Hammond Power Solutions NH SERIES Installation Guide

INSTALLATION, OPERATION AND MAINTENANCE GUIDE
FOR INDOOR/OUTDOOR DRY-TYPE TRANSFORMERS
FOR INDOOR/OUTDOOR DRY-TYPE TRANSFORMERS
WHICH UTILIZE A NH SERIES, NJ1, NJ2, NJ3 OR NJ4 ENCLOSURE
WHICH UTILIZE A NH SERIES, NJ1, NJ2, NJ3 OR NJ4 ENCLOSURE
*Note: This guide is Trilingual (English, French and Spanish)*
Literature No.: IOMGDDI
Issue Date: May 2010
(1) Do not lift or move a transformer without proper equipment and experienced personnel. On some larger kVA distribution transformers, lifting provisions are provided on the inside of the enclosure on the core & coil.
(2) Do not off-load the transformer until a full inspection has been completed.
(3) Use terminals only for electrical connections. Flexible connectors are recommended for bus connections. The transformer terminals are not designed to support the weight of supply or load
cables. Uni-strut supports can be added in the eld providing proper clearances are maintained.
(4) Connections should only be in accordance with the nameplate diagram or connection drawings.
(5) Make sure all power is disconnected before attempting any work on a transformer or inside of control box and ground all windings.
(6) Make certain all ground connections, line terminals and selected taps are complete and tighened before energizing the transformer.
(7) Do not attempt to change any taps - primary or secondary, while the transformer is energized.
(8) Do not change connections when the transformer is energized.
(9) Do not tamper with control panels, alarms, interlocks or control circuits.
(10) Do not adjust or remove any accessories or cover plates while the transformer is energized. No supply cables should come in contact with the core or any live part except the terminal that it is intende for.
CONTENTS
General 3 Handling 3 Receiving & Inspection 3 Storage 3 Installation 3 Ventilation 4 Accessibility 4 Transformer Sound Levels 4 Cable Connections 4 Grounding 5 Inspection Before Energization 5 Operation 5 Maintenance 6 Dry-out of Transformers 6 Accessories 6 Appendix A 7 Appendix B 8 Figure 1 9 Figure 2 10 Figure 3 11 Notes 12
- 2 -
INSTALLATION, OPERATION AND MAINTENANCE
OF DRY-TYPE TRANSFORMERS
GENERAL
Dry-type transformers are manufactured to provide optimum performance for a lifetime of uninterrupted service. Careful attention to the following instructions is recommended for safe and reliable operation.
Installation, operation and maintenance of transformers should be performed by authorized persons, familiar with electrical apparatus and the potential hazards involved.
Warning: Danger! There is the potential of electric shock whenever working in or around electrical equipment such as transformers. Power must be shut off before any work is conducted on a transformer.
As with any electrical device, transformers must be installed according to the requirements of the national and local electrical codes. Refer to ANSI/IEEE C57-94 may also be referred to for recommended installation, application, operation and maintenance of dry-type transformers.
HANDLING
Transformers are palletized and can either be lifted via a forklift truck or hoisted by the lifting lugs provided.
Appropriate lifting equipment should be used relative to the size of each transformer. For safety purposes and to protect the transformer, spreader bars are recommended.
No attempt should be made to lift or move a transformer from any points on the unit other than those indicated. Refer to Figures 1 and 2 (pages 9 and
10).
RECEIVING & INSPECTION
Immediately after receiving the transformer, it should be inspected for any transit damage and for correctness against the shipping documents.
The unit should be examined for any breaks in its packaging, dented or damaged enclosures or missing parts from the packing list.
If any damage is noted, a claim should be led
immediately with the carrier and a second copy of all
pertinent information relative to the order and the
circumstances should be led with the local sales ofce.
If this examination of the unit takes place outdoors, caution should be exercised such that inclement weather would not present further hazard.
STORAGE
Transformers that will not be immediately installed and energized, should be stored in a clean dry environment away from any environmental airborne contaminants.
It is recommended that transformers be stored in a heated building with the protective plastic wrap still installed.
INSTALLATION
Enclosures are designed and approved
in accordance with specications
CSA 22.2 No. 47 (General Purpose), CSA 22.2 No. 94 (Specialty Enclosures), NEMA 250 and UL 50. For IEC enclosure equivalents please see
IEC 60529 (Enclosure Classications
Designations).
a) Indoor/Outdoor Dry-Type Transformers with Enclosures
Most dry-type transformers are supplied with either a type 3R, 4 or 12 enclosure. Units may be installed indoors, or outdoors where applicable. If equipped with a type 1 enclosures, these units are for indoor use only.
