Typical Performance Data
General Purpose - Single Phase
HPS Sentinel G3
208V to 600V Primary, 120/240V Secondary, 60 Hz, 150oC
No
kVA
37.5 110 1280 6.0% 0.94% 1.78% 2.76% 5.10% 97.70% 98.20% 98.27% 98.13% 97.88% 97.69% 97.16%
100 240 2650 6.0% 0.75% 1.72% 2.23% 4.94% 98.12% 98.54% 98.60% 98.50% 98.30% 98.15% 97.73%
150 380 3300 4.0% 0.63% 1.20% 1.82% 3.43% 98.08% 98.57% 98.68% 98.63% 98.49% 98.36% 98.02%
167 410 3600 4.0% 0.62% 1.20% 1.81% 3.44% 98.14% 98.60% 98.70% 98.65% 98.51% 98.39% 98.04%
Performance data is subject to change without notice.
Load
Losses
(W)
15 60 550 5.2% 0.99% 1.56% 2.89% 4.47% 97.00% 97.75% 97.92% 97.84% 97.61% 97.42% 96.88%
25 80 910 5.5% 0.99% 1.65% 2.89% 4.73% 97.51% 98.06% 98.14% 98.00% 97.74% 97.53% 96.97%
50 130 1650 6.0% 0.91% 1.77% 2.68% 5.08% 97.93% 98.35% 98.39% 98.24% 97.98% 97.79% 97.27%
75 190 2150 6.0% 0.80% 1.74% 2.38% 4.99% 98.02% 98.45% 98.52% 98.40% 98.19% 98.02% 97.57%
Full
Load
Losses*
(W)
Impedance
at 35% load at 100% load
pf=1 pf=0.8 pf=1 pf=0.8 15% 25% 35% 50% 65% 75% 100%
Regulation
% Efficiency at different % of rated load
HPS Sentinel G3
208V to 600V Primary, 120/240V Secondary, 60 Hz, 150oC
No
kVA
37.5 90 1500 6.0% 1.09% 1.80% 3.17% 5.15% 97.98% 98.30% 98.27% 98.03% 97.69% 97.45% 96.80%
100 212 2990 6.0% 0.83% 1.75% 2.47% 5.03% 98.27% 98.59% 98.60% 98.43% 98.19% 98.00% 97.51%
150 332 3800 6.0% 0.73% 1.72% 2.17% 4.93% 98.25% 98.63% 98.68% 98.57% 98.37% 98.22% 97.80%
167 352 4250 6.4% 0.74% 1.82% 2.22% 5.23% 98.32% 98.66% 98.70% 98.57% 98.37% 98.21% 97.79%
Performance data is subject to change without notice.
Load
Losses
(W)
15 55 650 6.0% 1.17% 1.80% 3.39% 5.14% 97.14% 97.76% 97.84% 97.67% 97.36% 97.12% 96.46%
25 88 870 6.0% 0.95% 1.78% 2.79% 5.09% 97.33% 97.97% 98.10% 98.00% 97.77% 97.59% 97.07%
50 130 1650 6.0% 0.91% 1.77% 2.67% 5.07% 97.93% 98.35% 98.39% 98.24% 97.99% 97.80% 97.27%
75 170 2300 6.0% 0.85% 1.75% 2.51% 5.03% 98.17% 98.52% 98.54% 98.39% 98.14% 97.96% 97.46%
Full
Load
Losses*
(W)
Impedance
at 35% load at 100% load
pf=1 pf=0.8 pf=1 pf=0.8 15% 25% 35% 50% 65% 75% 100%
Regulation
% Efficiency at different % of rated load
26
Data subject to change without notice.
