WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in serious
injury, death, or property damage.
- Do not store or use gasoline or other ammable vapors and liquids in the vicinity of this or any other
appliance.
- WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch: do not use any phone in your building.
Leave the building immediately.
• Immediately call your gas supplier from a neighbour's phone. Follow the gas supplier's
instructions.
• If you cannot reach you gas supplier, call the re department.
Installation and service must be performed by a qualied installer, service agency or the gas supplier.
Tested by:
Installer: Please complete the details on the back cover
and leave this manual with the homeowner.
Homeowner: Please keep these instructions for future reference.
919-446d
FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 Venture St., Delta, BC Canada, V4G 1H4
04.26.17
2
|
HAMPTON
®
Direct Vent Freestanding Gas Stove
To the New Owner:
Congratulations!
You are the owner of a state-of-the-art Hampton® Gas Stove by FPI FIREPLACE PRODUCTS INTERNATIONAL LTD.
The H15-10 is a hand crafted appliance and has been designed to provide you with all the warmth and charm of a wood
replace at the ick of a switch. The model H15-10 has been approved by Warnock Hersey/Intertek for both safety and
eciency. As it also bears our own mark, it promises to provide you with economy, comfort and security for many trouble
free years to follow. Please take a moment now to acquaint yourself with these instructions and the many features of your
Hampton® Stove.
2 | Hampton® H15-10 Direct Vent Freestanding Gas Stove
dimensions
|
3
Dimensions
Unit Dimensions with horizontal vent.............................4
Unit Dimensions with vertical vent ................................. 5
Installation
Important Message ......................................................8
Hampton® H15-10 Direct Vent Freestanding Gas Stove | 3
4
22-7/8"
19-3/8"
24-11/16"
20-11/16"
17-13/16"
19-1/8"
14-1/4
13-5/8"
21-1/4"
19-1/8"
(525mm)
(451mm)
(485mm)
(540mm)
(626mm)
(581mm)
(492mm)
(345mm)
(485mm)
(361mm)
|
dimensions
UNIT DIMENSIONS WITH HORIZONTAL VENT
ALL PICTURES / DIAGRAMS SHOWN THROUGHOUT THIS MANUAL ARE FOR ILLUSTRATION PURPOSES ONLY.
ACTUAL PRODUCT MAY VARY DUE TO PRODUCT ENHANCEMENTS.
4 | Hampton® H15-10 Direct Vent Freestanding Gas Stove
UNIT DIMENSIONS WITH VERTICAL VENT
dimensions
|
5
Hampton® H15-10 Direct Vent Freestanding Gas Stove | 5
6
Fabriqué au Canada
919-447a
|
safety decal
This is a copy of the label that accompanies
each Direct Vent Freestanding Gas Stove. We
have printed a copy of the contents here for
your review.
®
NOTE: Hampton
units are constantly being improved. Check the label on the unit and if there is
a difference, the label on the unit is the correct one.
DUPLICATE SERIAL NO.
Listed: VENTED GAS FIREPLACE HEATER / FOYER AU GAZ À ÉVACUATION
Certified for/Certifi e pour: CANADA and U.S.A.é
Tested to: CAN/CGA-2.17-M91(R2009)
4001172
NATURAL GAS STOVE: Model H15-NG10
L
Minimum supply pressure
Model/Modele:
H15-NG10
Manifold pressure High
Manifold pressure Low
Maximum Input
Minimum Input
Orifice size
Altitude
PROPANE GAS STOVE: Model H15-LP10
L
Minimum supply pressure
Model/Modele:
H15-LP10
Manifold pressure High
Manifold pressure Low
Maximum Input
Minimum Input
Orifice size
Altitude
This appliance must be installed in accordance with local codes, if any; if none, follow the National Fuel Gas Code, ANSI Z223.1, or Natural Gas and Propane Installation
Code, CSA B149.1.
