ACCESSORIES (for transformers listed in sections 3, 4, 7 and 10)
ENCLOSURE MOUNTING KITS
If wall and/or ceiling mounting is desired for a
transformer, optional mounting kits can be ordered
separately. These mounting kits are NOT available for
all enclosure case styles. Therefore, it is important
that you conrm your enclosure case style, then use
the selection table to the right to determine if A) a
mounting kit is available and B) determine the correct
HPS “Mounting Kit” part number that you must order.
One kit is required for each transformer. Note: Some of the mounting kits can be used for
both wall and ceiling mount, while others are for wall
mounting only. The table indicates which mounting
methods are available for each kit. The NW2 wall/ceiling mounting kit also includes a drip plate.
The NW2 wall/ceiling mounting kit is only designed for units up to 750 pounds (341 kg) maximum.
ACCESSORIES (for transformers listed in sections 3, 4, 7 and 10)
NW2 CEILING MOUNT - MOUNTING DIMENSIONS
MB
Front View
MA
Top View
NOTE: Please refer to enclosure dimensional drawings on
page 256 for more detailed dimensional information.
MOUNTING BRACKETS
BOTTOM DRIP PLATE
HOLES FOR
1/2" ROD(4)
NH5DP & NH6DP WALL/CEILING MOUNTING KITS
The NH5 and NH6 enclosures are designed with
integral wall mounting capabilities. However, when
you wall mount them, you must also install the bottom
drip plate as shown below. The “MB” dimensions listed
in the table below indicate the location for the wall
mounting hardware.
For ceiling mounting of the NH5 and NH6, refer to
the “MA” dimensions listed in the table below and hang
the enclosure using appropriate sized ceiling hanger
rods. However, you must be sure to install the bottom
drip plate to the bottom of the enclosure, then bring the
hanger rod down through both the enclosure bottom
mounting holes and through the drip plate mounting
holes and install mounting hardware.
NOTE: Do not ceiling mount either the NH5 or
NH6 enclosures without installing the bottom drip
plate. All mounting hardware should be rated Grade
8 or higher.
Mounting Enclosure MA MB
Kit P/N Style Dimension Dimension
NH5DP NH5 9.00 7.00
NH6DP NH6 9.00 8.00
NOTE: Please refer to enclosure dimensional drawings on page
256 for more detailed dimensional information.
ACCESSORIES (for transformers listed in sections 3, 4, 7 and 10)
ANTI-VIBRATION PAD AND VIBRATION ISOLATOR KITS
All standard transformers come with installed internal vibration absorbing pads to minimize noise during operation.
Optional external “anti-vibration” pad and “vibration isolator” (for higher noise dampening) kits can be used to
reduce operating noise even further. All are resistant to industrial contaminants like oils, acids and alkalies.
ANTI-VIBRATION PAD KITS
Part No. Case Style
P1NH Series
P2NJ Series
All Anti-Vibration Pad kits and Vibration Isolator kits contain
a set of four (4) pads or isolators. Therefore only one kit is
required per transformer.
Description
Set of four (4) rubber
anti-vibration pads which
replace the standard
steel enclosure washers.
VIBRATION ISOLATOR KITS
Part
No.
NMP1Up to 340 lbsSet of four (4) molded
NMP2341 to 680 lbs
NMP3681 to 1040 lbs
NMP41041 to 1740 lbs
NMP51741 to 2330 lbs
NMP62331 to 3450 lbs
NMP73451 to 4690 lbs
ACCESSORIES (for transformers listed in sections 8 and 9)
NQTW1 and NQTW2 Wall Mounting Kits
Transformer
Weight (Lb)
Description
neoprene and steel
plate assemblies
that virtually
eliminate vibration
noise between the
transformer and the
mounting surface.
GENERAL
The NQTW1 and NQTW2 wall mounting kits are specically
designed for HPS commercial or industrial encapsulated (potted)
distribution transformer units up to a maximum of 45kVA or 800 pounds
(363 kg). These mounting kits are designed for encapsulated (potted)
units only, no drip plate is included/required. Please contact HPS
customer service if you have any questions.
Note: Always measure and secure mounting brackets to the wall
surface rst, then lift the transformer (using appropriate lifting equipment)
onto the brackets and attach using minimum Grade 8 hardware.
INFORMATION
Enclosure
Case Style
NQ0-NQ8WallIncluded
NQS10Wall or FloorNQTW2
NQT3-NQT6WallIncluded
NQT7-NQT8Wall or FloorNQTW1
ACCESSORIES (for transformers listed in sections 8 and 9)
NQT ENCLOSURE SERIES NEMA 4/12 GASKET KITS
The following options and accessories offered are available on all standard and custom three phase HPS
Titan® industrial encapsulated distribution transformers for harsh environments and hazardous locations (see
section 8), HPS Fortress™ commercial encapsulated distribution transformers (see section 8) and encapsulated
autotransformers (see section 9).
Optional NEMA 4/12 Gasket Kits
Standard NEMA 3R rated NQT enclosures can easily be converted to a NEMA 4 or 12 rating by ordering and
installing the appropriate gasket kit as listed in the table below.
Nema 4/12 Gasket shown installed
on inside of NQT enclosure wiring
compartment cover. Ensure gasket
holes are aligned with cover holes.
Optional Stainless Steel Enclosures
Optional NEMA 4 and 12 rated stainless steel enclosures for encapsulated transformers are identical to the
standard steel enclosure designs but are designed using either type 304 or 316 stainless steel in accordance with
ANSI, NEMA, UL and ABS requirements for indoor, outdoor and marine duty applications.