Ventilated enclosures are recommended for indoor installation but may also be installed outdoors where weather conditions allow a type 3R ventilated enclosure to be installed.
For any outdoor location, the appropriate applicable codes must be followed including cable installation and hardware suitable for outdoor service.
Water tight couplings must be used at the knockouts and any holes in the enclosure must be drilled below any un-insulated live parts, (below LV terminals).
Dry-type transformers may be located in an
upright position on walls, oors, posts, beams or other
- 3 -
locations capable of supporting their weight with the proper accessories attached. Refer to Appendix B (page 8) for wall mounting kits.
Conventional open ventilated dry-type transformers have a bottom screen for air convection. When transformers are mounted above the ground surface a catcher plate should be installed under each transformer as a safety precaution against any hot particles that may fall through the screen in the event of a faulted condition. Refer to Appendix B (page 8).
It is important that ventilated transformers be installed in a dry area where the ambient air is clean and free of dust, dirt, corrosive fumes, moisture, heat or other adverse conditions. Transformers should not be installed in such a place having the possibility of water logging inside the enclosure.
In the event that a transformer has been subjected to moisture or dampness before installation, ensure that it is completely cleaned and dried before energization. The blowing of warmed air through the transformer is recommended to dry internal components. Refer to the section on dry-out of transformers.
b) Indoor/Outdoor Transformers with Non- Ventilated Type 4, 4X or 12 Enclosures.
However, transformers should not be located in areas where stored items are likely to interfere with either natural air convection or the capability to have them inspected. Passage ways or other areas where people could be exposed to live parts during inspection should also be avoided.
Adequate protection should be provided under any circumstances.
TRANSFORMER SOUND LEVELS
Transformers are an electrically energized apparatus and by their nature emit sound due to their component materials.
Transformers are required to meet NEMA standards for the maximum sound levels permissible. These sound level standards vary from 40 to 60 DB and hence, can be an annoyance if located in close proximity to where people work or reside.
Care should therefore be exercised in selecting sites for transformers particularly to avoid sensitive
areas like hospitals, classrooms, medical or ofce
facilities.
The following guidelines may be helpful:
Transformers equipped with non-ventilated type 4, 4X or 12 enclosures maybe located either indoors or outdoors in any similar location noted above. Non­ventilated enclosed transformers, although slightly larger, offer much greater protection against a variety of elements such as dust, dirt, snow, moisture, rain etc.
For any outdoor location, the appropriate applicable codes must be followed including cable installation and hardware suitable for outdoor service.
VENTILATION
Transformers are required to be installed in an area where they can be cooled by means of the free circulation of air where the average ambient temperature is 30°C (86°F) and should not exceed 40°C (104°F) at any time.
Adequate ventilation is essential for transformers to meet their nameplate kVA capability. All general purpose transformers should be located away from walls or any other obstructions (at least 6 inches when
oor mounted and 4 inches when wall mounted) to
allow free, clean circulation of air through the ventilation openings or around a non-ventilated unit.
ACCESSIBILITY
NEC standards require that transformers be accessible for inspection and located accordingly.
Units should be mounted away from corners or
reecting walls or ceilings.
Cable or other exible conduit should be
considered to make connections.
All dry-type transformers are provided with isolation rubber mounts between the core and coil assembly and the enclosure. However, sound absorbing vibration isolators may also be installed between the transformer and its mounting surface.
Acoustically absorbing materials could be
considered for walls and ceilings around the unit.
The location of the unit should be located as far as practical from areas where sound levels could be considered undesirable.
CABLE CONNECTIONS
The connecting cable size is determined from the line current rating of the transformers primary and secondary windings and may be selected from the information in Appendix A (page 7). Cables rated for at least 90°C (194°F) is recommended as are ALC9CU lugs.
Convenient pre-punched knockouts are provided on all ventilated transformer enclosures up to 150 kVA
- 4 -
three phase and 100 kVA single phase, to facilitate cable entry.
For non-ventilated transformers, pre-punched knockouts are not provided and the appropriate cable connector suitable for the application must be used.
Please refer to gures 1 and 2 (pages 9 and 10)
for cable entry locations.