This appliance must be installed in accordance with the Standard CAN/CSA Z240 MH, Mobile Housing, in Canada, or with the Manufactured Home Construction and Safety
Standard, Title 24 CFR, Part 3280, in the United States, or when such a standard is not applicable, ANSI/NCSBCS A225.1/NFPA 501A, Manufactured Home Installations
Standard or ANSI A119.2 ou NFPA 501C Standard for Recreational Vehicles
This appliance is only for use with the type of gas indicated on the rating plate and may be installed in an aftermarket, permanently located, manufactured (mobile) home where
not prohibited by local codes. See owner's manual for details. Optional Fan Kit (Part # 382-917)
Installer l'appareil selon les codes ou règlements locaux, ou, en l'absence de tels règlements, selon les codes d'installation ANSI Z223.1, National Fuel Gas Code ou CSAB149.1 en vigueur.
Installer l'appareil selon la norme CAN/CSA-Z240, Série MM, Maison mobiles ou CAN/CSA-Z240 VC, Véhicules de camping, ou la norme 24 CFR Part 3280, Manufactured
Home Construction and Safety Standard. Si ces normes ne sont pas pertinentes, utilisez la norme ANSI/NCSBCS A225.1/NFPA 501A, Manufactured Home Installations
Standard, ou ANSI A119.2 ou NFPA 501C Standard for Recreational Vehicles.
Cet appareil doit être utilisé uniquement avec le type de gaz indiqué sur la plaque signalétique. Cet appareil peut être installé dans une maison préfabriquée ou mobile (É.-U.
seulement) installée à demeure si les règlements locaux le permettent. Voir la notice de l'utilisateur pour plus de renseignements. Cet appareil ne peut pas être utilisé avec
d'autres gaz sauf si une trousse de conversion certifiée est fournie.
This vented gas fireplace heater is not for use with air filters. Ne pas utiliser de filtre à air avec ce foyer au gaz à évacuation.
For use with glass doors certified with the appliance only. À utiliser uniquement avec les portes vitrées certifiées avec l'appareil.
For Use Only with Barrier (Part # 382-005) Follow installation instructions.
Utiliser uniquement avec l’écran de sécurité (pièce n°382-005). Suivre les consignes d'installation.
VENTED GAS FIREPLACE HEATER - NOT FOR USE WITH SOLID FUELS.
MAY BE INSTALLED IN MANUFACTURED (MOBILE) HOMES AFTER FIRST SALE.
APPAREIL FONCTIONNANT AU GAZ NATUREL
Modèle H15-NG10
Pression d’alimentation minimum
Pression manifold - lev e é é
Pression - basse manifold
D bit calorifique maximumé
D bit calorifique minimumé
Taille de l'orifice
Altitude
APPAREIL FONCTIONNANT AU PROPANE
Modèle H15-LP10
Pression d'alimentation minimum
Pression manifold - lev e é é
Pression manifold - basse
D bit calorifique maximumé
D bit calorifique minimumé
Taille de l'orifice
Altitude
DO NOT REMOVE THIS LABEL / NE PAS ENLEVER CETTE ÉTIQUETTE
Minimum Clearances to Combustibles /
aux matériaux combustibles
Horizontal
Minimum ceiling height from top of unit:24"/610mm
Hateur min plafond depuis le haut de
l'appareil: 24"/610mm
A 6" / 150mm
B 0" / 0mm
See Manual for details / Voir manuel pour plus de détails
Minimum clearance of Vent Terminal
to Outside Corner & Inside Corner:
with Dura-Vent Cap 12"/300mm
ELECTRICAL SUPPLY/ALIMENTATION ÉLECTRIQUE:
115V_60HZ less than/moins de 2 AMP
FPI Fireplace Products International Ltd.
Made in Canada/
301
Serial No./ No de série
301
Dégagements minimaux
Left Side Wall
Pipe
Right Side Wall
with AstroCap 6"/150mm
Delta, BC, Canada
Left Side Wall
Vertical
Pipe
Right Side Wall
C 2" / 50mm
E 2" / 50mm
For the State of Massachusetts, installation and repair must be done by a plumber or gasfitter licensed in the Commonwealth of Massachusetts.
For the State of Massachusetts, flexible connectors shall not exceed 36 inches in length.
For the State of Massachusetts, the appliances individual manual shut-off must be a t-handle type valve.
