GENERAL INFORMATION
HV HV
H1 H2 H1 H2
OR
OR
7 8642135 7 8642135
X4 X1X3X2
X4 X1X3X2
LV
LV LV
LV
X2
H2
H1
H3
X1
X3
X0
1
2
3
4
5
6
7
ELECTRICAL SCHEMATICS AND CONNECTION DIAGRAMS
SCD 1
SCHEMATIC CONNECTIONS
Primary Volts Connect lines to Inter-connect
240 480 416 H1, H4 H2-H3
120 240 208 H1, H4 H1-H3, H2-H4
Secondary Volts Connect lines to Inter-connect
24 32 48 240 X1, X4 X2-X3
12/24 16/32 24/48 120/240 X1, X2, X4 X2-X3
12 16 24 120 X1, X2 X2-X4, X1-X3
SCD 2
SCHEMATIC CONNECTIONS
Primary Volts Connect lines to Inter-connect
504 H1, H4 1-H2, 2-H3, H2-H3
492 H1, H4 3-H2, 2-H3, H2-H3
480 H1, H4 3-H2, 4-H3, H2-H3
468 H1, H4 5-H2, 4-H3, H2-H3
456 H1, H4 5-H2, 6-H3, H2-H3
444 H1, H4 7-H2, 6-H3, H2-H3
432 H1, H4 7-H2, 8-H3, H2-H3
252 H1, H4 1-H2, 2-H3, H1-H3, H2-H4
240 H1, H4 3-H2, 4-H3, H1-H3, H2-H4
228 H1, H4 5-H2, 6-H3, H1-H3, H2-H4
216 H1, H4 7-H2, 8-H3, H1-H3, H2-H4
Secondary Volts Connect lines to Inter-connect
240 X1, X4 X2- X3
120 X1, X2 X2-X4, X1-X3
120/240 X1, X2, X4 X2-X3
SCD 3
SCHEMATIC CONNECTIONS
GENERAL
INFORMATION
© Hammond Power Solutions Inc.
Primary Volts Connect lines to Inter-connect
630 H1, H2, H3 1-H1, 1-H2, 1-H3
615 H1, H2, H3 2-H1, 2-H2, 2-H3
600 H1, H2, H3 3-H1, 3-H2, 3-H3
585 H1, H2, H3 4-H1, 4-H2, 4-H3
570 H1, H2, H3 5-H1, 5-H2, 5-H3
480 H1, H2, H3 6-H1, 6-H2, 6-H3
456 H1, H2, H3 7-H1, 7-H2, 7-H3
432 H1, H2, H3 8-H1, 8-H2, 8-H3
Secondary Volts Connect lines to Inter-connect
208 480 X1, X2, X3 -
120 120 X1, X0 -
X2, X0 -
X3, X0 -
258
Data subject to change without notice.
GENERAL INFORMATION
HV HV
H1 H2 H1 H2
OR
OR
6 4 2 1 3 5 6 4 2 1 3 5
X4 X1 X3 X2
X4 X1 X3 X2
LV
LV LV
LV
H2
H3
H1
X1
X2
X0
X3
1
2
3
ELECTRICAL SCHEMATICS AND CONNECTION DIAGRAMS
SCD 4
SCHEMATIC CONNECTIONS
Primary Volts Connect lines to Inter-connect
208 277 347 380 416 600 H1, H2 ---
Secondary Volts Connect lines to Inter-connect
240 X1, X4 X2-X3
120/240 X1, X2, X4 X2-X3
120 X1, X2 X2-X4, X1-X3
SCD 5
SCHEMATIC CONNECTIONS
Primary Volts Connect lines to Inter-connect
120 208 240 277 380 416 480 600 H1, H2 1-2
114 198 228 263 395 456 570 H1, H2 2-3
108 188 216 249 347 374 432 540 H1, H2 3-4
SCD 6
SCD 7
Secondary Volts Connect lines to Inter-connect
240 X1, X4 X2-X3
120/240 X1, X2, X4 X2-X3
120 X1, X2 X2-X4, X1-X3
SCHEMATIC CONNECTIONS
Primary Volts Connect lines to Inter-connect
218 291 437 504 630 2520 4368 H1, H2 1-2
213 284 426 492 615 2460 4264 H1, H2 2-3
208 277 416 480 600 2400 4160 H1, H2 3-4
203 270 406 468 585 2340 4056 H1, H2 4-5
198 263 395 456 570 2280 3952 H1, H2 5-6
Secondary Volts Connect lines to Inter-connect
240 X1, X4 X2-X3
120/240 X1, X2, X4 X2-X3
120 X1, X2 X2-X4, X1-X3
SCHEMATIC CONNECTIONS
Primary Volts Connect lines to Inter-connect
218 242 252 437 483 504 604 630 H1, H2, H3 1
208 230 240 416 460 480 575 600 H1, H2, H3 2
198 219 228 395 437 456 570 570 H1, H2, H3 3
GENERAL
INFORMATION
© Hammond Power Solutions Inc.
Secondary Volts Connect lines to
208 230 240 380 416 460 480 600 X1, X2, X3
120 133 139 220 240 265 277 347 X1, X0 X2, X0 X3, X0
259
Data subject to change without notice.