Warning: Never attempt to change con­nections or taps unless the transformer is de-energized and all windings grounded.
Side entry of cables is recommended as it leaves the ventilated areas unobstructed.
Cable connection lugs of plated copper or aluminum may be used to connect to the transformer terminals. Terminals should be cleaned and electrical joint compounds are recommended for use on all electrical connections.
Refer to the transformer nameplate for primary and secondary voltage connection combinations and primary and/or secondary tap positions as applicable.
Transformers received from the factory will have tap leads installed on the nominal, or 100%, voltage position. The balance of the tap positions will still be coated with impregnation material and insulation.
To change taps, it is necessary to remove this insulation by gently removing the protective coating from the surface appropriately. The surface of the tap lead should be clean and coated subsequently with electrical compound.
NOTE: After installation of cables and connectors, a minimum of 1” clearance must be maintained from energized parts to all case parts.
GROUNDING
secondary and primary to secondary, should be greater than 10k ohms.
b) Before energizing and connecting any loads,
please measure and verify the output voltage
matches nameplate specications.
c) Ensure correct phase connections. Refer to the
nameplate vector diagram.
d) The load on a delta secondary winding with a 120 volt center tap should not exceed the normal current rating of the winding. This center tap is designed for a max. of 5% of the nameplate kVA.
e) When windings are connected in parallel (as in the case of dual voltage primaries), the primary taps for all coils must be connected to the identical percentage tap positions to avoid the shorting of turns. For tap positions, refer to the nameplate on the transformer.
f) The enclosure should be grounded with the appropriately sized conductor.
g) The total load among all the phases should be balanced as much as possible for optimum performance of the transformers windings.
Any three phase or single phase load may be connected to the transformer but the kVA loading on each phase must not exceed 1/3 of the nameplate kVA rating.
h) The clearance and tightness of all electrical connections should be checked.
i) If there is any reason to suspect that the transformer has been exposed to moisture during transit or storage, it should be checked for dryness before energization. This can be done by making an insulation resistance test. Dry-out procedures are on page 6.
All core and coil assemblies are solidly grounded to the enclosure internally to ensure that all conductive metal parts have the same potential.
The transformer enclosure in turn should also be securely and effectively grounded as a safety precaution.
This grounding should be in accordance with national electrical code standards.
INSPECTION BEFORE ENERGIZATION
For the safe and proper operation of the transformer, please check and verify the following:
a) The insulation resistance, core to primary, core to
OPERATION
For all relatively normal and clean installations, dry-type transformers will operate satisfactorily under normal conditions of energization and load.
For your reference, fully loaded dry-type transformers may appear warm to the touch, particularly on the cover of the unit.
Standards permit the temperatures of the cover to be 65°C (149°F) over ambient. This represents normal loading and should not be of concern.
Dry-type transformers are designed to operate continuously at their full nameplate kVA rating.
ANSI C57.96 provides guidance for loading
- 5 -
transformers under different conditions including:
Ambient temperatures that are varied from the ambient temperatures required for transformer operation.
Short time overload as it relates to time and temperature and the corresponding loss of life of the transformer.
Overload that results in a reduction of life expectancy of the transformer.
If the transformer is experiencing increased temperatures, the following load characteristics should be considered immediately:
Rigorous motor starting loads or other impact
type loading for which a specic transformer for
that application is required.
Over-excitation of unit due to excess supply line voltage or current.
Maintenance would include internal cleaning, tightening of links and bolted connections, servicing and inspection of auxiliary devices.
Air ducts should be free of any accumulation of dust and debris and any bolted connections of terminals must be in good condition.
Vacuuming or blowing of compressed air from the top down is an accepted practice for removing dust from the ducts of a transformer coil. Low pressure, dry air should be used to avoid further contamination of the windings by foreign material.
The ground connection should also be checked to ensure a low impedance connection. The accumulation of ice, snow or any other object blocking the ventilation should be cleaned up immediately during the operation of the transformer.
On outdoor units where filters have been installed, being exposed to the outside atmosphere can cause the filters to get dirty quickly. A periodic check of the filters will help avoid filter clogging and thus transformer overheating. Also, never run the transformer without the filters properly in place.
Ambient temperatures above standard.
Overload beyond ANSI C57.96 guidelines.
Harmonic distortions of the supply line voltage
and currents.
If overheating is noted, any attempt to add supplemental fan cooling must be in accordance with factory installation guidelines. Incorrectly installed fans
can misdirect the airow and cause serious
deterioration of the insulation life in a transformer coil.