The State of Massachusetts requires the installation of a carbon monoxide alarm in accordance with NFPA 720 and a CO alarm with battery back
up in the same room where the gas appliance is installed.
6 | Hampton® H15-10 Direct Vent Freestanding Gas Stove
requirements
MA Code - CO Detector
(for the State of Massachusetts only)
5.08: Modifications to NFPA-54, Chapter 10
(2) Revise 10.8.3 by adding the following additional requirements:
(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for
residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than
seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall
be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled
equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is
installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery
operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure
served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of
qualified licensed professionals for the installation of hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon
monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of
thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon
monoxide detector with an alarm shall be installed.
|
7
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions
shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight
(8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The
sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL
OBSTRUCTIONS".
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation
unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR
5.08(2)(a)1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by
the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or
structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product
Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the
instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a
Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies
"special venting systems", the following requirements shall be satisfied by the manufacturer:
1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and
2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and
detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions,
all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of
the installation.
Hampton® H15-10 Direct Vent Freestanding Gas Stove | 7
8
|
installation
IMPORTANT MESSAGE
SAVE THESE
INSTRUCTIONS
The Direct Vent Freestanding Gas Stove must
be installed in accordance with these instructions.
Carefully read all the instructions in this manual
first. Consult the building authority having jurisdiction to determine the need for a permit prior
to starting the installation.
Note: Failure to follow the instructions could
cause a malfunction of the heater
which could result in death, serious
bodily injury, and/or property damage.
Failure to follow these instructions
may also void your re insurance and/
or warranty.
Note: These instructions take precedence
over Simpson Dura-Vent instructions.
SPECIFICATIONS
Fuels: H15-NG10 is approved for use with
natural gas.
H15-LP10 is approved for use with
liquefied petroleum gases (propane).
Electrical: 120V A.C. system.
Optional Circulation Fan:
Variable speed, 125/75.
Log Sets: Ceramic fibre, 4 per set.
Vent System: Coaxial (6-5/8" outer / 4" inner
liner) rigid flue and termination cap.
MOBILE / MANUFACTURED
HOMES AFTER FIRST SALE
This Hampton® product has been tested and
listed by ITS Testing Services as a Direct Vent
Room Heater to the following standards:
CGA-2.17-M91, and ANSI Z21.88-2014/CSA
2.33-2014.
This Direct Vent System Appliance must be
installed in accordance with the manufacturer's
installation instructions and the Manufactured
Home Construction and Safety Standard, Title
24 CFR, Part 3280, or the current Standard of
Fire Safety Criteria for Manufactured Home Installations, Sites, and Communities ANSI/NFPA
501A, and with CAN/CSA Z240-MH Mobile Home
Standard in Canada.
This appliance installation must comply with the
manufacturer's installation instructions and local
codes, if any. In the absence of local codes follow the current National Fuel Gas Code, ANSI
Z223.1 and the current National Electrical Code
ANSI/NFPA 70 in the U.S.A., and the current CAN/
CGA B149 Gas Installation Code and the current
Canadian Electrical Code CSA C22.1 in Canada.
This Hampton® Mobile/Manufactured Home
Listed appliance comes factory equipped
with a means to secure the unit.
This Hampton® Mobile/Manufactured
Home listed appliance comes equipped
with a dedicated #8 ground lug to which
an 18 gauge copper wire from the steel
chassis ground must be attached.
This appliance may only be installed in an
aftermarket permanently located, manufactured (USA only) or mobile home,
where not prohibited by local codes.
This appliance is only for use with the
type of gas indicated on the rating plate.
This appliance is not convertible for use
with other gases, unless a certified kit
is used.
BEFORE YOU START
Safe installation and operation of this appliance requires common sense, however, we are required by
the Canadian Safety Standards and ANSI Standards
to make you aware of the following:
INSTALLATION AND REPAIR SHOULD
BE DONE BY AN AUTHORIZED
SERVICE PERSON. THE APPLIANCE
SHOULD BE INSPECTED BEFORE
USE AND AT LEAST ANNUALLY BY A
PROFESSIONAL SERVICE PERSON.
