exterior Vent
Terminal Locations" section and in your local
building codes.
The gas appliance and vent system must be
vented directly to the outside of the building,
and never be attached to a chimney serving
a separate solid fuel or gas-burning appliance. Each direct vent gas appliance must use
it's own separate vent system. Common vent
systems are prohibited.
VENT RESTRICTOR
POSITION
Vent restriction is required for certain venting
installations, see the diagrams in "Venting
Arrangment" section to determine if they are
required for your installation.
To set the Vent restriction as indicated in the
diagrams in the "Venting Arrangement" section,
simply loosen the screws and push the vent
restrictor plate to the correct position. Tighten
the screws.
Horizontal Termination:
Vent Restrictor setting at 36,000 Btu/h
Vertical Termination:
Vent Restrictor setting at 36,000 Btu/h
1) Wear gloves and safety glasses for protec-
2) Exercise extreme caution when using lad-
3) Be aware of electrical wiring locations in
Hampton® H35 Direct Vent Freestanding Gas Stove
SAFETY PRECAUTIONS
FOR THE INSTALLER
tion.
ders or on roof tops.
walls and ceilings.
9
INSTALLATION
EXTERIOR VENT TERMINAL LOCATIONS
any other appliance *(12"/30cm)
*(min. 84"/2.1m)
J= Clearance to service regulator vent outlet *(min. 36"/90cm)
K= Clearance to non-mechanical air supply inlet to building or the combustion air inlet to
L= Clearance to a mechanical air supply inlet *(min. 72"/1.8m)
M= **Clearance above paved sidewalk or a paved driveway located on public property
N= Clearance under veranda, porch, deck, or balcony *(min. 12"/30cm)***
Note: * As specifi ed in CGA B149 Installation Code. Note: Local codes or regulations
may require different clearances.
**A vent shall not terminate directly above a sidewalk or paved driveway which is located
between two single family dwellings and serves both dwellings.
***Only permitted if veranda, porch, deck, or balcony is fully open on a minimum of two
sides beneath the fl oor.
distance of (24"/60cm) from the centerline of the terminal (min. 22"/55cm) check with
local code.
Vent Termination Cap (min.12"/30cm), with Riser Vent (min. 6"/15cm)
Vent Termination Cap (min.12"/30cm), with Riser Vent (min. 6"/15cm)
Ceiling Support 949 - n/a from FPI 4DT-CS 4DFSP
Cathedral Support Box 941 4DT-CSS 4DRSB
Wall Support/Band 988 4DT-WS/B 4DWS
Offset Support 989 - n/a from FPI 4DT-OS N/A
Wall Thimble, Black 942 4DT-WT 4DWT
Wall Thimble Support Box/Ceiling Support 940 N/A N/A
Firestop Spacer 963 4DT-FS 4DFSP
Trim Plate, Black N/A 4DT-TP 4DFPB
Brass Trim for Wall Thimble/Ceiling Support 3951 N/A N/A
Do not combine venting components from
different venting systems.
However use of the the AstroCapTM and FPI
Riser is acceptable with all systems.
This product has been evaluated by Intertek
for use with Duravent Direct-Vent GS, Selkirk
Direct-Temp, Ameri Vent Direct venting and
Security Secure Vent systems.
The FPI AstroCap
American Metal Products Ameri Vent Direct Vent, Security Secure Vent®, Selkirk Direct-Temp. AstroCapTM is a proprietary trademark of FPI Fireplace
Products International Ltd. Dura-Vent® and Direct Vent GS are registered and/or proprietary trademarks of Simpson Dura-Vent Co. Inc.
TM
and FPI Riser Vent terminal are certifi ed for installations using FPI venting systems as well as Simpson Dura-Vent® Direct Vent GS,
24" Pipe
Length
When using Rigid Vent other than
Simpson Dura-Vent, 3 screws must be
used to secure rigid pipe to adaptor.