Dry-type transformers can be shut down and stored for extended periods of time without any deterioration. Care must be exercised to clean and dry units prior to energization, as previously outlined.
MAINTENANCE
Under normal operating conditions and environments, dry-type transformers do not require maintenance. However, periodic care and inspection is a good practice particularly dependent on the environmental conditions in which the unit is installed.
Peripheral inspection and external dust removal may be carried out while the transformer is in operation. However, access covers must not be opened under energized conditions.
Internal maintenance must be performed with a transformer de-energized, isolated and with the terminals grounded.
DRY-OUT OF TRANSFORMERS
In the event that transformers have been exposed to moisture such as condensation or rain, it is advisable to dry-out any unit prior to energization.
Drying may be accomplished by using any hot or warmed air, radiant heat or internal heat that is directed through the windings. Heated air should be allowed to rise up through the windings for a minimum of twenty four (24) hours after the evidence of condensation is no longer visible.
Transformers that have been exposed to ood
conditions, direct rain or sprinklers, may not be able to be dried out appropriately. Contact the transformer manufacturer for appropriate action.
ACCESSORIES
Dry-type distribution transformers are available with a number of accessories to facilitate installation. Consult your local dealer or distributor for the purchase of any of the items which may be carried in inventory.
1) Wall Mounting Brackets
Encapsulated transformers have integral wall mounting capabilities for units up to 285 lbs. Units over
285 lbs. must be oor mounted only.
Ventilated dry-type transformers are normally
designed to be oor mounted only. However, some
ventilated units up to 51kVA are supplied in enclosures that have integral wall mounting capabilities. These units can be conveniently mounted on walls, beams or
- 6 -
poles.
Conventional open ventilated dry-type transformers have a bottom screen for air convection. When transformers are mounted above the ground surface a catcher plate should be installed under each transformer as a safety precaution against any hot particles that may fall through the screen in the event of a faulted condition. Refer to Appendix B (page 8).
2) Sound Isolation Pads
APPENDIX A
AMPACITY RATINGS FOR CONNECTIONS
A. For a single phase transformer
Line Amperes = volt-amperes line volts
B. For a three phase transformer
All dry-type transformers have rubberized sound absorbing pads mounted internally between the core and coil assembly and the enclosure.
For maximum absorption of vibration and emission of sound, additional sound isolation pads are recommended for installation between the transformer and the mounting surface.
These molded neoprene and steel plate assemblies virtually eliminate vibration noise between the transformer and the mounting surface.
Consult the manufacture’s catalog for the part number of the correct isolation pad required
3) Connectors
Connectors for the installation of dry-type transformers are readily available. These connectors are suitable for either copper or aluminum cable.
Connectors should be sized and installed in accordance with your local electrical code requirements using the best practices to ensure safe and reliable operation. Cable surfaces should be cleaned and electrical compound should be used for all joints.
Selecting Connectors
a) Determine the primary current for the required
transformer from the Appendix A.
b) Similarly, determine the secondary current rating
for the transformer from Appendix A.
c) For 120/240 voltage connections the current
should be based on 240 volts.
d) For 240/480 volt connections, the current should
be based on 480 volts.