MORE FREQUENT CLEANING MAY
BE REQUIRED DUE TO EXCESSIVE
LINT FROM CARPETING, BEDDING
MATERIAL, ETC. IT IS IMPERATIVE THAT
CONTROL COMPARTMENTS, BURNERS
AND CIRCULATING AIR PASSAGEWAYS
OF THE APPLIANCE BE KEPT CLEAN.
DUE TO HIGH TEMPERATURES, THE
APPLIANCE SHOULD BE LOCATED
OUT OF TRAFFIC AND AWAY FROM
FURNITURE AND DRAPERIES.
WARNING: FAILURE TO INSTALL THIS
APPLIANCE CORRECTLY WILL VOID
YOUR WARRANTY AND MAY CAUSE A
SERIOUS HOUSE FIRE.
CHILDREN AND ADULTS SHOULD BE
ALERTED TO THE HAZARDS OF HIGH
SURFACE TEMPERATURES, ESPECIALLY THE FIREPLACE GLASS, AND
SHOULD STAY AWAY TO AVOID BURNS
OR CLOTHING IGNITION.
YOUNG CHILDREN SHOULD BE CAREFULLY SUPERVISED WHEN THEY ARE
IN THE SAME AREA AS THE APPLIANCE. TODDLERS, YOUNG CHILDREN
AND OTHERS MAY BE SUSCEPTIBLE
TO ACCIDENTAL CONTACT BURNS. A
PHYSICAL BARRIERS IS RECOMMENDED IF THERE ARE AT RISK INDIVIDUAL
IN THE HOUSE. TO RESTRICT ACCESS
TO A FIREPLACE OR STOVE, INSTALL
AN ADJUSTABLE SAFETY GATE TO
KEEP TODDLERS, YOUNG CHILDREN
AND OTHER AT RISK INDIVIDUALS OUT
OF THE ROOM AND AWAY FROM HOT
SURFACES.
CLOTHING OR OTHER FLAMMABLE
MATERIAL SHOULD NOT BE PLACED
ON OR NEAR THE APPLIANCE.
A BARRIER DESIGNED TO REDUCE
THE RISK OF BURNS FROM THE HOT
VIEWING GLASS IS PROVIDED WITH
THIS APPLIANCE AND SHALL BE
INSTALLED FOR THE PROTECTION
OF CHILDREN AND OTHER AT-RISK
INDIVIDUALS
IF THE BARRIER BECOMES DAMAGED,
THE BARRIER SHALL BE REPLACED
WITH THE MANUFACTURER'S BARRIER
FOR THIS APPLIANCE.
ANY SAFETY SCREEN, GUARD, OR
BARRIER REMOVED FOR SERVICING
AN APPLIANCE MUST BE REPLACED
PRIOR TO OPERATING THE APPLIANCE.
8 | Hampton® H15-10 Direct Vent Freestanding Gas Stove
installation
|
9
1) Provide adequate clearances for servicing,
proper operation and around the air openings
into the combustion chamber.
2) The appliance must be installed on a flat, solid,
continuous surface (e.g. wood, metal, concrete).
This may be the floor, or it can be raised up
on a platform to enhance its visual impact. The
appliance may be installed on carpeting, tile,
wood flooring or other combustible material,
because the appliance's base extends the full
width and depth of the appliance. The Direct
Vent Freestanding Gas Stove can be installed
in a wide variety of ways and will fit nearly any
room layout. It may be installed in a recessed
position, framed out into the room, or across
a corner.
3) The Direct Vent Freestanding Gas Stove is
approved for alcove installations, which meet
the clearances listed in the "Clearance to
Combustibles" section. This unit is approved
for manufactured home installations, see the
"Manufactured Mobile Home Additional Requirements" and "Rigid Pipe Venting Systems"
sections for the required vent arrangements.
If installed into a manufactured home the unit
must be bolted down to the floor.
4) This appliance is Listed for bedroom installations when used with a Listed Millivolt Thermostat. Some areas may have further requirements, check local codes before installation.
cleaning may be required due to excessive
lint from carpeting, bedding material, etc. It
is imperative that control compartments, and
circulating air passageways of the appliance
be kept clean and free from excessive lint from
carpeting.