Typical Performance Data
General Purpose - Three Phase
HPS Sentinel G3
480V Delta - 208 Wye/120V, 60Hz, 150oC
No
kVA
112.5 275 1850 3.5% 0.58% 1.04% 1.68% 2.97% 98.16% 98.63% 98.74% 98.70% 98.57% 98.46% 98.14%
150 335 2330 3.8% 0.55% 1.12% 1.61% 3.21% 98.31% 98.73% 98.83% 98.79% 98.66% 98.56% 98.25%
225 440 3300 3.8% 0.52% 1.11% 1.52% 3.18% 98.50% 98.86% 98.94% 98.89% 98.76% 98.66% 98.36%
300 560 3930 4.0% 0.47% 1.14% 1.38% 3.26% 98.58% 98.94% 99.02% 98.98% 98.87% 98.78% 98.53%
500 808 5860 4.5% 0.42% 1.23% 1.26% 3.53% 98.76% 99.07% 99.14% 99.10% 99.00% 98.92% 98.68%
750 980 8710 5.2% 0.42% 1.37% 1.28% 3.96% 98.97% 99.19% 99.23% 99.16% 99.05% 98.97% 98.72%
1000 1250 10400 5.2% 0.38% 1.36% 1.16% 3.91% 99.02% 99.25% 99.28% 99.24% 99.14% 99.07% 98.86%
Performance data is subject to change without notice.
Load
Losses
(W)
15 64 400 3.9% 0.93% 1.10% 2.68% 3.15% 96.86% 97.68% 97.89% 97.86% 97.67% 97.50% 97.00%
30 96 760 4.0% 0.89% 1.17% 2.57% 3.35% 97.56% 98.13% 98.23% 98.13% 97.90% 97.72% 97.22%
45 135 990 3.7% 0.77% 1.12% 2.22% 3.20% 97.72% 98.28% 98.40% 98.33% 98.15% 98.00% 97.57%
75 194 1470 3.5% 0.69% 1.05% 1.98% 3.02% 98.02% 98.50% 98.60% 98.53% 98.36% 98.22% 97.84%
Full
Load
Losses*
(W)
Impedance
Regulation
at 35% load at 100% load
pf=1 pf=0.8 pf=1 pf=0.8 15% 25% 35% 50% 65% 75% 100%
% Efficiency at different % of rated load
HPS Sentinel G3
480V Delta - 208 Wye/120V, 60Hz, 150oC
No
kVA
112.5 226 2260 5.0% 0.71% 1.46% 2.10% 4.18% 98.38% 98.71% 98.74% 98.61% 98.41% 98.26% 97.84%
150 315 2500 5.0% 0.60% 1.42% 1.77% 4.07% 98.38% 98.76% 98.83% 98.76% 98.61% 98.49% 98.16%
225 405 3580 5.4% 0.57% 1.51% 1.72% 4.33% 98.58% 98.89% 98.94% 98.86% 98.70% 98.59% 98.26%
300 540 4040 4.8% 0.48% 1.32% 1.45% 3.79% 98.62% 98.95% 99.02% 98.98% 98.86% 98.77% 98.50%
500 840 5590 5.2% 0.41% 1.37% 1.24% 3.95% 98.73% 99.06% 99.14% 99.11% 99.02% 98.95% 98.73%
750 1020 8370 5.8% 0.41% 1.50% 1.27% 4.35% 98.94% 99.18% 99.23% 99.18% 99.07% 98.99% 98.76%
1000 1180 11180 5.8% 0.41% 1.50% 1.28% 4.35% 99.05% 99.25% 99.28% 99.21% 99.10% 99.01% 98.78%
Performance data is subject to change without notice.
Load
Losses
(W)
15 62 420 4.0% 0.98% 1.12% 2.81% 3.21% 96.92% 97.70% 97.89% 97.82% 97.61% 97.42% 96.89%
30 86 840 4.1% 0.98% 1.19% 2.82% 3.40% 97.72% 98.19% 98.23% 98.06% 97.79% 97.58% 97.00%
45 120 1110 4.5% 0.87% 1.36% 2.51% 3.89% 97.90% 98.35% 98.40% 98.27% 98.03% 97.84% 97.34%
75 190 1490 5.0% 0.71% 1.46% 2.08% 4.18% 98.05% 98.51% 98.60% 98.52% 98.35% 98.20% 97.81%
Full
Load
Losses*
(W)
Impedance
Regulation
at 35% load at 100% load
pf=1 pf=0.8 pf=1 pf=0.8 15% 25% 35% 50% 65% 75% 100%
% Efficiency at different % of rated load
Data subject to change without notice.
27