12Hampton® H35 Direct Vent Freestanding Gas Stove
INSTALLATION
ROTATING 45O ELBOW FOR STRAIGHT HORIZONTAL TERMINATIONS
1) Remove all 4 screws that secure
the elbow to the unit using a 1/4"
magnetic nut driver.
Remove all 4 screws
and washers
Horizontal Terminations for All
Venting Systems
The shaded areas in the diagram below show
all allowable combinations of vertical runs
with horizontal terminations. Maximum one
90O elbow (two 45o elbows equal one 90o
elbow).
Propane and Natural Gas:
Residential, Manufactured and
Mobile Homes Installations
2) Rotate the elbow 180
3) Secure the elbow by securing
it with the 4 screws.
o
VENTING ARRANGEMENTS
Vertical Terminations Systems for
Residential Manufactured and Mobile Homes
The shaded area in the diagram below shows all allowable combinations of straight vertical
and offset to vertical runs with vertical terminations. Maximum two 45o elbows.
If the vent is ENCLOSED in a chase (min. size 9" x 9") maintain a 1-1/4" clearance to combustibles.
May be installed in Manufactured (Mobile) Homes after fi rst sale.
Offset to Vertical Terminations
The venting arrangements diagrammed below,
have a min. of 75% (fl ue loss) effi ciency with Fan
Off, as required for manufactured homes. (Actual
effi ciency may be as high as 85%)
May be installed in Manufactured (Mobile)
Homes after fi rst sale.
NOTE: See "Vent Restrictor Position" section for
installation instructions for the Vent Restrictor
Position.
Hampton® H35 Direct Vent Freestanding Gas Stove
13
INSTALLATION
HORIZONTAL TERMINATIONS USING RIGID PIPE
The two diagrams show all allowable combinations of straight horizontal termination
using Rigid Pipe. Restrictor position "A".
VENTING ARRANGEMENTS
Venting Arrangements -Straight Horizontal Termination at a De-Rated BTU
The diagrams show all allowable combinations of straight horizontal termination using
Rigid Pipe. Restrictor position "A". Refer to
the "Conversion Kit to Lower BTU Rating"
section for de-rating instructions.
Dura-Vent Snorkel Termination
Dura-Vent Snorkel Termination
Riser Vent Termination
Riser Vent Termination
*If this is an outside corner, the minimum distance between the vent and the outside corner
is 6” (15cm). See “F” on the diagram in the
"Exterior Vent Terminal Locations" section.
14Hampton® H35 Direct Vent Freestanding Gas Stove
Horizontal Venting with Two (2) 90o Elbows
One 90o elbow = Two 45o elbows.
INSTALLATION
Option V H + H1
A) 3' Min. 2' Max.
B) 4' Min. 3' Max.
C) 5' Min. 4' Max.
D) 6' Min. 5' Max.
E) 7' Min. 6' Max.
F) 8' Min. 8' Max.
Lengths do not include elbow indicated
Vent restrictor position A (fully open), refer to the
"Vent Restrictor Position" section.
With these options, maximum total pipe length is 30
feet with minimum of 8 feet
total vertical and maximum
8 feet total horizontal.
Please note minimum 1
foot between 90o elbows
is required.
Horizontal Venting with Two (2) 90o Elbows
One 90o elbow = Two 45o elbows.
H1
V
H
Option H V H + H1
A) 1' Max. 2' Min. 3' Max.
B) 2' Max. 3' Min. 5' Max.
C) 3' Max. 5' Min. 6' Max.
D) 4' Max. 7' Min. 7' Max.
E) 5' Max. 9' Min. 8' Max.
Lengths do not include elbow indicated
Vent restrictor position A (fully open), refer to the "Vent
Restrcitor Postion" section.
With these options, max.
total pipe length is 30 feet
with min. of 9 feet total
vertical and max. 8 feet
total horizontal.
Please note min. 1 foot
between 90o elbows is
required.
H1
H
V
Hampton® H35 Direct Vent Freestanding Gas Stove
15
Loading...
+ 33 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.