4) See general construction and assembly instructions. The appliance and vent should be
enclosed when installed in or passing through a
living area, where children may come in contact
with it.
5) This appliance must be connected to the specified vent and termination cap to the outside of
the building envelope.Never vent to another
room or inside a building. Make sure that the
vent is fitted as per the instructions starting in
the "Exterior Vent Terminal Locations" section.
6) Inspect the venting system annually for blockage and any signs of deterioration.
7) Venting terminals shall not be recessed into a
wall or siding.
8) Any safety glass removed for servicing must
be replaced prior to operating the appliance.
9) To prevent injury, do not allow anyone who is
unfamiliar with the operation to use the fireplace.
INSTALLATION CHECKLIST
a. Log Set Installation
b. Wall Thermostat
c. Remote Control
9) Final check. Refer to the "Final Check" section.
Before leaving this unit with the customer, the
installer must ensure that the appliance is firing correctly and operation fully explained to customer.
This includes:
1) Clocking the appliance to ensure the correct
firing rate (rate noted on label) after burning
appliance for 15 minutes.
2) If required, adjusting the primary air to ensure
that the flame does not carbon. First allow the
unit to burn for 15-20 min. to stabilize.
CAUTION: Any alteration to the product that
causes sooting or carboning that results in damage is not the responsibility of the manufacturer.
5) This appliance is Listed for Alcove installations,
maintain minimum Alcove clearances as follows, minimum width of 32-1/2" (825mm), a
maximum depth of 36" (914mm), and minimum
height of 24" (610mm) from top of unit to ceiling.
6) We recommend that you plan your installation on
paper using exact measurements for clearances
and floor protection before actually installing this
appliance. Have a qualified building inspector
review your plans before installation.
GENERAL SAFETY
INFORMATION
1) The appliance installation must conform with
local Canadian Electrical Code.
2) The appliance when installed, must be electrically grounded in accordance with local codes,
or in the absence of local codes with the current
National Electrical Code, ANSI/NFPA 70 or CSA
C22.1 Canadian Electrical Code.
3) The appliance should be inspected for shipping
damage before use and serviced annually by a professional service person. More frequent
Emissions from burning wood or gas could
contain chemicals known to the State of
California to cause cancer, birth defects or
other reproductive harm.
1) Locate your gas appliance. Refer to the following
sections:
a. Locating Your Gas Stove
b. Clearances to Combustibles
c. "Venting Introduction" to "Exterior Vent
Terminal Locations" sections.
2) Install Optional Fan. Refer to the "Optional Fan
Installation" section.
3) Set vent restrictor. Refer to the "Vent Restrictor
Position" section.
4) Install venting: Check all venting requirements.
See "Venting Introduction" to "Dura-Vent Vertical Termination" sections.
5) Make gas connections. Refer to the "Gas Connection" section.
If converting to Propane, make changes prior
as instructed in the "Conversion from Natural
Gas to Propane" section.
6) Install 3 AAA batteries into Remote transmitter and pair with the IFC board (see Remote
Control section).
7) Test Gas Pressure. Refer to the "Gas Pipe
Pressure Testing" section.
8) Install standard and optional features. Refer
to the following sections where applicable:
Hampton® H15-10 Direct Vent Freestanding Gas Stove | 9
10
|
installation
CLEARANCES TO
COMBUSTIBLES
The clearances listed are MINIMUM distances.
Measure the clearance to both the appliance and
the chimney connector. The farthest distance is correct if the two clearances do not coincide.
For example, if the appliance is set as indicated in
one of the figures but the connector is too close,
move the stove until the correct clearance to the
connector is obtained.
This appliance may be installed only with the
clearances as shown in the situations pictured.
Do not combine clearances from one type of
installation with another in order to achieve
closer clearances.
This unit can be installed on a solid combustible
surface like a wood floor. This unit can also be
installed directly on carpeting or vinyl.