Line Amperes = volt amperes 3 X line Volts
Full Load Current Table
Single Phase Transformer
Current in Amperes kVA Rating 120V 240V 416V 480V 600V
3 25.0 12.5 7.21 6.25 5.00 5 41.6 20.8 12.0 10.4 8.33
7.5 62.5 31.2 18.0 15.6 12.5 10 83.3 41.6 24.0 20.8 16.6 15 125 62.5 36.0 31.2 25.0 25 208 104 60.0 52.0 41.6
37.5 312 156 90.1 78.1 62.5 50 416 208 120 104 83.3 75 625 312 180 156 125 100 833 416 240 208 166 150 1250 625 360 312 250 167 1391 695 401 347 278 250 2083 1041 600 520 416 333 2775 1387 800 693 555
Full Load Current Table
Three Phase Transformer
Current in Amperes kVA Rating 208V 240V 380V 416V 480V 600V
2 5.55 4.81 3.03 2.77 2.40 1.92 3 8.32 7.21 4.55 4.16 3.60 2.88 6 16.6 14.4 9.11 8.32 7.21 5.77 9 24.9 21.6 13.6 12.4 10.8 8.66 15 41.6 36.0 22.7 20.8 18.0 14.4 30 83.2 72.1 45.5 41.6 36.0 28.8 45 124 108 68.3 62.4 54.1 43.3 75 208 180 113 104 90.2 72.1
112.5 312 270 170 156 135 108 150 416 360 227 208 180 144 225 624 541 341 312 270 216 300 832 721 455 416 360 288 450 1249 1082 683 624 541 433 500 1387 1202 759 693 601 481 600 1665 1443 911 832 721 577 750 2081 1804 1139 1040 902 721
- 7 -
APPENDIX B
LOCATION OF WALL MOUNTING BRACKETS AND CATCHER PLATES
FOR NH3 SERIES TYPE 3R ENCLOSURES
Optional Wall Mounting Bracket
Catcher Plate Where Local Code Requires
Catcher Plate Where Local Code Requires
APPENDIX B
LOCATION OF WALL MOUNTING BRACKETS AND CATCHER PLATES
FOR NH5 & NH6 SERIES TYPE 3R ENCLOSURES
Wall Mounting Hole Locations
Optional Ceiling Mounting Bracket
Catcher Plate Where Local Code Requires
Floor/Ceiling Mounting Hole Locations
- 8 -
FIGURE 1
Typical Type 3R, NH Series Ventilated Enclosure Assembly for Three Phase and Single Phase Transformers.
Notes:
Handling - units are designed to be raised by a fork lift from underneath the pallet. Final positioning of the unit 1.
with the pallet removed can be via a fork lift under the transformer with the forks between the channels.
Shipping - units are shipped on pallets which are to be removed at installation. 2.
Installation - This transformer can be installed indoor or outdoor providing a degree of protection against falling 3.
rain, sleet and external ice formation.
All general purpose/drive isolation transformers should be located away from walls or any other obstructions at 4.
least 6 inches when oor mounted and 4 inches when wall mounted.
DO NOT block bottom ventilation area.5.
Removable front access panel
Position fork lift under pallet
Cable entrance knockouts (2 per side)
For nal positioning
with pallet removed, fork lift points are under the transformer
- 9 -
FIGURE 2
Typical Type 3R, NJ Series Ventilated Enclosure Assembly for Three Phase or Single Phase Transformers.
Notes:
Handling - units are designed to be raised by a fork lift from underneath the pallet. Final positioning of the unit 1. with the pallet removed can be via a fork lift under the transformer with the forks between the channels. (Note:
for transformers weighing greater than 2350 lbs should be lifted by removing the top panel and accessing the lifting provisions on top of the top of the core and coil.)
Shipping - units are shipped on pallets which are to be removed at installation. 2.
Installation - This transformer can be installed indoor or outdoor providing a degree of protection against falling 3. rain, sleet and external ice formation.
All general purpose/drive isolation transformers should be located away from walls or any other obstructions at 4.
least 6 inches when oor mounted and 4 inches when wall mounted. (Note: These enclosures are not intended
to be wall mounted. They may be mounted on a customer supplied platform.)
DO NOT block bottom ventilation area.5.
Removable front access panel
Position fork lift under pallet
Recommended cable entry location (both sides). Refer to outline drawing for exact dimensions.
For nal positioning with pallet
removed, fork lift points are under the transformer. Forks must be inserted all the way through the depth.
- 10 -
FIGURE 3
Typical Type 4 & 12, NH Series Non-Ventilated Enclosure Assembly for Three Phase or Single Phase Transformers.
Notes:
Handling - units are designed to be raised by a fork lift from underneath the pallet. Final positioning of the unit 1. with the pallet removed can be via a fork lift under the transformer with the forks between the channels.
Shipping - units are shipped on pallets which are to be removed at installation. 2.
Installation - This is a non-ventilated indoor or outdoor enclosure designed primarily to provide a degree of 3. protection against falling dirt, rain, sleet, snow, windblown dust, splashing water, hose-directed water and that will be undamaged by the external formation of ice on the enclosure. It is suitable in areas where exposure to large amounts water from any direction is possible. (Note: not submersible)
All general purpose/drive isolation transformers should be located away from walls or any other obstructions at 4.
least 6 inches when oor mounted and 4 inches when wall mounted.
Lifting Hook
Removable front access panel
Position fork lift under pallet
Recommended cable entry location (either side). Refer to outline drawing for exact dimensions.
- 11 -
Loading...
+ 25 hidden pages