Use the minimum clearances shown in the diagrams below:
H15-NG10 & H15-LP10 Clearances
A Left Side Wall to Unit*6" / 150 mm
*B Back Wall to Unit 0" / 0 mm
C Vertical Vent Pipe to Back Wall
2" / 50 mm
E Unit Corner to Wall 2" / 50 mm
Unit Top to Alcove Ceiling 24" / 610 mm
Minimum ceiling height is 24" /610 mm from top
of unit.
*IMPORTANT
It is recommended that unit is moved away from
the wall, if installing the blower option, so the fan
can be easily installed and/or serviced.
LOCATING YOUR
GAS STOVE
When selecting a location for your stove, ensure
that the clearances listed above are met as well
as ensuring that there is adequate accessibility for
servicing and proper operation.
A) Cross Corner
* 12' max. only if vertical height is achieved.
B) Room Divider
C) Island
D) Flat on Wall
E) Flat on Wall Corner
F) Flush with Wall/Alcove
For Vent Termination requirements, see the "Exterior
Vent Terminal Locations" section.
MANUFACTURED MOBILE
HOME ADDITIONAL
REQUIREMENTS
1) Ensure that structural members are not cut or
weakened during installation.
2) Ensure proper grounding using the #8 ground
lug provided.
3) Appliance must be anchored to the floor with
the supplied anchoring methods.
10 | Hampton® H15-10 Direct Vent Freestanding Gas Stove
COMBUSTION AND
VENTILATION AIR
The combustion air from this appliance is drawn
from outside the building through the outer flue.
Extra provision for combustion air inside the
room is not required.
Lift light assy bracket o bolts to install
bulb
Remove one screw in location shown
4. Install bulb.
Note: Oils from hands will shorten the life of the bulbs,
do not handle bulbs with bare hands.
5. Reverse steps.
H15
OPTIONALFANINSTALLATION
Lift Rear Panel o of the 2 top bolts.
bolt
1. Remove the rear access panel on the back of
the stove by removing 2 bolts at the bottom of
the panel. Lift panel up and away to remove.
2. Place a grommet on wiring from fan to be plugged
into the receiver.
3. Remove left side access panel (when
facing front) by removing one screw.
4. Undo wire clip to release red and black
fan wires. Remove cap ends from the
wire spades and plug in fan wires - black
to black and red to red.
5. Tuck the fan assembly in behind the legs
as shown. On either side of the unit there
will be slits located on the body of the
stove. Slide the fan up into the slits until
the mounting holes line up with the holes
located on the fan assembly. Secure with
one screw per side (leave right side screw
loose).
6. Eliminate any slack from fan wire by
pulling into the unit and securing with
wire clip.
7. Tighten screw on right side.
8. Reinstall back access panel.
9. Plug the fan into the nearest outlet
10. To remove fan - reverse steps.
WARNING: Electrical Grounding Instructions
This appliance is equipped with a three pronged (grounding) plug for your protection against shock hazard and should be plugged directly into a properly grounded
three-prong receptacle. Do not cut or remove the grounding prong from this plug.
Cap ends
Thermostat (Optional)
(Millivolt)
OPTIONAL FAN
INSTALLATION
installation
|
11
Hampton® H15-10 Direct Vent Freestanding Gas Stove | 11
12
|
installation
GLASS FRONT
REMOVAL / INSTALLATION
1. Turn off stove and allow to return to room temperature.
2. Lift off cast top and place on a soft surface.
3. Remove 2 bolts and lift off cast front - place front
carefully on a soft surface.
5. Lift both latches securing glass door and
remove door.
6. To reinstall–reverse steps.
WALL THERMOSTAT
INSTALLATION
1. Open the front panel and remove the cover
plate by removing two screws.
2. Disconnect one of the wires from the switch
as shown, connect this wire to the thermostat.
4. Slide the light assembly bracket out of the way.
3. Ensure switch is set to <ON> position.
4. Reinstall front panel.
12 | Hampton® H15-10 Direct Vent Freestanding Gas Stove
installation
|
13
VENTING INTRODUCTION
The Horizontal Termination Kit and the Simpson
Dura-Vent Direct Vent venting systems, in combination with the Direct Vent Freestanding Gas
Stoves, H15-NG10, and H15-LP10, have been
tested and listed as direct vent heater systems by
Warnock Hersey.
These units use the "balanced flue" technology
Co-Axial system. The inner liner vents products
of combustion to the outside while the outer pipe
draws outside combustion air into the combustion
chamber thereby eliminating the need to use heated
room air for combustion and losing warm room air
up the chimney.
Note: These ue pipes must not be
connected to any other appliance.
The gas appliance and vent system must be vented
directly to the outside of the building, and never
be attached to a chimney serving a separate solid
fuel or gas burning appliance. Each direct vent gas
appliance must use it's own separate vent system.
Common vent systems are prohibited.
IMPORTANT
Read all instructions carefully before starting the
installation. Failure to follow these instructions may
create a fire or other safety hazard, and will void the
warranty. Be sure to check the venting and clearance to combustible requirements. Consult your
local building codes before beginning installation.
The location of the termination cap must conform
to the requirements in the "Exterior Vent Terminal
Locations" section.
INSTALLATION
PRECAUTIONS
These venting systems are engineered products
that have been designed and tested for use with
the H15-NG10, and H15-LP10. The warranty will
be voided and serious fire, health or other safety
hazards may result from any of the following actions:
1) Installation of any damaged Rigid Pipe component.
2) Unauthorized modification of any Rigid Pipe
System.
3) Installation other than as instructed by Simpson
Dura-Vent and FPI Fireplace Products International Ltd.
Warning: Always maintain required
clearances (air spaces) to nearby
combustibles to prevent a re hazard.
Do not ll air spaces with insulation.
Be sure to check the vent termination clearance
requirements from decks, windows, soffits, gas
regulators, air supply inlets and public walkways as
specified in the "Exterior Vent Terminal Locations"
section and in your local building codes.
The gas appliance and vent system must be
vented directly to the outside of the building,
and never be attached to a chimney serving a
separate solid fuel or gas-burning appliance.
Each direct vent gas appliance must use it's own
separate vent system. Common vent systems are
prohibited.
SAFETY PRECAUTIONS
FOR THE INSTALLER
1) Wear gloves and safety glasses for protection.
2) Exercise extreme caution when using ladders or on roof tops.
3) Be aware of electrical wiring locations in
walls and ceilings.
VENT RESTRICTOR
POSITION
To set the Vent restriction as indicated in the
Venting Arrangement diagrams in the "Rigid
Pipe Venting System" section, simply loosen
the screws and push the vent restrictor plate to
the correct position. Tighten the screws. This
will be located inside the firebox.
ROTATING ELBOW
1) Remove top casting.
2) Remove all 4 screws that secure
the elbow to the unit using a 1/4"
magnetic nut driver.
Remove all 4 screws
and washers
Hampton® H15-10 Direct Vent Freestanding Gas Stove | 13
3) Rotate the elbow 180
4) Secure the elbow by securing
it with the 4 screws.
o
14
|
installation
EXTERIOR VENT TERMINAL LOCATIONS
1
Minimum Clearance Requirements
A
Clearance above grade, veranda, porch, deck, or balcony12"(30cm)12"(30cm)
B
Clearance to window or door that may be opened 12"(30cm)9" (23cm)
C
Clearance to permanently closed window**
D
Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet (61cm)
from the center line of the terminal (check with the local code)
E
Clearance to unventilated soffit12"(30cm)12"(30cm)
F
Clearance to outside corner: with AstroCap and Vent Riser Termination Cap 6"(15cm)6"(15cm)
Clearance to outside corner: with all other approved Termination Caps.12"(30cm)12"(30cm)
G
Clearance to inside corner: with AstroCap and Vent Riser Termination Cap 6"(15cm) 6"(15cm)
Clearance to inside corner: with all other approved Termination Caps12"(30cm)12"(30cm)
H
Clearance to each side of center line extended above meter/regulator assembly 36"(90cm)
J
Clearance to service regulator vent outlet36"(90cm)*
K
Clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance12"(30cm)9" (23cm)
L
Clearance to a mechanical air supply inlet
#3' (91cm) above if within 10' (3m) horizontally.
M
Clearance above paved sidewalk or a paved driveway located on public property 84"(2.1m)
N
Clearance under veranda, porch, deck, or balcony 12"(30cm)
1
In accordance with current CSA B149.1, Natural Gas and Propane Installation Code
2
In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code
┼
A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings.
‡ Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
Clearance in accordance with local installation codes and the requirements of the gas supplier
*
a
3 feet (91cm) within a height of 15 feet (4.5m) above the meter / regulator assembly
b
3 feet (91cm) above - if within 10 feet (3m) horizontally
Canada
22"(56cm)22"(56cm)
a
72"(1.8m)36"(90cm)
┼
‡
USA
*
*
*
2
b
14 | Hampton® H15-10 Direct Vent Freestanding Gas Stove
installation
4” X 6-5/8” RIGID PIPE CROSS REFERENCE CHART
Components from different Manufacturers may not be mixed. Not all rigid pipe components are available directly from Regency.Note:The listed manufacturers may have other lengths not shown on this chart, which would also be approved.
4” X 6-5/8” RIGID PIPE
CROSS REFERENCE CHART
Components from different Manufacturers may not be mixed. Not All Rigid Pipe components are available directly from FPI.
* Olympia Ventis DV applicable for the following units only: B36XTE, B36XTCE, B41XTE, B41XTCE, P36, P36E
FPI
946-506/PVent Guard (Optional) for AstroCap946-205Vinyl Siding Shield for Riser Vent Te rminal
510-994Rigid Pipe Adaptor (Must use with all rigid piping)946-208/PVent Guard (Optional) for Riser Vent Terminal
640-530/PRiser Vent Terminal946-523/PAstroCap Horizontal Cap
Note: When using Metal-Fab Sure Seal Rigid Piping - please note that the Adaptor (4DDA) must be used in conjunction with FPI Rigid Pipe Adaptor (510-994).
Offset Pipe Selection: Use this table to determine offset pipe lengths.
Pipe Length
(L)
0” (0mm)4-7/8” (124mm)13-7/8” (340mm)Simpson Direct Vent Pro: www.duravent.com
4” x 6-5/8” VentingFor specifi c instructions on venting components - visit the
Run (X)Rise (Y)
16 | Hampton® H15-10 Direct Vent Freestanding Gas Stove
946-206Vinyl Siding Standoff for AstroCap
manufacturers website listed below.
Pipe Length
Vertical
Termination
Cap
Storm Collar
Flashing
Ceiling Firestop
24" Pipe
Length
Adj.Pipe Length
11"-14-5/8"
90 Elbow
o
Horizontal
Termination
Cap
Wall Thimble
Vinyl Siding
Standoff (Optional)
RIGID PIPE VENTING SYSTEMS
Horizontal or Vertical Terminations
Alternate
Horizontal
Termination
Caps
Max.
installation
|
17
WARNING:
Do not combine venting components from
different venting systems.
However use of the the AstroCapTM and FPI
Riser is acceptable with all systems.
This product has been evaluated by Intertek
for using a Rigid Pipe Adaptor in conjunction
with Duravent Direct-Vent, Selkirk Direct-Temp,
Ameri Vent Direct venting and Security Secure
Vent systems. Use of these systems with the
Rigid Pipe adaptor is deemed acceptable
and does not affect the Intertek WHI listing of
components.
The FPI AstroCap
American Metal Products Ameri Vent Direct Vent, Security Secure Vent®, Selkirk Direct-Temp. AstroCapTM is a proprietary trademark of FPI Fireplace
Products International Ltd. Dura-Vent® and Direct Vent are registered and/or proprietary trademarks of Simpson Dura-Vent Co. Inc.
TM
and FPI Riser Vent terminal are cer tified for installations using FPI venting systems as well as Simpson Dura-Vent® Direct Vent,
When using Rigid Vent other than
Simpson Dura-Vent, 3 screws must be
used to secure rigid pipe to adaptor.
Hampton® H15-10 Direct Vent Freestanding Gas Stove | 17
Loading...
+ 39 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.